PEM PDA Software

14
Effective Date 3/2007 For more information visit: www.itvss.com Eaton ® Innovative Technology ® PEM Handheld Software Installation and Operation Instruction Manual: IM01005004E Rev. 2 – March 2007

Transcript of PEM PDA Software

Page 1: PEM PDA Software

Effective Date 3/2007 For more information visit: www.itvss.com

Eaton® Innovative Technology® PEM Handheld Software Installation and Operation

Instruction Manual:IM01005004ERev. 2 – March 2007

Page 2: PEM PDA Software

IM01005004E PEM Handheld Software

Page A Rev. 2 - 3/2007

TABLE OF CONTENTS

Section Page

1 Introduction........................................................................................................................................... 1 2 Installation............................................................................................................................................. 1 3 Communicating with the PEM............................................................................................................. 3

3.1 IrDA .................................................................................................................................................. 3 3.2 TCP/IP.............................................................................................................................................. 4

4 Modes .................................................................................................................................................... 5 4.1 View mode ....................................................................................................................................... 5

4.1.1 Voltages ................................................................................................................................. 5 4.1.2 History Log ............................................................................................................................. 6 4.1.3 Event Counts–Surge, –2, –3 .................................................................................................. 8

4.2 Configuration Mode.......................................................................................................................... 9 4.2.1 IrDA or TCP/IP Page .............................................................................................................. 9 4.2.2 Device Config–1 ..................................................................................................................... 9

4.2.2.1 Device Name............................................................................................................. 9 4.2.2.2 Modbus Address ....................................................................................................... 9 4.2.2.3 Modbus Baudrate .................................................................................................... 10 4.2.2.4 TCP/IP Address....................................................................................................... 10 4.2.2.5 TCP/IP IP Mask....................................................................................................... 10 4.2.2.6 TCP/IP Gateway...................................................................................................... 10

4.2.3 Device Config–2 ................................................................................................................... 10 4.2.3.1 Frequency ............................................................................................................... 10 4.2.3.2 Voltage .................................................................................................................... 11 4.2.3.3 Reset Parameters ................................................................................................... 11 4.2.3.4 PDA Date/Time ....................................................................................................... 11 4.2.3.5 PEM Date/Time....................................................................................................... 11

Notice: Product improvements and enhancements are continuous; therefore the specifications and information contained in this document may change without notice.

Eaton Corporation shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material.

No part of this document may be reproduced for publication, or translated to another language without the prior written consent of Eaton Corporation.

Innovative Technology® is a registered trademark of Eaton Corporation. All other trademarks, trade names, service marks and logos referenced herein belong to their respective owner

Page 3: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 1

1 INTRODUCTION

The function of Eaton Corporation’s PEM Handheld Software is to monitor and control a TVSS Power Event Monitor (PEM) using a Personal Digital Assistant (PDA) running the Microsoft® Windows Mobile operating system along with Microsoft .NET Compact Framework 2.0 or greater. Functional testing of this software was completed using DELL® and HP® PDAs running Microsoft Windows Mobile 5.

The PEM Handheld Software gives a user the following abilities: • Voltage Monitoring • Event Count Display • Event Retrieval • PEM Configuration

It is assumed that users are familiar with the operation their particular PDAs, including: general setup and configuration; downloading and copying files from a personal computer to the PDA using ActiveSync, or similar program; and installing software on the PDA in the form of *.CAB files.

Use this manual in conjunction with PEM Instruction Manual IM01005003E.

2 INSTALLATION

1. Download the latest version of the PEM Handheld Software from Eaton Corporation’s Website http://www.itvss.com onto your personal computer. Use the search term “PEM Handheld Software” to locate the file on the Website. Note that the downloaded software will be in the form of a *.CAB file.

2. Using the file transfer software supplied with the PDA (e.g., Microsoft Active Sync), copy the *.CAB file from your personal computer to File Explorer / My Documents on your PDA.

3. Before installing the PEM Handheld Software, check that Microsoft .NET Compact Framework 2.0 or greater is installed on the PDA. If the PEM Handheld Software is installed with an older version of .NET Compact Framework, then the following error message will appear:

This application (Eaton PEM PDA Interface.exe) requires a newer version of the Microsoft® .NET Compact Framework than the version installed on this device.

You can check if .NET Compact Framework is installed on your PDA by tapping Start > Settings > System > Remove Programs to display a list of installed programs. If installed, Microsoft .NET CF 2.0 will appear in the list.

The latest version of .NET Compact Framework can be downloaded from the following link: http://msdn2.microsoft.com/en-us/netframework/aa497280.aspx

Important! Be sure to download the compact version and not the desktop version.

Page 4: PEM PDA Software

IM01005004E PEM Handheld Software

Page 2 Rev. 2 - 3/2007

4. Install the PEM Handheld Software by first tapping Start > File Explorer to display the contents of My Documents on the PDA, and then tapping the *.CAB file that was transferred to the PDA from the PC (there is no need to manually extract the files).

5. During the installation process the following pages may appear:

• If a previous installation was found, a warning is given that the old software will be removed. Tap OK to continue.

• If the PDA contains additional memory cards, the installation may prompt for the install location. It is recommended to install the software to the Device and not to a memory card.

• When installation begins, the program’s installation progress screen will appear followed by a message that the *.CAB file was successfully installed on you device. If the message that the program is from an unknown publisher should appear, simply Tap Yes to continue with the installation.

• Once installed, an Eaton PEM PDA Interface icon will appear on the PDA’s programs page. After installation is complete, we recommend restarting the PDA.

Page 5: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 3

3 COMMUNICATING WITH THE PEM

Tap Start > Programs > Eaton PEM PDA Interface icon on the PDA’s Programs page to start the software. After the software starts, tabs for IrDA and TCP/IP are displayed. Choose the desired communications method by tapping the desired tab and perform the procedures in either Section 3.1 IrDA or 3.2 TCP/IP.

3.1 IrDA

Perform the following to connect to the PEM via the PDA’s IrDA port:

1. First, ensure that the PDA is equipped with an IrDA port. If the IrDA port is on the bottom of the PDA, use the file rotate page menu option to rotate the page 180° to allow for easier access.

2. If necessary, tap the IrDA tab to display the IrDA Connect page.

3. Aim the PDA’s IrDA port at the IrDA port on the front cover of the PEM. Hold the PDA no more than 3 feet away from the PEM, at a viewing angle of no more than 60°.

4. If you know the PDA’s Modbus address (default is 3), use the Up/Down arrows to set the Modbus address to the desired value and then tap Set. If you do not know the address, simply set the Modbus address to 1. The PDA will scan all addresses until it finds the PEM.

5. Tap the Discover Devices button. When the PEM is found, the PDA will display the device name and address (Default Device Name is ??????????, and the address is 3). Note that the Device Name and Address can be changed per Section 4.2.2 Device Config–1.

6. Tap the Connect button.

7. When a connection is established, the PDA will do the following:

• Change Connect to Disconnect. • Remove the TCP/IP communications tab. • Switch to the program’s View Mode and display the Voltages page.

8. Once connected, refer to Section 4 Modes.

Page 6: PEM PDA Software

IM01005004E PEM Handheld Software

Page 4 Rev. 2 - 3/2007

3.2 TCP/IP

Important! Please Read. Before configuring the PDA to wirelessly communicate with the PEM as described below, the PEM’s IP Address, Mask, and Gateway must be set up to meet the configuration requirements of your wireless network by using either the optional Local Display Module, or using a personal computer connected to the PEM’s Ethernet port and running Eaton Corporation’s PEM PC Software. Refer to Instruction Manuals IM01005003E and IM01005006E for details.

Wireless network configuration is beyond the scope of this manual. Your company’s I.T. Department should perform the necessary integration of the PEM into their wireless network, or contact Eaton Corporation’s Power Quality Technical Support Center for assistance at 1-800-809-2772.

If this is the first time the PDA is being used to communicate with the PEM via TCP/IP wireless, or to make a new connection, perform the following steps to create a new Device Name and configure the PDA to match the PEM’s IP Address and Modbus Address. If the PDA has already been configured, then skip to the next procedure.

1. Tap the TCP/IP tab to display the TCP/IP Connect page.

2. Tap the Create Entry button to display the Create New Entry page.

3. Enter a Device Name that will appear on the TCP/IP Connect page using the PDA’s keypad function.

4. Enter the PEM’s wireless IP Address using the PDA’s keypad function.

5. Enter the PEM’s Modbus address (Default is 3) by tapping the Up/Down arrows.

6. Tap the Save Entry button to save the information and return to the TCP/IP Connect page.

7. Connect to the PEM as described below.

Connect to the PEM using an existing Device Name as follows:

1. On the TCP/IP Connect page, display the list of connections by tapping the Drop-Down arrow.

2. Tap the desired device name and then tap the Connect button

3. When a connection is established, the PDA will do the following: • Change Connect to Disconnect. • Remove the IrDA communications tab. • Switch to the program’s View Mode and display the

Voltages page.

Once connected, refer to Section 4 Modes.

Page 7: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 5

4 MODES

The PEM Handheld Software supports two modes, View and Config under the Mode menu. After a connection has been made, the software automatically switches in the View mode. To change modes, first tap the Mode menu item and then tap either View or Config.

4.1 View mode

The View mode consists of five tabbed pages that allow the user to monitor voltages, retrieve and save history log data, and view the number and type of events that have occurred.

4.1.1 Voltages

The Voltages page displays the PEM’s current line frequency along with its minimum and maximum values; line-to-line; line-to-line average; line-to-neutral; line-to-neutral average; and neutral-to-ground voltages. The voltages displayed, however, depend on the type of system being monitored—see table above. The example Voltages page above shows the measured voltages of a PEM Model 3Y101 as it monitors a 120 volt, Wye system.

Voltages Being Measured (Checkmark indicates voltage is actively being

measured; otherwise, voltage reads 0 or is not displayed)

PEM Model 1P101 1P201 1S101 3Y101 3Y201 3Y300 NN201 NN400 NN501

System

Wiring 4 4 4 4 4 4 3 3 3

System

Voltage

100 –

127 L-N

200 –

240 L-N

100 –

127 L-N

100 –

127 L-N

220 –

277 L-N

305 –

347 L-N

200 –

240 L-L

380 –

480 L-L

525 –

600 L-L

VAB

VBC

VCA

VLL – Avg

VAN

VBN

VCN

VLN – Avg

VNG

Page 8: PEM PDA Software

IM01005004E PEM Handheld Software

Page 6 Rev. 2 - 3/2007

4.1.2 History Log

The History Log page allows the user to retrieve, view, and save History Log events that have been recorded by the PEM.

When first displayed, this page shows the total number of events that have been recorded. In the example to the left, the Total Events box shows that 3 events have occurred numbered 0 thru 2.

To retrieve the History Log events, first enter the range of events to be retrieved by entering those values in the Start Event and End Event boxes (up to 5,000 events can be stored in the PEM); and then tapping the Retrieve button. The PDA will download the selected range of History Log events and display the data in the Event Data box.

To save the downloaded event data to a file, tap the File > Save History Log menu item to display the Save As page. The event data will be saved in an ASCII comma separated variable (CSV) type of file that can later be downloaded to a personal computer and viewed in most spreadsheet programs where the data can be viewed for analysis.

The Save As page allows the user to specify the following information:

• Name: Type in the name of the file to be saved (Default is history).

• Folder: Select the file location (Default is My Documents).

• Type: Select the File Type (Currently only CSV is supported).

• Location: – Select the Memory location (Default is Main memory).

Page 9: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 7

After the history log has been saved, the “Clear Display and PEM History Log?” dialog box will appear. Tap No to retain the history log in the PEM’s memory, or tap Yes to clear both the display and the PEM’s History Log of all events.

Note that by not clearing the history log, multiple retrievals can be performed. This allows the user to retrieve several ranges of History Log data for storage under different file names (e.g., Events 0000-0100, Events 0101-0200, Events 0201-0300, etc.).

Tip: To clear the Event Data page, first tap Mode > Config, and then return to the History Log page by tapping Mode > View > History Log.

The following spreadsheet shows a typical history log file as viewed in Microsoft Excel:

Page 10: PEM PDA Software

IM01005004E PEM Handheld Software

Page 8 Rev. 2 - 3/2007

4.1.3 Event Counts–Surge, –2, –3

There are three Event Counts pages that display the number and type of events that have occurred for each phase. The PDA automatically updates these pages once every 2 seconds. To immediately update the page, tap its Update button.

• Total Events: Total number of all events for each phase • Surge Events: Total number of surge events for each phase • 200% / 300% / 400% Surge: Number of surges that have occurred at each level for each phase • 10% / 20% Swell: Number of swells that have occurred at each level for each phase • 10% / 20% / 30% Sag: Number of sags that have occurred at each level for each phase • Sag/Swell Events: Total number of all sag and swell events for each phase.

Page 11: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 9

4.2 Configuration Mode

The Config mode consists of three tabbed pages that allow the user to disconnect from the PEM, and configure the PEM’s parameters.

4.2.1 IrDA or TCP/IP Page

When the Config mode is first entered, either the IrDA or TCP/IP page will appear. These pages show the name of the PEM currently being monitored, and allows the user to disconnect from the current PEM and connect to another unit.

Tap the Disconnect button to disconnect from the PEM. To connect to another PEM or create a new entry, refer to either Section 3.1 IrDA or 3.2 TCP/IP.

4.2.2 Device Config–1

4.2.2.1 Device Name

The Device Name is stored in the PEM and is the name that appears on the IrDA Connect page (refer to Section 3.1 IrDA). To change the device name, highlight the existing name and type in a new name using the PDA’s keypad function that is 20 characters or less in length, and then tap Set to transmit the new name to the PEM.

4.2.2.2 Modbus Address

To change the Modbus Address, first tap the Up/Down arrows until the desired address is displayed (1–255 decimal), and then tap Set to transmit the new address to the PEM.

Page 12: PEM PDA Software

IM01005004E PEM Handheld Software

Page 10 Rev. 2 - 3/2007

4.2.2.3 Modbus Baudrate

To change the Modbus Baudrate, first tap the Drop-Down arrow to display a list of baudrates (9600 or 19200); tap the desired baudrate; and then tap Set to transmit the new baudrate to the PEM.

4.2.2.4 TCP/IP Address

To change the IP Address, first highlight the existing IP Address value; type in a new address using the PDA’s keypad function; and then tap Set to transmit the new address to the PEM. Wait at least 10 seconds for the new IP Address to be processed before making another change.

4.2.2.5 TCP/IP IP Mask

To change the IP Mask, first highlight the existing IP Mask value; type in a new address using the PDA’s keypad function; and then tap Set to transmit the new IP Mask value to the PEM. Wait at least 10 seconds for the new IP Mask to be processed before making another change.

4.2.2.6 TCP/IP Gateway

To change the Gateway address, first highlight the existing Gateway address value; type in a new address using the PDA’s keypad function; and then tap Set to transmit the new address to the PEM. Wait at least 10 seconds for the new Gateway address to be processed before making another change.

4.2.3 Device Config–2

4.2.3.1 Frequency

The PEM’s system frequency no longer needs to be manually configured. If a Frequency value is displayed on the Device Config-2 page, then its value will automatically be the correct system frequency. Note that if a new frequency value is selected and the Set button is tapped, the new frequency value is accepted by the PEM; however, 30 seconds later the frequency is recalculated and changed back its actual value. Also note that the displayed frequency value will not update unless the user leaves and then re-enters the Device Config-2 page.

Page 13: PEM PDA Software

PEM Handheld Software IM01005004E

Rev. 2 - 3/2007 Page 11

4.2.3.2 Voltage

To change the system voltage, either highlight the existing Voltage value and type in a new value using the PDA’s keyboard function, or click the Up/Down arrows until the desired voltage value is displayed; and then tap Set to send the new Voltage value to the PEM. Note that the Voltage value must be within the range of the PEM’s model number as shown in the table in Section 4.1.1 Voltages.

4.2.3.3 Reset Parameters

The user can reset the following PEM parameters to zero, to their current values, or to their factory default values.

• History Log: Erase all events in the History Log. • Event Counts: Reset all Event Counts to zero. • Surge Only: Resets the Surge Event counts to zero. • Sag/Swell Only: Resets the Sag/Swell Event counts to zero. • Min/Max Freq: Resets the System Frequency Minimum and Maximum

values to the current frequency • Calibration: Restores the PEM calibration values to factory defaults.

(The calibration values can only be changed using the optional Local Display Module.)

To reset any of the above parameters, first tap the Drop-Down arrow to display a list of reset parameters; tap the desired parameter; and then tap Reset to send the command to reset the selected parameter to the PEM.

4.2.3.4 PDA Date/Time

Displays the PDA’s current Date (MM/DD/YY) and Time (HR/MIN/SEC AM/PM).

4.2.3.5 PEM Date/Time

Displays the PEM’s current Date (MM/DD/YY) and Time HR/MIN/SEC AM/PM). To synchronize the PEM’s date and time to that of the PDA, tap the Set to PDA Time button.

Page 14: PEM PDA Software

Eaton Corporation

1000 Cherrington Parkway Moon Township, PA 15108-4312 USA

www.itvss.com

© 2006–2007 Eaton Corporation For additional information please call: All Rights Reserved Power Quality Technical Support Center Publication No. IM01005004E 1-800-809-2772 Rev. 2 – March 2007