AIR CONDITIONERS
TECHNICAL & SERVICE MANUALModels PEFY-P20VMA(L)-E,
PEFY-P25VMA(L)-E,PEFY-P32VMA(L)-E,PEFY-P40VMA(L)-E,PEFY-P50VMA(L)-E,PEFY-P63VMA(L)-E
PEFY-P71VMA(L)-EPEFY-P80VMA(L)-EPEFY-P100VMA(L)-EPEFY-P125VMA(L)-EPEFY-P140VMA(L)-E
2012
http://planetaklimata.com.ua/http://planetaklimata.com.ua/
-
ii
HWE0812B GB
Safety PrecautionsRead before installation and performing electrical work
Symbol explanations
Thoroughly read the following safety precautions prior to installation.Observe these safety precautions for your safety.This equipment may have adverse effects on the equipment on the same power supply system.Contact the local power authority before connecting to the system.
WARNINGThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or death.
CAUTIONThis symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam-age to the unit.
Indicates an action that must be avoided.
Indicates important instructions.
Indicates a parts that requires grounding.
Indicates that caution must be taken with rotating parts. (This symbol is on the main unit label.)
Indicates that the parts that are marked with this symbol pose a risk of electric shock. (This symbol is on the main unit label.)
WARNINGCarefully read the labels affixed to the main unit.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak-age, electric shock, or fire.
Properly install the unit on a surface that can withstand its weight.
Unit installed on an unstable surface may fall and cause in-jury.
Only use specified cables. Securely connect each cable so that the terminals do not carry the weight of the cable.
Improperly connected cables may produce heat and start a fire.
Take appropriate safety measures against wind gusts and earthquakes to prevent the unit from toppling over.
Improper installation may cause the unit to topple over and cause injury or damage to the unit.
Only use accessories (i.e., air cleaners, humidifiers, electric heaters) recommended by Mitsubishi Electric.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, or fire.
Do not touch the heat exchanger fins with bare hands.
The fins are sharp and pose a risk of cuts.
In the event of a refrigerant leak, thoroughly ventilate the room.
If gaseous refrigerant leaks out and comes in contact with an open flame, toxic gases will be generated.
Properly install the unit according to the instructions in the Installation Manual.
Improper installation may result in water leakage, electric shock, or fire.
Have all electrical work performed by an authorized electri-cian according to the local regulations and the instructions in this manual. Use a dedicated circuit.
Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.
0000001526.book i ページ 2012年9月13日 木曜日 午後7時14分
http://planetaklimata.com.ua/katalog-proizvoditeli/Mitsubishi-Electric/
-
iiHWE0812B GB
Precautions for handling units for use with R410A
WARNING
Keep electrical parts away from water.
Wet electrical parts pose a risk of electric shock, smoke, or fire.
Securely attach the control box cover.
If the cover is not installed properly, dust or water may infil-trate and pose a risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit when installing or relocating the unit.
Infiltration of any other types of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small space, take appropriate precautions to prevent leaked refrigerant from reaching the limiting concentration.
Leaked refrigerant gas will displace oxygen and may cause oxygen starvation. Consult your dealer before installing the unit.
Consult your dealer or a qualified technician when moving or reinstalling the unit.
Improper installation may result in water leakage, electric shock, or fire.
After completing the service work, check for a refrigerant leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, toxic gases will be gener-ated.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features for these devices, or the use of accessories other than the ones that are recom-mended by Mitsubishi Electric may result in smoke, fire, or explosion.
Consult your dealer for proper disposal method.
Do not use a leak detection additive.
CAUTION
Do not use the existing refrigerant piping.
A large amount of chlorine that may be contained in the re-sidual refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.
Use refrigerant piping materials made of phosphorus deox-idized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and moisture.
Contaminants in the refrigerant piping may cause the refrig-erator oil to deteriorate.
Store the piping materials indoors, and keep both ends of the pipes sealed until immediately before brazing. (Keep el-bows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate or cause the compressor to malfunction.
Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re-frigerator oil to deteriorate.
Charge the system with refrigerant in the liquid phase.
If gaseous refrigerant is drawn out of the cylinder first, the composition of the remaining refrigerant in the cylinder will change and become unsuitable for use.
Only use R410A.
The use of other types of refrigerant that contain chloride may cause the refrigerator oil to deteriorate.
Use a vacuum pump with a check valve.
If a vacuum pump that is not equipped with a check valve is used, the vacuum pump oil may flow into the refrigerant cy-cle and cause the refrigerator oil to deteriorate.
Prepare tools for exclusive use with R 410A. Do not use the following tools if they have been used with the conventional refrigerant: gauge manifold, charging hose, gas leak detec-tor, check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.
If the refrigerant or the refrigerator oil that may be left on these tools are mixed in with R410A, it may cause the refrigerator oil in the new system to deteriorate. Infiltration of water may cause the refrigerator oil to deteriorate.Leak detectors for conventional refrigerants will not detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrigerant in the cylinder will change and become unsuitable for use.
Exercise special care when handling tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.
0000001526.book ii ページ 2012年9月13日 木曜日 午後7時14分
http://planetaklimata.com.ua/proizvoditeli/kondicionery-mitsubishi-electric/
-
CONTENTS
HWE0812B GB
I Features[1] Features.................................................................................................................................... 1
II Components and Functions[1] Components and Functions...................................................................................................... 2
III Specfications[1] Specifications............................................................................................................................ 4
1.Specfications .......................................................................................................................... 42.Electrical component specifications........................................................................................ 7
IV Outlines and Dimensions[1] Outlines and Dimensions.......................................................................................................... 8[2] Service Space......................................................................................................................... 10
V Wiring Diagram[1] Wiring Diagram ....................................................................................................................... 11
VI Refrigerant System Diagram[1] Refrigerant system diagram.................................................................................................... 13
VII Troubleshooting[1] Troubleshooting ...................................................................................................................... 14
1.Check methods..................................................................................................................... 142.DC fan motor (fan motor/indoor control board)..................................................................... 183.Address switch setting .......................................................................................................... 194.Voltage test points on the control board ............................................................................... 205.Dipswitch setting (Factory setting)........................................................................................ 21
VIII Disassembly Procedure[1] Disassembly Procedure.......................................................................................................... 24
1.Control box ........................................................................................................................... 242.Thermistor (Intake air) .......................................................................................................... 253.Drainpan ............................................................................................................................... 264.Thermistor (Gas pipe) (Liquid pipe) ...................................................................................... 275.Fan and fan motor ................................................................................................................ 286.Heat exchanger .................................................................................................................... 29
0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分
-
HWE0812B GB
0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分
-
[ I Features ]
- 1 -HWE0812B GB
I Features
[1] Features
Model Cooling capacity/Heating capacity
kW
PEFY-P20VMA(L)-E 2.2/2.5
PEFY-P25VMA(L)-E 2.8/3.2
PEFY-P32VMA(L)-E 3.6/4.0
PEFY-P40VMA(L)-E 4.5/5.0
PEFY-P50VMA(L)-E 5.6/6.3
PEFY-P63VMA(L)-E 7.1/8.0
PEFY-P71VMA(L)-E 8.0/9.0
PEFY-P80VMA(L)-E 9.0/10.0
PEFY-P100VMA(L)-E 11.2/12.5
PEFY-P125VMA(L)-E 14.0/16.0
PEFY-P140VMA(L)-E 16.0/18.0
0000001526.book 1 ページ 2012年9月13日 木曜日 午後7時14分
-
[ II Components and Functions ]
- 2 -HWE0812B GB
II Components and Functions
[1] Components and Functions1. Indoor (Main) Unit
2. Remote Controller[PAR-21MAA]Once the operation mode is selected, the unit will remain in the selected mode until changed.
(1) Remote Controller Buttons
Keep the remote controller out of direct sunlight to ensure accurate measurement of room temperature.The thermistor at the lower right-hand section of the remote controller must be free from obstructions to ensure accurate mea-surement of room temperature.
(1) In case of rear inlet (2) In case of bottom inlet
1 [Set Temperature] Button 7 [Vane Control] Button2 [Timer Menu] Button 8 [Ventilation] Button
[Monitor/Set] Button [Operation] Button3 [Mode] Button 9 [Check/Clear] Button
[Back] Button 10 [Test Run] Button4 [Timer On/Off] Button 11 [Filter] Button
[Set Day] Button [ ] Button5 [Louver] Button 12 [ON/OFF] Button
[Operation] Button 13 Position of built-in room thermistor6 [Fan Speed] Button 14 [Set Time] Button
Air inlet
Air outlet Air outlet
Air inlet
0000001526.book 2 ページ 2012年9月13日 木曜日 午後7時14分
-
[ II Components and Functions ]
- 3 -HWE0812B GB
(2) Remote Controller Display
A Current time/Timer time I Louver swing
B Centralized control indicator J Ventilation
C Timer OFF indicator K Filter sign
D Timer mode indicator L Sensor position
E Operation mode display: COOL, DRY, AUTO, FAN, HEAT
M Room temperature
F Function mode indicator N Vane setting
G Preset temperature O Fan speed
H Power indicator P Operation lamp
0000001526.book 3 ページ 2012年9月13日 木曜日 午後7時14分
-
[ III Specfications ]
- 4 -HWE0812B GB
III Specfications
[1] Specifications
1. Specfications
*1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).
Model PEFY-P20VMA(L)-E
PEFY-P25VMA(L)-E
PEFY-P32VMA(L)-E
PEFY-P40VMA(L)-E
Power supply Voltage V 1-phase 220-230-240
Frequency Hz 50/60
Cooling capacity *1 kW 2.2 2.8 3.6 4.5
Heating capacity *1 kW 2.5 3.2 4.0 5.0
Power consumption *2 Cooling kW 0.06(0.04) 0.07(0.05) 0.09(0.07)
Heating kW 0.04(0.04) 0.05(0.05) 0.07(0.07)
Current consumption *2 Cooling A 0.53(0.42) 0.55(0.44) 0.64(0.53)
Heating A 0.42(0.42) 0.44(0.44) 0.53(0.53)
External finish Galvanized
Dimensions Height mm 250
Width mm 700 900
Depth mm 732
Net weight *2 kg 23(22) 26(25)
Heat exchanger Cross fin(Aluminium fin and copper tube)
Fan Type Sirocco fan x 1
Airflow rate (Low-Mid-High)
m3/min 6.0-7.5-8.5 7.5-9.0-10.5 10.0-12.0-14.0
External static pressure
Pa 35/50/70/100/150
Motor Output kW 0.085
Air filter PP Honeycomb fabric (washable)
Refrigerant pipe dimensions
Gas (Brazed connection)
mm[in.] ø12.7[ø1/2]
Liquid (Brazed connection)
mm[in.] ø6.35[ø1/4]
Drain pipe dimensions mm[in.] O.D. 32[1-1/4]
Operating noise(Low-Mid-High) 35Pa dB (A) 23-24-25 23-25-28 23-26-29
50Pa 23-25-26 23-26-29 23-27-30
70Pa 23-26-28 24-27-30 24-28-31
100Pa 24-27-30 25-28-32 26-29-33
150Pa 25-30-34 28-32-36 29-33-37
35Pa 26-27-28 28-30-34
50Pa 26-28-29 28-30-34
70Pa 26-29-31 29-32-36
100Pa 27-30-33 29-33-37
150Pa 28-33-37 31-35-40 32-36-40
Measurement location 1
Aux. duct
* Measured in anechoic room.
2m 2m
1.5m
* Measured in anechoic room.
2m 1m
Aux. duct
1.5m
Measurement location 2
0000001526.book 4 ページ 2012年9月13日 木曜日 午後7時14分
-
[ III Specfications ]
- 5 -HWE0812B GB
*1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).
Model PEFY-P50VMA(L)-E
PEFY-P63VMA(L)-E
PEFY-P71VMA(L)-E
PEFY-P80VMA(L)-E
Power supply Voltage V 1-phase 220-230-240
Frequency Hz 50/60
Cooling capacity *1 kW 5.6 7.1 8.0 9.0
Heating capacity *1 kW 6.3 8.0 9.0 10.0
Power consumption *2 Cooling kW 0.11(0.09) 0.12(0.10) 0.14(0.12)
Heating kW 0.09(0.09) 0.10(0.10) 0.12(0.12)
Current consumption *2 Cooling A 0.74(0.63) 1.01(0.90) 1.15(1.04)
Heating A 0.63(0.63) 0.90(0.90) 1.04(1.04)
External finish Galvanized
Dimensions Height mm 250
Width mm 900 1100
Depth mm 732
Net weight *2 kg 26(25) 32(31)
Heat exchanger Cross fin(Aluminium fin and copper tube)
Fan Type Sirocco fan x 1
Sirocco fan x 2
Airflow rate (Low-Mid-High)
m3/min 12.0-14.5-17.0
13.5-16.0-19.0
14.5-18.0-21.0
External static pressure
Pa 35/50/70/100/150
Motor Output kW 0.085 0.121
Air filter PP Honeycomb fabric (washable)
Refrigerant pipe dimensions
Gas (Brazed con-nection)
mm[in.] ø12.7[ø1/2] ø15.88[ø5/8]
Liquid (Brazed connection)
mm[in.] ø6.35[ø1/4] ø9.52[ø3/8]
Drain pipe dimensions mm[in.] O.D. 32[1-1/4]
Operating noise(Low-Mid-High) 35Pa dB (A) 24-28-31 25-28-32 26-29-33
50Pa 25-29-32 25-29-33 26-29-34
70Pa 26-30-33 26-30-34 26-30-35
100Pa 27-31-34 27-31-35 29-33-37
150Pa 29-34-38 32-37-41
35Pa 28-31-35 29-32-35 30-33-37
50Pa 28-32-35 29-32-36 30-34-38
70Pa 29-33-37 30-33-38 31-36-39
100Pa 30-34-38 31-35-39 33-37-41
150Pa 32-37-41 33-38-41 36-41-44
Measurement location 1
Aux. duct
* Measured in anechoic room.
2m 2m
1.5m
* Measured in anechoic room.
2m 1m
Aux. duct
1.5m
Measurement location 2
0000001526.book 5 ページ 2012年9月13日 木曜日 午後7時14分
-
[ III Specfications ]
- 6 -HWE0812B GB
*1 Indoor temperature: 27°CDB/19°CWB (81°FDB/66°FWB) Outdoor temperature: 35°CDB (95°FDB) Indoor temperature: 20°CDB (68°FWB) Outdoor temperature: 7°CDB/6°CWB (45°FDB/43°FWB)*2 Figures in the parentheses indicate drainpump-less Model (L).
Model PEFY-P100VMA(L)-E
PEFY-P125VMA(L)-E
PEFY-P140VMA(L)-E
Power supply Voltage V 1-phase 220-230-240
Frequency Hz 50/60
Cooling capacity *1 kW 11.2 14.0 16.0
Heating capacity *1 kW 12.5 16.0 18.0
Power consumption *2 Cooling kW 0.24(0.22) 0.34(0.32) 0.36(0.34)
Heating kW 0.22(0.22) 0.32(0.32) 0.34(0.34)
Current consumption *2 Cooling A 1.47(1.36) 2.05(1.94) 2.21(2.10)
Heating A 1.36(1.36) 1.94(1.94) 2.10(2.10)
External finish Galvanized
Dimensions Height mm 250
Width mm 1400 1600
Depth mm 732
Net weight *2 kg 42(41) 46(45)
Heat exchanger Cross fin(Aluminium fin and copper tube)
Fan Type Sirocco fan x 2
Airflow rate (Low-Mid-High)
m3/min 23.0-28.0-33.0 28.0-34.0-40.0 29.5-35.5-42.0
External static pressure
Pa 35/50/70/100/150
Motor Output kW 0.244
Air filter PP Honeycomb fabric (washable)
Refrigerant pipe dimensions
Gas (Brazed con-nection)
mm[in.] ø15.88[ø5/8]
Liquid (Brazed connection)
mm[in.] ø9.52[ø3/8]
Drain pipe dimensions mm[in.] O.D. 32[1-1/4]
Operating noise(Low-Mid-High) 35Pa dB (A) 28-32-36 31-35-39 31-35-40
50Pa 28-33-37 32-36-40 33-37-42
70Pa 30-35-39 32-37-41 34-38-43
100Pa 31-36-40 33-39-42 35-39-44
150Pa 33-38-43 37-40-44 37-41-45
35Pa 31-36-40 35-40-44 36-41-45
50Pa 32-37-41 35-40-44 36-41-45
70Pa 33-38-42 37-41-45 38-42-46
100Pa 35-39-43 38-42-46 39-43-47
150Pa 37-42-45 39-44-47 40-45-48
Measurement location 1
Aux. duct
* Measured in anechoic room.
2m 2m
1.5m
* Measured in anechoic room.
2m 1m
Aux. duct
1.5m
Measurement location 2
0000001526.book 6 ページ 2012年9月13日 木曜日 午後7時14分
-
[ III Specfications ]
- 7 -HWE0812B GB
2. Electrical component specifications
Component Sym-bol
PEFY-P20VMA(L)-E
PEFY-P25VMA(L)-E
PEFY-P32VMA(L)-E
Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Fuse FUSE 250V 6.3A
Fan motor 8-pole, Output 85W SIC-70CW-D885-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2 (L, N, ) 250V 20A
Transmission terminal block
TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A
Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less
Component Sym-bol
PEFY-P40VMA(L)-E
PEFY-P50VMA(L)-E
PEFY-P63VMA(L)-E
PEFY-P71VMA(L)-E
PEFY-P80VMA(L)-E
Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Fuse FUSE 250V 6.3A
Fan motor 8-pole, Output 85W SIC-70CW-D885-2
8-pole, Output 121W SIC-70CW-D8121-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2 (L, N, ) 250V 20A
Transmission terminal block
TB5TB15
(1, 2) 250V 15A, (M1, M2, S) 250V 20A
Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less
Component Sym-bol
PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E
Room temperature thermistor
TH21 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Liquid pipe thermistor TH22 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Gas pipe thermistor TH23 Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Fuse FUSE 250V 6.3A
Fan motor 8-pole, Output 244W SIC-101CW-D8244-1
Linear expansion valve LEV 12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
Power supply terminal block
TB2 (L, N, ) 250V 20A
Transmission terminal block
TB5TB15 (1, 2) 250V 15A, (M1, M2, S) 250V 20A
Drain float switch DS Open/short detectionInitial contact resistance 500 mΩ or less
0000001526.book 7 ページ 2012年9月13日 木曜日 午後7時14分
-
[ IV Outlines and Dimensions ]
- 8 -HWE0812B GB
IV Outlines and Dimensions
[1] Outlines and Dimensions1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA-E
Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMA-E models, which have 2
fans. The PEFY-P20~50VMA-E model have 1 fans.
4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.
1558
1358
1500
1300
7Mo
del
A66
080
0
1200
700
754
900
954
860
9E 11
D 1060
C
1100
B 1154
PEFY
-P14
0VMA
-EPE
FY-P
100,1
25VM
A-E
PEFY
-P63
,71,80
VMA-
EPE
FY-P
40, 5
0VMA
-EPE
FY-P
20,25
,32VM
A-E
1400
1600
1454
1654
1500
1700
1360
1560
14 16
1000
1000F
858
800
G 658
1058
600
1480
1280
55
300
150
44 49
800
1000
260
LK 33
0
JH 1200
1500
1700
54 5432
037
0
544M
780
4
N 990
121210P 10 10ø1
5.88
ø9.52
ø12.7
ø6.35
Gas p
ipe1
Liquid
pipe
2
650 -10
(Actua
l leng
th)
Less
than
300m
m
Less than 700mm
Drain
hose
(I.D.ø
32)
Air F
ilter
G 21
A
B (Suspension bolt pitch)
C
23
Air
inlet
L6J
KK x (M - 1) = N
P - ø2.9
40
D (Duct) 20 100
57
73
10
643
(Sus
pens
ion bo
lt pitc
h)
10030100 x (E - 1) = F
5815
Susp
ensio
n bolt
hole
4 - 1
4 x 30
Slot
2 x E
- ø2
.9 Air outle
t
250
40
33122
178(Duct)23
1023
832
700732
136
67 356
100
41217
2 1
Contr
ol bo
xRe
friger
ant p
iping
Braz
ing co
nnec
tion (
liquid
)
Refrig
eran
t pipi
ngBr
azing
conn
ectio
n (ga
s)
Drain
pump
Term
inal b
lock (
Powe
r sou
rce)
Term
inal b
lock (
Tran
smiss
ion)
Drain
pipe
(O.D
.ø32
)(S
ponta
neou
s dra
ining
)
Drain
pipe
(O.D
. ø32
)
2 x 2
- ø2.9
210
18
112
1111
2
KJ
112
P - ø
2.9
11 112
JK
L6
JK
K x (
M - 1
) = N
0000001526.book 8 ページ 2012年9月13日 木曜日 午後7時14分
-
[ IV Outlines and Dimensions ]
- 9 -HWE0812B GB
2. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMAL-E
Note 1 Use M10 suspension bolts. (not supplied)2 Provide an access door for maintenance at the bottom.3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMAL-E models, which have
2 fans. The PEFY-P20~50VMAL-E model have 1 fans.
4 To connect an intake duct, uninstall the air filter on the unit, and install a locally procured air filter on the intake duct on the intake side.
1558
1358
1500
1300
7M
odel
A66
080
0
1200
700
754
900
954
860
9E 11
D 1060
C
1100
B 1154
PEFY
-P14
0VM
AL-E
PEFY
-P10
0,12
5VM
AL-E
PEFY
-P63
,71,
80VM
AL-E
PEFY
-P40
, 50V
MAL
-EPE
FY-P
20,2
5,32
VMAL
-E
1400
1600
1454
1654
1500
1700
1360
1560
14 16
1000
1000F
858
800
G 658
1058
600
1480
1280
55
300
150
44 49
800
1000
260
LK 33
0
JH 1200
1500
1700
54 5432
037
0
544M
780
4
N 990
121210P 10 10ø1
5.88
ø9.5
2
ø12.
7ø6
.35
Gas p
ipe1
Liquid
pipe
2
250
40
33122
21
23
178(Duct)23
10
3270
0732
136
67 356
100
217
643
(Sus
pens
ion bo
lt pitc
h) A
ir Fi
lter
Cont
rol b
oxRe
frige
rant
pipi
ngBr
azing
conn
ectio
n (liq
uid)
Refri
gera
nt p
iping
Braz
ing co
nnec
tion
(gas
)Te
rmina
l bloc
k (Po
wer s
ourc
e)
Term
inal b
lock (
Tran
smiss
ion)
Drain
pipe
(O.D
.ø32
)2
x 2 -
ø2.9
2 1
(Actu
al len
gth)
320 -10
J 6P - ø2.9
D (Duct)
210
18
G
A
B (Suspension bolt pitch)
C
100 x (E - 1) = F
Air
outle
tAi
rinl
et
Susp
ensio
n bo
lt hole
4 -
14 x
30 S
lot2
x E -
ø2.9
Drain
hose
(I.D.
ø32)
K x (M - 1) = NKLK
112
1111
2
24
20 100
57
7310
10030
15
J
K x (
M - 1
) = N
KJ
6L
KJ
11211
P - ø
2.9
112
0000001526.book 9 ページ 2012年9月13日 木曜日 午後7時14分
-
[ IV Outlines and Dimensions ]
- 10 -HWE0812B GB
[2] Service Space1.PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E
Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchanger, and electric box in one of the following ways.Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other objects.(1) When a space of 300 mm or more is available below the unit between the unit and the ceiling (Fig. 1)• Create access door 1 and 2 (450 × 450 mm each) as shown in Fig. 2.(Access door 2 is not required if enough space is available below the unit for a maintenance worker to work in.)
(2) When a space of less than 300 mm is available below the unit between the unit and the ceiling (At least 20 mm of space should be left below the unit as shown in Fig. 3.)• Create access door 1 diagonally below the electric box and access door 3 below the unit as shown in Fig. 4.or• Create access door 4 below the electric box and the unit as shown in Fig. 5.
Elec
tric b
ox
Ceiling
Min. 300 mm
Min. 10 mm
View
ed fr
om
the
direc
tion
of th
e ar
row
A
Acce
ss do
or 2 (
450 ×
450)
Ceilin
g beam
Intak
e air
Supp
ly air
Elec
tric b
ox
Ceilin
g
Min. 20 mm
Min.10 mm
View
ed fr
om
the
direc
tion
of th
e ar
row
B
Ceilin
g beam
Acce
ss do
or 3
Intak
e air
Supp
ly air
700
450
475
450
R 50~1
5045
0
450
100~
200
Botto
m o
f indo
or u
nit
Maint
enan
ce ac
cess
spac
e
Min. 3
00 m
m
(View
ed fr
om
the
direc
tion
of
the
arro
w A)
Acce
ss do
or 2
(450
× 45
0)
Acce
ss do
or 1
(450
× 45
0)
Q
Elec
tric b
ox
Acce
ss do
or 3
Q 50
S
777
450 100
~200
Maint
enan
ce ac
cess
spac
e
Botto
m of
indoo
r unit
Elec
tric b
ox
(View
ed fr
om th
e dir
ectio
n of
th
e ar
row
B)
Acce
ss do
or 1
(450
× 45
0)
450
4757
0050
Min. 3
00 m
m
777
T
50
50Q
700
Maint
enan
ce ac
cess
spac
e
Botto
m of
indoo
r unit
Electri
c box
Min. 3
00 m
m
(View
ed fr
om th
e dir
ectio
n of
th
e ar
row
B)
Acce
ss do
or 4
Fig.
1
Fig.
3
Fig.
2
Fig.
4Fi
g. 5
PE
FY-P
20,2
5,32
VM
A(L
)-E
PE
FY-P
40,5
0VM
A(L
)-E
PE
FY-P
63,7
1,80
VM
A(L
)-E
PE
FY-P
100,
125V
MA
(L)-
EP
EFY
-P14
0VM
A(L
)-E
Q 700
900
1100
1400
1600
S 800
1000
1200
1500
1700
T 1300
1500
1700
2000
2200
R50
~150
150~
250
250~
350
400~
500
500~
600
(mm
)M
odel
Uni
t: m
m
0000001526.book 10 ページ 2012年9月13日 木曜日 午後7時14分
-
[ V Wiring Diagram ]
- 11 -HWE0812B GB
V Wiring Diagram
[1] Wiring Diagram1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E
2 1
INSI
DE S
ECTI
ON
OF
CONT
ROL
BOX
FUSE
(16A
)
BREA
KER
(16A
)
PULL
BOX
TO N
EXT I
NDOO
R UN
IT
TO M
A RE
MOTE
CO
NTRO
LLER
TO O
UTDO
OR U
NIT
BC C
ONTR
OLLE
RRE
MOTE
CON
TROL
LER
P.B.
21
TB15
2 1
TB2
NL
S (S
HIEL
D)
M2 M1
TB5
ACL
21
1 3
35
1
X10
U
DC2
80-3
40V
Rect
ifier c
ircui
t
U
(Red
)
X01
CNP
F01
DSA
ZNR0
2
CND
ZNR0
1
(Blue
)
Drain
pump
Fan m
otor
53
21
44
45
67
12
11
23
(Blue
)CN
XB1
CNMF
CNXA
1CN
XC1
ONLY
FOR
PEF
Y-P·
VMA-
E
MS 3~
M 1~
I.B.
1
431 2
21542 3
CN4F
(Blue
)CN
XA2
CN52
CN20
CN41
CN51
CNXB
2
CNXC
2(R
ed)
CN44
(Gre
en)
1 2 4321 3 4
1 2
13
(Blac
k)
(Red
)
CN3A
(Blue
)
(Red
)
CN2A
LED1
LED2
CN27
SWE
CN90
CN10
5
CN2M
(Blue
)ONOF
FSW
3
SW2
SW1
1 2 43
CN4F
TH21
t°
A
FSTH
23TH
22t°
t°
FOR
PEFY
-P·V
MA-E
REFE
R TO
"A" F
OR P
EFY-
P·VM
AL-E
21 653 4
CN60
CN32
SWA
SW4
SW11
SW12
SW14
SWC
SW5
POW
ER S
UPPL
YAC
220-
240V
50
,60Hz
M LEV
0000001526.book 11 ページ 2012年9月13日 木曜日 午後7時14分
-
[ V Wiring Diagram ]
- 12 -HWE0812B GB
Table.1 SYMBOL EXPLANATION
SYM-BOL
NAME SYM-BOL
NAME SYM-BOL
NAME
I.B. Indoor controller board CN32 Connector (Remote switch) SW2 (I.B.)
Switch (for capacity code)
P.B. Power supply board CN41 Connector (HA terminal-A) SW3 (I.B.)
Switch (for mode selection)
TB2 Power source terminal block CN51 Connector (Centrally control) SW4(I.B.)
Switch (for model selection)
TB5 Transmission terminal block CN52 Connector (Remote indica-tion)
SW5(I.B.)
Switch (for mode selection)
TB15 Transmission terminal block CN90 Connector (Wireless) SWE(I.B.)
Connector (emergency opera-tion)
F01 Fuse AC 250V 6.3A CN105 Connector (IT terminal) SW11(I.B.)
Switch (1s digit address set)
ZNR01,02
Varistor CN2A Connector (0-10V Analog in-put)
SW12(I.B.)
Switch (10ths digit address set)
DSA Arrester FS Float switch SW14(I.B.)
Switch (BRANCH No.)
X01 Aux. relay TH21 Thermistor (inlet air temp.de-tection)
SWA(I.B.)
Switch (for static pressure se-lection)
X10 Aux. relay TH22 Thermistor (piping temp.de-tection / liguid)
SWC(I.B.)
Switch (for static pressure se-lection)
ACL AC reactor (Power factor im-provement)
TH23 Thermistor (piping temp. de-tection / gas)
CN27 Connector (Damper) SW1(I.B.)
Switch (for mode selection)
Note 1 Wiring to TB2, TB5, and TB15 indicated by the double-dashed lines is on-site work.2 terminal block, connector.
0000001526.book 12 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VI Refrigerant System Diagram ]
- 13 -HWE0812B GB
VI Refrigerant System Diagram
[1] Refrigerant system diagram
(A) Gas pipe thermistor TH23
(B) Gas pipe
(C) Liquid pipe
(D) Brazed connections
(E) Strainer (#100 mesh)
(F) Linear expansion valve
(G) Liquid pipe thermistor TH22
(H) Heat exchanger
(I) Room temperature thermistor TH21
Capacity PEFY-P20, 25, 32, 40, 50VMA(L)-E
PEFY-P63, 71, 80, 100, 125, 140VMA(L)-E
Gas pipe ø12.7 [1/2] ø15.88 [5/8]
Liquid pipe ø6.35 [1/4] ø9.52 [3/8]
(H)
(I)
(F)
(E)(E)
(C)
(G)
(A)
(D)
(B)
0000001526.book 13 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 14 -HWE0812B GB
VII Troubleshooting
[1] Troubleshooting
1. Check methods1. Component and check points(1) Thermistor
Room temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Disconnect the connector and measure the resistance between terminals with a tester.(Ambient temperature 10°C - 30°C)
1) Thermistor characteristic graph
(2) Fan motor (CNMF)Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valveDisconnect the connector, and measure the resistance between terminals with a tester.Refer to the next page for details.
Normal Abnormal
4.3kΩ - 9.6kΩ Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistorRoom temperature thermistor (TH21)Liquid pipe thermistor (TH22)Gas pipe thermistor (TH23)Drain sensor (DS)
Thermistor R0 = 15 kΩ 3%Multiplier of B = 3480 kΩ 2%
0°C 15kΩ10°C 9.6kΩ20°C 6.3kΩ25°C 5.2kΩ30°C 4.3kΩ40°C 3.0kΩ
(A) Temperature (°C)
(B) Resistance (kΩ)
Normal Abnormal
1-5 2-6 3-5 4-6 Open or shortWhite-Red Yellow-Brown Orange-Red Blue-Brown
200 kΩ 10%
(A) Brown (D) Orange
(B) Red (E) Yellow
(C) Blue (F) White
Rt = 15 exp { 3480( ) }1273+t
1273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)
1 2 3 4 5 6
LEV
M
(A)
(B)
(C)
(D)
(E)
(F) CN60
0000001526.book 14 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 15 -HWE0812B GB
1) Summary of linear expansion valve (LEV) operationThe LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
Pulse signal output and valve operation
The output pulse changes in the following order:When the valve closes 1 -> 2 -> 3 -> 4 -> 1When the valve opens 4 -> 3 -> 2 -> 1 -> 4When the valve position remains the same, all output signals will be OFF.If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
(A) Brown (F) White
(B) Red (G) Control board
(C) Blue (H) Connection (CN60)
(D) Orange (I) Drive circuit
(E) Yellow (J) Linear expansion valve
Phase number
Output pulse1 2 3 4
ø1 ON OFF OFF ONø2 ON ON OFF OFFø3 OFF ON ON OFFø4 OFF OFF ON ON
4
3
6
5
2
1
(G)
(H)
(I)
(J) (A)
(A)
(B)
(B)
(C)
(C)
(D)
(D) (E)
(E)
(F) (F)
12VDC
M
4
6
2 3
5 1
0000001526.book 15 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 16 -HWE0812B GB
2) LEV operation
When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the figure, it makes louder noise than would be heard when there is an open phase. Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against your ear.
3) Troubleshooting
(a) Close
(b) Open
(c) Fully open valve (2000 pulses)
(d) No. of pulses
(e) Extra tightning (80 - 100 pulse)
(f) Valve opening degree(f)
(a)
(b)
(e)
(d)
(c)
Symptom Checking Criteria Remedy
Circuit failure on the microcomputer
Disconnect the connectors on the control board, and connect LEDs to test the cir-cuit as shown below.
Pulse signals are output for 10 seconds when the main power is turned on. If there are LEDs that do not light up at all or remain lit after the pulses are turned off, there is a problem with the driving circuit.
Replace the in-door control board if driving circuit failure is detected.
Locked LEV The motor will idle and make small clicking noise if it is run while the LEV is locked. If this clicking noise is heard both when the valve is fully closed and while it is being opened, it indicates a problem.
Replace the LEV.
Disconnected or shorted LEV motor coils
easure the resistance between the coils with a tester (red-white, red-orange, brown-yellow, brown-blue). The normal range of resistance is 150 Ω 10%
Replace the LEV.
654321
1 k LED
0000001526.book 16 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 17 -HWE0812B GB
(4) Drain-up mechanismMeasure the resistance between the terminals with a tester. (coil temperature 20°C)
(5) Drain float switch (CN4F)Disconnect the connector, and measure the resistance between terminals with a tester.
Valve closure fail-ure (leaky valve)
To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature that appears on the operation monitor on the outdoor unit's multi control board while operating the indoor unit in question in the FAN mode and the other indoor units in the cooling mode.
Replace the LEV if the amount of leakage is great.
(A) Termistor (TH21)
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected. If the amount of leakage is insignificant, replacement of LEV is unnec-essary unless it is causing a problem.
Misconnections of connectors or con-tact failure
Perform a visual check for disconnected connectors.Perform a visual check of lead wire color.
Disconnect the connectors on the control board and perform a continuity test.
Symptom Checking Criteria Remedy
(A)
LEV
Normal Abnormal
340 Ω Open or short
(A) Moving part
(B) Switch
(C) Magnet
Position of the moving part Normal Abnormal
Up Short (any position but short)
Down Open (any position but open)
13
1234
(A)
(A)
(B)(C)
0000001526.book 17 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 18 -HWE0812B GB
2. DC fan motor (fan motor/indoor control board)1. CAUTION
A high voltage is applied to the connector for connection to the fan motor (CNMF). Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.
2. TroubleshootingSymptom: Indoor unit fan does not run.
Check fan motor connector contact (CNMF).
Replace the indoor control board.
Replace the indoor control board.
Fix the connection.
Yes
No
Yes
No
Yes
No
Check the fan motor position thermistor signal.Get the motor to make a full rotation or more, and measure the voltage at the test point VFG.(same with the voltage between fan connector 7 (+) and 4(-))
Is the fan motor connector (CNMF) fully inserted?
Is the voltage within the normal range?
Replace the motor.Are 0VDC and 15VDC displayed alternately?
Check the power supply.Measure the voltage at the indoor control board.
310 - 340VDC (same with the voltage between fan connector 1 (+) and 4(-))
15VDC (same with the voltage between fan connector 5 (+) and 4(-)) 1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))
[Values for Vsp are the values that are measured with the fan motor in operation. Vsp is 0V when the fan motor is stopped.]
VDCPower supply voltage
0000001526.book 18 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 19 -HWE0812B GB
3. Address switch settingMake sure that power to the unit is turned off.
1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12).Address setting is not required when the unit remote controller is used.On-site address setting is required for the indoor units to run.
2. Address settings vary in different systems.Refer to the section on address setting in the outdoor unit installation manual.
3. Address is set with a combination of SW12 (10's digit) and SW11 (1's digit).To set the address to "3," set SW12 to "0" and SW11 to "3."To set the address to "25," set SW 12 to "2" and SW 11 to "5."
(A) Indoor unit control board
(B) Factory setting
ONOFF
SW4
(A)
(B)Please see the WIRING LABEL on the control box.
body7.fm 19 ページ 2012年9月19日 水曜日 午前11時56分
-
[ VII Troubleshooting ]
- 20 -HWE0812B GB
4. Voltage test points on the control board1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E
F01 Fuse(AC 250V 6.3A)
CND Power supply voltage (220 - 240VAC)
CN2M For M-NET transmission cable connection (24 - 30VDC)
SWE Emergency operation
SW2 Capacity setting
SW4 Function setting
SW3 Function setting
CN32 Remote start/stop adapter
CN3A For MA remote controller cable connection (10 - 13 VDC (Between 1 and 3.))
CN52 Remote display
CN51 Centralized control
CN41 JAMA standard HA terminal A
CN44 Thermistor (liquid/gas tempera-ture)
CN4F Float thermistor
CN20 Thermistor (Inlet temperature)
CNMF Fan motor output1 - 4: 310 - 340 VDC5 - 4: 15 VDC6 - 4: 0 - 6.5 VDC7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC(0 - 15 pulse)
CNP Drain-up mechanism output (200VAC)
(*1)
VFG Voltage on the (-) side of PC51 and C25(Same with the voltage between 7 (+) and 4 (-) of CNMF)
VCC Voltage between the C25 pins 15 VDC(Same with the voltage between 5 (+) and 4 (-) of CNMF)
Vsp Voltage between the C53 pins0VDC (with the fan stopped)1 - 6.5VDC (with the fan in opera-tion)(Same with the voltage between 6 (+) and 4 (-) of CNMF)
CN3A
CN2M
SW4
CND
F01
CN32Indoor controller board
Power supply board
SW3
PC51(*1)
CN41CN51CN52
CN20
CN4FCN44
C25(*1)
C53(*1)
CNMF
SWESW2
CNP
0000001526.book 20 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 21 -HWE0812B GB
5. Dipswitch setting (Factory setting)1. Function setting(1) SW1
1) Adress board
(2) SW3
1) Indoor control boardDipswitch settings must be made while the unit is stopped.
Switch position Function Switch setting
ON OFF
1 Active Thermistor (Intake air thermistor)
Built-in thermistor on the remote controller
Indoor unit
2 Filter clogging detection Available Unavailable
3 Filter life 2500 hr 100 hr
4 Outdoor air intake Enabled Disabled
5 Remote display Thermo-ON signal Fan output
6 Humidifier operation During heating mode During heating operation
7 Fan speed Low Very low
8 Fan speed at heating Thermo-OFF Preset fan speed Follows the setting of SW1-7
9 Auto restart after power failure Enabled Disabled
10 Power start/stop Enabled Disabled
Factory setting
Switch position Function Switch setting
ON OFF
1 Unit type Cooling only Heat pump
2 - - -
3 - - -
4 - - -
5 - - -
6 - - -
7 - - -
8 Heating 4-deg up Disabled Enabled
9 - - -
10 - - -
Factory setting
PEFY-P25, 40, 63, 71, 80, 100, 125, 140VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32, 50VMA(L)-E
0000001526.book 21 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VII Troubleshooting ]
- 22 -HWE0812B GB
2. Capacity code setting(1) SW21) Indoor control board
Dipswitch settings must be made while the unit is stopped.Factory settingThe switches are set to correspond to the unit capacity.
3. Model setting(1) SW41) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Note: Changes made to the dipswitches SW1, SW2, and SW3 will become effective when the unit comes to a stop (remote controller off). There is no need to power cycle the unit.
4. Power voltage setting(1) SW51) Indoor control board
Dipswitch settings must be operated with the main power turned OFF.
Factory settingPlease see the WIRING LABEL on the control box.
Factory settingPlease see the WIRING LABEL on the control box.
Set SW5 to 240V side when the power supply is 240 volts.When the power supply is 220 and 230 volts, set SW5 to 220V side.
PEFY-P25VMA(L)-EPEFY-P20VMA(L)-E PEFY-P32VMA(L)-E PEFY-P40VMA(L)-E
PEFY-P50VMA(L)-E PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E
PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E
body7.fm 22 ページ 2012年9月19日 水曜日 午前11時53分
-
[ VII Troubleshooting ]
- 23 -HWE0812B GB
5. External static pressure(1) SWA, SWC1) Indoor control board
Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).
6. 1s and 10ths digits(1) SW11, SW12 (Rotary switch)
The use of a network remote controller (PAR-F27MEA) requires address setting. 1) Indoor control board
Address settings must be made while the unit is stopped.
7. Connection No. setting(1) SW14 (Rotary switch)
This switch is used when the unit connected to an R2 series of outdoor unit. 1) Indoor control board
Note: Changes to the dipswitches SW11, SW12, SW14, and SW15 must be made while the unit is stopped and the remote controller is OFF.
All models Factory setting
Factory setting
Factory setting
35Pa
1 2 3
SWA SWC
50Pa
1 2 3
SWA SWC
70Pa
1 2 3
SWA SWC
100Pa
1 2 3
SWA SWC
150Pa
123
SWA SWC1
2
1
2
1
2
1
2
1
2
1 2 3
SWA SWC
1
2
0000001526.book 23 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 24 -HWE0812B GB
VIII Disassembly Procedure
[1] Disassembly Procedure
1. Control boxExercise caution when removing heavy parts.
1. Removing the control box cover(1) Remove the three fixing screws on the cover (A) to re-
move it.
Fig.1
Fig.2
(A)
0000001526.book 24 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 25 -HWE0812B GB
2. Thermistor (Intake air)Exercise caution when removing heavy parts.
1. Remove the control box cover according to the procedure in section [1].
2. Remove the thermistor.(1) Pull out the thermistor holder (B) and thermistor (C) on
the control box.
Fig.3
(B), (C)
0000001526.book 25 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 26 -HWE0812B GB
3. DrainpanExercise caution when removing heavy parts.
1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in
the direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (D), (E) to
remove it.
Fig.4
2. Removing the drainpan(1) Pull out the drain pan in the direction of the arrow 2.
Fig.5
NoteDrain the water out of the drain pan before removing it.
(D) (E)
0000001526.book 26 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 27 -HWE0812B GB
4. Thermistor (Gas pipe) (Liquid pipe)Exercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in sec-tion [1].
2. Removing the Heat exchanger cover(1) Remove the four fixing screws on the heat exchanger cov-
er (F) to remove it.
Fig.6
3. Removing the thermistor(1) Remove the thermistor (G) from the thermistor holder (H)
on the copper tube.
Thermistor sizeLiquid pipe: ø8mmGas pipe: ø6mm
Fig.7
(F)
HEX
(G), (H)
0000001526.book 27 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 28 -HWE0812B GB
5. Fan and fan motorExercise caution when removing heavy parts.
1. Removing the filter and the bottom plate(1) Push down the tab on the filter, and pull out the filter in the
direction of the arrow 1.(2) Remove the fixing screws on the bottom plate (J) to re-
move it.
Fig.8
(a) Tab
2. Removing the fan casing (bottom half)(1) Squeeze the tabs on the fan casing to remove it in the di-
rection of arrow 2.
Fig.9
3. Removing the motor cable(1) Remove the motor cable threw the rubber bush.4. Removing the fan motor and the Sirocco fan(1) Remove the two motor fixing screws to remove the motor
and the Sirocco fan in the direction of arrow 3.
Fig.10
(2) Remove the four fan case fixing screws to take the top half of the fan casing off.
Fig.11
(J)
(a)
0000001526.book 28 ページ 2012年9月13日 木曜日 午後7時14分
-
[ VIII Disassembly Procedure ]
- 29 -HWE0812B GB
6. Heat exchangerExercise caution when removing heavy parts.
1. Remove the drain pan according to the procedure in section [1].
2. Remove the heat exchanger cover according to the proce-dure in section [4] 2.
3. Removing the cover(1) Remove the five fixing screws on the cover (K) to remove it.
Fig.12
(K) Pipe support plate
4. Removing the Heat exchanger(1) Remove the fixing screws on the heat exchanger (M) to re-
move it.
Fig.13
(K)
(M)
0000001526.book 29 ページ 2012年9月13日 木曜日 午後7時14分
-
KB79U866H02_GB.fm Page 18 Monday, April 25, 2011 3:16 PM
-
HWE0812B
New publication effective Sep. 2012Specifications subject to change without notice