Payback Calculation
-
Upload
venkat-cherukuri -
Category
Documents
-
view
219 -
download
0
Transcript of Payback Calculation
-
7/31/2019 Payback Calculation
1/2
PAYBACK CALCULATIONS FOR POWER FACTOR IMPROVEMENT at CHPP, Zambia.
A. Deduction in demand charges by improving power factorSystem present demand ( kVA1 ) = 2500 kVA
System present power factor (Cos 1) = 0.7
Power factor (Cos ) = kW/kVA
kW = kVA x Cos
at present power factor kW = kVA 1 x Cos 1 = 2500 x 0.7 = 1750
We are improving the power factor from 0.7 to 0.95 by installing the capacitor banks at CHPP MCC
Now system demand (kVA2) = kVA2
Power factor improvement (Cos2) = 0.95
Now at this power factor kW = kVA 2 x Cos 2
= kVA2 x 0.95
As at the same power required demands are different depending on the power factor
kVA 1 x Cos 1 = kVA 2 x Cos 2
1500 = kVA 2 x 0.95
kVA 2 = 1750/0.95 = 1842
after improving the power factor required demand at the same power is 1842 kVA instead of 2500 kVA
Therefore reduction in demand charges in energy bill due to reduction in maximum demand by
improving power factor from 0.7 to 0.9 shall be
Saving in demand charges per month = Rs. 100 x (2500 1842) = Rs. 1,84,200 per month
Net reduction per annum = 1,84,200 x 12 = 22,10,400
B. Cost investment for installation of power factor improving equipment There are two sets of 300 kVAr and one set of 250 kVAr capacitor banks for each MCC
Cost of capacitor banks = Rs. 1000000
Switching and associated equipment and installation = Rs. 200000
Total cost = Rs. 1200000
-
7/31/2019 Payback Calculation
2/2
C. Pay back calculationTotal cost of the capacitor banks = Rs. 1200000
Annual depreciation and interest @ 20% = 1200000 x 0.2 = Rs. 240000
Net annual saving = Rs. 2210400 240000 = Rs. 1970400
Net monthly saving = Rs. 1970400 / 12 = Rs. 164200
Therefore, payback period = 1200000 / 164200 = 7.3 months
This may be consider that as demand (kVA) got reduced by improving power factor, current on the
system also reduced further, I2 R losses also reduced. So there is further reduction in energy bill by
decreasing losses on the system
Advantages of improving power factor:
1. Reduced system losses, and the losses in the cables, lines, and feeder circuits and hence lowersizes could be opted.
2. Improved system voltages, thus enable maintaining rated voltage to motors, pumps and otherequipment. The voltage drop in supply conductors is a resistive loss, and wastes power heating
the conductors. A 5% drop in voltage means that 5% of your power is wasted as heat before it
even reaches the motor. Improving the power factor, especially at the motor terminals, can
improve your efficiency by reducing the line current and the line losses.
3. Improved voltage regulation.4. Increased system capacity, by release of kVA capacity of transformers and cables for the same
kW , thus permitting additional loading without immediate augmentation.