1 16/11/2016 1 09/11/2016 PASSIVE FIRE PROTECTION OF INSTALLATIONS CERTIFICATIONS & TESTS SEISMIC BEHAVIOR Fire Safety Academy 3 Giugno 2019 Milano

Transcript of PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire...

Page 1: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

116/11/2016 109/11/2016

PASSIVE FIRE PROTECTIONOF INSTALLATIONS

CERTIFICATIONS & TESTSSEISMIC BEHAVIOR

Fire Safety Academy

3 Giugno 2019

Milano

Page 2: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

AGENDA

1 Passive Fire Protection - Compartmentation

2 Passive Fire Protection – Firestopping, Testing & Approvals

3 Behavior under seismic conditions

2Passive Fire Protection – Firestopping / June 03 2019

Page 3: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

AGENDA

3

1 Passive Fire Protection - Compartmentation

2 Passive Fire Protection – Firestopping, Testing & Approvals

3 Behavior under seismic conditions

Passive Fire Protection – Firestopping / June 03 2019

Page 4: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

WHY FIRE PROTECTION ?

4Passive Fire Protection – Firestopping / June 03 2019

Page 5: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

PASSIVE FIRE PROTECTION

Passive Fire Protection is one of the three key components besides

active Fire Protection and education for fire protection in buildings

Passive Fire protection is a range of measures designed to prevent,

contain or slow the spread of fire from the area of origin to other areas

in the building to minimize damage and give occupants enough time to

evacuate

5Passive Fire Protection – Firestopping / June 03 2019

Page 6: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

Detection &

Alarm

Automatic / manual fire suppression are activated

i.g. automatic doors, notification fire department

i.g. occupants have time to move outside the building

Automatic

Suppression

Sprinkler / extinguishing systems

Compart-

mentation

Barriers such as walls, partitions and floors

to delay or prevent fire or smoke from propagating

from one space to another.

KEY ELEMENTS OF FIRE PROTECTION

Active

Passiv

e

6Passive Fire Protection – Firestopping / June 03 2019

Page 7: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

VERTICAL AND HORIZONTAL COMPARTMENTATION

7

Vertical compartmentation by

use of fire-resisting walls:

Fire can spread vertically via

openings in floors

Horizontal compartmentation by

use of fire-resisting floors:

Fire can spread horizontally via

openings in walls

Madrid Feb 2005 Windsor-Building

Passive Fire Protection – Firestopping / June 03 2019

Page 8: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

Unsealed/

Open Joints

Unsealed Cable

Penetrations

Unsealed Pipe

Penetrations/Ducts

Doors

Gaps at edge of

slab

Membrane

(one-sided)

penetrations

AREAS THAT CAN ALLOW FOR FIRE/SMOKE SPREAD

8Passive Fire Protection – Firestopping / June 03 2019

Page 9: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

COMPARTMENTATION

9Passive Fire Protection – Firestopping / June 03 2019

Page 10: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

SUCCESSFUL COMPARTMENTATION

10Passive Fire Protection – Firestopping / June 03 2019

Page 11: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

AGENDA

11

1 Passive Fire Protection - Compartmentation

2 Passive Fire Protection – Firestopping, Testing & Approvals

3 Behavior under seismic conditions

Passive Fire Protection – Firestopping / June 03 2019

Page 12: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

WHAT IS FIRESTOP ?

12Passive Fire Protection – Firestopping / June 03 2019

Firestop systems, if installed correctly, will help to maintain the

fire resistance of a floor or wall as it is penetrated by an object

or joint and resist the spread of smoke and fire.

It is part of the life safety plan in structures

Page 13: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

APPLICATION FOCUS INSTEAD OF PRODUCT FOCUS: OPENINGS IN BUILDINGS

All openings in fire rated walls and floors must be

protected by systems with adequate fire resistance.

Curtain wall Joints1

2 Penetrations of combustible and

non-combustible pipes

3 Mixed penetrations (cables and

pipes in one seal)

4 Linear Joints6

2

3

4

5

5 Cable penetrations

1

13

5

Passive Fire Protection – Firestopping / June 03 2019

Page 14: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

Non-Combustible Pipes

PIPE PENETRATIONS

Combustible Pipes

14Passive Fire Protection – Firestopping / June 03 2019

Page 15: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

CABLE PENETRATIONS

15

Cable Trays Single Cables / Bundles

Passive Fire Protection – Firestopping / June 03 2019

Page 16: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

LINEAR JOINT SEALS AND CURTAIN WALL JOINT SEALS

16

Linear Joint Seals Curtain Wall Seals

Passive Fire Protection – Firestopping / June 03 2019

Page 17: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

Heat

Flames

Gases

Heat

Flames

Gases

Heat

Flames

Gases

HOW IS THE FIRE RESISTANCE PERFORMANCE TESTEDAND CLASSIFIED IS CLASSIFIED IN RATINGS (EN)

Load Bearing Capacity

R - Rating

All criteria are measured in hours and minutes

17

Integrity

E - Rating

Insulation

EI - Rating

Passive Fire Protection – Firestopping / June 03 2019

Page 18: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

REAL FIRE DEVELOPMENT IS THE BASE FOR FIRE TESTING

18Passive Fire Protection – Firestopping / June 03 2019

Page 19: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

IN EUROPE EN TESTING IS ESTABLISHED AS THE HIGHEST TEST STANDARD - EXAMPLE PIPE PENETRATIONS

Schematic illustration for field of application rules

Standard configuration for multiple pipe penetrationsStandard configuration for multiple pipe

penetrations

Pre-defined configurations

and rules for the field of

application are given in EN

1366-3 for pipe testing.

The field of application will be defined based on the rules in the test standard.

Standard configurations or otherwise only the tested configuration will be covered

19Passive Fire Protection – Firestopping / June 03 2019

Page 20: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

During fire test

PIPE PENETRATIONS

After fire exposure & hose

stream

20Passive Fire Protection – Firestopping / June 03 2019

Page 21: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

PIPE PENETRATIONS

21Passive Fire Protection – Firestopping / June 03 2019

Page 22: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

Des. Type Size Material *) Ø

A1 S 5 x 1,5 PVC/PVC 14

A2 S 5 x 1,5 EPR / PO 14

A3 S 5 x 1,5 XLPE / EVA 14

B S 1 x 95 PVC / PVC 21

C1 S 4 x 95 PVC / PVC 47

C2 S 4 x 95 EPR / PO 61

C3 S 4 x 95 XLPE / EVA 46

E S 1 x 185 PVC/PVC 27

D1 S 4 x 185 PVC/PVC 52

D2 S 4 x 185 EPR / PO 80

D3 S 4 x 185 XLPE / EVA 63

F T 20x2x0,6 18

G1 W 1 x 95 PVC / - 17

G2 W 1 x 185 PVC / - 23

S = Sheathed

cSmall Sheathed

Large Sheathed

Telecommunication Cable

Wires

W = Wire

T = Telecommuni-cation cable

Medium Sheathed

The selection of cables for the standard configuration considers all known influencing parameters and is thought to be representative for all cables used in buildings in Europe.

EN TESTING – CABLE PENETRATIONS

Pre-defined

configurations and

rules for the field of

application are given

in EN 1366-3 for

cable testing.

Passive Fire Protection – Firestopping / June 03 2019

Page 23: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

CERTIFICATION - EUROPEAN CONSTRUCTION PRODUCTREGULATION & CE-MARKING

CPRThe Construction Products Regulation (305/2011/EU - CPR) – replacing the Construction Products Directive (89/106/EEC - CPD) is laying down harmonised

conditions for the marketing of construction products

hENHarmonized European Standard

EADEuropean Assessment Document

ETA/DOPEuropean Technical Assessment

CE - markingCertification / Declaration

DOPDeclaration of Performance

If hEN developed and publishedProducts without hEN

Both routes require EN Test & Classification standards

Voluntary route Mandatory

Passive Fire Protection – Firestopping / June 03 2019

Page 24: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

ETA PROCESS

EUROPEAN TECHNICAL ASSESSMENT

Test Standards (EN)

Testing

Test & Classification Report

European Technical Assessment (ETA)

Certificate of Conformity (CoC)

Declaration of Performance (DoP)

CE Marking

• ETA & DoP should be checked for

field of application and

performance results

• CE Marking means that a product

was tested according to

standardized European norms but

it says nothing about its

performance and field of

application.

Passive Fire Protection – Firestopping / June 03 2019

Page 25: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

AGENDA

25

1 Passive Fire Protection - Compartmentation

2 Passive Fire Protection – Firestopping, Testing & Approvals

3 Behavior under seismic conditions

Passive Fire Protection – Firestopping / June 03 2019

Page 26: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

For example, after the earthquake of Northridge in 1994, there were

a total of 466 fires reported after the earthquake, some of them were

due because of the rupture of natural gas valves.

About 50% of the fires reported in the data occurred more than

several hours (and up to several days) after the earthquake events

Sources: (1)A Method for Evaluating Fire After Earthquake Scenarios for Single Buildings. Elizabeth J. Kelly and Raymond N. Tell

(2) After the Shaking Stops: A Communitywide Approach to Managing Post-Quake Fires. Insurance Institute for Business & Home Safety

(3) Hospital Seismic Safety. California healthcare foundation January 2009

Multiple simultaneous ignitions: 50-75% of the fires start

immediately after the event

FIRE IS THE MOST COMMON POST EARTHQUAKE RISK

26Passive Fire Protection – Firestopping / June 03 2019

Page 27: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

DAMAGES TO NONSTRUCTURAL COMPONENTS CAN RESULT IN MAJOR ECONOMIC LOSS AND A THREAT TO LIFE SAFETY

Source: Earthquake effects on buildings. Christopher Arnold. FEMA Library, www.sponse.eu, www.italymagazine.com

In most buildings, the non-structural components account for 60 to 80

percent of the value of the building. Mostly these non structural components

are fragile, easily damaged and costly to repair or replace.

27Passive Fire Protection – Firestopping / June 03 2019

Page 28: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

BUILDING MOVEMENT THROUGH EARTHQUAKES

Example: Movement of wall / floor

• Pipes and cables are fixed to the ceiling

or the wall. During an earthquake the

penetrants can move in a different

direction than the walls or the floors

• All crossing points in the walls and floors

are critical

• Undefined movement of pipes/cables

within firestop penetrations is very likely

• Movement of pipes/cables will damage

stiff firestop products like sealants or

coated boards

• Risk of toxic smoke or fire to pass

through the opening

Different product types for each application available: Cables, cable trays and pipes

28Passive Fire Protection – Firestopping / June 03 2019

Page 29: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

SEISMIC TESTS OF PENETRATION SEALS

29

• Test results show big differences in the behaviour, appearance and failure

modes of different Firestop product systems. These results were verified

in a large scale seismic shake table test at the University of California,

San Diego.

• Quasi- static cyclic loads according to FEMA* 461 protocol applied

directly on one single penetrant, whereas the wall was fixed.

• The use of stiff and unflexible materials with low elasticity (e.g. mortars

and grouts, board systems, semi-plastic sealants) may be critical

especially in connection with pipes or cable trays where displacement

forces are high.

• Metal pipes may be deformed, plastic pipes may be bent during

movement.

• Low flexibility of the Firestop system will not be able to make up for the

penetrant movement.

• Penetrants or walls might break or even be destroyed.

Flexible or pre engineered systems with high safety level.

Passive Fire Protection – Firestopping / June 03 2019

Page 30: PASSIVE FIRE PROTECTION OF INSTALLATIONS … · 2019-06-17 · Alarm Automatic / manual fire suppression are activated i.g. automatic doors, notification fire department i.g. occupants

SUMMARY

• Active & Passive Fireprotection together with Education are the key elements for

Fire Safety, Compartmentation is essential for saving lives

• High Test Standards and a clearly defined Field of applicaitons together with s

strong Codes/Regualations are essential to use the right systems

• With the right design and Product Selection, Compartmentation also will work after

a seismic event

30Passive Fire Protection – Firestopping / June 03 2019