© Horizon Power Corporation Part 5 – LV Underground – Drawing Register Number Description U8 URD Mini Pillar Installation Guide U9 UDS Universal Pillar Installation Guide U10-1 UDS Universal Pillar Double Link Unit Drilling Detail U10-2 UDS Universal Pillar Double Link Unit Arrangement U15 Cable to LV Isolators, Crossarm and Cable Detail U16-1 Cable to LV Bare, Intermediate Direct Connection U16-2 Cable to LV Bare, Termination Direct Connection U17 ABC Fused Connection to Cable U18 25 SQ. mm Cable to ABC Direct Connection U19-1 25 SQ. mm Cable to LV Bare Intermediate Direct Connection U19-2 25 SQ. mm 4 Core Cable to 1 Phase Open Aerial U19-3 Transformer Pole to Pillar on Customer’s Property U19-4 25 SQ. mm Cable to LV Bare Termination Direct Connection U20 Wall Mounted Box, 100 Amp U21 Wall Mounted Box, 200 Amp U23-1 Unmetered Supply Cable Pit, Components Assembly U23-2 Unmetered Supply Mini Pillar Termination Details U24 LV Kiosk Type 1 U25 LV Kiosk Type 2 U26 LV Kiosk Type 3 U27 LV Cable to Fuse Switch U30-1 Below Ground Service Pit Installation Detail U30-2 Below Ground Service Pit Installation Detail – Application Guideline

Transcript of Part 5 – LV Underground – Drawing Register - Horizon Power · pillar kit double link keyed...

© Horizon Power Corporation

Part 5 – LV Underground – Drawing Register

Number Description

U8 URD Mini Pillar Installation Guide

U9 UDS Universal Pillar Installation Guide

U10-1 UDS Universal Pillar Double Link Unit Drilling Detail

U10-2 UDS Universal Pillar Double Link Unit Arrangement

U15 Cable to LV Isolators, Crossarm and Cable Detail

U16-1 Cable to LV Bare, Intermediate Direct Connection

U16-2 Cable to LV Bare, Termination Direct Connection

U17 ABC Fused Connection to Cable

U18 25 SQ. mm Cable to ABC Direct Connection

U19-1 25 SQ. mm Cable to LV Bare Intermediate Direct Connection

U19-2 25 SQ. mm 4 Core Cable to 1 Phase Open Aerial

U19-3 Transformer Pole to Pillar on Customer’s Property

U19-4 25 SQ. mm Cable to LV Bare Termination Direct Connection

U20 Wall Mounted Box, 100 Amp

U21 Wall Mounted Box, 200 Amp

U23-1 Unmetered Supply Cable Pit, Components Assembly

U23-2 Unmetered Supply Mini Pillar Termination Details

U24 LV Kiosk Type 1

U25 LV Kiosk Type 2

U26 LV Kiosk Type 3

U27 LV Cable to Fuse Switch

U30-1 Below Ground Service Pit Installation Detail

U30-2 Below Ground Service Pit Installation Detail – Application Guideline

© Horizon Power Corporation

Number Description

U35 Pillar Exclusion Zones

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

URD MINI PILLAR

INSTALLATION GUIDE

REVISION DATE

DRAWING No.

B JUNE 2011

U8

2

REAR VIEW

TERMINATIONS

SHEATH CUT

25mm SERVICE CABLE

ABOVE SOIL LEVEL

EARTH CLAMP

(STOCK FE0109 (1 KIT))

ON NEUTRAL

ALL CABLES & HEATSHRINK

FIT MASTIC LINED GLOVE TO

EARTH ROD

TOP OF

GL

RW

BN

FRONT VIEW

TERMINATIONS

ROAD

STREET LIGHTING

RED SPOT FUSE

100

440

300

EARTH ROD

BOLTED TO

NOTES:

5. FOR SPUDS SEE R35

4. FOR WORKING END SEE R33

FUSE SEE R32

3. FOR WAVECON TERMINAL BLOCK AND STREET LIGHT

2. FOR TERMINAL BLOCKS EXTRA NEUTRAL SEE R31

AND 500mm FROM EDGE.

1. PILLAR TO BE CENTRED 500mm INSIDE BOUNDARY

ALIGNMENT

PVC CONDUIT WHEN OFF

20-25mm DIAMETER ORANGE

FUSEWAY ENCLOSED WITH

CABLE TO STREET LIGHT

25mm SERVICE CABLE2

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

UDS UNIVERSAL PILLAR

INSTALLATION GUIDE

REVISION DATE

DRAWING No.

B JUNE 2011

U9

100

700 B

EF

OR

E C

UT

TIN

G

400

200

300

(INTERCONNECTOR OR SERVICE CABLE TO LARGE LOAD)

THIRD CABLE IF REQUIRED

TO ROADTO PROPERTY

TO ROADTO PROPERTY

TOP OF EARTH ROD

SHEATH CUT

G.L.

TOP BAR

LOWER BAR

RWB

P.V.C.

TOP OF EARTH ROD

PVC POULTICE

STREET MAINS

TERMINAL LUGS VIEWED FROM PROPERTY

BLOCK

TERMINAL

CUSTOMER

SUPPLY TO

FROM SHEATH CUT

TAIL LENGTHS 700

WITHIN PILLAR

EARTH SPEAR LOCATED

PILLAR

STREET MAINS

STREET MAINS

TERMINAL BLOCK

CONNECT TO NEUTRAL

SEE NOTE 3

NOTES:

ON NEUTRAL SCREENS & OVER PHASE LUGS

3. FIT MASTIC LINED GLOVE TO ALL CABLES & SHRINK

AND 500mm FROM EDGE.

2. PILLAR TO BE CENTRED 500mm INSIDE BOUNDARY

IN-LINE FUSE CARRIER INSTALLATION

1. REFER TO DRAWING U8 FOR STREET LIGHT

NEUTRAL LEAD FROM TERMINAL BLOCK

BOLTED TO NEUTRAL BAR AND ATTACHED TO

NEUTRAL SCREEN LUGS (ONE PER CABLE)

200

110

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

UDS UNIVERSAL PILLAR

DOUBLE LINK UNIT

DRILLING DETAIL

REVISION DATE

DRAWING No.

B JUNE 2011

U10-1

SEE NOTE 2

B W R

WITHIN PILLAR

EARTH SPEAR LOCATED

PILLAR

STREET MAINS

TO PROPERTY TO ROAD

CABLE TO LARGE LOAD)

(INTERCONNECTOR OR SERVICE

THIRD CABLE IF REQUIRED

BEF

OR

E

850

BEF

OR

E C

UT

TIN

G

700

200

300

200

400

100

(REAR VIEW)

TERMINAL BLOCKS

LINK

LINK

STREET MAINS

PVC POULTICE

P.V.C.

EARTH BAR

CONNECT TO

EARTH ROD

TOP OF

CU

TTIN

GLINKS (FRONT VIEW)

CONNECTION DIAGRAM

1 PHASE ONLY

PILLAR KIT

DOUBLE LINK

KEYED LINKS

REMOVABLE

EARTH BAR

G.L.

SHEATH CUT

TO ROADTO PROPERTY

STREET LIGHTS

SUPPLY TO

OR CUSTOMER

TRANSFORMER

TO RMU,

STREET MAINS

ON NEUTRAL SCREENS & OVER PHASE LUGS

2. FIT MASTIC LINED GLOVE TO ALL CABLES & SHRINK

AND 500mm FROM EDGE.

1. PILLAR TO BE CENTRED 500mm INSIDE BOUNDARY

NOTES:

EARTH ROD

TOP OF

TERMINAL LUGS VIEWED FROM PROPERTY

SHEATH CUT

850 FROM

TAIL LENGTHS

SHEATH CUT

700 FROM

TAIL LENGTHS

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

UDS UNIVERSAL PILLAR

DOUBLE LINK UNIT

ARRANGEMENT

REVISION DATE

DRAWING No.

B JUNE 2011

U10-2

DANGER

ELECTRICCABLES

WARNING : DO NOT BURY

ABOVE THIS LINE

SIDE ELEVATION

SECTION A-A

TOP VIEW

INDICATION ARROW

VIEW SHOWING

FRONT ELEVATION

WITH PILLAR SURFACE

BOLT TO BE FLUSH

TOP OF SECURITY

PVC Cu

25mm2 Gn/y

(IN 1 POSITION ONLY ON LID)

20 WIDE RAISED 1.5mm.

INDICATING ARROW TO BE

ONLY & AT 90 DEG TO SECURITY BOLTS

POSITIONS 180 DEG APART ON BASE SECTION

INDICATING ARROW TO BE LOCATED IN 2

COVER

SECURITY BOLT CL

255

500

APP

RO

X

345

20

25

10

(WITH COVER REMOVED)

10 HIGH LETTERING TO BE RAISED OR INDENTED 1.5mm

LOGO & 25mm LETTERING TO BE RAISED OR INDENTED 2mm.

INDICATOR LINE

GROUND LEVEL

LOGO : 40 x 25

SECURITY BOLTCL

A

A

CL

G.L.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

CABLE TO LV ISOLATORS

CROSSARM AND CABLE

DETAIL

REVISION DATE

DRAWING No.

B JUNE 2011

U15

ABC TAPS700

150

ABC TO CABLE TERMINATION

AND SPLICE

PG CLAMP

N B W R

ROADSIDE

(R7) CABLE GUARD

R3

(R7) CABLE CLEAT AND FITTINGS

R1

NOTE:

1. ALL HOLES 18 DIAMETER U.O.N.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

CABLE TO LV BARE INTERMEDIATE

DIRECT CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

U16-1

ABC TAPS

500

150

ABC TO CABLE TERMINATION

AND SPLICE

PG CLAMP

N B W R

ROADSIDE

(R7) CABLE GUARD

R3

(R7) CABLE CLEAT AND FITTINGS

R1

NOTE:

1. ALL HOLES 18 DIAMETER U.O.N.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

CABLE TO LV BARE TERMINATION

DIRECT CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

U16-2

ABC TAPS

500

150

ABC TO CABLE TERMINATION

CABLE CLEAT AND FITTINGS (R7)

AND SPLICE

PG CLAMP

CABLE GUARD (R7)

N B W RR3

R1

ROADSIDE

NOTE:

1. ALL HOLES 18 DIAMETER U.O.N.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

ABC FUSED CONNECTION TO CABLE

REVISION DATE

DRAWING No.

B JUNE 2011

U17

R1

R7

R8

ABC TO CABLE TERMINATION

(R7) CABLE CLEAT AND FITTINGS

(LV ONLY POLE)

TOP OF POLE

R8-3

(R7) CABLE GUARD AND FITTINGS

NOTE:

1. ALL HOLES 18 DIAMETER U.O.N.

(R1) 14 DIAMETER HOLES

4 CORE BUNDLED ABC

230

500

150

(R1) 14 DIAMETER HOLE

5000

NEUTRAL CONNECTION

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

25 SQ. mm CABLE TO ABC

DIRECT CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

U18

NOTE:

1. ALL HOLES 18 DIAMETER U.O.N.

500

150

HEAT SHRINK OVER CORES

HEAT SHRINK GLOVE

ABC IPC

(R7) CONDUIT SADDLE

FIXING DETAILS

(R7) CONDUIT UNDER CABLE GUARD

(R7) CABLE GUARD

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

25sqmm CABLE TO LV BARE INTERMEDIATE

DIRECT CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

U19-1

500

HEAT SHRINK GLOVE

OVER CORES

HEAT SHRINK

N B W RR3

R1

FIXING DETAILS

(R7) CONDUIT UNDER CABLE GUARD

(R7) CABLE GUARD

(R7) CONDUIT SADDLE

ROADSIDE

150

BI-METAL PG CLAMP

COPPER OR

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

25sqmm 4 CORE CABLE TO

1 PHASE OPEN AERIAL

REVISION DATE

DRAWING No.

B JUNE 2011

U19-2

500

HEAT SHRINK GLOVE

N R

R1

FIXING DETAILS

(R7) CONDUIT UNDER CABLE GUARD

(R7) CABLE GUARD

(R7) CONDUIT SADDLE

ROADSIDE

150

BI-METAL PG CLAMP

COPPER OR

BLUE CORES

BLACK AND

WHITE CORES

RED AND

WITH CABLE TIES

HELD TOGETHER

OVER CORES

HEAT SHRINK

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

TRANSFORMER POLE TO PILLAR

ON CUSTOMER PROPERTY

REVISION DATE

DRAWING No.

B JUNE 2011

U19-3

22

R7

LV CABLE ( 25mm - 185mm )

MINI/UNI PILLAR

G.L.

NOTES:

1000

750

150

SEE NOTES 1 & 2

500

AVAILABLE ON REQUEST).

3. CUSTOMER'S SPD TO GRADE WITH UPSTREAM PROTECTION (FUSE CURVE FOR UPSTREAM PROTECTION

2. TRANSFORMERS ABOVE 63kVA, FUSING TO BE INSTALLED IN THE PILLAR.

1. TRANSFORMERS 63kVA & SMALLER, FLOW LINE FUSE'S TO BE INSTALLED.

FITTING DETAILS

(R7) CABLE SADDLE/CLAMP

FIXING DETAILS

(R7) CONDUIT UNDER CABLE GUARD

(R7) CABLE GUARD

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

25sqmm CABLE TO LV BARE TERMINATION

DIRECT CONNECTION

REVISION DATE

DRAWING No.

B JUNE 2011

U19-4

500

HEAT SHRINK GLOVE

OVER CORES

HEAT SHRINK

(R7) CONDUIT SADDLE

150

ROADSIDE

N BR3 W R

FIXING DETAILS

(R7) CONDUIT UNDER CABLE GUARD

(R7) CABLE GUARD

BI-METAL PG CLAMP

COPPER OR

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

WALL MOUNTED BOX

100 AMP

REVISION DATE

DRAWING No.

B JUNE 2011

U20

N

300 175

370

2. MOUNTING HEIGHT MUST COMPLY WITH HORIZON POWER DESIGN REQUIREMENTS.

1. CUTOUT BOX ENCLOSURE MUST HAVE AN APPROVED HORIZON POWER LABEL.

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

WALL MOUNTED BOX

200 AMP

REVISION DATE

DRAWING No.

B JUNE 2011

U21

2. MOUNTING HEIGHT MUST COMPLY WITH HORIZON POWER DESIGN REQUIREMENTS.

1. CUTOUT BOX ENCLOSURE MUST HAVE AN APPROVED HORIZON POWER LABEL.

NOTES:

N

300 175

600

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

UNMETERED SUPPLY

CABLE PIT

COMPONENTS ASSEMBLY

REVISION DATE

DRAWING No.

B JUNE 2011

U23-1

DANGER ELECTRICITY

CUSTOMERSUPPLY

POWER

WHEN NOT IN ALLOTED ALIGNMENT

ORANGE 25O/DIA.

RIGID/CORRUGATED PVC CONDUIT

CABLE END

WITH 1M OF SHEATHING FROM

1.6M CABLE LAID INTO PIT

OVER CONDUCTORS

HEATSHRINK

CUSTOMER CABLE

DOUBLE INSULATED

CAT. No 563L2 OR SIMILAR.

CONNECTOR (2 SCREW) CLIPSAL

OVER CONDUCTOR

HEATSHRINK

MAIN POWER FUSE

LABEL 1

BLACK

RED

1 HOLE 27 DIA. ON CENTRE LINE

30A FUSE

ISOLATING POINT

POWER SUPPLY

LABEL 1

WIRING ARRANGEMENT

60

30

155

130

OF GEL WRAP SEAL AND SNAP SHUT

FIT NEUTRAL CONNECTOR IN CENTRE

CUSTOMER SIDE

OR SIMILAR.

25 DIA. CLIPSAL CAT NO 263/25

ADAPTOR (PLAIN TO SCREWED)

SEE NOTE 1

25 DIAMETER

PVC CORRUGATED CONDUIT

279C25 OR SIMILAR

25 DIA. CAT No

GLAND, CLIPSAL,

ABRADE SHEATH END

HEATSHRINK SLEEVE

MASTIC FILLED GLOVE

NOTES:

FOR DOUBLE INSULATION (REINFORCED INSULATION)

2. HEATSHRINK NOT REQUIRED FOR CABLE MEETING REQUIREMENTS

1. LID LIFTER AVAILABLE, RAMSET PART No. RCU013

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

UNMETERED SUPPLY

MINI PILLAR

TERMINATION DETAILS

REVISION DATE

DRAWING No.

B JUNE 2011

U23-2

R W B N

TO UMS/STREET LIGHT SUPPLY

WA

RNIN

G

SUPPLY

UNMETERED

UMS/STREET LIGHT SUPPLY

UMS/STREET LIGHT NEUTRAL

COVER

MOUNTING BOARD

TO ROAD CROSSING

FROM TEE JOINT

25mm SERVICE2

FROM TEE JOINT

SUPPLY FOR UMS/STREET LIGHT FUSE

UMS/STREET LIGHT FUSE WHERE REQUIRED

RED SPOT FUSECONNECTION LINK

37

87

(TO EARTH ROD)

EARTH

LABEL

ATTACH

RED

WHITE BACKGROUND

RED LETTERING ON

STOCK No. C20307

VIEW FROM STREET

VIEW FROM SIDE

LABEL DETAIL

CROSSING

TO ROAD

TERMINAL BLOCKS

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

LV KIOSK

TYPE 1

REVISION DATE

DRAWING No.

B JUNE 2011

U24

IN EACH DIAGRAM

EARTH SPEAR (2 OFF)

FRONT VIEW OF KIOSK

PLAN VIEW OF KIOSK FREESTANDING PLAN VIEW OF KIOSK IN RECESS

FRONT

750

750750

750

810

1400

750

600

FRONT

EARTH BAR

EARTH STAKE @ LESS THAN 10 OHM.

CABLE CLAMPS

U BOLT

TO EARTH GRID

(500 x 200 x 25)

CONCRETE SLABS

BUSBAR DETAILS

NOTES:

AND WHEN REQUIRED THE INSTALLATION OF THE FEEDER PILLAR

4. THE CUSTOMER IS RESPONSIBLE FOR THE FEEDER PILLAR RECESS IN THE WALL

OF 150mm, EARTH GRID TO BE CONNECTED AT EARTH BAR.

3. INSTALL EARTH GRID AROUND / IN FRONT OF KIOSK AT 750mm AND A DEPTH

2. REFER TO DCS REFERENCE R24 FOR KIOSK GENERAL ARRANGEMENT.

1. KIOSK NOT SUPPLIED WITH BUSBARS

SEE NOTE 3

BARE 70MM EARTH GRID

SEE NOTE 4

RECESS FOR PILLAR

EASEMENT

CABLE

GRID - 1 OHM MAX.

BARE 70MM Cu EARTH

R

W

BGROUND LINEGROUND LINE

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

LV KIOSK

TYPE 2

REVISION DATE

DRAWING No.

B JUNE 2011

U25

NOTES:

LV KIOSK TYPE 2 - DISTRICT SUBSTATION

FREESTANDINGIN 2HR FIRE RATED SUBSTATION

1m DEEP TRENCH

1600A

FGL

DISCONNECT

CUSTOMER

1600A

TRANSFORMERS

315/500/630/1000kVA

SEE NOTE 2

(500 x 200 x 25 THICK)

CONCRETE SLABS

1025

1600

1300

SUBSTATION

FLOOR OF

400 DEEP

MD METER

COVER

CABLE TERMINATION

DISCONNECT

1600A TRANSFORMER

FUSEWAYS

400/630A

DISCONNECT

1600A CUSTOMER

COVER

CABLE TERMINATION

3. APPROX MAXIMUM WEIGHT WITH 5 FUSEWAYS AND 2 DISCONNECTORS IS 240kg

4 x 10mm RAWLNUTS AND 4 x 10mm BOLTS x 75 LONG.

KIOSK BOLTED TO SUBSTATION WALL ABOVE THE TRENCH WITH

2. DRILL 4-HOLES 12 DIAMETER THRU REINFORCED SECTIONS.

1. REFER TO DCS REFERENCE R24 FOR KIOSK GENERAL ARRANGEMENT.

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

LV KIOSK

TYPE 3

REVISION DATE

DRAWING No.

B JUNE 2011

U26

NOTES:

LV KIOSK TYPE 3 - DISTRICT SUBSTATION

IN 2HR FIRE RATED SUBSTATION FREESTANDING

3. APPROX MAXIMUM WEIGHT WITH 5 FUSEWAYS AND 2 DISCONNECTORS IS 350kg

6 x 10mm RAWLNUTS AND 6 x 10mm BOLTS x 75 LONG.

KIOSK BOLTED TO SUBSTATION WALL ABOVE THE TRENCH WITH

2. DRILL 6-HOLES 12 DIAMETER THRU REINFORCED POINTS AS SHOWN.

1. REFER TO DCS REFERENCE R24 FOR KIOSK GENERAL ARRANGEMENT.

1m DEEP TRENCH

SUBSTATION

FLOOR OF

400 DEEP

SEE NOTE 2

(500 x 200 x 25 THICK)

CONCRETE SLABS

FGL

2200

1025

1600

TRANSFORMERS

2 x 1000kVA

DISCONNECT

TRANSFORMER

1600A

DISCONNECT

CUSTOMER

2000A

- UNITS

UP TO 4-400/630A FUSE

MD METER

DISCONNECT

2000A CUSTOMER

COVER

CABLE TERMINATION

COVER

CABLE TERMINATION

DISCONNECT

1600A TRANSFORMER

DISCONNECT

TRANSFORMER

1600A

FUSE - UNITS

UP TO 4-400/630A

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

SUBSTATION REFERENCE

LV CABLE TO FUSE SWITCH

REVISION DATE

DRAWING No.

B JUNE 2011

U27

TERMINATION PROCEDURE

SAFETY INSTRUCTION

400

STRIP

N

R

W

B

B

R

W

RE

AR

OF C

UBIC

LE

4 WAY GLOVE

HEAT SHRINK

15. LABEL CIRCUIT.

PROVIDED.

LUGS TO CONNECTORS USING BOLTS

14. ENSURE PHASING IS CORRECT, THEN BOLT

LUGS AND CONNECTIONS.

13. APPLY JOINTING COMPOUND TO PALMS OF

EACH LUG TO SEAL LUG AND CORE.

12. FIT 100mm LENGTH OF HEATSHRINK OVER

CORES.

11. FIT AND CRIMP SECTOR LUGS TO PHASE

FRONT.

THE BACK OF THE UNIT TO BLUE AT THE

POSITIONS, STARTING WITH RED PHASE AT

10. SET PHASE CORES TO FINAL TERMINATING

9. BOLT NEUTRAL TO NEUTRAL BAR.

WITH HEATSHRINK.

APPROPRIATE SIZE LUG. COVER EXPOSED LUG

TO NEUTRAL BAR, CUT AND CRIMP

8. SHAPE NEUTRAL CORE TO SUIT CONNECTION

REQUIRED LENGTH AND HEATSHRINK.

7. FIT BLACK HEATSHRINK OVER NEUTRAL FOR

STARTING FROM CENTRE.

INTO CRUTCH AREA AND HEATSHRINK

6. FIT HEATSHRINK GLOVE, PULL WELL DOWN

100mm.

5. ABRADE CABLE SHEATH FOR APPROXIMATELY

ONE CORE AT THE BACK OF THE CABLE.

4. BRING OUT NEUTRAL WIRES AND FORM INTO

3. REMOVE SHEATH ABOVE THIS MARK.

OF FUSE UNIT.

2. MARK SHEATH, CUT 600mm BELOW BOTTOM

CIRCUIT ON THE LV DISTRIBUTION BOARD.

1. POSITION THE CABLE TO SUIT THE CORRECT

TERMINATED OR MADE OFF BEFORE WORK COMMENCES AT THE FUSE SWITCH.

THE CABLE TO BE WORKED ON MUST BE DEAD AND THE REMOTE END MUST BE

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

BELOW GROUND SERVICE

PIT INSTALLATION DETAIL

REVISION DATE

DRAWING No.

B JUNE 2011

U30-1

EXTENDED TO FINISHED G.L.

CONCRETE COLLAR MAYBE

LOCKED IN PLACE TO FULLY SEAL.

THE TERMINAL CAPS MUST BE

8mm "ALLEN" KEY DRIVE TERMINAL SCREW.

CC0846

STOCK No

2 Finger glove

4 Finger glove

6mm2

Heatshrink tubing

10-25mm2

Heatshrink tubing

Raychem part no.

HP stock

Raychem part no.

HP stock

RED WHITE BLUE BLACK

COLOUR CODEDESCRIPTION

N/A 302K333-23/239(S20)

FE0032

FE0031

502K033-53/239(S15)

FE0105

RNF100 3/8'' Bk

FE0071

RNF100 1/2'' BkRNF100 1/2'' Bl

FE0104

RNF100 3/8'' Bl

FE0108FE0107

RNF100 3/8'' Wh

FE0103

RNF100 1/2'' WhRNF100 1/2'' Rd

FE0102

RNF100 3/8'' Rd

FE0106

STOCK No HL0360

CORES INTO CONNECTOR THRU GEL

PRE STRIPPED HEATSHRINK

FINISHED G.L.

GLOVE

MASTIC FILLED

SHEATH

Raychem part no.

HP stock

Raychem part no.

HP stock

N/A N/A

IN CONRETE LID CENTRE

RECESSED LIFTING BOLT WITH FLUSH MOUNTED CAP

UNDER LIDINSULATED DISC

8mm "ALLEN KEY SCREW CAP

CORE ENTRY

BELOW LOWER NECK OF PIT

EARTH ELECTRODE TO BE INSTALLED

SLEEVE

HEATSHRINK

NOTES:

USAGE OR POOR SOIL/SAND COMPOSITION.

6. CONCRETE COLLAR MAYBE REQUIRED FOR EXCESSIVE LOAD

FOR DOUBLE INSULATION (REINFORCED INSULATION).

5. HEATSHRINK NOT REQUIRED FOR CABLES MEETING REQUIREMENTS

CONNECTION LENGTH (SEE CONNECTOR).

4. STRIP HEATSHRINK & INSULATION FROM CORES TO REQUIRED

3. FIT GLOVE OVER CORES & CABLE THEN SHRINK TO FIT.

2. APPLY HEATSHRINK FULL LENGTH OVER CORES.

CROWDING.

1. CORE LENGTH SHOULD BE LIMITED TO 500mm TO AVOID OVER

SEE NOTE 6

WITH DRAWING U30-2

WHEN READ IN-CONJUNCTION

THIS DRAWING IS VALID ONLY

ROD STOCK No CE0300

13mm DIAMETER EARTH

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

BELOW GROUND SERVICE

PIT INSTALLATION DETAIL

REVISION DATE

DRAWING No.

B JUNE 2011

U30-2 A FIRST REVISION

B

REV DESCRIPTION

MINOR AESTHETICS REVISED

NOTES:

APPLICATION GUIDELINE

� THE PIT SHALL BE ACCESSIBLE FROM THE ROADWAY BOUNDARY

� THIS INFRASTRUCTURE SHALL COVER A MINIMUM OF 1m SQUARE, AND

THE PIT CANNOT BE BURIED, AND

� FINISHED GROUND LEVEL SHALL BE OF FIXED INFRASTRUCTURE, i.e. CONCRETE, PAVING OR OTHER WHERE

AS THE TOP OF THE CONCRETE LID, AND

� THE PIT SHALL BE LOCATED IN AN AREA SUCH THAT THE FINISHED GROUND LEVEL IS AT THE SAME HEIGHT

BELOW GROUND SERVICE PITS MAY BE INSTALLED UNDER THE FOLLOWING CONDITIONS

FURTHER DETAILS ARE AVAILABLE FROM DMS# 2074582

IS NOT DESIRABLE AND SHALL BE UNDERTAKEN WITHIN THE FOLLOWING GUIDELINE.

THE BELOW GROUND SERVICE PIT HAS BEEN DEVELOPED FOR USE IN AREAS IN WHICH A MINI-PILLAR LOCATION

CAUTION WHEN APPLYING HEATSHRINK TO AVOID DAMAGE TO GEL AREA.

PROTRUDING OUT OF GELPORT THEN CAP WITH HEATSHRINK.

10. PERMANENT DISCONNECTION - DO NOT REMOVE CABLE FROM PORT. CUT CABLE TO LEAVE APPROX 50mm

ANY ONE PORT.

MARK PORT WITH ONE SCRIBE FOR EACH DISCONNECTION. REPLACE CONNECTOR AFTER 3 DISCONNECTS FOR

9. TEMPORARY DISCONNECTION - COVER CABLE PORT WITH BLUE CAP OR TAPE TO AVOID GEL CONTAMINATION.

THE CABLE AS IT IS REMOVED.

8. WHEN DISCONNECTING CABLE FROM CONNECTOR REMOVE SLOWLY TO ALLOW GEL TO RE-SEAL ITSELF BEHIND

7. AFTER CLAMPING CABLE THE CLAMP CAP MUST BE LOCKED IN PLACE TO FULLY SEAL

LOOSE/OUT OF THE TERMINAL BLOCK

6. UPON TIGHTENING THE CLAMPING BOLT, GIVE THE CORE A SWIFT TUG TO ENSURE THAT IT DOES NOT COME

� 67.4 TO 180sqmm CONDUCTOR ---- 31.1 TO 39.5Nm TORQUE

� 21.1 TO 53.5sqmm CONDUCTOR ---- 25.4 TO 31.1Nm TORQUE

� 4 TO 15sqmm CONDUCTOR ---- 14.1 TO 19.8Nm TORQUE

THE RECOMMENDED TORQUE SETTINGS ARE LISTED BELOW IF TORQUE WRENCHES ARE USED.

WHILE TIGHTENING THE CLAMPING BOLT WITH A 8mm ALLEN KEY DRIVE.

5. INSERT THE STRIPPED CORE GENTLY THRU THE GEL AND HOLD IT FULLY HOME AGAINST THE TERMINAL BLOCK

4. WIPE CLEAN THE STRIPPED CORE AND ENSURE IT IS NOT CONTAMINATED WITH SAND, GREASE, etc.

3. STRIP INSULATION/HEATSHRINK FROM CORE END. SEE CONNECTOR FOR STRIP LENGTH.

2. DOUBLE INSULATION IS TO BE MAINTAINED INTO CONNECTOR GEL

1. DUST CAPS MUST BE LEFT ON ANY UNUSED CONNECTOR CABLE ENTRY TO AVOID GEL CONTAMINATION.

NOTES:

STANDARDS

DISTRIBUTION CONSTRUCTION

OPERATIONS

STRUCTURE

PILLAR EXCLUSION ZONES

REVISION DATE

DRAWING No.

A 24/08/15

U35

UTILITY SERVICE PROVIDERS CODE OF PRACTICE.

WHERE THERE IS A FRONT RETAINING WALL LESS THAN 1.1m IN HEIGHT, REFER TO ADDENDUM 1 OF THE 3.

SAME ZONES APPLY TO BOTH UNI-PILLARS AND MINI-PILLARS.2.

RADIUS SHALL BE MEASURED FROM CENTRE POINT OF PILLAR.1.

PILLAR EXCLUSION ZONES

EXCLUSION ZONE FOR FENCES(FOR BOTH MINI-PILLARS AND UNI-PILLARS)

1000

1000

500

500

PROPERTY BOUNDARY

PROPERTY BOUNDARY

EXCLUSION ZONE

PROPERTY BOUNDARY

STORMWATER EXCLUSION ZONE R600mm

EXCLUSION ZONE R500mm