Cables Part 1 Industrial & Domestic Cables Part 2 Fireres Cables

Transcript of Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings...

Page 1: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

CablesPart 1 Industrial & Domestic Cables

Part 2 Fireres Cables

Page 2: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Brief Introduction

Page 3: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

MAS Cables Limited is a subsidiary of Michelle Electrical Supplies (Hong Kong) Ltd. who has served Hong

Kong over twenty years since it established in 1981. In order to expand our services and take care our customers

the uttermost, MAS Cables was born to meet increasingly demand in building services. Our professional

staff plus our manufacturers with advanced technology and equipment will have a new look in the field.

This brochure covers the range of standard general wiring & power low voltage cables (Rated voltage <1000Volt)

used in building services, including conduit wirings, surface wirings, power cables, flexible cords and fire-

resistant cables. Another types of special cables such as high voltages cables ( Rated voltage up to 35kV),

rubber sheathed flexible cables, prefabricated branch cables, control cables, welding cables, mining cables,

oil pump cables & shipboard cables, etc. can be manufactured and where a project requires cables with special

properties or characteristics also consult with our experts.

MAS Cables has been accredited with global standards by SEV while our manufacturers also obtained DNV,

CNAB, CCC and certificates of ISO9001: 2000, ISO14001 : 1996 and OHSMS18001 : 2001.

We stick to the spirits is that we are committed to delivering the service you need . We will do our utmost to

give you the high “quality products you want, at the right time with real value for money.”

R

R

Page 4: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

CONTENTS

6491X 450/750V 1/C Cu/PVCConduit

Wirings

6491LSOH 450/750V 1/C Cu/LSOH

6181Y 600/1000V 1/C Cu/PVC/PVC

Surface

Wirings/

Power

Cables

6U81S 600/1000V 1/C Cu/XLPE/PVC

6U81LSOH 600/1000V 1/C Cu/XLPE/LSOH

Flexible

Cords3183Y 300/500V 3/C Cu/PVC/PVC

6941XL 600/1000V 1/C Cu/XLPE/PVC/AWA/PVC

6942XL 600/1000V 2/C Cu/XLPE/PVC/SWA/PVC

6943XL 600/1000V 3/C Cu/XLPE/PVC/SWA/PVC

6944XL 600/1000V 4/C Cu/XLPE/PVC/SWA/PVCXLPE

Armoured

Power

Cables 694nXL 600/1000V n/C Cu/XLPE/PVC/SWA/PVC

6941XLSOH 600/1000V 1/C Cu/XLPE/LSOH/AWA/LSOH

6942XLSOH 600/1000V 2/C Cu/XLPE/LSOH/SWA/LSOH

6943XLSOH 600/1000V 3/C Cu/XLPE/LSOH/SWA/LSOH

6944XLSOH 600/1000V 4/C Cu/XLPE/LSOH/SWA/LSOH

694nXLSOH 600/1000V n/C Cu/XLPE/LSOH/SWA/LSOH

Part 1 Industrial & Domestic Cables

P8

P9

P10

P11

P12

P13

P14

P15

P16

P17

P18

P19

P20

P21

P22

P23

PageConstructionCable Ref.Types

Page 5: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

FR1C 600/1000V 1/C Cu/FR/LSOHConduitWirings

FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH

600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH

FireResistant

XLPE

Armoured

Power

Cables

6943XFR 600/1000V 3/C Cu/FR/XLPE/LSOH/SWA/LSOH

6944XFR 600/1000V 4/C Cu/FR/XLPE/LSOH/SWA/LSOH

694nXFR 600/1000V n/C Cu/FR/XLPE/LSOH/SWA/LSOH

6942XFR

Part 2 Fireres Cables

P26

P27

P28

P29

P30

P31

P32Approvals

Technical References P33

P34-51Technical Information

PageConstructionCable Ref.Types

PowerCable

Page 6: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire
Page 7: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Part 1 Industrial & Domestic Cables

Page 8: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Conduit Wiring

Ref. 6491X - PVC Insulated Non Sheathed Single Core Cables

Standards: 60227 IEC01 of IEC60227-3 & IEC60332-1

Construction: Single core, solid or stranded plain annealedcopper conductor, PVC insulated.( In short form : 1/C Cu/PVC )

Voltage Rating: 450/750 Volts

Application: Suitable for use in conduit , trunking and fixed protectedinstallation in or on light fittings and inside appliances,switchgear and controlgear under normal temperature

Standard Colour: Red, Yellow, Blue, Black, Green/Yellow, Brown, Grey,Orange or White.

Approvals : SEV, CB & CENELEC

Harmonized Code: Solid Conductor-H07V-UStranded Conductor-H07V-R

Max. ConductorTemperature: 70o C

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes but 100m available for 1.5mm2 to 25mm2 only

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4D1A / 4D1B

8

6181

Y

MA

S

1. Copper Conductor(Solid / Stranded)

2. PVC Insulation

1

CA

BLE

MA

RK

ING

SA

MP

LE

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. Conductor

Resistance

at 20OC

Min. Insulation

Resistance

at 70O C

Calculated

Cable

Weight

( mm2 ) ( mm ) ( mm ) ( / km ) ( M

/ km ) ( kg / km )

1.5 1 0.7 3.3 12.10 0.0110 24

1.5 2 0.7 3.4 12.10 0.0100 25

2.5 1 0.8 3.9 7.41 0.0100 37

2.5 2 0.8 4.2 7.41 0.0090 39

4 2 0.8 4.8 4.61 0.0077 57

6 2 0.8 5.4 3.08 0.0065 79

10 2 1.0 6.8 1.83 0.0065 129

16 2 1.0 8.0 1.15 0.0050 195

25 2 1.2 9.8 0.73 0.0050 300

35 2 1.2 11.0 0.52 0.0040 404

50 2 1.4 13.0 0.39 0.0045 572

70 2 1.4 15.0 0.27 0.0035 787

95 2 1.6 17.0 0.19 0.0035 1049

120 2 1.6 19.0 0.15 0.0032 1320

150 2 1.8 21.0 0.12 0.0032 1638

185 2 2.0 23.5 0.10 0.0032 2030

240 2 2.2 26.5 0.08 0.0032 2617

300 2 2.4 29.5 0.06 0.0030 3263

400 2 2.6 33.5 0.05 0.0028 4305

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

264

91X

MA

SR

6491X 450 / 750V

1X4 S

Q M

M C

U / P

VC

IEC

60227-3 60227 IEC

01 CB

CE

NE

LEC

MA

DE

IN C

HIN

AS

EV

MA

SR

www.mes.com.hk

Page 9: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Conduit Wiring

Ref. 6491LSOH - Low Smoke Zero Halogen (LSOH) Insulated Non Sheathed

Single Core Cables

Standards: Modified IEC60502-1 for construction,IEC61034, IEC60754 & IEC60332-1

Construction: Single core, solid or stranded plain annealedcopper conductor, LSOH insulated.( In short form : 1/C Cu/LSOH)

Voltage Rating: 450/750 Volts

Application: Suitable for use in conduit , trunking and fixed protectedinstallation in or on light fittings and inside appliances,switchgear and controlgear under normal temperature

Standard Colour: Red, Yellow, Blue, Black, Green/Yellow, Brown or Grey

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

1. Copper Conductor(Solid / Stranded)

2. LSOH Insulation

2

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. Conductor

Resistance

at 20OC

Min. Insulation

Resistance

at 90O C

Calculated

Cable

Weight

* Conductor Class based on IEC60228

* Standard Packing: 500m for all above cable sizes but 100m available for 1.5 mm2 to 16mm2 only

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E1A / 4E1B

( mm2 ) ( mm ) ( mm ) (

/ km ) ( M

/km ) ( kg / km )

1.5 1 0.7 3.2 12.10 0.0110 21

1.5 2 0.7 3.3 12.10 0.0100 22

2.5 1 0.8 3.9 7.41 0.0100 33

2.5 2 0.8 4.0 7.41 0.0090 35

4 2 0.8 4.5 4.61 0.0077 48

6 2 0.8 5.1 3.08 0.0065 68

10 2 0.9 6.2 1.83 0.0065 110

16 2 0.9 7.2 1.15 0.0050 167

25 2 1.1 9.0 0.73 0.0050 259

35 2 1.1 10.2 0.52 0.0040 356

50 2 1.2 12.0 0.39 0.0045 562

70 2 1.3 14.0 0.27 0.0035 694

95 2 1.3 15.6 0.19 0.0035 929

120 2 1.4 17.5 0.15 0.0032 1170

150 2 1.6 20.0 0.12 0.0032 1463

185 2 1.9 22.0 0.10 0.0032 1815

240 2 2.0 25.0 0.08 0.0032 2341

300 2 2.1 27.3 0.06 0.0030 2906

400 2 2.3 31.3 0.05 0.0028 3864

6491

LSOH

MA

SR

1

Industrial & Domestic CablesCablesMAS R

CA

BLE

MA

RK

ING

SA

MP

LE

MA

SR

9 www.mes.com.hk

6491LS

OH

450 / 750V 1X

1.5 SQ

MM

CU

/ LS

OH

IEC

60502-1 / IEC

61034 / IEC

60754 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

Page 10: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Surface Wiring

Ref. 6181Y - PVC Insulated and PVC Sheathed Single Core Cables

Standards: IEC60502-1 & IEC60332-1

Construction: Single core, solid or stranded plain annealedcopper conductor, PVC insulated and PVC sheathed.( In short form : 1/C Cu/PVC/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic and light industrial wiring.Suitable for mounting to surface or on trays in free airor embedded in plaster.

Core Colour: Brown, Blue, Grey, Black, or other colours upon request

Sheath Colour: White, Grey or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 70o C

1. Copper Conductor(Solid / Stranded)

2. PVC Insulation

3. PVC Sheath

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Calculated

Cable

Weight

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes but 100m available for 1.5mm2 to 25mm2 only

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4D1A / 4D1B

6181

Y

( mm2 ) ( mm ) ( mm ) ( mm ) ( M

/ km ) ( kg / km )

1.5 1 0.8 1.4 6.6 12.10 51

2.5 1 0.8 1.4 7.0 7.41 64

4 2 1.0 1.4 7.9 4.61 89

6 2 1.0 1.4 8.4 3.08 113

10 2 1.0 1.4 9.7 1.83 158

16 2 1.0 1.4 10.7 1.15 221

25 2 1.2 1.4 12.0 0.73 324

35 2 1.2 1.4 12.9 0.52 428

Mean Overall

Diameter

Max. Conductor

Resistance

at 20OC

Sheath

Thickness

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

1

2

MA

SR

CA

BLE

MA

RK

ING

SA

MP

LE

6181Y 600 / 1000V

1X16 S

Q M

M C

U / P

VC

/ PV

C IE

C60502-1 C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

3

10

MA

SR

www.mes.com.hk

Page 11: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

1

Surface Power CablesRef. 6U81S - XLPE Insulated and PVC Sheathed Single Core Cables

Standards: IEC60502-1 & IEC60332-1

Construction: Single core, stranded plain annealed copperconductor, XLPE insulated and PVC sheathed.( In short form : 1/C Cu/XLPE/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free airor embedded in plaster.

Core Colour : Brown, Blue, Grey, Black or other colours upon request

Sheath Colour : White, Grey, Black, Red or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

1. Copper Conductor2. XLPE Insulation3. PVC Sheath

6U81

S

MA

SR

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. DC

Resistance

at 20OC

Calculated

Cable

Weight

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E1A / 4E1B

Sheath

Thickness

( mm2 ) ( mm ) ( mm ) ( mm ) ( M

/ km ) ( kg / km )

50 2 1.0 1.4 14.0 0.39 551

70 2 1.1 1.4 16.0 0.27 748

95 2 1.1 1.5 17.7 0.19 993

120 2 1.2 1.5 20.0 0.15 1242

150 2 1.4 1.6 21.7 0.12 1544

185 2 1.6 1.6 24.0 0.10 1895

240 2 1.7 1.7 26.8 0.08 2435

300 2 1.8 1.8 29.4 0.06 3015

400 2 2.0 1.9 33.5 0.05 3994

500 2 2.2 2.0 37.0 0.037 4966

630 2 2.4 2.2 41.2 0.028 6226

800 2 2.6 2.3 46.0 0.022 7867

1000 2 2.8 2.4 51.0 0.018 9793

Industrial & Domestic CablesCablesMAS R

3

2

1

CA

BLE

MA

RK

ING

SA

MP

LE

6U81S

600 / 1000V 1X

50 SQ

MM

CU

/ XL

PE

/ PV

C IE

C60502-1 C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

11

MA

SR

www.mes.com.hk

Page 12: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Surface Power Cables

Ref. 6U81LSOH - XLPE Insulated and LSOH Sheathed Single Core Cables

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Single core, stranded plain annealed copperconductor, XLPE insulated and LSOH sheathed.( In short form : 1/C Cu/XLPE/LSOH)

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free airor embedded in plaster.

Core Colour : Brown, Blue, Grey, Black or other colours upon request

Sheath Colour : White, Grey, Black, Red or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

1. Copper Conductor

2. XLPE Insulation

3. LSOH Sheath

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E1A / 4E1B

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. DC

Resistance

at 20OC

Calculated

Cable

Weight

( mm2 ) ( mm ) ( mm ) ( mm ) ( M /km ) ( kg/km )

16 2 0.7 1.4 9.6 1.15 205

25 2 0.9 1.4 11.2 0.73 302

35 2 0.9 1.4 12.4 0.52 403

50 2 1.0 1.4 14.0 0.39 554

70 2 1.1 1.4 16.0 0.27 752

95 2 1.1 1.5 17.7 0.19 997

120 2 1.2 1.5 20.0 0.15 1248

150 2 1.4 1.6 21.7 0.12 1550

185 2 1.6 1.6 24.0 0.10 1902

240 2 1.7 1.7 26.8 0.08 2443

300 2 1.8 1.8 29.4 0.06 3025

400 2 2.0 1.9 33.5 0.05 4006

500 2 2.2 2.0 37.0 0.037 4980

630 2 2.4 2.2 41.2 0.028 6243

800 2 2.6 2.3 46.0 0.022 7886

1000 2 2.8 2.4 51.0 0.018 9816

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

3

1

6U81

LSOH

CA

BLE

MA

RK

ING

SA

MP

LE

6U81L

SO

H 600 / 1000V

1X50 S

Q M

M C

U / X

LP

E / L

SO

H IE

C60502-1 C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

Sheath

Thickness

2

MA

SR

12

MA

SR

www.mes.com.hk

Page 13: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Flexible CordsRef. 3183Y - PVC Insulated and PVC Sheathed Three Core Flexible Cords

Standards: 60227 IEC53 of IEC60227-5 & IEC60332-1

Construction: Three core, flexible plain annealed copper conductor,PVC insulated with cores laid up and PVC sheathedcircular flexible cords.( In short form : 3/C Cu/PVC/PVC)

Voltage Rating: 300/500 Volts

Application: General use in indoors or outdoors in dry or dampconditions. Suitable use in machine tools, power tools,portable tools and appliances.Not recommended in contact with hot surfaces andused under low temperatures.

Core Colour : Green/Yellow, Blue and Brown

Sheath Colour : White, Grey or Black

Approvals : SEV, CB & CENELEC

Harmonized Code: H05VV-F

Max. ConductorTemperature: 70o C

1. Copper Conductor2. PVC Insulation3. PVC Sheath

No.of Core xNominal Section

Area ofConductor

Conductor

Class

Insulation

Thickness

Mean Overall Diameter Max. DC

Resistance

at 20OC

Calculated

Cable

Weight

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( / km ) ( kg / km )

3 x 0.75 5 0.6 0.8 6.4 8.0 0.011 71

3 x 1.0 5 0.6 0.8 6.8 8.4 0.010 82

3 x 1.5 5 0.7 0.9 8.0 9.8 0.010 116

3 x 2.5 5 0.8 1.1 9.6 12.0 0.009 174

Lower Limit Upper Limit

* Conductor Class based on IEC60228

* Standard Packing: 100m for all above cable sizes only

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4H3A / 4H3B

Industrial & Domestic CablesCablesMAS R

1

CA

BLE

MA

RK

ING

SA

MP

LE

MA

SR

Sheath

Thickness

3

2

3183

Y

13 www.mes.com.hk

MA

SR

3183Y 300 / 500V

3X0.75 S

Q M

M C

U / P

VC

/ PV

C 60227 IE

C53 H

05VV

-F C

B C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

Page 14: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 6941XL - XLPE Insulated and Double PVC Sheathed with Aluminium Wire

Armour (AWA) Single Core Power Cables

Standards: IEC60502-1

Construction: Single core, stranded plain annealed copperXLPE insulated, PVC inner sheathed, AWA andPVC outer sheathed.( In short form : 1/C Cu/XLPE/PVC/AWA/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free air,use in ducts or direct burial in ground.

Core Colour : Brown, Black, Blue, Grey or Red

Inner SheathColour : Black

Outer SheathColour: Black or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

Nominal Section

Area of

Conductor

Insulation

Thickness

Mean

Overall

Diameter

Max. DC

Resistance

at 20OC

Calculated

Cable

Weight

InnerSheath

Thickness

Approx.Diameter

UnderArmour

AWADiameter

OuterSheath

Thickness

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( mm ) ( mm ) (

/ km ) ( kg / km )

50 1.0 1.0 13.0 0.9 1.8 19.5 0.39 806

70 1.1 1.0 14.5 1.25 1.8 21.5 0.27 1030

95 1.1 1.0 16.5 1.25 1.8 24.5 0.19 1298

120 1.2 1.0 18.0 1.25 1.8 25.5 0.15 1570

150 1.4 1.0 20.0 1.60 1.8 27.5 0.12 1965

185 1.6 1.0 22.0 1.60 1.9 29.5 0.10 2372

240 1.7 1.0 24.5 1.60 2.0 33.0 0.08 2950

300 1.8 1.0 27.0 1.60 2.1 36.5 0.06 3580

400 2.0 1.2 30.5 2.00 2.2 40.5 0.05 4782

500 2.2 1.2 34.5 2.00 2.3 44.0 0.037 5828

630 2.4 1.2 38.0 2.00 2.5 49.5 0.028 7192

800 2.6 1.4 46.0 2.50 2.6 54.0 0.022 9174

1000 2.8 1.4 51.0 2.50 2.7 59.0 0.018 11217

* Stranded copper conductor based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E3A / 4E3B

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

6

1. Conductor

2. XLPE Insulation

3. PVC Inner Sheath

4. Aluminium Wire Armour

5. PVC Outer Sheath

1

2

4

3

5

CA

BLE

MA

RK

ING

SA

MP

LE

MA

SR

6941

XL

MA

SR

www.mes.com.hk14

6941XL 600 / 1000V

1X50 S

Q M

M C

U / X

LP

E / P

VC

/ AW

A / P

VC

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

Page 15: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power Cables

Ref. 6942XL - XLPE Insulated and Double PVC Sheathed with Steel Wire

Armour(SWA) Two Core Power Cables

Standards: IEC60502-1

Construction: Stranded plain annealed copper conductors,XLPE insulated, two cores laid up, extruded PVC bedding,galvanized steel wire armoured and PVC outer sheathed.( In short form : 2/C Cu/XLPE/PVC/SWA/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free air,use in ducts or direct burial in ground.

Core Colour: Red & Black, or Brown & Blue

Inner SheathColour: Black

Outer SheathColour: Black or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. PVC Inner Sheath

6. Steel Wire Armour

7. PVC Outer Sheath

On perf. cabletray or free air

ClippedDirect

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg / km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

2 x 1.5 0.7 7.6 0.90 12.8 312 12.10 27 29 31.00

2 x 2.5 0.7 8.4 0.90 13.6 356 7.41 36 39 19.00

2 x 4 0.7 9.4 0.90 14.6 416 4.61 49 52 12.00

2 x 6 0.7 10.4 0.90 15.6 484 3.08 62 66 7.90

2 x 10 0.7 12.0 1.25 18.1 772 1.83 85 90 4.70

2 x 16 0.7 13.8 1.25 19.9 958 1.15 110 115 2.90

2 x 25 0.9 16.8 1.60 23.6 1434 0.73 146 152 1.85

2 x 35 0.9 19.0 1.60 25.8 1731 0.52 180 188 1.35

2 x 50 1.0 22.0 1.60 29.0 2175 0.39 219 228 0.98

2 x 70 1.1 25.2 2.00 33.2 3023 0.27 279 291 0.67

2 x 95 1.1 28.8 2.00 37.1 3739 0.19 338 354 0.49

2 x 120 1.2 32.0 2.00 40.5 4427 0.15 392 410 0.39

2 x 150 1.4 35.6 2.00 44.4 5246 0.12 451 472 0.31

2 x 185 1.6 39.8 2.50 49.9 6793 0.10 515 539 0.25

2 x 240 1.7 44.6 2.50 55.1 8229 0.08 607 636 0.20

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesCablesMAS R

1

2

3

5

7

CA

BLE

MA

RK

ING

SA

MP

LE

6942XL 600 / 1000V

2X1.5 S

Q M

M C

U / X

LP

E / P

VC

/ SW

A / P

VC

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

6

4

MA

SR

www.mes.com.hk15

6942

XL

MA

SR

Page 16: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 6943XL - XLPE Insulated and Double PVC Sheathed with

Steel Wire Armour (SWA) Three Core Power Cables

Standards: IEC60502-1

Construction: Stranded plain annealed copper conductors, XLPEinsulated, three cores laid up, extruded PVC bedding,galvanized steel wire armoured and PVC outer sheathed.( In short form : 3/C Cu/XLPE/PVC/SWA/PVC)

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free air,use in ducts or direct burial in ground.

Core Colour: Red , Yellow & Blue, or Brown, Black & Grey

Inner SheathColour: Black

Outer SheathColour: Black or other colours upon request

Approvals : SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90o C

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. PVC Inner Sheath

6. Steel Wire Armour

7. PVC Outer Sheath

On perf. cabletray or free air

ClippedDirect

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

3 x 1.5 0.7 8.0 0.90 13.2 344 12.10 23 25 27.00

3 x 2.5 0.7 8.9 0.90 14.1 400 7.41 31 33 16.00

3 x 4 0.7 10.0 0.90 15.2 476 4.61 42 44 10.00

3 x 6 0.7 11.1 0.90 17.2 720 3.08 53 56 6.80

3 x 10 0.7 12.8 1.25 18.9 905 1.83 73 78 4.00

3 x 16 0.7 14.7 1.25 20.8 1152 1.15 94 99 2.50

3 x 25 0.9 18.0 1.60 24.8 1735 0.73 124 131 1.65

3 x 35 0.9 20.4 1.60 27.2 2137 0.52 154 162 1.15

3 x 50 1.0 23.6 1.60 30.7 2740 0.39 187 197 0.87

3 x 70 1.1 27.5 2.00 35.7 3849 0.27 238 251 0.60

3 x 95 1.1 30.9 2.00 39.4 4776 0.19 289 304 0.45

3 x 120 1.2 34.4 2.00 43.1 5719 0.15 335 353 0.37

3 x 150 1.4 38.7 2.50 48.7 7443 0.12 386 406 0.30

3 x 185 1.6 42.8 2.50 53.1 8785 0.10 441 463 0.26

3 x 240 1.7 47.9 2.50 58.7 10773 0.08 520 546 0.21

3 x 300 1.8 53.1 2.50 64.2 12915 0.06 599 628 0.19

3 x 400 2.0 60.7 3.15 73.6 17504 0.05 673 728 0.17

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 300mm2 and 400m only for cable size 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

2

3

5

6

7

CA

BLE

MA

RK

ING

SA

MP

LE

6943XL 600 / 1000V

3X50 S

Q M

M C

U / X

LP

E / P

VC

/ SW

A / P

VC

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

VM

AS

R

1

4

6943XL

MA

SR

16 www.mes.com.hk

Page 17: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 6944XL - XLPE Insulated and Double PVC Sheathed with Steel Wire Armour

(SWA) Four Core Power Cables

Standards: IEC60502-1

Construction: Stranded plain annealed copper conductors, XLPEinsulated, four cores laid up, extruded PVC bedding,galvanized steel wire armoured and PVC outer sheathed.( In short form : 4/C Cu/XLPE/PVC/SWA/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free air,use in ducts or direct burial in ground.

Core Colour : Red , Yellow , Blue & Black, or Brown, Black,Grey & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. PVC Inner Sheath

6. Steel Wire Armour

7. PVC Outer Sheath

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S WADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

6

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 240mm2 and 400m for cable sizes 300mm2 & 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

On perf. cabletray or free air

ClippedDirect

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

4 x 1.5 0.7 8.8 0.90 14.0 384 12.10 23 25 27.00

4 x 2.5 0.7 9.7 0.90 14.9 453 7.41 31 33 16.00

4 x 4 0.7 11.0 1.25 17.1 700 4.61 42 44 10.00

4 x 6 0.7 12.2 1.25 18.3 827 3.08 53 56 6.80

4 x 10 0.7 14.1 1.25 20.2 1058 1.83 73 78 4.00

4 x 16 0.7 16.3 1.60 23.1 1542 1.15 94 99 2.50

4 x 25 0.9 19.9 1.60 26.7 2074 0.73 124 131 1.65

4 x 35 0.9 22.6 1.60 29.6 2594 0.52 154 162 1.15

4 x 50 1.0 26.2 2.00 34.3 3669 0.39 187 197 0.87

4 x 70 1.1 30.5 2.00 38.9 4717 0.27 238 251 0.60

4 x 95 1.1 34.3 2.00 43.0 5907 0.19 289 304 0.45

4 x 120 1.2 38.6 2.50 48.7 7716 0.15 335 353 0.37

4 x 150 1.4 43.0 2.50 53.3 9221 0.12 386 406 0.30

4 x 185 1.6 47.6 2.50 58.2 10944 0.10 441 463 0.26

4 x 240 1.7 53.8 2.50 64.9 13567 0.08 520 546 0.21

4 x 300 1.8 59.1 2.50 70.6 16267 0.06 599 628 0.19

4 x 400 2.0 68.0 3.15 81.5 22080 0.05 673 728 0.17

Industrial & Domestic CablesCablesMAS R

6944XL

MA

SR

CA

BLE

MA

RK

ING

SA

MP

LE

MA

S

1

2

R6944X

L 600 / 1000V 4X

6 SQ

MM

CU

/ XL

PE

/ PV

C / S

WA

/ PV

C IE

C60502-1 C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

4

3

5

7

17 www.mes.com.hk

Page 18: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 694nXL - XLPE Insulated and Double PVC Sheathed with Steel Wire

Armour(SWA) n-Core Power Cables

1. Conductor

2. XLPE Insulation

3. Bindling Tape

4. PVC Inner Sheath

5. Steel Wire Armour

6. PVC Outer Sheath

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

4

Standards: IEC60502-1

Construction: Stranded plain annealed copper conductors,XLPE insulated, n cores laid up, extruded PVCbedding, galvanized steel wire armoured and PVCouter sheathed.( In short form : n/C Cu/XLPE/PVC/SWA/PVC )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair, use in ducts or direct burial in ground.

Core Colour : White with black numerals.

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. Conductor: 90oCTemperature

On perf. cabletray or free air

ClippedDirect

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The tabulated Current Ratings for above auxiliary cables assume that all cores are equally loaded.

* The Voltage Drop figures are extracted from Table 4E4B of BS7671 - 16th Edition, IEE Wiring Regulation

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

6945XL

MA

S

R

1

5

3

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg / km ) ( / km ) ( A ) ( A ) ( mV/A/m )

5 x 1.5 0.7 9.6 0.90 14.8 481 12.10 18.4 19.7 31.00

5 x 2.5 0.7 10.6 1.25 16.7 734 7.41 24.5 26.5 19.00

5 x 4 0.7 12.0 1.25 18.1 812 4.61 33.3 35.4 12.00

7 x 1.5 0.7 10.4 0.90 15.6 508 12.10 15 16 31.00

7 x 2.5 0.7 11.6 1.25 17.7 776 7.41 20 22 19.00

10 x 1.5 0.7 13.2 1.25 19.3 778 12.10 14 15 31.00

10 x 2.5 0.7 14.8 1.25 20.9 917 7.41 18 20 19.00

12 x 1.5 0.7 13.6 1.25 19.7 798 12.10 12 13 31.00

12 x 2.5 0.7 15.3 1.25 21.4 940 7.41 17 18 19.00

19 x 1.5 0.7 16.0 1.60 22.8 1070 12.10 11 12 31.00

19 x 2.5 0.7 18.0 1.60 24.8 1244 7.41 14 16 19.00

27 x 1.5 0.7 19.2 1.60 26.0 1238 12.10 10 11 31.00

27 x 2.5 0.7 21.7 1.60 28.6 1448 7.41 13 14 19.00

37 x 1.5 0.7 21.6 1.60 28.5 1375 12.10 8 9 31.00

37 x 2.5 0.7 24.4 1.60 31.5 1606 7.41 11 12 19.00

48 x 1.5 0.7 24.8 1.60 32.0 1562 12.10 9 10 31.00

48 x 2.5 0.7 28.5 2.00 36.8 2203 7.41 12 13 19.00

MA

S

CA

BLE

MA

RK

ING

SA

MP

LE

R6945X

L 600 / 1000V 5X

1.5 SQ

MM

CU

/ XL

PE

/ PV

C / S

WA

/ PV

C IE

C60502-1 C

EN

EL

EC

MA

DE

IN C

HIN

AS

EV

2

6

www.mes.com.hk18

Page 19: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

1. Conductor

2. XLPE Insulation

3. LSOH Inner Sheath

4. Aluminium Wire Armour

5. LSOH Sheath

Nominal SectionArea of

Conductor

InsulationThickness

Approx.Diameter

UnderArmour

AW ADiameter

Approx.NominalWeight

Max. DCResistance

at 20oC

Power CablesRef. 6941XLSOH - XLPE Insulated and Double LSOH Sheathed with Aluminium Wire

Armour(AWA) Single Core Power Cables

OuterSheath

Thickness

MeanOverall

Diameter

InnerSheath

Thickness

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Single core, stranded plain annealed copperXLPE insulated, LSOH inner sheathed, AWA andLSOH outer sheathed.( In short form : 1/C Cu/XLPE/LSOH/AWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair, use in ducts or direct burial in ground.

Core Colour : Brown, Black, Blue, Grey or Red

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

* Stranded copper conductor based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E3A / 4E3B

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( mm ) ( mm ) (

/ km ) ( kg / km )

16 0.7 1.0 7.9 0.9 1.8 14.4 1.15 348

25 0.9 1.0 9.4 0.9 1.8 16.1 0.73 466

35 0.9 1.0 10.5 1.25 1.8 18.3 0.52 637

50 1.0 1.0 12.0 1.25 1.8 20.0 0.39 815

70 1.1 1.0 13.6 1.25 1.8 21.7 0.27 1040

95 1.1 1.0 15.2 1.25 1.8 23.4 0.19 1309

120 1.2 1.0 16.8 1.25 1.8 25.2 0.15 1582

150 1.4 1.0 18.6 1.60 1.8 28.0 0.12 1979

185 1.6 1.0 20.5 1.60 2.0 30.5 0.10 2388

240 1.7 1.0 22.9 1.60 2.0 33.1 0.08 2968

300 1.8 1.0 25.1 1.60 2.1 35.8 0.06 3600

400 2.0 1.2 29.0 2.00 2.2 41.1 0.05 4806

500 2.2 1.2 32.0 2.00 2.3 44.7 0.037 5855

630 2.4 1.2 35.5 2.00 2.5 49.0 0.028 7224

800 2.6 1.4 39.9 2.50 2.6 55.1 0.022 9213

1000 2.8 1.4 44.1 2.50 2.7 60.0 0.018 11261

Industrial & Domestic CablesCablesMAS R

2

1

4

3

5

CA

BLE

MA

RK

ING

SA

MP

LE

6941XL

SO

H 600 / 1000V

1X50 S

Q M

M C

U / X

LP

E / L

SO

H / A

WA

/ LS

OH

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

VM

AS

R

19 www.mes.com.hk

6941

XLSO

H

MA

SR

Page 20: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Stranded plain annealed copper conductors,XLPE insulated, two cores laid up, extruded LSOHbedding, galvanized steel wire armoured and LSOHouter sheathed.( In short form : 2/C Cu/XLPE/LSOH/SWA/LSOH)

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in free air,use in ducts or direct burial in ground.

Core Colour : Red & Black, or Brown & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. LSOH Inner Sheath

6. Steel Wire Armour

7. LSOH Outer Sheath

ClippedDirect

On perf. cabletray or free air

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions :

(1) Reference Method 1 - Clipped Direct ; (2) Reference Method 11 - On a perforated horizontal or vertical

cable tray ; (3) Reference Method 13 - Free air

1

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

2 X 1.5 0.7 7.6 0.90 12.8 317 12.10 27 29 31.00

2 X 2.5 0.7 8.4 0.90 13.6 362 7.41 36 39 19.00

2 X 4 0.7 9.4 0.90 14.6 422 4.61 49 52 12.00

2 X 6 0.7 10.4 0.90 15.6 491 3.08 62 66 7.90

2 X 10 0.7 12.0 1.25 18.1 780 1.83 85 90 4.70

2 X 16 0.7 13.8 1.25 19.9 967 1.15 110 115 2.90

2 X 25 0.9 16.8 1.60 23.6 1444 0.73 146 152 1.85

2 X 35 0.9 19.0 1.60 25.8 1742 0.52 180 188 1.35

2 X 50 1.0 22.0 1.60 29.0 2189 0.39 219 228 0.98

2 X 70 1.1 25.2 2.00 33.2 3040 0.27 279 291 0.67

2 X 95 1.1 28.8 2.00 37.1 3759 0.19 338 354 0.49

2 X 120 1.2 32.0 2.00 40.5 4451 0.15 392 410 0.39

2 X 150 1.4 35.6 2.00 44.4 5272 0.12 451 472 0.31

2 X 185 1.6 39.8 2.50 49.9 6825 0.10 515 539 0.25

2 X 240 1.7 44.6 2.50 55.1 8267 0.08 607 636 0.20

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

Power Cables

Ref. 6942XLSOH - XLPE Insulated and Double LSOH Sheathed with Steel Wire

Armour (SWA) Two Core Power Cables

2

5

6

7

20

CA

BLE

MA

RK

ING

SA

MP

LE

6942XL

SO

H 600 / 1000V

2X120 S

Q M

M C

U / X

LP

E / L

SO

H / S

WA

/LS

OH

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

3

4

6942XLSOH

MA

S

R

MA

SR

www.mes.com.hk

Page 21: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power Cables

Ref. 6943XLSOH - XLPE Insulated and Double LSOH Sheathed with Steel Wire

Armour(SWA) Three Core Power Cables

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Stranded plain annealed copper conductors,XLPE insulated, three cores laid up, extruded LSOHbedding, galvanized steel wire armoured and LSOHouter sheathed.( In short form : 3/C Cu/XLPE/LSOH/SWA/LSOH)

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair, use in ducts or direct burial in ground.

Core Colour : Red , Yellow & Blue, or Brown, Black & Grey

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

21

6943XL

SO

H 600 / 1000V

3X4 S

Q M

M C

U / X

LP

E / L

SO

H / S

WA

/ LS

OH

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S WADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

Drop

R

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. LSOH Inner Sheath

6. Steel Wire Armour

7. LSOH Outer Sheath

ClippedDirect

On perf. cabletray or free air

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) ( / km ) ( A ) ( A ) ( mV/A/m )

3 x 1.5 0.7 8.0 0.90 13.2 349 12.10 23 25 27.00

3 x 2.5 0.7 8.9 0.90 14.1 405 7.41 31 33 16.00

3 x 4 0.7 10.0 0.90 15.2 483 4.61 42 44 10.00

3 x 6 0.7 11.1 0.90 17.2 727 3.08 53 56 6.80

3 x 10 0.7 12.8 1.25 18.9 913 1.83 73 78 4.00

3 x 16 0.7 14.7 1.25 20.8 1161 1.15 94 99 2.50

3 x 25 0.9 18.0 1.60 24.8 1746 0.73 124 131 1.65

3 x 35 0.9 20.4 1.60 27.2 2149 0.52 154 162 1.15

3 x 50 1.0 23.6 1.60 30.7 2755 0.39 187 197 0.87

3 x 70 1.1 27.5 2.00 35.7 3868 0.27 238 251 0.60

3 x 95 1.1 30.9 2.00 39.4 4798 0.19 289 304 0.45

3 x 120 1.2 34.4 2.00 43.1 5744 0.15 335 353 0.37

3 x 150 1.4 38.7 2.50 48.7 7474 0.12 386 406 0.30

3 x 185 1.6 42.8 2.50 53.1 8822 0.10 441 463 0.26

3 x 240 1.7 47.9 2.50 58.7 10815 0.08 520 546 0.21

3 x 300 1.8 53.1 2.50 64.2 12965 0.06 599 628 0.19

3 x 400 2.0 60.7 3.15 73.6 17566 0.05 673 728 0.17

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 300mm2 and 400m only for cable size 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesCablesMAS R

1

2

3

4

5

6

7

SE

V

CA

BLE

MA

RK

ING

SA

MP

LE

6943

XLSOH

MA

S

R

www.mes.com.hk

MA

SR

Page 22: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Industrial & Domestic Cables

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Stranded plain annealed copper conductors,XLPE insulated, four cores laid up, extruded LSOHbedding, galvanized steel wire armoured and LSOHouter sheathed.( In short form: 4/C Cu/XLPE/LSOH/SWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair, use in ducts or direct burial in ground.

Core Colour : Red , Yellow , Blue & Black, or Brown, Black, Grey & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

22

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCable

Weight

Cable CurrentCarrying Capacity

Voltage

Drop

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. LSOH Inner Sheath

6. Steel Wire Armour

7. LSOH Outer Sheath

ClippedDirect

On perf. cabletray or free air

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

4 X 1.5 0.7 8.8 0.90 14.0 390 12.10 23 25 27.00

4 X 2.5 0.7 9.7 0.90 14.9 459 7.41 31 33 16.00

4 X 4 0.7 11.0 1.25 17.1 708 4.61 42 44 10.00

4 X 6 0.7 12.2 1.25 18.3 835 3.08 53 56 6.80

4 X 10 0.7 14.1 1.25 20.2 1067 1.83 73 78 4.00

4 X 16 0.7 16.3 1.60 23.1 1552 1.15 94 99 2.50

4 X 25 0.9 19.9 1.60 26.7 2086 0.73 124 131 1.65

4 X 35 0.9 22.6 1.60 29.6 2608 0.52 154 162 1.15

4 X 50 1.0 26.2 2.00 34.3 3687 0.39 187 197 0.87

4 X 70 1.1 30.5 2.00 38.9 4739 0.27 238 251 0.60

4 X 95 1.1 34.3 2.00 43.0 5933 0.19 289 304 0.45

4 X 120 1.2 38.6 2.50 48.7 7748 0.15 335 353 0.37

4 X 150 1.4 43.0 2.50 53.3 9257 0.12 386 406 0.30

4 X 185 1.6 47.6 2.50 58.2 10986 0.10 441 463 0.26

4 X 240 1.7 53.8 2.50 64.9 13619 0.08 520 546 0.21

4 X 300 1.8 59.1 2.50 70.6 16326 0.06 599 628 0.19

4 X 400 2.0 68.0 3.15 81.5 22155 0.05 673 728 0.17

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 240mm2 and 400m for cable sizes 300mm2 & 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ; (2)

Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesIndustrial & Domestic CablesCablesMAS R

Power Cables

Ref. 6944XLSOH - XLPE Insulated and Double LSOH Sheathed with Steel Wire

Armour(SWA) Four Core Power Cables

6944XLSOH

MA

SR

MA

S

1

2

CA

BLE

MA

RK

ING

SA

MP

LE

R

5

4

6

7

3

6944XL

SO

H 600 / 1000V

4X50 S

Q M

M C

U / X

LP

E / L

SO

H / S

WA

/ LS

OH

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

www.mes.com.hk

Page 23: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 694nXLSOH -XLPE Insulated and Double LSOH Sheathed with Steel Wire

Armour(SWA) n-Core Power Cables

Industrial & Domestic Cables

23

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCable

Weight

Cable CurrentCarrying Capacity

Voltage

Drop

1. Conductor

2. XLPE Insulation

3. Filler

4. Bindling Tape

5. LSOH Inner Sheath

6. Steel Wire Armour

7. LSOH Outer Sheath

Standards: IEC60502-1, IEC61034, IEC60754 & IEC60332-3-24

Construction: Stranded plain annealed copper conductors,XLPE insulated, n cores laid up, extruded LSOHbedding, galvanized steel wire armoured and LSOHouter sheathed.( In short form: n/C Cu/XLPE/LSOH/SWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair, use in ducts or direct burial in ground.

Core Colour : White with black numerals.

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

ClippedDirect

On perf. cabletray or free air

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The tabulated Current Ratings for above auxiliary cables assume that all cores are equally loaded.

* The Voltage Drop figures are extracted from Table 4E4B of BS7671 - 16th Edition, IEE Wiring Regulation

Industrial & Domestic CablesCablesMAS R

1

2

34

5

6

6945XLSOH

MA

SR

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) ( / km ) ( A ) ( A ) ( mV/A/m )

5 x 1.5 0.7 9.6 0.90 14.8 490 12.10 18.4 19.7 31.00

5 x 2.5 0.7 10.6 1.25 16.7 743 7.41 24.5 26.5 19.00

5 x 4 0.7 12.0 1.25 18.1 821 4.61 33.3 35.4 12.00

7 x 1.5 0.7 10.4 0.90 15.6 516 12.10 15 16 31.00

7 x 2.5 0.7 11.6 1.25 17.7 785 7.41 20 22 19.00

10 x 1.5 0.7 13.2 1.25 19.3 787 12.10 14 15 31.00

10 x 2.5 0.7 14.8 1.25 20.9 928 7.41 18 20 19.00

12 x 1.5 0.7 13.6 1.25 19.7 807 12.10 12 13 31.00

12 x 2.5 0.7 15.3 1.25 21.4 950 7.41 17 18 19.00

19 x 1.5 0.7 16.0 1.60 22.8 1082 12.10 11 12 31.00

19 x 2.5 0.7 18.0 1.60 24.8 1257 7.41 14 16 19.00

27 x 1.5 0.7 19.2 1.60 26.0 1252 12.10 10 11 31.00

27 x 2.5 0.7 21.7 1.60 28.6 1463 7.41 13 14 19.00

37 x 1.5 0.7 21.6 1.60 28.5 1390 12.10 8 9 31.00

37 x 2.5 0.7 24.4 1.60 31.5 1624 7.41 11 12 19.00

48 x 1.5 0.7 24.8 1.60 32.0 1581 12.10 9 10 31.00

48 x 2.5 0.7 28.5 2.00 36.8 2227 7.41 12 13 19.00

CA

BLE

MA

RK

ING

SA

MP

LE

6945XL

SO

H 600 / 1000V

5X1.5 S

Q M

M C

U / X

LP

E / L

SO

H / S

WA

/ LS

OH

IEC

60502-1 CE

NE

LE

C M

AD

E IN

CH

INA

SE

VM

AS

R

www.mes.com.hk

Page 24: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire
Page 25: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Part 2 Fireres Cables

Page 26: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Conduit Wiring

Ref. FR1C - Fire Barrier Tape, Low Smoke Zero Halogen (LSOH) Insulated Non

Sheathed Single Core Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test ( < 0.5%HCI)Passes IEC60331-21 for fire resistant test (950oC, 3hrs)Passes BS6387 categories C, W & Z *Passes EN50200 (PH90 & PH120)

Construction: Single core, stranded plain annealedcopper conductor, mica/glass tape with LSOHinsulated. ( In short form: 1/C Cu/FR/LSOH )

Voltage Rating: 600/1000 Volts

Application: Fireres singlecore cables are suited for use in fire alarmsystem and emergency ligting or power circuits.

Standard Colour: Red, Yellow, Blue, Black, Green/Yellow, Brown or Grey

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

* For cables sizes from 1.5mm2 to 3.5mm2 , to satisfy the requirement of BS6387, testing for Cat. C, W & Z

was conducted using a 20mm steel conduit as the other metallic element while 50mm2 or above can pass

Cat. C without metallic element .

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E1A / 4E1B

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. Conductor

Resistance

at 20OC

Min. Insulation

Resistance

at 90O C

Calculated

Cable

Weight

( mm2 ) ( mm ) ( mm ) (

/ km ) ( M

/ km ) ( kg / km )

1.5 2 0.7 3.5 12.10 0.0100 23

2.5 2 0.8 4.2 7.41 0.0090 35

4 2 0.8 4.8 4.61 0.0077 51

6 2 0.8 5.4 3.08 0.0065 71

10 2 0.9 6.5 1.83 0.0065 113

16 2 0.9 8.0 1.15 0.0050 171

25 2 1.1 9.8 0.73 0.0050 265

35 2 1.1 11.0 0.52 0.0040 362

50 2 1.2 12.3 0.39 0.0045 509

70 2 1.3 14.3 0.27 0.0035 702

95 2 1.3 16.0 0.19 0.0035 938

120 2 1.4 18.0 0.15 0.0032 1181

150 2 1.8 20.3 0.12 0.0032 1475

185 2 1.9 22.3 0.10 0.0032 1828

240 2 2.0 25.3 0.08 0.0032 2356

300 2 2.1 28.0 0.06 0.0030 2923

400 2 2.3 32.0 0.05 0.0028 3883

500 2 2.5 35.1 0.04 0.0028 4835

Industrial & Domestic CablesFireres CablesCablesMAS R

1

3

FRIC

MA

SR

1. Conductor

2. Mica/Glass Tape

3. LSOH Sheath

2

CA

BLE

MA

RK

ING

SA

MP

LE

MA

SR

26 www.mes.com.hk

FRIC

600 / 1000V 1X

1.5 SQ

MM

CU

/ FR / LS

OH

BS

6387 CW

Z / IEC

61034 / IEC

60754 CE

NE

LEC

MA

DE

IN C

HIN

AS

EV

Page 27: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Surface Power Cables

Ref. FR1CXL - Fire Barrier Tape with XLPE Insulated and LSOH Sheathed

Single Core Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test ( < 0.5%HCI)Passes IEC60331-21 for fire resistant test ( 950oC , 3hrs)Passes IEC60331-3-24 for flame retardant testPasses BS6387 categories C, W & Z *Passes EN50200 (PH90 & PH120)

Construction: Single core, stranded plain annealed copperconductor, mica/glass with XLPE insulated and LSOHsheathed. ( In short form: 1/C Cu/FR/XLPE/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair and in installations where a fire situation maypose a major hazard & the maintenance of circuitintegrity is a requirement.

Core Colour : Brown, Blue, Grey, Black, or other colours upon request

Sheath Colour: White, Grey, Black, Red, or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

27

Fireres CablesCablesMAS R

1

3

1. Conductor

2. Mica/Glass Tape

covered by extruded

XLPE layer

3. LSOH Sheath

CA

BLE

MA

RK

ING

SA

MP

LE

MA

S

2

R

FRICXL

MA

SR

www.mes.com.hk

FR

ICX

L 600 / 1000V

1X50 S

Q M

M C

U / F

R / X

LP

E / L

SO

H B

S6387 C

WZ

/ IEC

61034 / IEC

60754 CE

NE

LE

C M

AD

E IN

CH

INA

SE

V

* Conductor Class based on IEC60228* Standard Packing : 500m for all above cable sizes* The Current Ratings and Voltage Drop figures refer to rear pages Technical Information Section

Table 4E1A / 4E1B

Nominal Section

Area of

Conductor

Conductor

Class

Insulation

Thickness

Mean Overall

Diameter

Max. DC

Resistance

at 20O C

Calculated

Cable

Weight

SheathThickness

Min. Insulation

Resistance

at 90O C

( mm2 ) ( mm ) ( mm ) ( mm ) (

/ km ) ( M

/ km ) ( kg / km )

16 2 0.7 1.4 11.0 1.150 0.0039 240

25 2 0.9 1.4 12.6 0.730 0.0039 460

35 2 0.9 1.4 14.0 0.520 0.0034 555

50 2 1.0 1.4 16.0 0.390 0.0032 730

70 2 1.1 1.4 18.0 0.270 0.0030 951

95 2 1.1 1.5 20.5 0.190 0.0026 1302

120 2 1.2 1.5 22.0 0.150 0.0026 1615

150 2 1.4 1.6 24.0 0.120 0.0026 2014

185 2 1.6 1.6 27.5 0.100 0.0025 2450

240 2 1.7 1.7 30.0 0.080 0.0025 3170

300 2 1.8 1.8 33.0 0.060 0.0023 3910

400 2 2.0 1.9 36.5 0.050 0.0023 5000

500 2 2.2 2.0 41.0 0.037 0.0023 6185

630 2 2.4 2.2 46.0 0.028 0.0022 6880

800 2 2.6 2.3 51.5 0.022 0.0021 8350

1000 2 2.8 2.4 56.5 0.018 0.0020 10435

Page 28: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 6942XFR - Fire Barrier Tape with XLPE Insulated and Double LSOH Sheathed

with Steel Wire Armour(SWA) Two Core Power Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test( < 0.5%HCI)Passes IEC60331-31 for fire with shock test ( 950oC, 2hrs)Passes IEC60331-3-24 for flame retardant testPasses BS6387 categories C, W & Z

Construction: Stranded plain annealed copper conductors, mica/glass with XLPE insulated, two cores laid up, extrudedLSOH bedding, galvanized steel wire armoured andLSOH outer sheathed.( In short form : 2/C Cu/FR/XLPE/LSOH/SWA/LSOH)

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair and in installations where a fire situation may posea pose a major hazard & the maintenance of circuitintegrity is a requirement.

Core Colour : Red & Black, or Brown & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

28

1. Conductor

2. Mica/Glass Tape

3. XLPE Insulation

4. Filler

5. Bindling Tape

6. LSOH Inner Sheath

7. Steel Wire Armour

8. LSOH Outer Sheath

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesCablesMAS R

1

2

3

4

5

6

7

8

MA

S

Fireres Cables

CA

BLE

MA

RK

ING

SA

MP

LE

R

6942XFR

MA

S

R

www.mes.com.hk

6942XFR

600 / 1000V 2X120 SQ M

M C

U / FR

/ XLPE / LSOH

/ SWA / LSO

H B

S6387 C

WZ / IEC

61034 / IEC60754 C

ENELEC

MA

DE IN

CH

INA

SE

V

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCable

Weight

Cable CurrentCarrying Capacity

Voltage

DropClippedDirect

On perf. cabletray or free air

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) ( mV/A/m )

2 x 1.5 0.7 7.6 0.90 13.8 320 12.10 27 29 31.00

2 x 2.5 0.7 8.4 0.90 14.6 366 7.41 36 39 19.00

2 x 4 0.7 9.4 0.90 15.6 426 4.61 49 52 12.00

2 x 6 0.7 10.4 0.90 16.6 496 3.08 62 66 7.90

2 x 10 0.7 12.0 1.25 19.1 788 1.83 85 90 4.70

2 x 16 0.7 13.8 1.25 21.0 977 1.15 110 115 2.90

2 x 25 0.9 16.8 1.60 24.6 1458 0.73 146 152 1.85

2 x 35 0.9 19.0 1.60 26.8 1759 0.52 180 188 1.35

2 x 50 1.0 22.0 1.60 30.0 2211 0.39 219 228 0.98

2 x 70 1.1 25.2 2.00 34.2 3070 0.27 279 291 0.67

2 x 95 1.1 28.8 2.00 38.1 3796 0.19 338 354 0.49

2 x 120 1.2 32.0 2.00 41.5 4496 0.15 392 410 0.39

2 x 150 1.4 35.6 2.00 45.4 5325 0.12 451 472 0.31

2 x 185 1.6 39.8 2.50 51.0 6893 0.10 515 539 0.25

2 x 240 1.7 44.6 2.50 56.0 8350 0.08 607 636 0.20

Page 29: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power CablesRef. 6943XFR - Fire Barrier Tape with XLPE Insulated and Double LSOH Sheathed

with Steel Wire Armour(SWA) Three Core Power Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test( < 0.5%HCI)Passes IEC60331-31 for fire with shock test ( 950oC , 2hrs)Passes IEC60331-3-24 for flame retardant testPasses BS6387 categories C, W & Z

Construction: Stranded plan annealed copper conductors, mical/glass with XLPE insulated, three cores laid up,extruded LSOH bedding, galvanized steel wirearmoured and LSOH outer sheathed.( In short form : 3/C Cu/FR/XLPE/LSOH/SWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair and in installations where a fire situation may posea major hazard & the maintenance of circuit integrityis a requirement.

Core Colour: Red , Yellow & Blue, or Brown, Black & Grey

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

29

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 300mm2 and 400m only for cable size 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ;

(2) Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

CablesMAS R

1. Conductor

2. Mica/Glass Tape

3. XLPE Insulation

4. Filler

5. Bindling Tape

6. LSOH Inner Sheath

7. Steel Wire Armour

8. LSOH Outer Sheath

Fireres Cables

CA

BLE

MA

RK

ING

SA

MP

LE

MA

S

54

R

1

2

3

6

7

8

6943XFR

MA

SR

www.mes.com.hk

6943XFR

600 / 1000V 3X

4 SQ

MM

CU

/ FR / X

LPE

/ LSO

H / S

WA

/ LSO

H B

S6387 C

WZ

/ IEC

61034 / IEC

60754 CE

NE

LEC

MA

DE

IN C

HIN

AS

EV

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

DropClippedDirect

On perf. cabletray or free air

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) ( / km ) ( A ) ( A ) ( mV/A/m )

3 x 1.5 0.7 8.0 0.90 14.4 352 12.10 23 25 27.00

3 x 2.5 0.7 8.9 0.90 15.3 409 7.41 31 33 16.00

3 x 4 0.7 10.0 0.90 16.4 488 4.61 42 44 10.00

3 x 6 0.7 11.1 0.90 17.2 734 3.08 53 56 6.80

3 x 10 0.7 12.8 1.25 18.4 922 1.83 73 78 4.00

3 x 16 0.7 14.7 1.25 20.1 1173 1.15 94 99 2.50

3 x 25 0.9 18.0 1.60 22.0 1921 0.73 124 131 1.65

3 x 35 0.9 20.4 1.60 26.0 2170 0.52 154 162 1.15

3 x 50 1.0 23.6 1.60 28.4 2783 0.39 187 197 0.87

3 x 70 1.1 27.5 2.00 32.0 3907 0.27 238 251 0.60

3 x 95 1.1 30.9 2.00 37.0 4846 0.19 289 304 0.45

3 x 120 1.2 34.4 2.00 40.6 5801 0.15 335 353 0.37

3 x 150 1.4 38.7 2.50 44.3 7549 0.12 386 406 0.30

3 x 185 1.6 42.8 2.50 54.3 8910 0.10 441 463 0.26

3 x 240 1.7 47.9 2.50 60.0 10923 0.08 520 546 0.21

3 x 300 1.8 53.1 2.50 65.4 13095 0.06 599 628 0.19

3 x 400 2.0 60.7 3.15 74.8 17742 0.05 673 728 0.17

Page 30: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power Cables

Ref. 6944XFR - Fire Barrier Tape with XLPE Insulated and Double LSOH Sheathed

with Steel Wire Armour(SWA) Four Core Power Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test( < 0.5%HCI)Passes IEC60331-31 for fire with shock test ( 950oC, 2hrs)Passes IEC60331-3-24 for flame retardant testPasses BS6387 categories C, W & Z

Construction: Stranded plain annealed copper conductors, mica/glass with XLPE insulated, four cores laid up, extrudedLSOH bedding, galvanized steel wire armoured andLSOH outer sheathed.( In short form: 4/C Cu/FR/XLPE/LSOH/SWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair and in installations where a fire situation maypose a major hazard & the maintenance of circuitintegrity is a requirement.

Core Colour : Red, Yellow, Blue & Black, or Brown, Black, Grey & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

30

1. Conductor

2. Mica/Glass Tape

3. XLPE Insulation

4. Filler

5. Bindling Tape

6. LSOH Inner Sheath

7. Steel Wire Armour

8. LSOH Outer Sheath

* Conductor Class based on IEC60228

* Standard Packing : 500m for cable sizes upto 300mm2 and 400m only for cable size 400mm2

* Minimum Bending Radius : Refer to page 50

* The Current Ratings and Voltage Drop figures are extracted from Table 4E4A / 4E4B of BS7671 - 16th Edition,

IEE Wiring Regulation for cables installed in following conditions : (1) Reference Method 1 - Clipped Direct ; (2)

Reference Method 11 - On a perforated horizontal or vertical cable tray ; (3) Reference Method 13 - Free air

Industrial & Domestic CablesCablesMAS R Fireres Cables

CA

BLE

MA

RK

ING

SA

MP

LE

2

3

1

8

5

MA

SR

6944XFR

MA

SR

6

7

4

www.mes.com.hk

6944XFR 600 / 1000V 4X6 SQ

MM

CU

/ FR / XLPE / LSO

H / SW

A / LSO

H B

S6387 C

WZ

/ IEC61034 / IEC

60754 CEN

ELEC M

AD

E IN C

HIN

AS

EV

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

DropClippedDirect

On perf. cabletray or free air

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) ( / km ) ( A ) ( A ) ( mV/A/m )

4 x 1.5 0.7 8.8 0.90 15.5 394 12.10 23 25 27.00

4 x 2.5 0.7 9.7 0.90 16.4 464 7.41 31 33 16.00

4 x 4 0.7 11.0 1.25 18.6 715 4.61 42 44 10.00

4 x 6 0.7 12.2 1.25 19.8 843 3.08 53 56 6.80

4 x 10 0.7 14.1 1.25 21.7 1078 1.83 73 78 4.00

4 x 16 0.7 16.3 1.60 24.6 1568 1.15 94 99 2.50

4 x 25 0.9 19.9 1.60 28.2 2107 0.73 124 131 1.65

4 x 35 0.9 22.6 1.60 31.1 2634 0.52 154 162 1.15

4 x 50 1.0 26.2 2.00 35.8 3724 0.39 187 197 0.87

4 x 70 1.1 30.5 2.00 40.4 4786 0.27 238 251 0.60

4 x 95 1.1 34.3 2.00 44.5 5992 0.19 289 304 0.45

4 x 120 1.2 38.6 2.50 50.2 7825 0.15 335 353 0.37

4 x 150 1.4 43.0 2.50 54.8 9350 0.12 386 406 0.30

4 x 185 1.6 47.6 2.50 59.7 11096 0.10 441 463 0.26

4 x 240 1.7 53.8 2.50 66.4 13755 0.08 520 546 0.21

4 x 300 1.8 59.1 2.50 71.1 16489 0.06 599 628 0.19

4 x 400 2.0 68.0 3.15 83.0 22377 0.05 673 728 0.17

Page 31: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Power Cables

Ref. 694nXFR - Fire Barrier Tape with XLPE Insulated and Double LSOH Sheathed

with Steel Wire Armour(SWA) n-Core Power Cables

Standards: Modified IEC60502-1 for constructionpasses IEC61034 for low smoke emission testpasses IEC60754 for acid gas emission test ( < 0.5%HCI)Passes IEC60331-31 for fire with shock test ( 950oC, 2hrs)Passes IEC60331-3-24 for flame retardant testPasses BS6387 categories C, W & Z

Construction: Stranded plain annealed copper conductors, mica /glass with XLPE insulated, n-cores laid up, extrudedLSOH bedding, galvanized steel wire armoured andLSOH outer sheathed.( In short form: n/C Cu/FR/XLPE/LSOH/SWA/LSOH )

Voltage Rating: 600/1000 Volts

Application: Domestic & Industrial power cables.Suitable for mounting to surface or on trays in freeair and in installations where a fire situation maypose a major hazard & the maintenance of circuitintegrity is a requirement.

Core Colour : White with Black numeralsGrey & Blue

Inner Sheath Colour: Black

Outer Sheath Colour: Black or other colours upon request

Approvals: SEV, CCA-NTR & CENELEC

Max. ConductorTemperature: 90oC

No. of Core xNominal Section

Area ofConductor

InsulationThickness

Approx.Diameter

UnderArmour

S W ADiameter

Approx.Overall

Diameter

Max. DCResistance

at 20oC

CalculatedCableWeight

Cable CurrentCarrying Capacity

Voltage

DropClippedDirect

On perf. cabletray or free air

* Conductor Class based on IEC60228

* Standard Packing : 500m for all above cable sizes

* Minimum Bending Radius : Refer to page 50

* The tabulated Current Ratings for above auxiliary cables assume that all cores are equally loaded.

* The Voltage Drop figures are extracted from Table 4E4B of BS7671 - 16th Edition, IEE Wiring Regulation

CablesMAS R

6945XFR

MA

SR

3

4

5

6

7

8

1

1. Conductor

2. Mica/Glass Tape

3. XLPE Insulation

4. Filler

5. Bindling Tape

6. LSOH Inner Sheath

7. Steel Wire Armour

8. LSOH Outer Sheath

Fireres Cables

( mm2 ) ( mm ) ( mm ) ( mm ) ( mm ) ( kg/km ) (

/ km ) ( A ) ( A ) (mV/A/m)

5 x 1.5 0.7 9.6 0.90 16.5 495 12.10 18.4 19.7 31.00

5 x 2.5 0.7 10.6 1.25 17.5 750 7.41 24.5 26.5 19.00

5 x 4 0.7 12.0 1.25 18.6 829 4.61 33.3 35.4 12.00

7 x 1.5 0.7 10.4 0.90 16.1 521 12.10 15 16 31.00

7 x 2.5 0.7 11.6 1.25 18.2 793 7.41 20 22 19.00

10 x 1.5 0.7 13.2 1.25 19.8 795 12.10 14 15 31.00

10 x 2.5 0.7 14.8 1.25 21.4 937 7.41 18 20 19.00

12 x 1.5 0.7 13.6 1.25 20.2 815 12.10 12 13 31.00

12 x 2.5 0.7 15.3 1.25 22.0 960 7.41 17 18 19.00

19 x 1.5 0.7 16.0 1.60 23.3 1093 12.10 11 12 31.00

19 x 2.5 0.7 18.0 1.60 25.3 1270 7.41 14 16 19.00

27 x 1.5 0.7 19.2 1.60 26.5 1265 12.10 10 11 31.00

27 x 2.5 0.7 21.7 1.60 29.1 1477 7.41 13 14 19.00

37 x 1.5 0.7 21.6 1.60 29.0 1404 12.10 8 9 31.00

37 x 2.5 0.7 24.4 1.60 32.0 1640 7.41 11 12 19.00

48 x 1.5 0.7 24.8 1.60 32.5 1597 12.10 9 10 31.00

48 x 2.5 0.7 28.5 2.00 37.3 2249 7.41 12 13 19.00

2

CA

BLE

MA

RK

ING

SA

MP

LE

MA

SR

31 www.mes.com.hk

6945XFR

600 / 1000V 5X

1.5 SQ

MM

CU

/ FR / X

LPE

/ LSO

H / S

WA

/ LSO

H B

S6387 C

WZ / IE

C61034 / IE

C60754 C

EN

ELE

C M

AD

E IN

CH

INA

SE

V

Page 32: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

European certification according to CCA

procedures (CENELEC Certification Agreement)

with NTR (Notification of Test Results)

IECEE CB Scheme

Worldwide System for

Conformity Testing and Certification

of Electrical Equipment

China National Centre for Quality

Supervision and Test of Electric Wire and Cable

ISO 9001

Cert. No. : 0112-2003-AQ-RGC-UKAS

China Compulsory Certification

ISO 9001

Cert. No. : 0602Q10358R1M

ISO 14001

Cert. No. : 00904E10028R0M

Cert. No.: E-7094 to 7115

Industrial & Domestic CablesApprovalsCablesMAS R

All MAS cables have been manufactured under strict quality management system

which awarded certificates issued from the following certification boards:

32

CCA-NTR with SEV mark of

conformity

www.mes.com.hk

Page 33: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

LISTS OF TECHNICAL REFERENCES

Industrial & Domestic CablesCablesMAS R Technical References

Table 4B1 Current rating correct factors for groups of more than

one circuit of single-core cables, or more than

one multi-core cable.

Table 4B3 Current rating correct factors for cables installed in

enclosed trenches.

Table 4D1A Current-carrying Capacity for Singlecore PVC insulated cables,

non-armoured, with or without sheath copper conductors to

BS6004 / 60227IEC01 / IEC60502-1

(Applied to product 6491X & 6181Y)

Table 4D1B Voltage Drop for Singlecore PVC insulated cables, non-armoured,

with or without sheath copper conductors to

BS6004 / 60227IEC01 / IEC60502-1

(Applied to product 6491X & 6181Y)

Table 4E1A Current-carrying Capacity for Singlecore cables having

thermosetting insulation, non-armoured, with or without sheath

copper conductors to BS7211/ BS7889 / IEC60502-1

(Applied to product 6491LSOH / 6U81S / 6U81LSOH / FR1C / FR1CXL)

Table 4E1B Voltage Drop for Singlecore cables having thermosetting insulation,

non-armoured, with or without sheath copper conductors to

BS7211/ BS7889 / IEC60502-1

(Applied to product 6491LSOH / 6U81S / 6U81LSOH / FR1C / FR1CXL)

Table 4E3A & 4E3B Current-carrying Capacity & Voltage Drop for Singlecore

cables having thermosetting insulation (non-magnetic armour),

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6941XL / 6941XLSOH )

Table 4E4A & 4E4B Current-carrying Capacity & Voltage Drop for

Multicore armoured cables having thermosetting insulation

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6942XL / 6943XL / 6944XL / 694nXL/

6942XLOSH / 6943XLOSH / 6944XLOSH / 694nXLSOH /

6942XFR / 6943XFR / 6944XFR / 694nXFR)

Table 4H3A & 4H3B Current-Carrying Capacity & Voltage Drop

for flexible cords to BS 6141 / BS6500 / IEC60227- 5

(Applied to product 3183Y)

Sustainsd current rating for XLPE insulated cables

Current rating correction factors for ambient temperature

Requirements for installation of cables and flexible cords

P36

P35

P34

P39

P40-41

P42-43

P44-45

P37-38

P46

P49

P50

P47-48

33 www.mes.com.hk

Page 34: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

The following pages of current rating, voltage drop and general installation methods are quoted

from BS7671 16th Edition, IEE Wiring Regulation. The information provided is for reference only,

it is better to consult with our experts before use.

Table 4B1 Current rating correct factors for groups of more than one circuit of single-core cables,

or more than one multi-core cable. (To be applied to the corresponding current-carrying

capacity for a single circuit in Tables 4D1 to 4D4, 4E1 to 4E4, 4F1, and 4F2, 4J1, 4K1 to

4K4, 4L1 to 4L4)**

34

* Spaced by a clearance between adjacent surfaces of at least one cable diameter (De). Where the horizontal

clearance between adjacent cables exceeds 2De, no correction factor need be applied.

**When cables having differing conductor operating temperatures are grouped together, the current rating shall

be based upon the lowest operating temperature of of any cable in the group.

Notes to Table 4B1

1. The factors in the table are applied to groups of cables all of one size. The value of current derived from

application of the appropriate factors is the maximum current to be carried by any of the cables in the group.

2. If, due to known operating conditions, a cable is expected to carry not more than 30% of its grouped rating,

it may be ignored for the purpose of obtaining the rating factor for the rest of the group.

For example, a group of N loaded cables would normally require a group reduction factor of Cg applied to the

tabulated It , however, if M cables in the group carry loads which are not greater than 0.3Cg It amperes the

other cables can be sized by using the group rating factor corresponding to (N-M) cables.

Cg

Number of circuits or multicore cablesReference method of installation(See Table 4A - IEE Regulations)

2 3 4 5 6 7 8 9 10 12 14 16 18 20

Enclosed (Method 3 or 4 ) or

bunched and clipped direct to a

non-metallic surface (Method 1)

0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38

Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - -

Spaced * 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90

Single layer clipped to

a non-metallic

surface (Method 1)

0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - -Touching

Spaced * 0.91 0.89 0.88 0.87 0.87 - - - - - - - - -

Single layer multicore

on a perforated metal

cab le t ray , ve r t . o r

hori. (Method 11)

Horizontal 0.90 0.85 - - - - - - - - - - - -Single layer,singlecoreon a perforated metalcab le t ray , touch ing(Method 11)

Vertical 0.85 - - - - - - - - - - - - -

Single layer multicore touching onladder supports (Method 13)

0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -

www.mes.com.hk

Page 35: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Industrial & Domestic CablesTechnical InformationCablesMAS R

35

The following pages of current rating, voltage drop and general installation methods are quoted

from BS7671 16th Edition, IEE Wiring Regulation

Correction Factor

Installation Method 18 Installation Method 19 Installation Method 20

6 singlecore cables,4 two corecables, or3 three orfour core

cables

6 singlecore cables,4 two corecables, or3 three orfour core

cables

12 singlecore cables,8 two corecables, or6 three orfour core

cables

12 singlecore cables,8 two corecables, or6 three orfour core

cables

18 singlecore cables,12 two corecables, or9 three orfour core

cables

24 singlecore cables,16 two corecables, or12 three orfour core

cables

8 singlecore cables,

or 4three orfour core

cables

Conductorcross-

sectionalarea

(mm2)

2 singlecorecables,

or 1three or

four corecables

3 singlecore cables,

or 2two corecables

4 singlecore cables,

or 2three or

four corecables

* When cables having differing conductor operating temperatures are grouped together, the current ratingshall be based upon the lowest operating temperature of of any cable in the group.

Table 4B3 Current rating correct factors for cables installed in enclosed trenches

( Installation methods 18, 19 & 20 of Table 4A)*

The correction factors tabulated below relate to the disposition of cables illustrated in

items 18 to 20 of Table 4A and are applicable to the current-carrying capacities for

Reference methods 12 or 13 of Table 4A Column 4

1 2 3 4 5 6 7 8 9 10 11

4 0.93 0.90 0.87 0.82 0.86 0.83 0.76 0.81 0.74 0.69

6 0.92 0.89 0.86 0.81 0.86 0.82 0.75 0.80 0.73 0.68

10 0.91 0.88 0.85 0.80 0.85 0.80 0.74 0.78 0.72 0.66

16 0.91 0.87 0.84 0.78 0.83 0.78 0.71 0.76 0.70 0.64

25 0.9 0.86 0.82 0.76 0.81 0.76 0.69 0.74 0.67 0.62

35 0.89 0.85 0.81 0.75 0.80 0.74 0.68 0.72 0.66 0.60

50 0.88 0.84 0.79 0.74 0.78 0.73 0.66 0.71 0.64 0.59

70 0.87 0.82 0.78 0.72 0.77 0.72 0.64 0.70 0.62 0.57

95 0.86 0.81 0.76 0.70 0.75 0.70 0.63 0.68 0.60 0.55

120 0.85 0.80 0.75 0.69 0.73 0.68 0.61 0.66 0.58 0.53

150 0.84 0.78 0.74 0.67 0.72 0.67 0.59 0.64 0.57 0.51

185 0.83 0.77 0.73 0.65 0.70 0.65 0.58 0.63 0.55 0.49

240 0.82 0.76 0.71 0.63 0.69 0.63 0.56 0.61 0.53 0.48

300 0.81 0.74 0.69 0.62 0.68 0.62 0.54 0.59 0.52 0.46

400 0.80 0.73 0.67 0.59 0.66 0.60 0.52 0.57 0.50 0.44

500 0.78 0.72 0.66 0.58 0.64 0.58 0.51 0.56 0.48 0.43

630 0.77 0.71 0.65 0.56 0.63 0.57 0.49 0.54 0.47 0.41

800 0.75 0.69 0.63 0.54 0.61 0.55 0.47 0.52 0.45 0.39

1000 0.73 0.67 0.61 0.52 0.59 0.53 0.45 0.50 0.43 0.37

www.mes.com.hk

Page 36: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

36

Table 4D1A Singlecore PVC insulated cables, non-armoured, with or without sheath copper

conductors to BS6004 / 60227IEC01 / IEC60502-1

(Applied to product 6491X & 6181Y)

Current-carrying capacity (Amperes)Ambient temperature : 300C

Conductor operating temperature : 700C

Notes to Table 4D1A

1. Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface toappendix 4 of BS7671, the 16th edition of the IEE Wiring Regulation.

2. The current-carrying capacities in column 2 to 5 are also applicable to flexible cables to BS6004 Table 1 andto 90OC heat resisting P.V.C cables to BS6231 where the cables are used in fixed installation

Conductorcross-

sectionalarea

Reference Method 4(enclosed in conduit in

thermally insulating wall etc.)

Reference Method 3(enclosed in conduit on

a wall or in trunking etc.)

Reference Method 1(clipped direct)

Reference Method 11 Reference Method 12 (free air)

HorizontalFlat Spaced

VerticalFlat Spaced

TrefoilOn a perforated cable tray,

horizontal or vertical)

2 cables,single phaseA.C or D.C

3 or 4 cables,three phase

A.C

2 cables,single phaseA.C or D.C

3 or 4 cables,three phase

A.C

2 cables,single phaseA.C or D.C

flat &touching

3 or 4 cables,three phaseA.C flat &

touching ortrefoil

2 cables,single phaseA.C or D.C

flat &touching

3 or 4 cables,three phaseA.C flat &

touching ortrefoil

2 cables,single phaseA.C or D.Cor 3 cablesthree phase

2 cables,single phaseA.C or D.Cor 3 cablesthree phase

3 cablestrefoil,

three phaseA.C.

1 2 3 4 5 6 7 8 9 10 11 12

(mm2) A A A A A A A A A A A

1.5 14.5 13.5 17.5 15.5 20 18 - - - - -

2.5 19.5 18 24 21 27 25 - - - - -

4 26 24 32. 28 37 33 - - - - -

6 34 31 41 36 47 43 - - - - -

10 46 42 57 50 65 59 - - - - -

16 61 56 76 68 87 79 - - - - -

25 80 73 101 89 114 104 126 112 146 130 110

35 99 89 125 110 141 129 156 141 181 162 137

50 119 108 151 134 182 167 191 172 219 197 167

70 151 136 192 171 234 214 246 223 281 254 216

95 182 164 232 207 284 261 300 273 341 311 264

120 210 188 269 239 330 303 349 318 396 362 308

150 240 216 300 262 381 349 404 369 456 419 356

185 273 245 341 296 436 400 463 424 521 480 409

240 320 286 400 346 515 472 549 504 615 569 485

300 367 328 458 394 594 545 635 584 709 659 561

400 - - 546 467 694 634 732 679 852 795 656

500 - - 626 533 792 723 835 778 982 920 749

630 - - 720 611 904 826 953 892 1138 1070 855

800 - - - - 1030 943 1086 1020 1265 1188 971

1000 - - - - 1154 1058 1216 1149 1420 1337 1079

www.mes.com.hk

Page 37: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

37

Table 4D1B Singlecore PVC insulated cables, non-armoured, with or without sheath

copper conductors to BS6004 / 60227IEC01 / IEC60502-1

(Applied to product 6491X & 6181Y)

Conductor operating temperature: 70oCVoltage drop per ampere per metre (mV) :

Conductorcross-

sectionalarea

Reference Method 3 & 4(enclosed in conduit etc

in or on a wall)

2 cables,D.C.

2 cables - single phase A.C

Reference Method 1 & 11(Clipped direct or on trays, Touching)

Reference Method 12(Spaced*)

1 2 3 4 5

(mm2) mV mV mV mV

1.5 29 29 29 29

2.5 18 18 18 18

4 11 11 11 11

6 7.3 7.3 7.3 7.3

10 4.4 4.4 4.4 4.4

16 2.8 2.8 2.8 2.8

r x z r x z r x z

25 1.75 1.80 0.33 1.80 1.75 0.20 1.75 1.75 0.29 1.80

35 1.25 1.30 0.31 1.30 1.25 0.195 1.25 1.25 0.28 1.30

50 0.93 0.95 0.30 1.00 0.93 0.190 0.95 0.93 0.28 0.97

70 0.63 0.65 0.29 0.72 0.63 0.185 0.66 0.63 0.27 0.69

95 0.46 0.49 0.28 0.56 0.47 0.180 0.50 0.47 0.27 0.54

120 0.36 0.39 0.27 0.47 0.37 0.175 0.41 0.37 0.26 0.45

150 0.29 0.31 0.27 0.41 0.30 0.175 0.34 0.29 0.26 0.39

185 0.23 0.25 0.27 0.37 0.24 0.170 0.29 0.24 0.26 0.35

240 0.180 0.195 0.26 0.33 0.185 0.165 0.25 0.185 0.25 0.31

300 0.145 0.160 0.26 0.31 0.150 0.165 0.22 0.150 0.25 0.29

400 0.105 0.130 0.26 0.29 0.120 0.160 0.20 0.115 0.25 0.27

500 0.086 0.110 0.26 0.28 0.098 0.155 0.185 0.093 0.24 0.26

630 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25

800 0.053 - 0.068 0.150 0.165 0.061 0.24 0.25

1000 0.042 - 0.059 0.150 0.160 0.050 0.24 0.24

www.mes.com.hk

Page 38: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

38

Conductorcross-

sectionalarea

Reference Method 3 & 4(enclosed in conduit etc

in or on a wall)

3 or 4 cables - Three phase A.C

Reference Method 1 & 11(Flat & Touching)

Reference Method 12(Flat Spaced*)

Reference Method 1, 11 & 12(In trefoil)

1 6 7 8 9

(mm2) mV mV mV mV

1 38 38 38 38

1.5 25 25 25 25

2.5 15 15 15 15

4 9.5 9.5 9.5 9.5

6 6.4 6.4 6.4 6.4

10 3.8 3.8 3.8 3.8

16 2.4 2.4 2.4 2.4

r x z r x z r x z r x z

25 1.50 0.29 1.55 1.50 0.175 1.50 1.50 0.25 1.55 1.50 1.32 1.55

35 1.10 0.27 1.10 1.10 0.170 1.10 1.10 0.24 1.10 1.10 1.32 1.15

50 0.81 0.26 0.85 0.80 0.165 0.82 0.80 0.24 0.84 0.80 0.32 0.86

70 0.56 0.25 0.61 0.55 0.160 0.57 0.55 0.24 0.60 0.55 0.31 0.63

95 0.42 0.24 0.48 0.41 0.155 0.43 0.41 0.23 0.47 0.40 0.31 0.51

120 0.33 0.23 0.41 0.32 0.150 0.36 0.32 0.23 0.40 0.32 0.30 0.44

150 0.27 0.23 0.36 0.26 0.150 0.30 0.26 0.23 0.34 0.26 0.30 0.40

185 0.22 0.23 0.32 0.21 0.145 0.26 0.21 0.22 0.31 0.21 0.30 0.36

240 0.17 0.23 0.29 0.160 0.145 0.22 0.160 0.22 0.27 0.160 0.29 0.34

300 0.14 0.23 0.27 0.130 0.140 0.190 0.130 0.22 0.25 0.130 0.29 0.32

400 0.12 0.22 0.25 0.105 0.140 0.175 0.105 0.21 0.24 0.100 0.29 0.31

500 0.10 0.22 0.25 0.086 0.135 0.160 0.086 0.21 0.23 0.081 0.29 0.30

630 0.08 0.22 0.24 0.072 0.135 0.150 0.072 0.21 0.22 0.066 0.28 0.29

800 - 0.060 0.130 0.145 0.060 0.21 0.22 0.053 0.28 0.29

1000 - 0.052 0.130 0.140 0.052 0.20 0.21 0.044 0.28 0.28

Table 4D1B (Continued)

Voltage drop per ampere per metre (mV) :

Notes to Table 4D1B

Spacings larger than those specified in Method 12 (see Table 4A of BS7671, the 16th Edition of the IEE Wiring

Regulations) will result in larger voltage drop.

Conductor operating temperature: 70oC

www.mes.com.hk

Page 39: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

39

Conductorcross-

sectionalarea

Reference Method 4(enclosed in conduit in

thermally insulating wall etc.)

Reference Method 3(enclosed in conduit on

a wall or in trunking etc.)

Reference Method 1(clipped direct)

Reference Method 11 Reference Method 12 (free air)

HorizontalFlat Spaced

VerticalFlat Spaced

Trefoil(on a perforated cable tray,horizontal or vertical)

2 cables,single phaseA.C or D.C

3 or 4 cables,three phase

A.C

2 cables,single-phase

A.C or D.C

3 or 4 cables,three phase

A.C

2 cables,single phaseA.C or D.C

flat &touching

3 or 4 cables,three phaseA.C flat &

touching ortrefoil

2 cables,single phaseA.C or D.C

flat &touching

3 or 4 cables,three-phase

A.C flat &touching or

trefoil

2 cables,single-phaseA.C or D.C or 3 cablesthree-phase

2 cables,single-phaseA.C or D.Cor 3 cablesthree-phase

3 cablestrefoil,three-

phase A.C.

1 2 3 4 5 6 7 8 9 10 11 12

(mm2) A A A A A A A A A A A

1.5 18 17 22 19 25 23 - - - - -

2.5 24 23 30 26 34 31 - - - - -

4 33 30 40 35 46 41 - - - - -

6 43 39 51 45 59 54 - - - - -

10 58 53 71 63 81 74 - - - - -

16 76 70 95 85 109 99 - - - - -

25 100 91 126 111 143 130 158 140 183 163 138

35 124 111 156 138 176 161 195 176 226 203 171

50 149 135 189 168 228 209 293 215 274 246 209

70 189 170 240 214 293 268 308 279 351 318 270

95 228 205 290 259 355 326 375 341 426 389 330

120 263 235 336 299 413 379 436 398 495 453 385

150 300 270 375 328 476 436 505 461 570 524 445

185 341 306 426 370 545 500 579 530 651 600 511

240 400 358 500 433 644 590 686 630 769 711 606

300 459 410 573 493 743 681 794 730 886 824 701

400 - - 683 584 868 793 915 849 1065 994 820

500 - - 783 666 990 904 1044 973 1228 1150 936

630 - - 900 764 1130 1033 1191 1115 1423 1338 1069

800 - - - - 1288 1179 1358 1275 1581 1485 1214

1000 - - - - 1443 1323 1520 1436 1775 1671 1349

Conductor operating temperature: 70oC

Table 4E1A Singlecore cables having thermosetting insulation, non-armoured, with

or without sheath copper conductors to BS7211/ BS7889 / IEC60502-1

(Applied to product 6491LSOH / 6U81S / 6U81LSOH / FR1C / FR1CXL)

Ambient temperature : 30oC

Notes to Table 4E1A1. Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface to

appendix 4 of BS7671, the 16th edition of the IEE Wiring Regulation.

2. The current-carrying capacities in column 2 to 5 are also applicable to flexible cables to BS7211 Table 3(b)where the cables are used in fixed installation.

3. For cables in ridgid P.V.C. conduit the values stated in Table 4D1 of BS7671 of the 16th Edition of the IEEWiring Regulations are applicable.

4. Where a conductor operates at a temperature exceeding 70OC it shall be ascertained that the equipmentconnected to the conductor is suitable for the conductor operating temperature (See Regulation 512-02 ofBS7671 of the 16th Edition of the IEE Wiring Regulations)

Current-carrying capacity (Amperes)

www.mes.com.hk

Page 40: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

40

Conductorcross-

sectionalarea

Reference Method 3 & 4(enclosed in conduit etc

in or on a wall)

2 cables,D.C.

2 cables - Single phase A.C

Reference Method 1 & 11(Clipped direct or on trays, Touching)

Reference Method 12(Spaced*)

1 2 3 4 5

(mm2) mV mV mV mV

1.5 31 31 31 31

2.5 19 19 19 19

4 12 12 12 12

6 7.9 7.9 7.9 7.9

10 4.7 4.7 4.7 4.7

16 2.9 2.9 2.9 2.9

r x z r x z r x z r

25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85

35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35

50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00

70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73

95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56

120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47

150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41

185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36

240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31

300 0.155 0.175 0.25 0.31 0.160 0.160 0.22 0.155 0.25 0.29

400 0.120 0.140 0.25 0.29 0.130 0.155 0.20 0.125 0.24 0.27

500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26

630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25

800 0.056 - 0.072 0.150 0.170 0.064 0.24 0.25

1000 0.045 - 0.063 0.150 0.165 0.054 0.24 0.24

Table 4E1B Singlecore cables having thermosetting insulation, non-armoured,

with or without sheath copper conductors to BS7211/ BS7889 / IEC60502-1

(Applied to product 6491LSOH / 6U81S / 6U81LSOH / FR1C / FR1CXL)

Voltage drop per ampere per metre (mV) : Conductor operating temperature: 90oC

Notes to Table 4E1B

Spacings larger than those specified in Method 12 (see Table 4A of BS7671, the 16th Edition of the IEE Wiring

Regulations) will result in larger voltage drop.

www.mes.com.hk

Page 41: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

41

Table 4E1B (Continued)

Conductorcross-

sectionalarea

Reference Method 3 & 4(enclosed in conduit etc

in or on a wall)

3 or 4 cables - Three phase A.C

Reference Method 1, 11 & 12(in trefoil)

Reference Method 12(Flat Spaced*)

1 6 7 8 9

(mm2) mV mV mV mV

1.5 27 27 27 27

2.5 16 16 16 16

4 10 10 10 10

6 6.8 6.8 6.8 6.8

10 4.0 4.0 4.0 4.0

16 2.5 2.5 2.5 2.5

r x z r x z r x z r x z

25 1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65

35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 1.15 1.15 0.26 1.20

50 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89

70 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65

95 0.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49

120 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42

150 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37

185 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33

240 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.170 0.24 0.29

300 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27

400 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.160 0.195 0.110 0.24 0.26

500 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.160 0.180 0.085 0.24 0.25

630 0.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170 0.068 0.23 0.24

800 - 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24

1000 - 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24

Reference Method 1, 11(Flat & Touching)

Voltage drop per ampere per metre (mV) :

Notes to Table 4E1B

Spacings larger than those specified in Method 12 (see Table 4A of BS7671, the 16th Edition of the IEE Wiring

Regulations) will result in larger voltage drop.

www.mes.com.hk

Page 42: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

42

Conductorcross-

sectionalarea

Reference Method 1(clipped direct)

Reference Method 11(on a perforated cable tray)

Reference Method 12 (Free Air)

HorizontalFlat Spaced

VerticalFlat Spaced

3 cablesTrefoil

2 cables,single phaseA.C or D.C.

Flat &Touching

3 or 4 cables,three phase

A.C.Flat&

Touching

2 cables,single phaseA.C or D.C.

Flat &Touching

3 or 4 cables,three phaseA.C .Flat &Touching

2 cables singlephase A..C.

2 cables, D.C. 3 or 4 cables, three phase A.C.

1 2 3 4 5 6 7 8 9 10 11 12

(mm2) A A A A A A A A A A A

50 237 220 253 232 282 266 284 270 288 266 222

70 303 277 322 293 357 337 356 349 358 331 285

95 367 333 389 352 436 412 446 426 425 393 346

120 425 383 449 405 504 477 519 497 485 449 402

150 488 437 516 462 566 539 600 575 549 510 463

185 557 496 587 524 643 614 688 660 618 574 529

240 656 579 689 612 749 714 815 782 715 666 625

300 755 662 792 700 842 805 943 906 810 755 720

400 853 717 899 767 929 889 1137 1094 848 797 815

500 962 791 1016 851 1032 989 1314 1266 923 871 918

630 1082 861 1146 935 1139 1092 1528 1474 992 940 1027

800 1170 904 1246 987 1204 1155 1809 1744 1042 978 1119

1000 1261 961 1345 1055 1289 1238 2100 2026 1110 1041 1214

VerticalSpaced

HorizontalSpaced

VerticalFlat

Spaced

Horizontalflat

Spaced

Table 4E3A Singlecore cables having thermosetting insulation (non-magnetic armour),

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6941XL / 6941XLSOH )

Ambient temperature : 30oCCurrent-carrying capacity (Amperes) Conductor operating temperature : 90oC

Notes to Table 4E3A

1. Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface toappendix 4 of BS7671, the 16th edition of the IEE Wiring Regulation.

2. Where a conductor operates at a temperature exceeding 70OC it shall be ascertained that the equipmentconnected to the conductor is suitable for the conductor operating temperature

(See Regulation 512-02 of BS7671 of the 16th Edition of the IEE Wiring Regulations)

www.mes.com.hk

Page 43: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

43

Conductorcross-

sectionalarea

3 or 4 cables - single phase A.C.

Reference Methods 1 & 11

(touching)

ReferenceMethod 12

(flat spaced*)

1 2 3 4 5 6 7

(mm2) mV mV mV mV mV mV

r x z r x z r x z r x z r x z r

50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.90

70 0.67 0.68 0.200 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70

95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58

120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.51

150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.45

185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41

240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37

300 0.155 0.170 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34

400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33

500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31

630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29

800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26

1000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

ReferenceMethods 1 & 11 and 12

(in trefoil touching)

2cablesD.C.

2 cables - single phase A.C.

ReferenceMethod 12(spaced*)

ReferenceMethods 1 & 11(flat touching)

Voltage drop per ampere per metre (mV) : Conductor operating temperature : 90oC

Notes to Table 4E3B

Spacings larger than those specified in Method 12 (see Table 4A of BS7671, the 16th Edition of the IEE WiringRegulations) will result in larger voltage drop.

Table 4E3B Singlecore cables having thermosetting insulation (non-magnetic armour),

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6941XL / 6941XLSOH )

www.mes.com.hk

Page 44: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

44

Table 4E4A Multicore armoured cables having thermosetting insulation

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6942XL / 6943XL / 6944XL / 694nXL / 6942XLOSH

/ 6943XLOSH / 6944XLOSH / 694nXLSOH / 6942XFR / 6943XFR /

6944XFR / 694nXFR)

Conductorcross-sectional

area

Reference Method 1(Clipped direct)

1 2 3 4 5

(mm2) A A A A

1.5 27 23 29 25

2.5 36 31 39 33

4 49 42 52 44

6 62 53 66 56

10 85 73 90 78

16 110 94 115 99

25 146 124 152 131

35 180 154 188 162

50 219 187 228 197

70 279 238 291 251

95 338 289 354 304

120 392 335 410 353

150 451 386 472 406

185 515 441 539 463

240 607 520 636 546

300 698 599 732 628

400 787 673 847 728

1 two core cable singlephase A.C.or D.C

1 three or four core cablethree phase A.C.

Reference Method 1(on a perforated horizontal or vertical cable tray )

or Reference method 13 ( Free Air)

1 two core cable singlephase A.C. or D.C.

1 three or four core cablethree phase A.C.

Current-carrying capacity (Amperes) Conductor operating temperature : 90oC

Notes to Table 4E4A

1. Where the conductor is to be protected by a semi-enclosed fuse to BS3036, see item 6.2 of the preface toappendix 4 of BS7671, the 16th edition of the IEE Wiring Regulation.

2. Where a conductor operates at a temperature exceeding 70oC it shall be ascertained that the equipmentconnected to the conductor is suitable for the conductor operating temperature

(See Regulation 512-02 of BS7671 of the 16th Edition of the IEE Wiring Regulations)

Ambient temperature : 30oC

wwwwww.mes.com.hk

Page 45: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Table 4E4B Multicore armoured cables having thermosetting insulation

copper conductors to BS5467/ BS6724 / IEC60502-1

(Applied to product 6942XL / 6943XL / 6944XL / 694nXL/ 6942XLOSH

/ 6943XLOSH / 6944XLOSH / 694nXLSOH/ 6942XFR / 6943XFR /

6944XFR / 694nXFR)

Technical InformationCablesMAS R

45

Conductorcross-sectional

area

1 2 3 4

(mm2) mV/A/m mV/A/m mV/A/m

1.5 31.0 31.0 27.0

2.5 19.0 19.0 16.0

4 12.0 12.0 10.0

6 7.9 7.9 6.8

10 4.7 4.7 4.0

16 2.9 2.9 2.5

r x z r x Z

25 1.85 1.85 0.160 1.90 1.60 0.140 1.65

35 1.35 1.35 0.155 1.35 1.15 0.135 1.15

50 0.98 0.99 0.155 1.00 0.86 0.135 0.87

70 0.67 0.67 0.150 0.69 0.59 0.130 0.60

95 0.49 0.50 0.150 0.52 0.43 0.130 0.45

120 0.39 0.40 0.145 0.42 0.34 0.130 0.37

150 0.31 0.32 0.145 0.35 0.28 0.125 0.30

185 0.25 0.26 0.145 0.29 0.22 0.125 0.26

240 0.195 0.20 0.140 0.24 0.175 0.125 0.21

300 0.155 0.16 0.140 0.21 0.140 0.120 0.185

400 0.120 0.13 0.140 0.190 0.115 0.120 0.165

Two corecable, D.C Two core cable, single-phase A.C. Three or four core cable, Three-phase A.C.

Voltage drop per ampere per metre (mV) : Conductor operating temperature : 90oC

www.mes.com.hk

Page 46: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

46

Notes

The tabulated voltage drop values are for 60oC rubber insulated and P.V.C. insulated flexible cords and for

85oC rubber or P.V.C insulated flexible cords are to be multiplied by 1.09

Table 4H3A & 4H3B Current-Carrying Capacity & Voltage Drop

for flexible cords to BS 6141 / BS6500 / IEC60227- 5

(Applied to product 3183Y)

Nominalcross-sectional

area of conductor

1 2 3 4 5 6

mm2 A A mV mV kg

0.75 6 6 62 54 3

1.0 10 10 46 40 5

1.5 16 16 32 27 5

2.5 25 20 19 16 5

D.C. or singlephase A.C.

Current-carrying capacity (Amperes) Volt drop per ampere per metre

Three-phaseA.C.

D.C. or singlephase A.C.

Three-phase A.C.

Maximum masssupportable by twin

flexible cord(see regulation 522-08-06)

Conductor operating temperature : 60oC

Technical InformationCablesMAS R

www.mes.com.hk

Page 47: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

47

Nominalconductor

area

600/1000V three single core cablesin trefoil arrangement

Direct BuriedArmoured

DuctArmoured

(Trefoil Ducts)

AirUnarmoured

AirArmoured

1 2 3 4 5

(mm2) A A A A

50 231 231 223 231

70 284 278 264 295

95 340 327 352 362

120 386 366 412 420

150 431 396 475 483

185 485 437 551 555

240 558 489 658 654

300 623 534 761 745

400 691 567 887 851

500 765 615 1027 963

630 641 664 1186 1084

800 888 692 1347 1178

1000 942 735 1503 1278

The tabulated figures of sustained current ratings for XLPE insulated 600/1000 cables with copper

conductors quoted from ERA 69-30 Pt.V are derived in calculation by assuming the following

standard conditions: -

a) Thermal resistivity of soil : 1.2 Km / W

b) Ground temperature : 15oC

c) Ambient air temperature : 25oC

d) Maximum sustained conductor temperature : 90oC

e) Depth of burial, from ground surface to : 500 mm

centre of cable, centre of duct to centreof trefoil group or duct

f) Current ratings based three customary installation methods :

1 ) Laid direct 2) In single way ducts & 3) In air

g) Single core cables installed in trefoil arrangement or in trefoil ducts.

Sustained current rating (Amperes) (50Hz)(Applied to our product 6941XL / 6941XLSOH / 6U81S / FR1CXL)

Sustainsd current rating for XLPE insulated cables

www.mes.com.hk

Page 48: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCablesMAS R

48

Sustained current rating (Amperes) (50Hz)(Applied to our product 6942XL to 6944XL, 6942XLSOH to 6944XLSOH and 6942XFR to 6944XFR)

Notes

1. Generally, the current rating will be changed if there is a difference from the standard conditions. The

rating for most conditions can be calculated by multiplying the sustained current rating by factors(s) which

can be consulted with us.

2. In normal conditions, if a cable directly buried in the ground is operated under continuous load (100% load

factor) at the maximum conductor temperature, the thermal resistivity of the soil surrounding the cable

may, in the course of time, increase from its original value as a result of drying-out proccesses. As a

consequence, the conductor temperature may greatly exceed the maximum value. If such operating

conditions are foreseen, adequate provisions shall be made.

Nominalconductor

area

600/1000V three single core cablesin trefoil arrangement

Direct Buried Duct Air Direct Direct Buried Air

600/1000V one three or four coreamrmoured cable

1 2 3 4 5 6 7

(mm2) A A A A A A

1.5 38 31 31 32 26 26

2.5 49 41 41 42 34 35

4 69 53 55 55 45 47

6 81 67 70 69 56 59

10 109 89 95 92 75 82

16 141 115 126 119 96 107

25 183 148 164 152 124 140

35 219 178 202 182 149 172

50 259 211 244 217 177 209

70 317 260 306 266 218 263

95 381 313 378 319 263 324

120 433 357 437 363 300 376

150 485 401 499 406 338 430

185 547 455 576 458 382 495

240 632 527 680 529 442 564

300 708 592 775 592 496 666

400 799 669 892 667 570 766

wwwwww.mes.com.hk

Page 49: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Technical InformationCables

49

Correction factorXLPE insulated cables

Ambient temperature( oC )

PVC insulated( 70oC )

Correction factor

Thermosetting insulated ( 90oC )

25 1.03 1.02

30 1.00 1.00

35 0.94 0.96

40 0.87 0.91

45 0.79 0.87

50 0.71 0.82

55 0.61 0.76

60 0.50 0.71

65 0.35 0.65

70 - 0.58

75 - 0.50

80 - 0.41

85 - 0.29

Current rating correction factors for ambient temperature

Tabulated figures quoted from ERA 69-30 Pt. V

Tabulated figures quoted from BS7671 of the 16th Edition of the IEE Wiring Regulations

www.mes.com.hk

Ambient temperature ( oC ) Laid direct In ducts In air

10 1.03 1.03 1.11

15 1.00 1.00 1.07

20 0.97 0.97 1.04

25 0.93 0.93 1.00

30 0.89 0.89 0.96

35 0.86 0.86 0.92

40 0.82 0.82 0.88

45 0.77 0.77 0.83

50 0.73 0.73 0.78

55 0.68 0.68 0.73

60 0.63 0.63 0.68

65 0.58 0.58 0.62

70 - - 0.55

75 - - 0.48

80 - - 0.39

85 - - 0.28

MAS R

Page 50: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

Non-armoured, sheathed cables Armoured cables

*Overall diameter(D)of cables(mm)

Horizontal #mm

Vertical #mm

Horizontal #mm

Vertical #mm

Cable construction

Non-armoured with circular conductors

*Overall diameter orConductor type

Factor to be applied to the O.D.*of cable to determine the minimum

internal bending radius

3(2)#

4(3)#

6

Non-armoured with shaped conductors any 8

Armoured with circular conductors any 6

Armoured with shaped conductors any 8

Flexible cords< 25mm

< 25mm 3 (fixed situations)

6 (subject to flexing)

Recommended minimum bending radius

Notes

* To be taken as the major axis for flat cables

# The figures in brackets relates to single core with circular stranded conductors, installed in conduit ducting

or trunking.

Recommended maximum spacing of cleats/clips for fixed wiring of single cables

Notes

* To be taken as the major axis for flat cables# The spacings stated for horizontal runs may be applied also to runs at an angle of more than 30O or less

from the vertical, the vertical spacings are applicable.

www.mes.com.hk50

< 10mm

>10 < 25

> 25

D < 9 250 400 - -

9 < D < 15 300 400 350 450

15 < D < 20 350 450 400 550

20 < D < 40 400 550 450 600

40 < D < 50 600 800 900 1100

50 < D < 60 750 1000 950 1100

60 < D < 70 900 1200 1000 1200

70 < D 1000 1400 1200 1400

Technical InformationCablesMAS R

Requirements for installation of cables and flexible cords

Page 51: Part 1 Industrial & Domestic Cables Part 2 Fireres Cables 600/1000V 1/C Cu/FR/LSOH Conduit Wirings FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOH 600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH Fire

6491X 450/750V 1/C Cu/PVCConduitWirings

6491LSOH 450/750V 1/C Cu/LSOH

6181Y 600/1000V 1/C Cu/PVC/PVCSurfaceWirings/PowerCables

6U81S 600/1000V 1/C Cu/XLPE/PVC

6U81LSOH 600/1000V 1/C Cu/XLPE/LSOH

FlexibleCords 3183Y 300/500V 3/C Cu/PVC/PVC

6941XL 600/1000V 1/C Cu/XLPE/PVC/AWA/PVC

6942XL 600/1000V 2/C Cu/XLPE/PVC/SWA/PVC

6943XL 600/1000V 3/C Cu/XLPE/PVC/SWA/PVC

6944XL 600/1000V 4/C Cu/XLPE/PVC/SWA/PVCXLPE

Armoured

Power

Cables 694nXL 600/1000V n/C Cu/XLPE/PVC/SWA/PVC

6941XLSOH 600/1000V 1/C Cu/XLPE/LSOH/AWA/LSOH

6942XLSOH 600/1000V 2/C Cu/XLPE/LSOH/SWA/LSOH

6943XLSOH 600/1000V 3/C Cu/XLPE/LSOH/SWA/LSOH

6944XLSOH 600/1000V 4/C Cu/XLPE/LSOH/SWA/LSOH

694nXLSOH 600/1000V n/C Cu/XLPE/LSOH/SWA/LSOH

FR1CConduitWirings

Part 2 Fires Cables

ConstructionCable Ref.Types

Part 1 Industrial & Domestic Cables

600/1000V 1/C Cu/FR/LSOH

FR1CXL 600/1000V 1/C Cu/FR/XLPE/LSOHPowerCable

600/1000V 2/C Cu/FR/XLPE/LSOH/SWA/LSOH

6943XFR 600/1000V 3/C Cu/FR/XLPE/LSOH/SWA/LSOH

6942XFR

IEC Standard Used

60227 IEC01 of IEC60227-3

Relevant Known BSStandard

BS6004: 2000 Table 4

IEC60502-1: 2004IEC60754 / IEC61034

BS7211: 1998 Table 3

IEC60502-1: 2004 BS6004: 2000 Table 7

IEC60502-1: 2004 BS7889: 1997

IEC60502-1: 2004IEC60754 / IEC61034

Not available

60227 IEC53 of IEC60227-5 BS6500: 2000 Table 27

IEC60502-1: 2004 BS5467: 1997 Table 4

IEC60502-1: 2004 BS5467: 1997 Table 6

IEC60502-1: 2004 BS5467: 1997 Table 8

IEC60502-1: 2004 BS5467: 1997 Table 10

IEC60502-1: 2004 BS5467: 1997

IEC60502-1:2004 BS6724: 1997 Table 4

IEC60502-1: 2004 BS6724: 1997 Table 6

IEC60502-1: 2004 BS6724: 1997 Table 8

IEC60502-1: 2004 BS6724:1997 Table 10

IEC60502-1: 2004 BS6724: 1997

IEC60331 IEC60331

IEC60502-1: 2004 Not available

IEC60502-1:2004IEC60331 BS7846: 2000 Table 4

IEC60502-1: 2004IEC60331

BS7846: 2000 Table 5

Fire

Resistant

Armoured

Power

Cables

Technical InformationCablesMAS R

6944XFR 600/1000V 4/C Cu/FR/XLPE/LSOH/SWA/LSOH

600/1000V n/C Cu/FR/XLPE/LSOH/SWA/LSOH

IEC60502-1: 2004IEC60331 BS7846: 2000 Table 6

694nXFRIEC60502-1: 2004IEC60331

BS7846: 2000

IEC and BS Standards References

New Core Colours

SINGLE PHASE

RED to BROWN

Existing New Harmonised

BLACK to BLUE

BLUE to GREY

BLACK to BLUE

www.mes.com.hk51

YELLOW to BLACK

THREE PHASE

RED to BROWN

Existing New Harmonised

THREE PHASE

Existing New Harmonised