WHEN REPLACING PCB ASSEMBLIES, PLEASE WEAR AN ESD WRIST STRAP AND CONNECT IT TO ELECTRICAL GROUND RISK OF FIRE AND ELECTRICAL SHOCK Contact, improper installation, or improper servicing MAY RESULT IN DEATH OR SERIOUS INJURY! Fixture must be installed by a qualified electrician only. Fixture is intended for installation in accordance with the National Electrical Code, local and federal code specifications. Disconnect power at electrical panel before servicing. Retain these instructions for maintenance reference. ADVERTENCIA: RIESGO DE INCENDIO O IMPACTO ELÉCTRICO Conexión, instalación inapropiada o servicio incorrecto PUEDE CAUSAR MUERTE O HERIDAS GRAVES.La luminaria debe ser instalada únicamente por un eléctrico califi cado. La luminaria debe instalarse de acuerdo al Norma eléctrica nacional, al igual que especificaciones locales y normas federales. Se debe desconectar la corriente eléctrica antes de realizar la mantención. Conservar estas instrucciones como referencia para futuras mantenciones. ATTENTION: RISQUE D’INCENDIE ET D’ELECTROCUTION Une installation, un entretien ou un contact physique non conforme pourraient mener à un DANGER DE MORT OU DE BLESSURE GRAVE! L’appareil doit être installé uniquement par un électricien professionnel qualifi é. L’installation doit respecter le code électrique national de même que les lois locales et fédérales en vigueur. Veuillez fermer l’alimentation électrique au panneau principal avant tout entretien. Conserver ces instructions pour référence et tout entretien futur. NOTE National or municipal codes must be followed regarding fixture installation and set back of thermal insulating material from luminaire. As a guideline, any insulation material must be held away from the luminaire by a minimum of 3". Fixtures are not designed for direct contact with thermal insulation. PANOS 5.25" Round Wall Wash – Flanged The following installation instructions relate to the options below INSTALLATION INSTRUCTIONS 5.25" PANOS Wall Wash, Flanged, Round Fixture and driver module are each ordered separately. Fixture ships with installation ring. Driver module ships with mounting plate. Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

Transcript of PANOS 5.25 Round Wall Wash – Flanged -...

Page 1: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

WHEN REPLACING PCB ASSEMBLIES, PLEASE WEAR AN ESD WRIST STRAP AND CONNECT IT TO ELECTRICAL GROUND

RISK OF FIRE AND ELECTRICAL SHOCKContact, improper installation, or improper servicing MAY RESULT IN DEATH OR SERIOUS INJURY! Fixture must be installed by a qualified electrician only. Fixture is intended for installation in accordance with the National Electrical Code, local and federal code specifications. Disconnect power at electrical panel before servicing. Retain these instructions for maintenance reference.

ADVERTENCIA: RIESGO DE INCENDIO O IMPACTO ELÉCTRICOConexión, instalación inapropiada o servicio incorrecto PUEDE CAUSAR MUERTE O HERIDAS GRAVES.La luminaria debe ser instalada únicamente por un eléctrico califi cado. La luminaria debe instalarse de acuerdo al Norma eléctrica nacional, al igual que especificaciones locales y normas federales. Se debe desconectar la corriente eléctrica antes de realizar la mantención. Conservar estas instrucciones como referencia para futuras mantenciones.

ATTENTION: RISQUE D’INCENDIE ET D’ELECTROCUTIONUne installation, un entretien ou un contact physique non conforme pourraient mener à un DANGER DE MORT OU DE BLESSURE GRAVE! L’appareil doit être installé uniquement par un électricien professionnel qualifi é. L’installation doit respecter le code électrique national de même que les lois locales et fédérales en vigueur. Veuillez fermer l’alimentation électrique au panneau principal avant tout entretien. Conserver ces instructions pour référence et tout entretien futur.

NOTENational or municipal codes must be followed regarding fixture installation and set back of thermal insulating material from luminaire. As a guideline, any insulation material must be held away from the luminaire by a minimum of 3". Fixtures are not designed for direct contact with thermal insulation.

PANOS 5.25" Round Wall Wash – Flanged

The following installation instructions relate to the options below

INSTALLATION INSTRUCTIONS

5.25" PANOS Wall Wash, Flanged, Round

Fixture and driver module are each ordered separately.Fixture ships with installation ring. Driver module ships with mounting plate.

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

Page 2: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

INSTALLATION INSTRUCTIONS

1 Cut opening in ceiling. Ensure a minimum clearance of 2" around proposed fixture location within the ceiling before beginning.

3 Install installation ring into ceiling making sure that the side of the ring with the red sticker is next to the wall. Fastening springs will flip over, pull down on springs to secure ring to ceiling structure. Adjust mounting brackets so bottom of flange is flush with ceiling line. (1-9/16" ceiling thickness, max.)

2 Place mounting plate* over ceiling opening, working through adjacent ceiling tile.*For standard installation, this step is only required for accessible ceilings.

4 Make electrical connections as shown. Ground rough-in usingthe green ground wire. For non-dimming installations, cap off the two control wires and connect the hot, neutral, and ground as normal. For 0-10V dimming applications, connect the DIM+ to the positive, and the DIM- to the negative. Note: Driver module may vary based on ceiling type.

STANDARD INSTALLATION

PANOS 5.25" Round Wall Wash – Flanged

ROUND

5-7/8" diameter

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

ceiling tile

mounting plate

Red Sticker

Zumtobel Lighting, Inc. ©20173300 Route 9WHighland, NY 12528-2630

February 10, 2017 10:02 AM

[email protected]

www.zumtobel.us

In a continuing e�ort to o�er the best product possible, we

zumtobel.us are the most recent version and supersede all other versions that exist in any other printed or electronic form.

Page 2

Standard Installation

1 Cut opening in ceiling Ensure a minimum clearance of 2” around

Square Round

2-11/16”x2-11/16” 2-11/16” diameter

1.

2.

1.

BLACK = LINEWHITE = NEUTRALGREEN = GROUNDDIM+ = E1DIM- = E2

ceiling le

installa on plate(square)

ceiling le

installa on plate(round)

Installation Instructions

PANOS 2.25”Square & Round, Flanged

Downlight

2 Place installation plate* over ceiling opening, working through adjacent ceiling tile. *For standard installation, this step is only required for accessible ceilings.

3 Install installation ring into ceiling Fastening springs will fold down, pull down on springs to secure ring to ceiling structure. Adjust

ceiling thickness, max.)

4 Make electrical connections as shown. Ground rough-in using the green ground wire. For non-dimming installations, cap o� the two con-trol wires and connect the hot, neutral, and ground as normal. For 0-10V dimming applications, connect the DIM+ to the positive, and the DIM- to the negative. Note: Driver module may vary based on ceiling type.

BLACK –LINE

WHITE –NEUTRAL

GREEN – GROUND

PURPLE –DIM+/E1

GRAY – DIM-/E2

Page 3: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

USE U.S. TOLERANCES BELOWUNLESS OTHERWISE SPECIFIED1. ALL DIMENSIONS ARE IN MILLIMETERS. 2. TOLERANCES ON: A. DECIMALS .X 0.5 .XX 0.2 B. WHOLE NUMBERS 0.8 C. ANGLES 1 3. REMOVE ALL BURRS AND SHARP EDGES TO 0.4 MAX. 4. DO NOT SCALE DRAWING SURFACE FINISH: SURFIN

Chked. date: - Copyright according to ISO 16016

Chked. by: - -Date: 6/25/2018 - TRIPAR_T D-Name: S.Remer Description Document IProject: - Basic material: - Size: DSurface treatment/aftertreatment: - Scale: 1:1 3RD ProjectionGen. tolerance: Sheetm. part tol.: Plastic part tol.: Info.: -

Issue no. Issue date Issue by Issue chked. by Issue text

D

C

B

A

D

C

B

A

8 7 6 5 4 3 2 1

8 7 6 5 4 3 2 1

1:1.333

FEED BY OTHERS

LED FEED WIRE

DRIVER MODULE driver module

feed

LED feed wire

INSTALLATION INSTRUCTIONS

5 For accessible ceilings place driver module through openingin adjacent tile. Secure fixture to permanent structure as per local code. Use bend up tabs as required.

6 Connect driver module to fixture as shown.Red = LED +Black = LED –7 Connect* safety cord to fixture with safety clip as shown.*This step is only required for inaccessible ceilings.

5 For inaccessible ceilings place driver module through ceiling cutout.

8 Insert fixture into housing after removing red sticker from installation ring. Twist until fixture clicks into place. Pay close attention to ensure that reflector points to wall wash surface.

STANDARD INSTALLATION (continued)

PANOS 5.25" Round Wall Wash – Flanged

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

safety cord

fixture power cable (female)

fixture power cable (male)

safety clip

drivermodule

safety cord

Page 4: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

INSTALLATION INSTRUCTIONS

5 Place mounting plate over ceiling opening by folding plate and inserting it through ceiling cutout. Ensure that holes in the plate align properly with ceiling cutout.6 Install installation ring into ceiling as per standard instructions.

2 Place mounting plate over ceiling opening working throughopening in adjacent ceiling tile. Ensure that holes in the plate align properly with ceiling cutout.3 Install driver module in ceiling.4 Install installation ring into ceiling as per standard instructions.

7 Make electrical connections as shown. Ground rough-in usingthe green ground wire. For non-dimming installations, cap off the two control wires and connect the hot, neutral, and ground as normal. For 0-10V dimming applications, connect the DIM+ to the positive, and the DIM- to the negative. For EM installation, attach the switched hot to the orange line in the whip. Note: Driver module may vary based on ceiling type.

EMERGENCY INSTALLATION

PANOS 5.25" Round Wall Wash – Flanged

INACCESSIBLE CEILINGS

ACCESSIBLE CEILINGS

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

BLACK = UNSWITCHED HOTWHITE = NEUTRALGREEN = GROUNDDIM += E1DIM - = E2ORANGE = SWITCHED HOT

USE U.S. TOLERANCES BELOWUNLESS OTHERWISE SPECIFIED1. ALL DIMENSIONS ARE IN MILLIMETERS. 2. TOLERANCES ON: A. DECIMALS .X 0.5 .XX 0.2 B. WHOLE NUMBERS 0.8 C. ANGLES 1 3. REMOVE ALL BURRS AND SHARP EDGES TO 0.4 MAX. 4. DO NOT SCALE DRAWING SURFACE FINISH: SURFIN

Chked. date: - Copyright according to ISO 16016Zumtobel Group

Chked. by: - -Date: 6/25/2018 - TRIPAR_T D-Name: S.Remer Description Document IProject: - Basic material: - Size: DSurface treatment/aftertreatment: - Scale: 1:1 3RD ProjectionGen. tolerance: EN 22768 mK Sheetm. part tol.: DIN 6930-2 m Plastic part tol.: DIN 16742 Info.: -

Issue no. Issue date Issue by Issue chked. by Issue text

D

C

B

A

D

C

B

A

8 7 6 5 4 3 2 1

8 7 6 5 4 3 2 1

FEED BY OTHERS

EM PACKREMOVE WITH COVER

TO ACCESS WIRING

1:1.333

LED FEEDW/WHITE CONNECTOR

EM TEST SWITCH CONNECTIONW/YELLOW CONNECTOR

DRIVER MODLUE

EM pack

driver module

feed

LED feed

test switch connection

RED – UNSWITCHED HOT

BLACK –LINE

WHITE –NEUTRAL

GREEN – GROUND

PURPLE –DIM+/E1

GRAY – DIM-/E2

1 Cut opening in ceiling and drill hole for EM button. Refer to page 2 for fixture cutout sizes. Dimensions for pipe hole size and position are below. In above diagrams, X refers to the distance between the centers of the two holes.

X

ceiling cutout

pipe hole cutout

Pipe Hole Diameter:

Fixture Shape:

TILED

3/8"

TILED

3-9/16"

SHEETROCK

7/16"

SHEETROCK

3-3/4"

Page 5: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

INSTALLATION INSTRUCTIONS

8 For inaccessible ceilings, insert driver module into ceiling andconnect driver module to fixture as per standard instructions.9 Connect driver module to test switch as shown above.Purple = +Brown = –

10 Install fixture into ceiling as per standard instructions.11 Install pipe hole cover into installation frame through ceilingcutout. The pipe hole cover will be held in place by a bracket that slides into place.

EMERGENCY INSTALLATION (Continued)

PANOS 5.25" Round Wall Wash – Flanged

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

accessible ceilings inaccessible ceilings

Page 6: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

INSTALLATION INSTRUCTIONS

1 Unpack hanger bar assembly.2 Cut opening in ceiling using dimensions on page 2.3 Attach mounting plate to brackets Using a 8-32 self tapping screw (provided by Zumtobel).

7 Bend tabs on hanger bar ends until they are able to lay flush against stud.8 Secure hanger bar onto stud per local code. Hammer in tabs onhanger bars to secure to wood or screw through holes in hanger bar with 3/16" lag screw.9 Installation of fixture as per standard instructions may continueafter sheet rock has been installed. Bracket height may need to be adjusted to ensure plate is flush with sheet rock.

4 Remove ceiling tile adjacent to the ceiling cutout.5 Install hanger bar onto ceiling grid, working through the opening in the adjacent tile. Hanger bar length can be adjusted based on ceiling type. Secure fixture to permanent structure per local code. Construction wire may be looped through holes provided.6 Replace adjacent ceiling tile and proceed with standard installation instructions.

HANGER BAR INSTALLATION (Optional)

PANOS .25" Round Wall Wash – Flanged

INACCESSIBLE CEILINGS

ACCESSIBLE CEILINGS

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

Note: Hanger bar may only be installed prior to sheet rock installation.

Page 7: PANOS 5.25 Round Wall Wash – Flanged - Zumtobelzumtobel.us/media/product_downloads/2018-08-10_14... · two control wires and connect the hot, neutral, and ground as 0-10V dimming

MAINTENANCE

PANOS .25" Round Wall Wash – Flanged

INSTALLATION INSTRUCTIONS

Zumtobel Lighting, Inc. ©2018 3300 Route 9W, Highland NY 12528-2630 845-691-6262 | 800-448-4131 [email protected] 080618_F

RELAMPING Contact Zumtobel at 1-800-448-4131 for replacement LED module. Please provide the original fixture description per the label inside the fixture. Once replacement LED module has been received, follow these steps.

CLEANING Wipe with soft lint-free cloth. Do not use glass cleaner or other solvents.

ACCESS TO DRIVERFor Accessible Ceilings: Remove adjacent ceiling tile to access junction box and driver. The driver is mounted on junction box cover with internal wiring. For Inaccessible Ceilings: After trim removal continue pulling trim to access driver box housing and guide through ceiling opening. Remove cover on enclosure to access driver and wiring.

1 Please wear clean cotton gloves and electrostatic discharge protection. At the minimum, an ESD wrist strap should be worn and properly grounded.

2 Turn power off.

3 Disconnect LED wire at connector by pushing down on connector side clips then pulling apart.

4 Remove LED Board. Gently twist refl ector CCW and remove from trim assembly. Using a thin blade screwdriver (or similar) gently pry back tabs on lens housing and remove from heatsink.Unscrew the ‘2’ Torx screws and remove the LED board/board holder.

5 Using a scraper (putty knife) remove the old thermal film from casting and wipe clean with a clean cloth.

6 Remove transparent film protection from both sides of the new thermal film with your fingers.

7 Place the new thermal film on bottom of new LED board and align LED board in holder.

8 Align the mounting holes in LED board to the holes in the aluminum casted heatsink.

9 Using the 3 mm Torx screws, and the screwdriver which has a blade length of 6" long, install the screws into holes on the LED board holder.

10 Reverse Procedure to reinstall fixture.

11 Turn on the power.

12 For disposal, please send the old LED module back to Zumtobel using the ESD bag provided.