Panduit Hiland Grounding

32
Introduction Grounding Roadmaps Equipment & Rack Grounding Kits Common Bonding Network (CBN) Components Crimping Tools Technical Information Index S TRUCTURED G ROUND SYSTEM FOR DATA CENTER GROUNDING Table of Contents INTRODUCTION How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 GROUNDING ROADMAPS Common Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 EQUIPMENT & RACK GROUNDING KITS Features and Benefits — PANDUIT ® STRUCTUREDGROUND System for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 COMMON BONDING NETWORK (CBN) COMPONENTS BICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17 Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 CRIMPING TOOLS Hand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 CONTOUR CRIMP Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 TECHNICAL INFORMATION PANDUIT ® STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28 Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29 Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 INDEX Part Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 1 S TRUCTURED G ROUND GROUNDING SYSTEM CATALOG WW - PCCB 04

description

CABLING

Transcript of Panduit Hiland Grounding

Page 1: Panduit Hiland Grounding

Introduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Table of ContentsINTRODUCTION

How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

GROUNDING ROADMAPSCommon Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

EQUIPMENT & RACK GROUNDING KITSFeatures and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System

for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

COMMON BONDING NETWORK (CBN) COMPONENTSBICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

CRIMPING TOOLSHand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24CONTOUR CRIMP ™ Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

TECHNICAL INFORMATIONPANDUIT ® STRUCTUREDGROUND ™ System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE)

per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

INDEXPart Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

1

STRUCTUREDGROUND™ GROUNDING SYSTEM C A T A L O G – W W - P C C B 0 4

Page 2: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

2

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

How to Use This Catalog

Common Bonding Network (CBN)page 4

Grounding Roadmapspages 5-9

Detailed ProductInformationpages 11-23

Technical Information — Includes Application Standards and BICSI TDM Manual, 10th Editionpages 28-30

Detailed ToolInformationpages 24-27

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

4

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to groundyour building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,IEEE Std 1100 (IEEE Emerald Book), UL and CSA

Common Bonding Network (CBN)

TelecommunicationsRoom(see roadmap on page 8)

Data Center(see roadmap on page 6)

Service Entrance(see roadmap on page 5)

See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.For more data center grounding information, see www.panduit.com/dcgrounding.

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

6

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Data Center Grounding Roadmap

Back of Racks Shown

Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

AC Panel*

2

2

3

3

4

1

1

5

Raised Floor Pedestal

Common Bonding Network (CBN)

Building Steel

Conduit

TelecommunicationsBonding Backbone

(TBB)

Data Equipment Racks3

Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

Copper Compression HTAP and Clear Cover: HTWC(see page 19)

Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

3

1 4

Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

5

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of theraised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance withapplicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

7For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory)

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Data Center Rack Grounding (Raised Floor)

Back of Rack Shown

Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

Common Bonding Network – typically #2 AWGbare copper code conductor is used underfloor

Equipment Jumper Kit 24" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 36" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 24" L, 45° Bent: RGEJ(see page 12)

Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

Rack Grounding Strip Kit: RGS(see page 11)

Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

Paint Piercing GroundingWasher Kit: RGW(see page 13)

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

20

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Code/Flex Conductor HTAP

• Used to tap into continuous conductors as asplice or pigtailing

• Each HTAP terminates a wide range ofconductor sizes and combinations of codeand flex conductors Class G, H, I andLocomotive to suit a variety of applications

• Slotted design allows quick and easyassembly of conductor to HTAP using 3PANDUIT 94 V-0 cable ties included

• Tap grooves are separated from one anotherallowing them to function independently soHTAP can be used with a single or multipletaps providing maximum design andinstallation flexibility

• Color coded and marked with PANDUIT dieindex numbers for proper crimp die selection

• Requires crimping tools and dies, see pages25, 26 and 27

• UL Listed and CSA Certified for applicationsup to 600V when crimped with PANDUITand specified competitor crimping tools andPANDUIT crimping dies

• Tin plated to inhibit corrosion

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

For Making Parallel and Multiple Tap Connections on Code and Flex Conductors

HTAP

TAP

RUN

Part Number

Copper Conductor Size RangeFigure

Dimensions (In.)

PANDUITCrimping

Tool

PANDUITDie Color& Die No.

WireStrip

Length(In.)

Std.Pkg.Qty.

WireStrandType Run Tap 1 Tap 2 Tap 3 L W H

HTCT6-6-1Code

#6 - #10AWG

#6 - #14AWG

— —

.61 .40 .99 CT-930, CT-2931 Orange,PH6

11/16 1

Flex#6 - #10

AWG#6 - #14

AWG

HTCT2-2-1Code

#2 - #6AWG

STR/SOL

#2 - #6 AWGSTR/SOL

#8 - #14AWG

#8 - #14AWG

.76 .61 1.55 CT-930, CT-2931 Brown,PH2

13/16 1

Flex#2 - #8AWG

#2 - #8 AWG #8 - #14AWG

#8 - #14AWG

HTCT250-2-1Code

250 kcmil -#2 AWG

#2 - #6 AWGSTR/SOL

#8 - #14AWG

.92 .96 1.92 CT-930, CT-2931 Purple,PH25

1 1

Flex4/0 - #2AWG

#2 - #8 AWG #8 - #14AWG

HTCT250-250-1Code

250 kcmil -#2 AWG

250 kcmil -#2 AWG

— —

.90 .89 1.92 CT-930, CT-2931 Purple,PH25

1 1

Flex4/0 - #2AWG

4/0 - #2AWG

TAP 1

RUN

H

WL

WRUN

TAP 1TAP 2

TAP 3

L

H

W L

RUN

H

TAP 1 TAP 2 TAP 1

W L

H

RUN

HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

26

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool• Two stage rapid advance hydraulic system minimizes

cycle time• Provides UL Listed and CSA Certified connections on

PANDUIT ® PAN-LUG ™ copper and aluminum lugs andsplices and copper taps

• Open "C-Head" design allows easy loading of crimpingdies and connectors, saves time

• Rubber boot on crimp head provides abrasion protection• Ram automatically retracts when crimp cycle is complete

• Tool provided with two, high capacity 12 VDC rechargeablenickel-metal hydride batteries — provides for continuousoperation and eliminates "memory" build-up, one hourcharge time

• Eight second crimp cycle time provides quick terminations,saves time

• Uses industry standard Makita* batteries and charger —industry proven reliability easy to obtain from localretail sources

• Requires crimping dies, see page 27• Dies installed using spring loaded die retention pins — no

need for tools• Crimp head rotates 360 degrees — provides versatility for

use in restricted spaces

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.*Makita is a registered trademark of Makita Corporation in the United States.

Part Number Part Description

Std.Pkg.Qty.

CT-2931 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors:

• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor• Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor• Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor• Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor• Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor• Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor

Warranty: 3 years

CT-2931 includes:• Tool• Two 12 VDC, rechargeable NiMH batteries• One battery charger• Steel tool case with storage for batteries, charger and crimp dies

1

Page 3: Panduit Hiland Grounding

3For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

What are the effects of improper grounding?

Decreased Efficiency• Electrical noise is introduced on data cables when surges are not properly dissipated by the grounding system.They cause

faulty data signals and dropped packets, thus decreasing the throughput and overall efficiency of your network.

Lower Reliability• According to insurance industry data, improper grounding of communication systems leads to $500 million per year of

damage to property and/or equipment due to lightning. (1)

• The Information Technology Industry Council states that grounding is the single-most important factor in reliable networkequipment performance. (2)

• More than 90% of problems in data communications equipment, including reboot, lockup, and data corruption, aretraced to problems with grounding. (3)

• Industry experts estimate that 27%-33% of damaged equipment in a user's facility is caused by electrostatic discharge.The component cost of repairing damaged equipment is substantial for complex circuit boards, especially when laborand downtime are considered. (4)

• According to the IEEE, the typical AC third prong ground is almost never sufficient to prevent damage to network equipment. (5)

Safety Risks• Personal injury from electric shock caused by improper grounding can cause immeasurable human suffering and

significant expense.• Potential fire hazards exist when heat is generated from electrical surges that find a high resistance path to ground.

Can you afford improper grounding?

Network equipment, such as switches, routers and storage devices, costs anywhere from thousands of dollars to hundreds ofthousands of dollars.The cost of proper grounding is only a tiny fraction of the cost of the equipment it is protecting.

Clearly the biggest cost of improper grounding is the inability to service customers properly.

PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding gives you what you need to properly protectyour investment.

TThhee PPuurrppoossee ooff GGrroouunnddiinnggThe grounding system is not just an insurance policy against a lightning strike. It is an active,functioning system that provides protection for personnel and equipment. Proper grounding isessential for efficient network performance.

The purpose of the grounding system is to create a low impedance path to earth ground for electricalsurges and transient voltages. Lightning, fault currents, circuit switching (motors turning on and off),and electrostatic discharge are the common causes of these surges and transient voltages. Aneffective grounding system minimizes the detrimental effects of these electrical surges.

A properly designed grounding system is one that is intentional, visually verifiable, adequately sizedto handle expected currents safely, and one that directs these potentially damaging currents awayfrom sensitive communication equipment. Any metallic component that is part of the data centerinfrastructure (such as equipment, racks, ladder racks, enclosures, cable trays, etc.) must be bondedto the grounding system.

1. Mike Holt, "Prevent Shocks in Your Communications: Understanding How the NEC Relies on Ground Resistance Theory Leads to aSuccessful Application of Communications Grounding," Electrical Construction & Maintenance, September 2002.

2. Information Technology Industry Council (ITI, formerly CBEMA), Guidelines for Grounding Information Technology Equipment. InformationLetter, ITI, 15 February 1997.

3. Donald G. Pennington and Paul Holzer, "Doing Battle with Those Ground Transients," Electronic Engineering Times, 8 January 1996.

4. ESDA, "Fundamentals of ESD: Part 1 — An Introduction to ESD," 2001, <http://www.esda.org/basics/part1.cfm> (1 October 2004).

5. Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEEStd 1100-1999, 1999.

Page 4: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

4

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to groundyour building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,IEEE Std 1100 (IEEE Emerald Book), UL and CSA

Common Bonding Network (CBN)

TelecommunicationsRoom(see roadmap on page 8)

Data Center(see roadmap on page 6)

Service Entrance(see roadmap on page 5)

See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.For more data center grounding information, see www.panduit.com/dcgrounding.

Page 5: Panduit Hiland Grounding

5For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

Copper Compression HTAP and Clear Cover: HTWC(see page 19)

Service Entrance Grounding Roadmap

Bronze, U-Bolt Grounding Clamp: GPL(see page 22) connected by a cable to

(HTAP)2

Bronze, Water Pipe Grounding Clamp: KP(see page 23)

3

4

1

1

2

AC Service Entrance

Earth Ground

3

3

3

2

1

6

3

Telecommunications BondingBackbone (TBB)**

Grounding Equalizer (GE)

Cable Entrance

AC Panel*

Water Meter4 4

• Complies with J-STD-607-A and IEEE Std 1100 (IEEE Emerald Book)

• Grounding Equalizer (GE) is required when two or more Telecommunications Bonding Backbones (TBB) are used within amulti-story building; bond TBBs together with a GE at the top floor and at a minimum of every third floor in between

Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

5

5

Telecommunications MainGrounding Busbar (TMGB) andBusbar Label (see page 15)

7

7

Bronze, Grounding Rod Clamp: WB(see page 23) connected by a cable to

(U-Bolt Grounding Clamp)

6

Conduit

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.**Specification J-STD-607-A specifies different size conductors based on the length of the Telecommunications Bonding Backbone (TBB). See page 30 forRecommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) Per J-STD-607-A.

2

Page 6: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

6

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Data Center Grounding Roadmap

Back of Racks Shown

Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

AC Panel*

2

2

3

3

4

1

1

5

Raised Floor Pedestal

Common Bonding Network (CBN)

Building Steel

Conduit

TelecommunicationsBonding Backbone

(TBB)

Data Equipment Racks3

Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

Copper Compression HTAP and Clear Cover: HTWC(see page 19)

Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

3

1 4

Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

5

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of theraised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance withapplicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

Page 7: Panduit Hiland Grounding

7For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Data Center Rack Grounding (Raised Floor)

Back of Rack Shown

Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

Common Bonding Network — typically #2 AWGbare copper code conductor is used underfloor

Equipment Jumper Kit 24" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 36" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 24" L, 45° Bent: RGEJ(see page 12)

Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

Rack Grounding Strip Kit: RGS(see page 11)

Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

Paint Piercing GroundingWasher Kit: RGW(see page 13)

Page 8: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

8

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Telecommunications Room Grounding Roadmap

2

1

1

Building Steel

3

3

5

Grounding Equalizer (GE)

Conduit

AC Panel*

Back of Racks Shown

Telecommunications GroundingBusbar (TGB) and Busbar Label(see page 15)

Copper Compression, Two-Hole, LongBarrel with Window Lug: LCC-W (see pages 16-17)

Copper Compression HTAP and Clear Cover: HTWC(see page 19)

Bronze, U-Bolt Grounding Clamp: GPL(see page 22)2

3

1 4

Telecommunications Grounding and BondingConductor Label Kit: LTYK(see page 15)

5

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.A typical overhead cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure allof the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The PANDUITBonding/Grounding System does not insure required bonding of the overhead cabling system metallic components.

3

4

TelecommunicationsBonding Backbone

(TBB)

• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), ULand CSA

• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity betweenmetallic components and the grounded rack

• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet membersto the rack grounding strip

1

Page 9: Panduit Hiland Grounding

9For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Telecommunications Room Rack Grounding

Aisle Ground — typically #2 AWG insulated copper codeconductor is used overhead

Back of Rack Shown

Common Bonding Network (CBN) toRack Jumper Kit: RGCBNJ(see page 11)

Equipment Jumper Kit 24" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 36" L, 90° Bent: RGEJ(see page 12)

Equipment Jumper Kit 24" L, 45° Bent: RGEJ(see page 12)

Electrostatic Discharge (ESD)Port Kit recommended foruse on front and back of rack:RGESD (see page 13)

Rack Grounding Strip Kit: RGS(see page 11)

Bonding Screws are used tomount patch panels to the front ofthe rack: RGTBS (see page 14)

Paint Piercing GroundingWasher Kit: RGW(see page 13)

Page 10: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

10

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Rack Grounding Strip is made from highconductivity, low resistance wrought copperand tin plated to inhibit corrosion, providing

the lowest impedance path to ground

Jumper has UL, VW-1 flame rated greeninsulation and is factory terminated withcopper compression, two-hole, long barrelwith window lug; lug is UL Listed, CSACertified and meets NEBS Level 3 with a singlestud hole and slot which allows mounting for½" to 5/8" hole spacing and accommodatesstud sizes ¼", #12 and 6mm

Paint Piercing Grounding Washer ismade from hardened steel and electro zinc plated which inhibits corrosion to provide asuperior bond between frame members onbolt-together racks

Thread-Forming Screws are made fromelectro zinc plated steel and provide a bond tothe rack by removing paint from threadedholes without creating metal shavings

Electrostatic Discharge (ESD) Port is madefrom high conductivity, low resistance copperand tin plated to inhibit corrosion plus itfunctions as an ESD wrist strap hanger

Electrostatic Discharge (ESD) ProtectionSticker is provided in black and yellow forhigh visibility and easy identification as anESD port

Copper Compression HTAP is UL Listed andCSA Certified; used to make a highly reliable,permanent bond between the commonbonding network and common bondingnetwork (CBN) to rack jumper kit

Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System for DataCenter GroundingPANDUIT offers a variety of kits with premium components to ensure superior grounding with the highest reliability available.• Provides highest reliability with an all-copper rack

grounding system to maintain data center systemperformance and protect network equipment

• Complies with data center standard TIA-942 and is UL Listed and CSA Certified

• Incorporates a flexible design that can be used withracks which meet EIA-310-D

• Offers ease of installation — no paint scraping required to bond racks; factory terminated jumpers simplybolt in place

ElectrostaticDischarge (ESD)Port Kit(see page 13)

RackGroundingStrip Kit(see page 11)

Common Bonding Network (CBN)to Rack Jumper Kit (see page 11)

Equipment Jumper Kit(see page 12)

A

B

C

D

E

F

G

C

C

C

A

C

C

D

E

F

B

G

B

D

D

Page 11: Panduit Hiland Grounding

11For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Equipment & Rack Grounding Kits

Rack Grounding Strip Kits

• Bonds up to 44 RU per rack • EIA Universal mounting hole pattern

Common Bonding Network (CBN) to Rack Jumper Kit

• Bonds the rack grounding strip to the CBN• HTAP, included in kit, requires crimping tool and die; see

the CT-930 crimping tool on page 25, the CT-2931 crimp-ing tool on page 26 and the CD-930H-250 crimping die onpage 27

• HTAP is UL Listed and CSA Certified for applications up to600V when crimped with PANDUIT and specifiedcompetitor crimping tools and PANDUIT crimping dies;see the Termination Solutions Catalog SA-TMCB02 for thecomplete line of PANDUIT crimping tools

*An equal number of M6 x 12mm thread-forming screws also provided in each kit.**HTAP also sold separately, see page 20.

*An equal number of M6 x 12mm thread-forming screws also provided in each kit.

Part Number Part Description

Std.Pkg.Qty.

RGS134-1 Rack grounding strip; 78.65" length; .67" width; .05" thickness;provided with .16 oz (5cc) of antioxidant and three #12-24 x 1/2"thread-forming screws*

1

RGS134-10-1 10 rack grounding strips; 78.65" length; .67" width; .05" thickness;provided with .16 oz (5cc) of antioxidant and 30 #12-24 x 1/2"thread-forming screws*

1

Part Number Part Description

Std.Pkg.Qty.

Std.Ctn.Qty.

RGCBNJ660P #6 AWG jumper; 60" length; 45° bent lug on grounding strip side;provided with .16 oz (5cc) of antioxidant, two #12-24 x 1/2"thread-forming screws* and a copper compression HTAP** forconnecting to the CBN in sizes ranging from #2 AWG to 250 kcmil

1 10

Page 12: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

12

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

3" or smaller

Equipment Jumper Kits

• Bonds network equipment to rack grounding strip• Jumper kit available with both ends factory terminated to

provide a bolt on solution• Jumper kit available with one end factory terminated to

attach to the rack grounding strip; free end accommodatesunique equipment terminations

• Use jumpers with 90° bent lug, on grounding strip side, forhigh density grounding requirements up to one groundpoint per RU

• Use jumpers with 45° bent lugs, on grounding strip side, forimproved cable management

• Use 24" jumpers when network equipment ground point islocated near the grounding strip side of the rack

• Use 36" jumpers when network equipment ground point islocated away from the grounding strip side of the rack

RGEJ1024PF

3" or larger

RGEJ1057PF

Select equipment jumpers with 45° lugsfor lower density applications or shallowdepth equipment to provide improved cablemanagement.

Select 24" equipment jumpers with 90°lugs when equipment grounding connectionis close to the grounding strip.

Select 36" equipment jumpers with 90° lugswhen equipment grounding connection is onthe opposite side from the grounding strip.

How to Select the Appropriate Equipment Jumper

*An equal number of M6 x 12mm thread-forming screws also provided in each kit.

Part Number Part Description

Std.Pkg.Qty.

Std.Ctn.Qty.

#10 AWG equipment jumpers factory terminated on both endsRGEJ1024PH #10 AWG jumper; 24" length; 45° bent lug on grounding strip side

to straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

1 10

RGEJ1024PF #10 AWG jumper; 24" length; 90° bent lug on grounding strip sideto straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

1 10

RGEJ1036PF #10 AWG jumper; 36" length; 90° bent lug on grounding strip sideto straight lug on equipment; provided with .16 oz (5cc) ofantioxidant and four #12-24 x 1/2" thread-forming screws*

1 10

#6 AWG equipment jumpers factory terminated on both endsRGEJ624PH #6 AWG jumper; 24" length; 45° bent lug on grounding strip side to

straight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

1 10

RGEJ624PF #6 AWG jumper; 24" length; 90° bent lug on grounding strip side tostraight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

1 10

RGEJ636PF #6 AWG jumper; 36" length; 90° bent lug on grounding strip side tostraight lug on equipment; provided with .16 oz (5cc) of antioxidantand four #12-24 x 1/2" thread-forming screws*

1 10

#10 AWG equipment jumper factory terminated on one endRGEJ1057PF #10 AWG jumper; 57" length; 90° bent lug on grounding strip side;

provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"thread-forming screws*

1 10

#6 AWG equipment jumper factory terminated on one endRGEJ657PF #6 AWG jumper; 57" length; 90° bent lug on grounding strip side;

provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"thread-forming screws*

1 10

Page 13: Panduit Hiland Grounding

13For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingSTRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Electrostatic Discharge (ESD) Port Kit• Accommodates standard ESD wrist strap 4mm plug • Can be mounted to front or back of rack for

convenient access

• Bent 45°, acts as a hook to hold wrist strap• Barrel permanently marked with the protective earth

(ground) symbol

Paint Piercing Grounding Washer Kits• Bonds frame members on bolt-together racks• No paint scraping required

• Green color coding to indicate bonding application

Contact your local electrical distributor for their selection of Electrostatic Discharge (ESD) wrist straps.*One M6 x 12mm thread-forming screw also provided in each kit.ESD port must be attached to a grounded member.

Part Number Part Description

Std.Pkg.Qty.

RGW-12-1 12 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant; for use with standard equipment racks:CMR19X84, CMR19X84S and CMR23X84

1

RGW-32-1 32 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant; for use with 4 post rack NF4PR84 anddata rack DR84

1

RGW-100-1 100 paint piercing bonding washers for 3/8" stud size; .875 O.D.; providedwith .16 oz (5cc) of antioxidant

1

Part Number Part Description

Std.Pkg.Qty.

RGESD-1 ESD port kit; provided with an ESD protection sticker, .16 oz (5cc) ofantioxidant and one #12-24 x 1/2" thread-forming screw*

1

Page 14: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

14

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Thread-Forming Screws• Thread-forming, provides a bond to the rack by removing

paint from threaded holes without creating metal shavings• Easily installed with 5/16" socket head wrench or flat

blade screwdriver

Retrofit Rack Grounding Kits• Provides a dedicated ground system to maintain system

performance and protect network equipment when RGSrack grounding strip kit cannot be used (see page 11)

• Optimized for installation on 19" racks that meet EIA-310-D,with functioning equipment, and are deployed in the field

• Provides a complete system of matched components thatcan be easily selected to save cost and labor

remove paint from the rack

RGRKCBNJEJ RGRKCBNJ

NetworkEquipment

HTAP(seepage 20)

RackGroundingBusbarRGRB19

Lug(see pages16-18)

RackGroundingKitRGRKCBNJEJ

Rack Grounding KitRGRKCBNJ

GroundingJumperRGREJ696orRGREJ1096

GroundingJumperRGREJ696

Part Number Part Description

Std.Pkg.Qty.

Std.Ctn.Qty.

RGRKCBNJEJ Rack grounding kit to ground the rack and one piece of equipment;includes one RGRB19 busbar, one HTCT250-2-1 HTAP and twoRGREJ696 grounding jumpers

1 10

RGRKCBNJ Rack grounding kit to ground the rack; includes one RGRB19busbar, one HTCT250-2-1 HTAP and one RGREJ696grounding jumper

1 10

RGRB19 Rack grounding busbar; can be positioned anywhere on the rack;19" length; tin plated; 14 holes arranged for flexibility in mounting;mounting hole sets have 1/2" spacing; provided with two#12-24 x 1/2" thread-forming screws* for mounting

1 10

RGREJ696 Grounding jumper; #6 AWG; 96" length; one end factoryterminated to lug; provided with .16 oz (5cc) of antioxidant and four#12-24 x 1/2" thread-forming screws* and other mounting hardwareas appropriate

1 10

RGREJ1096 Grounding jumper; #10 AWG; 96" length; one end factoryterminated to lug; provided with .16 oz (5cc) of antioxidant and four#12-24 x 1/2" thread-forming screws* and other mounting hardwareas appropriate

1 10

Part Number Part Description

Std.Pkg.Qty.

RGTS-C Thread-forming grounding screw, #12-24 x 1/2" 100

RGTSM6-C Thread-forming grounding screw, M6 x 12mm 100

Bonding Screws• Creates an electrical bond between painted patch panels

and racks• Serrations on bottom of screw remove paint from patch

panel, thus providing metal-to-metal contact

• Thread-forming, provides a bond to the rack by removingpaint from threaded holes without creating metal shavings

• Easily installed with Phillips screwdriver

Part Number Part Description

Std.Pkg.Qty.

RGTBS-C Thread-forming bonding screw, #12-24 x 1/2" 100

RGTBSM6-C Thread-forming bonding screw, M6 x 15mm 100

*An equal number of M6 x 12mm thread-forming screws also provided in each kit.

• Thread-forming screws eliminate the need to manually

Page 15: Panduit Hiland Grounding

15For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingSTRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

BICSI/J-STD-607-A Telecommunications Grounding Busbars

Common Bonding Network (CBN) Components

ULRC US

• Meets BICSI and J-STD-607-A requirements for networksystems grounding applications

• Made of high conductivity copper and tin plated toinhibit corrosion

• Comes pre-assembled with brackets and insulatorsattached for quick installation

• Use PANDUIT self-laminating laser/ink jet labels to identifybusbars to meet TIA/EIA-606-A

TGB

TMGB

C200X100FJJ

For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identificationproducts, see the Identification Solutions Catalog SA-IDCB16.*Busbar labels sold separately.

Part Number Bar Size

No. of 5/16"hole sets,

5/8" spacing

No. of 7/16"hole sets,1" spacing

Can Be ClearlyIdentified with PANDUIT

Laser/Ink Jet Label*

Std.Pkg.Qty.

Telecommunications Grounding Busbars (TGB)GB2B0304TPI-1 1/4" x 2" x 10" 4 3

C200X100FJJ1

GB2B0306TPI-1 1/4" x 2" x 12" 6 3 1

GB2B0312TPI-1 1/4" x 2" x 20" 12 3 1

Telecommunications Main Grounding Busbars (TMGB)GB4B0612TPI-1 1/4" x 4" x 12" 12 6

C200X100FJJ1

GB4B0624TPI-1 1/4" x 4" x 20" 24 6 1

Telecommunications Grounding and Bonding Conductor Label Kit

For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identificationproducts, see the Identification Solutions Catalog SA-IDCB16.

• Meets labeling requirements of J-STD-607-A; eachtelecommunications grounding and bonding conductor shallbe labeled as close as practicable to its point of termination ina readable position

• Can be applied as a wrap-around marker (parallel to cable) orflag marker (45° or 90°) to cable

• Kit includes everything needed to properly label cables; oneflame retardant cable tie and one rigid plastic yellow tagprinted with “IF THIS CONNECTOR OR CABLE IS LOOSEOR MUST BE REMOVED, PLEASE CALL THE BUILDINGTELECOMMUNICATIONS MANAGER”

Part Number Part Description

Std.Pkg.Qty.

LTYK Label kit includes printed tag and one flame retardant cable tie 10

Page 16: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

16

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

For Use with Stranded Copper Conductors

Code Conductor, Two-Hole, Long Barrel with Window Lug

• Meets J-STD-607-A requirements fornetwork systems grounding applications

• Tested by Telcordia — meets NEBSLevel 3

• Requires crimping tools and dies, seepages 24, 25, 26 and 27

• UL Listed for use up to 35KV**, temperaturerated 90°C and CSA Certified to 600V whencrimped with PANDUIT and specifiedcompetitor crimping tools and dies

• UL Listed and CSA Certified for wirerange-taking capability when crimped withPANDUIT ® UNI-DIE ™ dieless crimping tools

• Color coded barrels marked with PANDUITand specified competitor die index numbersfor proper crimp die selection

• Long barrel maximizes number of crimpsand provides premium wire pull-out strengthand electrical performance

• Inspection window to visually assure fullconductor insertion

• Tin plated to inhibit corrosion• Available with NEMA hole sizes and spacing

Ring Terminal, Vinyl Expanded Insulation

• Expanded wire entry allows for large O.D. wire insulation ormultiple wire crimps within one wire barrel

• Industry standard color coding to indicate wire range

• Brazed seam assures a reliable crimp• Insulation support• Requires crimping tools, see page 24

C

L

W

For additional sizes and configurations and to see the complete line of PAN-TERM ® Terminals, see the TerminationSolutions Catalog SA-TMCB02.‡UL and CSA approved tooling/product combinations. For crimping tools see page 24.**To order in bulk, replace -C in the part number with -M for a bulk package of 1000 and replace -L with -D for abulk package of 500.

PartNumber

WireRange

ColorCode

StockThickness

Max.Ins.

StudSize

FigureDimensions (In.)

PANDUITCrimping

Tool

Std.Pkg.Qty.**

Std.Ctn.Qty.L W C

PV14-6RX-C

16-14AWG Blue

.03 .200 #6 .96 .31 .25

CT-100‡,CT-1550‡

100 500

PV14-8RX-C .03 .200 #8 .96 .31 .25 100 500

PV14-10RX-C .03 .200 #10 .96 .31 .25 100 500

PV14-14RX-C .03 .200 1/4" 1.16 .46 .37 100 500

PV10-6RX-L

12-10AWG Yellow

.04 .250 #6 1.10 .31 .30

CT-100‡,CT-1550‡

50 500

PV10-8RX-L .04 .250 #8 1.10 .31 .30 50 500

PV10-10RX-L .04 .250 #10 1.10 .31 .30 50 500

PV10-14RX-L .04 .250 1/4" 1.29 .52 .39 50 500

Page 17: Panduit Hiland Grounding

17For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingSTRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

W

HOLESPACING

L

T

BINSPECTION

WINDOW

W

HOLESPACING

L

T

BINSPECTIONWINDOW

Figure 1 Figure 2: Slotted Lug

B

INSPECTIONWINDOW

W

HOLESPACING

L

T45˚

HOLESPACING

L

T

B

INSPECTIONWINDOW

90˚

W

Figure 3: Slotted Lug45°Bent

Figure 4: Slotted Lug90°Bent

Code Conductor, Two-Hole, Long Barrel with Window Lug (continued)

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.*Not tested to NEBS Level 3 requirements.**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

Part NumberFigure

No.

CopperConductor

Size

StudHoleSize(In.)

StudHole

Spacing(In.)

FigureDimensions (In.)

PANDUITCrimping

Tool

PANDUITDie Color& Die No.

BurndyDieNo.

T&BDieNo.

WireStrip

Length(In.)

Std.Pkg.Qty.W B T L

LCC10-14JAW-L* 2#14 – #10AWG STR,#12 – #10AWG SOL

1/4 .50 – .63 .42 .53 .05 1.93

CT-100,CT-1570

— — — 9/16 50

LCC10-14JAWH-L* 3 1/4 .50 – .63 .42 .53 .05 1.78 — — — 9/16 50

LCC10-14JAWF-L* 4 1/4 .50 – .63 .42 .53 .05 1.56 — — — 9/16 50

LCC10-14BW-L* 1 1/4 .75 .42 .53 .05 2.06 — — — 9/16 50

LCC8-10ABW-L 2

#8 AWG

#10 .63 – .75 .41 .70 .08 2.14CT-1700,CT-930,CT-2931

Red P21 49 21 3/4 50

LCC8-14ABW-L 2 1/4 .63 – .75 .48 .70 .07 2.23 Red P21 49 21 3/4 50

LCC8-14DW-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 49 21 3/4 50

LCC8-38DW-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 49 21 3/4 50

LCC6-10ABW-L 2

#6 AWG

#10 .63 – .75 .46 1.07 .08 2.52

CT-1700,CT-930,CT-2931

Blue P24 7 24 1 1/8 50

LCC6-14JAW-L 2 1/4 .50 – .63 .48 1.07 .08 2.49 Blue P24 7 24 1 1/8 50

LCC6-14JAWH-L 3 1/4 .50 – .63 .48 1.07 .08 2.08 Blue P24 7 24 1 1/8 50

LCC6-14JAWF-L 4 1/4 .50 – .63 .48 1.07 .08 1.66 Blue P24 7 24 1 1/8 50

LCC6-14BDW-L 2 1/4 .75 – 1.00 .48 1.07 .08 2.86 Blue P24 7 24 1 1/8 50

LCC6-14EW-L 1 1/4 1.25 .48 1.07 .08 3.11 Blue P24 7 24 1 1/8 50

LCC6-56BW-L 1 5/16 .75 .56 1.07 .07 2.73 Blue P24 7 24 1 1/8 50

LCC6-38BDW-L 2 3/8 .75 – 1.00 .62 1.07 .06 3.08 Blue P24 7 24 1 1/8 50

LCC4-14ADW-L 2#4 – #3

AWG STR

1/4 .63 – 1.00 .55 1.05 .09 2.63 CT-1700,CT-930,CT-2931

Gray P29 8 29 1 1/8 50

LCC4-38DW-L 1 3/8 1.00 .62 1.05 .08 3.09 Gray P29 8 29 1 1/8 50

LCC2-14AW-Q 1#2 AWG

1/4 .63 .60 1.16 .10 2.67 CT-1700,CT-930,CT-2931

Brown P33 10 33 1 1/4 25

LCC2-38DW-Q 1 3/8 1.00 .66 1.16 .10 3.24 Brown P33 10 33 1 1/4 25

LCC1-14AW-E 1#1 AWG

1/4 .63 .70 1.36 .11 2.89 CT-1700,CT-930,CT-2931

Green P37 11 37 1 7/16 20

LCC1-38DW-E 1 3/8 1.00 .70 1.36 .11 3.46 Green P37 11 37 1 7/16 20

LCC1/0-14AW-X 11/0 AWG

1/4 .63 .76 1.44 .12 3.07 CT-930,CT-2931

Pink P42 12 42 1 1/2 10

LCC1/0-38DW-X 1 3/8 1.00 .76 1.44 .12 3.57 Pink P42 12 42 1 1/2 10

LCC2/0-14AW-X 12/0 AWG

1/4 .63 .85 1.50 .13 3.23 CT-930,CT-2931

Black P45 13 45 1 9/16 10

LCC2/0-38DW-X 1 3/8 1.00 .85 1.50 .13 3.67 Black P45 13 45 1 9/16 10

LCC3/0-38DW-X 13/0 AWG

3/8 1.00 .96 1.50 .13 3.70CT-930,CT-2931

Orange P50 14 50 1 9/16 10

LCC3/0-12W-X 1 1/2 1.75 .96 1.50 .13 4.87 Orange P50 14 50 1 9/16 10

LCC4/0-14AW-X 14/0 AWG

1/4 .63 1.06 1.56 .14 3.35 CT-930,CT-2931

Purple P54 15 54 1 5/8 10

LCC4/0-38DW-X 1 3/8 1.00 1.06 1.56 .14 3.81 Purple P54 15 54 1 5/8 10

LCC250-38DW-X 1250 kcmil

3/8 1.00 1.17 1.61 .14 3.89 CT-930,CT-2931

Yellow P62 16 62 1 11/16 10

LCC250-12DW-X 1 1/2 1.00 1.17 1.61 .14 4.12 Yellow P62 16 62 1 11/16 10

Page 18: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

18

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Flex Conductor, Two-Hole, Long Barrel with Window Lug

• Meets J-STD-607-A requirements fornetwork systems grounding applications

• Requires crimping tools and dies, see pages24, 25, 26 and 27

• UL Listed for use up to 35KV**, temperaturerated 90°C and CSA Certified to 600V whencrimped with PANDUIT and specifiedcompetitor crimping tools and dies

• Color coded barrels marked with PANDUITand specified competitor die index numbersfor proper crimp die selection

• Can be used with code conductor andflex conductor class: G, H, I, K, M andLocomotive

• Long barrel maximizes number of crimpsand provides premium wire pull-out strengthand electrical performance

• Inspection window to visually assure fullconductor insertion

• Generously beveled wire entry preventsbent back strands when inserting conductorinto barrel

• Tin plated to inhibit corrosion• Available with NEMA hole sizes and spacing

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

W

HOLESPACING

L

INSPECTIONWINDOW

T

B

For Use with Flexible, Extra-Flexible and Code Stranded Copper Conductors

Figure 1 Figure 2: Slotted Lug

W

HOLESPACING

L

T

BINSPECTIONWINDOW

Part NumberFigure

No.

FlexConductor

Size CodeConductor

Size

StudHoleSize(In.)

StudHole

Spacing(In.)

FigureDimensions

(In.) PANDUITCrimping

Tool

PANDUITDie Color& Die No.

WireStrip

Length(In.)

Std.Pkg.Qty.

ClassG, H, I, K, M Locomotive W B T L

LCCX8-10AB-L 2

#8 AWG #8 AWG #8 AWG

#10 .63 – .75 .41 .70 .08 2.14CT-1700,CT-930,CT-2931

Red P21 3/4 50LCCX8-14AB-L 2 1/4 .63 – .75 .48 .70 .07 2.23 Red P21 3/4 50LCCX8-14D-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 3/4 50LCCX8-38D-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 3/4 50LCCX6-10B-L 1

#6 AWG #6 AWG #6 AWG

#10 .75 .46 1.07 .08 2.52

CT-1700,CT-930,CT-2931

Blue P24 1 1/8 50LCCX6-14AB-L 2 1/4 .63 – .75 .48 1.07 .08 2.61 Blue P24 1 1/8 50LCCX6-14D-L 1 1/4 1.00 .48 1.07 .08 2.86 Blue P24 1 1/8 50LCCX6-38AC-L 2 3/8 .63 – .88 .62 1.07 .06 2.96 Blue P24 1 1/8 50LCCX6-38D-L 1 3/8 1.00 .62 1.07 .06 3.08 Blue P24 1 1/8 50LCCX4-14AB-L 2

#4 AWG #5, #4, #3AWG

#4 – #3AWG STR

1/4 .63 – .75 .55 1.05 .09 2.63 CT-1700,CT-930,CT-2931

Gray P29 1 1/8 50

LCCX4-38BD-L 2 3/8 .75 – 1.00 .62 1.05 .08 3.09 Gray P29 1 1/8 50

LCCX2-38D-E 1 #2 AWG #2 AWG #2 AWG 3/8 1.00 .70 1.36 .11 3.46 CT-1700,CT-930,CT-2931

BrownP33

1 7/16 20

LCCX1-14A-X 1#1 AWG #1 AWG #1 AWG

1/4 .63 .76 1.44 .12 3.07 CT-930,CT-2931

Green P37 1 1/2 10LCCX1-38D-X 1 3/8 1.00 .76 1.44 .12 3.57 Green P37 1 1/2 10LCCX1/0-14A-X 1

1/0 AWG 1/0 AWG 1/0 AWG1/4 .63 .85 1.50 .13 3.23 CT-930,

CT-2931Pink P42 1 9/16 10

LCCX1/0-38D-X 1 3/8 1.00 .85 1.50 .13 3.67 Pink P42 1 9/16 10LCCX2/0-14A-X 1

2/0 AWG 2/0 AWG 2/0 AWG1/4 .63 .96 1.50 .13 3.27 CT-930,

CT-2931Black P45 1 9/16 10

LCCX2/0-38D-X 1 3/8 1.00 .96 1.50 .13 3.70 Black P45 1 9/16 10LCCX3/0-38D-X 1 3/0 AWG 3/0 AWG 3/0 AWG 3/8 1.00 1.06 1.56 .14 3.81 CT-930,

CT-2931Orange

P501 5/8 10

LCCX4/0-38D-X 1 4/0 AWG 4/0 AWG 4/0 AWG 3/8 1.00 1.19 2.24 .16 4.55 CT-930,CT-2931

PurpleP54

2 5/16 10

LCCX250-38D-X 1 250 kcmil 262.6 kcmil — 3/8 1.00 1.28 2.24 .17 4.59 CT-930,CT-2931

Yellow P62 2 5/16 10

Page 19: Panduit Hiland Grounding

19For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Code/Flex Conductor HTAP Kit• Includes all components to make a complete HTAP and

cover installation: HTCT HTAP, matching CLRCVR clearcover and cable ties

• Each HTCT HTAP designed to terminate a wide range ofcopper code and flex conductor combinations toaccommodate a variety of applications

• HTAPs incorporate a unique slotted design that allows forquick and easy installation using supplied PANDUIT cableties; saves time and cost

• Matching clear covers are made from high impact plasticand provide high impact strength and 360° viewing ofinstalled HTAP

• Clear covers have a UL 94 V-0 flame rating and anoxygen index of 28 providing self-extinguishing, flameretardant properties

• Requires crimping tools and dies, see pages 25, 26 and27

• UL Listed and CSA Certified for applications up to 600Vwhen crimped with PANDUIT and specified competitor

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.See pages 20 and 21 for more information on HTAPs and clear covers, including crimping tools.Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the LS7 Printer and to see the complete line ofPANDUIT identification products, see the Identification Solutions Catalog SA-IDCB16.

TAP 1

RUN

H

WL

WRUN

TAP 1TAP 2

TAP 3

L

H

W L

RUN

H

TAP 1 TAP 2 TAP 1

W L

H

RUN

HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

Part Number

Components Copper Conductor Size Range

Std.Pkg.Qty.

HTAPPart No.

ClearCover

Part No.

WireStrandType Run Tap1 Tap 2 Tap 3

HTWC6-6-1 HTCT6-6-1 CLRCVR1-1 Code #6 – #10 AWG #6 – #14 AWG— —

1

Flex #6 – #10 AWG #6 – #14 AWG

HTWC2-2-1 HTCT2-2-1 CLRCVR2-1Code

#2 – #6 AWGSTR/SOL

#2 – #6 AWGSTR/SOL

#8 – #14 AWG #8 – #14 AWG 1

Flex #2 – #8 AWG #2 – #8 AWG #8 – #14 AWG #8 – #14 AWG

HTWC250-2-1 HTCT250-2-1 CLRCVR3-1Code

250 kcmil – #2AWG

#2 – #6 AWGSTR/SOL

#8 – #14 AWG—

1

Flex 4/0 – #2 AWG #2 – #8 AWG #8 – #14 AWG

HTWC250-250-1 HTCT250-250-1 CLRCVR3-1Code

250 kcmil – #2AWG

250 kcmil – #2AWG — —

1

Flex 4/0 – #2 AWG 4/0 – #2 AWG

Page 20: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

20

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Code/Flex Conductor HTAP

• Used to tap into continuous conductors as asplice or pigtailing

• Each HTAP terminates a wide range ofconductor sizes and combinations of codeand flex conductors Class G, H, I andLocomotive to suit a variety of applications

• Slotted design allows quick and easyassembly of conductor to HTAP using 3PANDUIT 94 V-0 cable ties included

• Tap grooves are separated from one anotherallowing them to function independently soHTAP can be used with a single or multipletaps providing maximum design andinstallation flexibility

• Color coded and marked with PANDUIT dieindex numbers for proper crimp die selection

• Requires crimping tools and dies, seepages 25, 26 and 27

• UL Listed and CSA Certified for applicationsup to 600V when crimped with PANDUITand specified competitor crimping tools andPANDUIT crimping dies

• Tin plated to inhibit corrosion

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

For Making Parallel and Multiple Tap Connections on Code and Flex Conductors

HTAP

TAP

RUN

TAP 1

RUN

H

WL

WRUN

TAP 1TAP 2

TAP 3

L

H

W L

RUN

H

TAP 1 TAP 2 TAP 1

W L

H

RUN

HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

Part Number

Copper Conductor Size RangeFigure

Dimensions (In.)

PANDUITCrimping

Tool

PANDUITDie Color& Die No.

WireStrip

Length(In.)

Std.Pkg.Qty.

WireStrandType Run Tap 1 Tap 2 Tap 3 L W H

HTCT6-6-1Code

#6 – #10AWG

#6 – #14AWG

— —

.61 .40 .99 CT-930, CT-2931 Orange,PH6

11/16 1

Flex#6 – #10

AWG#6 – #14

AWG

HTCT2-2-1Code

#2 – #6AWG

STR/SOL

#2 – #6 AWGSTR/SOL

#8 – #14AWG

#8 – #14AWG

.76 .61 1.55 CT-930, CT-2931 Brown,PH2

13/16 1

Flex#2 – #8AWG

#2 – #8 AWG #8 – #14AWG

#8 – #14AWG

HTCT250-2-1Code

250 kcmil –#2 AWG

#2 – #6 AWGSTR/SOL

#8 – #14AWG

.92 .96 1.92 CT-930, CT-2931 Purple,PH25

1 1

Flex4/0 – #2

AWG#2 – #8 AWG #8 – #14

AWG

HTCT250-250-1Code

250 kcmil –#2 AWG

250 kcmil –#2 AWG

— —

.90 .89 1.92 CT-930, CT-2931 Purple,PH25

1 1

Flex4/0 – #2

AWG4/0 – #2

AWG

Page 21: Panduit Hiland Grounding

21For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Clear Covers for HTCT HTAPs

• Made of high impact plastic to provide high impact strengthand 360° inspections of crimped connection to assure thecrimp is complete and the correct die was used

• Incorporate dual self-latching spring loaded latches andsupplied with two PANDUIT UL 94 V-0 cable ties — allowfor easy snap-on assembly and ensure covers are secured

• Low profile design minimizes space requirements• Each cover half supports installation information labels

inside plastic retainer strips to allow labels to be viewedon either side of cover and to protect labels frombeing removed

• Incorporate molded in flash barriers which encompass theHTAP installation providing protection against electricalflash over

• UL 94 V-0 flame rating and oxygen index of 28 providingself-extinguishing, flame retardant properties

• Part number, voltage rating, temperature rating and HTCTpart number molded into cover for easy identification

• Flexible fingers located at each end of cover preventforeign objects from entering cover and are made fromductile plastic material that allows easy installation andwill not damage conductor insulation

For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and GroundingConnectors, see the Termination Solutions Catalog SA-TMCB02.Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on theLS7 Printer and to see the complete line of PANDUIT identification products, see the Identification SolutionsCatalog SA-IDCB16.

H

L W

Part NumberUse With HTAP

Part Number

Figure Dimensions(In.)

Std.Pkg.Qty.L W H

CLRCVR1-1 HTCT6-6 4.48 1.41 1.20 1

CLRCVR2-1 HTCT2-2 5.10 1.66 1.40 1

CLRCVR3-1 HTCT250-2, HTCT250-250 5.35 2.16 1.40 1

Shown Assembled

For Use with PANDUIT HTCT HTAPs

Page 22: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

22

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Grounding Clamp, U-Bolt, Bronze

• Used to ground copper conductor parallel or at a rightangle to a rod, tube or pipe

• Made from high strength, electrolytic cast bronze • High strength silicon bronze hardware provides long term

reliable assembly

• Accommodates a wide range of pipe, tube, rod andconductor sizes — minimizes inventory

• UL Listed for grounding and bonding and suitable for directburial in earth or concrete

For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

ULRC US

H

LW

Part Number

GroundRod Size

(In.)

IronPipe Size

(In.)ConductorSize Range

Figure Dimensions(In.)

BoltDia.(In.)

HexSize(In.)

TighteningTorque

(In.-Lbs.)

Std.Pkg.Qty.L W H

GPL-8-Q 7/8 or 1 1/2 or 3/4 #8 SOL – #4 STR 2.38 1.38 2.63 3/8 9/16 110 25

GPL-14-X — 1 #8 SOL – #4 STR 2.63 1.38 2.75 3/8 9/16 110 10

GPL-15-X — 1 #4 SOL – 2/0 STR 2.63 1.63 2.75 3/8 9/16 180 10

Page 23: Panduit Hiland Grounding

23For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Grounding Clamp for Water Pipes, Bronze

• Used to ground copper code conductor to water pipe orcopper tube

• Cast from high strength, electrolytic bronze to providereliable grounding connections

• Plated steel screws provide high strength andinhibit corrosion

• Accommodates a wide range of pipe, tube, rod andconductor sizes — minimizes inventory

• UL Listed for grounding and bonding and suitable for directburial in earth or concrete

For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.

L W

Grounding Rod Clamp, Bronze• Used for grounding copper conductor parallel to

ground rods• Made from high strength, seamless electrolytic bronze to

provide long term durability • High strength silicon bronze hardware provides long term

reliable assembly

• Accommodates a wide range of rod and conductorsizes — minimizes inventory

• UL Listed and CSA Certified for grounding and bondingand suitable for direct burial in earth and concrete

For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination SolutionsCatalog SA-TMCB02.

Part Number

GroundRodSize

Conductor SizeRange

FigureDimensions (In.)

HexSize(In.)

TighteningTorque

(In.-Lbs.)

Std.Pkg.Qty.L W H

WB12-L 1/2 #2 – #10 STR#10 SOL

.88 .84 1.28 1/2 180 50

WB34-X 5/83/4

1/0 – #8 STR#2 – #8 STR

1.03 1.06 1.54 1/2 180 10

WB58-Q 5/8 1/0 – #8 STR 1.04 .92 1.40 1/2 180 25

W L

H

Part Number

Water PipeRange

(In.)ConductorSize Range

FigureDimensions (In.)

Tightening Torque(In.-Lbs.)

Std.Pkg.Qty.L W Conductor Clamp

KP1-C 1/2 – 1 #10 SOL – #2 STR 2.28 .66 50 50 100

KP2-L 1 1/4 – 2 #10 SOL – #2 STR 3.58 .73 50 50 50

Page 24: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

24

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Hand Operated Plier Type Tool

Crimping Tools

• Plier type • Installer controlled crimp

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

Part Number Part Description

Std.Pkg.Qty.

CT-100 Crimps most PANDUIT #26 – #10 AWG insulated and non-insulatedterminals, disconnects and splices. Cuts #4, #6, #8 and #10 screw sizes.Cuts and strips wire. Excellent all-around application tool of heat treatedfinished steel with comfortable cushioned plastic grip handles.

1

CONTOUR CRIMP ™ Controlled Cycle Tools• Specifically designed for the installation of PAN-TERM ®

terminals, disconnects and splices • Low handle effort — increases productivity

• Superior crimp performance • Reliable — backed by a two year warranty

CT-1550

CT- 1700

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

Part Number Part Description

Std.Pkg.Qty.

CT-1550 Crimps most PAN-TERM ® #22 – #10 AWG nylon and vinyl insulatedterminals, splices and disconnects. The CT-1550 has the red/blue pocketclosest to the pivot which provides a reduced crimp effort for those whomake red/blue terminations.

1

CT-1570 Crimps most PAN-TERM ® #22 – #10 AWG and .5-6.0mm non-insulatedterminals and disconnects. Crimps PANDUIT #22 – #10 AWG and.5-6.0mm non-insulated splices, and #10 AWG compression lugs.

1

CT-1700 Crimps PANDUIT #8 – #2 AWG non-insulated tubular terminals (Sseries), #8 – #1 AWG copper lugs and splices, #6 – #4 AWG aluminumlugs and splices and CTAPF copper taps for #14 – #3 AWG. Includes 5position, color coded rotating die.

1

CT-1570

Page 25: Panduit Hiland Grounding

25For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Die Type, Manual Hydraulic, 14 Ton, Crimping Tool• Two-stage rapid advance hydraulic system minimizes

number of pumps required to complete a crimp —saves time

• Cushioned grip prevents hands from slipping on tool —reduces fatigue

• Provides UL Listed and CSA Certified connections onPANDUIT ® PAN-LUG™ copper and aluminum lugs andsplices and copper taps

• Open “C-Head” design allows easy loading of crimping diesand connectors, saves time

• Requires crimping dies, see page 27• Dies installed using spring loaded die retention pins, no

need for tools• Rubber boot on crimp head provides abrasion protection• Audible “pop-off” valve indicates crimp completion• Crimp head rotates 180°, provides versatility for use in

restricted spaces

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.

Part Number Part Description

Std.Pkg.Qty.

CT-930 Terminates PANDUIT ® PAN-LUG™ Compression Connectors:

• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor• Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor• Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor• Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor• Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor• Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor

Warranty: 5 years

CT-930 includes:• Tool• Plastic tool case with die storage

1

Page 26: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

26

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool• Two stage rapid advance hydraulic system minimizes

cycle time• Provides UL Listed and CSA Certified connections on

PANDUIT ® PAN-LUG™ copper and aluminum lugs andsplices and copper taps

• Open “C-Head” design allows easy loading of crimpingdies and connectors, saves time

• Rubber boot on crimp head provides abrasion protection• Ram automatically retracts when crimp cycle is complete

• Tool provided with two, high capacity 12 VDC rechargeablenickel-metal hydride batteries — provides for continuousoperation and eliminates “memory” build-up, one hourcharge time

• Eight second crimp cycle time provides quick terminations,saves time

• Uses industry standard Makita* batteries and charger —industry proven reliability easy to obtain from localretail sources

• Requires crimping dies, see page 27• Dies installed using spring loaded die retention pins — no

need for tools• Crimp head rotates 360° — provides versatility for use in

restricted spaces

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.*Makita is a registered trademark of Makita Corporation.

Part Number Part Description

Std.Pkg.Qty.

CT-2931 Terminates PANDUIT ® PAN-LUG™ Compression Connectors:

• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor• Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor• Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor• Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor• Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor• Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor

Warranty: 3 years

CT-2931 includes:• Tool• Two 12 VDC, rechargeable NiMH batteries• One battery charger• Steel tool case with storage for batteries, charger and crimp dies

1

Page 27: Panduit Hiland Grounding

27For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

CD-920 Crimping Dies• Crimping dies and connectors are color coded for

easy matching• Embosses die index number on connector barrels for post

crimp inspection

• Part number permanently marked on crimping die foreasy identification

• Provides circumferential crimp results in terminations withpremium electrical and mechanical performance

• Used in PANDUIT crimping tools; see the CT-930 crimpingtool on page 25, the CT-2931 crimping tool on page 26and the complete line of PANDUIT crimping tools in theTermination Solutions Catalog SA-TMCB02

CD-920

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

Die Number

DieColor

Part Number

Used to Install PANDUIT HTAP Part Numbers Std.Pkg.Qty.Copper HTAP and Die Color & Die No.

CD-920H-6 HTCT6-6-1, Orange PH6 1

CD-920H-2 HTCT2-2-1, Brown PH2 1

CD-930H-250 HTCT250-2-1, HTCT250-250-1, Purple PH25

1

Part Number

Used to Install PANDUIT Compression Lug & Splice Sizes Std.Pkg.Qty.Copper Code Conductor Size and Die Color & Die No.

CD-920-8 #8 AWG, Red P21 1

CD-920-6 #6 AWG, Blue P24 1

CD-920-4 #4 AWG, Gray P29 1

CD-920-2 #2 AWG, Brown P33 1

CD-920-1 #1 AWG, Green P37 1

CD-920-1/0 1/0 AWG, Pink P42 1

CD-920-2/0 2/0 AWG, Black P45 1

CD-920-3/0 3/0 AWG, Orange P50 1

CD-920-4/0 4/0 AWG, Purple P54 1

CD-920-250 250 kcmil, Yellow P62 1

Page 28: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

28

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

PANDUIT ® STRUCTUREDGROUND™ System for Data Center GroundingApplication Standards

IEEE Std 1100-1999 (IEEE Emerald Book) – IEEERecommended Practice for Powering and GroundingElectronic Equipment

The main objective of the Emerald Book is to provide a consensus ofrecommended practices to address electronic equipmentperformance issues while maintaining a safe installation, asspecified in the National Electrical Code® (NEC®) (NFPA 70-1999)and recognized testing laboratories' standards.

Alliance for Telecommunications IndustrySolutions ATIS

ATIS is a technical planning and standards development organization that is committed to rapidly developing and promotingtechnical and operations standards for the communications andrelated information technologies industry worldwide using a pragmatic, flexible and open approach. Over 1,200 participants frommore than 400 communications companies are active in ATIS’ 22industry committees, and its Incubator Solutions Program.www.atis.org

J-STD-607-A-2002, Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications is jointly developed by TIA/EIA and ATIS’technical committee T1E1. This document is available on the ATIS Document Center at www.atis.org.

Adhering to the grounding principles outlined in J-STD-607-A helpsensure that telecommunications equipment and systems operate reliably. As stated in J-STD-607-A, the preferred means ofconnecting conductors to busbars is by using two-hole irreversible compression lugs listed by a nationally recognized testing laboratory (NRTL) such as UL. PANDUIT ® PAN-LUG™ CopperCompression Connectors meet these requirements, in all of thebarrel sizes specified by the 607 standard.

Telecommunications Industry Association TIA

The Telecommunications Industry Association is a leading U.S.non-profit trade association serving the communications andinformation technology industry. TIA represents providers ofcommunications and information technology products and servicesfor the global marketplace through its core competencies instandards development.

ANSI/TIA-942 Draft 5.0a – Telecommunications Infrastructure Standard for Data Centers

TIA-942 states that electrical continuity is required throughout therack materials. Adhering to these principles protects networkequipment and maintains system performance. PANDUIT ®

STRUCTUREDGROUND ™ System for Data Center Grounding meetsTIA-942 requirements by incorporating an all-copper grounding path.Paint piercing grounding washers ensure metal to metal contact ofrack members and two-hole compression lugs for a permanent andreliable connection.

The Institute of Electrical and ElectronicsEngineers, Inc. (IEEE)

The IEEE promotes the engineering process of creating,developing, integrating, sharing, and applying knowledge aboutelectro and information technologies and sciences for the benefitof humanity and the profession.

NEBS Level 3 Criteria is the minimum level of environmental compatibility needed to provide maximum assurance of equipment operability within the network facility environment.

The Level 3 Criteria is the highest assurance of product operability.Products that meet NEBS Level 3 Criteria are suited for equipmentapplications which demand minimal service interruptions over the lifespan of the equipment. PANDUIT is the first in the industry to have asystem of copper compression lugs and splices (#8 AWG – 1,000kcmil) and crimping tools physically and rigorously tested byTelcordia Technologies to meet NEBS Level 3 compliance.

NEBS Level 3 Approval as Tested by Telcordia Technologies

Telcordia Technologies, formerly known as Bellcore, serves as thetesting agency for the Regional Bell Operating Companies. NetworkEquipment-Building Systems (NEBS) was developed by Bellcoreand is currently maintained by Telcordia Technologies. NEBS wasdeveloped to standardize requirements for Central Office Equipmentand to develop criteria for personal safety, protection of property andoperational continuity.

Canadian Standards Association

Canadian Standards Association is a not-for-profit membershipbased association serving business, industry, government, and consumers in Canada and the global marketplace. C.S.A. works inCanada and around the world to develop standards that enhancepublic safety and health.

Underwriters Laboratories, Inc.

Underwriters Laboratories, Inc. is an independent, not-for-profitsafety testing and certification organization based in theUnited States.

• UL 467 Grounding and Bonding Equipment • UL 486A Wire Connectors and Soldering Lugs for Use with

Copper Conductors – Covers pressure wire connectors and soldering lugs for use with copper conductors according to the National Electrical Code NFPA 70

• UL VW-1 Flammability Rating

Underwriters Laboratories, Inc. Standards applicable to specified PANDUIT ® STRUCTUREDGROUND™ System for Data Center Groundingand PAN-LUG™ Power and Grounding Connectors.

• C22.2 NO. 41-M1987 (R2004) Grounding and Bonding Equipment

• C22.2 NO. 65-03 Wire Connectors

Canadian Standards Association standards that are applicable tospecified PANDUIT ® STRUCTUREDGROUND™ System for Data CenterGrounding and PAN-LUG™ Power and Grounding Connectors.

Page 29: Panduit Hiland Grounding

29For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Roof

Backbone pathway

Suspended ceiling area

TR

Bu

ildin

g s

tee

l

TGB

GE TR

TGB

TGB TGB

Bu

ildin

g s

tee

l

Backbone pathway

Backbone pathway

Suspended ceiling area

TR

(TB

B)

Exte

rio

r b

uild

ing

wa

ll

Exte

rio

r b

uild

ing

wa

ll

TBB

Sleeve

Suspended ceiling area

TBB within conduitACEG

(TB

B)

ElectricalEF

Groundingelectrodesystem

GEC

TMGB

BCT

Primary cableprotection

EF ER

Panelboard

TGB

(TB

B)

TR

ACEG = Alternating current equipment ground BC = Bonding conductor BCT = Bonding conductor for telecommunications EF = Entrance facility ER = Equipment room GE = Grounding equalizer GEC = Grounding electrode conductor TBB = Telecommunications bonding backbone TGB = Telecommunications grounding busbar TMGB = Telecommunications main grounding busbar TR = Telecommunications room

Red iron

Red iron

Red iron

GE

Source: BICSI TDM Manual, 10th Edition

Specification Layout for Data Center Grounding per BICSI TDM Manual,10th Edition

For more technical grounding information, please see the Data Center Grounding White Paper at www.panduit.com/dcgrounding.

Page 30: Panduit Hiland Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

30

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Ground A conducting connection, whether intentional or accidental, by which an electric circuit or equipment is connected to the earth, or to some conducting body of relatively large extent that serves in place of the earth.

Bonding The permanent joining of metallic parts to form an electrically conductive path that will assure electrical continuity and the capacity to conduct safely any current likely to be imposed.

Common Bonding Network (CBN) The principal means for affecting bonding and earthing inside a building.

Key Terminology

Recommended Sizing of the Telecommunications Bonding Backbone (TBB)and Grounding Equalizer (GE) per J-STD-607-A

Recommended Cable Sizes for Grounding Applications

The TBB shall be a copper conductor. The minimum conductor size shall be a No. 6 AWG. The TBBshall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a 3/0 AWG. TheTBB may be insulated. The Bonding conductor for Telecommunications (BCT) shall be, as a minimum,the same size as the TBB.(1)

1. Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J-STD-607-A,October 2002.

Purpose

Use theFollowing

Code CablesOther connections to the TGB and TMGB,including building steel, main water pipe, etc.

#6 AWG, green insulated

Underfloor CBN #2 AWG, bareConnections to Underfloor CBN from pipes,ventilation ducts, etc.

#6 AWG, bare

Connection from Underfloor CBN to TGB 2/0 AWG, bare

Sizing of the TBB

TBB Lengthlinear M (ft) TBB Size (AWG)

less than 4 (13) 6

4 – 6 (14 – 20) 4

6 – 8 (21 – 26) 3

8 – 10 (27 – 33) 2

10 – 13 (34 – 41) 1

13 – 16 (42 – 52) 1/0

16 – 20 (53 – 66) 2/0

greater than 20 (66) 3/0*

*3/0 may not always be available. 4/0 is a more common size that may be substituted.

Page 31: Panduit Hiland Grounding

31For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover).

STRUCTUREDGROUND™ System for Data Center GroundingIntroduction

STRUCTUREDGROUND™ System for Data Center Grounding

Introduction

GroundingRoadmaps

Equipment& Rack

GroundingKits

CommonBondingNetwork

(CBN)Components

CrimpingTools

TechnicalInformation

Index

STRUCTUREDGROUND™ SYSTEM FOR DATA CENTER GROUNDING

Part Number Index

Part Number PageNumber

CCD-920-1 . . . . . . . . . . . . . . . . . . . . .27CD-920-1/0 . . . . . . . . . . . . . . . . . . . .27CD-920-2 . . . . . . . . . . . . . . . . . . . . .27CD-920-2/0 . . . . . . . . . . . . . . . . . . . .27CD-920-250 . . . . . . . . . . . . . . . . . . .27CD-920-3/0 . . . . . . . . . . . . . . . . . . . .27CD-920-4 . . . . . . . . . . . . . . . . . . . . .27CD-920-4/0 . . . . . . . . . . . . . . . . . . . .27CD-920-6 . . . . . . . . . . . . . . . . . . . . .27CD-920-8 . . . . . . . . . . . . . . . . . . . . .27CD-920H-2 . . . . . . . . . . . . . . . . . . . .27CD-920H-6 . . . . . . . . . . . . . . . . . . . .27CD-930H-250 . . . . . . . . . . . . . . . . . .27CLRCVR1-1 . . . . . . . . . . . . . . . . . . .21CLRCVR2-1 . . . . . . . . . . . . . . . . . . .21CLRCVR3-1 . . . . . . . . . . . . . . . . . . .21CT-100 . . . . . . . . . . . . . . . . . . . . . . .24CT-1550 . . . . . . . . . . . . . . . . . . . . . .24CT-1570 . . . . . . . . . . . . . . . . . . . . . .24CT-1700 . . . . . . . . . . . . . . . . . . . . . .24CT-2931 . . . . . . . . . . . . . . . . . . . . . .26CT-930 . . . . . . . . . . . . . . . . . . . . . . .25

GGB2B0304TPI-1 . . . . . . . . . . . . . . . .15GB2B0306TPI-1 . . . . . . . . . . . . . . . .15GB2B0312TPI-1 . . . . . . . . . . . . . . . .15GB4B0612TPI-1 . . . . . . . . . . . . . . . .15GB4B0624TPI-1 . . . . . . . . . . . . . . . .15GPL-14-X . . . . . . . . . . . . . . . . . . . . .22GPL-15-X . . . . . . . . . . . . . . . . . . . . .22GPL-8-Q . . . . . . . . . . . . . . . . . . . . . .22

HHTCT2-2-1 . . . . . . . . . . . . . . . . . . . .20HTCT250-2-1 . . . . . . . . . . . . . . . . . .20HTCT250-250-1 . . . . . . . . . . . . . . . .20HTCT6-6-1 . . . . . . . . . . . . . . . . . . . .20HTWC2-2-1 . . . . . . . . . . . . . . . . . . . .19HTWC250-2-1 . . . . . . . . . . . . . . . . . .19HTWC250-250-1 . . . . . . . . . . . . . . . .19HTWC6-6-1 . . . . . . . . . . . . . . . . . . . .19

KKP1-C . . . . . . . . . . . . . . . . . . . . . . .23KP2-L . . . . . . . . . . . . . . . . . . . . . . . .23

LLCC1-14AW-E . . . . . . . . . . . . . . . . . .17LCC1-38DW-E . . . . . . . . . . . . . . . . .17LCC1/0-14AW-X . . . . . . . . . . . . . . . .17LCC1/0-38DW-X . . . . . . . . . . . . . . . .17LCC10-14BW-L . . . . . . . . . . . . . . . . .17LCC10-14JAW-L . . . . . . . . . . . . . . .17LCC10-14JAWF-L . . . . . . . . . . . . . . .17LCC10-14JAWH-L . . . . . . . . . . . . . . .17LCC2-14AW-Q . . . . . . . . . . . . . . . . .17LCC2-38DW-Q . . . . . . . . . . . . . . . . .17LCC2/0-14AW-X . . . . . . . . . . . . . . . .17LCC2/0-38DW-X . . . . . . . . . . . . . . . .17LCC250-12DW-X . . . . . . . . . . . . . . . .17LCC250-38DW-X . . . . . . . . . . . . . . . .17LCC3/0-12W-X . . . . . . . . . . . . . . . . .17LCC3/0-38DW-X . . . . . . . . . . . . . . . .17LCC4-14ADW-L . . . . . . . . . . . . . . . . .17LCC4-38DW-L . . . . . . . . . . . . . . . . . .17LCC4/0-14AW-X . . . . . . . . . . . . . . . .17LCC4/0-38DW-X . . . . . . . . . . . . . . . .17LCC6-10ABW-L . . . . . . . . . . . . . . . . .17LCC6-14BDW-L . . . . . . . . . . . . . . . . .17LCC6-14EW-L . . . . . . . . . . . . . . . . . .17LCC6-14JAW-L . . . . . . . . . . . . . . . . .17LCC6-14JAWF-L . . . . . . . . . . . . . . . .17LCC6-14JAWH-L . . . . . . . . . . . . . . . .17LCC6-38BDW-L . . . . . . . . . . . . . . . . .17LCC6-56BW-L . . . . . . . . . . . . . . . . . .17LCC8-10ABW-L . . . . . . . . . . . . . . . . .17LCC8-14ABW-L . . . . . . . . . . . . . . . . .17LCC8-14DW-L . . . . . . . . . . . . . . . . . .17LCC8-38DW-L . . . . . . . . . . . . . . . . . .17LCCX1-14A-X . . . . . . . . . . . . . . . . . .18LCCX1-38D-X . . . . . . . . . . . . . . . . . .18LCCX1/0-14A-X . . . . . . . . . . . . . . . .18LCCX1/0-38D-X . . . . . . . . . . . . . . . .18LCCX2-38D-E . . . . . . . . . . . . . . . . . .18LCCX2/0-14A-X . . . . . . . . . . . . . . . .18LCCX2/0-38D-X . . . . . . . . . . . . . . . .18LCCX250-38D-X . . . . . . . . . . . . . . . .18LCCX3/0-38D-X . . . . . . . . . . . . . . . .18LCCX4-14AB-L . . . . . . . . . . . . . . . . .18LCCX4-38BD-L . . . . . . . . . . . . . . . . .18LCCX4/0-38D-X . . . . . . . . . . . . . . . .18LCCX6-10B-L . . . . . . . . . . . . . . . . . .18LCCX6-14AB-L . . . . . . . . . . . . . . . . .18LCCX6-14D-L . . . . . . . . . . . . . . . . . .18LCCX6-38AC-L . . . . . . . . . . . . . . . . .18LCCX6-38D-L . . . . . . . . . . . . . . . . . .18LCCX8-10AB-L . . . . . . . . . . . . . . . . .18LCCX8-14AB-L . . . . . . . . . . . . . . . . .18LCCX8-14D-L . . . . . . . . . . . . . . . . . .18LCCX8-38D-L . . . . . . . . . . . . . . . . . .18LTYK . . . . . . . . . . . . . . . . . . . . . . . . .15

PPV10-10RX-L . . . . . . . . . . . . . . . . . .16PV10-14RX-L . . . . . . . . . . . . . . . . . .16PV10-6RX-L . . . . . . . . . . . . . . . . . . .16PV10-8RX-L . . . . . . . . . . . . . . . . . . .16PV14-10RX-C . . . . . . . . . . . . . . . . . .16PV14-14RX-C . . . . . . . . . . . . . . . . . .16PV14-6RX-C . . . . . . . . . . . . . . . . . . .16PV14-8RX-C . . . . . . . . . . . . . . . . . . .16

RRGCBNJ660P . . . . . . . . . . . . . . . . . .11RGEJ1024PF . . . . . . . . . . . . . . . . . .12RGEJ1024PH . . . . . . . . . . . . . . . . . .12RGEJ1036PF . . . . . . . . . . . . . . . . . .12RGEJ1057PF . . . . . . . . . . . . . . . . . .12RGEJ624PF . . . . . . . . . . . . . . . . . . .12RGEJ624PH . . . . . . . . . . . . . . . . . . .12RGEJ636PF . . . . . . . . . . . . . . . . . . .12RGEJ657PF . . . . . . . . . . . . . . . . . . .12RGESD-1 . . . . . . . . . . . . . . . . . . . . .13RGRB19 . . . . . . . . . . . . . . . . . . . . . .14RGREJ1096 . . . . . . . . . . . . . . . . . . .14RGREJ696 . . . . . . . . . . . . . . . . . . . .14RGRKCBNJ . . . . . . . . . . . . . . . . . . .14RGRKCBNJEJ . . . . . . . . . . . . . . . . .14RGS134-1 . . . . . . . . . . . . . . . . . . . . .11RGS134-10-1 . . . . . . . . . . . . . . . . . .11RGTBS-C . . . . . . . . . . . . . . . . . . . . .14RGTBSM6-C . . . . . . . . . . . . . . . . . . .14RGTS-C . . . . . . . . . . . . . . . . . . . . . .14RGTSM6-C . . . . . . . . . . . . . . . . . . . .14RGW-100-1 . . . . . . . . . . . . . . . . . . . .13RGW-12-1 . . . . . . . . . . . . . . . . . . . . .13RGW-32-1 . . . . . . . . . . . . . . . . . . . . .13

WWB12-L . . . . . . . . . . . . . . . . . . . . . . .23WB34-X . . . . . . . . . . . . . . . . . . . . . .23WB58-Q . . . . . . . . . . . . . . . . . . . . . .23

Part Number PageNumber

Part Number PageNumber

Page 32: Panduit Hiland Grounding

32

Termination SolutionsSA-TMCB02

!PAN-TERM ® Terminals!PAN-TERM ® Disconnects!PAN-TERM ® Splices!PAN-TERM ® Ferrules!PAN-LUG™ Compression

Connectors

!Crimping Tools and Dies!PAN-LUG™ Mechanical Connectors!PAN-LUG™ Grounding Connectors!Support Products

Wiring DuctSA-WDCB05

!PANDUCT ® Slotted WallWiring Duct

!PANDUCT ® Solid Wall Raceway!PANDUCT ® Halogen Free Slotted

Wall Wiring Duct !PANDUCT ® Flush Cover Round

Hole Wiring Duct

!PANDUCT ® Hinged Slotted WallWiring Duct

!PANDUCT ® Flexible Wiring Duct!PANDUCT ® Low Smoke Slotted

Wall Wiring Duct!Wiring Duct Accessories and

Installation Tools

Surface RacewaySA-SRCB02

!Office Furniture Raceway!Cove Raceway!PAN-WAY ® TG-70 Surface Raceway!PAN-WAY ® T-70 & Twin-70

Surface Raceway!PAN-WAY ® T-45 Surface Raceway!ULTIMATE ID ® Network

Labeling System

!Faceplates, Surface Mount OutletBoxes & Labeling Administration

!PAN-WAY ® LD Profile SurfaceRaceway

!PAN-WAY ® T130 Surface Raceway!PAN-POLE ™ Outlet Poles

PANDUIT is a global leader in cabling and communication products,delivering end-to-end solutions in support of

demanding electrical and networking requirements.

PANDUIT Catalogs

Stainless Steel ProductsSA-SSCB06

!PAN-STEEL ® Stainless Steel Cable Ties

!PAN-STEEL ® Stainless SteelStrapping

!Installation Tools

!PAN-STEEL® System Accessories!PAN-STEEL® System

Permanent Identification

Identification ProductsSA-IDCB16

!Hand-Held Printers!Desktop Printers!Labeling Software!Computer Printable Labels!Wire Markers

!Lockout/Tagout Products!Voltage Markers!Warning Labels!Safety Signs and Tags!Letters and Numbers

Wiring Accessories/Abrasion ProtectionSA-CTCB03

!Adhesive Backed Cable TieMounts

!Screw Applied Cable Tie Mounts!Flat Cable Mounts!Fixed Diameter Clamps!Harness Board Accessories!Spiral Wrap

!Grommet Edging!Braided Expandable Sleeving!Corrugated Loom Tubing

and Fittings!Heat Shrink Tubing!Non-Shrink PVC Tubing!PAN-WRAP ™ Split Harness Wrap

Network ConnectivitySA-NCCB04

!Modules!ULTIMATE ID ® System!Work Area!Zone Cabling!Patch Panels, Copper Patch

Cords & Punchdowns!Fiber Connectors, Enclosures &

Patch Cords

!Racks & Cable Management!Grounding and Bonding!Fiber Routing!Surface Raceway!Labeling & Administration!Cable Ties & Accessories

Cable TiesSA-CTCB03

!PAN-TY ® Cable Ties!PAN-TY ® Clamp Ties!PAN-TY ® Push Mount Ties!PAN-TY ® Marker Ties!DOME-TOP ® Barb Ty Cable Ties!DOME-TOP ® Barb Ty Clamp Ties!DOME-TOP ® Barb Ty Marker Ties

!CONTOUR-TY ® Cable Ties!DURA-TY ™ Cable Ties!BELT-TY ™ In-Line Cable Ties!TAK-TY ® Hook & Loop Cable Ties!STA-STRAP ® Cable Ties!Cable Tie Installation Tools!Custom Hot Stamping