Page 1/31 CHATS-AS October 9-11, 2013 | Cambridge, MA © 2013, ITER Organization Process Analyses of...
-
Upload
rodolfo-helme -
Category
Documents
-
view
217 -
download
4
Transcript of Page 1/31 CHATS-AS October 9-11, 2013 | Cambridge, MA © 2013, ITER Organization Process Analyses of...
Page 1/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Process Analyses of ITER Toroidal Field Structure Cooling Scheme
R. MAEKAWA, S. TAKAMI*, A. IWAMOTO*, H.S. CHANG, A. FORGEAS, M. CHALIFOUR, L. SERIO
IO/CEP/PED/CSE*National Institute for Fusion Science
At CHATS-AS
October 9, 2013
Disclaimer: The views and opinions expressed herein do not necessarily reflect those of the ITER Organization
Page 2/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Outline
• Background
• Objective
• Introduction– ITER cryogenic system– ACB-ST and ST modeling
• Nominal operation
• Mitigation
• Disruption
• Conclusion
Page 3/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
ITER TOKAMAK
TF coil/structureNb3Sn/SS: 18
CS Nb3Sn: 6
PF/CCNbTi: 6/63
Cryostat24 m high x 28 m dia.
~4400 tons for ST can be used as thermal damper
Page 4/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Background
• ITER; – Achieve Q>10 Production of 500MW fusion power– DT phase starting from 2027
– 15 MA baseline -> Substantial dynamic heat load from TOKAMAK ~50 kW variations in 1800s• Eddy current • AC losses• Nuclear heating
Page 5/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Background
• Substantial Dynamic Heat Load during POS ~50 kW
• Cryoplant has to demonstrate its robustness– Countermeasure
A Cryoplant operation in terms of “Boosting” (40-100kW)B “Mitigation” to surpass peak-to-peak heat load
– Plan A: Cryoplant boosting• Difficulties to balance three CBs operated in parallel
to adjust the refrigeration power of 50 kW in 1800s– Plan B: Mitigation
• Utilization of massive TF ST as thermal buffer– Plan C??
Page 6/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Objective; Mitigation scheme implementation• Achieve (provide) a quasi-static operating
condition for Cryoplant (plant friendly)
• “Mitigation” with TF-ST, applying different process controls to Auxiliary Cold Box (ACB-ST)
– Developed dynamic simulation model as implementing a classical Proportional-Integral (PI) Control
• ALL ANALYSES ARE BASED ON THE CRYOPLANT POINT OF VIEW
Page 7/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
ITER Cryogenic System
• 75 kW @4.5K (40-110 KW ADAPTATION)
TF PF/CC
CCB
ST
ST
Cold Compressor
SHe LHe heat exchanger
Cold Circulator
Clients
CB1 CB2 CB3
Cryoplant
PFTF
CC
CP
CP
CTCB
CS
CS
LHe Tank LHe Subcooler
ACB
Page 8/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
ACB-ST & ST
ACB-ST
Supply Cryoline (55m)
Return Cryoline (49m)
Supply Feeder (68m)
Return Feeder (38m)
Transit time of SHe~300s
Page 9/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
TF ST Cooling Pipe Layout
BU(20)~17m long
Outer Board Leg: Connected to Gravity Support
BP(14)~18m
AP(20)~16m
AU(20)~19m
Cross section of AU&AP
• Cooling pipe layout for BU
Page 10/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Massflow Rate for each Segment
# of channel
L (m)
Transit (s)
m (g/s) Re f h(W/m2-K)
Total m (g/s)
AP 20 16.0 38.4 2.7 1.18e5 0.018 616.11 54.0
BP 14 17.7 42.5 2.7 1.18e5 0.018 616.11 37.8
AU 20 19.0 112.0 1.1 4.81e4 0.021 300.39 22.0
BU 20 17.2 101.4 1.1 4.81e4 0.021 300.39 22.0
Page 11/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
ACB-ST w/ ST
• Nominal Operation– PI control
• LHe level (SHE feed)• Subcooler pressure
(LP Return)
• Mitigation– “Inferential” control
1. Speed variation2. HX bypass3. ST bypass
SHeReturn
HX bypass
LICPIC
ST bypassSupply
Return
FIC
AP20
AU20
BU20
BP14
1
2
3
41 2
3
Page 12/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Modeling
• One cooling channel w/ massive weight piping
• Four spatial divisions with different heat inputs
• SHe Cooling Module is based on 1st law of thermo dynamics
Integrated Cooling Channel in each Segment (h and A_heat
transfer)
BU(1)
BP(1)
AP(1)
AU(1)
dt
dEWQ
dAnvP
edVet
WQ
SCVC
Page 13/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Heat Load
• Eddy current & Nuclear heating on AP1 & AP3– 17.4 kW nuclear heating to define the upper bound
(13.8kW as baseline)
AP1
AP2
AP3
AP4
Page 14/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
NOMINAL OPERATIONCope w/ Dynamic Heat Load by Adjusting Cooling power
Page 15/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Nominal Operation-processArrangement of cooling circuit w/ process control
• HX bypass & ST bypass are closed!
• PIC is implemented at LP Return line
SHeReturn
AP20
AU20
BU20
BP14
Page 16/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Simulation Result-Nominal operation
• 14.2MJ of thermal energy deposition in each POS
• Variation of heat loads & LHe level in the
subcooler
Page 17/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
SHE Loop-Nominal operation
• SHe loop behavior – T & P variations & m variation in each segment
• 1
Page 18/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Summary-Nominal Operation
• Peak-to-peak variation of heat loads (~10 kW)
w/ 14.2MJ of thermal energy deposition
• Good tracking performance of LHe level and subcooler pressure regulations
• Impact on massflow rate is acceptable for cold circulator operation and TF coil operation; temporary reduction of flow rates
• Feasibility of operation depends on Cryoplant
Page 19/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
MITIGATIONReducing the impact of Cryoplant operation
Page 20/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
SHeReturn
AP20
AU20
BU20
BP14
2
Mitigation; Circulator Speed
Page 21/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
SHeReturn
AP20
AU20
BU20
BP14
2
Mitigation-HX Bypass
HX massflow change
Page 22/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Mitigation-ST Bypass
Massflow at ST
• Two disturbances for
CC– POS and m regulations
SHeReturn
AP20
AU20
BU20
BP14
3
•
Page 23/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Mitigation
• Replace peak profile to Flat Topped Peak
• Manipulation of 14.2MJ in 30 min.
Page 24/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Variation in HX and/or ST
Control Action-MitigationSpeed & HX bypass ST bypass with Supply
valve
Page 25/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
ST Cooling Effect-MitigationEffective cooling for
ST Loop T variation at ST
Page 26/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Summary; Mitigation
• Three schemes demonstrate comparable results for Mitigation
• Speed variation should be the first choice to implement for the process control
– Pumping energy saving– Constant ST inlet temperature; TF Coil operation– Production of LHe during “Dwell” (as providing the
constant refrigeration power from Cryoplant)
Page 27/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Disruption• Thermal energy deposition ~10 MJ in 1sec.
• Heat load to Cryoplant is not acceptable– Compressor, turbine, cold compressor trips– Exceed the HX performance
Cooling loop; HX bypass
Not compliant
Page 28/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Disruption; summary
• The same control logic as Mitigation cannot be applicable in the case of disruption
• Dedicated control logic has to be developed and implemented
– To be compliant with a project requirement
Page 29/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
• Impact from m
regulation
Cold Circulator Operation
Disruption-Nominal ST bypass-Mitigation•
Page 30/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Conclusion• Nominal operation can be sustained based on
the classical PI control (as long as Cryoplant cope w/)
• Mitigation schemes demonstrate comparable
result
• Circulator speed variation should be implemented based on the energy saving, constant inlet temp. to ST and more LHe accumulation in the Tank
• Circulator operation is enclosed in the high efficiency envelope
• ST bypass demands wider operation field on cold circulator
Page 31/31
CHATS-AS October 9-11, 2013 | Cambridge, MA© 2013, ITER Organization
Open Issue
• Dedicated control is required in the case of DISRUPTION
• Risk of Cryoplant shutdown– Trip of expansion turbine, compressor station, cold
compressor