PACKAGED STORAGEWATER HEATERSSingle-Wall or Double-Wall Tube Bundles
Also Available:
Unpackaged Storage Water Heaters
Features• Completely assembled storage water heaters with tube bundle or electric heating elements, automatic controls, valves, piping, circulating system, wiring, insulation and skid mounted• Provides for peak load outputs and utilizes off peak boiler capacity• Small, medium, or large storage volumes available in vertical and horizontal models• ACE Temp Control System• Tube bundle readily accessible without moving heater, shell or foundation• Quality components for high performance
Standard EquipmentTank• ASME Section VIII Div I vessel• National Board registered• 125 and 150 psig design working pressure• 12" x 16" manway on 42" diameter and larger diameter tanks; inspection openings for all others• Carbon steel fittings• Lining: Glass (160ºF), cement (180ºF), pre-krete (350ºF), unlined• Lifting straps or lugs• Drain fittings• Anodes on glass lined tanks
Tube Bundle• 150 psig design working pressure
• SB-75 seamless copper U-tube• Single wall tubing• Steel cap and tube sheet
Support• Vertical: pipe legs• Horizontal: saddles
Controls• Water-to-water: Self-operating, Electric or Pneumatic control valve (standard) Steam-to-water: Electric, Pneumatic or Pilot-operated control valve • Temperature-Pressure gauge• High limit aquastat• 150 psig ASME pressure relief valve• ACE Temp Control System, including all bronze circulating pump with copper piping and isolation valve• Steam to water model only: F&T steam trap and vacuum breaker• Panel mounted gauges
Insulation & Jacketing• 22 gauge galvanized steel jacket, backed by 11/2" of insulation• Painted with primer
Packaged Storage Water HeatersThe ACE storage water heaters are dependable and quiet. They provide peak load output and use off-peak boiler capacity. Units are available in a variety of confi gurations to meet a wide range of requirements for temperature rise and G.P.H. recovery.
18
Optional EquipmentTube Bundle• Double wall copper or cupro-nickel (90/10) tubing• Single wall cupro-nickel (90/10) or 304 stainless steel tubing• Stainless steel cap and tube sheet• High temp water applications• 4 pass tube bundle design
Support• Vertical: Ring base, angle iron legs• No support / leg coupling, only for unpackaged
Controls• Pneumatic or electric control valve, with temperature controller NEMA 1 control panel and inlet strainer• Unpackaged• Double safety solenoid dump valve• Building automation relays• Alarm bell with silencer switch
Operating Controls• Digital panel• Remote SetPoint panel• Local monitoring panel• Building Automation panel• Ajax Communication Gateway
Insulation & Jacketing• Mirror finish stainless steel jacketing• 3" thick insulation
Vertical PackageStorage Water HeaterPhoto may vary from actual model
19
A.S.M.E.
Photo may vary from actual model
Series
www.ajaxboiler.com
Packaged Storage Water Heaters
VERTICALSTEAM-TO-WATERPILOT-OPERATED
HORIZONTALSTEAM-TO-WATERPILOT-OPERATED
Packaging items may extend beyond vessel dimensions. For vertical packaging, add approximately 15" to tank height for overall height and 24" diameter for depth. For horizontal packaging, size is tank diameter and overall length add approximately 15" (for base) to obtain height and 24" to overall length to allow for coil and controls. Output is based upon clean copper tube condition. Ajax recommends 25% to 75% oversizing depending upon hardness of water. Tubes should be inspected frequently and descaled as required.1Ace Temp Control System Automatic Rapid Temperature Response. The Ace Temp Control System will accurately vary the fl ow of steam of the heating coil in proportion to the variation in fl ow and temperature of the domestic water demands. Ace Temp Control System provides rapid response by locating control bulb in recirculating line thereby eliminating delays due to lengthy bleed lines. Ace Temp Control System senses blended water temperature for instant smooth opening and closing of steam control valve, also eliminates excessive cycling of steam valve that can occur when short bursts of cold water are fl ushed over an immersed sensor bulb.
20
Steam Pressure Gauge
VaccumBreaker
Control System1
with Sensors
Temp. & Press. Gauge
Lifting LugsHot Water Outlet
CirculatorPump
RecirculationLine
Condensate Out
Cold Water Inlet
Strainer
11/2" Insulation &Metal Jacketing
Anode(for glass lined tanks)
Relief Valve
STORAGE SECTION
HEATING SECTION
DrainDouble
WallSingleWall
Manhole12"x16"
(for 36" Dia. and up tank only)
Safety Solenoid
Aquastat
ControlBox
Steam In
Control Valve
Plug Valve& Piping
Coil PullArea
Manhole12"x16" (for 36" Dia.and up tank only)
Lifting Lugsor StrapsHot Water Outlet
DoubleWall
Anode(for glass lined tanks)
Steam Pressure Gauge
Control1
System withSensors
Temp. & Press. Gauge
Circulator Pump
Condensate Out
Steam In
11/2" Insulation &Metal Jacketing
Control Valve
Relief Valve
SingleWall
Cold In Drain
STORAGE SECTION
HEATING SECTION
Coil PullAreaAquastat
Strainer
Plug Valve& Piping
RecirculationLine
Control Box
VacuumBreakerSafety Solenoid
A.S.M.E.
A.S.M.E.
HORIZONTALSTEAM TO WATERPNEUMATIC
Packaging items may extend beyond vessel dimensions. For vertical packaging, add approximately 15" to tank height for overall height and 24" diameter for depth. For horizontal packaging, size is tank diameter and overall length add approximately 15" (for base) to obtain height and 24" to overall lenght to allow for coil and controls. Output is based upon clean copper tube condition. Ace recommends 25% to 75% oversizing depending upon hardness of water. Tubes should be inspected frequently and descaled as required.1Ace Temp Control System Automatic Rapid Temperature Response. The Ace Temp Control System will accurately vary the fl ow of steam of the heating coil in proportion to the variation in fl ow and temperature of the domestic water demands. Ace Temp Control System provides rapid response by locating control bulb in recirculating line thereby eliminating delays due to lengthy bleed lines. Ace Temp Control System senses blended water temperature for instant smooth opening and closing of steam control valve, also eliminates excessive cycling of steam valve that can occur when short bursts of cold water are fl ushed over an immersed sensor bulb.
VERTICALSTEAM-TO-WATERPNEUMATIC
21
Anode(for glass lined tanks)
Temp. & Press. Gauge
Lifting strap or lugsHot WaterOutlet
Circulator Pump
Condensate Out Cold Water Inlet
Steam In
11/2" Insulation &Metal Jacketing
Drain
Relief Valve
To air supply
DoubleWall
SingleWall
Manhole12"x16" (for 36" Dia.and up tank only)
STORAGE SECTION
HEATING SECTIONStrainer
Plug Valve& Piping
Control Valve
AquastatSafety Solenoid
Steam Pressure Gauge
Control Box
Control1
System withSensors
RecirculationLine
Coil PullArea
Steam Pressure Gauge
Temp. & Press. Gauge
Hot Water Outlet
Circulator Pump
RecirculationLine
Cold Water Inlet
Strainers
11/2" Insulation &Metal Jacketing Anode
(for glass lined tanks)
PneumaticControl
To air supply
Relief Valve
DoubleWall
SingleWall
Safety Solenoid
Aquastat
Condensate Out
Lifting lugs
Coil PullArea
Control Valve
Control Box
Control System1
with Sensors
Drain Plug Valve& Piping
HEATING SECTION
STORAGE SECTION
A.S.M.E.
A.S.M.E.
Series
www.ajaxboiler.com
Packaged Storage Water Heaters
Packaging items may extend beyond vessel dimensions. 3-way blending valve may vary according to manufacturer’s design. Please check with factory for specifi c piping. For vertical packaging, add approximately 15" to tank height for overall height and 24" diameter for depth. For horizontal packaging, size is tank diameter and overall length add approximately 15" (for base) to obtain height and 24" to overall lenght to allow for coil and controls. Output is based upon clean copper tube condition. Ace recommends 25% to 75% oversizing depending upon hardness of water. Tubes should be inspected frequently and descaled as required.1Ace Temp Control System Automatic Rapid Temperature Response. The Ace Temp Control System will accurately vary the fl ow of steam of the heating coil in proportion to the variation in fl ow and temperature of the domestic water demands. Ace Temp Control System provides rapid response by locating control bulb in recirculating line thereby eliminating delays due to lengthy bleed lines. Ace Temp Control System senses blended water temperature for instant smooth opening and closing of steam control valve, also eliminates excessive cycling of steam valve that can occur when short bursts of cold water are fl ushed over an immersed sensor bulb.
VERTICALWATER-TO-WATERPNEUMATIC
HORIZONTALWATER-TO-WATERPNEUMATIC
22
ReliefValve
Temp. & Press. Gauge
Control Box
B.W. Temp.Gauge
In & Out
CirculatorPump
Anode(for glass lined tanks)
Pneumatic Control
Boiler WaterSupply Inlet
Safety Solenoid
Cold Water Inlet Drain
Lifting strap or lugs
Air Supply
Coil PullArea
Hot WaterOutlet
DoubleWall
SingleWall
Manhole12"x16" (for 36" Dia.and up tank only)
Control Valve
Aquastat
Plug Valve& Piping
Boiler WaterReturn
Control System1
with Sensors HEATING SECTION
STORAGE SECTION
B.W. Temp.Gauge In & Out
Control System1
with Sensors
Drain
Lifting lugs
CirculatorPump
Temp. & Press.Gauge
Recirculation Line
Boiler Water InletCold Water Inlet
Aquastat
Safety Solenoid
11/2" Insulation &Metal Jacketing
Anode(for glass lined tanks)
Control Box
To air supply
Relief Valve
Manhole12"x16" (for 36" Dia.and up tank only)
STORAGE SECTION
HEATING SECTION
DoubleWall
SingleWall
Coil PullArea
Boiler Water Return
Pneumatic Control
Control Valve
Plug Valve& PipingA.S.M.E.
A.S.M.E.
Packaging items may extend beyond vessel dimensions. 3-way blending valve may vary according to manufacturer’s design. Please check with factory for specifi c piping. For vertical packaging, add approximately 15" to tank height for overall height and 24" diameter for depth. For horizontal packaging, size is tank diameter and overall length add approximately 15" (for base) to obtain height and 24" to overall lenght to allow for coil and controls. Output is based upon clean copper tube condition. Ace recommends 25% to 75% oversizing depending upon hardness of water. Tubes should be inspected frequently and descaled as required.1Ace Temp Control System Automatic Rapid Temperature Response. The Ace Temp Control System will accurately vary the fl ow of steam of the heating coil in proportion to the variation in fl ow and temperature of the domestic water demands. Ace Temp Control System provides rapid response by locating control bulb in recirculating line thereby eliminating delays due to lengthy bleed lines. Ace Temp Control System senses blended water temperature for instant smooth opening and closing of steam control valve, also eliminates excessive cycling of steam valve that can occur when short bursts of cold water are fl ushed over an immersed sensor bulb.
VERTICALWATER-TO-WATERSELF-OPERATING
HORIZONTALWATER-TO-WATERSELF-OPERATING
23
B.W. Temp.Gauge In & Out
Temp. & Press. Gauge
Lifting LugsHot Water Outlet
Circulator Pump
RecirculationLine
Boiler Water Inlet
Cold Water Inlet
Drain
Boiler WaterReturn
11/2" Insulation &Metal Jacketing
Anode(for glass lined tanks)
Relief Valve
DoubleWall
SingleWall
STORAGE SECTION
HEATING SECTION
CoilPullArea
Plug valve &piping
Manhole12"x16" (for 36" Dia.and up tank only)
Control System1
with Sensors
Control Valve
Relief ValveTemp. & Press. Gauge
B.W. Temp.Gauge In & Out
CirculatorPump
Anode(for glass lined tanks) 11/2" Insulation &
Metal Jacketing
Control Valve
Boiler WaterSupply Inlet
Lifting strap or lugs
DrainCold WaterInlet
Coil PullArea
Hot WaterOutlet
DoubleWall
SingleWall
HEATING SECTION
Manhole12"x16" (for 36" Dia.and up tank only)
STORAGE SECTION
Plug Valve& Piping
Recirculation Line
Boiler WaterReturn
A.S.M.E.
A.S.M.E.
Series
www.ajaxboiler.com
NOMINALBUNDLE
SIZE1
DIMENSION COMMONTO 2, 4, & 6 PASS 2-PASS 4-PASS 6-PASS
E* F G H JBUNDLE IN. K J
BUNDLE IN. K JBUNDLE IN. K
5 13 59/16 8 11/4 13/8 11/4 13/8 N/A N/A6 20 65/8 8 11/2 15/8 11/2 15/8 1 18 24 85/8 9 21/2 21/8 2 21/8 11/2 13/8
10 26 103/4 11 3 23/4 21/2 23/4 2 15/812 28 123/4 15 4F 31/4 3 31/4 21/2 214 30 14 17 4F 31/2 4F 31/2 3 21/416 34 16 19 5F 4 4F 4 4F 21/2
Unpackaged Storage Water HeaterHorizontal A.S.M.E. 125 or 150 psig Storage Water Heater with Standard Fittings
TANK DIAMETER (IN.)
18 24 30 36 42 48 54 60 66 72
(A) Water Conn. 11/2 11/2 2 2 2 3 3 3 3 3(B) Head Depth 6 71/2 9 101/2 12 131/2 11/2 161/2 171/2 20
Unpackaged Storage Water Heaters
Unpackaged Storage Water Heaters
24
A.S.M.E.
1 18" Dia. and larger bundles available. Consult factory. The dimensional table is also applicable for double-wall tube bundles.2 12"x16" Manway standard only on all Section VIII tanks 42" diameter and above. All others to have inspection openings as required by ASME Code.3 Refer to storage tank section.
Fitting locations to be dimensioned from head and shell joint. Tolerance ±2%.
CAP/BONNET CONFIGURATIONCAP/BONNET CONFIGURATION
2-PASS 4-PASS 6-PASS
C
C
C
CC
C
DD
DK
2-Pass bundles are furnished for all steam units. Multi-pass bundles are normally furnished for all hot water boiler units. 2-Pass bundles will be furnished if heating medium or boiler water fl ow is unknown.
* See E table below.
TANKDIA. 18 24 30 36 42 48 54 60 66 72
BUNDLESIZE E
5 5 5 8 86 6 6 10 11 11 12 12 138 7 7 9 9 13 13 14 14 15 1610 13 14 14 15 16 1712 14 15 15 16 17 1814 18 1916 19 20
Drain 11/2"
Coil Support ACold In
G
EEF
HH9"
Operating11/4" Control
3/4" Thermostat
ReliefValve
B
A Hot Out
4" 4"
STORAGE SECTION
HEATING SECTION
Manway2
Tank3 O.A.L.
Tank3 O.D.
6"
Bundle pull area
11/2" Recirc. far side
Anode openingsglass lined only
Vertical A.S.M.E. 125 or 150 psig Storage Water Heater with Standard Fittings
NOMINALBUNDLE
SIZE1
DIMENSION COMMONTO 2, 4, & 6 PASS 2-PASS 4-PASS 6-PASS
E F G H JBUNDLE IN. K J
BUNDLE IN. K JBUNDLE IN. K
5 8 16 59/16 8 11/4 13/8 11/4 13/8 N/A N/A6 8 20 65/8 8 11/2 15/8 11/2 15/8 1 18 9 24 85/8 9 21/2 21/8 2 21/8 11/2 13/8
10 10 26 103/4 11 3 23/4 21/2 23/4 2 15/812 12 28 123/4 15 4F 31/4 3 31/4 21/2 214 13 30 14 17 4F 31/2 4F 31/2 3 21/416 14 34 16 19 5F 4 4F 4 4F 21/2
TANK DIAMETER (IN.)
18 24 30 36 42 48 54 60 66 72
(A) Water Conn. 11/2 11/2 2 2 2 3 3 3 3 3(B) Head Depth 6 71/2 9 101/2 12 131/2 151/2 161/2 171/2 20
G
TOP VIEW
25
A.S.M.E.
1 18" Dia. and larger bundles available. Consult factory. The dimensional table is also applicable for double-wall tube bundles.2 12"x16" Manway standard only on all Section VIII tanks 42" diameter and above. All others to have inspection openings as required by ASME Code.3 Refer to storage tank section.
Fitting locations to be dimensioned from head and shell joint. Tolerance ±2%.
CAP/BONNET CONFIGURATIONCAP/BONNET CONFIGURATION
2-PASS 4-PASS 6-PASS
C
C
C
CC
C
DD
DK
2-Pass bundles are furnished for all steam units. Multi-pass bundles are normally furnished for all hot water boiler units. 2-Pass bundles will be furnished if heating medium or boiler water fl ow is unknown.
11/2" Recir. Far Side
3/4" Thermostat
OperatingControl
STORAGE SECTION
HEATING SECTION
Anode OpeningGlass Lined Only
Coil SupportDrain
F
E
BB
A Cold In
ReliefValve
A Hot Out
G
Manway2
9"
H
Tank3 O.D.
Tank3 O.A.L.
Bundlepull area
Series
35
Double-Wall Tube BundlesMeets Uniform Plumbing Code requirements for heating potable water. Prevents cross-contamination. Tested and certifi ed by the City of Los Angeles Testing Laboratory.
• Easy Inspections and low maintenance• Fully visible, 360º vented leak detection between tubesheets.• Bolting and gaskets for potable water and heating medium are completely independent.• Individual tube access for easy maintenance.• Optional: Tubesheet contacting potable water is solid 304 stainless steel.• Used to upgrade present single-wall tube bundles.• Available in storage semi-instantaneous water heaters and exchangers with copper or
cupro-nickel tubes and carbon steel or stainless steel tube sheets (Up to 400 PSIG with cupro-nickel tubes)
Double-Wall Protection PerformanceTube failure can be caused by corrosion, erosion, and vibration, and can result in the contamination of the domestic water system to be contaminated by a heating medium such as steam, hydronic water, glycol solution, etc. There is no practical way to have the heating medium sterile or free from harmful treatment compounds or corrosion by-products. A low pressure heating medium circuit does not ensure contamination protection of indirect, single-wall water heaters. Whether they are shell and tube, shell and coil, plate and frame, or any other type, all consist of relatively thin wall heat transfer surface separating the heating medium from the domestic water system. Therefore, the potential for cross contamination is real and in some instances contamination has occured. Several states and cities are now insisting on double-wall vented construction in all direct type domestic water heaters. Plumbing codes have also been re-written to include double-wall protection. Ajax Boiler has developed the most practical, “state-of-the-art” double tube wall heaters to preclude any possibility of contaminating the domestic water system.
The Ace Series double-wall is the most positive form of double tube wall construction available, with no sacrifi ce in water heater effeciency or performance over a single tube wall heater.
The heat transfer surface is 5/8" O.D. x .042" thick inner wall and 3/4" O.D. x .042" outer wall SB-75 copper tubing. The .042" dimensions are actual net tube wall thicknesses which equal .084" thickness of total wall separation. This is more than twice the thickness of many single wall water heater products. Both inside and outside tube surfaces are smooth (prime) with no fins or surface irregularities to promote scale formation or corrosion attack.
Double-wall tubing has a similar overall heat conductivity as a single wall tube of equivalent wall thickness. The heat transfer capabilities were determined by actual tests conducted at the Ajax Boiler facilities. Each tube has multiple parallel and continuous vent paths.
www.ajaxboiler.com34
Condensing will occur during the combustion process when the combustion gases come in contact with cool heating surfaces of boilers and water heaters. Condensation will cause damage to all fi red boilers and water heaters.
The moisture from condensation will cause incomplete combustion which will reduce the combustion effi ciency and cause sooting of the boiler. Sooting will reduce the heat transfer effi ciency and clog the fl ue gas passages disrupting the combustion process. On atmospheric fi red boilers, clogged fl ue passages may cause fl ame roll out from the combustion chamber and a fi re hazard.
Moisture in the fl ue gases from condensation will cause rusting of the boiler tubes and the boiler stack and also damage boiler refractory and insulation.
Condensation can be prevented in properly designed boiler and water heating systems by maintaining inlet water temperatures above the dew point. Dew point, depending upon the atmospheric pressure, temperature and humidity conditions, will normally occur when the water inlet temperature is in the 120ºF to 130ºF range. It is generally accepted therefore, that 140ºF boiler water inlet temperature should be maintained to provide a small operating safety margin. Condensation damage can also be reduced by limiting cold start ups to once or twice a year. Night set back controls and delayed-system three way valves can minimize low temperature fi ring.
For low temperature applications such as water source heat pumps, low temperature heating systems, low temperature water heating application such as used in convalescent home, Ajax Boiler Inc. offer boiler and water heater “return loop blend” (RLB) packages. The RLB packages are furnished with manual valves for systems with relatively constant fl ow and temperature conditions. Failure to maintain 140ºF inlet water temperature will void your boiler warranty.
For a main loop fl ow of 3,520GPH, at a temperature rise of 30ºF, select Model B11G from the table. (Note: Maximum main loop supply temperature is 200ºF.)
For only main loop fl ow and temperature rise conditions, the boiler will heat a fraction of the main loop fl ow. The heated water will then be returned to the main loop where it will mix with unheated water to provide the desired loop temperature. For inlet water temperatures below 140ºF, some of the hot water exiting the boiler must be returned to the boiler water inlet to provide a blended inlet water temperature of 140ºF or higher. This return-blend action is activated by closing the blend valve until the temperature at the boiler inlet reaches 140ºF.
For boiler output higher than 1,200,000BTU/Hr, use multiple units.
LOW TEMPERATURE WATER HEATING SYSTEMSIZING CALCULATION AND EXAMPLE
TO SIZE: BOILER, CIRCULATORINPUT System Operating Conditions: Loop Flow (F1)GPM Loop Supply Temp. (T1)ºF Loop Return Temp. (T2)ºFSELECT Boiler Water Inlet Temp. (T3) Minimum Temp. 140ºF Boiler Water Outlet Temp. (T4) 180ºF to 200ºF
SIZING CALCULATION FORMULASHeat required to heat loop (required output) BTU/HR I1 = 500 F1(T1 - T2)Boiler input required BTU/HR I2 = I1 x 1.25Boiler Flow (boiler blend water) GPM F2 = F1(T1 - T2) / (T4 - T3)Flow required out of loop GPM F3 = I1 / 500 (T4 - T2)Circulator Flow GPM F4 = F2 - F3
SIZING CALCULATION EXAMPLEINPUT Flow and Temperatures: Normal LoadDesign Conditions: Input Loop Flow GPM F1 250 Loop Supply Temp. ºF T1 75 Loop Return Temp. ºF T2 70Boiler Operating Temperatures and Flow: Select Boiler Flow GPM F2 Boiler Water IN Temp. ºF T3 140 Boiler Water OUT Temp. ºF T4 200
Calculate: Heat required to heat loop (required output) BTU/HR I1 = 500 F1(T1 - T2) I1 = 500 (250) (75-70) I1 = 625,000 BTU/HR
Boiler input required BTU/HR I2 = I1 x 1.25 I2 = 781,250 BTU/HR
Suggest using size B8 Water Heater or Boiler - 800,000 BTU/HR Input
Boiler Flow (including blend water) GPM F2 = F1(T1 - T2) / (T4 - T3) F2 = 250 (75-70) / (200-140) F2 = 20.8 GPM
Flow required out of loop GPM F3 = I1 / 500 (T4 - T2) F3 = 625,000 / 500 (200-70) F3 = 9.6 GPM
Circulator Flow GPM F4 = F2 - F3
F4 = 20.8 - 9.6 F4 = 11.2 GPM
Return Loop Blend
Main Loop
Main Loop
T1
T4F2
F2
F1T2
T4F4
T3 F3
www.ajaxboiler.com36
The Ajax Boiler Factory limited warranty provides assurance that all products are free from manufactures defects at the time of shipment and meet specifi cations and performance described in the product literature. It is important to understand the difference between a factory warranty and an installed warranty. There are many factors that can occur to the products after they are shipped that the company has no control over and cannot fully verify. These include: 1. Hidden damage during the shipping 2. Handling damage 3. Damage during storage 4. Installation conditions 5. Other unknown variables in the system design, operations, maintenance, pulsation and vibrations.
The installed warranty is the responsibility of the architect, specifying engineer, contractor and or owner who jointly have control over the application, installation, location, operating and maintenance conditions. The AJAX BOILER INC. warranty excludes extended liabilities. Extended liability typically occurs when products are installed without proper drainage, fl ooding containment or when safety devices are not tested and repaired or replaced when needed. Product problems are often caused by the condition of the water, the lack of water treatment and or the improper treatment of the water, insuffi cient combustion air, improper draft conditions, bolts not re-tightened, pipes not fl ushed and cleaned of oil, metal chips, rags, vibration and pulsation etc. These are installation, operating and/or maintenance conditions that are beyond the seller’s responsibility and are not covered by the factory warranty, but may be covered by the installer’s warranty. The factory warranty covering company products is based upon extensive product development and testing. Combustion products under go certifi cation testing and approvals to Underwriters Laboratory standards. Auditing of the production of combustion products is conducted by a nationally recognized testing laboratory. Pressure vessel products are designed and manufactured to American Society of Mechanical Engineering (A.S.M.E.) and National Board (NB) Design standards. Design reviews, factory product manufacturing quality inspections and testing are carried out by a third party National Board authorized inspection agency. AJAX BOILER INC. products have proven themselves in service for over 85 years which indicates that the company products perform exceedingly well when normal installation, operating
and maintenance conditions exist. The following is a review from the terms and conditions of sale. Also included in paragraph two, below, is the AJAX BOILER INC. non-conformance policy.
1. AJAX BOILER INC. warrants its products against defective material and/or workmanship only. The warranty does not apply to operational failures, electrical failures, gasket leaks, and or other malfunctions caused by improper application, installation and or maintenance.2. It is the buyer’s responsibility to inspect and accept the product, when received, as conforming to their purchase order, specifi cations and approved drawings. All claims for non-conformance, errors, shortages, etc. must be made within 10 days after receipt of the shipment.3. AJAX BOILER INC. do not provide a warranty or guarantee, express or implied, in any manner, form, usage of trade, merchant-ability or fi tness which extend beyond the product description and quotation.4. AJAX BOILER INC. liability is limited to the factory repair or replacement of warranty failures, or non-conformance, upon the return of the product to the factory.5. AJAX BOILER INC. is not liable for any direct or consequential damages.6. The AJAX BOILER INC. warranty is based upon section 23161(2) of the uniform commercial code and is printed in the terms and conditions of sale which is referenced in every quotation, on the back of sales order acknowledgements and invoices. It is legally correct and is an industry standard policy.
THERMAL SHOCK In addition to our standard one (1) year warranty against defective parts and workmanship, AJAX BOILER INC. provides the following guarantee with all commercial hot water, forced circulation, space heating boilers: AJAX BOILER INC. guarantees this new boiler pressure vessel for ten (10) years after date of installation from damage due to thermal shock. Thermal shock occurs when cold makeup water, up to 150°F less than the boiler water outlet temperature, is added directly into the boiler while the boiler is operating within the normal temperature range from 140°F to 250°F with a temperature rise from 20°F to 40°F. This guarantee shall cover damage to the boiler tubes, tube headers, and tube sheets when such damage is attributed to unequal expansion, poor circulation and/or other causes quite often described as “thermal shock.” This guarantee does not cover damage or failures that can
37
be attributed to corrosion, condensation, scale, boiler treatment chemicals, dirt accumulation, low water conditions, or any other abnormal operating conditions. The liability of AJAX BOILER INC. is limited solely to the replacement of the complete pressure vessel, with tubes, if found by our inspection to be damaged by thermal shock. In no event shall AJAX BOILER INC. be held liable for replacement labor charges or for freight or handling charges.
AJAX BOILER INC. provides a limited warranty on its products aganst defective material and/or workmanship only. This limited warranty is not applicable to operational failures, electrical failures, gasket leaks, wear or malfunctions caused by improper application, installation, and/or maintenance.
The following Limited Warranty periods are from date of shipment: Boiler Pressure Vessels: One year.Carbon Steel Tank and Heat Exchanger Pressure Vessels: One year.Stainless Steel Tanks: Three years.Boiler Copper Fin Coils: Three years.High Effi ciency Condensing Boiler: One Year (Three years on Coil).Single-Wall or Double-Wall Tank/Exchanger Coils: One year.Single-Wall or Double-Wall Mini-Packs: One year.Atlas Series Condensing Boiler: One Year.Linings: (Pro-Rated Warranty) Section VIII Tanks: Glass 36” dia. and above (fi ve years). Glass 30” dia. and under (one year). Cement (fi ve years). Prekrete (ten years). In Section IV Tanks: Glass (one year).Controls: Components manufactured by other than AJAX BOILER INC. such as controls, instruments, forced draft burner, etc., provided with the boilers and packaged products are not covered by the AJAX BOILER INC. Warranty. However, AJAX BOILER INC. extends to the customer the same warranty provided by the manufacturer to AJAX BOILER INC. The customer shall receive the full benefi ts of adjustments made to AJAX BOILER INC. by the manufacturer.
Any claim for adjustment under this limited warranty must be made within the warranty period. AJAX BOILER INC.’s liability shall be limited to factory repair
or, at AJAX BOILER INC.’s option, replacement of all parts which, upon test and examination by AJAX BOILER INC., prove to be defective material and or workmanship and within the above limited warranty. If required by AJAX BOILER INC., parts which are claimed to be defective must be promptly delivered to the AJAX BOILER INC. facility, transportation charges prepaid. This warranty does not cover the cost of labor, removal, or installation of the warranted item during the limited period. This warranty is limited to the above and applies only for the period set forth. AJAX BOILER INC. will not be liable for any loss damage, direct, incidental or consequential damages of any kind, whether based upon warranty, contract, negligence or strict liability and arising in connection with the sale, use or repair of the products. AJAX BOILER INC.’s maximum liability shall not exceed the contract price for the products or component claimed to be defective or unsuitable. AJAX BOILER INC. does not warrant the product’s merchantability or fi tness for any particular purpose and in no event shall be held responsible for any consequential damages.
For complete Limited Warranty conditions see Section G and H under terms and conditions of sale.
The brand and product names contained within are trademarks or registered of their respective holders. Performance, dimensions, specifi cations are effective with date of issue and are subject to change without prior notice. AJAX BOILER INC. maintains a policy of continuous improvements and therefore reserves the right to change specifi cation without notice. AJAX BOILER INC. cannot be responsible for errors in typography or photography.