PACKAGED AIR CONDITIONERS R410A R410A 07P03E-C-0

Transcript of PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size...

Page 1: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

PACKAGED AIR CONDITIONERS R410AR410A

07P03E-C-0

Page 2: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

1

New Inverter SeriesNew Inverter Series

AB

C

DE

F

G

CLASSAAA

MHI models have cleared the class A standard, the highest energy saving level, with their high COP (coefficient of performance).

Thanks to achievement of the highest COP level in the industry,the energy consumption has been cut by 24~38% comparedwith our former models (constant speed models).

Industry Leading COPIndustry Leading COP

All models employ R410A, with RoHS* complianceAll models employ R410A, with RoHS* compliance

RoHS*RoHS : Restriction of Hazardous Substances

R410AR410A

Energy labeling“Class A”

Page 3: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

2

INDEXLINE-UP

INDOOR UNIT

OUTDOOR UNIT

WIRED REMOTE CONTROLLER

SUPER LINK Control System

OUTDOOR UNIT Dimensions

5

9

21

22

23

25

370mm

970mm

3.59mm2

Foot print

New model(8HP)Former model(8HP)

Foot print

720mm

1350mm

9.72mm2

A Reduction by

63%

Realization of significant reduction in size and weight comparedwith our former models, applying front blow outlet on all models.Reductions are 50% in weight of 6HP, 72% in volume of 8HP and63% in the foot print of 8HP.

Compact DesignCompact Design

R410A

Page 4: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

3

Compact Design

Size reduction and high efficiencyperformance on the compressor(4-6HP)

Improved efficiency of heat exchanger

Employment of DC fan motor has enabled to realize an excellent

efficiency of approx. 60% higher than former models.

Employment of DC fan motor

Reliability in the protection of compressor has been improved by

optimizing the controls of oil return, electronic expansion valve, etc.

ControllabilityA control over wide range of capacity and a high efficiency has been realized by inverter-driven scroll compressors.In addition, the starting current significantly is improved.The size has also been reduced by 3.2% in height and 31.8% in volume.

Employment of the inverter compressor(8/10HP)

Redesigning the fins to a straight shape has reduced the pressure loss of the airflow in the heat exchanger. Surface treatment on the fin has enhanced the frost resistance capacity compared with former models.Owing to the reduction in the size of heat exchanger, the appropriate number of circuits for each HP has been applied. Employment of a high-speed motor has increased the airflow and enabled to keep the cooling capacity under a condition of higher outdoor air temperatures*.

Former model New model

Heigh

t at 4

40 m

m

Outside diameter of shellø185mm

Hei

ght a

t 318

mm

ø133mm

Reduction in height by 27.7%Reduction in volume by 62.6%

Formercompressor

New modelDC rotary compressor

* Vector control means a. technique to realize an optimum control by converting the current wave to a smooth sinusoidal waveform

* Comparison with former models

��������� �� ����� ���

Former model New model Reduction

82 74 -8118 74 -44125 74 -51225 122 -103225 140 -85

4.0HP

63 60 -33.0HP

5.0HP

6.0HP

8.0HP

10.0HP

* Comparison with former models

��������� �� ������ ��

Former model New model Reduction

328 303 8%467 303 35%467 303 35%

1643 467 72%1643 540 67%

4.0HP

5.0HP

6.0HP

8.0HP

10.0HP

253 224 11%3.0HP

Employment of DC rotary compressor has enabled to utilize a high-speed range of up to 120 rps at the maximum to secure the required capacity.Optimum compressor control has been realized by employing the vector control*. Moreover, the starting current has been improved significantly compared with existing models.

* Limitation of use is around43: at the maximum.

�������� ������� ������ ���������� ���

FDCVA302HENR (3.0HP) FDCVA402HENAR/HESAR(4.0HP)

FDCVA502HENAR/HESAR(5.0HP)

FDCVA602HENAR/HESAR(6.0HP)

FDCVA802HESAR (8.0HP) FDCVA1002HESAR (10.0HP)

Width

380mm

185mm

380mm

350mm

390mm

455mmHeight

Height

Height Height

Width

Depth

350mmDepth

95mm

Easy installation Fits into elevators

Page 5: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

4

Consideration on the Environment

All models of the New inverter series use a new refrigerant R410A characterized by the ozone depletion coefficient being 0.

In order to comply with RoHS standard, the new inverter series products use lead-free solder. It was considered to be too difficult to use lead-free solder because it requires higher soldering temperatures at assembling, which could jeopardize the reliability of assembly, etc. PbF soldering method developed by MHI, however, has enabled a higher reliability for lead-free printed circuit boards.*"RoHS" is the abbreviation of the new European standard, which means reduction of hazardous substances.

Employment of lead-free solder

FDCVA802HESAR (8.0HP)

DC fan motor uses less energyPOINT1

Optimization of heat exchanger path.More efficient heating and cooling

POINT2

Super heat control with low pressure sensor, works better in tough conditions

POINT3

High efficiency refrigeration circuitPOINT4

Newly developed High efficiency DC scroll compressor

POINT5

970mm370mm

1

2

3

5

4

High Efficiency

New Inverter Technology means a 24~38% decrease in annual energy consumption.

Employment of the new refrigerant

A High Performance and Excellent Energy Conservation are achieved at the same time by an increased capacity of heat exchanger and employment of high efficiency DC motor etc.

Energy Conservation

Adapt to RoHS

10.0HPCalculation condition: based on JRA4048 place: Tokyo, type of the room: shop

8.0HP6.0HP4.0HP3.0HP0

5000

10000

15000 -24%

-34%

-38%-34%

-37%

Former modelNew model

12531.4

10307.5

7193.56510.9

3528.3

9486.4

6799.3

4491.14292.4

2220.2

5.0HP

-26%

5268.53878.1

[kWp/year]

Convenience

A dry contact is equipped on an indoor unit to meet a possible need for signal output on the site.

Installation workability (8&10HP)

Using piping attachment that has flared connection and brazed connection ends, there is no need conduct brazing work inside the outdoor unit.

XR5

CnT

XR1~5 : approx. DC12v

XR3

XR1

XR2

XR4

XR5

XR1

XR2

XR3

XR4

output1 (run)

output2 (heat)

output3 (comp on)

output4 (alarm)

common

Po

wer

sou

rce

in put

Flaredconnection

Brazedconnection

�� � �������� ���� ��� �� � ������ ��

NEW

270mm

Page 6: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

5

SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]

CEILINGSUSPENDEDMODEL

Model

FDTVA 4way-cassette

FDTCVA4way-cassette(600mm x 600mm)

FDUMVA(Low/Middle Static)

FDUVA(High Static)

FDKNVA

FDENVA

CEILINGCASSETTEMODEL

DUCTCONNECTEDMODEL

WALLMOUNTEDMODEL

Indoorunit

Outdoorunit

Indoorunit

Outdoorunit

Indoorunit

Outdoorunit

Indoorunit

Outdoorunit

Indoorunit

Outdoorunit

Set1phase

1phase

1phase

3phase

1phase3phase1phase

1phase

1phase

3phase

1phase3phase1phase3phase

1phase3phase

1.5

FDTA151R

FDTVA151HEN1R FDTVA201HEN1R FDTVA251HEN1R

FDTA201R FDTA251R

Set

FDTCA151R

FDTCVA151HEN1R FDTCVA201HEN1R

FDTCA201R

SetFDUMVA201HEN2R FDUMVA251HEN2R

FDUMA202R FDUMA252R

Set

FDKNA151R

FDKNVA151HEN1R FDKNVA201HEN1R FDKNVA251HEN1R

FDKNA201R FDKNA251R

Set

FDENA151R

FDENVA151HEN1R FDENVA201HEN1R FDENVA251HEN1R

FDCVA151HENR FDCVA201HENR FDCVA251HENR

FDCVA151HENR FDCVA201HENR

FDCVA201HENR FDCVA251HENR

FDCVA151HENR FDCVA201HENR FDCVA251HENR

FDCVA151HENR FDCVA201HENR FDCVA251HENR

FDENA201R FDENA251R

HPkWBtukcal

2.0 2.54.0

13,7003,440

5.017,1004,300

5.619,1004,816

Page 7: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

6

FDTVA302HEN1R

FDTA301R FDTA401R FDTA501R FDTA601R

FDUMVA302HEN2R FDUMVA402HEN2R FDUMVA502HEN2R FDUMVA602HEN2RFDUMVA402HES2R FDUMVA502HES2R FDUMVA602HES2R *FDUVA801HES2R *FDUVA1002HES2R

FDUMA302R FDUMA402R FDUMA502R FDUMA602R FDUA801R FDUA1001R

FDENVA302HEN1R FDENVA402HEN2R FDENVA502HEN2R FDENVA602HEN2RFDENVA402HES2R FDENVA502HES2R FDENVA602HES2R

FDCVA302HENR

FDCVA402HESAR FDCVA502HESAR FDCVA602HESAR

FDCVA402HENAR FDCVA502HENAR FDCVA602HENAR

FDCVA302HENR FDCVA402HENAR FDCVA502HENAR FDCVA602HENARFDCVA402HESAR FDCVA502HESAR FDCVA602HESAR FDCVA802HESAR FDCVA1002HESAR

FDCVA302HENRFDCVA402HESAR FDCVA502HESAR FDCVA602HESARFDCVA402HENAR FDCVA502HENAR FDCVA602HENAR

FDENA301R FDENA401R FDENA501R FDENA601R

3.0 4.0 5.0 6.0 8.0 10.0 7.0

23,9006,020

10.034,1008,600

12.542,70010,750

14.047,80012,040

20.068,30017,200

25.085,40021,500

Capacity Range (Rated Cooling Capacity)

*FDTVA402HEN2R FDTVA502HEN2R FDTVA602HEN2R

*FDTVA402HES2R FDTVA502HES2R FDTVA602HES2R

*Not available in 60Hz

Page 8: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

7

MULTI [OUTDOOR UNIT : INDOOR UNIT = 1 : 2, 3, 4] - V MULTI SYSTEM

Model

FDTVA

FDTCVA

FDUMVA

FDKNVA

FDENVA

Indoorunit

BranchPipe

TwinTripleDouble TwinTwinTripleDouble Twin

151 x 2

DIS-WA1

201 x 2

DIS-WA1

251x 2, 201+301

DIS-WA1

FDCVA302HENRFDCVA502HENARFDCVA502HESAR

FDCVA402HENARFDCVA402HESAR

Outdoor unit

HPkWBtuKcal

3.07.0

23,9006,020

4.010.0

34,1008,600

5.012.5

42,70010,750

Capacity

Different models(FDTVA,FDUMVA,FDENVA) and capacity(151 ~ 501) can be selected freely.Exception : In case of FDKNVA, FDTCVA series are selected, same model and capacity combination is required.

V Multi System Refrigerant piping work

Outdoor unit

Indoor unit

Liquid line

Gas line

39 190

1019

ID25.4

ID15.88

ID15.88

ID9.52

ID9.52

ID9.52

OD12.7 ID9.52

12

80

184

8

8010

Select the piping specification to fit the specification of Indoor unit and installation location.

Decision of piping specification

Outdoor unit

FDCVA302FDCVA402FDCVA502FDCVA602

151+151201+201251+251301+301

Indoor unit

Liquid line

Gas line

(Example)

24 210

8105

50811

ID15.88

ID15.88

ID15.88

ID9.52

ID9.52

ID9.52

ID9.52

OD15.88

2 piece 2 piece

ID12.7φ6.35 flared nut

11

48

180

8

8010

Models FDCVA302~602[Branch pipe set : DIS-WA1]

If you are using this model in combination with the 151 ~ 251 Series indoor units, use the irregular fittings 3 supplied with the branch piping set and make the branch piping (branch ~ indoor unit) liquid piping size 9.52.Mark is 4 to FDCVA302, 402 only.

Chart of shapes of branch piping parts (DIS-WA1)

Item Liquid pipe

Main pipeModelIndoor unit

combinations

Gas pipe Mark

1

Liquid pipe Reducer Mark

3

ReducerMark

2

Mark

4

1 to 4 in the drawing include parts provided in the branch piping set. It shows the codes for the shapes of different-diameter connections.Branch piping should always be arranged to have level or perpendicular branch. (Refer to the preceding page for details.)

Notes (1)

(2)

Branch pipe

Gas pipe

Main pipe Branch pipe

Notes (1)

(2)

9.52X t0.8 9.52X t0.812.7X t0.8

15.88X t1.015.88X t1.0

FDCVA802

FDCVA1002

401+401

501+501

(Example)Models FDCVA802, 1002[Branch pipe set : DIS-WB1]

Chart of shapes of branch piping parts (DIS-WB1)

Item Liquid pipe

Main pipeModelIndoor unit

combinations

1 to 3 in the drawing include parts provided in the branch piping set. It shows the codes for the shapes of different-diameter connections.Branch piping should always be arranged to have level or perpendicular branch. (Refer to the preceding page for details.)

Notes (1)

(2)

Branch pipe

Gas pipe

Main pipe Branch pipe

Notes (1)

9.52X t0.8

12.7X t0.89.52X t0.8 25.4X t0.8 15.88X t1.0

Gas pipe Mark

1

Liquid pipe Mark

2

Reducer Mark

3

2-Way Branch

FloorFloorMount sections levelwith the floor.

Floor

Mount sections perpendicular to the floor.

Floor

3-Way Branch

FloorMount sections levelwith the floor.

Floor

Mount sections perpendicular to the floor.

23

1

23

3

4

4

1

In the case of the FDCVA802, if the length of the main pipe exceeds 40 m, make the liquid piping size 12.7.

Up to four individual indoor units can be connected toa single outdoor unit.

V Multi System

Ideal for the installation in Large, single zone open Areas and L-shaped rooms, the Multi-

Type V series allows an extensive degree of flexibility in the selection of indoor units.

Specifically, the selection of indoor units with differing capacities and differing or similar

types is available, as is the selection of indoor units with similar capacities and differing

types. Furthermore, a maximum of up to four individual indoor units can be operated with

a single outdoor unit.

Twin

typ

e

The branch piping (both gas and liquid lines) should always be arranged to have a level or perpendicular branch.

Page 9: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

8

Combination in the table can be operated at 50/60Hz. FDTA401R is not available in 60Hz.

301 x 2201+201+201

DIS-WA1DIS-TA1

401 x 2, 301+501301+301+301

201+201+201+201DIS-WB1DIS-TB1

DIS-WA1 x 2, DIS-WB1 x 1

501 x 2201+401+401, 251+251+501, 301+301+401

251+251+251+251DIS-WB1DIS-TB1

DIS-WA1 x 2, DIS-WB1 x 1

FDCVA602HENARFDCVA602HESAR FDCVA802HESAR FDCVA1002HESAR

6.014.0

47,80012,040

8.020.0

68,30017,200

10.025.0

85,40021,500

Range (Cooling Capacity)

Chart of shapes of branch piping parts (DIS-TB1)

Outdoor unit

Indoor unit

Liquid line

Gas line

Outdoor unit

Indoor unit100 80 80

10

300

ID9.52

ID25.4

ID15.88×3 ID9.52×3100

10 14˚

100

8 8

217

8

3030

Liquid line

Gas line

8105

50

ID9.52φ6.35Flared nut

OD12.7 ID9.52

8010

OD15.88 ID12.7

8010

Model FDCVA602 [Branch pipe set : DIS-TA1]

Model FDCVA802, 1002[Branch pipe set : DIS-TB1]

Chart of shapes of branch piping parts (DIS-WB1)

Gas pipe Liquid pipe ReducerMark Mark Mark

39 190

1019

ID25.4

ID15.88

ID15.88

ID9.52

ID9.52

ID9.52

OD12.7 ID9.51

11

80

184

8

8010

Chart of shapes of branch piping parts (DIS-WA1)

Gas pipe Liquid pipe ReducerMark Mark Mark

24 210

8105

50

811

ID15.88

ID15.88

ID15.88

ID9.52

ID9.52

ID9.52 ID9.52

OD15.88 ID12.7

2 piece

2 piece

φ6.35 flared nut

11

48

180

8

8010

5

1 to 7 in the drawing include parts provided in the branch piping set. It shows the codes for the shapes of different-diameter connections.Branch piping should always be arranged to have level or perpendicular branch. Mark 3 shows for the FDCVA802 model only.

Item Liquid pipe

Main pipe 1st branch pipe 2nd branch pipe

9.52X t0.8

12.7X t0.89.52X t0.8

Main pipe 1st branch pipe 2nd branch pipe

Gas pipe

ModelFDCVA802

FDCVA1002

In the case of the FDCVA802, if the length of the main pipe exceeds 40 m, make the liquid piping size 12.7.Use the irregular fittings 6 supplied with the branch piping set on the indoor unit side, and make the branch piping (branch ~ indoor unit) liquid piping size 9.52.Mark is 7 to FDCVA802 only.

Notes (1)(2)

(3)

Notes (1)(2)(3)

Indoor unitcombinations

201+201+201+201

251+251+251+251

Item Liquid pipe

Main pipeModel

FDCVA802

Indoor unitcombinations

301+301+301

Outdoor unit

Indoor unitDIS-WA1

DIS-WA1

DIS-WB1

Gas line

Liquid line

6

Models FDCVA802, 1002 [Branch pipe set : DIS-WA1x2set, DIS-WB1x1set]

4321

6

7

Gas pipe Mark

1

Liquid pipe Mark

2

Reducer Mark

-

Reducer Mark

-

Reducer Mark

-

1 to 2 in the drawing include parts provided in the branch piping set. It shows the codes for the shapes of different-diameter connections.Branch piping should always be arranged to have level or perpendicular branch. (Refer to the preceding page for details.)

Notes (1)

(2)

9.52X t0.8 15.88X t1.015.88X t1.0

12.7X t0.825.4X t1.0

6

6

6

5

5

7

7

7

4

7

4

23

1

9.52X t0.8 9.52X t0.8

Branch pipe

Gas pipe

Main pipe

25.4X t1.0 15.88X t0.8

Branch pipe

Notes (1) If the length of the main pipe exceeds 40 m, make the liquid piping size 12.7.

Chart of shapes of branch piping parts (DIS-TA1)

100 80 80

8105

5010

300

ID9.52

ID15.88

ID12.7×3 ID9.52×3

ID9.52φ6.35Flared nut

10 14˚

100

8

237

8

3030

Item Liquid pipe

Main pipeModel

FDCVA602

Indoor unitcombinations

201+201+201

Gas pipe Mark

1

Liquid pipe Mark

2

Reducer Mark

3

1 to 3 in the drawing include parts provided in the branch piping set. It shows the codes for the shapes of different-diameter connections.Branch piping should always be arranged to have level or perpendicular branch. (Refer to the preceding page for details.)

Notes (1)

(2)

9.52X t0.8 9.52X t0.8

Branch pipe

Gas pipe

Main pipe

15.88X t1.0 12.7X t0.8

Branch pipe

Use the irregular fittings 3 supplied with the branch piping set on the indoor unit side, and make the branch piping (branch ~ indoor unit) liquid piping size 9.52.

Notes (1)

ID25.4 OD22.2 OD25.4 ID22.2

A B

This kit includes the following parts.

Install this kit according to the following.

(*) ID: Inner diameter.

Brazing Brazing

Service valve of theoutdoor unit (Gas side)

A B

Connection piping to be procured locally

Field piping φ22(OD) Branching pipe set(DIS-WB1, DIS-TB1)

or service valve of indoor unit(FDU model)

Applicable outdoor models

FDCVA802

FDCVA1002

Installation manual for pipe size reducer kit 22.2 (OD) size of the refrigerant gas pipe can be used by using this kit, although 25.4 (OD) size of the refrigerant gas pipe is standard.(When 25.4 (OD) size of the refrigerant gas pipe is used, this kit doesn't be needed.)(*) OD: Outer diameter.

2

1

2

3

3

31

Trip

le t

ype

Do

ub

le t

win

typ

e

3 piece

2 piece 2 piece 1 piece

Page 10: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

9

FDTVA series(4way-cassette type)

FDTVA151/201/251/301401/501/601

New panel design. A new model, beauty emerging from functionality.

INDOOR UNITCEILING CASSETTE MODEL

Air outlet Air inlet grille

VIEW M

VIEW N

VIEW A VIEW B

Decorative Panel

700

or le

ss(M

ax. D

rain

up

)

Drain hose(Accessories)(Local setting)

Hole for wiring

850

a95

35

b

187

137

332

637

422

420

310

267

950

630

295~325

e10

0

2555

c14

0

80 10016

0d

60140

140

f

2500

1000

M

4-ø44-ø4860~890(Ceiling hole size)

Fresh airopening for ducting

Exhaust airopening forducting

780(Suspension bolts pitch)

675(

Sus

pen

sion

bol

ts p

itch) Control box

Control box

Gas piping

Liquid piping

Lug forsuspension bolts

Space for installation and service

or m

ore

or more

Obstacle

Holes fortapping screws

Holes fortapping screws

HolesHoles

Suspension bolts

N

B

A

Drain(Connectable with VP25)

45or

mor

e

Outline drawing (Unit:mm)

model

FDTA151~301

FDTA401

FDTA501~601

a

212

212

269

b

270

295

365

c

123

148

218

d

43

68

138

e

122

147

215

f

52

77

147

Dimension Table

A new design keeps the ceiling cleanInstallation is easier with corner covers

R410AR410A

Point

1 Installation workabilityInstallation height canbe adjusted from frontpanel's corner cover.

Wireless remote controller kit.Receiver kit

Receiver kit can be set in any corner of front panel.Corner cover can be removed and

help installation work.

RCN-T-35W-ER(Option)

CLASSAAA

RC-E1R(Option)

Former Model (8series) New Model (1series)

Air flow improved, a new louver shape and angle keeps the ceiling clean.

Ceiling contaminationreduced by improvedlouver shape and angle.

Point

2 "Clearer" Air flow

Wireless remote controller Wired remote controller

Page 11: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

10

R410AAPlus more acoustic

insulation has created a

drastic reduction of noise

level.

Sound pressure level:dB(A)Lo-mode

35

40

45

20

25

30

50dB(A)

1.5 2.0 2.5 3.0 4.0 5.0

3335

31

35

4038

4340

6.0

HP

40

3131 31

Former model

New model

3phase,380-415V 50Hz/380V 60Hz

Point

3 New design --- Drastic-reduction of noise level

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)

Input

COP

Energy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsPanelNet weightPanel+Remote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/Heating

Cooling/Heating

Cooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x DepthHeight x Width x DepthUnit+Panel

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmmmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

1Phase 220-240V 50Hz ,1Phase 220V 60Hz

Inverter

FDTVA302HEN1RFDTA301R

FDCVA302HENR

*FDTVA402HEN2RFDTA401R

FDCVA402HENAR

FDTVA502HEN2RFDTA501R

FDCVA502HENAR

B/B

45-43-40

365x840x840

31+7

7.1(3.8~8.0)

8.0(4.0~9.0)

50Hz:1.90/2.0760Hz:1.91/2.0850Hz:3.74/3.8660Hz:3.72/3.85

A/A

2.95(30)9.52/15.88

35-33-3148

17-15-13Cooling:60 Heating:48.5

270x840x840

24+7

750x880(+88)x34060

10.0(6.1~11.2)

11.2(5.6~12.5)

2.88/3.12

3.47/3.59

A/B

43-41-3850

22-20-18

295x840x840

26+7

12.5(6.5~14.0)

14.0(6.2~16.0)

4.05/3.97

3.09/3.53

5229-26-23

14.0(6.7~14.8)

16.0(6.3~16.8)

4.65/4.54

3.01/3.52

5

5330-26-23

35x950x950

T-PSA-35W-ER+RCN-T-35W-ER, T-PSA-35W-ER+RC-E1R

RotaryEEV

503015

18~30D.B-15~43D.B*2

18~30D.B-10~24D.B

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

*1 : Indicates the value at mild mode in an anechoic chamber.

*2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

*Not available in 60Hz

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)

Input

COP

Energy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsPanelNet weightPanel+Remote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/Heating

Cooling/Heating

Cooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x DepthHeight x Width x DepthUnit+Panel

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmmmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

FDTVA151HEN1RFDTA151R

FDCVA151HENR

33-32-31

15-14-13

1.55(30)6.35/12.7

FDTVA201HEN1RFDTA201R

FDCVA201HENR

1Phase 220-240V 50Hz ,1Phase 220V 60Hz

Inverter

FDTVA251HEN1RFDTA251R

FDCVA251HENR

4.0(1.8~4.7)

4.5(2.0~5.4)

50Hz:1.22/1.3260Hz:1.23/1.3250Hz:3.28/3.4160Hz:3.25/3.41

A/B

5.0(2.2~5.6)

5.4(2.5~6.3)

50Hz:1.42/1.4960Hz:1.43/1.4950Hz:3.52/3.6260Hz:3.50/3.62

A/A5

48

41270x840x84035x950x950

24+7T-PSA-35W-ER+RCN-T-35W-ER, T-PSA-35W-ER+RC-E1R

595x780(+67)x29040

ScrollEEV

403015

18~30D.B-5~43D.B18~30D.B-10~24D.B

5.6(2.8~6.3)

6.7(3.1~7.1)

50Hz:1.64/1.7860Hz:1.65/1.7950Hz:3.41/3.7660Hz:3.39/3.74

A/A

35-33-31

17-15-13

1.75(30)6.35/15.88

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

*FDTVA402HES2RFDTA401R

FDCVA402HESAR

FDTVA502HES2RFDTA501R

FDCVA502HESAR

FDTVA602HES2RFDTA601R

FDCVA602HESAR

FDTVA602HEN2RFDTA601R

FDCVA602HENAR

10.0(6.1~11.2)

11.2(5.6~12.5)

2.97/2.92

3.37/3.84

A/A

43-41-3850

22-20-18

295x840x840

26+7

12.5(6.5~14.0)

14.0(6.2~16.0)

4.05/3.97

3.09/3.53

5229-26-23

14.0(6.7~14.8)

16.0(6.3~16.8)

4.65/4.54

3.01/3.52

5330-26-23

B/B

45-43-40

365x840x840

31+7

Cooling:75 Heating:73

845x970x37074

3.8(30)9.52/15.88

Page 12: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

11

FDTCVA series(4way-cassette type)

FDTCVA

Super Compact 4-way-cassette type for metric ceiling mounted system

Outline drawing (Unit:mm)

R410AR410A

Compact designComfortable and ConvenientThe industry's Top-class COP 3.75*

* FDTCVA151HEN1R, heating mode.

A A

A

185

190 223

321

348

530

Sus

pens

ion

bolts

530 Suspension bolts pitch

541

Controlbox

Drain hose(Accessories)(Local setting)

600

or le

ss

292~325

(Max

. Dra

in u

p)

VIEW A

60140

100

100

115

140

6-ø4

Holes for tapping screws

Hole

Obstacle

1000 or more

1000

or

mor

e

Space for installation and service

64

200 48

Opening for exit wiring 413

700

Air outletAir inlet grille

Decorative Panel

144323570

13719

7

35

9319

6 248

45 o

r mor

e

Lug forsuspension bolts

Gas piping

Liquid piping

Suspension bolts

Drain

ø12.7 (1/2")

ø6.35 (1/4") (Connectable with VP25)

(M10 or M8)

INDOOR UNITCEILING CASSETTE MODEL

RCN-TC-W-ER(Option)

RC-E1R(Option)

CLASSAAA

Wireless remote controller Wired remote controller

Page 13: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

12

R410AA Point

1 Compact ConceptThe industry's lowest 248mm height.Panel size (700x700) is suitable for 600x600 ceiling panel.

All indoor unit size is (WxD: 570x570). It brings easy installation for

600x600 ceiling panel.

Height248mm

Point

2 Comfortable and ConvenientWired remote controller or Wireless

remote controller can be selected.

All units are 19.5kg, light weight unit.

600mm Drain Pump is mounted.• New designed panel is developed exclusively for FDTCA series.

Thanks to width and depth of exterior

dimensions of a indoor unit are 570mm

each, the installation work can be conducted

smoothly with a beautiful finishing even in

case of 2x4 ceiling size.

Drain can be discharged upward by 600 mm from the ceiling surface close to the indoor unit.It allows a piping layout with a high degree of freedom depending on the installation location.

Flexible hose

600mm

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsPanelNet weightPanel+Remote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x DepthHeight x Width x DepthUnit+Panel

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmmmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

FDTCVA151HEN1RFDTCA151R

FDCVA151HENR

4.0(1.8~4.7)

4.5(2.0~5.4)

1.15/1.203.48/3.75

A/A

*1 : Indicates the value at mild mode

FDTCVA201HEN1RFDTCA201R

FDCVA201HENR

5.0(2.2~5.6)

5.4(2.5~6.3)

1.62/1.533.09/3.53

B/B

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

542-38-35

4811.5-10-8

41248x570x57035x700x700

16+3.5TC-PSA-24W-ER+RCN-TC-W-ER, TC-PSA-24W-ER+RC-E1R

595x780(+67)x29040

ScrollEEV

1.55(30)6.35/12.7

403015

18-30 D.B-5-43 D.B18-30 D.B-10-24 D.B

1Phase 220-240V 50Hz ,1Phase 220V 60Hz

Inverter

Page 14: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

13

Selectable static pressure (Max 85Pa on 3 to 5HP).

Flexible duct design with selectableair suction (direct suction/duct suction).

Built-in 600mm high-head drain pump.The industry's lowest noise level.

FDUMVA series

FDUMVA202/252/302/402/502/602

INDOOR UNITDUCT CONNECTED MODEL

RC-E1R (Option)

Wired remote controller

Outline drawing(Unit:mm)

Models FDUMA252R,302R

69

45 860 45

5920

013

0

165 285950

285 215465510

80 635

405

460

35 149

274

299

199

295~325

(Gravity drainage)

(M10x4pcs.)

600

or le

ss

Suspensionbolts

Air return duct

Drain ( VP20)

Hole for wiring

ø200

80.518

213205

5971

95018

4511

8

284

986 (Suspension bolts pitch)

Liquid piping252:ø6.35(1/4")302:ø9.52(3/8")

472

Drain hose piece(Accessory)(Installed at site)

Gas pipingø15.88(5/8")

Outside airopeningfor ducting(Knock out)

Exhaust airopening for ducting(Knock out)

A

90

Control box

Air supply duct

B

4-ø4

Holes oftapping screws

ø149

ø170ø170

Max

.Dra

in up

Drain

VIEW B VIEW A

Duct flangeinner dimeter( )

Connectablewith VP20( )

Duc

t fla

nge

inne

r dim

eter

(

)

Susp

ensio

nbo

lts p

itch

(

)

Model FDUMA202R

69

786 (Suspension bolts pitch)

VIEW A VIEW B

Liquid piping6.35(1/4")

295~325

750

750

660

200

59

4545

635510465405

460

80

299

274 199

149

185 320 245

205 213

284

18 1880.5

5971

4511

8

130

35

472

Duct flangeinner dimeter

Drain hose piece(Accessory)(Installed at site)

(Gravity drainage)

Gas piping12.7(1/2")

(M10x4pcs.)

Outside airopeningfor ducting(Knock out)

Exhaust airopening for ducting(Knock out)

A

90

600

or le

ss

Control box

Suspensionbolts

Air return duct

Air supply duct

Drain(VP20)

B

Hole for wiring (4-ø4)

Hole oftappingscrews

ø200

ø149

ø170ø170

Max

.Dra

in u

p

Drain

( )

Connectable with VP20( )

Duc

t fla

nge

inne

r dim

eter

(

)

Sus

pens

ionbo

lts p

itch

(

)

R410AR410ACLASSAAA

Page 15: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

14

Models FDUMA402R,502R,602R

69

A

1406 (Suspension bolts pitch)

Liquid pipingø9.52(3/8")

472

Drain hose piece(Accessory)(Installed at site)

Gas pipingø15.88(5/8")

Outside airopeningfor ducting(Knock out)

Exhaust air openingfor ducting(Knock out)

90

Control box

Air return duct

Air supply duct

B

(4-ø4)

Holes oftappingscrews

ø149

ø170 ø170

150

21320545128045

7024

0

18 1370

4511

8

5876

80.518

284

295~325

(Gravity drainage)

(M10x4pcs.)

600

or le

ss

Suspensionbolts

Drain(VP20)

Holesforwiring

ø200

Max

.Dra

in up

1751370

325 250

200

51063580

465405

460

35013

0

320 320 320 235

86

Drain

(Duct flange inner dimeter)

VIEW B VIEW A

Connectablewith VP20( )

Duc

t fla

nge

inne

r dim

eter

(

)

Susp

ensio

nbo

lts pi

tch(

)

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)

Input

COP

Energy labelInrush current

Noise Ievel

Air flow

Static pressureExterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/Heating

Cooling/Heating

Cooling/Heating

Indoor*1

OutdoorIndoor*1

Outdoor

Height x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

Pammkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

SPECIFICATIONS

Indo

or u

nitO

utdo

or u

nit

Ran

ge o

fus

age

Lim

itatio

ns

FDUMVA402HEN2RFDUMA402R

FDCVA402HENAR

FDUMVA502HEN2RFDUMA502R

FDCVA502HENAR

38-36-33

34-31-27

standard:60, Max:85

FDUMVA602HEN2RFDUMA602R

FDCVA602HENAR

5

Cooling:75 Heating:73

350x1,370x63559

RC-E1R845x970x370

74RotaryEEV

3.8(30)9.52/15.88

503015

18-30 D.B-15-43 D.B*2

18-30 D.B-10-24 D.B

1Phase 220-240V 50Hz ,1Phase 220V 60Hz

Inverter10.0

(6.1~11.2)

11.2(6.0~12.5)

50Hz:2.80/2.7760Hz:2.80/2.8050Hz:3.57/4.0460Hz:3.57/4.00

A/A

37-35-3250

28-25-22

standard:60, Max:90

12.5(6.7~14.0)

14.0(6.2~16.0)

50Hz:4.03/3.8060Hz:4.03/3.8550Hz:3.10/3.6860Hz:3.10/3.64

B/A

52

14.0(6.7~14.5)

16.0(6.3~16.5)

50Hz:4.95/4.7560Hz:4.95/4.9150Hz:2.83/3.3760Hz:2.83/3.26

C/C

53

Option (Filter kits) : UM-FL1E(FDUMA202R), UM-FL2E(FDUMA252R,302R), UM-FL3E(FDUMA402R,502R,602R)

*1 : Indicates the value at mild mode in an anechoic chamber.

*2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

kW

kW

kW

A

dB(A)

CMM

Pammkg

mmkg

kg(m)øm

<O/U>O/UI/UO/UI/UO/U

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Static pressureExterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

Outdoor

Height x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

FDUMVA201HEN2RFDUMA202R

FDCVA201HENR

FDUMVA251HEN2RFDUMA252R

FDCVA251HENR

1Phase 220-240V 50Hz ,1Phase 220V 60Hz

Inverter

FDUMVA302HEN2RFDUMA302R

FDCVA302HENR

5.0(2.2~5.6)

5.4(2.5~6.3)

1.53/1.583.27/3.42

14-12-11

299x750x63534

1.55(30)6.35/12.7

5.6(2.8~6.3)

6.4(3.1~7.1)

1.66/1.823.37/3.52

5

4818-16-14

standard:50, Max:85

RC-E1R

EEV1.75(30)

6.35/15.88

3015

18~30D.B

18~30D.B-10~24D.B

299x950x63540

7.1(3.5~8.0)

8.0(4.0~9.0)

2.08/2.213.41/3.62

A/A

35-32-29

20-18-15Cooling:60 Heating:48.5

750x880(+88)x34060

Rotary

2.95(30)9.52/15.88

50

-15~43D.B*2

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

R410AAOutline drawing(Unit:mm)

A/B

34-31-28

41

595x780(+67)x29040

Scroll

40

-5~43D.B

FDUMVA402HES2RFDUMA402R

FDCVA402HESAR

FDUMVA502HES2RFDUMA502R

FDCVA502HESAR

3phase,380-415V 50Hz/380V 60Hz

38-36-33

34-31-27

standard:60, Max:85

FDUMVA602HES2RFDUMA602R

FDCVA602HESAR

10.0(6.1~11.2)

11.2(6.0~12.5)

50Hz:2.80/2.7760Hz:2.80/2.8050Hz:3.57/4.0460Hz:3.57/4.00

A/A

37-35-3250

28-25-22

standard:60, Max:90

12.5(6.7~14.0)

14.0(6.2~16.0)

50Hz:4.03/3.8060Hz:4.03/3.8550Hz:3.10/3.6860Hz:3.10/3.64

B/A

52

14.0(6.7~14.5)

16.0(6.3~16.5)

50Hz:4.95/4.7560Hz:4.95/4.9150Hz:2.83/3.3760Hz:2.83/3.26

C/C

53

Page 16: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

15

INDOOR UNIT

FDUVA seriesR410AR410A

Higher level silenceThin type unit with the height at 360 mm.Adaptability to higher static pressures

FDUVA 801/10001

Control box

Fan motorHigh static pressure silent fan

Slide type fan system

Thin type duct connection opening

Point

1 Enhanced installation workability

Point

2 Adaptability to higher static pressures

Height360mm

This is a real and earnest model for duct air-conditioning.

A unit external static pressure of up to 200 Pa is possible.

Precise air flow designing is possible.

High static pressure of 200 Pa extends the degree of freedom in the designingof air conditioners.

Quiet, Lightweight and Compact

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Static pressureExterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

Outdoor

Height x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

Pammkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

SPECIFICATIONS

Indo

or u

nitO

utdo

or u

nit

Ran

ge o

fus

age

Lim

itatio

ns

*FDUVA802HES2RFDUA801R

FDCVA802HESAR

*FDUVA1002HES2RFDUA1001R

FDCVA1002HESAR

20.0(7.0~22.4)

22.4(7.6~25.0)

6.50/6.323.08/3.54

B/B

485751

1,300x970x370122

5.4(30)9.52/25.4

25.0(10.6~28.0)

28.0(9.5~31.5)

9.05/8.222.76/3.41

D/B

49Cooling:57 Heating:58

68

1,505x970x370140

7.2(30)12.7/25.4

3Phase,380-415V,50Hz

Inverter

With the 8 horsepower, the noise is only 48dB, the weight is

only 92kg, and the height is only 360mm.

The indoor unit is

completely hidden in the

ceiling, so this is suitable for

spaces with classy interior

decoration.

DUCT CONNECTED MODEL

5

Cooling:150 Heating:145standard:100, Max:200

360x1,570x83092

RC-E1R

ScrollEEV

703015

18-30 D.B-15-43 D.B*2

18-30 D.B-10-24 D.B

RC-E1R(Option)

Wired remote controller

*1 : Indicates the value at mild mode in an anechoic chamber.

*2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

Outline drawing (Unit:mm)830

794 (Suspension bolts pitch)

Liquid piping 801: ø9.52 (3/8")1001:ø12.7 (1/2") ø25.4 (1")

Gas piping

Control box

1690

1640

(S

uspe

nsio

n bo

lts p

itch)

1570

25 60609525

100

80

18 18A

Drain (VP25)(Gravity drainage)

360

310

30

80 510 25

170185

530

106

(Low

of su

spen

sion l

eg)

Low

Upper25

Space for installation and service

Slab

Ceiling

or m

ore

300

or m

ore

200

900 or more 900 or more

Inspection hole

Installation hole

(Service space of side)

(600 x 600)

Servicespace

Servicespace

100 or more

400 or morePiping space

60

900

3535

100

Inspection hole

(Service space of lower)

(900 x 1730) Installationspace

Hole for wiring

(ø25)

Hole for screw(M5 x 20 pcs.)

Suspension bolts(M10 x 4 pcs.)

49

138 13 77

138 13

250

(Duc

t for

dim

ensio

n)

Supply air

13813

45 200

60

13813

601450 (Duct for dimension)

6 x 200 = 1200

(Duc

t for

dim

ensi

on)

13 138

1365 138 13 13

163 1636 x 200 = 12001500 (Duct for dimension)

Holes for screw(M5 x 20 pcs.) Return air duct

200

35 35

250

View A

*Not available in 60Hz

Page 17: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

R410A

Applicable indoor unit models Ceiling recessed type (4way-cassette) FDTA, Ceiling suspension type FDENA

Enzymes used for filters are natural lytic enzymes.The lytic enzymes attack cell walls of microorganisms trapped on a filter and destroy them, so that they will show a powerful sterilizing effect to decrease the number of molds and bacteria. Where such enzymes exist, air filters are kept sanitary and clean. Naturally, air passing through such filters is clean and safe.

A debut of the enzyme sterilizing filter to which enzymes used in detergent, etc. are chemically bonded.

Enzyme filter Conventional filter

A filter coated with bacterium has been placed on the gelatin cultivate medium for seven days

No breeding on the filter

Filter

Breeding on and around the filter

Filter

Mold

Enzyme Sterilizing Filter

Effect on bacterium Effect on molds

Enzyme's sterilizing mechanism

Conventional Filter

Air

flo

w

Enzyme Filter

Air

flo

w

Optional Parts

TopicsTopics Wide & Various air flow

Jet Air ScrollApplying aerodynamic analysis technologies used in developing jet engines to air conditioners.

CFD (computational fluid dynamics), used in blade shape design of jet engines, has been applied to the design of air channels in air conditioners to develop the ideal air channel system (air circulation). The airflow of the jets created in this system enable a large volume of air to be blown with minimum power consumption, yet the air flow is uniform, quiet and reaches points a long distance from the blower.

Old typeNew type

Colors in the figure show the air speed.

Slow Fast

CouplingCell wallFilter fiber

EnzymeBacterium

EnzymeEnzyme

Powerful sterilizing effect

Sterilization

Enzymeloaded fiber

Live bacterium

Destroyingbacteria

DIRTY AIR

A filter kills and destroys bacteria.

A debut of an

epochal filter.

FDKNVAseries

WALL MOUNTED TYPE

16

Page 18: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

17

INDOOR UNIT

FDKNVA seriesSuper slim unit equipped with aero-trap louvers

WALL MOUNTED MODEL

R410AR410A

Slim designSlim design achieved with the adoption of heat exchangersfolded to form multiple stages.

Outline drawing (Unit:mm)

Servicespace

4-12X18(Long hole)

Servicespace

Installation Position Diagram when viewed from the front and installation space.

67 60 63.5

533.5603.5

515 53.5

44.5

15

284.

2 5.

3 8.

540

100

73.5693 5073.5

182.5 450 207.5

50 50

220.

5 47

.5

44.5

25

44

60

3240

44

60

14.560 813

3 60

44

60

840

298

(Rig

ht)

(Lef

t)

Drain hose(VP16)

Liquidpiping

Gas pipingø65

ø65

Ser

vice

spac

eS

ervi

cesp

ace

UnitMounting plate

Hole on wall forrear connection

Hole on wall forrear connection

Outlet for piping Outlet for piping(On both side)

Outlet for electric wiring

Space for installation and service

ormore

ormore

or m

ore

or mor

e

4015

10050

FDKNA151/201/251

The industry’s Top-class COPA new design promising a neat installation finishEquipped with a easy clean mechanism

FDKNA151/201/251

By adopting MHI's unique wide, multiple-stage folded heat exchangers, which are bent to form three sections

surrounding the fan, a slim compact body is realized. Further, the adoption of a big wing cross flow fan, each fan

blade of which is extended longitudinally to reduce the fan diameter, has made it possible to realize an excellently

low noise level of 39dB registered with the FDKNA251 model. As a result of improvement in the panel design,

diffuser louver shape, and swing angle, the air blast is deftly guided away to avoid contact with the ceiling.

Heat exchanger folded to form multiple stages

Big wing cross flow fan

Point

1

RCN-E1R(Option)

RC-E1R(Option)

Wireless remote controller Wired remote controller

Page 19: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

Improved maintainability

Innovative design Installation workabilityComfortable space producedwith a low resistance air flow design

Easy clean mechanism for easy maintenance

FDKNVA series are the same slim designpromising neat installation.

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

*1 : Indicates the value at mild mode

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

FDKNVA151HEN1RFDKNA151R

FDCVA151HENR

4.0(1.8~4.7)

4.5(2.0~5.4)

1.30/1.303.08/3.46

B/B

42-40-37

11-10-9

FDKNVA201HEN1RFDKNA201R

FDCVA201HENR

5.0(2.2~5.6)

5.4(2.5~6.3)

1.66/1.583.01/3.42

B/B5

44-41-3848

12-11-941

298x840x24012

595x780(+67)x29040

40

1.55(30)6.35/12.7

1Phase 220-240V 50Hz , 1Phase 220V 60Hz

Inverter

RCN-E1R, RC-E1R

ScrollEEV

3015

18~30D.B-5~43D.B18~30D.B-10~24D.B

FDKNVA251HEN1RFDKNA251R

FDCVA251HENR

5.6(2.8~6.0)

6.3(3.1~7.1)

1.99/1.852.81/3.41

C/B

45-42-39

13-11-10

1.75(30)6.35/15.88

New wall-mounted model air

conditioners have adopted the

air flow design that was proved

to minimize resistance in a

CFD analysis to achieve

uniform air conditioning to the

farthest corners of the room.

Because of its slim design, it fits neatly

on a wall.

FDKNVA series have adopted an easy clean mechanism, which allows the front panel to

be detached and attached easily. This improves maintainability of these models, making

cleaning inside of the air conditioner with an easy task.

Since it allows cleaning to be done easily in a short time, it is quite suitable for a shop,

etc.

The panel can be removed easily from the unit.

Computational Fluid Dynamics.

Height298mm

Depth240mmNew Model Former Model

Point

2Point

3

Point

4

18

R410A

Page 20: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

19

INDOOR UNIT

Outline drawing (Unit:mm)

model

FDENA151,201

FDENA251,301

FDENA401~601

a

1022

1272

1572

b

990

1240

1540

c

1070

1320

1620

d

215

215

255

e

210

210

250

Dimension Table

68

410

690

135 145

271

235

10953

195

52

290(Suspension bolts pitch)Holes for suspension bolts(M8 to M10X 4pcs.Not included)

Liquid piping

Gas piping

Drain holeconnection(1)

(VP20)

300

100150

5

Space for installation and service

or more

or moreor more or

mor

e

Obstacles

10 53

Note(1) The slope of drain piping inside the unit is able to take incline of 10mm.

Drain hole

7675

110

135

308

b

d

c

40

24

e5

173

40

24a (Suspension bolts pitch)

Air outlet

Liquid pipingGas piping

Indication board

Air inlet grille

connection(1)(VP20)

Drain holeconnection(1)

(VP20)

FDENVA series

FDENVA151/201/251/301/401/501/601

Slim body suits most installation conditions

The industry’s lowest noise level

R410AR410A

CEILING SUSPENDED MODEL

CLASSAAA

RCN-E1R(Option)

RC-E1R(Option)

Wireless remote controller Wired remote controller

The refrigerant pipe from the unit can be arranged in three directions, rear, right and up. The drain pipe can be arranged in two directions, left and right. This will allow a free layout of piping for various installation conditions. The unit can only be serviced from the bottom.

Increased freedom of a piping layout

Point

1 Improved installation workability

All models fit compactly on ceiling. (Height-210mm or 250mm). Plain, modern design featuring rounded edges gives room a comfortable atmosphere.FDENA151 weights 30kg the lightest level in the industry. Convenient and quick installation.

Point

2

Rear

Right

UpHeight210mm

Installation workability

Page 21: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

20

Reviewing sirocco fan (diameter and wide) enables

drastic reduction of noise level.

35

40

45

20

25

30

50

1.5 2.0 2.5 3.0 4.0 5.0

38 39 38 39 38

43 44 43 43

6.0HP

3937 37

Conventional model

New model

Point

3 New design --- Drastic-reduction of noise level

Sound pressure level:dB(A)Lo-mode

dB(A)

R410AA Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

FDENVA151HEN1RFDENA151R

FDCVA151HENR

39-38-37

11-9-7

210x1,070x69030

1.55(30)6.35/12.7

FDENVA251HEN1RFDENA251R

FDCVA251HENR

FDENVA201HEN1RFDENA201R

FDCVA201HENR

3.8(1.8~4.7)

4.5(2.0~5.4)

1.18/1.323.22/3.41

5.6(2.8~6.3)

6.7(3.1~7.1)

1.74/1.873.22/3.58

41-39-38

18-14-12

210x1,320x69036

1.75(30)6.35/15.88

5.0(2.2~5.6)

5.4(2.5~6.3)

1.54/1.573.25/3.44

A/B5

48

41

RCN-E1R, RC-E1R595x780(+67)x290

40ScrollEEV

403015

18~30D.B-5~43D.B18~30D.B-10~24D.B

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

1Phase 220-240V 50HZ , 1Phase 220V 60Hz

Inverter

Set model nameIndoor nameOutdoor name

Power source

TypeNominal cooling capacity (Min~Max)Nominal heating capacity (Min~Max)InputCOPEnergy labelInrush current

Noise Ievel

Air flow

Exterior dimensionsNet weightRemote controllerExterior dimensionsNet weightType of compressorRef.controlRef.amount prechargedRef.piping size Ref.piping length Vertical height difference

Air temp.

ISO-T1(JIS)

ISO-T1(JIS)

Cooling/HeatingCooling/HeatingCooling/Heating

Indoor*1

OutdoorIndoor*1

OutdoorHeight x Width x Depth

Height x Width x Depth

Liquid/Gas

between O/Uand I/U

Cooling

Heating

kW

kW

kW

A

dB(A)

CMM

mmkg

mmkg

kg(m)ø

m<O/U>O/UI/UO/UI/UO/U

FDENVA502HEN2RFDENA501R

FDCVA502HENAR

FDENVA602HEN2RFDENA601R

FDCVA602HENAR

7.1(3.5~8.0)

8.0(4.0~9.0)

2.06/2.213.45/3.62

41-39-3848

18-14-12Cooling:60 Heating:45210x1,320x690

36

750x880(+88)x34060

2.95(30)9.52/15.88

*1 : Indicates the value at mild mode in an anechoic chamber.

*2 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.

FDENVA302HEN1RFDENA301R

FDCVA302HENR

SPECIFICATIONS

Indo

or u

nit

Out

door

uni

t R

ange

of

usag

eLi

mita

tions

1Phase 220-240V 50HZ , 1Phase 220V 60Hz

Inverter12.5

(6.5~14.0)14.0

(6.2~16.0)4.35/3.952.87/3.54

52

14.0(6.7~14.5)

16.0(6.3~16.5)

4.95/4.692.83/3.41

5

53

RCN-E1R, RC-E1R

RotaryEEV

503015

18~30D.B-15~43D.B*2

18~30D.B-10~24D.B

Cooling:75 Heating:73250x1,620x690

46

845x970x37074

3.8(30)9.52/15.88

C/B

46-44-43

29-26-23

FDENVA402HEN2RFDENA401R

FDCVA402HENAR

10.0(6.1~11.2)

11.2(5.9~12.5)

2.85/2.973.51/3.77

44-41-3950

26-23-21

A/A

FDENVA402HES2RFDENA401R

FDCVA402HESAR

FDENVA502HES2RFDENA501R

FDCVA502HESAR

3phase,380-415V 50Hz/380V 60Hz

C/B

46-44-43

29-26-23

FDENVA602HES2RFDENA601A

FDCVA602HESAR

10.0(6.1~11.2)

11.2(5.9~12.5)2.85/2.973.51/3.77

A/A

44-41-3950

26-23-21

12.5(6.5~14.0)

14.0(6.2~16.0)4.35/3.952.87/3.54

52

14.0(6.7~14.5)

16.0(6.3~16.5)4.95/4.692.83/3.41

53

Page 22: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

21

The RC-E1R controller enables extensive access to service and maintenance technical data combined with easy to use function and a clear LCD display.

1.Ventilation indicationDisplays operation of external outside air fan.

2.Centralised control indicationIlluminated when centralised control is functioning.

3.Timer indicationIndicates time period ON/OFF when setting timer.

4.Set temperatureDisplays set temperature ˚C.

8.Unit address switchTo select 'a' numbered unit within a connected group.

9.Maintenance diagnosisTo display error codes and history.

10.Test run switchCommissioning sequence in cooling

11.Reset switchTo cancel previously set functions.

12.Weekly timerTo select and set weekly operation schedule.

13.Function set switchTo register selected operation settings.

This switch has no function. When this switch is pressed, INVALID OPER(Invalid Operation) is displayed,but it does not mean a failure.

7.GRILL switch

5.Temperature setting switch6.Clock setting switch

To set the timer mode and the weekly timer functions.

OUTDOOR UNIT (1.5-10.0HP)

Piping size (diameter) reduced

Installation workability

Height difference(Outdoor>indoor)

Piping length

1.5~10.0HP 30m

1.5 ~ 2.5HP : 40m3.0 ~ 6.0HP : 50m8.0 ~10.0HP : 70m

Enhanced installation workability thanks to the extended pipe length – longest levelin the industry, pre-charged refrigerant and reduced piping size.

Long allowable pipe length up to 70m (8.0-10.0HP) meeting also the installation conditionsat large-scale commercial facilities

Pipe length can be extended up to 70m. This

opens up the possibility to apply to large-scale

commercial facilities as well, which

conventionally called for multiple type models.

Pipe length – 70m1 Refrigerant pre-charged pipe length extending to 30m2

Reduced refrigerant piping size that significantly enhances the installation workability3

Refrigerant pre-charged pipe length

extends up to 30m.

This eliminates the need to add

refrigerant on site, which sets it free from

trouble of excessive or insufficient

charging of refrigerant, and allows

carrying out the installation smoothly.

Refrigerant piping size has been reduced in order to adapt to new high-density and high-pressure

refrigerant R410A.This has enabled to realize a higher refrigeration capacity and reduced the

pressure loss, which allows further reducing the piping work cost.

Refrigerant may be recharged, of course, when it has leaked accidentally.

R407C R410A

15.88 12.728.58 22.22

1.5 2.0 2.5 3.0 4.0 5.0 6.0 8.0 10.0

Liquid

HP

Gas

Former model (R407C)

New model (R410A)

Former model (R407C)

New model (R410A)

6.35

-

12.7

-

6.35

6.35

12.7

15.88

6.35

9.52

15.88

15.88

9.52

9.52

15.88

15.88

9.52

9.52

15.88

19.05

9.52

9.52

15.88

19.05

9.52

-

15.88

-

9.52

12.7

22.22*

25.4

12.7

15.88

22.22*

28.58

*Use the reducer kit.

Noises(dB(A))

45

50

60

55

40

57

48

FDC256HEN3 FDCVA251HENR

9dB(A)down

Former modelNew model

(dB(A))

45

50

40FDCVA151/251/251HENR

SilentMode

4847

CoolingHeating

Noise reductions*FDCVA251HEN

By reducing a pressure drop

in a unit, optimizing airflow

rates and minimizing airflow

disturbance, noise

reductions are up to 9dB(A).

Noise reductions up to 9dB(A) by comparison with the existing outdoor unit models

Silent mode

You can switch to the

silent mode, in which

the outdoor fan

revolution is lowered.

This allows you to run the unit in the night in a residential zone.

FDCVA151HENRFDCVA201HENRFDCVA251HENR(1.5HP~2.5HP)

FDCVA402HENARFDCVA502HENARFDCVA602HENARFDCVA402HESARFDCVA502HESARFDCVA602HESAR

(4.0HP~6.0HP)

FDCVA802HESAR(8.0HP)

FDCVA1002HESAR(10.0HP)

FDCVA302HENR(3.0HP)

Page 23: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

22

The RC-E1R controller enables extensive access to service and maintenance technical data combined with easy to use function and a clear LCD display.

The RC-E1R controller enables extensive access to service and maintenance technical data combined with easy to use function and a clear LCD display.

RUN

Time

Timer-1 Timer-3Timer-2 Timer-48 9 10 11 12 13 14 15 16 23...... ......

STOP

Timer operation

RC-E1R stores operation data when an anomaly occurs and indicates the error on the LED. It also indicates cumulative operation hours of the air conditioner and compressor since commissioning.

Run hour meters to facilitate maintenance checking Optional mode settings

Weekly timer function as standardThe temperature sensor is housed in the top section of the remote control unit. This arrangement has improved the sensitivity of the remote control unit's heat sensor, which permits more finely controlled air conditioning.

Room temperature controlled by the remote control sensorRC-E1R provides (as a standard feature) a weekly timer, which allows one-week operation schedules to be registered. A user can specify up to four times a day to start/stop the air conditioner. (Temperature setting is also possible with the timer).

Functional setting with remote control operation switches. High Ceiling Mode Fan Tap No. Filter Sign Enabled/Disabled Remote Sensor Enabled/Disabled

Lucid indication and easy operation

Further improved functionality

A new type remote control unit adopting a completely new design has further improved the visibility of information displayed on the screen such as selected settings, operation data and error events by employing a dot LCD.

Adoption of a large dot LCDHaving adopted rubber switches for operation switches, it now offers the improved feeling of a touch.

Rubber switches to improve the feeling of a touch

1.Ventilation indicationDisplays operation of external outside air fan.

2.Centralised control indicationIlluminated when centralised control is functioning.

3.Timer indicationIndicates time period ON/OFF when setting timer.

4.Set temperatureDisplays set temperature ˚C.

8.Unit address switchTo select 'a' numbered unit within a connected group.

9.Maintenance diagnosisTo display error codes and history.

10.Test run switchCommissioning sequence in cooling

11.Reset switchTo cancel previously set functions.

12.Weekly timerTo select and set weekly operation schedule.

13.Function set switchTo register selected operation settings.

1.Ventilation indication

Changeable range

Upper limit

Lower limit

effective forheating operation

effective fornon-heating operation

RC-E1R allows the upper and lower limits of a set temperature range to be specified separately. By adjusting a set temperature range, you can ensure energy saving air conditioning by avoiding excessive cooling or heating.

Changeable set temperature ranges

WIRED CONTROLLER (RC-E1R)Displays operation of external outside air fan.

2.Centralised control indicationIlluminated when centralised control is functioning.

3.Timer indicationIndicates time period ON/OFF when setting timer.

4.Set temperatureDisplays set temperature ˚C.

This switch has no function. When this switch is pressed, INVALID OPER(Invalid Operation) is displayed,but it does not mean a failure.

7.GRILL switchThis switch has no function. When this switch is pressed, INVALID OPER(Invalid Operation) is displayed,but it does not mean a failure.

7.GRILL switch

5.Temperature setting switch5.Temperature setting switch6.Clock setting switch

To set the timer mode and the weekly timer functions.6.Clock setting switch

To set the timer mode and the weekly timer functions.

8.Unit address switchTo select 'a' numbered unit within a connected group.

9.Maintenance diagnosisTo display error codes and history.

10.Test run switchCommissioning sequence in cooling

11.Reset switchTo cancel previously set functions.

12.Weekly timerTo select and set weekly operation schedule.

13.Function set switchTo register selected operation settings.

14.Remote control sensorSlits to allow air movement to sensor.

15.Timer indicationShows sequence of four ON/OFF functions per day.

16.Fan speed indicationIndicates selected fan speed.

17.Operation modeIndicates cooling/heating/fan only mode etc.

18.Operation/Fault indication lampIlluminated green when unit is operating, flashes red when error is detected.

19.ON/OFF switchTo switch unit ON/OFF

20.Mode Operation switchTo select operation mode cooling/heating/fan only

21.Ventilation switchTo run/stop external ventilation unit-can also be interlocked.

22.Fan speed adjustmentSelection of low/med/high fan speed.

23.Louver switchTo select louver position or auto swing function.

12 14

13

23

20

21

22

19

18

17

15

16

11

1

2

3

4

6

5

7

8

9

10

Page 24: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

23

SC-SLA1-ER

SC-SLA2A-ER

SuperLink Adapter SuperLink Adapter

KX4 series

Up to 96 indoor units* are controlled from the Internet Explorer.*In case of SLA1 or SLA2A being installed, up to 64 (32x2) indoor units can be connected. SLA3/SLB3 can't be installed.

Up to 96 indoor units* are controlled centrally from a single BGW! *In case of SLA1 or SLA2A being installed, up to 64 (32x2) indoor units can be connected. SLA3/SLB3 can't be installed.

Kindly note that additional engineering service cost is required.

Up to 96 indoor units* are linked as an open network! Centrally controlled through LonWorks!*In case of SLA1 or SLA2A being installed, up to 64 (32x2) indoor units can be connected. SLA3/SLB3 can't be installed.

Start/stop control of up to 16 indoor units is possible either individually or collectively. With simple operations, you can effect centralized control.

Centralized control of up to 48 indoor units. It can allow connection with a weekly timer without using any interface.

Easy operation realized with a large color LCD and touch panel. Up to 144 indoor units can be controlled, when three SUPERLINK systems are connected.

SC-SLA1-ER

SC-WGW-AR/BR(SC-WGW-BR is with electric power calculation function)

SUPERLINK WEB Gateway

SC-BGW-ARSUPERLINK BACnet Gateway

SC-LGW-ARSUPERLINK LonWorks Gateway

SC-SLA2A-ERCenter Console

SC-SLA3-ER/SC-SLB3-ER

SUPERLINKControl System SUPERLINKControl System

Page 25: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

24

Outdoor unit

Internal/external Crossing

Indoor unit

Remote controlSL E Board

Networkoptions

X Y Z

X Y Z X Y ZA B

A B

Outdoor unit

Internal/external Crossing

Inside Inside Inside Inside

R RSL EBoard

Networkoptions

Outdoor unit

Internal/external Crossing

Inside Inside Inside Inside

R RSL EBoard

Outdoor unit

Internal/external Crossing

Inside Inside Inside

R RSL EBoard

Networkoptions

Outdoor unit

Internal/external Crossing

Inside Inside

SL EBoard

Networkoptions

Outdoor unit

Internal/external Crossing

Inside Inside

SL EBoard

Networkoptions

Wireless Kit

Wireless remote control

Basic Connections Plural Controls by Multiple Remote Controls. Mixture of Multiple Units

Plural Controls by Multiple Remote Controls. Mixture of Multiple Units Without Remote Control Wireless Kit

(3) Metal box dimension

85

40

35

30

905

100

70

22.5

2-ø6

SUPER LINK E BOARD (SC-AD-ER)This board is used when conducting control of the single package (wired remote controller unit) 1-type series using a Super link option (SC-SLA1-E, SC-SLA2A-E, etc).

(1) Functions (a) Transmits the settings from the Super link option to the indoor units. (b) Returns the priority indoor unit data in response to a data request from the Super link option. (c) Inspects the error status of connected indoor units and transmits the inspection codes to the Super link option. (d) A maximum of 16 units can be controlled (if in the same operation mode).

(2) Wiring connection diagram

(a) Set the super link network address with SW1 (10-position) and SW2 (1-position). (b) Without a remote control (no wired remote control and no wireless remote control), set SL E board SW3-1 to ON (Master).

Connection to super link(total length of wires: 1000 m maximum)0.75 ~ 2.0 mm2 2-core

Connection to the terminal blockfor remote control (polar)(total length of wires: 600 m maximum)

SL E BOARD A

B

X

Y

Z

X

Y

Z

Blue

Blue

Red

White

Black

Master/Slave address Network address [00] ~ [47]

No.1234

Name ot the recommended signal wireShielded wireVinyl cabtyre round cordVinyl cabtyre round cable Control vinyl insulated, vinyl sheathed cable

ONOFF

Master/Slave AddressSW 3-1

MasterSlave

Shielded wires:100 ~ 200 m : 0.5 mm2 X 3-core wires ~ 300 m : 0.75 mm2 X 3-core wires ~ 400 m : 1.25 mm2 X 3-core wires ~ 600 m : 2.0 mm2 X 3-core wires Make sure to ground one side only of the shielded wire.

Set “00” ~ “47” with the address SW (rotary SW) of the SL E board.

• Transmit the information of plural “Master” units to the network.

• Transmit the abnormalities of the “Slave” units to the network.

Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.

Setting the “Master/Slave” remote controls with the dip SW of the remote control board.

Set the SL E board dip SW to “Master” SW3-1 ON.The network option SLA-1-E is not allowed (This will disturb switching of the operation mode)

SUPERLINKControl System

Page 26: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

25

FDCVA302HENR(unit:mm)

FDCVA402HENAR, 502HENAR, 602HENAR402HESAR, 502HESAR, 602HESAR (unit:mm)

FDCVA151HENR, 201HENR, 251HENR(unit:mm)

Minimum installation space

Intake

outlet

Intake

L2

L1

L3

L4

42.5

96

.5

595

14.4

B

A

Check joint

C

Terminal block

29.7 90.6

35°

35°

E

D

58.6

13

2

43.1

51.9

471.5 50

12

510

2-R6

106

780 67

463

49.6

45

.4

290

286.4

164 17.5

14

312.

5 13

.5

340

Mark

ABCDE

Item

Refrigerant gas side pipe connection tapRefrigerant liquid side pipe connection tapPipe/cable draw-out portDrain discharge portAnchor bolt hole

ø12.7(flare)ø6.35(flare)

ø20.5x5places M10x4places

ø15.88(flare)151,201 251

OUTDOOR UNIT Dimensions

Servicespace

Notes:(1) It must not be surrounded by walls on the four sides.(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than

15mm.(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet

faces perpendicularly to the dominant wind direction.(4) Leave a 1m or larger space above the unit.(5) A wall in front of the blower outlet must not exceed the units height.(6) The unit name plate is attached on the lower right corner of the front panel.

280Open

80250

2807580

Open

Open100100250

321

L1

L2

L3

L4

Dimensions

Examples of installation

Mark

A

B

CDEF

ItemRefrigerant gas side pipeconnection tapRefrigerant liquid side pipeconnection tapPipe/cable draw-out portDrain discharge portAnchor bolt holeCable draw-out port

ø15.88(flare)

ø9.52(flare)

ø20.3x3places M10x4placesø30.3x3places

Notes:(1) It must not be surrounded by walls on the four sides.(2) The unit must be fixed with anchor bolts.An anchor

bolt must not protrude more than 15mm.(3) Where the unit is subject to strong winds, lay it in such

a direction that the blower outlet faces perpendicularly to the dominant wind direction.

(4) Leave a 1m or larger space above the unit.(5) A wall in front of the blower outlet must not exceed the

units height.(6) The unit name plate is attached on the lower right

corner of the front panel.

Mark

A

B

CDEF

ItemRefrigerant gas side pipeconnection tapRefrigerant liquid side pipeconnection tapPipe/cable draw-out portDrain discharge portAnchor bolt holeCable draw-out port

ø15.88(flare)

ø9.52(flare)

ø20.3x3places M10x4placesø30.3x3places

Notes:(1) It must not be surrounded by walls on the four sides.(2) The unit must be fixed with anchor bolts.An anchor

bolt must not protrude more than 15mm.(3) Where the unit is subject to strong winds, lay it in such

a direction that the blower outlet faces perpendicularly to the dominant wind direction.

(4) Leave a 1m or larger space above the unit.(5) A wall in front of the blower outlet must not exceed the

units height.(6) The unit name plate is attached on the lower right

corner of the front panel.

500Open100250

Open250150250

Open300100250

321

L1

L2

L3

L4

Dimensions

Examples of installation

500Open150

5

Open5

3005

Open300150

5

321

L1

L2

L3

L4

Dimensions

Examples of installation

222

40

20

40

20

340

380

31047

40

55

580

150

150

30

30

48.5

103.

3

750

24.1

D

2-ø15 25.829.8

87.9880150580150

61

53222360

15

340

6147

.5

1938

019

418

165.5 25.5

Terminal block

A

5140 36

100

845

10 110

50

195

242

279

970

50 15

55

5027

52

110

50

195

B

B

A

A

Terminal block

F

CCC VIEW A5015

7050

150

40

F

E

370

4040

410

2020

55

60

388262

38

60

190 580 200

60 15

103

15

C

D

Minimum installation space

L1

L2L3

outlet

Intake

Intake

Servicespace

L4

Minimum installation space

L1

L2L3

outlet

Intake

Intake

Servicespace

L4

E

D

B

A

Page 27: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

26

FDCVA1002HESAR(unit:mm)

FDCVA802HESAR(unit:mm) Mark

A

B

CDE

F

G

ItemRefrigerant gas side connectionto the piping attachmentRefrigerant liquid side pipeconnectionPipe/cable draw-out portDrain discharge portAnchor bolt hole

Cable draw-out port

Refrigerant gas sidepipe connection

ø19.05(flare)

ø9.52(flare)

ø20.3x3places M10x4places

ø30.2x2places(front side)ø45(right side)ø50(rear side)

ø22.22(brazing)

Notes:(1) It must not be surrounded by walls on the four sides.(2) The unit must be fixed with anchor bolts.An anchor bolt must not

protrude more than 15mm.(3) Where the unit is subject to strong winds, lay it in such a direction

that the blower outlet faces perpendicularly to the dominant wind direction.

(4) Leave a 1m or larger space above the unit.(5) A wall in front of the blower outlet must not exceed the units height.(6) The unit name plate is attached on the lower right corner of the

front panel.

ItemRefrigerant gas side connectionto the piping attachmentRefrigerant liquid side pipeconnectionPipe/cable draw-out portDrain discharge portAnchor bolt hole

Cable draw-out port

Refrigerant gas sidepipe connection

ø19.05(flare)

ø12.7(flare)

ø20.3x3places M10x4places

ø30.2x2places(front side)ø45(right side)ø50(rear side)

ø22.22(brazing)

Mark

A

B

CDE

F

G

Notes:(1) It must not be surrounded by walls on the four sides.(2) The unit must be fixed with anchor bolts.An anchor bolt must not

protrude more than 15mm.(3) Where the unit is subject to strong winds, lay it in such a direction

that the blower outlet faces perpendicularly to the dominant wind direction.

(4) Leave a 1m or larger space above the unit.(5) A wall in front of the blower outlet must not exceed the units height.(6) The unit name plate is attached on the lower right corner of the

front panel.

500Open150

5

Open5

3005

Open300150

5

321

L1

L2

L3

L4

Dimensions

Examples of installation

52

27 50

170

5085

370

410

2020 40

40

55

60

262 388

38

580190 200

103

15

60 1560

C

D

E

F

C

B

A

G

Terminal block for power cable connection

1300

10

55

1550

970

50

625

576

306*

15585

35F

C

A

50

15 50

50

160

70

F

C

VIEW A

Minimum installation space

Intake

outlet

Intake

Servicespace

L1

L2L3

L4

52

27 50

170

5085

F

C

Terminal block for power cable connection

A

G

576

306*

1505

10

55

1550

970

50

619

15585

35

B

F

C

370

410

2020 40

40

55

60

262 388

38

580190 200

103

15

60 1560

C

D

E

A

50

15 50

50

160

70

F

C

VIEW A

500Open150

5

Open5

3005

Open300150

5

321

L1

L2

L3

L4

Dimensions

Examples of installation

Minimum installation space

Intake

outlet

Intake

Servicespace

L1

L2L3

L4

B

AG

44*

120

60

69

45*

48

B

AG

44*

120

60

69

45*

48

270mm

Flared connection

Brazed connection

270mm

Flared connection

Brazed connection

Page 28: PACKAGED AIR CONDITIONERS R410A - ΠΑΠΑΓΙΑΝΝΗΣ GREEN.pdf · 3 Compact Design Size reduction and high efficiency performance on the compressor(4-6HP) Improved efficiency

May2007(4B)R

Safety Precautions

Before starting use

Printed in Japan

Air-conditioner usage targetThe air-conditioner described in this catalog is a dedicated cooling/heating device for human use. Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc. This could cause the quality of the items to drop, etc. Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur.

Before useAlways read the "User,s Manual" thoroughly before starting use.

InstallationAlways commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires. Use the MHI-designated products for the accessories such as the air purifier, humidifier, and auxiliary electric heater for heating.

Usage placeDo not install in places where combustible gas could leak or where there are sparks. Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.

Refrigerant leakageThe refrigerant gas (R410A) used for Air conditioner is non-toxic and inflammable in its original state. However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.

Use in snowy areasTake the following measures when installing the outdoor unit in snowy areas.

·Snow showInstall a snow-prevention hood so that the snow does not obstruct the air intake port, and so that the snow does not enter and freeze in the outdoor unit.

·Snow pilingIn areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.

Automatic defrosting deviceIf the temperature is low, and the humidity is high, frost will stick to the heat exchanger of the outdoor unit. If use is continued, the heating performance will drop. The "Automatic defrosting device" will function to remove this frost. After heating for approx, three to ten minutes, it will stop, and the frost will be removed. After defrosting, hot air will be blown again.

Servicing the air-conditionerAfter the air-conditioner is used for several seasons, dirt will build up in the air-conditioner causing the performance to drop. In addition to regular servicing, we recommend the maintenance contract (charged for) by a specialist.

Heating performanceThe heating performance values (kW) described in catalog are the values obtained by operating at an outdoor temperature of 7 C and indoor temperature of 20 C as set forth in the ISO Standards. As the heating performance decreases as the outdoor temperature drops, if the outdoor temperature is too low and the heating performance is insufficient, use other heating appliances as well.

Indication of sound valuesThe sound values are the values (A scale) measured in a chamber such as an anechoic chamber following the ISO Standards. In the actual installation state, the value is normally larger than the values given in the catalog due to the effect of surrounding noise and echo. Take this into consideration when installing.

Use in oil atmosphereAvoid installing this unit in as atmosphere where oil scatters or builds up, such as in a kitchen or machine factory. If the oil adheres to the heat exchanger, the heat exchanging performance will drop, mist may be generated, and the synthetic resin parts may deform and break.

Use in acidic or alkaline atmosphereIf this unit is used in an acidic or alkaline atmosphere such as hot spring areas having high levels of sulfuric gases, places where the exhaust of the heat exchanger is sucked in, or at coastal areas where the unit is subject to salt breezes, the outer plate or heat exchanger, etc., will corrode.

Use in places with high ceilingsIf the ceiling is high, install a circulator to improve the heat and air flow distribution when heating.

HB91-07P03E-C-0

Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.

Head Office : Mitsubishi Heavy Industries, Ltd. 16-5 2-Chome Kounan Minato-ku Tokyo 108-8215, Japan

Our factories are ISO9001 and ISO14001 certified.

BIWAJIMA PLANT Mitsubishi Heavy Industries, Ltd.

Air-conditioning & Refrigeration Systems HeadquartersCertificate number : JQA-0709

Date of certification : December 1994

BIWAJIMA PLANT Mitsubishi Heavy Industries, Ltd.

Air-conditioning & Refrigeration Systems HeadquartersCertificate number : JQA-EM0256

Date of certification : November 1998

MITSUBISHI HEAVY INDUSTRIES-MAHAJAK AIR CONDITIONERS CO., LTD.

Certificate Number : 04100 1998 0813Date of Registration : October 1998

Recycled paper with 100% compounding ratio is used.

This catalogue uses recycled paper with 100% compounding ratio in consideration of the environment. It is printed with soybean ink which contains less organic solvent.

R410A

Mitsubishi HeavyIndustries-Haier (Quingdao)

Air-conditioners Co.,Ltd.Certificate number : 01-1998-083

Date of certification : December 1998

MITSUBISHI HEAVY INDUSTRIES-MAHAJAK AIR CONDITIONERS CO.,LTD.