PACI RAS Gen Group
Misoperation on 5-15-2018
Pacific Gas & Electric
July 24th, 2018
PAGE 2 PACI RAS Internal
Pacific A/C Intertie (PACI) RAS
Background
▪ Monitors TLO, DLO, and SLO combination of the 500kV lines within
PG&E and, based on predetermined System conditions, takes
automated corrective actions, including but not limited to
load/generation dropping, bypassing of series compensation,
insertion/removal of shunt devices and Intertie Separation
▪ Helps maintain 500kV Electric Grid Stability and thermal overloads of
the underlying Transmission system
▪ 3rd most important system for PG&E to have working after a major
catastrophe – Telecom, EMS, RAS
▪ Must be available at least 99.995% of the time (all but 26 minutes of the
year).
PAGE 3 PACI RAS Internal
Tracy
Dixon
Round Mt.
Table Mt.
MalinCapt. Jack
Olinda
Vaca
Vincent
Midway
Gates
DiabloCanyon
Los Banos
Metcalf
Tesla
MossLanding
RAS monitors status of Circuit Breakers and
Undercurrent Relays needed to determine line
status.
Controllers are designed to recognize line
outages and issue remedial actions within 30
milliseconds.
Remedial Actions are predetermined by
information stored in RAS Tables.
500KV NETWORK THROUGH PG&E
PAGE 4 PACI RAS Internal
Caribou/ButtValley
Helms
Wheeler RidgeWind GapBuena Vista
Pearblossom
Olinda
Tracy
Round Mt.
Four Corners
Munro ControlCenter (MCC)
SierraPacific Power
Cascade
Dittmer
Midway
Table Mt.
Chief Joseph BrakeGrand CouleeMcNary PHJohn Day PHWanapum PHWells PHRocky Beach PHShrum, MicaRevelstokeAGC Off
Pacific NW Remedials
Kern OilKern PPTaftMidsun Sw StaMidway Sub
Elk Hills
La Paloma 1&2
Sunset Gen
La Paloma 3&4
IRAS Gen GroupsIn Midway Area
El CerritoVaca DixonNewarkMonta Vista
PittsburgLakewoodMartin
San MateoGold Hill
Ignacio Fulton
Moss Landing Salinas Green Valley Stagg
IRAS Load Groups
Hyatt
Kinport
Maxwell
PACI RAS OUTPUTS (Remedials)
PAGE 5 PACI RAS Internal
Block Diagram
Field to Control Center
IED
IED
System A/C
IED
IED
System B/D
Substation 1
IED
IED
IED
System A/C
IED
IED
IED
System B/D
Substation 2
Channel
Banks
A B
IEDIED
GW
IED IED
GW
IED IED
C D
Data GatewaysProtocol Converters provide Cross-Over of data from Systems AC BD
AC and BD SystemsSubstations have separate System AC and System DB devices.The top (ACST) or (BDST) Chassis talks point-to-point with it’s counter-part in the Control Centers.
Inputs are Hardwired and Cross-Messaged.The IED device local to the controller is hard-wired.
All Remedial are hard-wiredOutput RA’s are hard-wired to local IED’s and Cross-wired to the other Controller in the same control center
The location of a fault in a
route determines if the data
can either reach one or
neither control center.
In other words, it’s possible for
Controller A to receive data on
Route 1 (system AC) while
controller C looses
communication.
Route 1 Route 2 Route 1 Route 2
PAGE 6 PACI RAS Internal
Past Performance
2010 2011 2012
Date of Event
7/16/2010 3/27/2011 3/17/2012
Customer Impact
22,070 customers 169,314 customers 58,296 customers
Root Cause Design error WPE – Script Deviation System Isolation--Field
Duration Approx. 24 Min. 1 hour momentary
Action Items /
Mitigations
-QA development
system (completed in
2013)
-Procedure to govern
administration of any
future PACIRAS
Testing
-Seeking changes in
required testing.
WECC approved testing
changes in late 2013.
Awaiting FERC approval
– 2014. Note: Testing
annually is not required
as RAS platforms are
continuously monitored
for performance.
PAGE 7 PACI RAS Internal
Event Details
PAGE 8 PACI RAS Internal
Sequence of Events
▪ On May 14, 2018, PG&E installed a new battery bank with two new
rectifiers at Midway substation.
▪ On May 15, 2018 at approximately 08:30 PST, most of the RFL 9745’s at
Midway substation started sending trips to the remote IRAS Generation
Groups 2, 3, 4 and 5.
o IRAS Gen Group 2 consists of Elk Hills CTG 1, CTG 2 and STG (System B/D)
o IRAS Gen Group 3 consists of La Paloma Units 1 and 2 (System B/D)
o IRAS Gen Group 4 consists of Sunrise CTG 1, CTG 2 and STG 3 (System B/D)
o IRAS Gen Group 5 consists of La Paloma Units 3 and 4 (System A/C)
▪ At the time of the event, only Elk Hills was generating. La Paloma and
Sunrise were off-line. The event resulted in the tripping of 400 MW of
generation at Elk Hills.
▪ Even after the initial event, trip signals were still being received at each of
the remote IRAS Gen Group sites.
PAGE 9 PACI RAS Internal
Sequence of Events (continued…)
▪ It was confirmed by the RAS Operations personnel that the trip signals were
not initiated the centralized PACI RAS Controllers nor any of the scheme’s
N60 devices.
▪ During the troubleshooting process, System Protection recommended to
cut-out the trips to IRAS Gen Group 2, IRAS Gen Group 3, IRAS Gen
Group 4 and IRAS Gen Group 5
▪ The source of the unintended trips signals was identified as a failure of one
of the rectifiers that had been installed just the previous day. The nature of
the failed rectifier resulted in a 80V AC signal being present from each of
the DC legs to ground.
▪ The bad rectifier was taken off line and the unintended trips signals cleared.
PAGE 10 PACI RAS Internal
Next steps
▪ An internal CAP (Corrective Action Program) Item was created and the
need to perform an Apparent Cause Evaluation (ACE) was identified.
▪ The projected due date for this ACE and the associated report is 8/15/2018
▪ The failed rectifier was sent back to the manufacturer for repair and was
recently returned to service earlier this month.
PAGE 11 PACI RAS Internal
WECC EPAS Questions
PAGE 12 PACI RAS Internal
How did the rectifier affect the RAS
system?
▪ The nature of the failure introduced an AC signal on the
DC legs of the rectifier.
▪ When the AC signal was positive and above the trip
setting, the erroneous signals were sent. This was
consistent with the continuous trip signal being
sent/received via the RFL equipment until the failed
rectifier was taken offline.
PAGE 13 PACI RAS Internal
What was the trip signal that was lost
(DC, Rectifier failure, low ac output, etc)?
▪ A trip signal was not lost in this case.
▪ Each Midway Gen group segment trip command has
physical output(s) at Midway Substation and each output
is wired via copper to the respective RFL 9745 input
(DTT Send). The RFL 9745 DC inputs sensed a positive
assertion (trip command) while the Ripple AC was
present.
PAGE 14 PACI RAS Internal
Please provide a diagram of the relevant
portions of the report
▪ See following two slides
PAGE 17 PACI RAS Internal
Questions ?