P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

35
POWER SYSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Transcript of P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Page 1: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

POWER SYSTEMChapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Page 2: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

POWER FACTOR The cosine of angle between voltage and current in an

a.c. circuit is known as power factor. In an a.c. circuit, there is generally

a phase difference φ between voltage

and current. The term cos φ is called

the power factor of the circuit. If the circuit is inductive, the current lags behind the

voltage and the power factor is referred to as lagging. However, in a capacitive circuit, current leads the volt-

age and power factor is said to be leading.

Page 3: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

POWER FACTOR VALUE It is a usual practice to attach the word ‘lagging’ or

‘leading’ with the numerical value of power factor to signify whether the current lags or leads the voltage. Thus if the circuit has a p.f. of 0·5 and the current lags the voltage, we generally write p.f. as 0·5 lagging.

Sometimes power factor is expressed as a percentage. Thus 0·8 OA = VI cos φ and represents the active power in watts or kW lagging power factor may be expressed as 80% lagging.

Page 4: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Power Triangle

The analysis of power factor can also be made in terms of power drawn by the a.c. circuit.We have the power triangle OAB shown in Fig. 6.2 where

OA = VI cos φ and represents the

active power in watts or kW AB = VI sin φ and represents the

reactive power in VAR or kVAR OB = VI and represents the apparent power in VA

or kVA

Page 5: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

POINTS FORM THE POWER TRIANGLE

The apparent power in an a.c. circuit has two components

viz., active and reactive power at right angles to each other.

(OB) ² = (OA) ² + (AB) ²

or (apparent power)² = (active power)² + (reactive power)²

or (kVA)² = (kW)² + (kVAR)² Power factor, cos φ = OA = active power = kW

OB apparent power kVA

Thus the power factor of a circuit may also be defined as the ratio of active power to the apparent power. This is a perfectly general definition and can be applied to all cases, what- ever be the waveform.

Page 6: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

The lagging * reactive power is responsible for the low power factor. It is clear from the power triangle that smaller the reactive power component, the higher is the power factor of the circuit.

kVAR = kVA sin φ = Kw sin φ

cos φ

kVAR = kW tan φ

* If the current lags behind the voltage, the reactive power drawn is known as lagging reactive power. How- ever, if the circuit current leads the voltage, the reactive power is known as leading reactive power.

Page 7: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

For leading currents, the power triangle becomes reversed. This fact provides a key to the power factor improvement. If a device taking leading reactive power (e.g. capacitor) is connected in parallel with the load, then the lagging reactive power of the load will be partly neutralised, thus improving the power factor of the load.

The power factor of a circuit can be defined in one of the following three ways :

• Power factor = cos φ = cosine of angle between V and I• Power factor = R = Resistance

z Impedance• Power factor = VI cos φ = Active power

VI Apparent Power

Page 8: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

The reactive power is neither consumed in the circuit nor it

does any useful work. It merely flows back and forth in both directions in the circuit. A wattmeter does not measure reactive power.

Disadvantages of Low Power Factor The power factor plays an importance role in a.c. circuits since power consumed depends upon this factor.

Large kVA rating of equipment. The electrical machinery (e.g., alternators, transformers, switchgear) is

always rated in *kVA. Now,kVA = kW cos φ

Page 9: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

It is clear that kVA rating of the equipment is inversely proportional to power factor. The

smaller the power factor, the larger is the kVA

rating. Therefore, at low power factor, the kVA

rating of the equipment has to be made more,making the equipment larger and expensive.

Page 10: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Greater conductor size To transmit or distribute a fixed amount of power at constant

voltage, the conductor will have to carry more current at low power factor. This necessitates large conductor size.

Page 11: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Large copper losses The large current at low power factor causes more I2R losses in all

the elements of the supply system. This results in poor efficiency.

Poor voltage regulation The large current at low lagging power factor causes greater

voltage drops in alternators, transformers, transmission lines and distributors. This results in the decreased voltage available at the supply end, thus impairing the performance of utilisation devices. In order to keep the receiving end voltage within permissible limits, extra equipment (i.e., voltage regulators) is required.

Page 12: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Reduced handling capacity of system The lagging power factor reduces the handling capacity of all the

elements of the system. It is because the reactive component of current prevents the full utilisation of installed capacity.

Causes of Low Power Factor Low power factor is undesirable from economic point of view.

Normally, the power factor of the whole load on the supply system in lower than 0·8. The following are the causes of low power factor:

Most of the a.c. motors are of induction type (1 φ and 3 φ induction motors) which have low lagging power factor. These motors work at a power factor which is extremely small on light load (0·2 to 0·3) and rises to 0·8 or 0·9 at full load.

Page 13: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Arc lamps, electric discharge lamps and industrial heating furnaces operate at low lagging power factor.

The load on the power system is varying ; being high during morning and evening and low at other times. During low load period, supply voltage is increased which increases the magnetisation current. This results in the decreased power factor.

Page 14: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

POWER FACTOR CORRECTION

Most domestic loads (such as washing machines, air conditioners, and refrigerators) and industrial loads (such as induction motors) are inductive and operate at a low lagging power factor.

Although the inductive nature of the load cannot be changed, we can increase its power factor.

Defination The process of increasing the power factor without altering the

voltage or current to the original load is known as power factor correction.

Page 15: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)
Page 16: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Since most loads are inductive, as shown in Fig. 11.27(a), a load’s

power factor is improved or corrected by deliberately installing a capacitor in parallel with the load, as shown in Fig. 11.27(b).

The effect of adding the capacitor can be illustrated using either the power triangle or the phasor diagram of the currents involved. Figure 11.28 shows the latter, where it is assumed that the circuit in Fig. 11.27(a) has a

power factor of cosø1 ,while the one in Fig. 11.27(b) has a power factor of cosø2. It is evident from Fig. 11.28 that adding the capacitor has caused the phase angle between the supplied voltage and current to reduce from ø1 to ø2 thereby increasing the power factor.

Page 17: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

We also notice from the magnitudes of the vectors in Fig. 11.28 that with the same supplied voltage, the circuit in Fig. 11.27(a) draws larger current IL than the current I drawn by the circuit in Fig. 11.27(b).

Power companies charge more for larger currents, because they result in increased power losses (by a squared factor, since ). Therefore, it is beneficial to both the power company and the consumer that every effort is made to minimize current level or keep the power factor as close to unity as possible. By choosing a suitable size for the capacitor, the current can be made to be completely in phase with the voltage, implying unity power factor.

Page 18: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Power Factor Improvement Equipment Normally, the power factor of the whole load on a large generating

station is in the region of 0·8 to 0·9. However, sometimes it is lower and in such cases it is generally desirable to take special steps to improve the power factor. This can be achieved by the following equipment :1.Static capacitors. 2.Synchronous condenser

3. Phase advancers.

Page 19: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)
Page 20: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

1)Static capacitor The power factor can be improved by connecting capacitors in

parallel with the equipment operating at lagging power factor. The capacitor (generally known as static capacitor) draws a leading

current and partly or completely neutralises the lagging reactive compo- nent of load current.

This raises the power factor of the load. For three-phase loads, the capacitors can be connected in delta or star as shown in Fig. 6.4. Static capacitors are invariably used for power factor improvement in factories.

Page 21: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Advantages They have low losses. They require little maintenance as there are no rotating parts. They can be easily installed as they are light and require no

foundation. They can work under ordinary atmospheric conditions.

Disadvantages They have short service life ranging from 8 to 10 years. They are easily damaged if the voltage exceeds the rated value. Once the capacitors are damaged, their repair is uneconomical.

Page 22: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

2)Synchronous condenser. A synchronous motor takes a leading current when over-

excited and, therefore, behaves as a capacitor. An over-excited synchronous motor running on no load is known as synchronous condenser.

When such a machine is connected in parallel with the supply, it takes a leading current which partly neutralises the lagging reactive component of the load. Thus the power factor is improved.

Page 23: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Advantages By varying the field excitation, the magnitude of current

drawn by the motor can be changed by any amount. This helps in achieving stepless † control of power factor.

Page 24: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

The motor windings have high thermal stability to short circuit currents.

The faults can be removed easily.

Disadvantages There are considerable losses in the motor. The maintenance cost is high. It produces noise. Except in sizes above 500 kVA, the cost is greater than that of static

capacitors of the same rating. As a synchronous motor has no self-starting torque, therefore, an

auxiliary equipment has to be provided for this purpose.

Page 25: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

3)Phase advancers Phase advancers are used to improve the power factor of

induction motors. The low power factor of an induction motor is due to the fact that its stator winding draws exciting current which lags be- hind the supply voltage by 90°.

If the exciting ampere turns can be provided from some other a.c. source, then the stator winding will be relieved of exciting current and the power factor of the motor can be improved.

This job is accomplished by the phase advancer which is simply an a.c. exciter. The phase advancer is mounted on the same shaft as the main motor and is connected in the rotor circuit of the motor. It provides exciting ampere turns to the rotor circuit at slip frequency.

Page 26: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Synchronous Condenser

Static Capacitor

By providing more ampere turns than required, the induction motor can be made to operate on leading power factor like an over-excited synchronous motor.

Page 27: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Example 6.1 An alternator is supplying a load of 300 kW at a p.f. of 0·6 lagging. If the power factor is raised to unity, how many more kilowatts can alternator supply for the same kVA loading ?

Data Given:-

load=300kW

at P.F1=0.6 lagging

P.F2=1

P=?

Page 28: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Solution :

kVA = kW = 300 = 500 kVA

cos φ 0. 6

kW at 0·6 p.f. = 300 kW

kW at 1 p.f. = 500 * 1 = 500 kW

Increased power supplied by the alternator

= 500 - 300 = 200 kW

Page 29: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Importance of Power Factor Improvement

The improvement of power factor is very important for both consumers and generating stations as discussed below :

For consumers. A consumer has to pay electricity charges for his maximum demand in kVA plus the units consumed. If the consumer imporves the power factor, then there is a reduction† in his maximum kVA demand and consequently there will be annual saving due to maximum demand charges. Although power factor improvement involves extra annual expenditure on account of p.f. correction equipment, yet improvement of p.f. to a proper value results in the net annual saving for the consumer.

Page 30: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

For generating stations. A generating station is as much concerned with power factor im- provement as the consumer. The generators in a power station are rated in kVA but the useful output depends upon kW output. As station output is kW = kVA ´ cos φ, therefore, number of units supplied by it depends upon the power factor. The greater the power factor of the generating station, the higher is the kWh it delivers to the system. This leads to the conclusion that improved power factor increases the earning capacity of the power station.

Page 31: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Meeting the Increased kW Demand on Power Stations

The useful output of a power station is the kW output delivered by it to the supply system. Sometimes, a power station is required to deliver more kW to meet the increase in power demand. This can be achieved by either of the following two methods :

By increasing the kVA capacity of the power station at the same power factor (say cos φ 1). Obviously, extra cost will be incurred to increase the kVA capacity of the station.

By improving the power factor of the station from cos φ 1 to cos φ 2 without increasing the kVA capacity of the station. This will also involve extra cost on account of power factor correction equipment.

Page 32: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Example When connected to a 120-V (rms), 60-Hz power line, a

load absorbs 4 kW at a lagging power factor of 0.8. Find

the value of capacitance necessary to raise the pf to 0.95.

Solution:If the pf =0.8,then cosø1 =0.8   ø1 =36.87° where ø1 is the phase difference between voltage

and current.We obtain the apparent power from the real power

and the pf as

Page 33: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

S1=P / cos ø1 = 4000 /0.8 = 5000 VA

The reactive power is

Q1 =S1 *sin ø1 = 5000* sin 36.87 = 3000 VAR

When the pf is raised to 0.95, cos ø2 =0.95 ø2 = 18.19The real power P has not changed. But the apparent

powerhas changed; its new value is S2= P/Cos ø2 = 4000/0.95 = 4210.5 VAThe new reactive power is Q2 =S2* sin ø2 = 1314.4 VAR

Page 34: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

The difference between the new and old reactive powers is

due to the parallel addition of the capacitor to the load. The

reactive power due to the capacitor is QC= Q1 – Q2 = 3000 - 1314.4 = 1685.6 VARAnd C = QC / ωV ²rms = 1685.6 /2 *60*120² 𝜋

=310.5 F𝝁 Note: Capacitors are normally purchased for

voltages they expect to see. In this case, the maximum voltage this capacitor will see is about 170 V peak. We would suggest purchasing a capacitor with a voltage rating equal to, say, 200 V.

Page 35: P OWER S YSTEM Chapter #6 Power Factor Improvement Rashid Gulzar (Bsee01123176)

Thank You