OWNER: NMSU PROJECT #3354 - Facilities & Services...2019/08/08 · CONSULTANTS: ARCHITECT: DESERT...
Transcript of OWNER: NMSU PROJECT #3354 - Facilities & Services...2019/08/08 · CONSULTANTS: ARCHITECT: DESERT...
PROJECTION (PLAN / ELEVATION)
EXISTING WALL TO REMAIN
STUCCO
CUT (SECTION)
CONCRETE
EARTH
RIGID INSULATION
BATT INSULATION
WOOD BLOCKING
SPRAYED INSULATION
EXISTING CONDITIONS TO REMAIN - NO WORK
NEW WALL / NEW CONSTRUCTION
BUILDING SECTION SYMBOL WALL SECTION SYMBOL
ELEVATION SYMBOLS REFERENCE KEYNOTE SYMBOL
A101
1SIM
DETAIL SYMBOL
A101
1SIM
SIMILAR, TYPICAL, OR MIRRORED REFERENCE
SIMILAR, TYPICAL, OR MIRRORED REFERENCE
SPOT DIMENSIONS
HEIGHT INDICATION (ABOVE RESPECTIVE GROUND FLOOR LEVEL ELEVATION)
0'-0"
WINDOW/ DOOR TAG SYMBOLS
WALL TAG SYMBOL
PARTITION TYPE
1,234 SF
12
ROOM NUMBER
AREA
OCCUPANT LOAD
ROOM TAG SYMBOL
Room name101
CH= 1'-0"
CEILING TAG SYMBOL
HEIGHT INDICATION (ABOVE RESPECTIVE FLOOR LEVEL ELEVATION)
DETAIL
SHEET NUMBER
SHEET NUMBER
BUILDING SECTIONNUMBER
SHEET NUMBER
DETAIL
SHEET NUMBER
BUILDING SECTION NUMBER
SHEET NUMBER
ELEVATION NUMBER
A1 A101
E3/A504
DETAIL / SHEET #E3/A
504
A101
1SIM
A101
1SIM
A101
1SIM
1
A101
1t
101 DOOR TAG
1tWINDOW TAG
1
KEYED NOTE - REFERS TO KEYNOTE LEGEND ON EACH SHEET
PROJECT LOCATION
SAM STEEL WAY
STEWART ST.
E. U
NIO
N A
VE
GREGG ST.
S. E
SP
INA
ST
.
KN
OX
ST
.
SW
EE
T A
VE
.
STERN DR.
ALTERATIONS TO EXISTING BUILDING - LEVEL 1 ALTERATIONS
Per IBC 2015 - 304.1EXISTING OCCUPANCY CLASSIFICATION - GROUP B (UNCHANGED)
EXISTING CONSTRUCTION TYPE - IIBSPRINKLERED: NO
TOTAL GSF OF WORK AREA: 393 GSFNET SF OF WORK AREA: 366 SF
OCCUPANT LOAD FACTOR - Per IBC 2015 1004.1.2
BUSINESS AREA (B) - 100 GSF/OCCUPANTOCCUPANT LOAD OF WORK AREA: 393 SF/100 = 4 OCCUPANTS (OCCUPANCY AND EGRESS UNCHANGED BY NEW CONSTRUCTION)
RE
G
I ST ERED A RCH
I T
EC
T
ST
AT
E
OF NEWMEX
ICORICHARD HAAS
NO. 2530
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022
SHEET NO.
SHEET TITLE
ISS
UE
:
D
C
B
A
1 3 4 52
08.19.2019
NO
T F
OR
CO
NSTR
UC
TIO
N
PROJECT NO.206-102
G001
COVER SHEET
08/1
9/2
019
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
ION
DA
CC
HE
AL
TH
AN
D P
UB
LIC
SE
RV
ICE
S B
LD
G.
34
00
ES
PIN
A S
TLA
S C
RU
CE
S, N
M 8
80
03
95%
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
DRAWING INDEXOWNER:REGENTS OF NEW MEXICO STTE UNIVERSITY
CONTACT: MICHAEL VIELMA - ASSISTANT PROJECT MANAGER
CONSULTANTS:
ARCHITECT:
DESERT PEAK ARCHITECTS, INC
1014 SOUTH MAIN STREET
LAS CRUCES, NM 88005
P. (575) 528 - 0022
CONTACT: RICHARD HAAS
ELECTRICAL
VICINITY MAP
NMSU PROJECT #3354
DACC FLUOROSCOPY SUITE
RENOVATION
RAXIS ENGINEERING3800 N. MESAEL PASO, TX. 79902(915) 539-2515
CONTACT: JOSE MORALES
COVER G-SHEETS
G001 COVER SHEET
DACC HEALTH AND PUBLIC SERVICES BLDG.3400 ESPINA ST.
LAS CRUCES, NM 88003
ELECTRICAL
E100 ELECTRICAL GENERAL NOTES
E200 ELECTRICAL DEMOLITION PLAN
E300 ELECTRICAL PLAN
E400 ELECTRICAL RISER
MATERIAL LEGEND
SYMBOL LEGEND
2015 INTERNATIONAL BUILDING CODE2015 EXISTING BUILDING CODE2015 NM COMMERCIAL CODES2015 UNIFORM MECHANICAL CODE2015 NM MECHANICAL CODE2017 NATIONAL ELECTRICAL CODE2017 NM ELECTRICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE
DESIGN CODES
ARCHITECTURAL
A101 FIRST FLOOR PLAN & REFLECTED CEILING PLAN
A301 WALL SECTION, DETAILS AND SCHEDULES
DEMOLITION
D100 - DEMOLITION PLAN
PROJECT INFORMATION
Mark
Date
Description
NO WORK
NO WORKNO WORKNO WORK
NO WORK
NO WORK
NO WORK
OFFICE
185A
RADIOLOGICAL TECH LAB
185
1
2
1
1
1
3
4
C4 D100
5
3'-3" 3'-3"
2'-6
"
6
7
7
7
7
11
12
TYP
11
11
11
13
13
14
14
14
16
EQ EQ20
185C
185D
21
22
B5
A301
C4 D100
NO WORK
NO WORKNO WORKNO WORK
NO WORK
NO WORK
NO WORK
RADIOLOGICAL TECH LAB
185
OFFICE
185A
8
9
10
8
9
10
15
15
17
18
19
19185D
185C
23
A. INFORMATION SHOWN HERE REFLECTS EXISTING RECORDS AND ON-SITE OBSERVATIONS. THE DEMOLITION WORK SHOWN IS INTENDED TO CONVEY THE GENERAL NATURE & SCOPE OF THE WORK REQUIRED. THE CONTRACTOR SHALL PERFORM ALL DEMOLITION WORK NECESSARY TO COMPLETE THE NEW WORK.
B. REMOVE ALL EXISTING PIPING, DUCTWORK, WIRING, ETC. THAT IS NOT REQUIRED TO SUPPORT THE PROPER OPERATION OF THE NEW WORK AND EXISTING SYSTEMS TO REMAIN.
C. PROTECT PIPING, DUCTOWRK, CONDUIT, ETC. FROM ENTRANCE OF FOREIGN MATERIALS. D. DIMENSIONS ARE NOMINAL FROM FACE OF EXISTING.E. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS AND SHALL NOTIFY
ARCHITECT OF ANY DISCREPANCIES.F. CONTRACTOR SHALL PROVIDE TEMPORARY BARRIERS DURING CONSTRUCTION TO PROVIDE DUST
AND DEBRIS CONTROL. CONTRACTOR TO COORDINATE BARRIER LOCATIONS WITH OWNER/ARCHITECT.
G. CONTRACTOR SHALL PROTECT ALL EXISTING TO REMAIN ITEMS WITHIN THE WORK AREA TO PREVENT DAMAGE. THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE DONE TO EXISTING CONDITIONS TO REMAIN.
H. CONTRACTOR SHALL COORDINATE SITE ACCESS AND STAGING AREA WITH OWNER/ARCHITECT.I. THE CONTRACTOR SHALL REPAIR AND REPLACE ANY ITEM OR SURFACE DAMAGED BY THE WORK,
OR AS REQUIRED BY NEW INSTALLATION.J. ALL DEMOLISHED MATERIALS TO BE REMOVED FROM SITE. U.N.O.K. CONTRACTOR SHALL KEEP ALL EXISTING EXIT WAYS CLEAR AND OPEN DURING CONSTRUCTION.L. HAZRDOUS MATERIALS - IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS WILL BE ENCOUNTERED
DURING THE WORK. UPON DISCOVERY OF HAZARDOUS MATERIALS, CONTRACTOR SHALL STOP WORK AND INFORM THE OWNER/ARCHITECT
M. REMOVE OR RELOCATE ALL MEP FEATURES AS NECESSARY (WHETHER SPECIFICALLY SHOWN OR NOT)
N. REMOVE ALL EXPOSED CONDUIT AND WIRE-MOLD THAT IS NOT TO BE RE-USED.O. REMOVE ALL POWER AND LOW VOLTAGE WIRES THAT ARE NOT RE-USED BACK TO THE NEAREST
JUNCTION BOX.
FIRST FLOOR0' - 0"
EQ EQ
2'-10
"4
'-8
"
6'-6"
5
B5
A301
ALTERNATE SCHEDULE - DEMOLITIONALTERNATE #1: DEMOLISH AND REMOVE EXISTING VINYL TILE FLOORING IN ROOMS 185D AND 185C. PREP FLOOR FOR NEW FINISHED. (BASE BID: PREP EXISTING VCT FLOORING AS REQUIRED FOR NEW PAINT. REFER TO ALTERNATE SCHEDULE IN NEW WORK)
RE
G
I ST ERED A RCH
I T
EC
T
ST
AT
E
OF NEWMEX
ICORICHARD HAAS
NO. 2530
N
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022
SHEET NO.
SHEET TITLE
ISS
UE
:
D
C
B
A
1 3 4 52
08.19.2019
KEY PLAN
PROJECT LOCATION
NO
T F
OR
CO
NSTR
UC
TIO
N
PROJECT NO.206-102
D100
DEMOLTION PLAN
08/1
9/2
019
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
ION
DA
CC
HE
AL
TH
AN
D P
UB
LIC
SE
RV
ICE
S B
LD
G.
34
00
ES
PIN
A S
TLA
S C
RU
CE
S, N
M 8
80
03
95%
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
PROJECT NORTH
KEYNOTE LEGEND1 REMOVE EXISTING GYPSUM BOARD SHEATHING (THIS SIDE ONLY) - PREP WALLS FOR NEW LEAD LINER
AND NEW GYPSUM BOARD SHEATHING
2 DEMOLISH AND REMOVE EXISTING DOOR AND DOOR FRAME. PREP OPENING FOR NEW LEAD LINED DOOR
AND FRAME
3 DEMOLISH AND REMOVE EXISTING WALL AS SHOWN. PATCH/REPAIR EXISTING WALLS TO REMAIN AS
REQUIRED FOR NEW PAINT. CONTRACTOR TO IDENTIFY ACTIVE NATURE OF IN-WALL WATER LINES;
REMOVE WATER PIPING BACK TO NEAREST MAIN AND CAP. REMOVE UN-USED COPPER PIPING.
4 REMOVE EXISTING DOOR, DOOR HARDWARE AND DOOR FRAME. SALVAGE DOOR AND DOOR HARDWARE
5 DEMOLISH AND REMOVE PORTION OF WALL AS REQUIED FOR NEW 6'-0" LONG X 4'-0" TALL WINDOW -
VERIFY ROUGH OPENING SIZE REQUIREMENTS IN FIELD. REMOVE JUNCTION BOXES, CONDUIT AND
WIRING AS REQUIRED. RECEPTACLES TO BE RE-LOCATED IN NEW WORK.
6 DEMOLISH AND REMOVE PORTION OF WALL AS REQUIRED FOR NEW 3'-0" X 7'-0" DOOR AND FRAME. CUT
AND CAP COPPER PIPING ABOVE ROUGH OPENING - ABANDON IN PLACE. REMOVE JUNCTION BOXES,
CONDUIT AND WIRING AS REQUIRED. RECEPTACLES TO BE RE-LOCATED IN NEW WORK.
7 REMOVE EXISTING BASE BOARD (THIS SIDE ONLY)
8 DEMOLISH AND REMOVE ACOUSTIC CEILING TILES AND CEILING GRID. CAREFULLY REMOVE ANY CEILING
MOUNTED EQUIPMENT - KEEP IN CLEAN, SAFE AREA FOR RE-USE
9 CAREFULLY REMOVE EXISTING LIGHT FIXTURES. KEEP IN CLEAN, SAFE AREA FOR RE-USE
10 CAREFULLY REMOVE EXISTING CEILING MOUNTED DIFFUSERS AND GRILLES. KEEP IN CLEAN, SAFE AREA
FOR RE-USE
11 EXISTING DOOR TO REMAIN
12 EXISTING WALL TO REMAIN
13 ALTERNATE #1 - REMOVE EXISTING VCT FLOORING IN THIS AREA. PREP FLOOR FOR NEW FINISHES (BASE
BID: PREP EXISTING VCT FLOORING AS REQUIRED FOR NEW PAINT)
14 EXISTING FLOORING TO REMAIN - NO WORK
15 EXISTING CEILING AND FIXTURES TO REMAIN - NO WORK
16 CAREFULLY REMOVE SURFACE MOUNTED TV MOUNT AND WHITE BOARD IN THIS AREA. SALVAGE BACK TO
OWNER FOR RE-USE.
17 DEMOLISH AND REMOVE EXISTING GYPSUM BOARD CEILING AND SUSPENSION SYSTEM
18 CAREFULLY REMOVE EXISTING SURFACE MOUNTED LIGHT FIXTURE. SALVAGE BACK TO OWNER FOR RE-USE
19 REMOVE EXISTING SURFACE MOUNTED DIFFUSER AND RETURN GRILLE.
20 DEMOLISH AND REMOVE FLOOR SINK. CAP AND ABANDON PIPING IN PLACE. PREP FLOOR FOR CONCRETE
PATCH IN NEW WORK.
21 CONTRACTOR TO IDENTIFY ACTIVE NATURE OF COPPER PIPING IN THIS LOCATION. IF ACTIVE, CUT AND
CAP PIPING IN-WALL AND ABONDON IN PLACE. REMOVE UNUSED PIPING.
22 CONTRACTOR TO IDENTIFY ACTIVE NATURE OF COPPER PIPING IN THIS LOCATION. IF ACTIVE, CUT AND
CAP PIPING ABOVE CEILING SPACE. REMOVE UNUSED PIPING.
23 REMOVE UNUSED VENT DUCT IN CEILING SPACE
1/4" = 1'-0"D100A4 DEMOLITION PLAN
1/4" = 1'-0"D100A1 DEMOLITION RCP
PROJECT NORTH
GENERAL NOTES
1/4" = 1'-0"D100C4 DEMOLITION ELEVATION
Mark
Date
Description
NO WORK
NO WORKNO WORKNO WORK
NO WORK
NO WORK
NO WORK
OFFICE
185A
RADIOLOGICAL TECH LAB
185
A
B5
A301
STUDENT OBSERVATION AREA
185C
FLUOROSCOPY EQUIPMENT ROOM
185B
1
1
1
12
2
185B
185C
4
4
5
56
A301
A5
A301
A316
17
17
16
18
6'-0"
20
17
(ALTERNATE #1 - REMOVE AND REPLACE EXISTING VINYL FLOOR TILE IN THIS ROOM WITH NEW VINYL FLOOR TILE TO MATCH EXISTING. PROVIDE FLOOR TRANSITION STRIPS WHERE NEW FLOORING MEETS DISSIMALAR FLOORING MATERIAL
17
21 21
TYP TYP
A. LEAD LINER CONTRACTOR TO COORDINATE ALL LEAD LINING REQUIREMENTS WITH QUALIFIED HEALTH RADIATION PHYSICIST AS HIRED BY NMSU. ALL LEAD LINED MATERIALS AND ACCESSORIES ARE TO BE PROVIDED FROM A SINGLE SOURCE MANUFACTURER AND INSTALLED BY QUALIFIED CONTRACTORS.
B. PROVIDE FIRE RESISTANT WOOD BLOCKING BETWEEN STUDS AT ALL WALL MOUNTED EQUIPMENT, BOARDS, GRAB BARS, CASEWORK, ETC
C. REFER TO WALL PARTITION TYPE FOR GENERAL PARTITION NOTESD. REFER TO REFLECTED CEILING PLAN FOR CEILING-MOUNTED EQUIPMENT, CEILING
TRANSITIONS AND DETAIL INFORMATION. COORDINATE ALL CEILING MOUNTED FIXTURES AND EQUIPMENT WITH MEP DRAWINGS.
E. REFER TO WINDOW TYPE LEGEND FOR WINDOW SIZES.F. DIMENSIONS ARE FROM FINISHED FACE OF EXISTING WALLS OR FACE OF STUD
FOR NEW WALLS U.N.O.
FIRST FLOOR0' - 0"
FINISHED FLOOR
CEILING LINE
STEEL DECK
TERMINATE GYP 6" ABOVE CEILING - TYP
EXISTING METAL STUD WITH LEAD LINED GYP - ONE SIDE
3-5/8" METAL STUD W/ STANDARD GYP - ONE
SIDE & LEAD LINED GYP -ONE SIDE
RESILIENT BASE
1
6"
GAP WITH CLIPS ALLOWING
MOVEMENT
2
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
EXISTING METAL STUD WALL TO REMAIN
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY
NMSU). LEAD LINING TO BEINTEGRAL TO GYPSUM WALLBOARD.
3-5/8" METAL STUDS, 16" OCMINIMUM
GYPSUM BOARD 5/8",STANDARD - TAPE AND
TEXTURE TO MATCH EXISTING -PAINT
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY
NMSU). LEAD LINING TO BEINTEGRAL TO GYPSUM WALLBOARD.
RESILIENT BASE(EACH SIDE)
ALTERNATE SCHEDULE ALTERNATE #1: DEMOLISH AND REMOVE EXISTING VINYL TILE FLOORING IN ROOMS 185D AND 185C. PREP FLOOR FOR NEW FINISHES. PROVIDE AND INSTALL NEW VINYL TILE FLOORING IN THIS AREA TO MATCH EXISTING. PROVIDE FLOOR TRANSITION STRIPS WHERE NEW FLOORING MEETS DISSIMALAR FLOORING MATERIAL. (BASE BID: PREP EXISTING VCT FLOORING AS REQUIRED FOR NEW PAINT. INFILL MISSING PORTIONS OF VCT TILE WITH NEW VCT TILE OF SIMILAR SIZE AND THICKNESS. CLEAN SURFACE WITH ABRASSIVE PAD. PAINT WITH BONDING PRIMER AND FINISH WITH FLOOR PAINT. INSTALL FLOOR PAINT PER MANUFACTURER'S RECOMMENDATIONS.)
EQ
EQ
NO WORK
NO WORKNO WORKNO WORK
NO WORK
NO WORK
NO WORK
9
9
10
10
11
11
12
13
14
15
12
13
CH=9' - 0"
CH=9' - 0"
B
A
C
D
B
A
11 11
19
SCHEDULED ACOUSTICAL TILE
CEILING24" x 48"
EXISTING CEILING TO
REMAIN - NO WORK
EXISTING HVAC SUPPLY AIR DIFFUSER TO BE RE-INSTALLED IN NEW CEILING GRID - REF DIFFUSER AND GRILLE SCHEDULE
EXISTING 2x4 FLUORESCENT LIGHT FIXTURE TO BE RE-INSTALLED IN NEW CEILING GRID- REF ELECTRICAL SHEETS.
NEW 2x4 FLUORESCENT LIGHT FIXTURE. PROVIDED BY NMSU, INSTALLED BY CONTRACTOR- REF ELECTRICAL SHEETS.
NEW HVAC SUPPLY AIR DIFFUSER TO MATCH EXISTING - REF DIFFUSER AND GRILLE SCHEDULE
EXISTING HVAC RETURN GRILLE TO BE RE-INSTALLED IN NEW CEILING GRID - REF DIFFUSER AND GRILLE SCHEDULE
NEW HVAC RETURN GRILLE TO MATCH EXISTING - REF DIFFUSER AND GRILLE SCHEDULE
RE
G
I ST ERED A RCH
I T
EC
T
ST
AT
E
OF NEWMEX
ICORICHARD HAAS
NO. 2530
N
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022
SHEET NO.
SHEET TITLE
ISS
UE
:
D
C
B
A
1 3 4 52
08.19.2019
KEY PLAN
PROJECT LOCATION
NO
T F
OR
CO
NSTR
UC
TIO
N
PROJECT NO.206-102
A101
FIRST FLOOR PLAN &
REFLECTED CEILING
PLAN
08/1
9/2
019
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
ION
DA
CC
HE
AL
TH
AN
D P
UB
LIC
SE
RV
ICE
S B
LD
G.
34
00
ES
PIN
A S
TLA
S C
RU
CE
S, N
M 8
80
03
95%
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1/4" = 1'-0"A101A2 FIRST FLOOR PLAN
GENERAL NOTESKEYNOTE LEGEND1 RESILIENT BASE
2 LEAD BACKED DRYWALL. TYPE X STANDARD 5/8"
3 LEAD LINING AS SPECIFIED BY QUALIFIED HEALTH RADIATION PHYSICIST (AS HIRED BY
NMSU). LEAD LINING TO BE INTEGRAL TO GYPSUM WALL BOARD.
4 EXISTING VINYL FLOORING TO REMAIN. CLEAN AND PREPARE SURFACE WITH ABRASSIVE
PAD TO RECEIVE NEW PAINT. PAINT WITH BONDING PRIMER AND FINISH WITH FLOOR
PAINT. (ALTERNATE #1 - REMOVE AND REPLACE EXISTING VINYL FLOOR TILE IN THIS
ROOM WITH NEW VINYL FLOOR TILE TO MATCH EXISTING. PROVIDE FLOOR TRANSITION
STRIPS WHERE NEW FLOORING MEETS DISSIMILAR FLOORING MATERIAL).
5 PROVIDE VINYL FLOOR TILE OF EQUAL SIZE AND THICKESS TO THE ADJACENT EXISTING
VINYL FLOOR TILE IN AREAS WHERE WALLS HAND PLUMBING FIXTURES HAVE BEEN
REMOVED. CLEAN AND PREPARE SURFACE WITH ABRASSIVE PAD. PAINT FLOORING WITH
BONDING PRIMER AND FINISH WITH FLOOR PAINT. COLOR AS SELECTED BY NMSU
ARCHITECT.
6 PROVIDE AND INSTALL CONCRETE FLOOR LEVELER IN AREA WHERE FLOOR SINK HAS
BEEN REMOVED
7 3-5/8" METAL STUDS, 16" OC MINIMUM
8 GYPSUM BOARD 5/8", STANDARD - TAPE AND TEXTURE TO MATCH EXISTING - PAINT
9 EXISTING CEILING AND FIXTURES TO REMAIN - NO WORK
10 SUSPENDED TILE CEILING, 2X4 - REFER TO ROOM FINISH LEGEND FOR TILE
DESIGNATION
11 CONTRACTOR TO RE-INSTALL EXISTING 2X4 FLUORESCENT LIGHT FIXTURE IN NEW
CEILING GRID
12 CONTRACTOR TO RE-INSTALL EXISTING HVAC RETURN GRILLE IN NEW CEILING GRID
13 CONTRACTOR TO RE-INSTALL EXISTING HVAC SUPPLY AIR DIFFUSER IN NEW CEILING
GRID
14 NEW MECHANICAL DIFFUSER - REFER TO SCHEDULE
15 NEW RETURN GRILLE - REFER TO SCHEDULE
16 ELECTRICAL SWITCH - REFER TO ELECTRICAL
17 DATA AND ELECTRICAL RECEPTACLE - REFER TO ELECTRICAL
18 EXISTING VINYL FLOORING TO REMAIN. CLEAN
19 LIGHT FIXTURE - REFER TO ELECTRICAL
20 PLASTIC LAMINATE OVER 3/4" MDF UNDERLAYMENT. PROVIDE GROMMETS IN LOCATIONS
AS INDICATED BY NMSU.
21 PATCH/REPAIR DAMAGED PORTIONS OF EXISTING GYPSUM WALL BOARD. PAINT TO
MATCH EXISTING. TOUCH-UP EXISTING PAINT AS REQUIRED
PROJECT NORTH
TRUE NORTH
1/2" = 1'-0"A101C1 WALL PARTITION TYPES
1/4" = 1'-0"A101A1 FIRST FLOOR REFLECTED CEILING PLAN
RCP LEGEND
PROJECT NORTH
TRUE NORTH
DIFFUSER AND GRILLE SCHEDULEType Mark Manufacturer Model Description
B EXISTING EXISTING RE-INSTALL EXISTING RETURN GRILLE IN NEW CEILING GRID
A EXISTING EXISTING RE-INSTALL EXISTING SUPPLY DIFFUSER IN NEW CEILING GRID
D TITUS SBF RETURN GRILLE; STANDARD FINISH - #26 WHITE; STEEL CONSTRUCTION; 12" X 24" FACE,1/2" BLADE SPACING; LAY-IN
C TITUS TMS SUPPLY DIFFUSER TO MATCH EXISTING; STANDARD FINISH - #26 WHITE; STEELCONSTRUCTION; 24" X 24" FACE; LAY-IN; CONTRATOR TO FIELD VERIFY REQUIRED NECKSIZE
Mark
Date
Description
A. CONTRACTOR TO COORDINATE WITH NMSU FOR FINAL SELECTION OF ALL FINISHES AND COLORS.
B. EXTEND ALL STUDS TO STEEL DECKING. PROVIDE CERAMIC TILE IN ALL
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
VARIES
2" 2"
3-5/8" METAL STUDS, 16" OC MINIMUM
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY NMSU).LEAD LINING TO BE INTEGRALTO GYPSUM WALL BOARD.
HOLLOW METAL STEEL FRAME -LEAD LINED - PROVIDE 3 ANCHORSPER JAMB, PAINT
COORDINATE WITH PHYSICIST REPORT FOR LEAD LINIGHT THICKNESS
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
VARIES
BUILT-UP METAL STUD HEADER
2" 2"
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY NMSU).LEAD LINING TO BE INTEGRAL TOGYPSUM WALL BOARD.
HOLLOW METAL STEEL FRAME -LEAD LINED - PROVIDE 3 ANCHORSPER JAMB, PAINT
COORDINATE WITH PHYSICIST REPORT FOR LEAD LINIGHT THICKNESS
3-5/8" METAL STUDS, 16" OC MINIMUM
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
5 7/8"
2" 2"
3-5/8" METAL STUDS, 16" OC MINIMUM
HOLLOW METAL STEEL FRAME WITH3 ANCHORS PER JAMB, PAINT
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
5 7/8"
BUILT-UP METAL STUD HEADER
2" 2"
HOLLOW METAL STEEL FRAME WITH3 ANCHORS PER JAMB, PAINT
3-5/8" METAL STUDS, 16" OC MINIMUM
FIRST FLOOR0' - 0"
4'-0
"3
'-0
"
A301
B4
11
1
6
12
11
9
12
A
A301
B3
2'-10
"
13
14
B
7'-0
"
3'-0"
A
SOLID CORE WOOD DOOR WITH RADIATION
PROTECTION - MATCH EXISTING SPECIES AND
FINISH
SOLID CORE WOOD DOOR - MATCH EXISTING
SPECIES AND FINISH
3'-0"
7'-0
"
1 2
7'-2
"
2"3'-0"2"
3'-4"
7'-0
"2
"
2"3'-0"2"
3'-4"
7'-2
"
2"
7'-0
"
HM FRAME - PRIME AND PAINT
HM FRAME WITH RADIATION SHILDING -
PRIME AND PAINT
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
VARIES
2"2"
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY NMSU).LEAD LINING TO BE INTEGRAL TOGYPSUM WALL BOARD.
HOLLOW METAL STEEL FRAME -LEAD LINED - PROVIDE 3 ANCHORSPER JAMB, PAINT
COORDINATE WITH PHYSICIST REPORT FOR
LEAD LINIGHT THICKNESS
3-5/8" METAL STUDS, 16" OC MINIMUM
BUILT-UP METAL STUD HEADER- 6" DEPTH
X-RAY LEAD GLASS - INSTALL PERMANUFACTURER'SRECOMMENDATIONS AND INACCORDANCE WITH QUALIFIEDPHYSICIST REQUIREMENTS.
GLAZING STOP
CONT. SEALANT
CONT. SEALANT
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
VARIES
2" 2"
3-5/8" METAL STUDS, 16" OC MINIMUM
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY NMSU).LEAD LINING TO BE INTEGRALTO GYPSUM WALL BOARD.
HOLLOW METAL STEEL FRAME -LEAD LINED - PROVIDE 3 ANCHORSPER JAMB, PAINT
COORDINATE WITH PHYSICIST REPORT FOR
LEAD LINIGHT THICKNESS
X-RAY LEAD GLASS - INSTALLPER MANUFACTURER'SRECOMMENDATIONS AND INACCORDANCE WITH QUALIFIEDPHYSICIST REQUIREMENTS.
GLAZING STOP
CONT. SEALANT
CONT. SEALANT
BOX STUD
A. COORDINATE EXACT FLOORING LAYOUT PATTERNS AND MATERIALS WITH THE ARCHITECT PRIOR TO COMPLETING ANY FLOORING WORK.
B. CONTRACTOR TO PROVIDE TRANSITIONS AT ALL INTERSECTIONS BETWEEN DISSIMILAR MATERIALS WHERE NECESSARY. COORDINATE THESE LOCATIONS WITH THE ARCHITECT PRIOR TO COMPLETING ANY FLOORING WORK..
C. REFER TO SPECIFICATIONS FOR MORE DETAILED INFORMATION ON THE ACCEPTABLE FLOORING PRODUCTS AND APPLICATIONS
GENERAL NOTES - FLOOR FINISHES
FIRST FLOOR0' - 0"
HOLLOW METAL FRAME -LEAD LINED WITH X-RAY PROTECTION GLAZING
WINDOW DETAILS
HEAD JAMB SILL MULLION
A301B4 A301B3A301B2 NONE
A
4'-0
"3
'-0
"
6'-0"
2"
3'-8
"
2"
2" 5'-8" 2"
1.
LEAD BACKED DRYWALL. TYPE XSTANDARD 5/8"
1/2"
GYPSUM BOARD 5/8", STANDARD -TAPE AND TEXTURE TO MATCHEXISTING - PAINT
CONT. SEALANT
CONT. SEALANT
VARIES
2"
2"
3-5/8" METAL STUDS, 16" OC MINIMUM
LEAD LINING AS SPECIFIED BYQUALIFIED HEALTH RADIATIONPHYSICIST (AS HIRED BY NMSU).LEAD LINING TO BE INTEGRALTO GYPSUM WALL BOARD.
HOLLOW METAL STEEL FRAME -LEAD LINED - PROVIDE 3 ANCHORSPER JAMB, PAINT
COORDINATE WITH PHYSICIST REPORT FOR LEAD LINIGHT THICKNESS
CONT. SEALANT
GLAZING STOP
X-RAY LEAD GLASS - INSTALL PERMANUFACTURER'SRECOMMENDATIONS AND INACCORDANCE WITH QUALIFIEDPHYSICIST REQUIREMENTS.
CONT. SEALANT
GLAZING SCHEDULE
1. X-RAY LEAD GLASS - 1/4"- CLEAR - COORDINATE WITH QUALIFIED PHYSICIST (AS HIRED BY NMSU) FOR REQUIREMENTS
RE
G
I ST ERED A RCH
I T
EC
T
ST
AT
E
OF NEWMEX
ICORICHARD HAAS
NO. 2530
This document may not be reproduced in whole or part by any means, electronic or otherwise without the explicit written permission of Desert Peak Architects P.C.. All reports, plans, specifications, computer files, field data and other documents and instruments prepared by the Architect as instruments of service shall remain the property of the Architect. The Architect shall retain all common law, statutory, and other reserved rights, including the copyright thereto.
DESERT PEAK ARCHITECTS P.C.311 N MAIN STREETLAS CRUCESNEW MEXICO 88001P. 575.528.0022
SHEET NO.
SHEET TITLE
ISS
UE
:
D
C
B
A
1 3 4 52
08.19.2019
NO
T F
OR
CO
NSTR
UC
TIO
N
PROJECT NO.206-102
A301
WALL SECTION,
DETAILS AND
SCHEDULES
08/1
9/2
019
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
ION
DA
CC
HE
AL
TH
AN
D P
UB
LIC
SE
RV
ICE
S B
LD
G.
34
00
ES
PIN
A S
TLA
S C
RU
CE
S, N
M 8
80
03
95%
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
KEYNOTE LEGEND1 LEAD BACKED DRYWALL. TYPE X STANDARD 5/8"
2 GYPSUM BOARD 5/8", STANDARD - TAPE AND TEXTURE TO MATCH EXISTING -
PAINT
3 CONT. SEALANT
4 BUILT-UP METAL STUD HEADER
5 3-5/8" METAL STUDS, 16" OC MINIMUM
6 LEAD LINING AS SPECIFIED BY QUALIFIED HEALTH RADIATION PHYSICIST (AS
HIRED BY NMSU). LEAD LINING TO BE INTEGRAL TO GYPSUM WALL BOARD.
7 HOLLOW METAL STEEL FRAME - LEAD LINED - PROVIDE 3 ANCHORS PER JAMB,
PAINT
8 HOLLOW METAL STEEL FRAME WITH 3 ANCHORS PER JAMB, PAINT
9 X-RAY LEAD GLASS - INSTALL PER MANUFACTURER'S RECOMMENDATIONS AND IN
ACCORDANCE WITH QUALIFIED PHYSICIST REQUIREMENTS.
10 GLAZING STOP
11 SUSPENDED TILE CEILING, 2X4 - REFER TO ROOM FINISH LEGEND FOR TILE
DESIGNATION
12 EXISTING WALL TO REMAIN
13 PLASTIC LAMINATE OVER 3/4" MDF UNDERLAYMENT. PROVIDE GROMMETS IN
LOCATIONS AS INDICATED BY NMSU.
14 IN-WALL FLUSH MOUNTED HEAVY DUTY COUNTERTOP SUPPORT BRACKET, 1/4"
STEEL MIN.- 18" O.C. MIN. OR SPACED AS RECOMMENDED BY BRACKET
MANUFACTURER
GENERAL NOTES
1 1/2" = 1'-0"A301A5 HM JAMB DETAIL - LEAD LINED
1 1/2" = 1'-0"A301A4 HM HEAD DETAIL - LEAD LINED
1 1/2" = 1'-0"A301A3 HM JAMB DETAIL
1 1/2" = 1'-0"A301A1 HM HEAD DETAIL
1/2" = 1'-0"A301B5 WALL SECTION
1/4" = 1'-0"A301D4 DOOR TYPES
FIRST FLOOR DOOR AND FRAME SCHEDULEDOOR FRAME MISC
MARK WIDTH HT MATERIAL THK ELEV MATL ELEV MATLHDWSET COMMENTS
185B 3' - 0" 7' - 0" SCWD - LL 1 3/4" B HMLL 2 HMLL 2 LEAD LINED WOOD DOOR WITH LEAD LINED HOLLOW METAL FRAME. WOOD DOOR SPECIESAND FINISH TO MATCH EXISTING WOOD DOORS. HM FRAME COLOR TO MATCH EXISTING HMFRAME COLOR
185C 3' - 0" 7' - 0" SCWD 1 3/4" A HM 1 HM 1 WOOD DOOR SPECIES AND FINISH TO MATCH EXISTING WOOD DOORS. HM FRAME COLORTO MATCH EXISTING HM FRAME COLOR
1/4" = 1'-0"A301C4 HM FRAME TYPES
1 1/2" = 1'-0"A301B4 HM HEAD DETAIL - LEAD LINED
1 1/2" = 1'-0"A301B3 HM SILL DETAIL - LEAD LINED
ABBREVIATION LEGENDHM: HOLLOW METALHMLL: HOLLOW METAL - LEAD LINEDSCWD - LL: SOLID CORE WOOD DOOR - LEAD LINEDSCWD: SOLID CORE WOOD DOORE: EXISTING FINISHES TO REMAIN - PATCH/REPAIR AS REQUIRED BY NEW WORK.
PAINT TO MATCH EXISTING.RB: RUBBER BASEP: GYPSUM WALL BOARD; TAPE AND TEXTURE TO MATCH EXISTING - PAINTEP: EXISTING VINYL FLOOR TILE TO REMAIN. INFILL MISSING TILES WITH SIMILAR MATERIAL.
PREP FLOOR FOR NEW FLOOR PAINT. PAINTATC: ACOUSTICAL TILE CEILING
ROOM FINISH SCHEDULEROOM ID FLOOR WALLS CEILING
COMMENTSROOM NO ROOM NAME FLOOR BASE NORTH SOUTH EAST WEST MATL
185 RADIOLOGICAL TECH LAB E E E E E E E EXISTING FINISHES TO REMAIN. PATCH/REPAIRAS REQUIRED BY NEW WORK
185A OFFICE E E E E E E E EXISTING FINISHES TO REMAIN. PATCH/REPAIRAS REQUIRED BY NEW WORK
185B FLUOROSCOPY EQUIPMENTROOM
E RB P P P P ATC EXISTING VINYL FLOOR TILE TO REMAIN.CLEAN.
185C STUDENT OBSERVATION AREA EP RB P P P P ATC EXISTING VINYL FLOOR TILE TO REMAIN. INFILLMISSING TILES WITH SIMILAR MATERIAL. PREPFLOOR FOR NEW FLOOR PAINT. PAINT
1/4" = 1'-0"A301C1 WINDOW TYPES
1 1/2" = 1'-0"A301B2 HM JAMB DETAIL - LEAD LINED
Mark
Date
Description
08/19/19
19-194
N
This document may not be
reproduced in whole or part by any
means, electronic or otherwise
without the explicit written
permission of Desert Peak
Architects P.C.. All reports, plans,
specifications, computer files, field
data and other documents and
instruments prepared by the
Architect as instruments of service
shall remain the property of the
Architect. The Architect shall retain
all common law, statutory, and
other reserved rights, including the
copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
SU
E:
D
C
B
A
1 3 4 52
KEY PLAN
PROJECT
LOCATION
PROJECT NO.
206-102
08/19/19
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
IO
N
DA
CC
H
EA
LT
H A
ND
P
UB
LIC
S
ER
VIC
ES
B
LD
G.
3400 E
SP
IN
A S
T
LA
S C
RU
CE
S, N
M 88003
95%
C
ON
ST
RU
CT
IO
N D
OC
UM
EN
TS
Mark
Date
Description
E100
ELECTRICAL
GENERAL NOTES
ELECTRICAL GENERAL NOTES
”
”
ELECTRICAL SPECIFICATIONS
“ ”
NO WORKNO WORKNO WORK
NO WORK
NO WORK
OFFICE
185A
RADIOLOGICAL TECH LAB
185
TYP
NO WORK
NO WORKNO WORKNO WORK
NO WORK
RADIOLOGICAL TECH LAB
185
OFFICE
185A
08/19/19
19-194
N
This document may not be
reproduced in whole or part by any
means, electronic or otherwise
without the explicit written
permission of Desert Peak
Architects P.C.. All reports, plans,
specifications, computer files, field
data and other documents and
instruments prepared by the
Architect as instruments of service
shall remain the property of the
Architect. The Architect shall retain
all common law, statutory, and
other reserved rights, including the
copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
SU
E:
D
C
B
A
1 3 4 52
KEY PLAN
PROJECT
LOCATION
PROJECT NO.
206-102
08/19/19
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
IO
N
DA
CC
H
EA
LT
H A
ND
P
UB
LIC
S
ER
VIC
ES
B
LD
G.
3400 E
SP
IN
A S
T
LA
S C
RU
CE
S, N
M 88003
95%
C
ON
ST
RU
CT
IO
N D
OC
UM
EN
TS
Mark
Date
Description
ELECTRICAL LIGHTING PLAN
1/4" = 1'-0"
DEMOLITION GENERAL NOTES:
E200
ELECTRICAL
DEMOLITION PLAN
OFFICE
185A
RADIOLOGICAL TECH LAB
185
STUDENT OBSERVATION AREA
185C
FLUOROSCOPY EQUIPMENT ROOM
185B
08/19/19
19-194
N
This document may not be
reproduced in whole or part by any
means, electronic or otherwise
without the explicit written
permission of Desert Peak
Architects P.C.. All reports, plans,
specifications, computer files, field
data and other documents and
instruments prepared by the
Architect as instruments of service
shall remain the property of the
Architect. The Architect shall retain
all common law, statutory, and
other reserved rights, including the
copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
SU
E:
D
C
B
A
1 3 4 52
KEY PLAN
PROJECT
LOCATION
PROJECT NO.
206-102
08/19/19
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
IO
N
DA
CC
H
EA
LT
H A
ND
P
UB
LIC
S
ER
VIC
ES
B
LD
G.
3400 E
SP
IN
A S
T
LA
S C
RU
CE
S, N
M 88003
95%
C
ON
ST
RU
CT
IO
N D
OC
UM
EN
TS
Mark
Date
Description
ELECTRICAL POWER PLAN
1/4" = 1'-0"
ELECTRICAL POWER PLAN
1/4" = 1'-0"
E300
ELECTRICAL
PLAN
LIGHTING PLAN KEYED NOTES
08/19/19
19-194
N
This document may not be
reproduced in whole or part by any
means, electronic or otherwise
without the explicit written
permission of Desert Peak
Architects P.C.. All reports, plans,
specifications, computer files, field
data and other documents and
instruments prepared by the
Architect as instruments of service
shall remain the property of the
Architect. The Architect shall retain
all common law, statutory, and
other reserved rights, including the
copyright thereto.
DESERT PEAK ARCHITECTS P.C.
311 N MAIN STREET
LAS CRUCES
NEW MEXICO 88001
P. 575.528.0022
SHEET NO.
SHEET TITLE
IS
SU
E:
D
C
B
A
1 3 4 52
KEY PLAN
PROJECT
LOCATION
PROJECT NO.
206-102
08/19/19
FL
UO
RO
SC
OP
Y S
UIT
E R
EN
OV
AT
IO
N
DA
CC
H
EA
LT
H A
ND
P
UB
LIC
S
ER
VIC
ES
B
LD
G.
3400 E
SP
IN
A S
T
LA
S C
RU
CE
S, N
M 88003
95%
C
ON
ST
RU
CT
IO
N D
OC
UM
EN
TS
Mark
Date
Description
2'X4' FLUORESCENT
LIGHT FIXTURE
WIRE HANGER
J-BOX
CEILING
3/8" MIN.
FLEX CONDUIT
EMT CONDUIT
BEAM CLAMP
LAY-IN FIXTURE MOUNTING DETAIL
T-BAR
SUPPORT
TYP. PHONE/DATA BOX
NTS
18"
FINISH FLOOR
FINISH CEILING
1" CONDUIT
W/PULLSTRING
GROUNDING
BUSHING
ISOLATED
PHONE/DATA
J-BOX
RECEPTACLE
TYPICAL FOR ALL
NTS
RECEPTACLE AND SWITCH LABEL
NOTE: PROVIDE WITH 1/8" BLACK LETTER WITH WHITE LABELS, INDICATING PANEL AND CIRCUIT FEEDING DEVICE.
A-1 A-1
ELECTRICAL RISER DIAGRAM
SCALE: N.T.S
ELECTRICAL RISER DIAGRAM KEYED NOTES
E400
ELECTRICAL
RISER