Overcurrent Protection Relays

download Overcurrent Protection Relays

of 19

Transcript of Overcurrent Protection Relays

  • 7/25/2019 Overcurrent Protection Relays

    1/19

    18/08/2

    EE 3043

    Power Systems III

    Power System ProtectionRelay Coordination

    by

    Dr. Lidula N. Widangama Arachchige

    Department of Electrical EngineeringUniversity of Moratuwa, Sri Lanka

    1

    Outline

    Relay coordination

    Types of Over-current relays

    Discrimination by time, current, time and current

    Inverse characteristics

    Discriminative grading

    Earth fault detection

    Theory and operation of directional over current

    2

  • 7/25/2019 Overcurrent Protection Relays

    2/19

    18/08/2

    Over-current Protection

    Over-current Relays: Most common form of protection

    Use to deal with excessive currents due to faults in the

    power system

    Use the current level to detect faults

    Primarily intended to operate under faults

    Not designed to protect systems against overloads

    3

    Types of Over-current relays

    Instantaneous

    Definite Time

    Inverse Time

    4

  • 7/25/2019 Overcurrent Protection Relays

    3/19

    18/08/2

    Instantaneous Over-current Relay

    Named as Definite current relay as well

    Operate instantaneously when the current reaches a

    predetermined value

    Characteristic curve

    5

    t

    iiPickup

    Coordination of Instantaneous Relays

    Based on the fact:

    Fault current varies with the position of the fault

    Calculate the fault currents at Bus-bars A, B, C and D

    6

    Vs/3

    j 0.485 j 0.24 j 0.04 j 2.12

    CBA D

  • 7/25/2019 Overcurrent Protection Relays

    4/19

    18/08/2

    Coordination of Instantaneous Relays

    Relay furthest away from the source will operate for

    a low current value

    Relay operating currents are progressively increased

    towards the source

    7

    t

    i

    D CB A

    Drawbacks of having only Instantaneous Protection

    Little selectivity at high values of fault currents

    Difficult to distinguish between the fault currents at

    two points when the impedance between the two

    points is small compared to the impedance back to

    the source

    8

  • 7/25/2019 Overcurrent Protection Relays

    5/19

    18/08/2

    Definite-Time Over-current Relay

    Allows adjustment of operating time according to the

    current level

    Relay can be adjusted to trip the breaker nearest to

    the fault in the shortest time

    9

    i

    t

    iPickup

    tSet

    Different Settings of Definite-Time Over-current Relays

    Current Setting (Pickup Setting, Plug Setting, Tap

    Setting)

    To select the value of current at which the relay will start

    responding

    Time-dial Setting

    To obtain the exact timing of the relay operation

    10

  • 7/25/2019 Overcurrent Protection Relays

    6/19

    18/08/2

    Coordination of Definite-Time Over-current Relays

    The time interval between each relay should be long

    enough to ensure the upstream relays do not

    operate before the fault is cleared by the nearest

    circuit breaker to the fault

    11

    t

    i

    D CB A

    Discrimination

    margin

    Drawbacks of Definite-Time Over-current Relays

    Longest fault clearance time occurs for the section

    closest to the source, where the fault current is the

    highest

    12

  • 7/25/2019 Overcurrent Protection Relays

    7/19

    18/08/2

    Inverse-Time Relay

    Relay operating time is inversely proportional to the

    fault current

    Also referred to as Inverse Definite Minimum Time

    (IDMT) relays

    For very high currents, much shorter tripping times

    can be achieved without the risk of protectionselectivity

    13

    Categorization of IDMT Relays

    Inverse

    Very Inverse

    Extremely Inverse

    14

  • 7/25/2019 Overcurrent Protection Relays

    8/19

    18/08/2

    Coordination of IDMT Relays

    For a fault beyond A, Relay at A should operate

    before the Relay at B operates

    Relay characteristic curves can be adjusted by

    selecting two parameters

    Pick-up current or plug setting Time dial or time multiplier setting

    15

    B A

    Pickup Setting

    Referred to as plug setting or tap setting as well

    Defines the pick-up current of the relay

    Plug Multiplier Setting (PMS)

    Fault current is expressed as multiples of the pickup setting

    in the characteristic curves

    16

    currentup-Pick

    ansformercurrent trtheofsecondaryin thecurrentFaultPMS

  • 7/25/2019 Overcurrent Protection Relays

    9/19

    18/08/2

    Time Dial Setting

    Adjust the time delay before the relay operates

    whenever the current reaches a value equal or

    greater than the relay current setting

    17

    Costruction of an Induction Disc Relay

    18

  • 7/25/2019 Overcurrent Protection Relays

    10/19

    18/08/2

    Inverse Current Relay Characteritics

    For a given relay, a set ofcharacteristic curves canbe generated for differenttime multiplier settings(TMS)

    Current axis is given asmultiples of the pick-upcurrent

    In most relays, continuous

    adjustment of TMS ispossible

    19

    Relay Characteristics for Proper Coordination

    20

    B A

  • 7/25/2019 Overcurrent Protection Relays

    11/19

    18/08/2

    Inverse-Current Relay: Standard Characteristics

    IEC Standard

    21

    Inverse-Current Relay: Standard Characteristics

    ANSI/IEEE Standards

    22

  • 7/25/2019 Overcurrent Protection Relays

    12/19

    18/08/2

    Connection of Phase and Earth Fault Over-current Relays

    23

    Setting Over-current Relays

    Over-current relays are normally supplied with both

    Instantaneous element

    Time delay element

    Setting of the relay involves

    Selecting parameters that defines the required time/currentcharacteristics

    The process has to be carried out twice for:

    Phase relaysusing 3 phase short circuit fault currents

    Earth fault relaysusing phase-to-earth fault currents

    24

  • 7/25/2019 Overcurrent Protection Relays

    13/19

    18/08/2

    Coordination of Over-Current Relays

    Selection of the correct characteristics

    Choice of relay current settings

    Choice of grading margins

    Selection of time settings

    25

    Setting Instantaneous Over-Current Units

    Instantaneous units are useful for:

    Reducing the operating time of the relays for severe

    system faults

    Avoiding loss of selectivity in a protection system with

    relays having different characteristics

    26

  • 7/25/2019 Overcurrent Protection Relays

    14/19

    18/08/2

    Criteria for setting Instantaneous Units

    Criteria differ depending on the

    location

    Type of system element being protected

    Criteria is defined separately for

    Lines between substations

    Transformers

    Distribution lines

    27

    Setting Instantaneous Over-current Units

    Lines between substations Iset = 125% of the maximum symmetrical fault current at the next

    downstream substation

    Setting is started from the substation furthest from the sourceand proceeded backward towards the source

    The 25% margin avoids overlapping with the downstreaminstantaneous unit when a dc off set is present

    In HV systems operating at 220kV or above, higher margin

    should be usedHigh X/R ratio result in higher dc offsets

    When the coordination of time delay units is lost due to crossingof characteristics, the instantaneous unit of the downstreamsubstation is set at a lower value to avoid the loss ofcoordination

    28

  • 7/25/2019 Overcurrent Protection Relays

    15/19

    18/08/2

    Setting Instantaneous Over-current Units

    Distribution lines supplying MV/LV transformers

    One of the following criteria can be used

    50% of the maximum short circuit current at the point of CT

    supplying the relay

    Between 6 to 10 times the maximum circuit rating

    29

    Setting Instantaneous Over-current Units

    Instantaneous over-current relay installed at the primary(HV) side of a transformer

    125-150% of the short circuit current at the bus bar on the LVside, referred to the HV sideHigher margin is required to avoid lack of coordination with the high

    inrush currents

    30

  • 7/25/2019 Overcurrent Protection Relays

    16/19

    18/08/2

    Setting Time-delay Over-current Relays

    Definitetime relays and inverse time relays can be

    adjusted by selecting the pick-up setting and time

    dial or time multiplier setting

    31

    Pick-up Setting of Phase Over-current Relays

    Where,

    OLF = overload factor

    CTR = CT ratio

    Recommended OLF values

    Motors = 1.05

    Lines, Transformers, Generators = 1.251.5

    Distribution feeders = up to 2

    32

  • 7/25/2019 Overcurrent Protection Relays

    17/19

    18/08/2

    Pick-up Setting of Earth Over-current Relays

    Where,

    UBF = unbalanced factor

    Recommended UBF values

    Typical = 0.2

    HV lines = 0.1 Distribution feeders = 0.3

    33

    Procedure for calculating the time dial setting

    Step-1: Determine the required operating time t1of

    the relay furthest from the source

    Use the lowest time dial setting

    Consider the pick-up current of the instantaneous relay

    Raise the time dial setting if the following conditions apply

    Necessary to coordinate with devices (eg. Fuses) installed

    downstream

    Load current during re-energizing (cold load pick-up) is high

    34

  • 7/25/2019 Overcurrent Protection Relays

    18/19

    18/08/2

    Procedure for calculating the time dial setting

    Step-2: Determine the operating time of relay at thenext substation towards the source

    t2a=t1+tmargin Use the fault current used to determine the timing t1of

    the previous relay for this calculation

    Step-3: With the same fault current as in theprevious step, knowing t2aand the pick-up currentfor relay 2, calculate the time dial setting for relay 2

    Use the closest available time dial setting whosecharacteristics is above the calculated value

    35

    Procedure for calculating the time dial setting

    Step-4: Determine the operating time t2bof relay 2

    but now using the fault current just before the

    operation of instantaneous unit

    Step-5: Continue the procedure with the sequence

    starting from the second step

    36

  • 7/25/2019 Overcurrent Protection Relays

    19/19

    18/08/2

    Time Discrimination Margin

    Typical values: 0.25 s

    0.4 s

    This value avoids loss of selectivity due to one or more ofthe following: Breaker opening time

    Relay overrun time after the fault has been cleared

    In numerical relays there is no overrun and margin could beselected as low as 0.2s

    Variations in fault levels, deviations from the characteristicscurves and errors in the current transformers

    Single phase faults on star side of a Dy transformer arenot seen on the Delta side. When setting earth fault relays, the lowest available time dial

    setting can be applied to the relays on the Delta side

    37