Overall Heat Transfer Coefficient

A heat exchanger typically involves two flowing fluids separated by a solid

wall. Heat is first transferred from the hot fluid to the wall by convection,

through the wall by conduction, and from the wall to the cold fluid again

by convection. Any radiation effects are usually included in the convection

heat transfer coefficients.

Page 3: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

3

For tubular heat exchangers we must take into account the conduction resistance in

the wall and convection resistances of the fluids at the inner and outer tube surfaces.

oo

io

ii AhkL

DD

AhUA

1

2

)/ln(11

LDA

LDA

oo

ii

ooii AUAUUA

111

Note that:

Overall Heat Transfer Coefficient

The Ai is the area of the inner surface of the wall

that separates the two fluids, and Ao is the area of

the outer surface of the wall. In other words, Ai and

Ao are surface areas of the separating wall wetted

by the inner and the outer fluids, respectively.

When one fluid flows inside a circular tube and the

other outside of it, we have:

where inner tube surface

where outer tube surface

Page 4: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Overall Heat Transfer Coefficient

Then Eq. for the overall heat transfer coefficient simplifies to

where U≈ Ui ≈ Uo.

hi and ho are the individual convection heat transfer coefficients inside and outside the tube.

Page 5: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

5

Overall Heat Transfer Coefficient

Page 6: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Fouling

Page 7: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

7

The performance of heat exchangers usually deteriorates with time as a result of

accumulation of deposits on heat transfer surfaces.

The layer of deposits represents additional resistance to heat transfer and causes the

rate of heat transfer in a heat exchanger to decrease. The net effect of these

accumulations on heat transfer is represented by a Fouling factor, Rf .

The overall heat transfer coefficient can be written:

ooo

ofio

i

if

ii AhA

R

kL

DD

A

R

AhUA

1

2

)/ln(11"

,"

,

Fouling

Page 8: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

8

Some values of fouling factors are given here. More comprehensive tables of fouling factors

are available in handbooks. As you would expect, considerable uncertainty exists in these

values, and they should be used as a guide in the selection and evaluation of heat exchangers to

account for the effects of anticipated fouling on heat transfer.

Fouling

Page 9: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

9

Schematic

Page 10: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

10

Schematic

Re < 2000 – laminar flow

Re > 4000 – Turbulent flow

Page 11: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

11

Re < 2000 – laminar flow

Re > 4000 – Turbulent flow

Page 12: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 13: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

13

Schematic

Page 14: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Multipass and Cross-Flow Heat Exchangers

Use of a Correction Factor

The log mean temperature difference ΔTlm relation developed earlier is limited to parallel-flow and

counter-flow heat exchangers only. In such cases, it is convenient to relate the equivalent

temperature difference to the log mean temperature difference relation for the counter-flow case as:

where F is the correction factor, which depends on the

geometry of the heat exchanger and the inlet and outlet

temperatures of the hot and cold fluid streams. The ΔTlm,CF is

the log mean temperature difference for the case of a counter-

flow heat exchanger with the same inlet and outlet

temperatures and is determined from the above equation, and

by taking:

ΔT1= Th,in – Tc,out and ΔT2= Th,out – Tc,in as shown in the

figure.

Page 15: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Multipass and Cross-Flow Heat Exchangers

where the subscripts 1 and 2 represent the inlet and outlet, respectively.

Note that for a shell-and-tube heat exchanger, T and t represent the shell-

and tube-side temperatures, respectively, as shown in the correction factor

charts.

Page 16: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 17: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

17

Example (3) : Cross Flow Heat exchangers

Cross flow heat exchanger

Page 18: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

18

Page 19: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

19

Example (4)

Investigate the heat-transfer performance of the HEX in example 3 if the oil

flow rate is reduced in half while the steam flow remains same. Assume U

remains constant at 275 W/m2.°C

Page 20: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

20

Q= mCp (t2 – 15) = m Cp (130 – T1) (a)

Q = U A TLMTD F (b)

This why there was a need for another easier method

Effective-Ntu method

Page 21: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Multipass and Cross-Flow Heat Exchangers

Page 22: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Multipass and Cross-Flow Heat Exchangers

FIGURE 23–18

Correction factor F charts for common shell-and-tube and cross-flow heat exchangers

Page 23: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 24: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 25: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 26: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 27: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 28: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 29: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 30: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 31: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 32: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 33: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

THE EFFECTIVENESS–NTU METHOD

Once ΔTlm, the mass flow rates, and the overall heat transfer coefficient (U) are

available, the heat transfer surface area of the heat exchanger can be

determined from

Therefore, the LMTD method is very suitable for determining the size of a heat

exchanger to realize prescribed outlet temperatures when the mass flow rates and

the inlet and outlet temperatures of the hot and cold fluids are specified.

With the LMTD method, the task is to select a heat exchanger that will meet the

prescribed heat transfer requirements. The procedure to be followed by the

selection process is:

1. Select the type of heat exchanger suitable for the application.

2. Determine any unknown inlet or outlet temperature and the heat transfer rate using

an energy balance.

3. Calculate the log mean temperature difference ΔTlm and the correction factor F, if

necessary.

4. Obtain (select or calculate) the value of the overall heat transfer coefficient U.

5. Calculate the heat transfer surface area As .

Page 34: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

NTU ≡ Number of Transfer Units

This method is based on a dimensionless parameter called the heat transfer

effectiveness ε, defined as:

THE EFFECTIVENESS–NTU METHOD

The actual heat transfer rate in a heat exchanger can

be determined from an energy balance on the hot or

cold fluids and can be expressed as:

To determine the maximum possible heat transfer rate

in a heat exchanger, we first recognize that the

maximum temperature difference:

the maximum possible heat transfer rate in a heat exchanger is:

where Cmin is the smaller of Ch =ṁhCPh and CC= mCCpc

Page 35: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

NTU ≡ Number of Transfer Units (ε)

Consider two counter-flow heat exchangers, one in which the cold fluid has the larger ΔT

(smaller m⋅cp) and a second in which the cold fluid has the smaller ΔT (larger m⋅cp):

The effectiveness is the ratio of the energy recovered in a HX to that recoverable in an ideal HX.

Note that the use of the upper case T in the numerator, in contrast to our normal terminology,

does not indicate that the hot fluid temperature change is used here.

Page 36: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

36

Water at the rate of 68 kg/min is heated from 35 to 75 °C by an oil having a specific

heat of 1.9 kJ/kg. °C. The fluids are used in counterflow double pipe heat exchanger,

and the oil enters the exchanger at 110 °C and leaves at 75 °C. The overall heat-

transfer coefficient is 320 W/m2.°C. Calculate the heat exchanger area.

Solution: The total heat transfer is determined from the energy absorbed by the

water.

Since all the fluid temperatures are known, the LMTD can be calculated by using the temperature

scheme.

Example: Double pipe heat exchanger

From the expression:

)/ln( io

iolm

TT

TTT

Page 37: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Heat Exchangers 37

Continue Example (1) : (1:2) Shell & Tube heat exchanger,

knowing that water is in the shell side and oil is in the tube

side, recalculate the needed area ..??

= (75- 110)/(35-110) = 0.467

= (35- 75)/(75-110) = 1.143

Page 38: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 39: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 40: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 41: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

The determination of requires the availability of the inlet temperature of

the hot and cold fluids and their mass flow rates, which are usually specified.

Then, once the effectiveness of the heat exchanger is known, the actual heat

transfer rate can be determined from:

The below Equ developed before in previous lecture for a parallel-flow heat

exchanger:

can be rearranged as:

Also, solving the following Eq. for Th,out

Gives:

Page 42: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Then:

which simplifies to:

We now manipulate the definition of effectiveness to obtain:

Substituting this result into Eq. 23–36 and solving for e gives the following relation for the

effectiveness of a parallel-flow heat exchanger:

Eq. 23–36

Taking either Cc or Ch to be Cmin (both approaches give the same result), the relation above can

be expressed more conveniently as:

Page 43: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Effectiveness relations of the heat exchangers typically involve the

dimensionless group UAs /Cmin. This quantity is called the number of transfer

units NTU and is expressed as:

where U is the overall heat transfer coefficient and As is the heat transfer surface area

of the heat exchanger.

NTU is a measure of the heat transfer surface area As . Thus, the larger the NTU,

the larger the heat exchanger.

In heat exchanger analysis, it is also convenient to define another dimensionless

quantity called the capacity ratio c as:

Page 44: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Effectiveness relations have been developed for a large number of heat exchangers,

and the results are given in the Table below. The effectivenesses of some common

types of heat exchangers are also plotted in the becoming figures

Page 46: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 48: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Some observations from the effectiveness relations and charts already given:

1. The value of the effectiveness ranges from 0 to 1. It increases rapidly with NTU for

small values (up to about NTU 1.5) but rather slowly for larger values. Therefore, the

use of a heat exchanger with a large NTU (usually larger than 3) and thus a large size

cannot be justified economically, since a large increase in NTU in this case

corresponds to a small increase in effectiveness. Thus, a heat exchanger with a very

high effectiveness may be highly desirable from a heat transfer point of view but

rather undesirable from an economical point of view.

2. For a given NTU and capacity ratio c = Cmin /Cmax, the

counter-flow heat exchanger has the highest effectiveness,

followed closely by the cross-flow heat exchangers with

both fluids unmixed. As you might expect, the lowest

effectiveness values are encountered in parallel-flow heat

exchangers (Fig. 23–27).

Page 49: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

3. The effectiveness of a heat exchanger is independent of the capacity ratio c for

NTU values of less than about 0.3.

4. The value of the capacity ratio c ranges between 0 and 1. For a given NTU, the

effectiveness becomes a maximum for c = 0 and a minimum for c =1.

The case c = Cmin/Cmax→ 0 corresponds to Cmax→∞, which is realized during a phase-change process

in a condenser or boiler. condenser or boiler. All effectiveness relations in this case reduce to:

Page 50: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

it can also be determined from the effectiveness–NTU method by first

evaluating the effectiveness ε from its definition

and then the NTU from the appropriate NTU relation mentioned in the

following Table.

Page 51: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Example

Find:

(a) minimum flow rate required for the hot process water.

(b) required overall heat transfer coefficient and whether it is possible to accomplish this

heating.

(c) for CF arrangements minimum process water flow required and the effectiveness?

A thin-walled concentric tube heat exchanger of 0.19m length is to be used to

heat deionized water from 40 to 60°C at a flow rate of 5 kg/s. the deionized

water flows through the inner tube of 30mm diameter while hot process water at

95°C flows in the annulus formed with the outer tube of 60 mm diameter. The

thermo physical properties of the fluids are:

Page 52: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Assumptions:

(1) Negligible heat loss to surroundings.

(2) Negligible kinetic and potential energy

changes.

Page 53: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 54: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Example

Schematic

Assumptions: (1) Negligible heat loss to surroundings and kinetic and potential

energy changes, (2) Constant properties.

An automobile radiator may be viewed as a cross-flow heat exchanger with both

fluids unmixed. Water, which has flow rate of 0.05kg/s, enters the radiator at 400K

and is to leave at 330 K. The water is cooled by air which enters at 0.75kg/s and

300K. If the overall heat transfer coefficient is 200W/m2 .K, what is the required

heat transfer surface area?

Known: flow rate and inlet temperature for automobile radiator. Overall heat

transfer coefficient. Find: Area required to achieve a prescribed outlet temperature.

Page 55: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Analysis: The required heat transfer rate is

Using the ε-NTU method,

Page 56: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Water at 225 kg/h is to be heated from 35 to 95 ͦ C by means of a concentric tube heat

exchanger. Oil at 225kg/h and 210 ͦ C, with a specific heat of 2095 J/kg.K, is to be used as the

hot fluid. If the overall heat transfer coefficient based on the outer diameter of the inner tube

is 550 W/m2.K, determine the length of the exchanger if the outer diameters is 100mm.

Known: Concentric tube heat exchanger. Find: Length of the exchanger

Example

Schematic

Assumptions: (1) Negligible heat loss to surroundings, (2) Negligible kinetic and potential

energy changes, (3) Constant properties.

The heat rate, q, can be evaluated from an energy balance on the cold fluid:

Page 57: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 58: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Consider a very long, concentric tube heat exchanger having hot and cold water inlet

temperatures of 85 and 15 °C. The flow rate of the hot water is twice that of the cold water.

Assuming equivalent hot and cold water specifies heats; determine the hot water outlet

temperature for the following modes of operation (a) Counter flow, (b) Parallel flow.

Known: A very long, concentric tube heat exchanger having hot and cold water inlet

temperatures of 85 and 15°C, respectively: flow rate of the hot water is twice that of the cold

water. Find: outlet temperatures for counter flow and parallel flow operations.

Example

Schematic

Assumptions:

(1) equivalent hot and cold water specific heats,

(2) Negligible Kinetic and potential energy changes,

(3) No heat loss to surroundings.

Page 59: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Operating in the counter flow mode is:

Substituting numerical values:

Page 60: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 61: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 62: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 63: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 64: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 65: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 66: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 67: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 68: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Page 69: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer
Tables.pptx
Page 70: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

ṁhCph

Page 71: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Capacity Ratio, CR

The final non-dimensional ratio needed here is the capacity ratio,

defined as follows:

Page 72: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

SELECTION OF HEAT EXCHANGERS

Heat exchangers are complicated devices, and the results obtained with the simplified

approaches presented above should be used with care.

The proper selection depends on several factors:

1. Heat Transfer Rate:

A heat exchanger should be capable of transferring heat at the specified rate in order

to achieve the desired temperature change of the fluid at the specified mass flow rate.

2. Cost:

Budgetary limitations usually play an important role in the selection of heat exchangers,

except for some specialized cases where “money is no object.”

3. Pumping Power:

In a heat exchanger, both fluids are usually forced to flow by pumps or fans that

consume electrical power. The annual cost of electricity associated with the operation

of the pumps and fans can be determined from:

Page 73: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

4. Size and Weight:

Normally, the smaller and the lighter the heat exchanger, the better it is.

5. Type:

The type of heat exchanger to be selected depends primarily on the type of fluids

involved, the size and weight limitations, and the presence of any phase change

processes.

6. Materials:

The materials used in the construction of the heat exchanger may be an important

consideration in the selection of heat exchangers.

For example, the thermal and structural stress effects need not be considered at

pressures below 15 atm or temperatures below 150°C.

SELECTION OF HEAT EXCHANGERS

Page 74: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 75: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic

Page 76: Overall Heat Transfer Coefficient - جامعة نزوى · > 4000 – Turbulent ... The fluids are used in counterflow double pipe heat exchanger, ... required overall heat transfer

Schematic