OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity,...

82
OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION “Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs” STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 1 of 3 APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP) OFFICE USE ONLY APPLICATION #: OSP – 0297 – 10 OSHPD Special Seismic Certification Preapproval (OSP) Type: New Renewal Manufacturer Information Manufacturer: Daikin North America, LLC Manufacturer’s Technical Representative: Madhav Kashinath Mailing Address: Daikin Texas Technology Park, 19001 Kermier Road, Waller, TX, 77484 Telephone: (713) 346-6650 Email: [email protected] Product Information Product Name: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S Product Type: Split Air Conditioning Units Product Model Number: Varies, see attachment. (List all unique product identification numbers and/or part numbers) General Description: Indoor and outdoor heating and cooling units with steel enclosures. . Mounting Description: Rigid base mounted, rigid wall mounted, and ceiling suspended. Applicant Information Applicant Company Name: Structural Integrity Associates, Inc. dba TRU Compliance Contact Person: Andrew M. Coughlin, SE Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138 Telephone: 844-878-0200 Email: [email protected] I hereby agree to reimburse the Office of Statewide Health Planning and Development review fees in accordance with the California Administrative Code, 2016. Signature of Applicant: Date: 01/22/2018 Title: Director, TRU Compliance Company Name: Structural Integrity Associates, Inc. dba TRU Compliance 03/14/2018 OSP-0297-10 Page 1 of 82

Transcript of OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity,...

Page 1: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION

“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”

STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 1 of 3

APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

OFFICE USE ONLY

APPLICATION #: OSP – 0297 – 10

OSHPD Special Seismic Certification Preapproval (OSP)

Type: New Renewal

Manufacturer Information

Manufacturer: Daikin North America, LLC

Manufacturer’s Technical Representative: Madhav Kashinath

Mailing Address: Daikin Texas Technology Park, 19001 Kermier Road, Waller, TX, 77484

Telephone: (713) 346-6650 Email: [email protected]

Product Information

Product Name: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S

Product Type: Split Air Conditioning Units

Product Model Number: Varies, see attachment. (List all unique product identification numbers and/or part numbers)

General Description: Indoor and outdoor heating and cooling units with steel enclosures.

.

Mounting Description: Rigid base mounted, rigid wall mounted, and ceiling suspended.

Applicant Information

Applicant Company Name: Structural Integrity Associates, Inc. dba TRU Compliance

Contact Person: Andrew M. Coughlin, SE

Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138

Telephone: 844-878-0200 Email: [email protected] I hereby agree to reimburse the Office of Statewide Health Planning and Development review fees in accordance with the California Administrative Code, 2016. Signature of Applicant:

Date: 01/22/2018 Title: Director, TRU Compliance Company Name:

Structural Integrity Associates, Inc. dba TRU Compliance

03/14/2018

OSP-0297-10

Page 1 of 82

Page 2: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION

“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”

California Licensed Structural Engineer Responsible for the Engineering and Test Report(s)

Company Name: Structural Integrity Associates, Inc. dba TRU Compliance

Name: Andrew M. Coughlin California License Number: S6082

Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138

Telephone: 844-878-0200 Email: [email protected]

Supports and Attachments Preapproval

Supports and attachments are preapproved under OPM- (Separate application for OSHPD Preapproval of Manufacturer’s Certification (OPM) of Supports and attachments is required)

Supports and attachments are not preapproved

Certification Method

Testing in accordance with: ICC-ES AC156

Other (Please Specify):

Testing Laboratory

Company Name: Environmental Testing Laboratory

Contact Name: Paul E. Little

Mailing Address: 11034 Indian Trail, Dallas, TX 75229

Telephone: 972.247.9657 Email: [email protected]

Company Name: Clark Testing

Contact Name: Russ Matich

Mailing Address: 1801 Route 51, Jefferson Hills, PA 15025

Telephone: 412-387-1025 Email: [email protected]

Company Name: QualTech NP by Curtiss-Wright

Contact Name: Jason VonNida

Mailing Address: 4600 East Tech Drive, Cincinnati, OH 45245

Telephone: 513-201-2139 Email: [email protected]

STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 2 of 3

03/14/2018

OSP-0297-10

Page 2 of 82

Page 3: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION

“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”

STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 12/16/15) Page 3 of 3

Seismic Parameters

Design in accordance with ASCE 7-10 Chapter 13: Yes No

Design Basis of Equipment or Components (Fp/Wp) = 1.50 (SDS = 2.00, z/h = 1); 1.13 (SDS = 2.50, z/h = 0)

SDS (Design spectral response acceleration at short period, g) = 2.00 (z/h = 1); 2.50 (z/h = 0)

ap (In-structure equipment or component amplification factor) = 2.5

Rp (Equipment or component response modification factor) = 6.0

Ω0 (System overstrength factor) = 2.0

Ip (Importance factor) = 1.5

z/h (Height factor ratio) = 1 (SDS = 2.00); 0 (SDS = 2.50)

Equipment or Component Natural Frequencies (Hz) = See Attachment

Overall dimensions and weight (or range thereof) = See Attachment

Equipment or Components @ grade designed in accordance with ASCE 7-10 Chapter 15: Yes No

Design Basis of Equipment or Components (V/W) =

SDS (Design spectral response acceleration at short period, g) =

SD1 (Design spectral response acceleration at 1 second period, g) =

R (Response modification coefficient ) =

Ω0 (System overstrength factor) =

Cd (Deflection amplification factor) =

Ip (Importance factor) = 1.5

Height to Center of Gravity above base =

Equipment or Component Natural Frequencies (Hz) =

Overall dimensions and weight (or range thereof) =

Tank(s) designed in accordance with ASME BPVC, 2015: Yes No

List of Attachments Supporting Special Seismic Certification

Test Report(s) Drawings Calculations Manufacturer’s Catalog

Other(s) (Please Specify): Attachment A

OSHPD Approval (For Office Use Only) – Approval Expires on December 31, 2022

Signature: Date: March 14, 2018

Print Name: Timothy J. Piland Title: SSE

Special Seismic Certification Valid Up to : SDS (g) = See Above z/h = See Above

Condition of Approval (if applicable):

03/14/2018

OSP-0297-10

Page 3 of 82

Page 4: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

11.3 30.1 21.6 75 1

11.2 31.3 22.4 99 Interp.

11.3 30.1 21.6 75 Interp.

11.2 31.3 22.4 99 Interp.

11.8 32.5 28.9 104 Interp.

11.2 31.3 22.4 99 Interp.

11.8 32.5 28.9 104 Interp.

12.6 35.4 30.3 159 2

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 3

12.6 35.4 30.3 150 Extrap.

12.6 35.4 30.3 150 Extrap.

12.6 35.4 30.3 150 Extrap.

12.6 35.4 30.3 150 Extrap.

12.6 35.4 30.3 150 Extrap.

12.6 35.4 30.3 150 4

RZR24_VJU1

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

RXS30_VJU1,2

RKS36_VJU1,2

RXS36_VJU1,2

RZR18_VJU1

RZQ18_VJU1

RXS09_VJU1

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

RXS24_VJU1

RXG15_VJU1

Outdoor Heat Pump

(Split System,

Quaternity, SkyAir)

9,000 to 36,000

BTU/hr; Qualified

design categories: T

Dimension (in)Notes

Weight

(lb)

1.5

Outdoor Heat Pump

(SkyAir)

18,000 to 30,000

BTU/hr;

Qualified design

categories: P

Model Line

RZQ30_VJU1

Model

RXG09_VJU1

RZQ24_VJU1

RZR30_VJU1

1Requires seismic enhancements: (4) ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.2Requires mounting w/ (4) 1/16”x1-1/2” angled aluminum straps approximately 30˚relative to vertical surface of the unit with (2)

#10 SMS to top of unit & 1/4ӯ bolt to floor

RKS30_VJU1,2

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

RXS12_VJU1

RXG12_VJU1

I P = Seismic Certification Limits:Building Code: CBC 2016

RXS15_VJU1

RXS18_VJU1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 4 of 82

Page 5: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

12.6 35.4 52.9 283 Interp.

12.6 35.4 52.9 283 Interp.

12.6 35.4 52.9 283 Interp.

12.6 35.4 52.9 283 Interp.

12.6 35.4 52.9 283 Interp.

12.6 35.4 52.9 283 5

30.1 36.7 66.1 420 Extrap.

30.1 36.7 66.1 433 Extrap.

30.1 48.9 66.1 620 8

30.1 48.9 66.1 633 Interp.

30.1 48.9 66.1 620 Interp.

30.1 48.9 66.1 633 Interp.

30.1 51.2 66.1 747 Interp.

30.1 73.3 66.1 866 Interp.

30.1 85.5 66.1 1040 Interp.

30.1 85.5 66.1 1066 Interp.

30.1 85.5 66.1 1040 Interp.

30.1 85.5 66.1 1066 Interp.

30.1 97.8 66.1 1240 Interp.

Outdoor Heat Pumps

(VRV III)

72,000 to 360,000

BTU/hr (cooling

capacity);

Qualified design

categories: PA, PB, PC

1Requires seismic enhancements: (4) ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.2Requires mounting w/ (4) 1/16”x 2” angled aluminum straps approximately 30˚relative to vertical surface of the unit with (2) #10

SMS to top of unit & 1/4ӯ bolt to floor.3Requires seismic enhancements: #10 SMS top cover to frame & (10) #10 SMS compressor cover to frame (RXYMQ)

RXYQ192_YD

RXYQ168_YD

RXYQ192_TJ

Outdoor Heat Pump

(SkyAir, VRV III-S)

36,000 to 47,500

BTU/hr;

Qualified design

categories: P

RZQ36_VJU1,2

RZQ42_VJU1,2

RXYQ96_YD

RXYQ144_TJ

RXYQ144_YD

RXYQ168_TJ

RXYQ72 + RXYQ96

RXYQ72_TJ

RXYQ120_TJ

RXYQ120_YD

RXYQ216_TJ

RXYQ72 + RXYQ120

RXYQ72 + RXYQ120

RZR42_VJU1,2

RXYMQ48_VJU2,3

RXYQ96 + RXYQ120

RXYQ72_YD

2 x RXYQ72

RXYQ96_TJ

RZR36_VJU1,2

RXYMQ36_VJU2,3

RXYQ72 + RXYQ96

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 5 of 82

Page 6: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

30.1 97.75 66.1 1266 Interp.

30.1 97.8 66.1 1240 Interp.

30.1 97.8 66.1 1266 Interp.

30.1 134.4 66.1 1660 Interp.

30.1 134.4 66.1 1699 Interp.

30.1 134.4 66.1 1660 Interp.

30.1 134.4 66.1 1699 Interp.

30.1 134.4 66.1 1660 Interp.

30.1 134.4 66.1 1699 Interp.

30.1 146.6 66.1 1860 Interp.

30.1 146.6 66.1 1899 Interp.

30.1 146.6 66.1 1860 Interp.

30.1 146.6 66.1 1899 Interp.

30.1 51.2 66.1 730 Extrap.

30.1 51.2 66.1 732 Extrap.

30.1 36.7 66.1 450 6

30.1 36.7 66.1 463 Interp.

30.1 51.2 66.1 730 Interp.

30.1 51.2 66.1 732 Interp.

30.1 36.7 66.1 560 Interp.

30.1 36.7 66.1 573 Interp.

30.1 51.2 66.1 730 Interp.

30.1 51.2 66.1 732 9

Outdoor Heat Pumps

(VRV III)

72,000 to 360,000

BTU/hr (cooling

capacity);

Qualified design

categories: PA, PB, PC

RXYQ360_TJ

RXYQ72 + RXYQ96 + RXYQ120

RXYQ288_YD RXYQ72 + RXYQ96 + RXYQ120

RXYQ312_TJ RXYQ72 + 2 x RXYQ120

2 x RXYQ120

RXYQ240_YD 2 x RXYQ120

RXYQ312_YD RXYQ72 + 2 x RXYQ120

RXYQ336_TJ RXYQ96 + 2 x RXYQ120

RXYQ336_YD RXYQ96 + 2 x RXYQ120

RXYQ360_YD

3 x RXYQ120

RXYQ216_YD RXYQ96 + RXYQ120

REMQ96_YD

REYQ120_TJ

REYQ120_YD

Outdoor Heat

Recovery Units (VRV

III)

72,000 to 336,000

BTU/hr (cooling

capacity);

Qualified design

categories: PA, PB, PC

3 x RXYQ120

REYQ72_TJ

REYQ72_YD

REMQ72_TJ

REMQ72_YD

REMQ96_TJ

REYQ96_TJ

REYQ96_YD

RXYQ264_YD RXYQ72 + 2 x RXYQ96

RXYQ288_TJ

RXYQ264_TJ RXYQ72 + 2 x RXYQ96

RXYQ240_TJ

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 6 of 82

Page 7: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

30.1 36.7 66.1 560 Interp.

30.1 36.7 66.1 573 Interp.

30.1 51.2 66.1 747 10

30.1 73.4 66.1 926 Interp.

30.1 73.4 66.1 1010 Interp.

30.1 73.4 66.1 1036 Interp.

30.1 73.4 66.1 1120 Interp.

30.1 73.4 66.1 1146 Interp.

30.1 73.4 66.1 1120 Interp.

30.1 73.4 66.1 1146 Interp.

30.1 73.4 66.1 1120 Interp.

30.1 73.4 66.1 1146 Interp.

30.1 110.1 66.1 1570 Interp.

30.1 110.1 66.1 1609 Interp.

30.1 110.1 66.1 1570 Interp.

30.1 110.1 66.1 1609 Interp.

30.1 110.1 66.1 1680 Interp.

30.1 110.1 66.1 1719 Interp.

30.1 110.1 66.1 1680 Interp.

30.1 110.1 66.1 1719 Interp.

REYQ312_YD 2 x REMQ96 + REMQ120

REYQ336_YD REMQ96 + 2 x REMQ120

REYQ144_TJ

REYQ144_YD

REYQ240_YD 2 x REMQ120

REYQ264_TJ REMQ72 + 2 x REMQ96

REYQ264_YD REMQ72 + 2 x REMQ96

REMQ96 + REMQ120

2 x REMQ120

REYQ192_YDOutdoor Heat

Recovery Units (VRV

III)

72,000 to 336,000

BTU/hr (cooling

capacity);

Qualified design

categories: PA, PB, PC

REYQ288_TJ REMQ72 + REMQ96 + REMQ120

2 x REMQ72

REYQ168_TJ REMQ72 + REMQ96

REYQ168_YD REMQ72 + REMQ96

REYQ336_TJ REMQ96 + 2 x REMQ120

2 x REMQ96

REMQ96 + REMQ120REYQ216_TJ

REYQ288_YD

REYQ312_TJ 2 x REMQ96 + REMQ120

2 x REMQ96REYQ192_TJ

REMQ72 + REMQ96 + REMQ120

REYQ216_YD

REYQ240_TJ

REMQ120_TJ

REMQ120_YD

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 7 of 82

Page 8: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

30.2 36.7 66.7 435 27

30.2 36.7 66.7 451 Interp.

30.2 48.9 66.7 525 Interp.

30.2 48.9 66.7 553 Interp.

30.2 48.9 66.7 528 Interp.

30.2 48.9 66.7 556 Interp.

30.2 48.9 66.7 695 Interp.

30.2 48.9 66.7 709 Interp.

30.2 48.9 66.7 695 Interp.

30.2 48.9 66.7 709 28

30.2 85.6 66.7 963 Interp.

30.2 85.6 66.7 1007 Interp.

30.2 97.8 66.7 1053 Interp.

30.2 60.4 66.7 133 Interp.

30.2 97.8 66.7 1056 Interp.

30.2 97.8 66.7 1112 Interp.

30.2 97.8 66.7 1223 Interp.

30.2 97.8 66.7 1265 Interp.

30.2 97.8 66.7 1390 Interp.

30.2 97.8 66.7 1418 Interp.

30.2 97.8 66.7 1390 Interp.

30.2 97.8 66.7 1418 Interp.

RXYQ312_TJ1

RXYQ312_YD1

Outdoor Heat Pump

(VRV IV) 72,000 to

408,000 BTU/hr

(cooling capacity);

Qualified design

categories: T

RXYQ144 + RXYQ120

2 x RXYQ120

2 x RXYQ120

2 x RXYQ144

2 x RXYQ144

RXYQ288_TJ1

RXYQ120_TJ1

RXYQ120_YD1

RXYQ144_TJ1

RXYQ144_YD1

RXYQ96_YD1

RXYQ144 + RXYQ120

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

RXYQ216_YD1

RXYQ240_TJ1

RXYQ240_YD1

RXYQ168 + RXYQ144

RXYQ72_TJ

RXYQ72_YD

RXYQ168_TJ1

RXYQ168_YD1

RXYQ96_TJ1

RXYQ264_YD1

RXYQ192_TJ1

RXYQ168 + RXYQ144

RXYQ120 + RXYQ72

RXYQ120 + RXYQ72

RXYQ264_TJ1

RXYQ192_YD1

RXYQ216_TJ1

RXYQ288_YD1

RXYQ120 + RXYQ96

RXYQ120 + RXYQ96

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 8 of 82

Page 9: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

30.2 97.8 67 1390 Interp.

30.2 97.8 67 1418 Interp.

30.2 146.6 67 1584 Interp.

30.2 146.6 67 1668 Interp.

30.2 146.6 67 1748 Interp.

30.2 146.6 67 1818 Interp.

30.2 146.6 67 1915 Interp.

30.2 146.6 67 1971 Interp.

30.2 36.7 66.7 507 29

30.2 36.7 66.7 527 Interp.

30.2 48.9 66.7 703 Interp.

30.2 48.9 66.7 717 Interp.

30.2 48.9 66.7 703 Interp.

30.2 48.9 66.7 717 Interp.

30.2 48.9 66.7 780 Interp.

30.2 48.9 66.7 794 Interp.

30.2 48.9 66.7 780 Interp.

30.2 48.9 66.7 794 30

30.2 85.6 66.7 1210 Interp.

30.2 85.6 66.7 1244 Interp.

30.2 97.8 66.7 1406 Interp.

30.2 97.8 66.7 1434 Interp.

REYQ120 + REYQ72

REYQ168_TJ1

REYQ168_YD1

REYQ192_TJ1

REYQ72_YD

REYQ144_YD1

RXYQ384_TJ1

2 x RXYQ168RXYQ336_TJ1

RXYQ336_YD1

RXYQ408_YD1

REYQ72_TJ

REYQ96_YD1

REYQ120_TJ1

REYQ120_YD1

REYQ144_TJ1

REYQ216_YD1

REYQ192_YD1

REYQ216_TJ1

Outdoor Heat

Recovery Units (VRV

IV) 72,000 to 456,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

REYQ120 + REYQ96

REYQ96_TJ1

RXYQ360_TJ1

RXYQ360_YD1

RXYQ384_YD1

RXYQ408_TJ1

REYQ120 + REYQ72

2 x RXYQ168

RXYQ168 + RXYQ120 + RXYQ96

RXYQ168 + RXYQ120 + RXYQ96

RXYQ168 + RXYQ144 + RXYQ96

RXYQ168 + RXYQ144 + RXYQ96

3 x RXYQ120

3 x RXYQ120

Outdoor Heat Pump

(VRV IV) 72,000 to

408,000 BTU/hr

(cooling capacity);

Qualified design

categories: T

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

REYQ120 + REYQ96

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 9 of 82

Page 10: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

30.2 97.8 66.7 1483 Interp.

30.2 97.8 66.7 1511 Interp.

30.2 97.8 66.7 1483 Interp.

30.2 97.8 66.7 1511 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 149.7 66.7 2109 Interp.

30.2 149.7 66.7 2151 Interp.

30.2 149.7 66.7 2186 Interp.

30.2 149.7 66.7 2228 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2305 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2382 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2382 Interp.

REYQ432_TJ1

REYQ240_YD1

3 x REYQ144

3 x REYQ144

REYQ288_TJ1

REYQ288_YD1

REYQ312_TJ1

REYQ312_YD1

REYQ336_TJ1

REYQ336_YD1

REYQ144 + REYQ96

REYQ384_TJ1

REYQ384_YD1

REYQ408_TJ1

REYQ408_YD1

REYQ456_YD1

REYQ432_YD1

REYQ456_TJ1

REYQ360_TJ1

REYQ360_YD1

REYQ240_TJ1

REYQ264_TJ1

REYQ264_YD1

2 x REYQ144

REYQ144 + REYQ120

REYQ144 + REYQ120

REYQ168 + 2 x REYQ144

REYQ168 + 2 x REYQ144

3 x REYQ120

3 x REYQ120

REYQ168 + REYQ120 + REYQ96

REYQ168 + REYQ120 + REYQ96

REYQ168 + REYQ144 + REYQ96

2 x REYQ168

REYQ144 + REYQ96

REYQ168 + REYQ144 + REYQ96

2 x REYQ144

REYQ168 + REYQ144

REYQ168 + REYQ144

2 x REYQ168

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

Outdoor Heat

Recovery Units (VRV

IV) 72,000 to 456,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 10 of 82

Page 11: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

12.6 37 39 172 37

12.6 37 39 176 Interp.

12.6 35.4 52.9 423 38

22.2 30.1 38.6 423 39

22.2 30.1 38.6 423 Interp.

22.2 30.1 38.6 423 Interp.

3Requires seismic enhancements: (4)ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.

RWEQ96_TJU/TJU-HROutdoor Water Cooled

Heat Recovery Unit

(VRV-W) 208/230V,

144,000 BTU/hr

(cooling capacity);

Qualified design

categories: T

RWEQ120_TJU/TJU-HR2

RXTQ48_VJU1,3

RXTQ60_VJU1,3

2Units are identical to UUT except for software.

RXTQ36_VJU1,3

Outdoor Heat Pump

(VRV-IV S) 34, 200 to

57,000 BTU/hr;

Qualified design

categories: T

RWEQ144_TJU/TJU-HR2

1Required seismic enhancements: Two (2) stainless steel straps ( ¾” wide and 0.02” thick), running perpendicular to the units

width, approximately 30˚relative to vertical surface of the unit ,attached with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish

Screws. Two (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws used to attach each end of the strap to the mounting fixture.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 11 of 82

Page 12: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 12 of 82

Page 13: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

Nomenclature: SkyAir, VRV III-S Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 13 of 82

Page 14: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

TABLE 1Daikin North America, LLC

Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

Rigid base mounted.

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

UUT

Mounting Configuration:

Model Line:

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Manufacturer:

Dimension (in)Notes

Weight

(lb)

1.5

Model Line Model

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

I P = Seismic Certification Limits:Building Code: CBC 2016

Nomenclature: VRV III-S, VRV III, VRV IV Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 14 of 82

Page 15: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

9.3 31.3 11.4 26.0 Extrap.

14.4 34.3 10.8 20.0 Extrap.

8.2 35.0 12.0 31.0 11

9.3 31.3 11.4 26.0 12

14.4 34.3 10.8 22.0 Interp.

8.2 35.0 12.0 31.0 Interp.

9.3 31.3 11.4 26.0 Interp.

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 Interp.

8.2 35.0 12.0 31.0 Interp.

9.0 41.4 11.4 31.0 14

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 Interp.

9.3 41.4 11.4 31.0 Interp.

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 13

9.0 41.4 11.4 31.0 Interp.

9.3 41.4 11.4 31.0 Interp.

9.4 47.3 13.4 38.0 Interp.

9.4 47.3 13.4 38.0 15

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 2Model Line: Indoor Wall Mounted Fan Coil (Split System, Quaternity, SkyAir)

FTXN15_VJU

FTXS15_VJU

FTXG15_VJU

FTXS12_VJU

FTXG12_VJU

FXAQ12_VJU

UUT

FXAQ07_VJU

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet.

Certified Options Summary:

Mounting Configuration:

Rigid wall mounted

Indoor Fan Coil (Split

System, Quaternity,

SkyAir)

7,500 to 36,000

BTU/hr;

Qualified design

categories: H (FTXG), P

(FXAQ), L (FTXS), P

(FAQ)

FTXS30_VJU

FTXS36_VJU

FTXS24_VJU

FAQ24_VJU

FXAQ24_VJU

FAQ18_VJU

FTXN18_VJU

FTXS18_VJU

FXAQ18_VJU

FTXN24_VJU

FTXS09_VJU

FTXG09_VJU

FXAQ09_VJU

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 15 of 82

Page 16: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 2Model Line: Indoor Wall Mounted Fan Coil (Split System, Quaternity, SkyAir)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet.

Certified Options Summary:

Mounting Configuration:

Rigid wall mounted

Nomenclature: Split System, Quaternity, SkyAir Indoor Units

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 16 of 82

Page 17: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 2Model Line: Indoor Wall Mounted Fan Coil (Split System, Quaternity, SkyAir)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet.

Certified Options Summary:

Mounting Configuration:

Rigid wall mounted

Nomenclature: SkyAir Indoor Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 17 of 82

Page 18: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

26.8 37.8 7.7 55 16

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 55.1 7.7 80 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 17

37.4 37.4 7.8 58 33

37.4 37.4 7.8 58 Interp.

37.4 37.4 7.8 60 Interp.

37.4 37.4 7.8 60 42

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

FXHQ24_VJU

FHQ30_VJU

FHQ36_VJU

Indoor Fan Coil

(SkyAir, VRV III-S, VRV

III)

12,000 to 40,500

BTU/hr;

Qualified design

categories: M

FHQ18_VJU

FHQ24_VJU

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

FXHQ36_VJU

FXHQ12_VJU

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

FXUQ36_VJU1

FXUQ24_VJU1

FHQ42_VJU

Indoor Fan Coil (VRV IV)

18,000 to 36,000 BTU/hr;

Qualified design

categories: P

1Requires seismic enhancements: Heavy duty square washers (1.6" x 1.3 x 0.2”) were used at top and bottow of mounting

bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover attachment to unit, were crimped closed to secure

cover to unit.

FXUQ30_VJU1

FXUQ18_VJU1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 18 of 82

Page 19: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

27.6 21.7 11.8 55 Extrap.

27.6 21.7 11.8 55 Extrap.

27.6 27.6 11.8 55 20

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 21

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 Interp.

27.6 55.1 11.8 80 Interp.

27.6 55.1 11.8 102 Interp.

27.6 55.1 11.8 101 Interp.

27.6 55.1 11.8 102 Interp.

27.6 55.1 11.8 101 22

43.3 29.3 18.5 190 23

43.3 54.4 18.5 271 Interp.

43.3 54.4 18.1 302 Interp.

43.3 54.4 18.5 271 Interp.

43.3 54.4 18.1 302 24

FXMQ18_VJU1

2Requires seismic enhancements: One (1) #10 SMS at each mounting ear (4 total)

1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

FBQ24_VJU1

FXMQ72MFVJU2

FXMQ07_VJU1

Indoor Fan Coil (VRV III-

S, VRV III)

7,500 to 96,000

BTU/hr;

Qualified design

categories: P

FXMQ09_VJU1

FXMQ12_VJU1

FXMQ72MVJU2

FXMQ96MFVJU2

FXMQ96MVJU2

FXMQ48_VJU1

FXMQ48MFVJU2

FBQ36_VJU1

FXMQ36_VJU1

FBQ42_VJU1

FXMQ24_VJU1

FBQ30_VJU1

FXMQ30_VJU1

FBQ18_VJU1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 19 of 82

Page 20: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

33.1 33.1 9.7 43 35

33.1 33.1 9.7 43 18

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 58 Interp.

33.1 33.1 11.3 58 Interp.

33.1 33.1 11.3 55 Interp.

33.1 33.1 11.3 55 Interp.

33.1 33.1 11.3 58 19

FCQ18_VJU1

FXFQ18_VJU2

FCQ24_VJU1

2Requires seismic enhancements: Eight (8) #10 SMS in each mounting ear. Four (4) cable tie (shipped with unit) chains, each with

two links, between decoration panel cover latches and through mounting ear. Two (2) strips of heavy duty Velcro® tape 1” x 2” at

each corner cover (eight total).

1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

FXFQ24_VJU2

FXFQ48_VJU2

FXFQ36_VJU2

FCQ42_VJU1

FXFQ09_VJU2

FXFQ12_VJU2

Indoor Fan Coil

(SkyAir, VRV III-S, VRV

III, VRV IV)

9,500 to 48,000

BTU/hr;

Qualified design

categories: P, T

FXFQ07_VJU2

FCQ36_VJU1

FCQ30_VJU2

FXFQ30_VJU2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 20 of 82

Page 21: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

Nomenclature: SkyAir Indoor Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 21 of 82

Page 22: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

Nomenclature: VRV III, VRV IV Indoor Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 22 of 82

Page 23: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

12.2 15.3 8.1 26 25

12.2 15.3 8.1 26 Interp.

12.2 15.3 8.1 33 Interp.

25.0 41.5 8.3 132 Interp.

25.0 62.1 8.3 196 26

18.9 14.6 11.8 49 31

18.9 22.8 11.8 68 Interp.

18.9 22.8 11.8 73 Interp.

18.9 32.3 11.8 101 Interp.

18.9 32.3 11.8 106 32

1Seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2) machine screws through each mounting ear.

Indoor Single Port

Branch Selector (VRV III)

36 to 96 capacity index;

Qualified design

categories: P, T

Indoor Multi Port Branch

Selector (VRV IV)

144 to 290 total capacity

index;

Qualified design

categories: T

BS8Q54_VJ1

BS10Q54_VJ1

BS12Q54_VJ1

BSV6Q36_VJU

BS4Q54_VJ1

BS6Q54_VJ1

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended.

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Indoor Branch Selectors (VRV III, VRV IV)

UUT

BSVQ36_VJU

BSVQ60_VJU

BSVQ96_VJU

BSV4Q36_VJU

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 23 of 82

Page 24: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended.

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Indoor Branch Selectors (VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Nomenclature: VRV III Indoor Branch Selector Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 24 of 82

Page 25: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended.

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Indoor Branch Selectors (VRV III, VRV IV)

UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Nomenclature: VRV IV Indoor Branch Selector Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 25 of 82

Page 26: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

21 17.5 45 115 40

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 140 Interp.

21 21 54.43 150 Interp.

21 21 54.43 150 Interp.

22 24.5 58 167 Interp.

21 24.5 58 167 41

Base mounted - rigid

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 5Model Line: Indoor Air Handling Unit

UUT

FXTQ12_VJU

FXTQ18_VJU

FXTQ24_VJU

FXTQ30_VJU

FXTQ36_VJU

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

FXTQ42_VJU

FXTQ48_VJU

FXTQ54_VJU

FXTQ60_VJU

FXTQ09_VJU

Air Handling Unit

9,500-60,000 BTU/hr

(cooling capacity)

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 26 of 82

Page 27: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS = 2.0 z/h = 1.0

S DS = 2.5 z/h = 0.0

Depth Width Height

Base mounted - rigid

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

Manufacturer: Daikin North America, LLCTABLE 5Model Line: Indoor Air Handling Unit

UUT

Building Code: CBC 2016 Seismic Certification Limits: I P = 1.5

Model Line ModelDimension (in) Weight

(lb)Notes

Nomenclature: VRV III Indoor Branch Selector Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 27 of 82

Page 28: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

2

3

1

4

5

6

7

8

9,10

27

28

29

30

37

Interp.

38

39

1

2

3

4

37

Swing Compressor

7mm x 0.3mm coil, Al fin, Cu tube

18,000 BTU/hr, 208-230V

1YC23AEXD 12,000 BTU/hr, 208-230V

2YC63BXD#A 21,500 BTU/hr, 208-230V

3P287611-2 8mm x 0.3 mm coil, Al fin, Cu tube

Heat Exchanger

5018937

6019568 7mm x 0.3mm coil, Al fin, Cu tube

6019584

CA-RXYQ8PYD

7009440

8mm x 0.3 mm coil, Al fin, Cu tube

7mm x 0.3mm coil, Al fin, Cu tube

2YC63FXD#D 36,000 BTU/hr, 208-230V

2YC63HXD

Daikin

Daikin

7009559 7mm x 0.3mm coil, Al fin, Cu tube

7500019

Component Type Manufacturer Model Description Notes

6021439 7mm x 0.3mm coil, Al fin, Cu tube

CA-RXYQ10PYD 8mm x 0.3 mm coil, Al fin, Cu tube

CA-REYQ5PY1 8mm x 0.3 mm coil, Al fin, Cu tube

6025911 36,000 BTU/hr, 208-230V

7mm x 0.3mm coil, Al fin, Cu tube

7500099 7mm x 0.3mm coil, Al fin, Cu tube

3P138067-2 7mm x 0.27 mm coil, Al fin, Cu tube

18-3/4" x 4-1/2" Stainless Steel Braze Plate

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 6Model Line: Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

CA-RZQ71K 8mm x 0.3 mm coil, Al fin, Cu tube

3P142404-2 8mm x 0.3 mm coil, Al fin, Cu tube

2P170976-3 8mm x 0.3 mm coil, Al fin, Cu tube

CA-RXYQ12PY1 8mm x 0.3 mm coil, Al fin, Cu tube

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 28 of 82

Page 29: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

Component Type Manufacturer Model Description Notes UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 6Model Line: Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

38

27

28,30

29

30

5

7,9

7,9

6

8

8,10

39

1

2

3

4

5

6

7

8,9

10

27

Swing Compressor

Fan Motor

Panasonic

JT100G-VDLW 48,000 BTU/hr, 208-230V, Carbon Steel

3SB40632-6 23W, 208-230V UUT: Polyester resin tested

1873054

7009494

72,000 BTU/hr, 208-230V, Carbon Steel

72,000 BTU/hr, 208-230V, Carbon Steel

60W, 208-230V UUT: Polyester resin tested

3SB40675-1

JT100GCVDKW

JT1G-VDKWYRScroll Compressor Daikin 60,000 BTU/hr, 208-230V, Carbon Steel

96,000 BTU/hr, 460V, Carbon Steel

JT170G-KWYD 60,000 BTU/hr, 460V, Carbon Steel

7009487 96,000 BTU/hr, 460V, Carbon Steel

UUT: Polyester resin testedWada Electric 3P123189-1 70W, 208-230V

3SB40622-3NIDEC

Panasonic

Daikin 57, 000 BTU/hr, 208-230V

Propellor Fan 500 Watts

6025930

7009548

72,000 BTU/hr, 208-230V, Carbon Steel Same model # as 48,000 BTU/hr unit

200W, 208-230V UUT: Polyester resin tested

UUT: Polyester resin tested

UUT: Polyester resin tested

UUT: Polyester resin tested

UUT: Aluminum tested

UUT: Polyester resin tested

UUT: Polyester resin tested

70Wx2, 208-230V3P171341-1NIDEC

3P170259-1 Direct Drive 750W, 208-230V

3P180619-1

3P170281-2

3P180619-1

1713309

Direct Drive 750W, 460V

Direct Drive (350Wx2), 208-230V or 460V

Direct Drive (350W x 2), 208-230V

JT100GCVDKW 48,000 BTU/hr, 208-230V, Carbon Steel Same model # as 72,000 BTU/hr unit

5018933 144,000 BTU/hr. 208-230V Carbon Steel

JT170G-KWTJ 48,000 BTU/hr, 208-230V, Carbon Steel

Panasonic

NIDEC

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 29 of 82

Page 30: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

Component Type Manufacturer Model Description Notes UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 6Model Line: Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S)

28,30

29

37

38

39

1,2

4,5

1,2

3

6,7,8,9,10

,27,28,29,

30

6016145 Propeller Fan, 200 Watts, 208-230 V UUT: Polyester resin testedFan Motor

Daikin

Panasonic

KPW5E80 Plastic

2024336

KPW937A4 Plastic

5019722

UKV-25D Copper, SS, ResinSaginomiya

BRP2A81

UTT: Polyester resin tested

Cool/Heat Selector

Low Ambient Wind

Baffle

Expansion Valve

2219437 Propellor Fan 400 Watts

4012442 Propellor Fan 650 Watts

DaikinPlastic, Requires BRP2A81 ABC Terminal

Kit

CAM-B30YGDMFujikoki

UUT: Polyester resin tested

UUT: Polyester resin tested

Propeller Fan, 70 Watts, 208-230 V UUT: Polyester resin tested

Copper, SS, Resin

Daikin

23 Watts, 208-230 V

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 30 of 82

Page 31: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

11

13

12

14

15

11

12

15

14

13

12

14

11

11

12

13

14

15

11

13,15

11

Daikin

Photocatalytic Filter Daikin

2P168924-4

2P171400-2 7mm x 0.3 mm coil, Al fin, Cu tube

6.35mm x 0.3 mm coil, Al fin, Cu tube1P287200-1

4000835 Plastic Mesh

3P204553-2

Filter Daikin

NIDEC

Fan Motor

Heat Exchanger

Panasonic

FujikokiExpansion Valve

1685846 Plastic Mesh

1288416

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

Plastic Mesh

1380242 Plastic Mesh

Plastic Mesh

Cross Flow Fan 40W, 208-230V3SB40565-1 UUT: Polyester resin tested

Cross Flow Fan 43W, 208-230V

Deodorizing Filter Daikin 1843053 Plastic Mesh

Component Type Manufacturer Model Description Notes

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 7Model Line: Indoor Wall Mounted Fan Coil (Split System, Quaternity, SkyAir)

Cross Flow Fan 48W, 208-230V

Copper, SS, Resin

3SB40591-1

3SB40720-1

2SA50075-1-KU

UUT: Polyester resin tested

UUT: Polyester resin tested

4009476

3SB40647-3 Cross Flow Fan 23W, 208-230V UUT: Polyester resin tested

3SB40672-1 Cross Flow Fan 64W, 208-230V UUT: Polyester resin tested

Copper, SS, Resin

Plastic Mesh

2SA50075-1-SI

1700125

6.35mm x 0.3 mm coil, Al fin, Cu tube

7mm x 0.3 mm coil, Al fin, Cu tube

2P222543-1 7mm x 0.3 mm coil, Al fin, Cu tube

1843039 Photocatalytic

1840489 Photocatalytic

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 31 of 82

Page 32: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

Component Type Manufacturer Model Description Notes

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 7Model Line: Indoor Wall Mounted Fan Coil (Split System, Quaternity, SkyAir)

Individual Zone

ControllerDaikin BRC7E818 12, 14Plastic

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 32 of 82

Page 33: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

16

17

18

19

20

21

22

23

24

33

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

35

42

7mm x 0.3 mm coil, Al fin, Cu tube

2PN05189-3 7mm x 0.3 mm coil, Al fin, Cu tube

7mm x 0.3 mm coil, Al fin, Cu tube

2110770 7mm x 0.3 mm coil, Al fin, Cu tube

2110763 7mm x 0.3 mm coil, Al fin, Cu tube

2110756 7mm x 0.3 mm coil, Al fin, Cu tube

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 8Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

3P288942-1 7mm x 0.3 mm coil, Al fin, Cu tube

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

AFREX

Heat ExchangerCRB-FXYMP280M 8mm x 0.3 mm coil, Al fin, Cu tube

2273936 7mm x 0.3 mm coil, Al fin, Cu tube

2P231854-1 7mm x 0.3 mm coil, Al fin, Cu tube

Component Type Manufacturer Model Description Notes

3P288941-1 7mm x 0.3 mm coil, Al fin, Cu tube

1993042

3P290389-1 7mm x 0.3 mm coil, Al fin, Cu tube

2218100 7mm x 0.3 mm coil, Al fin, Cu tube

2PN05185-3

7mm x 0.3 mm coil, Al fin, Cu tube

CRB-FXYMP224M 8mm x 0.3 mm coil, Al fin, Cu tube

2P231856-1 7mm x 0.3 mm coil, Al fin, Cu tube

1993035

1993059 7mm x 0.3 mm coil, Al fin, Cu tube

1993028 7mm x 0.3 mm coil, Al fin, Cu tube

Daikin

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 33 of 82

Page 34: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 8Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

Component Type Manufacturer Model Description Notes

16

17

21

22

33

35

18

Interp.

19

42

20

23,24

16

17

20

21

22,23

24

18

19

3PN04404-1 Sirocco Fan 130W, 208-230V

UUT: Aluminum tested

3P204674-2 Sirocco Fan 350W, 208-230V UUT: Aluminum tested

QTS48D11M UUT: Polyester resin tested

3PN04213-1 Sirocco Fan 60W, 208-230V UUT: Polyester resin tested

Copper, SS, Resin

3SA50095-1

Copper, SS, Resin

2SA50046-1-SU Copper, SS, Resin

Panasonic

QTS48D11M Turbo Fan 106W, 208-230V

QTS48C15M Turbo Fan 48W, 208-230V UUT: Polyester resin tested

QTS106C15M Turbo Fan 106W, 208-230V

3P173872-1 Turbo Fan 56W, 208-230V UUT: Polyester resin tested

3P173873-1 Turbo Fan 120W, 208-230V UUT: Polyester resin tested

3P229859-1 Sirocco Fan 90W, 208-230V UUT: Polyester resin tested

3P028033-1 Sirocco Fan 380W, 208-230V UUT: Carbon steel tested

2SA50046-2-KE, Copper, SS, Resin

2SA50046-2-KA

UUT: Polyester resin tested

2SA50046-2-KA Copper, SS, Resin

Turbo Fan 46W, 208-230V

Expansion Valve

Fujikoki

Saginomiya

UUT: Polyester resin tested

3P259061-2 Sirocco Fan 350W, 208-230V

Copper, SS, Resin

2SA50046-1-KE

Copper, SS, Resin

2SA50046-2-KE Copper, SS, Resin

3SA50093-1

Fan Motor

TOP

NIDEC

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 34 of 82

Page 35: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 8Model Line: Indoor Ceiling Fan Coil (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV)

UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

Component Type Manufacturer Model Description Notes

18,19

18,19

18,19

20

21

22

23

24

Interp.

Interp.

20,21,22

16

17

1245349 Plastic Mesh

KRP1H98

Fresh Air Intake Kit with or without T Pipe,

Carbon Sheet Steel

DACA-MQ96M-13-1K MERV 13 Filter Kit (Throwaway Type)

KRP1C75Wiring Adapter PCB (requires KRP1H98 for

FXFQ_PVJU), Plastic

DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type) Sheet Steel Box

DACA-FXMQ30-13-1K MERV 13 Filter Kit (Throwaway Type) Sheet Steel Box

DACA-FQP13-1K MERV 13 Filter & Kit Sheet Steel Box with Media Type Filter

1245363 Plastic Mesh

KRP4A74 Group Control Adaptor PCB, Plastic

17

18,19

18,19

Sheet Steel Box

Filter Daikin

Miscellaneous Daikin

Individual Zone

ControllerDaikin BRC7E83 Plastic

Installation Box for Adapter PCB, Plastic

KRP4A71 Group Control Adaptor PCB, Plastic

KRP1C74 Wireless Adapter PCB, Plastic

Sheet Steel Box

DACA-MQ48F-13-1K MERV 13 Filter Kit (Throwaway Type)

KRP4A96 Mounting Plate for Accessory PCB

KDDP55B160K

DACA-FXMQ48-13-1K MERV 13 Filter Kit (Throwaway Type)

Steel Plate

Sheet Steel Box

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 35 of 82

Page 36: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

25

25

25

25

25

25

25

25

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 9Model Line: Indoor Branch Selectors (VRV III, VRV IV)

1801408 Body/Motor Operated Valve, Copper

1801390 Body/Motor Operated Valve, Copper

Component Type Manufacturer Model Description Notes UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

Valve Daikin

261939745

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve (Main

Discharge), Copper26

1939752Coil/Motor Operated Valve (Sub Cool),

Copper26

1939769Coil/Motor Operated Valve (Sub

Discharge), Copper26

1939776Coil/Motor Operated Valve (Sub Suction),

Copper26

Coil/Motor Operated Valve (Main Suction),

Copper

1801275, Coil/Motor Operated Valve, Copper

1801268, Coil/Motor Operated Valve, Copper

1801415 Body/Motor Operated Valve, Copper

1801299,

1801282,

1939738

1801251 Coil/Motor Operated Valve, Copper

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 36 of 82

Page 37: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 9Model Line: Indoor Branch Selectors (VRV III, VRV IV)

Component Type Manufacturer Model Description Notes UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

31,32

31,32

31,32

31,32

31,32

31,32

31,32

31,32

31,32

31,32

31,32

31,32

2227515 Coil/Electronic Exp. Valve Assy., Copper

Valve Daikin

2227452 Coil/Electronic Exp. Valve Assy., Copper

2227469 Coil/Electronic Exp. Valve Assy., Copper

2227508 Coil/Electronic Exp. Valve Assy., Copper

2227445 Coil/Electronic Exp. Valve Assy., Copper

2271202 Coil/Electronic Exp. Valve, Copper

2271194 Coil/Electronic Exp. Valve, Copper

2227476

2271219

2227490 Coil/Electronic Exp. Valve Assy., Copper

2271226 Coil/Electronic Exp. Valve, Copper

2227483 Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve, Copper

Coil/Electronic Exp. Valve Assy., Copper

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 37 of 82

Page 38: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

40

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

41

40

Interp.

Interp.

41

40

Interp.

41

40

Interp.

Interp.

Interp.

Interp.

Interp.

3/8" x 1/8", Al Tube, Al fin FXTQ30

0270A01162 3/8" x 1/8", Al Tube, Al fin

FXTQ42

3S500049-1 FXTQ12

0131M00271 3/4 Hp, Serial ECM FXTQ42-48

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 10Model Line: Air Handling Unit

Component Type Manufacturer Model Description Notes

0270A01157 3/8" x 1/8", Al Tube, Al fin FXTQ12

FXTQ09-36

0270A01156 3/8" x 1/8", Al Tube, Al fin

FXTQ36

Heat Exchanger Daikin

Fan Motor Daikin

FXTQ60

FXTQ09

0270A01159 3/8" x 1/8", Al Tube, Al fin FXTQ18

0270A01160 3/8" x 1/8", Al Tube, Al fin FXTQ24

0270A01161

UUT

0270A01197 3/8" x 1/8", Al Tube, Al fin

FXTQ54, 60 - tested in FXTQ600270A01206 3/8" x 1/8", Al Tube, Al fin

0131M00270 1/2 Hp, Serial ECM

FXTQ36, 42

0271A00206 10 x 8" , Galvanized Steel FXTQ54,60 - tested in FXTQ60

FXTQ30

3S500048-1

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

FXTQ24

3S500052-1

9 x 6", Galvanized Steel FXTQ09-36, tested in FXTQ09

0271A00029 10 x 8" , Galvanized Steel FXTQ42,48

3S500053-1

0131M00272 1 Hp, Serial ECMFXTQ54

Blower Assembly Daikin

0271A00299

0270A01196 3/8" x 1/8", Al Tube, Al fin

FXTQ48

FXTQ09

3S500050-1 FXTQ18

3S500051-1DaikinExpansion Valve Pulse motor electronic expansion valve

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 38 of 82

Page 39: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

S DS =

S DS =

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT

Manufacturer: Daikin North America, LLCTABLE 10Model Line: Air Handling Unit

Component Type Manufacturer Model Description Notes UUT

Building Code: CBC 2016 Seismic Certification Limits:2.0 z/h = 1.0

I P = 1.52.5 z/h = 0.0

413S500054-1 FXTQ54, 60 - tested in FXTQ60DaikinExpansion Valve Pulse motor electronic expansion valve

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 39 of 82

Page 40: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

1.5

Notes:

15FTXS36LVJU, 36lb, Wall - Rigid

MountQ1222.0, Rev 0 QualTech NP 2.92 1.0

2.90 1.0 1.5

14FAQ18PVJU, 31lb, Wall - Rigid

MountQ1222.0, Rev 0 QualTech NP 2.98 1.0 1.5

10REYQ144PBTJ, 728lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

6

2.95 1.0 1.5

2.92 1.0 1.5

2.87 1.0 1.5

2.98 1.0

1.5

3.05 1.0 1.5

2.98 1.0 1.5

Q1222.0, Rev 0 QualTech NP

1.5

REMQ72PBTJ, 444lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

8RXYQ96PBTJ, 585lb, Base - Rigid

Mount

13FTXS24LVJU, 32lb, Wall - Rigid

MountQ1222.0, Rev 0 QualTech NP

2.87 1.0

1.0 1.5

2.98 1.0

11FTXG09HVJU, 29lb, Wall - Rigid

MountQ1222.0, Rev 0 QualTech NP

12FXAQ09PVJU, 25lb, Wall - Rigid

MountQ1222.0, Rev 0 QualTech NP

9REYQ120PBYD, 736lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

Q1222.0, Rev 0 QualTech NP

3 1.0 1.5

SDS z/h Ip

1RXS09LVJU, 75lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

UUT Unit Description Report Number Testing Laboratory

QualTech NP

2.50 1.0 1.5

RXS36LVJU, 181lb, Base - Rigid

MountQ1222.0, Rev 0

2.92 1.0 1.5

2.87

UNIT UNDER TEST (UUT)TESTING SUMMARY SHEET

7REMQ120PBYD, 568lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

2RXS24LVJU, 158lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

4RZQ30PVJU, 147lb, Base - Rigid

MountQ1222.0, Rev 0 QualTech NP

5RXYMQ48PVJU, 271lb, Base - Rigid

Mount

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

1.5

2.98

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 40 of 82

Page 41: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

SDS z/h IpUUT Unit Description Report Number Testing Laboratory

UNIT UNDER TEST (UUT)TESTING SUMMARY SHEET

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

1.5

30REYQ168TYDN, 798lb, Base - Rigid

MountJID 15-1054, Rev 0 Clark Testing

1.5

28RXYQ168TYDN, 702lb, Base - Rigid

MountJID 15-1054, Rev 0 Clark Testing

1.5

26

Q1222.0, Rev 0 QualTech NP 2.95 1.0

1.5

BSV6Q36PVJU, 203lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.95 1.0 1.5

27RXYQ72TTJU, 444lb, Base - Rigid

MountJID 15-1054, Rev 0 Clark Testing 2.50 1.0

25BSVQ36PVJU, 25lb, Ceiling -

Suspended

24FXMQ96MVJU, 376lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.92 1.0 1.5

Q1222.0, Rev 0 QualTech NP 2.98 1.0

23

1.5

3.05 1.0 1.5

FXFQ09PVJU, 70lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.92 1.0 1.5

FXMQ48MFVJU, 212lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP

16FXHQ12MVJU, 59lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.98 1.0

2.98 1.0

21FXMQ18PVJU, 99lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.90 1.0

19

1.5

22

1.5

QualTech NP 2.92

17FHQ42MVJU, 93lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP

20FXMQ12PVJU, 67lb, Ceiling -

SuspendedQ1222.0, Rev 0

Notes:

29REYQ72TTJU, 518lb, Base - Rigid

MountJID 15-1054, Rev 0 Clark Testing 2.50 1.0

1.0 1.5

FXMQ48PVJU, 128lb, Ceiling -

SuspendedQ1222.0, Rev 0 QualTech NP 2.98 1.0 1.5

FXFQ48PVJU, 82lb, Ceiling -

Suspended

18

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 41 of 82

Page 42: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

SDS z/h IpUUT Unit Description Report Number Testing Laboratory

UNIT UNDER TEST (UUT)TESTING SUMMARY SHEET

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

2.00 1.0 1.5

2.50 0.0 1.5

NOT USED

34

35FXFQ07TVJU, 54lb, Ceiling -

SuspendedJID 15-1054, Rev 0 Clark Testing

36

NOT USED

38RXTQ60TAVJU, 221.5 lb, Base -

Rigid Mount14662, Rev 2

Environment Testing

Laboratory, Inc.

39RWEQ96TATJU, 439 lb, Base -

Rigid Mount14662, Rev 2

Notes:

41FXUQ36PVJU, 60.5 lb, Ceiling -

Suspended

31BS4Q54TVJ, 48lb, Ceiling -

SuspendedJID 15-1054, Rev 0 Clark Testing

32BS12Q54TVJ, 104lb, Ceiling -

SuspendedJID 15-1054, Rev 0 Clark Testing

33FXUQ18PVJU, 56lb, Ceiling -

SuspendedJID 15-1054, Rev 0 Clark Testing

14662, Rev 2Environment Testing

Laboratory, Inc.

Environment Testing

Laboratory, Inc.

40FXTQ60TAVJU, 147 lb, Base - Rigid

Mount14662, Rev 2

Environment Testing

Laboratory, Inc.

37RXTQ36TAVJU, 175.5 lb, Base -

Rigid Mount14662, Rev 2

Environment Testing

Laboratory, Inc.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 42 of 82

Page 43: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

75

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.87 1.0 1.5 4.59 3.44 1.91 0.77

Model Number: RXS09LVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 1Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

11.8 33.5 21.5 29.5 >33.3 14.6

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.27 mm coil DAIKIN 3P138067-2

Compressor: 12,000 Btu/h DAIKIN 1YC23AEXD

Fan: Propeller 23W NIDEC 3SB40632-6

Printed Circuit Boards: Main DAIKIN 4009626, Filter DAIKIN 4009359

Expansion Valve: FUJIKOKI CAM-B30YGDM

Other: DAIKIN Carbon Steel cabinet, DAIKIN KPW937A4 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 43 of 82

Page 44: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

158

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: RXS24LVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 2Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

11.5 29.5 14.3 12.2 6.6 14.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 2P170976-3

Compressor: 21,500 Btu/h DAIKIN 2YC63BXD#A

Fan: Propeller 60W NIDEC 3SB40622-3

Printed Circuit Boards: Main DAIKIN 4009630, Filter DAIKIN 1688256

Expansion Valve: FUJIKOKI CAM-B30YGDM, Other: DAIKIN Carbon steel cabinet, DAIKIN KPW945A4 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 44 of 82

Page 45: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

181

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Rigid base mounted with (4) 1/2”Ø A307 bolts & (4) 1/16”x1-1/2” aluminum straps were secured approximately 30˚relative to

vertical surface of the unit with (2) #10 SMS to unit & 1/4ӯ bolt to table

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: RXS36LVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 3Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

14.0 37.0 39.3 11.5 6.6 14.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 3P287611-2

Compressor: 36,000 Btu/h DAIKIN 2YC63FXD#D

Fan: Propeller 200W Panasonic 3SB40675-1

Printed Circuit Board: Main DAIKIN 4009635

Expansion Valve Valve: Saginomiya UKV-25D, Other: DAIKIN Carbon steel cabinet

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 45 of 82

Page 46: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

147

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.5 1.0 1.5 4.00 3.00 1.67 0.67

Model Number: RZQ30PVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 4Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

14.0 35.3 30.8 28.8 8.2 14.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-RZQ71K

Compressor: 18000 Btu/h DAIKIN 2YC63HXD

Fan: Propeller Fan 70W WADA ELECTRIC 3P123189-1

Printed Circuit Boards: Main DAIKIN 1939093, 2053202; Display DAIKIN 1939101

Other: DAIKIN Carbon steel cabinet, DAIKIN KPW5E80 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 46 of 82

Page 47: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

271

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Rigid base mounted with (4) 1/2”Ø A307 bolts & (4) 1/16”x 2” aluminum straps were secured approximately 30˚relative to vertical

surface of the unit with (2) #10 SMS to unit & 1/4ӯ bolt to table

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: RXYMQ48PVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit & (3) #10 SMS top cover to frame & (10) #10 SMS compressor cover to frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 5Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

14.3 35.3 52.0 7 7.3 14.5

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 3P142404-2

Compressor: 48,000 Btu/h DAIKIN JT100G-VDLW

Fan: Propeller Fan (70W x 2) NIDEC 3P171341-1

Printed Circuit Boards: Main DAIKIN 2022215; Service DAIKIN 1717990; Noise Filter DAIKIN 4005917; C/H Selctor DAIKIN 1718018

Other: DAIKIN Carbon steel cabinet; DAIKIN KPW5E80 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 47 of 82

Page 48: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

444

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.87 1.0 1.5 4.59 3.44 1.91 0.77

Model Number: REMQ72PBTJ Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 6Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.3 36.8 66.0 7.7 6.4 14.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-RXYQ8PYD

Compressor: 72,000 Btu/h DAIKIN JT100GCVDKW, Fan: Propeller Fan/Direct Drive 750W 3P170259-1

Printed Circuit Boards: Main DAIKIN 1926042; Earth Leakage Detector DAIKIN 1894239; Printed Circuit Assy. (Sub) DAIKIN

1852242; Noise Filter DAIKIN 1852235; Inverter DAIKIN 1852228; Inverter Assy. (Fan Driver) DAIKIN 1697089

Other: DAIKIN Carbon steel cabinet; DAIKIN BRP2A81 Cool/Heat Selector (Requires BRP2A81 ABC Terminal Kit)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 48 of 82

Page 49: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

568

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: REMQ120PBYD Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 7Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.3 36.8 66.0 8.1 7.9 14.5

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-RXYQ10PYD, Compressors: 60,000 Btu/h DAIKIN JT1G-VDKWYR; 60,000 Btu/h

DAIKIN JT170G-KWYD, Fan: Propeller Fan/Direct Drive 750W Panasonic 3P180619-1

Printed Circuit Boards: Main DAIKIN 2066594; Earth Leakage Detector DAIKIN 1894239; Inverter DAIKIN 1873085; Printed Circuit

Assy. (Sub) DAIKIN 1852242; Current Sensor DAIKIN 1695780; ABC I/P DAIKIN 1716788

Other: DAIKIN Carbon steel cabinet; DAIKIN BRP2A81 Cool/Heat Selector (Requires BRP2A81 ABC Terminal Kit)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 49 of 82

Page 50: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

585

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 3.05 1.0 1.5 4.88 3.66 2.03 0.81

Model Number: RXYQ96PBTJ Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 8Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.1 48.9 66.0 9.1 7.2 14.5

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-RXYQ12PY1, Compressors: Capacity 48,000 Btu/h, 2200 W DAIKIN JT100GCVDKW; Capacity

48,000 Btu/h, 4500 W DAIKIN JT170G-KWTJ, Fan: Propeller Fan/Direct Drive (350W x 2) NIDEC 3P170281-2

Printed Circuit Boards: Main DAIKIN 2041533; Noise Filter DAIKIN 1852235; Printed Circuit Assy. (Inverter) DAIKIN 1873078; Inverter Assy. (Fan

Driver) DAIKIN 1873092; Current Sensor DAIKIN 1695780; Earth Leakage Dectector DAIKIN 1894246; ABC I/P DAIKIN 1716788, Other: DAIKIN

Carbon steel cabinet; DAIKIN BRP2A81 Cool/Heat Selector (Requires BRP2A81 ABC Terminal Kit)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 50 of 82

Page 51: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

736

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.87 1.0 1.5 4.59 3.44 1.91 0.77

Model Number: REYQ120PBYD Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 9Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.3 51.4 66.0 9.5 8.2 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-REYQ5PY1, Compressors: Capacity 60,000 Btu/h, 3500 W DAIKIN JT1G-VDKWYR;

Capacity 60,000 Btu/h, 4500 W DAIKIN JT170G-KWYD, Fan: Propeller Fan/Direct Drive (350W x 2) NIDEC 3P170281-2

Printed Circuit Boards: Main DAIKIN 2041533; Noise Filter DAIKIN 1852235; Printed Circuit Assy. (Inverter) DAIKIN 1873078;

Inverter Assy. (Fan Driver) DAIKIN 1873092; Earth Leakage Dectector DAIKIN 1894246

Other: DAIKIN Carbon steel cabinet; DAIKIN BRP2A81 Cool/Heat Selector (Requires BRP2A81 ABC Terminal Kit)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 51 of 82

Page 52: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

728

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: REYQ144PBTJ Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 10Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.3 51.4 66.0 8.4 7.7 14.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CA-REYQ5PY1, Compressor: Capacity 72,000 Btu/h (2), 3800 W (2) DAIKIN

JT100GCVDKW, Fan: Propeller Fan/Direct Drive (750W x 2) Panasonic 3P180619-1

Printed Circuit Boards: Printed Circuit Assy. (Inverter) DAIKIN 1873078; Printed Circuit Assy. (Sub 1) DAIKIN 1852242; Printed

Circuit Assy. (Sub 2) DAIKIN 1873148; Earth Leakage Detector DAIKIN 1894246; Main DAIKIN 2041533

Other: DAIKIN Carbon steel cabinet; DAIKIN BRP2A81 Cool/Heat Selector (Requires BRP2A81 ABC Terminal Kit)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 52 of 82

Page 53: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

29

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw & (1) #10-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.95 1.0 1.5 4.72 3.54 1.97 0.79

Model Number: FTXG09HVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 11Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

8.5 35.0 12.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 3P204553-2

Fan: Cross Flow Fan 23W NIDEC 3SB40647-3

Printed Circuit Boards: Printed Circuit Assy(Photo/Display) DAIKIN 1840054; Pyroelectric Passive Infrared Sensor DAIKIN 1840061;

Main DAIKIN 4009433

Other: DAIKIN 1843053 Deodorizing filters; DAIKIN 1700125 Filter; DAIKIN 1685846 Filter; DAIKIN 1843039 Photocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 53 of 82

Page 54: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

25

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Wall mounted with (4) 3/8ӯ A307 bolts & (5) #10 self-tapping screws

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Model Number: FXAQ09PVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 12Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

9.3 31.0 11.5 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P168924-4

Fan: Cross Flow Fan 40W NIDEC 3SB40565-1

Printed Circuit Boards: Main DAIKIN 4008765; Main DAIKIN 4005831

Expansion Valve: Fujikoki 2SA50075-1-KU

Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN 1288416 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 54 of 82

Page 55: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

32

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #10-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.90 1.0 1.5 4.64 3.48 1.93 0.77

Model Number: FTXS24LVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 13Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

9.8 40.8 13.4 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 1P287200-1

Fan: Cross Flow Fan 48W Panasonic 3SB40720-1

Printed Circuit Boards: Printed Cicuit Assy(Photo/Display) DAIKIN 4000843; Printed Crt Assy(Infrared Sensor) DAIKIN 4000844;

Main DAIKIN 4009491

Other: DAIKIN 4009476 Filter; DAIKIN 1840489 Photocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 55 of 82

Page 56: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

31

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Wall mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: FAQ18PVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 14Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

8.5 41.1 11.5 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P171400-2

Fan: Cross Flow Fan 43W Panasonic 3SB40591-1

Printed Circuit Board: Main DAIKIN 1884472

Expansion Valve: Valve Fujikoki 2SA50075-1-SI

Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN Plastic Mesh 1380242 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 56 of 82

Page 57: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

36

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Model Number: FTXS36LVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 15Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

9.5 46.9 13.4 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P222543-1

Fan: Cross Flow Fan 64W NIDEC 3SB40672-1

Printed Circuit Boards: Printed Cicuit Assy.(Photo/Display) DAIKIN 4000843; Printed CriAssy. (Infrared Sensor) DAIKIN 4000844;

Main DAIKIN 4009500

Other: DAIKIN 4000835 Plastic Mesh Filter; DAIKIN 1840489 Phtocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 57 of 82

Page 58: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

59

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: FXHQ12MVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 16Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

8.0 37.5 27.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05185-3

Fan: Sirocco Fan 60W Panasonic 3PN04213-1

Printed Circuit Boards: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J

Expansion Valve: Valve Fujikoki 2SA50046-2-KE

Other: DAIKIN 1245349 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 58 of 82

Page 59: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

93

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 3.05 1.0 1.5 4.88 3.66 2.03 0.81

Model Number: FHQ24MVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 17Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

8.0 62.0 27.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05189-3

Fan: Sirocco Fan 130W Panasonic 3PN04404-1

Printed Circuit Board: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J

Expansion Valve: Valve Fujikoki 2SA50046-2-KA

Other: DAIKIN BRC7E83 Individual Zone Controller; DAIKIN 1245363 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 59 of 82

Page 60: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

70

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers & nuts above and below mounting ears & (8)

1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end. Unit maintained structural integrity and remained functional per

manufacturer requirement. Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Model Number: FXFQ09PVJU Serial Number:

Product Construction Summary:

Plastic cabinet with 6-#10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 18Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

33.0 33.0 9.5 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P231854-1, Fan: 3P173872-1 Turbo Fan 56W Panasonic 3P173872-1

Printed Circuit Board: Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74 , Expansion Valve: Valve Saginomiya

3SA50093-1

Other: Installation Box for Adapter PCB DAIKIN KRP1H98; DAIKIN KRP1C75 Wiring Adapter PCB (requires KRP1H98 for

FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 60 of 82

Page 61: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

82

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers and nuts above and below mounting ears & (8)

1/8” diagonal cable braces w/ Mason SCB-1 clips at each end. Unit maintained structural integrity and remained functional per

manufacturer requirement. Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.95 1.0 1.5 4.72 3.54 1.97 0.79

Model Number: FXFQ48PVJU Serial Number:

Product Construction Summary:

Plastic cabinet with 6-#10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 19Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

33.0 33.0 11.4 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7mm coil DAIKIN 2P231856-1, Fan: 3P173873-1 Turbo Fan 120W Panasonic 3P173873-1, Printed Circuit Boards:

Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74

Expansion Valve: Valve Saginomiya 3SA50095-1, Other: DAIKIN KRP1H98 Installation Box for Adapter PCB; DAIKIN KRP1C75

Wiring Adapter PCB (requires KRP1H98

for FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 61 of 82

Page 62: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

67

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ A14(4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each

end. Unit maintained structural integrity and remained functional per manufacturer requirement. Contents were included in

testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Model Number: FXMQ12PVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 20Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

25.0 30.0 12.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P290389-1, Fan: Sirocco Fan 90W NIDEC 3P229859-1

Printed Circuit Boards: Main DAIKIN 4006121; Printed Circuit Assy. (Fan) DAIKIN 4006122

Expansion Valve: Valve Fujikoki 2SA50046-1-KE

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 62 of 82

Page 63: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

99

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.90 1.0 1.5 4.64 3.48 1.93 0.77

Model Number: FXMQ18PVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 21Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.0 42.5 12.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288941-1, Fan: Sirocco Fan 350W Panasonic 3P259061-2

Printed Circuit Board: Printed Circuit Assy. DAIKIN 1863862; Printed Circuit Assy. (Inverter) DAIKIN 2007595; Main DAIKIN 4006121,

Expansion Valve: Valve Fujikoki 2SA50046-1-SU

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 63 of 82

Page 64: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

128

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: FXMQ48PVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 22Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.0 58.5 12.0 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288942-1, Fan: Sirocco Fan 350W Panasonic 3P204674-2

Printed Circuit Boards: Inverter Assy. DAIKIN 2007588; DAIKIN 1863862; Main DAIKIN 4006121, Expansion Valve: Valve Fujikoki

2SA50046-2-KA

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 64 of 82

Page 65: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

212

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: FXMQ48MFVJU Serial Number:

Product Construction Summary:

Plastic cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 23Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

33.5 44.5 18.5 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP224M

Fan: Sirocco Fan 380W TOP 3P028033-1, Printed Circuit Board: Main DAIKIN 1962257

Expansion Valve: Valve Fujikoki 2SA50046-2-KA

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 65 of 82

Page 66: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

376

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with 1/2” washers and nuts above and below mounting ears &

(8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end. Unit maintained structural integrity and remained functional

per manufacturer requirement. Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.92 1.0 1.5 4.67 3.50 1.95 0.78

Model Number: FXMQ96MVJU Serial Number:

Product Construction Summary:

Plastic cabinet with #10 SMS at each mounting ear (4 total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 24Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

44.5 58.5 19.5 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP280M

Fan: Sirocco Fan (380W x 2) TOP 3P028033-1, Printed Circuit Boards: Main DAIKIN 1962257; Main DAIKIN 1962219

Expansion Valve: Valve Fujikoki 2SA50046-2-KE

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 66 of 82

Page 67: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

25

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted with (4) 3/8”Ø A36 hanger rods & (8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.98 1.0 1.5 4.77 3.58 1.99 0.79

Model Number: BSVQ36PVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 25Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

13.0 12.5 8.1 N/A N/A N/A

Options/Subcomponent Summary:

Printed Circuit Board: Main DAIKIN 1893591

Valves: BODY/ MOTOR OPERATED VALVE DAIKIN 1801408; COIL/ MOTOR OPERATED VALVE DAIKIN 1801299; BODY/ MOTOR

OPERATED VALVE DAIKIN 1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801282; BODY/ MOTOR OPERATED VALVE DAIKIN

1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801275; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR

OPERATED VALVE DAIKIN 1801268; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR OPERATED VALVE DAIKIN

1801251UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 67 of 82

Page 68: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

203

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.95 1.0 1.5 4.72 3.54 1.97 0.79

Model Number: BSV6Q36PVJU Serial Number:

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 26Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

25.0 62.1 8.1 N/A N/A N/A

Options/Subcomponent Summary:

Printed Circuit Board: Main DAIKIN 2058618

Valves: COIL/ MOTOR OPERATED VALVE (MAIN SUCTION)DAIKIN 1939738; COIL/ MOTOR OPERATED VALVE (MAIN DISCHARGE)

DAIKIN 1939745; COIL/ MOTOR OPERATED VALVE (SUB SUCTION) DAIKIN 1939752; COIL/ MOTOR OPERATED VALVE (SUB

DISCHARGE)

DAIKIN 1939769; COIL/ MOTOR OPERATED VALVE (SUB COOL) DAIKIN 1939776

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 68 of 82

Page 69: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

444

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Model Number: RXYQ72TTJU Serial Number: 1510195615

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 27Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.2 36.7 66.7 5.4 21.2 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009440

Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 1873054

Fan Motor: Propellor Fan 500 Watts, 208-230V, Panasonic, 1713309

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.5 1.0 1.5 4.00 3.00 1.67 0.67

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 69 of 82

Page 70: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

702

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: RXYQ168TYDN Serial Number: 1510119528

Product Construction Summary:

Carbon steel cabinet with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 28Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.2 48.9 66.7 4.5 6.8 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009559

Compressor: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494

Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 70 of 82

Page 71: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

518

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Model Number: REYQ72TTJU Serial Number: 1510085242

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 29Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.2 36.7 66.7 4.9 7.5 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500019

Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 7009487

Fan Motor: Propellor Fan 400 Watts, 208-230V, Panasonic, 2219437

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156 2.5 1.0 1.5 4.00 3.00 1.67 0.67

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 71 of 82

Page 72: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

798

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: REYQ168TYDN Serial Number: 1506206866

Product Construction Summary:

Carbon steel cabinet with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 30Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

30.2 48.9 66.7 4.2 5.4 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500099

Compressors: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494 and 7009548

Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 72 of 82

Page 73: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

48

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: BS4Q54TVJ Serial Number: A001008

Product Construction Summary:

Carbon steel cabinet with seismic enhancements: Additional (4) #10 self tapping screws in each mounting ear connection

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 31Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

18.9 14.6 11.8 N/A N/A N/A

Options/Subcomponent Summary:

Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP.

VALVE ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469;

COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE

ASSY., DAIKIN 2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/

ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 73 of 82

Page 74: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

104

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: BS12Q54TVJ Serial Number: A000140

Product Construction Summary:

Carbon steel cabinet with seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2) machine screws

through each mounting ear.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 32Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

18.9 32.3 11.8 N/A N/A N/A

Options/Subcomponent Summary:

Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP. VALVE

ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469; COIL/

ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN

2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/ ELECTRONIC EXP.

VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 74 of 82

Page 75: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

56

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: FXUQ18PVJU Serial Number: C000176

Product Construction Summary:

Plastic and carbon steel cabinet with seismic upgrades: Four (4) 15/32” x 4-1/2” x 0.041” extension springs between grille cover

and unit corner, fastened to existing screws and retightened. Springs extended approximately 2”. Heavy duty square washer

(1.5”x1.5”) top and bottom of mounting bracket with (2) ½” flat washers as spacers on top only.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 33Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

37.4 37.4 7.8 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 2273936

Fan Motor: QTS48D11M Turbo Fan 46W, 208-230V, Panasonic 2110749

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 75 of 82

Page 76: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

54

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.20 2.40 1.33 0.53

2.5 0.0 1.5 2.50 1.00 1.67 0.67

Model Number: FXFQ07TVJU Serial Number: C000406

Product Construction Summary:

Carbon steel cabinet with seismic upgrades: Eight (8) #10 SMS in each mounting ear. Four (4) cable tie (shipped with unit) chains,

each with two links, between decoration panel cover latches and through mounting ear. Two (2) strips of heavy duty Velcro®

tape 1” x 2” at each corner cover (eight total).

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 35Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

33.1 33.1 9.7 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 1993028

Fan Motor: QTS48C15M Turbo Fan 48W, 208-230V, Panasonic 1993105

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Test Mounting Details:

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 76 of 82

Page 77: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

175.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #37 was also secured to the shake table with stainless-steel

strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of

the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping

was affixed to the top of the test unit with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws. Unit maintained structural

integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: RXTQ36TAVJU Serial Number: F000419

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 37Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

12-5/8 37 39 13.21 12.1 > 33.3

Options/Subcomponent Summary:

Daikin Heat Exchanger 6021439

Daikin Swing Compressor 15.3A 6025911

Fan Motor 200W Daikin 6016145

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 77 of 82

Page 78: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

221.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #38 was also secured to the shake table with stainless-steel

strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of

the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping

was affixed to the top of the test unit with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws.

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: RXTQ60TAVJU Serial Number: F001523

Product Construction Summary:

Carbon steel cabinet with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 38Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

12-5/8 35-7/16 52-15/16 >33.3 10.97 > 33.3

Options/Subcomponent Summary:

Daikin Heat Exchanger 6019584

Swing Compressor 23.2A Daikin 2025911

Fan Motor (2) 70W Daikin 2024336

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 78 of 82

Page 79: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

439

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

Test Mounting Details:

Rigid base mounted with (4) 5/8”Grade 5 Bolts

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

Model Number: RWEQ96TATJU Serial Number: 1700004

Product Construction Summary:

Carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 39Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

22-1/6 30-1/8 38-9/16 10.25 8.80 20.52

Options/Subcomponent Summary:

Daikin Heat Exhanger 5018937, Scroll Compressor Dakikin 5018933, Daikin Fan Motor 5019722

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 79 of 82

Page 80: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

94.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

UUT#40 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#40’s plenum box

dimensions are as follows: 21.25” x 18.5” x 25.12” with a weight 80.5 lbs. UUT #40 was secured to the plenum box with (5) #10 -16

x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box was secured to

the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer through

slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: FXTQ09TAVJU Serial Number: 1702209059

Product Construction Summary:

Carbon steel cabinet mounted to plenum box.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 40Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

21 17-1/2 45 10.68 10.65 11.1

Options/Subcomponent Summary:

1/2 Hp Fan Motor, electric expansion valve-Daikin 3S500048-1, Daikin Heat Exchanger 0270A01156

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 80 of 82

Page 81: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

147

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

Test Mounting Details:

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

UUT #41 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#41’s plenum box

dimensions are as follows: 21.25” x 25.5” x 25.12” with a weight 98.0 lbs. UUT #41 was secured to their respective plenum boxes

with (5) #10 -16 x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box

was secured to the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer

through slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

Model Number: FXTQ60TAVJU Serial Number: 1710220821

Product Construction Summary:

Carbon steel cabinet mounted to plenum box.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 41Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

21 24-1/2 58 8.83 12.45 27.63

Options/Subcomponent Summary:

1 Hp Fan Motor, electric expansion valve-Daikin 3S500054-1, Daikin Heat Exchanger 0270A01206

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 81 of 82

Page 82: OSHPD Special Seismic Certification Preapproval (OSP) Outdoor Units (Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S) Rigid base mounted. Note: Installed mounting

TRU PROJECT NO. 1700803

60.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0 1.5 3.2 2.4 1.33 0.53

2.5 0.0 1.5 2.5 1 1.67 0.67

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLCUUT 42Model Line: Split System, Quaternity, SkyAir, VRV III-S, VRV III, VRV IV, VRV IV-S, RWEQ

Side-Side Vertical

37-3/8 37-3/8 7-13/16 N/A N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 2110756

Fan Motor: QTS48D11M Turbo Fan 106W, 208-230V, Panasonic

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-0 clips at

each end.

Unit maintained structural integrity and remained functional per manufacturer requirement.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2016 ICC-ES AC156

Model Number: FXUQ36PVJU

Serial Number: C000618

Product Construction Summary:

Plastic and carbon steel cabinet with seismic upgrades: Heavy duty square washers (1.6" x 1.3 x 0.2”) were used at top and

bottow of mounting bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover attachment to uni t, were

crimped closed to secure cover to unit.

Test Mounting Details:

Two Ø diag. cable braces at

each corner

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 03/14/2018

OSP-0297-10

Page 82 of 82