Original VELUX smoke-ventilation roof window GGL / GGU ...
Transcript of Original VELUX smoke-ventilation roof window GGL / GGU ...
Original VELUX smoke-ventilation roof window
GGL / GGU smoke ventilation
Complete smoke-ventilation system in compliance with European EN norms• Appears as standard VELUX roof windows in the roof (without wind deflector)• Available with double or triple glazing• Comfort ventilation possible at the touch of a button. Rain sensor available.• Complete control system for single or groups of windows
Smoke-ventilation roof window
GGLGGL
GGUGGU
GGL including wind deflector GGL including wind deflector
GGU including wind deflector GGU including wind deflector
---- 306640 ---- 307340
---- 006640---- 007340
---- SD00402 ---- SD00403 ---- SD00402 ---- SD00403
Wood with triple glazingWood with double glazing
Polyurethane with triple glazingPolyurethane with double glazing
Wood with triple glazingWood with double glazing
Polyurethane with triple glazingPolyurethane with double glazing
EN 12101-2 EN 12101-2
EN 12101-2 EN 12101-2
EN 12101-2 EN 12101-2
EN 12101-2 EN 12101-2
Window type: Product code: Explanation: EN certified:
(15°-60°)
Control systems for smoke ventilation
Size grid
Contact:VELUX Denmark A/SBreltevej 162970 HørsholmSupport: 2323 4545
Fast & easy to installOriginal Perfect fit Weather proof Warranty Certification
• 2 x 10 amp.• Controls up to 8
GGL/GGU smoke ventilation windows or 2 CSP flat-roof smoke ventilation windows.
• Dimensions: W x H x D 398 x 393 x 127 mm
• Break-glass point for activating smoke ventilation function.
• Wall switch enabling natural ventilation for daily comfort.
• Smoke detector for early fire detection.
• Closes window in comfort ventilation mode in case of rain.
• Delivered with 75 cm cable without connector.
MK04
78 x 98
MK06
78 x 118
MK08
78 x 140
SK06
114 x 118
SK08
114 x 140
UK04
134 x 98 134 x 140
UK08
0.33
0.19
0.63
0.43
0.29
0.76
0.55
0.43
0.91
0.55
0.28
1.17
0.70
0.44
1.38
0.51
0.16
1.14
0.73
0.38
1.65
Geometrical opening area Av in m2
Aerodynamic area Aa in m2 with wind deflector
Aerodynamic area Aa in m2 without wind deflector
SpecificationsVELUX smoke
ventilation window
Control system
KFX 210
Control unit
KFC 210
Control unit
KFC 220
Break-glass point
KFK 100
Comfort switch
KFK 200
Smoke detector
KFA 100
Rain sensor
KLA 200
Complete control system for up to
4 GGL/GGU smoke-ventilation roof window or 1
CSP flat-roof smoke ventilation window.
Includes: KFC 210KFK 100KFA 100
• 10 amp.• Controls up to 4
GGL/GGU smoke- ventilation roof windows or 1 CSP flat-roof smoke ventilation window.
• Dimensions: W x H x D 398 x 393 x 127 mm
Classification in accordance with the parameters of European EN 12101-2
Reliability (Re)
Snow load (SL)
Low Temperature (T)
Wind load (WL)
Heat Exposure (B)
For more information, visit www.velux.nnWe reserve the right to change technical specifications
Re 1000+10000
SL 1000
T (-15)
WL 3000
B 300