Option G4, G5 and G8, 4189340696 UK_2012.07.13

download Option G4, G5 and G8, 4189340696 UK_2012.07.13

of 88

Transcript of Option G4, G5 and G8, 4189340696 UK_2012.07.13

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    1/88

    DEIF A/S Frisenborgvej 33 DK-7800 Skive

    Tel.: +45 9614 9614 Fax: +45 9614 9615

    [email protected] www.deif.com

    Automatic Genset Controller, AGC

    DESCRIPTION OF OPTIONS

    Options G4, G5 and G8

    Power management Functional description

    Display units

    Power management setup

    Power management functions

    Parameter lists

    Document no.: 4189340696CSW version:

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    2/88

    1. Delilmi tation1.1. Scope of options G4, G5 and G8...........................................................................................................5

    2. General information

    2.1. Warnings, legal information and safety..................................................................................................62.1.1. Warnings and notes ......................................................................................................................62.1.2. Legal information and disclaimer ..................................................................................................6

    2.1.3. Safety issues ................................................................................................................................6

    2.1.4. Electrostatic discharge awareness ...............................................................................................6

    2.1.5. Factory settings ............................................................................................................................6

    3. Descrip tion of opt ions3.1. ANSI numbers........................................................................................................................................7

    3.1.1. ANSI..............................................................................................................................................7

    3.2. Options G4, G5and G8..........................................................................................................................7

    3.2.1. G4, G5 and G8..............................................................................................................................73.3. Terminal description...............................................................................................................................9

    3.3.1. Description of terminals.................................................................................................................9

    3.4. Breaker feedbacks...............................................................................................................................103.4.1. Generator breaker.......................................................................................................................10

    3.4.2. Mains breaker (MB) feedback......................................................................................................10

    3.4.3. Tie breaker (TB)...........................................................................................................................103.5. Wiring diagrams...................................................................................................................................11

    3.5.1. Diagrams.....................................................................................................................................11

    4. Functional description4.1. Power management functions..............................................................................................................12

    4.1.1. Description of functions ..............................................................................................................12

    4.2. Terminal strip overview........................................................................................................................13

    4.2.1. AGC generator unit......................................................................................................................13

    4.2.2. AGC mains unit............................................................................................................................15

    4.2.3. AGC bus tie unit...........................................................................................................................174.3. Applications..........................................................................................................................................19

    4.3.1. Application possibilities................................................................................................................19

    4.3.2. Island operation plant..................................................................................................................20

    4.3.3. Parallel with mains plant..............................................................................................................21

    4.3.4. Dual mains plant..........................................................................................................................22

    4.3.5. ATS plant.....................................................................................................................................234.3.6. ATS plant, multiple start...............................................................................................................23

    4.3.7. ATS plant, mains unit...................................................................................................................24

    4.3.8. Multiple mains..............................................................................................................................25

    5. Display units5.1. DU for option G5..................................................................................................................................26

    5.1.1. Option G5 displays .....................................................................................................................26

    5.2. Generator unit display..........................................................................................................................265.2.1. Display.........................................................................................................................................26

    5.3. Mains unit display.................................................................................................................................275.3.1. Display.........................................................................................................................................27

    5.4. BTB unit display...................................................................................................................................27

    5.4.1. Display.........................................................................................................................................27

    6. Power management setup6.1. Initial power management setup..........................................................................................................28

    6.1.1. How to set up...............................................................................................................................28

    6.1.2. Display setup...............................................................................................................................28

    6.1.3. PC software setup.......................................................................................................................28

    6.1.4. Application design........................................................................................................................28

    Option G4, G5 and G8, 4189340696 UK

    DEIF A/S Page 2 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    3/88

    6.2. Remove unit from PM...........................................................................................................................316.2.1. Possibilities..................................................................................................................................31

    6.2.2. Auxiliary supply OFF....................................................................................................................31

    6.2.3. Quick setup..................................................................................................................................32

    6.2.4. Auxiliary supply ON.....................................................................................................................326.3. CANbus failure handling.......................................................................................................................336.3.1. CAN failure mode........................................................................................................................33

    6.3.2. Redundant CANbus communication............................................................................................34

    6.3.3. CANbus alarms............................................................................................................................34

    6.3.4. CANbus fail class.........................................................................................................................35

    6.4. Quick setup..........................................................................................................................................35

    6.4.1. Quick setup..................................................................................................................................356.4.2. Limitations....................................................................................................................................37

    6.5. 9180 Quick setup.................................................................................................................................38

    6.5.1. 9180 Quick setup.........................................................................................................................38

    6.5.2. 9190 Application broadcast.........................................................................................................38

    7. Power management functions

    7.1. Command unit......................................................................................................................................407.1.1. Command unit.............................................................................................................................40

    7.2. Load-dependent starting and stopping.................................................................................................40

    7.2.1. Starting and stopping...................................................................................................................407.2.2. Terminology.................................................................................................................................41

    7.2.3. Principle available power method.............................................................................................44

    7.2.4. Principle percentage method....................................................................................................44

    7.2.5. Adjusting load-dependent start....................................................................................................45

    7.2.6. Adjusting load-dependent stop....................................................................................................46

    7.2.7. Power window..............................................................................................................................477.3. Load management...............................................................................................................................47

    7.3.1. Load management.......................................................................................................................47

    7.3.2. Functionality description (refer to the diagram below).................................................................48

    7.4. Load sharing.........................................................................................................................................49

    7.4.1. Load sharing ...............................................................................................................................497.5. Island ramp up......................................................................................................................................50

    7.5.1. Island ramp up with load steps....................................................................................................50

    7.6. Fixed power ramp up with load steps...................................................................................................51

    7.7. Freeze power ramp..............................................................................................................................51

    7.8. ATS applications..................................................................................................................................52

    7.8.1. AGC mains installed....................................................................................................................527.8.2. ATS island mode.........................................................................................................................52

    7.9. Fail class..............................................................................................................................................53

    7.10. Local/remote/timer operation..............................................................................................................53

    7.10.1. Local selection...........................................................................................................................53

    7.10.2. Remote selection.......................................................................................................................54

    7.10.3. Plant operation...........................................................................................................................547.10.4. Timer selection..........................................................................................................................54

    7.10.5. Principle.....................................................................................................................................55

    7.11. Multi starting gensets.........................................................................................................................56

    7.11.1. Multi-start configuration.............................................................................................................56

    7.11.2. Numbers to start........................................................................................................................57

    7.11.3. Minimumnumbers running........................................................................................................577.12. Priority selection.................................................................................................................................58

    7.12.1. Manual.......................................................................................................................................58

    7.12.2. Running hours...........................................................................................................................60

    7.12.3. Fuel optimisation........................................................................................................................61

    7.13. Conditional connection of heavy consumers......................................................................................647.13.1. Power feedback from the heavy consumer...............................................................................65

    7.13.2. Engagement sequence for HCs with fixed load.........................................................................67

    7.14. Ground relay.......................................................................................................................................67

    Option G4, G5 and G8, 4189340696 UK

    DEIF A/S Page 3 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    4/88

    7.14.1. Ground relay..............................................................................................................................677.15. Stop of non-connected gensets..........................................................................................................68

    7.16. Secured mode....................................................................................................................................68

    7.17. Base load...........................................................................................................................................69

    7.18. Asymmetric load sharing (LS)............................................................................................................697.19. Tie breaker configuration....................................................................................................................707.19.1. Tie breaker selection.................................................................................................................70

    7.19.2. Tie breaker control.....................................................................................................................70

    7.19.3. Tie breaker open point...............................................................................................................70

    7.19.4. Power capacity..........................................................................................................................71

    7.20. Island application with TB...................................................................................................................72

    7.21. Multiple mains....................................................................................................................................737.21.1. Definitions..................................................................................................................................74

    7.21.2. Configuration.............................................................................................................................76

    7.21.3. Plant mode handling..................................................................................................................77

    7.22. Dual mains.........................................................................................................................................79

    7.22.1. Configuration.............................................................................................................................80

    7.22.2. Plant mode handling..................................................................................................................81

    7.22.3. Internal CAN ID..........................................................................................................................837.22.4. AGC mains unit redundancy......................................................................................................83

    7.22.5. Tie breaker configuration...........................................................................................................84

    7.23. Configurable CAN IDs........................................................................................................................85

    7.24. CAN flags...........................................................................................................................................867.25. Common PF control...........................................................................................................................86

    8. Parameter lists8.1. Common settings.................................................................................................................................88

    Option G4, G5 and G8, 4189340696 UK

    DEIF A/S Page 4 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    5/88

    1. Delilmitation

    1.1 Scope of options G4, G5 and G8

    This description of options covers the following products:

    AGC-3 SW version 3.6x.x or later

    AGC-4 SW version 4.1x.x or later

    Option G4, G5 and G8, 4189340696 UK Delilmitation

    DEIF A/S Page 5 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    6/88

    2. General information

    2.1 Warnings, legal information and safety

    2.1.1 Warnings and notesThroughout this document, a number of warnings and notes with helpful user information will be presented.

    To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-

    al text.

    Warnings

    Warnings indicate a potentially dangerous situation, which cou ld result i n death, personal in-

    jury or damaged equipment, i f certain guidelines are not fo llowed.

    Notes

    Notes provide general information, which will be helpful for the reader to bear in mind.

    2.1.2 Legal information and disclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how

    to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the

    installation or the operation of the set must be contacted.

    The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-

    ranty will be lost.

    Disclaimer

    DEIF A/S reserves the right to change any of the contents of this document without prior notice.

    2.1.3 Safety issuesInstalling and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,

    the installation should only be carried out by authorised personnel who understand the risks involved in work-

    ing with live electrical equipment.

    Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-

    puts as this could lead to injury or death.

    2.1.4 Electrostatic discharge awarenessSufficient care must be taken to protect the terminal against static discharges during the installation. Once the

    unit is installed and connected, these precautions are no longer necessary.

    2.1.5 Factory settingsThe Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values

    and are not necessarily the correct settings for matching the engine/generator set in question. Precautions

    must be taken to check the settings before running the engine/generator set.

    Option G4, G5 and G8, 4189340696 UK General information

    DEIF A/S Page 6 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    7/88

    3. Description of options

    3.1 ANSI numbers

    3.1.1 ANSI

    Function ANSI no.

    Power management -

    3.2 Options G4, G5 and G8

    3.2.1 G4, G5 and G8The options G4, G5 and G8 (power management) are software options and therefore not related to any hard-

    ware apart from the standard-installed hardware.

    The options G4, G5 and G8 are alike in the basic functionality. In the below table the differences are shown:

    Product AGC gen. AGC mains AGC bus tie

    Option G4 X X

    Option G5 X X X

    Option G8 X

    This means that all functionalities available in the G4 and G8 options will also be available in the G5 option,

    but all power management functionalities regarding the mains connections and the sequences handling the

    mains are not available in the G4 option, and only generator fulctionality will be available in the G8 option.

    As the basic power management functions are similar in the three options, it will be possible to mix controllers

    specified with one of the three options in the same application.

    Option G4, G5 and G8, 4189340696 UK Description of options

    DEIF A/S Page 7 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    8/88

    A number of AGC units are being used in the power management application, i.e. one for each mains breaker

    and tie breaker (AGC mains unit), if installed, one for each bus tie breaker (AGC bus tie unit) and one for

    each generator (AGC generator unit). All units communicate by means of an internal CANbus connection.

    The AGC mains unit includes the power management option and can therefore only be used with option G5

    applications. The generator AGC unit must be specified with either option G4, G5 or G8, because this unit

    can be used in single genset applications and in power management applications.

    Option G4, G5 and G8, 4189340696 UK Description of options

    DEIF A/S Page 8 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    9/88

    3.3 Terminal description

    3.3.1 Description of terminalsThe CANbus interface for the internal communication between AGC units in a G4/G5/G8 application is placed

    on the engine interface PCB in slot #7.

    Term. Function Technical data Description

    98 +12/24V DC 12/24V DC +/-30% DC power supply/common for 118

    99 0V DC

    100 MPU input 2-70V AC/10-10.000 Hz Magnetic pick-up

    101 MPU GND

    102 A 0(4)-20 mA

    Digital

    Pt100Pt1000

    VDO

    0-40V DC

    Multi-input 1

    103 B

    104 C

    105 A Multi-input 2

    106 B

    107 C

    108 A Multi-input 3

    109 B

    110 C

    111 Com. Common Common for terminals 112-117

    112 Digital input 112 Optocoupler Configurable

    113 Digital input 113 Optocoupler Configurable114 Digital input 114 Optocoupler Configurable

    115 Digital input 115 Optocoupler Ext. engine failure/configurable

    116 Digital input 116 Optocoupler Start enable/configurable

    117 Digital input 117 Optocoupler Running feedback/configurable

    118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120

    119 NO Relay24V DC/5 A Run coil

    120 NO Relay24V DC/5 A Start prepare

    121 Com. Relay250V AC/8 A Crank (starter)

    122 NO

    123 Com. Relay24V DC/5 A Stop coil w/wire failure detection

    124 NO

    A1 CAN-H CANbus interface A

    A2 GND

    A3 CAN-L

    B1 CAN-H CANbus interface B

    B2 GND

    Option G4, G5 and G8, 4189340696 UK Description of options

    DEIF A/S Page 9 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    10/88

    Term. Function Technical data Description

    B3 CAN-L

    In menus 7540 and 7550, you can choose which CANbus interface you wish to use for internal communica-

    tion. For CANbus redundancy it is possible to use both communication interfaces.

    If the LED marked "CAN B" on the main unit is alive, then the CANbus port(s) is (are) switched

    on.

    3.4 Breaker feedbacks

    3.4.1 Generator breakerThe feedbacks of the generator breaker must always be connected (terminals 26 and 27).

    3.4.2 Mains breaker (MB) feedback

    MB present: The feedbacks of the mains breaker must always be connected (terminals 24 and 25).

    MB not present: Selected in the power plant constructor (USW).

    When no MB is represented, the MB open and close relays together with the inputs for MB

    open and close feedbacks (terminals 24 and 25) will be configurable.

    3.4.3 Tie breaker (TB)

    TB present: The feedbacks of the tie breaker must always be connected (terminals 26 and 27).

    TB not present: Selected in the power plant constructor (USW)

    When no TB is represented, the TB open and close relays together with the inputs for TB open

    and close feedbacks (terminals 26 and 27) will be configurable.

    Option G4, G5 and G8, 4189340696 UK Description of options

    DEIF A/S Page 10 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    11/88

    3.5 Wiring diagrams

    3.5.1 DiagramsThe following diagrams show examples with three AGC units connected, e.g. one AGC mains and two gener-

    ator AGC units.

    Multi-line 2

    CANbus interface 1

    A1 A2 A3

    H GND L

    Multi-line 2

    CANbus interface 1

    A1 A2 A3

    H GND L

    Multi-line 2

    CANbus interface 1

    A1 A2 A3

    H GND L

    120 120

    Multi-line 2

    CANbus interface 2

    B1 B2 B3

    H GND L

    Multi-line 2

    CANbus interface 2

    B1 B2 B3

    H GND L

    Multi-line 2

    CANbus interface 2

    B1 B2 B3

    H GND L

    120 120

    Multi-line 2

    CANbus interface 1

    A1 A2 A3

    H GND L

    Multi-line 2

    CANbus interface 2

    B1 B2 B3

    H GND L

    Multi-line 2

    CANbus interface 1

    A1 A2 A3

    H GND L

    120 120

    As you can see from the last example, it is possible to mix CANbus interface 1 and 2.

    For distances above 300 metres we recommend to use a CAN to fibre converter.

    Do not connect the cable shield to the GND terminal of the AGC units.

    Option G4, G5 and G8, 4189340696 UK Description of options

    DEIF A/S Page 11 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    12/88

    4. Functional description

    4.1 Power management functions

    4.1.1 Description of functionsIn the following chapter, the power management functions of the AGC are listed.

    Plant modes:

    Island mode (no mains unit)

    Automatic Mains Failure (needs mains unit)

    Fixed power/base load (needs mains unit)

    Peak shaving (needs mains unit)

    Load takeover (needs mains unit)

    Mains power export (needs mains unit)

    Display: Mains unit display showing mains breaker and tie breaker

    Generator unit showing generator and generator breaker

    Power management functions:

    Load-dependent start/stop

    Priority selection

    Manual

    Running hours

    Fuel optimisation

    Ground relay control

    ATS control

    Safety stop (fail class = trip and stop)

    Load management Multiple mains support

    Secured mode

    Quick setup/broadcast

    Base load

    Heavy consumer (HC)

    Asymmetric load sharing (LS)

    Common PF control

    CAN flags

    Please refer to the Designers Reference Handbook for standard functions not relating to the

    power management option.

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 12 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    13/88

    4.2 Terminal str ip overview

    4.2.1 AGC generator unit

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 13 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    14/88

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 14 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    15/88

    4.2.2 AGC mains unit

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 15 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    16/88

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 16 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    17/88

    4.2.3 AGC bus tie unit

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 17 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    18/88

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 18 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    19/88

    4.3 Appl ications

    4.3.1 Application possibili tiesThe G4 and G5 options can be used for the applications listed in the table below. The G8 option can only be

    used for an island application with DG units.

    Appl ication Drawing below Comment

    Island operation Island mode plant Multiple gensets

    Automatic Mains Failure Parallel with 1-16 mains No back synchronising

    Automatic Mains Failure Parallel with 1-16 mains With back synchronising

    Automatic Mains Failure ATS plant, multiple start Multiple start system

    Automatic Mains Failure ATS plant, mains unit Mains unit installed

    Fixed power Parallel Also called base load

    1-16 mains units

    Mains power export Parallel 1-16 mains units

    Load takeover Parallel 1-16 mains units

    Peak shaving Parallel 1-16 mains units

    Refer to the Designers Reference Handbook for description o f the individual genset modes.

    Regarding AC and DC connections fo r the individual applications, please refer to the Installa-

    tion Instructions.

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 19 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    20/88

    4.3.2 Island operation plantIn an application where up to 16 gensets are installed, the AGC will automatically operate in an island mode

    with load-dependent starting and stopping.

    G

    Generator

    breaker

    (GB 1)

    Diesel generator set 1

    Busbar

    G

    Generator

    breaker

    (GB 2)

    Diesel generator set 2

    CANbus

    Controller

    Display 1

    Controller

    Display 2

    If a mains unit is installed and connected (e.g. for preparing future requirements to the application), the island

    mode operation is selected in the mains unit.

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 20 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    21/88

    4.3.3 Parallel with mains plantAn application where a mains breaker is installed together with up to 16 gensets is shown below.

    The application also supports a redundant mains unit.

    The application is shown with a tie breaker, but it is also possible to use the application without a tie breaker.

    The tie breaker can only be placed as shown in the drawing below.

    G

    Generator

    breaker

    (GB 1)

    Diesel generator set 1

    Busbar

    G

    Generator

    breaker

    (GB 2)

    Diesel generator set 2

    CANbus

    Tie

    Breaker

    (GB)

    Mains

    breaker

    (MB)

    Mains

    Consumers

    Controller

    Display 1

    Controller

    Display 2

    Controller

    Display mains

    This one-line diagram is also valid for AMF plants without back synchronising and load take-

    over plants without possibil ity of synchron ising the genset to the mains.

    If no CTs are installed on the AGC mains, a 4-20 mA power transducer TAS-331 can be used

    instead.

    The CT measurements are used when the transducer setup is 4/20 mA = 0/0 kW. The transduc-

    er is used when the transducer setup is changed from 0/0 kW.

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 21 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    22/88

    4.3.4 Dual mains plantAn application with two mains breakers installed together with up to 16 gensets is shown below.

    The application also supports redundant AGC mains units.

    The application is shown with a tie breaker, but it is also possible to use the application without a tie breaker.

    G

    Generator

    breaker

    (GB 1)

    Diesel generator set 1

    Busbar

    G

    Generator

    breaker

    (GB 2)

    Diesel generator set 2

    CANbus

    Tie

    Breaker

    (GB)

    Mains

    breaker(MB 1)

    Mains 1

    Consumers

    Mains

    breaker(MB 2)

    Mains 2

    Optional Optional

    Controller

    Display 1

    Controller

    Display 2

    Controller

    Display mains 1B

    Controller

    Display mains 2A

    Controller

    Display mains 2B

    Controller

    Display mains 1A

    The tie breaker can only be placed as shown in the drawing.

    In this application it wi ll not be possible to synchronise the tie breaker.

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 22 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    23/88

    4.3.5 ATS plantApplications that use an ATS for switching between mains supply and generator supply are supported as

    well. Two application examples which use an ATS are shown below.

    4.3.6 ATS plant, mult iple start

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 23 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    24/88

    4.3.7 ATS plant, mains unit

    Display

    Tie

    Breaker

    (TB)

    Mains

    Consumers

    Controller

    G

    Diesel generator set 3

    Controller

    Display 3

    G

    Diesel generator set 1

    Busbar

    G

    Diesel generator set 2

    CANbus

    Controller

    Display 1

    Controller

    Display 2

    ATSON/OFF

    Mains okay

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 24 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    25/88

    4.3.8 Multiple mainsAn example of a multiple mains plant is shown below. This is just an example; please refer to the chapter on

    multiple mains for further information about the possible combinations.

    G

    Generator

    breaker

    (GB 1)

    Diesel generator set 1

    Busbar

    G

    Generator

    breaker

    (GB 2)

    Diesel generator set 2

    CANbus

    Tie

    breaker

    (TB 17)

    Mains

    breaker

    (MB 17)

    Mains 17

    Consumers

    BTB 33

    G

    Generator

    breaker

    (GB 3)

    Diesel generator set 3

    BUSBAR

    G

    Generator

    breaker

    (GB 4)

    Diesel generator set 4

    CANBUS

    Tie

    breaker

    TB 18)

    Mains

    breaker(MB 18)

    Mains 18

    Consumers

    Controller

    Display 1

    Controller

    Display 2

    Controller

    Display 3

    Controller

    Display BTB 33

    Controller

    Display 4

    Controller

    Display mains 17

    Controller

    Display mains 18

    Option G4, G5 and G8, 4189340696 UK Functional description

    DEIF A/S Page 25 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    26/88

    5. Display units

    5.1 DU for opt ion G5

    5.1.1 Option G5 displaysThree displays exist for the option G5.

    See the Designers Reference Handbook or the Operators Manual for detailed information

    about push-button functions and LED indication.

    5.2 Generator uni t display

    5.2.1 Display

    Automatic Gen-set Controller

    multi-line AGC

    VIEW

    LOG

    Auto

    Alarm Inh.

    Self check ok

    Power

    SEL

    BACK

    MODE

    JUMP

    START

    INFO

    STOP

    Alarm

    Alarm

    OnRun

    G

    Load

    Option G4, G5 and G8, 4189340696 UK Display units

    DEIF A/S Page 26 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    27/88

    5.3 Mains uni t display

    5.3.1 Display

    Automatic Gen-set Controller

    VIEW

    LOG

    Auto

    Alarm Inh.

    Self check ok

    Power

    SEL

    BACK

    MODE

    JUMP

    START

    INFO

    STOP

    Alarm

    Alarm

    multi-line AGC MAINS

    On On

    Load

    5.4 BTB unit display

    5.4.1 Display

    Automatic Gen-set Controller

    multi-line AGC BUS TIE

    VIEW

    LOG

    Auto

    Alarm Inh.

    Self check ok

    Power

    SEL

    BACK

    On

    INFO

    JUMP

    Alarm

    Alarm

    MODE

    Option G4, G5 and G8, 4189340696 UK Display units

    DEIF A/S Page 27 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    28/88

    6. Power management setup

    6.1 Init ial power management setup

    6.1.1 How to set upThe AGC is set up using the display and the PC utility software.

    6.1.2 Display setupEnter the menu 9100 using the JUMP push-button. Select one of the following AGC types:

    1. Mains unit

    2. DG unit

    3. BTB unit

    When this setting is adjusted, the device returns to factory settings! Therefore this must be

    changed prior to other adjustments.

    Enter the menu 9170 using the JUMP push-button. Select "CAN protocol 2" for a multi mains functionality.

    Select "CAN protocol 1" for dual mains or single applications.

    An alarm appears i f CAN protocol 2 is needed.

    6.1.3 PC software setupThe communication ID must be adjusted in the utility software for each of the AGC units. In the screen shot

    below, the internal communication ID is set to 1.

    The numbering of the communication IDs must always start from the lowest number, so an application always

    includes a DG with ID 1. The principle also applies to the AGC mains where the numbering starts from ID 17and to the BTB units where the numbering starts from ID 33.

    6.1.4 Application designThe application is designed through the utility software. Please select configuration.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 28 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    29/88

    Select a new application and adjust the settings in this dialogue box.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 29 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    30/88

    Description Comments

    Product

    type

    Select AGC. PPM is a power management system for marine use.

    Plant

    type

    Select between

    Single DG

    Standard

    Dual mains

    Genset group

    plant

    Genset group

    Use "single DG" if option G5 is not selected (or if single functionality is

    needed for a G5 AGC).

    Use "standard" if a power management application is needed.

    Use "dual mains" if the power management application with two mains

    units known from version 3.0-3.2 are to be used.

    Genset group plant and genset group are used for power plants con-

    sisting of 17-256 gensets in the same application. Contact

    [email protected] further information.

    Config-

    uration

    selec-

    tion

    The AGC is able to in-

    clude four applications.

    One of these can be

    active.

    Write a proper name of

    your application.

    Press "Yes" in the pop-up window to set the application to active when

    downloading it to the AGC.

    It is possible to see which application is active when the USW is con-

    nected to the AGC.

    Bus tie

    options

    Select "Wrap busbar"

    if the BTBs are con-

    nected in a ring.

    CAN

    line op-

    tions

    CAN line A: Connect

    A1-A3.

    CAN line B: Connect

    B1-B3.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 30 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    31/88

    Now the application can be designed using the section control panel.

    For each area it is defined whether a generator and a mains is present, and the number and type of breakers.

    6.2 Remove unit from PM

    6.2.1 Possibi lit iesIf one or more units have to be taken out of the power management system, the following possibilities exist

    depending on the situation.

    6.2.2 Auxil iary supply OFFThe auxiliary supply must be removed from the AGC. This means that a CANbus alarm occurs on the other

    AGCs. These alarms appear in a 2 DG plant where ID 2 is powered down:

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 31 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    32/88

    Alarms Functioning unit (ID 1)

    System alarm Failed CAN tx line

    System alarm CAN ID 2 MISSINGMenu 7533 Miss. all units

    Menu 7535 Any DG missing

    The alarms will be present at all times during the failure. A reconfiguration of the power plant is required to

    remove the alarms.

    6.2.3 Quick setupNormally, the quick setup function is only used for simple rental applications. It only requires a few settings to

    be running, and these settings can be made via the DU-2 display on the AGC, so no utility software is nee-

    ded.

    For more details, please refer to the chapter "Quick setup" in this document.

    The mode changes according to the setting in CAN failure mode (menu 7532).

    When the AGC is reconnected, the ID will automatically be enabled again in the other units when the ID has

    been recognised. If the AGC that is reconnected is a new unit with the factory settings set in the parameter

    file, a "Duplicate CAN ID" error message will appear. When an ID is chosen for the new unit, and the ID chos-

    en is already active in another device, the error message "CAN ID not available" will appear, and the ID is

    reset to the start value.

    6.2.4 Auxil iary supply ONIf a failure appears on the CANbus lines of an AGC, the following alarms appear in the example where a fail-

    ure appears at ID 2:

    Alarms Defective unit Funct ioning unit

    System alarm Failed CAN tx line Failed CAN tx line

    System alarm CAN ID 1 MISSING CAN ID 2 MISSING

    Menu 7533 Miss. all units Miss. all units

    Menu 7535 Any DG missing Any DG missing

    If the auxiliary supply of the unit where the CANbus is not functioning is connected, the AGC can be adjustedto another mode than AUTO. In that case the genset will not take part in the power management routines.

    Semi-automatic start or automatic start is possible if the mode is changed to SEMI or AUTO

    mode. The only exception to this is when BLOCK mode is selected on a genset AGC. In this

    situation the GB can be closed withou t allowance from the power management system.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 32 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    33/88

    6.3 CANbus failure handling

    6.3.1 CAN failure modeIn case of a CAN failure on the internal CAN controlling the power management, the system can be set up in

    different ways. In menu 7530 it is decided how the power management system will react in case of a CAN

    failure.

    1. If "MANUAL" is selected, all AGC units will change mode to manual mode, and this way the regula-

    tors will have no reaction, and it will not be possible to close any breakers.

    Example 1:

    A break on the CAN line is made between ID1 and ID2 shown below.

    Both gensets are running and all breakers are closed.

    When the break occurs, the regulators will stop on both gensets, but they will stay online. As the gensetshave no valid information about the other unit, over time a blackout can occur as no load sharing is active

    between the units.

    If for example six gensets are available in an island application, and the CAN failure happens between ID3

    and ID4, the load sharing will still be disabled between all units, as it is the manual mode which is activated.

    If the CAN error happens when no gensets are running, it will block the whole system and it will not be possi-

    ble to start any gensets, before the CAN error has been fixed.

    G

    Generator

    breaker

    (GB 1)

    Diesel generator set 1

    Busbar

    G

    Generator

    breaker

    (GB 2)

    Diesel generator set 2

    CANbus

    Controller

    Display 1

    Controller

    Display 2

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 33 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    34/88

    2. If "SEMI-AUTO" is selected, all AGC units will change mode to semi-auto mode, and this way the

    regulators will continue to regulate the load on the gensets which are still "visible" on the internal

    CAN communication. This means that in the example with six gensets, the load sharing will contin-

    ue between the units which are still connected (ID1-ID3 and ID4-ID6).

    If the CAN error happens when no gensets are running, it will not block the whole system, and it will be possi-

    ble to start all the gensets in SEMI-AUTO mode, even though the CAN error has not been fixed.

    A message will be shown in the status line "BLACKOUT ENABLE" on the display.

    If the CANbus error is p resent and no generator breakers are closed, it wil l be possible to

    close two breakers on the same busbar, which may result in fatal damage to the whole system.

    It is recommended to use the analogue load sharing (option G3) and an interlock system to

    prevent this situation.

    3. If "No mode change" is selected, all AGC units will stay in the mode they were in before the failure

    appeared.

    This setting makes it possible to keep the system in Auto mode in case of a CAN failure, however, the faulty

    unit will not be a part of the power management, since it cannot send or receive status and commands on the

    CANbus.

    If this selection is used, it is recommended to use the CANbus fail class settings to disconnect the faulty units

    (refer to the "CANbus fail class" in this chapter).

    If the CANbus error is p resent and no generator breakers are closed, it wil l be possible to

    close two breakers on the same busbar, which may result in fatal damage to the whole system.

    It is recommended to use the analogue load sharing (option G3) and an interlock system to

    prevent this situation.

    6.3.2 Redundant CANbus communicationIt is possible to use two CANbus communication lines; CAN I/F 1 (A1/A2/A3) and CAN I/F 2 (B1/B2/B3). This

    way, the communication will be redundant, and if one of the CANbus communication lines are damaged, the

    application will still continue in Auto mode with full functionality.

    6.3.3 CANbus alarmsThe following alarms can be displayed on an AGC unit in case of CANbus communication failures:

    CAN A ID X MISSING

    The AGC unit has lost CANbus communication to one or more CAN IDs on CANbus I/F A.

    CAN A MAINS X MISSING

    The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F A.

    CAN A BTB X MISSING

    The AGC unit has lost CANbus communication to the AGC BTB unit on CANbus I/F A.

    CAN B ID X MISSING

    The AGC unit has lost CANbus communication to one or more CAN IDs on CANbus I/F B.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 34 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    35/88

    CAN B MAINS X MISSING

    The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F B.

    CAN B BTB X MISSING

    The AGC unit has lost CANbus communication to the AGC BTB unit on CANbus I/F B.

    MISSING ALL UNITS

    The AGC unit has lost the CANbus communication to all the other units. The fail class set in menu 7533

    will be executed.

    FATAL CAN ERROR

    The AGC unit has lost CANbus communication to more than one CAN ID on the CANbus line. The fail

    class set in menu 7534 will be executed.

    ANY DG MISSING

    The AGC unit has lost CANbus communication to one of the generator CAN IDs on the CANbus line. Thefail class set in menu 7535 will be executed.

    ANY MAINS MISSING

    The AGC unit has lost CANbus communication to one of the mains CAN IDs on the CANbus line. The fail

    class set in menu 7536 will be executed.

    ANY BTB MISSING

    The AGC unit has lost CANbus communication to one of the BTB CAN IDs on the CANbus line(s). The

    fail class set in menu 7536 will be executed.

    6.3.4 CANbus fail classIn menu 7530 it is possible to set a fail class of the following CANbus alarms:

    Missing all units

    Fatal CAN error

    Any DG missing

    Any mains missing

    By using these settings, it is possible to disconnect the faulty units and in this way keep the system running in

    Auto mode. (Depends on the setting 7532).

    For a general description of "Fail class" please refer to the Designers Reference Handbook.

    6.4 Quick setup

    6.4.1 Quick setupThis function is made to provide an easy user interface for applications where it is vital for the end-user to be

    able to change the application quickly and easily.

    It is often applications for the rental market that need this flexibility, and therefore there are some limitations

    as to which applications that can be handled through the quick setup menu.

    The following applications can be handled through the quick setup menu.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 35 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    36/88

    Island applications

    Simple applications with connection to one mains

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 36 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    37/88

    6.4.2 LimitationsIn most cases, the rental applications are very simple applications, and therefore there are some limitations

    that have to be considered when using the quick setup menu:

    It will not be possible to have any AGC bus tie units in the application.

    It will not be possible to set up a "dual mains" application through the quick setup menu.

    This function is made to facilitate change of a plant configuration without AGC BTB units. Entering the quick

    setup menu 9180 via the DU-2 display makes it possible to add or remove a genset without the use of utility

    software. It is only possible to do the same basic setup as through the "application configuration" in the utility

    software.

    The functions marked with clear text in the screen shots below can be accessed through the quick setup

    menu.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 37 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    38/88

    6.5 9180 Quick setup

    6.5.1 9180 Quick setup9181 Mode

    OFF: When the mode menu is set to "OFF", the existing application that is about to have this genset

    included will not look for this new genset. This will give the operator time to connect all wiring

    and to do the basic setup of the genset.

    Setup

    Plant:

    When the mode menu is set to "Setup Plant", the new AGC will receive the application config-

    uration from the other units in the plant. The new AGC will then notify the rest of the applica-

    tion that a new ID is available on the line. If the ID of the new AGC already exists, the new

    AGC will based on the ID numbers in the application configuration have the highest ID + 1

    assigned. This new ID will then be included in the application configuration in all the other

    AGCs. During this process, the existing application will be able to continue running and will not

    be affected by the upgrade of the system.

    The new AGC will automatically go to block mode to ensure that it is in a safe mode. When the

    setup is done, the end-user must decide in which running mode the added genset is to run.

    If there are already 16 gensets on the CAN line and a new AGC tries to connect to the plant, an

    alarm text, "No IDs available", will appear.

    Setup

    Stand-

    alone:

    When the mode menu is set to "Setup Stand-alone", the AGC will change the application

    configuration, so it will no longer be a part of the application. When the ID is removed from

    the application, the new application will be broadcasted to the other AGCs. The IDs of the

    existing gensets in the application will maintain their ID, as a rearrangement could lead to

    unnecessary starting and stopping of the gensets.

    If the genset that is to be removed is running, it will not be possible/allowed to continue the

    process until the genset has stopped. If it is attempted to disconnect, an info text, "Quick set-

    up error", will appear.

    If "Setup Stand-alone" is activated when the genset is running, an info text, "Quick setup er-

    ror" , will appear.

    If an AGC BTB is detected in the application, an indicating alarm, "Appl. no t possible", will ap-

    pear.

    Change of setup from standard to single DG unit: When disconnecting a standard AGC unit i n

    a system, it is important to change the menu 9181, plant setup. After disconnecting, the AGC

    unit will become a single DG.

    6.5.2 9190 Application broadcastThis function makes it possible to broadcast an application over the CAN line from one AGC to all units

    present in the application. It takes one operation to activate the broadcast function. It can be done in two

    ways:

    1. By sending the application.

    2. By sending the application and activating it.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 38 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    39/88

    Menu 9191 Enable

    OFF: When it is set to OFF, no broadcast will be made.

    Broadcast: Broadcast of the selected application in menu 9192 will be sent to the units in the

    application.

    Broadcast + Acti-

    vate

    Broadcast is activated and the application in menu 9192 will be broadcasted and

    activated in all units.

    Menu 9192 Application

    Applications 1-4 can be drawn in the utility software.

    The following pop-up windows in the utility software will guide you through the broadcast.

    Option G4, G5 and G8, 4189340696 UK Power management setup

    DEIF A/S Page 39 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    40/88

    7. Power management functions

    7.1 Command unit

    7.1.1 Command unitThe power management system is a multi-master system. In a multi-master system, the available generator

    units automatically perform the power management control. This means that the system never depends on

    only one master unit.

    If for instance one unit ID is disabled, and this was the command unit, then the next available unit will take

    over the command functions.

    The above also applies to the AGC mains units in that case the command unit is called Mains Command

    Unit (MCU).

    The command unit cannot be selected by the operator. It is automatically selected when a power manage-

    ment setting is accessed.

    7.2 Load-dependent starting and stopping

    7.2.1 Starting and stoppingThe purpose of this function is to ensure that sufficient power is always available on the busbar. This means

    that the gensets will automatically be started and stopped in order to let only the sufficient number of gensets

    run. This optimises the fuel economy and the maintenance intervals.

    The load-dependent start/stop function is active when the plant is in AUTO mode. The starting and stopping

    of the gensets is automatically carried out according to the adjusted setpoints and priority selection.

    The load-dependent start/stop function can be selected as:

    Rated power setpoint (P) [kW]

    Apparent power setpoint (S) [kVA]

    Actual or load percentage value [%]

    The load-dependent starting and stopping can be selected to base on either produced power calculation (%)

    or available power calculation (P or S).

    The easiest way is to use produced power calculation; however, this method is not suited for systems with

    three or more generators as regards fuel savings and saving running hours.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 40 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    41/88

    7.2.2 TerminologyThe table shows the abbreviations used.

    Short Description Comment

    PAVAILABLE Available power PTOTAL- PPRODUCED

    PTOTAL Total power PNOMINALof running sets with GBs closed

    PPRODUCED Produced power

    PNOMINAL Nominal power

    PNOMINAL-STOP Nominal power of the genset to stop Priority-dependent

    Deactivate load-dependent stop

    The load-dependent stop can be deactivated through M-logic, should this be preferred. This is necessary e.g.

    to allow operators to start the factory load after a blackout before the normal load-dependent operation canbe started.

    In the example below, the function is activated with terminal 43. Now the operator can switch the load-de-

    pendent stop ON or OFF with a switch connected to terminal 44.

    Produced power method

    This method is in effect if % power is selected in menu 8880 as basis for the start/stop calculation.

    If the load % of a generator exceeds the "Start next" setpoint, the start sequence of the lowest priority genera-

    tor in stand-by will be initiated.

    If the load % of a generator drops below the "Stop next" setpoint, the stop sequence of the running generator

    with the highest priority number will be initiated.

    If the load of the plant decreases so much that the generator with the highest priority number can be stopped

    and an available power of at least the stop setpoint in % is available, then the stop sequence of this generator

    will be initiated.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 41 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    42/88

    -200

    -100

    0

    100

    200

    300

    400

    500

    kW% load

    Time

    1 2 3

    Load dep. start90

    10Load dep. stop

    1 Load increase

    2 Load start delay runs out; PMS start command

    3 Stand by genset running and connecting to the busbar

    Power produced

    % power

    Available power method

    This method is in effect if P [kW] or S [kVA] is selected as basis for the start/stop calculation.

    Independent of the selection (P [kW] or S [kVA]), the functionality is basically identical; therefore the example

    of the functionality below will be given for the load-dependent start function with selected rated power (P) val-

    ue.

    The apparent power setpoint is typically selected if the connected load has an inductive character and the

    power factor is below 0.7.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 42 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    43/88

    Description

    This drawing illustrates the terms used.

    PNOM1500 kW

    PNOM1000 kW

    PNOM1000 kW100%

    70%

    DG1 DG2 DG3

    = 2450 kW

    = 1050 kW (available power)

    = 3500 kW ~ 100%

    Consumed power at the busbar

    Nominal power

    The nominal power is the rated power of the genset that can be read on the type plate of the generator.

    Total power

    The total power is the summation of the rated nominal power of each individual genset. In the example above

    the plant consists of three DGs:

    DG1 = 1500 kW

    DG2 = 1000 kW

    DG3 = 1000 kW

    That is a total of 3500 kW

    Produced power

    The produced power is defined as the existing load on the busbar. In the example above the produced power

    is indicated as the hatched area, and the total of the three gensets = 2450 kW.

    Available power

    The available power is the difference between the maximum possible power produced by the gensets and the

    actual produced power.

    In the example above the plant consists of three gensets, in total 3500 kW. The load consumes 2450 kW in

    total. Since the total load PTOTALis 3500 kW, and the produced load PPRODUCEDis 2450 kW, then the avail-

    able power PAVAILABLEis 1050 kW, meaning that the gensets can handle this load if it should be added to

    the busbar.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 43 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    44/88

    7.2.3 Principle available power methodOne genset is running and is supplying the load. The load increases which means that the available power/

    apparent power decreases. At a certain time the load has increased so much that only a little amount of pow-er/apparent power is available, and the next priority genset will be started in order to increase the amount of

    available power/apparent power.

    When the load drops, the available power/apparent power will increase. When the available power/apparent

    power has increased above the stop level plus the nominal power of the last priority genset, then the last pri-

    ority genset will be stopped. Please note that the nominal power of the genset to be stopped is added to the

    adjusted stop level. The reason is that otherwise the available power/apparent power would immediately drop

    below the start level again.

    Example:

    If the adjusted stop level is 200 kW (PSTOP= 200 kW), and the genset with the last priority is 1000

    kW, it is necessary that the available power reaches 1200 kW, because the available power will be

    reduced with 1000 kW immediately after the last priority genset is stopped.

    7.2.4 Principle percentage methodOne genset is running and is supplying the load. The load increases which means that the % load increases.

    At a certain time the load has increased so much that the load % start will start up the next priority genset in

    order to take some of the load.

    When the load drops, the produced power will decrease. When the produced power has decreased below the

    stop level plus the nominal power of the last priority genset, then the last priority genset will be stopped.

    Please note that the nominal power of the genset to be stopped is added to the adjusted stop level. The rea-

    son is that otherwise the produced power would immediately drop below the start level again.

    Example:

    If the adjusted stop level is 10% (100 kW produced power), and the genset with the last priority is

    1000 kW, the last priority generator will produce 20% (200 W) after stop. It is necessary that the start

    level is above this value, otherwise an ongoing starting and stopping will take place.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 44 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    45/88

    7.2.5 Adjust ing load-dependent startIn the example below the available power is 200 kW. When the load increases, the available power drops

    below the start limit. The stand-by genset will start when the start timer runs out, and after the synchronisingthe available power increases (in this example to 500 kW).

    -200

    -100

    0

    100

    200

    300

    400

    500

    P-Avail. on busbar

    Time

    1 2 3

    Load start limit

    1 Load increase

    2 Load start delay runs out; PMS start command

    3 Stand by genset running and connecting to the busbar

    Measured P-Avail.Predicted P-Avail.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 45 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    46/88

    7.2.6 Adjust ing load-dependent stopIn the example below the available power is 500 kW. When the load decreases, the available power increa-

    ses to 750 kW. The AGC now calculates what happens if the last priority genset is stopped. In the examplebelow the last priority genset is 400 kW which means that it can be stopped, because the available power will

    still be above the stop level.

    Now the difference between the stop level and the available power is 50 kW. This means that only if the gen-

    set, which now has the last priority, is 50 kW, it can be stopped!

    700

    600

    400

    500

    300

    200

    100

    0

    Load decreases

    Load stop delay runs out; PM stop command

    Last priority genset stopped

    Load stop limit

    1

    1

    2

    3

    2 3

    If the order of priorit y is changed, the following must be observed:

    If the priority does not seem to change as expected, it is because the load-dependent stop

    function is not able to stop the lowest priority after having started the new first priorit y. Thatwould cause two DGs to be running at low load instead of one DG.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 46 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    47/88

    7.2.7 Power windowThe difference between the programmed load-dependent start and stop limits forms the power hysteresis be-

    tween the start and stop. This is shown in the diagram below:

    Available power

    at the busbar

    Load-depending start

    Load-depending stop

    Load stop

    limit

    Load start

    limit

    1. DG

    Start

    2. DG

    Start

    3. DG

    Start

    3. DG

    Stop

    2. DG

    Stop

    Power

    window

    PDG1

    PDG2

    PDG3

    PDG3

    PDG2

    7.3 Load management

    7.3.1 Load managementThe function is used to activate a relay when a specific amount of power is available. The purpose of this

    function is to be able to connect load groups when the gensets of the emergency power plant are running.

    In each of the gensets, five levels can be adjusted (menus 8220-8260):

    Available power 1

    Available power 2

    Available power 3

    Available power 4

    Available power 5

    These setpoints can activate a relay when the specific amount of available power is reached. The relay out-

    put can be used for connecting load groups when sufficient power is available. The relays will activate when

    the available power is higher than the setpoint, but be aware that when the load groups are being connected,

    the available power will decrease and the relay(s) deactivate again if the available power is below the set-

    point. So it is necessary to make an external holding circuit.

    The number of available relays is option-dependent.

    The function is not depending on the running modes. The relays will activate in all modes including block. To

    avoid activation, e.g. when the genset is stopped, the inhibit function should be used.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 47 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    48/88

    Regarding the inhibit function, please refer to the Designers Reference Handbook.

    It is possible to adjust different levels of available power in all gensets. This gives the possibility to use sever-

    al load groups if this is necessary.

    Example:

    In the example below, generator #1 is started followed by generator #2. The simplified diagram shows the two

    gensets and two load groups that are being connected by the available power relays R1 and R2 on AGC1.

    G

    Diesel generator set 1

    G

    Diesel generator set 2

    Load

    Group 1

    Trip load group 1

    R1

    K1

    K1Load

    Group 2

    Trip load group 2

    R2

    K2

    K2

    R1 R2

    Multi-line 2 Multi-line 2

    7.3.2 Functionality description (refer to the diagram below)The generator #1 is started, and the timer t1 starts running when the GB1 closes. When the t1 is expired, the

    selected relay activates (R1), and in the example a 200 kW load group is connected. Now the available power

    falls to 300 kW. After some time the generator #2 is started and its generator breaker is synchronised. When

    the GB2 closes, the timer t2 runs. When the timer t2 expires, the selected relay activates (R2), and the sec-

    ond load group of 200 kW is connected. Now the available power falls to 600 kW.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 48 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    49/88

    GB1ON

    t1

    t2

    R1 R2

    200

    1000

    800

    600

    400

    PAVAIL

    kW

    GB2ON

    To connect the load groups, individual relays can be selected on each AGC or on one of the AGC units only.

    7.4 Load sharing

    7.4.1 Load sharingWhen the power management communication is running, the load sharing between the gensets is done byusing the CANbus communication between the AGC units.

    If both CANbus ports are being used (A1-A3 and B1-B3), the communication automatically switches to the

    other port if e.g. A1-A3 is disconnected or faulty. (Please refer to the description of redundant CANbus).

    If both CANbus lines are disconnected or faulty, the AGCs do not automatically switch over to analogue load

    sharing. This has to be set up in M-logic: Use the command "Force analogue loadshare". Now the load shar-

    ing continues based on the signals from terminals 37/38/39. This means that the power management will be

    lost, but the gensets already running will stay stable.

    The option G3 has to be active to have the backup of the analogue load share line.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 49 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    50/88

    7.5 Island ramp up

    7.5.1 Island ramp up with load steps

    Power[kWh]

    Time [sec]GB closed

    Delay,step1

    Power ramp [%/s]

    CAN load share setpoint

    Rampup,read

    fromloadshare

    line S

    tandardload

    sharing

    One step before theload share setpoint is

    reached the ramp upfunction is switched off

    Delay,step2

    Delay,step3

    Delay,step4

    Delay,step5

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 50 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    51/88

    7.6 Fixed power ramp up with load steps

    Power[kWh]

    Time [sec]GB closed

    Delay,step1

    Power ramp[%/s]

    Power Set point

    Rampdown

    Stop signal

    Rampup,read

    Fromloadshare

    line

    Delay,step2

    Delay,step3

    Delay,step4

    Delay,step5

    When menu 2614 is enabled, the power setpoint continues to rise in ramp up steps, determined by menu

    2615, towards the load sharing setpoint. The delay time between each ramp up step will be determined by

    menu 2613. The ramp up will continue until the load sharing setpoint is reached and then switch the regulator

    to standard load sharing mode.

    If the delay point is set to 20% and the number of load steps is set to 3, the genset will ramp to 20%, wait the

    configured delay time, ramp to 40%, wait, ramp to 60%, wait and then ramp to the system setpoint. If the

    setpoint is at 50%, the ramp will stop at 50%.

    7.7 Freeze power ramp

    A way to define the ramp up steps is to use the freeze power ramp command in M-logic.

    Freeze power ramp active:

    1. The power ramp will stop at any point of the ramp, and this setpoint will be kept as long as the function is

    active.

    2. If the function is activated while ramping from one delay point to the other, the ramp will be fixed until the

    function is deactivated again.

    3. If the function is activated while the delay timer is timing out, the timer will be stopped and will not contin-

    ue until the function is deactivated again.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 51 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    52/88

    7.8 ATS appl ications

    Two possibilities are available; the mains unit can either be installed or not.

    7.8.1 AGC mains installed

    See single line diagram for " Parallel with mains plant" .

    In an AMF application the AGC mains will normally operate the mains breaker and thereby make sure that

    the supply is coming from the mains if this is healthy.

    This function allows the AGC to be used in an application where an automatic transfer switch is installed. This

    is known as an ATS.

    In the applications shown as one-line diagrams in the chapter Functional description it can be seen that theATS will take care of the switching between the generator supply and the mains supply.

    If ATS is selected, the AGC has no control over the ATS ("mains breaker").

    Description

    Normally the AGC detects a mains failure based on the voltage and frequency measurement on the mains.

    However, when ATS is selected in menu 7085 it is necessary to use a digital input together with the position

    feedbacks from the ATS. Thus, the mains failure is not detected by the AGC measurements but by the follow-

    ing two requirements:

    1. Alternative start input ON2. ATS (MB) feedback OFF

    To make the AGC detect a mains failure, the alternative start input has to be ON and the MB OFF feedback

    has to be active.

    The input used as "Al ternative start" function is configured in the PC utility software (USW).

    The mains unit will not try to operate the ATS (mains breaker) at all. But it is still necessary that position feed-

    backs are wired up.

    It is possible to have a tie breaker installed. This is useful if more gensets need to be started before supplying

    the load, because the tie breaker will not close until the required number of gensets is available.

    7.8.2 ATS island mode

    See single line diagram for " Island operating plant".

    If this application is needed, the gensets can be started by activating the "auto start/stop" input. The gensets

    will be started and stopped according to the power demand. That is, they will operate in load-dependent start/

    stop mode.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 52 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    53/88

    Be aware that since no tie breaker is installed, it is important that the fir st genset to close on

    the busbar can carry the load. If the load is too high, the genset will be overloaded.

    This application can be combined with the multi start function .

    7.9 Fail class

    The fail classes described in the Designers Reference Handbook are still valid when the power management

    option is selected. In addition to these fail classes the safety stop can be used in the AGC units with power

    management.

    This means that when a trip + stop alarm occurs, the faulty genset will stay on the busbar until the next priori-

    ty genset is started and synchronised to the bus. When the incoming genset has taken the load, the faulty

    genset will ramp down the power, followed by trip of the breaker, cooling down of the engine and finally stop.

    If the faulty genset has the last priority, or no standby gensets are available, then it will stay on the busbar

    and will not trip.

    If no genset can start in a safety stop situation, then the faulty genset will no t be stopped.

    Therefore it is important that the safety stop is backed up, e.g. by a trip and stop alarm or a

    shutdown alarm.

    7.10 Local/remote/timer operation

    The plant can be adjusted to local, remote or timer operation (menu 8021). This selection is done in the com-

    mand unit, i.e. one of the generator units.

    The setting defines how the plant is started while it is in AUTO mode.

    The settings can be changed in M-logic and via display or PC utility software.

    Display Utility SW

    (Parameter setup)

    M-logic

    Local X X X

    Remote start X X X

    Timer start X X -

    The purpose of the selection is to decide whether the plant can be started from the display (local operator),

    from remote (e.g. PLC) or by an internal timer. Remote means that the control can be carried out by activat-

    ing the digital input or through Modbus/Profibus communication.

    7.10.1 Local selectionAll operation is carried out on the display. In island operation any generator unit display can be used, and in

    load takeover, mains power export and fixed power the mains unit display must be used. The plant mode

    must be AUTO.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 53 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    54/88

    7.10.2 Remote select ionThe plant is started using the digital input "auto start/stop" when "remote" is selected.

    Island mode

    In island mode the "auto start/stop" input on any of the generator AGCs can be used for starting the plant.

    However, DEIF recommends to wire up the "auto start/stop" input to all of the AGCs to be sure that the auto-

    matic operation is able to continue even though one of the DGs is taken out for service (power supply discon-

    nected to the AGC).

    In island mode any running mode (MAN, AUTO, SEMI, BLOCK) can be selected on the generator units, and

    the remote start signal is still working for the remaining AGC which is still in AUTO mode.

    Parallel to mains mode

    In load takeover, mains power export and fixed power mode the "auto start/stop" input on the mains unit must

    be used for starting the plant.

    7.10.3 Plant operationThe table shows how the plant is started:

    Plant mode Selection Local Remote

    Island mode Display on generator units Auto start/stop on gen. units

    Fixed power mode Display on mains unit Auto start/stop on mains unit

    Mains power export Display on mains unit Auto start/stop on mains unit

    Load takeover Display on mains unit Auto start/stop on mains unit

    In peak shaving and AMF the automatic operation starts automatically depending on the impor-

    ted power (peak shaving) or mains failures (AMF).

    7.10.4 Timer selectionThe operation of the plant is controlled by up to eight internal command timers which are programmed using

    the PC utility software (USW).

    The function can be used in load takeover, mains power export and fixed power, and the mains unit has to be

    in auto.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 54 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    55/88

    7.10.5 Principle

    Start

    LocalNo

    RemoteNo

    Press stop

    button

    Plant runningPress start

    button

    Yes

    No

    Yes

    Yes

    Local mode

    Stop plant

    No

    No

    Yes

    Start plantAuto

    start/stop

    ON

    Plant running

    Auto

    start/stop

    ON

    Yes

    Yes

    No

    Yes

    Remote mode

    Start plant

    No

    Yes

    No

    Stop plant

    Timer ON

    Plant running Timer ONYes

    No

    Yes

    Timer mode

    Start plant

    No

    Yes

    No

    Stop plant

    Yes

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 55 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    56/88

    7.11 Multi starting gensets

    The multi-start function can be used to determine the number of gensets to start. This means that when the

    start sequence is initiated through push-button, digital input or automatic start, then the adjusted numbers of

    gensets will start.

    This function is typically used e.g. together with applications where a certain number of gensets is required to

    supply the load.

    Example:

    In an AMF application with a tie breaker, the tie breaker must not close before the maximum power is

    available (power capacity setpoint).

    The multi-start function is adjusted in menu 8922-8926.

    7.11.1 Multi-start configurationThe multi-start function can be adjusted to operate with two different settings. These settings consist of set-

    points for how many gensets to start and the minimum number of running gensets.

    It is possible to switch between the settings using M-Logic or menu 8924.

    Setpoint 1 Setpoint 2

    Multi-start (numbers to start) 8922 8925

    Min no. running 8923 8926

    Default setting

    Star t condi tion Setpoint 1 Setpoint 2 Default set ting of DGs to star t

    Emergency operation Mains failure - X Start all DGs

    Normal operation No mains failure X - Auto calculate

    The default setting of the selection between setpoint 1 and setpoint 2 is made so the setpoint 1 is adjusted to

    "Auto calculation" and is used in all modes except for AMF. Setpoint 2 will automatically be selected in case a

    mains failure occurs (this is adjusted in M-logic). Setpoint 2 is adjusted to 16 gensets which means that all

    available gensets will start when the mains failure occurs.

    Option G4, G5 and G8, 4189340696 UK Power management functions

    DEIF A/S Page 56 of 88

  • 7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13

    57/88

    The default setting can be changed, if convenient.

    7.11.2 Numbers to startThe numbers to start (menu 8922/8925) can be selected depending on the number of DGs available. The

    load-depending start and stop function will be active as soon as the generator breakers are closed or, if a tie

    breaker is installed, as soon as the tie breaker is closed. It is possible to adjust the number of gensets, or an

    auto calculation can be selected.

    If it is needed to delay the load-dependent start and stop function, it can be done through the

    M-logic funct ion.

    Auto calculation

    When auto calculation is selected, the sufficient number of gensets will be started as soon as the start com-

    mand is given. This is not depending on the plant mode.

    Example:

    In a four DG plant each generator is rated with 1000 kW. The setpoint for load-dependent start (menu

    8001) is adjusted to 100 kW.

    If a start command is given in fixed power mode and the setpoint is 2000 kW, then three gensets will

    be started immediately and the fourth genset will remain stopped. Three gensets will be started be-

    cause two gensets are requested to supply the load (2*1000 = 2000 kW) and the load-dependent start

    function requests the third genset.

    7.11.3 Minimum numbers runningThe multi starting function can be combined with the setting of a minimum number of running gensets (menu

    8923/8926). This means that the load-dependent stop function is disregarded when only the specific number

    of gensets is running. This is also the situation even though the load would justify a load-dependent stop