Option G4, G5 and G8, 4189340696 UK_2012.07.13
-
Upload
gustavo-pereira -
Category
Documents
-
view
217 -
download
0
Transcript of Option G4, G5 and G8, 4189340696 UK_2012.07.13
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
1/88
DEIF A/S Frisenborgvej 33 DK-7800 Skive
Tel.: +45 9614 9614 Fax: +45 9614 9615
[email protected] www.deif.com
Automatic Genset Controller, AGC
DESCRIPTION OF OPTIONS
Options G4, G5 and G8
Power management Functional description
Display units
Power management setup
Power management functions
Parameter lists
Document no.: 4189340696CSW version:
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
2/88
1. Delilmi tation1.1. Scope of options G4, G5 and G8...........................................................................................................5
2. General information
2.1. Warnings, legal information and safety..................................................................................................62.1.1. Warnings and notes ......................................................................................................................62.1.2. Legal information and disclaimer ..................................................................................................6
2.1.3. Safety issues ................................................................................................................................6
2.1.4. Electrostatic discharge awareness ...............................................................................................6
2.1.5. Factory settings ............................................................................................................................6
3. Descrip tion of opt ions3.1. ANSI numbers........................................................................................................................................7
3.1.1. ANSI..............................................................................................................................................7
3.2. Options G4, G5and G8..........................................................................................................................7
3.2.1. G4, G5 and G8..............................................................................................................................73.3. Terminal description...............................................................................................................................9
3.3.1. Description of terminals.................................................................................................................9
3.4. Breaker feedbacks...............................................................................................................................103.4.1. Generator breaker.......................................................................................................................10
3.4.2. Mains breaker (MB) feedback......................................................................................................10
3.4.3. Tie breaker (TB)...........................................................................................................................103.5. Wiring diagrams...................................................................................................................................11
3.5.1. Diagrams.....................................................................................................................................11
4. Functional description4.1. Power management functions..............................................................................................................12
4.1.1. Description of functions ..............................................................................................................12
4.2. Terminal strip overview........................................................................................................................13
4.2.1. AGC generator unit......................................................................................................................13
4.2.2. AGC mains unit............................................................................................................................15
4.2.3. AGC bus tie unit...........................................................................................................................174.3. Applications..........................................................................................................................................19
4.3.1. Application possibilities................................................................................................................19
4.3.2. Island operation plant..................................................................................................................20
4.3.3. Parallel with mains plant..............................................................................................................21
4.3.4. Dual mains plant..........................................................................................................................22
4.3.5. ATS plant.....................................................................................................................................234.3.6. ATS plant, multiple start...............................................................................................................23
4.3.7. ATS plant, mains unit...................................................................................................................24
4.3.8. Multiple mains..............................................................................................................................25
5. Display units5.1. DU for option G5..................................................................................................................................26
5.1.1. Option G5 displays .....................................................................................................................26
5.2. Generator unit display..........................................................................................................................265.2.1. Display.........................................................................................................................................26
5.3. Mains unit display.................................................................................................................................275.3.1. Display.........................................................................................................................................27
5.4. BTB unit display...................................................................................................................................27
5.4.1. Display.........................................................................................................................................27
6. Power management setup6.1. Initial power management setup..........................................................................................................28
6.1.1. How to set up...............................................................................................................................28
6.1.2. Display setup...............................................................................................................................28
6.1.3. PC software setup.......................................................................................................................28
6.1.4. Application design........................................................................................................................28
Option G4, G5 and G8, 4189340696 UK
DEIF A/S Page 2 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
3/88
6.2. Remove unit from PM...........................................................................................................................316.2.1. Possibilities..................................................................................................................................31
6.2.2. Auxiliary supply OFF....................................................................................................................31
6.2.3. Quick setup..................................................................................................................................32
6.2.4. Auxiliary supply ON.....................................................................................................................326.3. CANbus failure handling.......................................................................................................................336.3.1. CAN failure mode........................................................................................................................33
6.3.2. Redundant CANbus communication............................................................................................34
6.3.3. CANbus alarms............................................................................................................................34
6.3.4. CANbus fail class.........................................................................................................................35
6.4. Quick setup..........................................................................................................................................35
6.4.1. Quick setup..................................................................................................................................356.4.2. Limitations....................................................................................................................................37
6.5. 9180 Quick setup.................................................................................................................................38
6.5.1. 9180 Quick setup.........................................................................................................................38
6.5.2. 9190 Application broadcast.........................................................................................................38
7. Power management functions
7.1. Command unit......................................................................................................................................407.1.1. Command unit.............................................................................................................................40
7.2. Load-dependent starting and stopping.................................................................................................40
7.2.1. Starting and stopping...................................................................................................................407.2.2. Terminology.................................................................................................................................41
7.2.3. Principle available power method.............................................................................................44
7.2.4. Principle percentage method....................................................................................................44
7.2.5. Adjusting load-dependent start....................................................................................................45
7.2.6. Adjusting load-dependent stop....................................................................................................46
7.2.7. Power window..............................................................................................................................477.3. Load management...............................................................................................................................47
7.3.1. Load management.......................................................................................................................47
7.3.2. Functionality description (refer to the diagram below).................................................................48
7.4. Load sharing.........................................................................................................................................49
7.4.1. Load sharing ...............................................................................................................................497.5. Island ramp up......................................................................................................................................50
7.5.1. Island ramp up with load steps....................................................................................................50
7.6. Fixed power ramp up with load steps...................................................................................................51
7.7. Freeze power ramp..............................................................................................................................51
7.8. ATS applications..................................................................................................................................52
7.8.1. AGC mains installed....................................................................................................................527.8.2. ATS island mode.........................................................................................................................52
7.9. Fail class..............................................................................................................................................53
7.10. Local/remote/timer operation..............................................................................................................53
7.10.1. Local selection...........................................................................................................................53
7.10.2. Remote selection.......................................................................................................................54
7.10.3. Plant operation...........................................................................................................................547.10.4. Timer selection..........................................................................................................................54
7.10.5. Principle.....................................................................................................................................55
7.11. Multi starting gensets.........................................................................................................................56
7.11.1. Multi-start configuration.............................................................................................................56
7.11.2. Numbers to start........................................................................................................................57
7.11.3. Minimumnumbers running........................................................................................................577.12. Priority selection.................................................................................................................................58
7.12.1. Manual.......................................................................................................................................58
7.12.2. Running hours...........................................................................................................................60
7.12.3. Fuel optimisation........................................................................................................................61
7.13. Conditional connection of heavy consumers......................................................................................647.13.1. Power feedback from the heavy consumer...............................................................................65
7.13.2. Engagement sequence for HCs with fixed load.........................................................................67
7.14. Ground relay.......................................................................................................................................67
Option G4, G5 and G8, 4189340696 UK
DEIF A/S Page 3 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
4/88
7.14.1. Ground relay..............................................................................................................................677.15. Stop of non-connected gensets..........................................................................................................68
7.16. Secured mode....................................................................................................................................68
7.17. Base load...........................................................................................................................................69
7.18. Asymmetric load sharing (LS)............................................................................................................697.19. Tie breaker configuration....................................................................................................................707.19.1. Tie breaker selection.................................................................................................................70
7.19.2. Tie breaker control.....................................................................................................................70
7.19.3. Tie breaker open point...............................................................................................................70
7.19.4. Power capacity..........................................................................................................................71
7.20. Island application with TB...................................................................................................................72
7.21. Multiple mains....................................................................................................................................737.21.1. Definitions..................................................................................................................................74
7.21.2. Configuration.............................................................................................................................76
7.21.3. Plant mode handling..................................................................................................................77
7.22. Dual mains.........................................................................................................................................79
7.22.1. Configuration.............................................................................................................................80
7.22.2. Plant mode handling..................................................................................................................81
7.22.3. Internal CAN ID..........................................................................................................................837.22.4. AGC mains unit redundancy......................................................................................................83
7.22.5. Tie breaker configuration...........................................................................................................84
7.23. Configurable CAN IDs........................................................................................................................85
7.24. CAN flags...........................................................................................................................................867.25. Common PF control...........................................................................................................................86
8. Parameter lists8.1. Common settings.................................................................................................................................88
Option G4, G5 and G8, 4189340696 UK
DEIF A/S Page 4 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
5/88
1. Delilmitation
1.1 Scope of options G4, G5 and G8
This description of options covers the following products:
AGC-3 SW version 3.6x.x or later
AGC-4 SW version 4.1x.x or later
Option G4, G5 and G8, 4189340696 UK Delilmitation
DEIF A/S Page 5 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
6/88
2. General information
2.1 Warnings, legal information and safety
2.1.1 Warnings and notesThroughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which cou ld result i n death, personal in-
jury or damaged equipment, i f certain guidelines are not fo llowed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
2.1.2 Legal information and disclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how
to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the
installation or the operation of the set must be contacted.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
2.1.3 Safety issuesInstalling and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore,
the installation should only be carried out by authorised personnel who understand the risks involved in work-
ing with live electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
2.1.4 Electrostatic discharge awarenessSufficient care must be taken to protect the terminal against static discharges during the installation. Once the
unit is installed and connected, these precautions are no longer necessary.
2.1.5 Factory settingsThe Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values
and are not necessarily the correct settings for matching the engine/generator set in question. Precautions
must be taken to check the settings before running the engine/generator set.
Option G4, G5 and G8, 4189340696 UK General information
DEIF A/S Page 6 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
7/88
3. Description of options
3.1 ANSI numbers
3.1.1 ANSI
Function ANSI no.
Power management -
3.2 Options G4, G5 and G8
3.2.1 G4, G5 and G8The options G4, G5 and G8 (power management) are software options and therefore not related to any hard-
ware apart from the standard-installed hardware.
The options G4, G5 and G8 are alike in the basic functionality. In the below table the differences are shown:
Product AGC gen. AGC mains AGC bus tie
Option G4 X X
Option G5 X X X
Option G8 X
This means that all functionalities available in the G4 and G8 options will also be available in the G5 option,
but all power management functionalities regarding the mains connections and the sequences handling the
mains are not available in the G4 option, and only generator fulctionality will be available in the G8 option.
As the basic power management functions are similar in the three options, it will be possible to mix controllers
specified with one of the three options in the same application.
Option G4, G5 and G8, 4189340696 UK Description of options
DEIF A/S Page 7 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
8/88
A number of AGC units are being used in the power management application, i.e. one for each mains breaker
and tie breaker (AGC mains unit), if installed, one for each bus tie breaker (AGC bus tie unit) and one for
each generator (AGC generator unit). All units communicate by means of an internal CANbus connection.
The AGC mains unit includes the power management option and can therefore only be used with option G5
applications. The generator AGC unit must be specified with either option G4, G5 or G8, because this unit
can be used in single genset applications and in power management applications.
Option G4, G5 and G8, 4189340696 UK Description of options
DEIF A/S Page 8 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
9/88
3.3 Terminal description
3.3.1 Description of terminalsThe CANbus interface for the internal communication between AGC units in a G4/G5/G8 application is placed
on the engine interface PCB in slot #7.
Term. Function Technical data Description
98 +12/24V DC 12/24V DC +/-30% DC power supply/common for 118
99 0V DC
100 MPU input 2-70V AC/10-10.000 Hz Magnetic pick-up
101 MPU GND
102 A 0(4)-20 mA
Digital
Pt100Pt1000
VDO
0-40V DC
Multi-input 1
103 B
104 C
105 A Multi-input 2
106 B
107 C
108 A Multi-input 3
109 B
110 C
111 Com. Common Common for terminals 112-117
112 Digital input 112 Optocoupler Configurable
113 Digital input 113 Optocoupler Configurable114 Digital input 114 Optocoupler Configurable
115 Digital input 115 Optocoupler Ext. engine failure/configurable
116 Digital input 116 Optocoupler Start enable/configurable
117 Digital input 117 Optocoupler Running feedback/configurable
118 Digital input 118 Optocoupler Emergency stop and common for 119 and 120
119 NO Relay24V DC/5 A Run coil
120 NO Relay24V DC/5 A Start prepare
121 Com. Relay250V AC/8 A Crank (starter)
122 NO
123 Com. Relay24V DC/5 A Stop coil w/wire failure detection
124 NO
A1 CAN-H CANbus interface A
A2 GND
A3 CAN-L
B1 CAN-H CANbus interface B
B2 GND
Option G4, G5 and G8, 4189340696 UK Description of options
DEIF A/S Page 9 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
10/88
Term. Function Technical data Description
B3 CAN-L
In menus 7540 and 7550, you can choose which CANbus interface you wish to use for internal communica-
tion. For CANbus redundancy it is possible to use both communication interfaces.
If the LED marked "CAN B" on the main unit is alive, then the CANbus port(s) is (are) switched
on.
3.4 Breaker feedbacks
3.4.1 Generator breakerThe feedbacks of the generator breaker must always be connected (terminals 26 and 27).
3.4.2 Mains breaker (MB) feedback
MB present: The feedbacks of the mains breaker must always be connected (terminals 24 and 25).
MB not present: Selected in the power plant constructor (USW).
When no MB is represented, the MB open and close relays together with the inputs for MB
open and close feedbacks (terminals 24 and 25) will be configurable.
3.4.3 Tie breaker (TB)
TB present: The feedbacks of the tie breaker must always be connected (terminals 26 and 27).
TB not present: Selected in the power plant constructor (USW)
When no TB is represented, the TB open and close relays together with the inputs for TB open
and close feedbacks (terminals 26 and 27) will be configurable.
Option G4, G5 and G8, 4189340696 UK Description of options
DEIF A/S Page 10 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
11/88
3.5 Wiring diagrams
3.5.1 DiagramsThe following diagrams show examples with three AGC units connected, e.g. one AGC mains and two gener-
ator AGC units.
Multi-line 2
CANbus interface 1
A1 A2 A3
H GND L
Multi-line 2
CANbus interface 1
A1 A2 A3
H GND L
Multi-line 2
CANbus interface 1
A1 A2 A3
H GND L
120 120
Multi-line 2
CANbus interface 2
B1 B2 B3
H GND L
Multi-line 2
CANbus interface 2
B1 B2 B3
H GND L
Multi-line 2
CANbus interface 2
B1 B2 B3
H GND L
120 120
Multi-line 2
CANbus interface 1
A1 A2 A3
H GND L
Multi-line 2
CANbus interface 2
B1 B2 B3
H GND L
Multi-line 2
CANbus interface 1
A1 A2 A3
H GND L
120 120
As you can see from the last example, it is possible to mix CANbus interface 1 and 2.
For distances above 300 metres we recommend to use a CAN to fibre converter.
Do not connect the cable shield to the GND terminal of the AGC units.
Option G4, G5 and G8, 4189340696 UK Description of options
DEIF A/S Page 11 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
12/88
4. Functional description
4.1 Power management functions
4.1.1 Description of functionsIn the following chapter, the power management functions of the AGC are listed.
Plant modes:
Island mode (no mains unit)
Automatic Mains Failure (needs mains unit)
Fixed power/base load (needs mains unit)
Peak shaving (needs mains unit)
Load takeover (needs mains unit)
Mains power export (needs mains unit)
Display: Mains unit display showing mains breaker and tie breaker
Generator unit showing generator and generator breaker
Power management functions:
Load-dependent start/stop
Priority selection
Manual
Running hours
Fuel optimisation
Ground relay control
ATS control
Safety stop (fail class = trip and stop)
Load management Multiple mains support
Secured mode
Quick setup/broadcast
Base load
Heavy consumer (HC)
Asymmetric load sharing (LS)
Common PF control
CAN flags
Please refer to the Designers Reference Handbook for standard functions not relating to the
power management option.
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 12 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
13/88
4.2 Terminal str ip overview
4.2.1 AGC generator unit
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 13 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
14/88
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 14 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
15/88
4.2.2 AGC mains unit
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 15 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
16/88
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 16 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
17/88
4.2.3 AGC bus tie unit
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 17 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
18/88
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 18 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
19/88
4.3 Appl ications
4.3.1 Application possibili tiesThe G4 and G5 options can be used for the applications listed in the table below. The G8 option can only be
used for an island application with DG units.
Appl ication Drawing below Comment
Island operation Island mode plant Multiple gensets
Automatic Mains Failure Parallel with 1-16 mains No back synchronising
Automatic Mains Failure Parallel with 1-16 mains With back synchronising
Automatic Mains Failure ATS plant, multiple start Multiple start system
Automatic Mains Failure ATS plant, mains unit Mains unit installed
Fixed power Parallel Also called base load
1-16 mains units
Mains power export Parallel 1-16 mains units
Load takeover Parallel 1-16 mains units
Peak shaving Parallel 1-16 mains units
Refer to the Designers Reference Handbook for description o f the individual genset modes.
Regarding AC and DC connections fo r the individual applications, please refer to the Installa-
tion Instructions.
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 19 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
20/88
4.3.2 Island operation plantIn an application where up to 16 gensets are installed, the AGC will automatically operate in an island mode
with load-dependent starting and stopping.
G
Generator
breaker
(GB 1)
Diesel generator set 1
Busbar
G
Generator
breaker
(GB 2)
Diesel generator set 2
CANbus
Controller
Display 1
Controller
Display 2
If a mains unit is installed and connected (e.g. for preparing future requirements to the application), the island
mode operation is selected in the mains unit.
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 20 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
21/88
4.3.3 Parallel with mains plantAn application where a mains breaker is installed together with up to 16 gensets is shown below.
The application also supports a redundant mains unit.
The application is shown with a tie breaker, but it is also possible to use the application without a tie breaker.
The tie breaker can only be placed as shown in the drawing below.
G
Generator
breaker
(GB 1)
Diesel generator set 1
Busbar
G
Generator
breaker
(GB 2)
Diesel generator set 2
CANbus
Tie
Breaker
(GB)
Mains
breaker
(MB)
Mains
Consumers
Controller
Display 1
Controller
Display 2
Controller
Display mains
This one-line diagram is also valid for AMF plants without back synchronising and load take-
over plants without possibil ity of synchron ising the genset to the mains.
If no CTs are installed on the AGC mains, a 4-20 mA power transducer TAS-331 can be used
instead.
The CT measurements are used when the transducer setup is 4/20 mA = 0/0 kW. The transduc-
er is used when the transducer setup is changed from 0/0 kW.
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 21 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
22/88
4.3.4 Dual mains plantAn application with two mains breakers installed together with up to 16 gensets is shown below.
The application also supports redundant AGC mains units.
The application is shown with a tie breaker, but it is also possible to use the application without a tie breaker.
G
Generator
breaker
(GB 1)
Diesel generator set 1
Busbar
G
Generator
breaker
(GB 2)
Diesel generator set 2
CANbus
Tie
Breaker
(GB)
Mains
breaker(MB 1)
Mains 1
Consumers
Mains
breaker(MB 2)
Mains 2
Optional Optional
Controller
Display 1
Controller
Display 2
Controller
Display mains 1B
Controller
Display mains 2A
Controller
Display mains 2B
Controller
Display mains 1A
The tie breaker can only be placed as shown in the drawing.
In this application it wi ll not be possible to synchronise the tie breaker.
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 22 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
23/88
4.3.5 ATS plantApplications that use an ATS for switching between mains supply and generator supply are supported as
well. Two application examples which use an ATS are shown below.
4.3.6 ATS plant, mult iple start
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 23 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
24/88
4.3.7 ATS plant, mains unit
Display
Tie
Breaker
(TB)
Mains
Consumers
Controller
G
Diesel generator set 3
Controller
Display 3
G
Diesel generator set 1
Busbar
G
Diesel generator set 2
CANbus
Controller
Display 1
Controller
Display 2
ATSON/OFF
Mains okay
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 24 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
25/88
4.3.8 Multiple mainsAn example of a multiple mains plant is shown below. This is just an example; please refer to the chapter on
multiple mains for further information about the possible combinations.
G
Generator
breaker
(GB 1)
Diesel generator set 1
Busbar
G
Generator
breaker
(GB 2)
Diesel generator set 2
CANbus
Tie
breaker
(TB 17)
Mains
breaker
(MB 17)
Mains 17
Consumers
BTB 33
G
Generator
breaker
(GB 3)
Diesel generator set 3
BUSBAR
G
Generator
breaker
(GB 4)
Diesel generator set 4
CANBUS
Tie
breaker
TB 18)
Mains
breaker(MB 18)
Mains 18
Consumers
Controller
Display 1
Controller
Display 2
Controller
Display 3
Controller
Display BTB 33
Controller
Display 4
Controller
Display mains 17
Controller
Display mains 18
Option G4, G5 and G8, 4189340696 UK Functional description
DEIF A/S Page 25 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
26/88
5. Display units
5.1 DU for opt ion G5
5.1.1 Option G5 displaysThree displays exist for the option G5.
See the Designers Reference Handbook or the Operators Manual for detailed information
about push-button functions and LED indication.
5.2 Generator uni t display
5.2.1 Display
Automatic Gen-set Controller
multi-line AGC
VIEW
LOG
Auto
Alarm Inh.
Self check ok
Power
SEL
BACK
MODE
JUMP
START
INFO
STOP
Alarm
Alarm
OnRun
G
Load
Option G4, G5 and G8, 4189340696 UK Display units
DEIF A/S Page 26 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
27/88
5.3 Mains uni t display
5.3.1 Display
Automatic Gen-set Controller
VIEW
LOG
Auto
Alarm Inh.
Self check ok
Power
SEL
BACK
MODE
JUMP
START
INFO
STOP
Alarm
Alarm
multi-line AGC MAINS
On On
Load
5.4 BTB unit display
5.4.1 Display
Automatic Gen-set Controller
multi-line AGC BUS TIE
VIEW
LOG
Auto
Alarm Inh.
Self check ok
Power
SEL
BACK
On
INFO
JUMP
Alarm
Alarm
MODE
Option G4, G5 and G8, 4189340696 UK Display units
DEIF A/S Page 27 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
28/88
6. Power management setup
6.1 Init ial power management setup
6.1.1 How to set upThe AGC is set up using the display and the PC utility software.
6.1.2 Display setupEnter the menu 9100 using the JUMP push-button. Select one of the following AGC types:
1. Mains unit
2. DG unit
3. BTB unit
When this setting is adjusted, the device returns to factory settings! Therefore this must be
changed prior to other adjustments.
Enter the menu 9170 using the JUMP push-button. Select "CAN protocol 2" for a multi mains functionality.
Select "CAN protocol 1" for dual mains or single applications.
An alarm appears i f CAN protocol 2 is needed.
6.1.3 PC software setupThe communication ID must be adjusted in the utility software for each of the AGC units. In the screen shot
below, the internal communication ID is set to 1.
The numbering of the communication IDs must always start from the lowest number, so an application always
includes a DG with ID 1. The principle also applies to the AGC mains where the numbering starts from ID 17and to the BTB units where the numbering starts from ID 33.
6.1.4 Application designThe application is designed through the utility software. Please select configuration.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 28 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
29/88
Select a new application and adjust the settings in this dialogue box.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 29 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
30/88
Description Comments
Product
type
Select AGC. PPM is a power management system for marine use.
Plant
type
Select between
Single DG
Standard
Dual mains
Genset group
plant
Genset group
Use "single DG" if option G5 is not selected (or if single functionality is
needed for a G5 AGC).
Use "standard" if a power management application is needed.
Use "dual mains" if the power management application with two mains
units known from version 3.0-3.2 are to be used.
Genset group plant and genset group are used for power plants con-
sisting of 17-256 gensets in the same application. Contact
[email protected] further information.
Config-
uration
selec-
tion
The AGC is able to in-
clude four applications.
One of these can be
active.
Write a proper name of
your application.
Press "Yes" in the pop-up window to set the application to active when
downloading it to the AGC.
It is possible to see which application is active when the USW is con-
nected to the AGC.
Bus tie
options
Select "Wrap busbar"
if the BTBs are con-
nected in a ring.
CAN
line op-
tions
CAN line A: Connect
A1-A3.
CAN line B: Connect
B1-B3.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 30 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
31/88
Now the application can be designed using the section control panel.
For each area it is defined whether a generator and a mains is present, and the number and type of breakers.
6.2 Remove unit from PM
6.2.1 Possibi lit iesIf one or more units have to be taken out of the power management system, the following possibilities exist
depending on the situation.
6.2.2 Auxil iary supply OFFThe auxiliary supply must be removed from the AGC. This means that a CANbus alarm occurs on the other
AGCs. These alarms appear in a 2 DG plant where ID 2 is powered down:
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 31 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
32/88
Alarms Functioning unit (ID 1)
System alarm Failed CAN tx line
System alarm CAN ID 2 MISSINGMenu 7533 Miss. all units
Menu 7535 Any DG missing
The alarms will be present at all times during the failure. A reconfiguration of the power plant is required to
remove the alarms.
6.2.3 Quick setupNormally, the quick setup function is only used for simple rental applications. It only requires a few settings to
be running, and these settings can be made via the DU-2 display on the AGC, so no utility software is nee-
ded.
For more details, please refer to the chapter "Quick setup" in this document.
The mode changes according to the setting in CAN failure mode (menu 7532).
When the AGC is reconnected, the ID will automatically be enabled again in the other units when the ID has
been recognised. If the AGC that is reconnected is a new unit with the factory settings set in the parameter
file, a "Duplicate CAN ID" error message will appear. When an ID is chosen for the new unit, and the ID chos-
en is already active in another device, the error message "CAN ID not available" will appear, and the ID is
reset to the start value.
6.2.4 Auxil iary supply ONIf a failure appears on the CANbus lines of an AGC, the following alarms appear in the example where a fail-
ure appears at ID 2:
Alarms Defective unit Funct ioning unit
System alarm Failed CAN tx line Failed CAN tx line
System alarm CAN ID 1 MISSING CAN ID 2 MISSING
Menu 7533 Miss. all units Miss. all units
Menu 7535 Any DG missing Any DG missing
If the auxiliary supply of the unit where the CANbus is not functioning is connected, the AGC can be adjustedto another mode than AUTO. In that case the genset will not take part in the power management routines.
Semi-automatic start or automatic start is possible if the mode is changed to SEMI or AUTO
mode. The only exception to this is when BLOCK mode is selected on a genset AGC. In this
situation the GB can be closed withou t allowance from the power management system.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 32 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
33/88
6.3 CANbus failure handling
6.3.1 CAN failure modeIn case of a CAN failure on the internal CAN controlling the power management, the system can be set up in
different ways. In menu 7530 it is decided how the power management system will react in case of a CAN
failure.
1. If "MANUAL" is selected, all AGC units will change mode to manual mode, and this way the regula-
tors will have no reaction, and it will not be possible to close any breakers.
Example 1:
A break on the CAN line is made between ID1 and ID2 shown below.
Both gensets are running and all breakers are closed.
When the break occurs, the regulators will stop on both gensets, but they will stay online. As the gensetshave no valid information about the other unit, over time a blackout can occur as no load sharing is active
between the units.
If for example six gensets are available in an island application, and the CAN failure happens between ID3
and ID4, the load sharing will still be disabled between all units, as it is the manual mode which is activated.
If the CAN error happens when no gensets are running, it will block the whole system and it will not be possi-
ble to start any gensets, before the CAN error has been fixed.
G
Generator
breaker
(GB 1)
Diesel generator set 1
Busbar
G
Generator
breaker
(GB 2)
Diesel generator set 2
CANbus
Controller
Display 1
Controller
Display 2
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 33 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
34/88
2. If "SEMI-AUTO" is selected, all AGC units will change mode to semi-auto mode, and this way the
regulators will continue to regulate the load on the gensets which are still "visible" on the internal
CAN communication. This means that in the example with six gensets, the load sharing will contin-
ue between the units which are still connected (ID1-ID3 and ID4-ID6).
If the CAN error happens when no gensets are running, it will not block the whole system, and it will be possi-
ble to start all the gensets in SEMI-AUTO mode, even though the CAN error has not been fixed.
A message will be shown in the status line "BLACKOUT ENABLE" on the display.
If the CANbus error is p resent and no generator breakers are closed, it wil l be possible to
close two breakers on the same busbar, which may result in fatal damage to the whole system.
It is recommended to use the analogue load sharing (option G3) and an interlock system to
prevent this situation.
3. If "No mode change" is selected, all AGC units will stay in the mode they were in before the failure
appeared.
This setting makes it possible to keep the system in Auto mode in case of a CAN failure, however, the faulty
unit will not be a part of the power management, since it cannot send or receive status and commands on the
CANbus.
If this selection is used, it is recommended to use the CANbus fail class settings to disconnect the faulty units
(refer to the "CANbus fail class" in this chapter).
If the CANbus error is p resent and no generator breakers are closed, it wil l be possible to
close two breakers on the same busbar, which may result in fatal damage to the whole system.
It is recommended to use the analogue load sharing (option G3) and an interlock system to
prevent this situation.
6.3.2 Redundant CANbus communicationIt is possible to use two CANbus communication lines; CAN I/F 1 (A1/A2/A3) and CAN I/F 2 (B1/B2/B3). This
way, the communication will be redundant, and if one of the CANbus communication lines are damaged, the
application will still continue in Auto mode with full functionality.
6.3.3 CANbus alarmsThe following alarms can be displayed on an AGC unit in case of CANbus communication failures:
CAN A ID X MISSING
The AGC unit has lost CANbus communication to one or more CAN IDs on CANbus I/F A.
CAN A MAINS X MISSING
The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F A.
CAN A BTB X MISSING
The AGC unit has lost CANbus communication to the AGC BTB unit on CANbus I/F A.
CAN B ID X MISSING
The AGC unit has lost CANbus communication to one or more CAN IDs on CANbus I/F B.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 34 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
35/88
CAN B MAINS X MISSING
The AGC unit has lost CANbus communication to the AGC mains unit on CANbus I/F B.
CAN B BTB X MISSING
The AGC unit has lost CANbus communication to the AGC BTB unit on CANbus I/F B.
MISSING ALL UNITS
The AGC unit has lost the CANbus communication to all the other units. The fail class set in menu 7533
will be executed.
FATAL CAN ERROR
The AGC unit has lost CANbus communication to more than one CAN ID on the CANbus line. The fail
class set in menu 7534 will be executed.
ANY DG MISSING
The AGC unit has lost CANbus communication to one of the generator CAN IDs on the CANbus line. Thefail class set in menu 7535 will be executed.
ANY MAINS MISSING
The AGC unit has lost CANbus communication to one of the mains CAN IDs on the CANbus line. The fail
class set in menu 7536 will be executed.
ANY BTB MISSING
The AGC unit has lost CANbus communication to one of the BTB CAN IDs on the CANbus line(s). The
fail class set in menu 7536 will be executed.
6.3.4 CANbus fail classIn menu 7530 it is possible to set a fail class of the following CANbus alarms:
Missing all units
Fatal CAN error
Any DG missing
Any mains missing
By using these settings, it is possible to disconnect the faulty units and in this way keep the system running in
Auto mode. (Depends on the setting 7532).
For a general description of "Fail class" please refer to the Designers Reference Handbook.
6.4 Quick setup
6.4.1 Quick setupThis function is made to provide an easy user interface for applications where it is vital for the end-user to be
able to change the application quickly and easily.
It is often applications for the rental market that need this flexibility, and therefore there are some limitations
as to which applications that can be handled through the quick setup menu.
The following applications can be handled through the quick setup menu.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 35 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
36/88
Island applications
Simple applications with connection to one mains
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 36 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
37/88
6.4.2 LimitationsIn most cases, the rental applications are very simple applications, and therefore there are some limitations
that have to be considered when using the quick setup menu:
It will not be possible to have any AGC bus tie units in the application.
It will not be possible to set up a "dual mains" application through the quick setup menu.
This function is made to facilitate change of a plant configuration without AGC BTB units. Entering the quick
setup menu 9180 via the DU-2 display makes it possible to add or remove a genset without the use of utility
software. It is only possible to do the same basic setup as through the "application configuration" in the utility
software.
The functions marked with clear text in the screen shots below can be accessed through the quick setup
menu.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 37 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
38/88
6.5 9180 Quick setup
6.5.1 9180 Quick setup9181 Mode
OFF: When the mode menu is set to "OFF", the existing application that is about to have this genset
included will not look for this new genset. This will give the operator time to connect all wiring
and to do the basic setup of the genset.
Setup
Plant:
When the mode menu is set to "Setup Plant", the new AGC will receive the application config-
uration from the other units in the plant. The new AGC will then notify the rest of the applica-
tion that a new ID is available on the line. If the ID of the new AGC already exists, the new
AGC will based on the ID numbers in the application configuration have the highest ID + 1
assigned. This new ID will then be included in the application configuration in all the other
AGCs. During this process, the existing application will be able to continue running and will not
be affected by the upgrade of the system.
The new AGC will automatically go to block mode to ensure that it is in a safe mode. When the
setup is done, the end-user must decide in which running mode the added genset is to run.
If there are already 16 gensets on the CAN line and a new AGC tries to connect to the plant, an
alarm text, "No IDs available", will appear.
Setup
Stand-
alone:
When the mode menu is set to "Setup Stand-alone", the AGC will change the application
configuration, so it will no longer be a part of the application. When the ID is removed from
the application, the new application will be broadcasted to the other AGCs. The IDs of the
existing gensets in the application will maintain their ID, as a rearrangement could lead to
unnecessary starting and stopping of the gensets.
If the genset that is to be removed is running, it will not be possible/allowed to continue the
process until the genset has stopped. If it is attempted to disconnect, an info text, "Quick set-
up error", will appear.
If "Setup Stand-alone" is activated when the genset is running, an info text, "Quick setup er-
ror" , will appear.
If an AGC BTB is detected in the application, an indicating alarm, "Appl. no t possible", will ap-
pear.
Change of setup from standard to single DG unit: When disconnecting a standard AGC unit i n
a system, it is important to change the menu 9181, plant setup. After disconnecting, the AGC
unit will become a single DG.
6.5.2 9190 Application broadcastThis function makes it possible to broadcast an application over the CAN line from one AGC to all units
present in the application. It takes one operation to activate the broadcast function. It can be done in two
ways:
1. By sending the application.
2. By sending the application and activating it.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 38 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
39/88
Menu 9191 Enable
OFF: When it is set to OFF, no broadcast will be made.
Broadcast: Broadcast of the selected application in menu 9192 will be sent to the units in the
application.
Broadcast + Acti-
vate
Broadcast is activated and the application in menu 9192 will be broadcasted and
activated in all units.
Menu 9192 Application
Applications 1-4 can be drawn in the utility software.
The following pop-up windows in the utility software will guide you through the broadcast.
Option G4, G5 and G8, 4189340696 UK Power management setup
DEIF A/S Page 39 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
40/88
7. Power management functions
7.1 Command unit
7.1.1 Command unitThe power management system is a multi-master system. In a multi-master system, the available generator
units automatically perform the power management control. This means that the system never depends on
only one master unit.
If for instance one unit ID is disabled, and this was the command unit, then the next available unit will take
over the command functions.
The above also applies to the AGC mains units in that case the command unit is called Mains Command
Unit (MCU).
The command unit cannot be selected by the operator. It is automatically selected when a power manage-
ment setting is accessed.
7.2 Load-dependent starting and stopping
7.2.1 Starting and stoppingThe purpose of this function is to ensure that sufficient power is always available on the busbar. This means
that the gensets will automatically be started and stopped in order to let only the sufficient number of gensets
run. This optimises the fuel economy and the maintenance intervals.
The load-dependent start/stop function is active when the plant is in AUTO mode. The starting and stopping
of the gensets is automatically carried out according to the adjusted setpoints and priority selection.
The load-dependent start/stop function can be selected as:
Rated power setpoint (P) [kW]
Apparent power setpoint (S) [kVA]
Actual or load percentage value [%]
The load-dependent starting and stopping can be selected to base on either produced power calculation (%)
or available power calculation (P or S).
The easiest way is to use produced power calculation; however, this method is not suited for systems with
three or more generators as regards fuel savings and saving running hours.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 40 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
41/88
7.2.2 TerminologyThe table shows the abbreviations used.
Short Description Comment
PAVAILABLE Available power PTOTAL- PPRODUCED
PTOTAL Total power PNOMINALof running sets with GBs closed
PPRODUCED Produced power
PNOMINAL Nominal power
PNOMINAL-STOP Nominal power of the genset to stop Priority-dependent
Deactivate load-dependent stop
The load-dependent stop can be deactivated through M-logic, should this be preferred. This is necessary e.g.
to allow operators to start the factory load after a blackout before the normal load-dependent operation canbe started.
In the example below, the function is activated with terminal 43. Now the operator can switch the load-de-
pendent stop ON or OFF with a switch connected to terminal 44.
Produced power method
This method is in effect if % power is selected in menu 8880 as basis for the start/stop calculation.
If the load % of a generator exceeds the "Start next" setpoint, the start sequence of the lowest priority genera-
tor in stand-by will be initiated.
If the load % of a generator drops below the "Stop next" setpoint, the stop sequence of the running generator
with the highest priority number will be initiated.
If the load of the plant decreases so much that the generator with the highest priority number can be stopped
and an available power of at least the stop setpoint in % is available, then the stop sequence of this generator
will be initiated.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 41 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
42/88
-200
-100
0
100
200
300
400
500
kW% load
Time
1 2 3
Load dep. start90
10Load dep. stop
1 Load increase
2 Load start delay runs out; PMS start command
3 Stand by genset running and connecting to the busbar
Power produced
% power
Available power method
This method is in effect if P [kW] or S [kVA] is selected as basis for the start/stop calculation.
Independent of the selection (P [kW] or S [kVA]), the functionality is basically identical; therefore the example
of the functionality below will be given for the load-dependent start function with selected rated power (P) val-
ue.
The apparent power setpoint is typically selected if the connected load has an inductive character and the
power factor is below 0.7.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 42 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
43/88
Description
This drawing illustrates the terms used.
PNOM1500 kW
PNOM1000 kW
PNOM1000 kW100%
70%
DG1 DG2 DG3
= 2450 kW
= 1050 kW (available power)
= 3500 kW ~ 100%
Consumed power at the busbar
Nominal power
The nominal power is the rated power of the genset that can be read on the type plate of the generator.
Total power
The total power is the summation of the rated nominal power of each individual genset. In the example above
the plant consists of three DGs:
DG1 = 1500 kW
DG2 = 1000 kW
DG3 = 1000 kW
That is a total of 3500 kW
Produced power
The produced power is defined as the existing load on the busbar. In the example above the produced power
is indicated as the hatched area, and the total of the three gensets = 2450 kW.
Available power
The available power is the difference between the maximum possible power produced by the gensets and the
actual produced power.
In the example above the plant consists of three gensets, in total 3500 kW. The load consumes 2450 kW in
total. Since the total load PTOTALis 3500 kW, and the produced load PPRODUCEDis 2450 kW, then the avail-
able power PAVAILABLEis 1050 kW, meaning that the gensets can handle this load if it should be added to
the busbar.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 43 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
44/88
7.2.3 Principle available power methodOne genset is running and is supplying the load. The load increases which means that the available power/
apparent power decreases. At a certain time the load has increased so much that only a little amount of pow-er/apparent power is available, and the next priority genset will be started in order to increase the amount of
available power/apparent power.
When the load drops, the available power/apparent power will increase. When the available power/apparent
power has increased above the stop level plus the nominal power of the last priority genset, then the last pri-
ority genset will be stopped. Please note that the nominal power of the genset to be stopped is added to the
adjusted stop level. The reason is that otherwise the available power/apparent power would immediately drop
below the start level again.
Example:
If the adjusted stop level is 200 kW (PSTOP= 200 kW), and the genset with the last priority is 1000
kW, it is necessary that the available power reaches 1200 kW, because the available power will be
reduced with 1000 kW immediately after the last priority genset is stopped.
7.2.4 Principle percentage methodOne genset is running and is supplying the load. The load increases which means that the % load increases.
At a certain time the load has increased so much that the load % start will start up the next priority genset in
order to take some of the load.
When the load drops, the produced power will decrease. When the produced power has decreased below the
stop level plus the nominal power of the last priority genset, then the last priority genset will be stopped.
Please note that the nominal power of the genset to be stopped is added to the adjusted stop level. The rea-
son is that otherwise the produced power would immediately drop below the start level again.
Example:
If the adjusted stop level is 10% (100 kW produced power), and the genset with the last priority is
1000 kW, the last priority generator will produce 20% (200 W) after stop. It is necessary that the start
level is above this value, otherwise an ongoing starting and stopping will take place.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 44 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
45/88
7.2.5 Adjust ing load-dependent startIn the example below the available power is 200 kW. When the load increases, the available power drops
below the start limit. The stand-by genset will start when the start timer runs out, and after the synchronisingthe available power increases (in this example to 500 kW).
-200
-100
0
100
200
300
400
500
P-Avail. on busbar
Time
1 2 3
Load start limit
1 Load increase
2 Load start delay runs out; PMS start command
3 Stand by genset running and connecting to the busbar
Measured P-Avail.Predicted P-Avail.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 45 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
46/88
7.2.6 Adjust ing load-dependent stopIn the example below the available power is 500 kW. When the load decreases, the available power increa-
ses to 750 kW. The AGC now calculates what happens if the last priority genset is stopped. In the examplebelow the last priority genset is 400 kW which means that it can be stopped, because the available power will
still be above the stop level.
Now the difference between the stop level and the available power is 50 kW. This means that only if the gen-
set, which now has the last priority, is 50 kW, it can be stopped!
700
600
400
500
300
200
100
0
Load decreases
Load stop delay runs out; PM stop command
Last priority genset stopped
Load stop limit
1
1
2
3
2 3
If the order of priorit y is changed, the following must be observed:
If the priority does not seem to change as expected, it is because the load-dependent stop
function is not able to stop the lowest priority after having started the new first priorit y. Thatwould cause two DGs to be running at low load instead of one DG.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 46 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
47/88
7.2.7 Power windowThe difference between the programmed load-dependent start and stop limits forms the power hysteresis be-
tween the start and stop. This is shown in the diagram below:
Available power
at the busbar
Load-depending start
Load-depending stop
Load stop
limit
Load start
limit
1. DG
Start
2. DG
Start
3. DG
Start
3. DG
Stop
2. DG
Stop
Power
window
PDG1
PDG2
PDG3
PDG3
PDG2
7.3 Load management
7.3.1 Load managementThe function is used to activate a relay when a specific amount of power is available. The purpose of this
function is to be able to connect load groups when the gensets of the emergency power plant are running.
In each of the gensets, five levels can be adjusted (menus 8220-8260):
Available power 1
Available power 2
Available power 3
Available power 4
Available power 5
These setpoints can activate a relay when the specific amount of available power is reached. The relay out-
put can be used for connecting load groups when sufficient power is available. The relays will activate when
the available power is higher than the setpoint, but be aware that when the load groups are being connected,
the available power will decrease and the relay(s) deactivate again if the available power is below the set-
point. So it is necessary to make an external holding circuit.
The number of available relays is option-dependent.
The function is not depending on the running modes. The relays will activate in all modes including block. To
avoid activation, e.g. when the genset is stopped, the inhibit function should be used.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 47 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
48/88
Regarding the inhibit function, please refer to the Designers Reference Handbook.
It is possible to adjust different levels of available power in all gensets. This gives the possibility to use sever-
al load groups if this is necessary.
Example:
In the example below, generator #1 is started followed by generator #2. The simplified diagram shows the two
gensets and two load groups that are being connected by the available power relays R1 and R2 on AGC1.
G
Diesel generator set 1
G
Diesel generator set 2
Load
Group 1
Trip load group 1
R1
K1
K1Load
Group 2
Trip load group 2
R2
K2
K2
R1 R2
Multi-line 2 Multi-line 2
7.3.2 Functionality description (refer to the diagram below)The generator #1 is started, and the timer t1 starts running when the GB1 closes. When the t1 is expired, the
selected relay activates (R1), and in the example a 200 kW load group is connected. Now the available power
falls to 300 kW. After some time the generator #2 is started and its generator breaker is synchronised. When
the GB2 closes, the timer t2 runs. When the timer t2 expires, the selected relay activates (R2), and the sec-
ond load group of 200 kW is connected. Now the available power falls to 600 kW.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 48 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
49/88
GB1ON
t1
t2
R1 R2
200
1000
800
600
400
PAVAIL
kW
GB2ON
To connect the load groups, individual relays can be selected on each AGC or on one of the AGC units only.
7.4 Load sharing
7.4.1 Load sharingWhen the power management communication is running, the load sharing between the gensets is done byusing the CANbus communication between the AGC units.
If both CANbus ports are being used (A1-A3 and B1-B3), the communication automatically switches to the
other port if e.g. A1-A3 is disconnected or faulty. (Please refer to the description of redundant CANbus).
If both CANbus lines are disconnected or faulty, the AGCs do not automatically switch over to analogue load
sharing. This has to be set up in M-logic: Use the command "Force analogue loadshare". Now the load shar-
ing continues based on the signals from terminals 37/38/39. This means that the power management will be
lost, but the gensets already running will stay stable.
The option G3 has to be active to have the backup of the analogue load share line.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 49 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
50/88
7.5 Island ramp up
7.5.1 Island ramp up with load steps
Power[kWh]
Time [sec]GB closed
Delay,step1
Power ramp [%/s]
CAN load share setpoint
Rampup,read
fromloadshare
line S
tandardload
sharing
One step before theload share setpoint is
reached the ramp upfunction is switched off
Delay,step2
Delay,step3
Delay,step4
Delay,step5
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 50 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
51/88
7.6 Fixed power ramp up with load steps
Power[kWh]
Time [sec]GB closed
Delay,step1
Power ramp[%/s]
Power Set point
Rampdown
Stop signal
Rampup,read
Fromloadshare
line
Delay,step2
Delay,step3
Delay,step4
Delay,step5
When menu 2614 is enabled, the power setpoint continues to rise in ramp up steps, determined by menu
2615, towards the load sharing setpoint. The delay time between each ramp up step will be determined by
menu 2613. The ramp up will continue until the load sharing setpoint is reached and then switch the regulator
to standard load sharing mode.
If the delay point is set to 20% and the number of load steps is set to 3, the genset will ramp to 20%, wait the
configured delay time, ramp to 40%, wait, ramp to 60%, wait and then ramp to the system setpoint. If the
setpoint is at 50%, the ramp will stop at 50%.
7.7 Freeze power ramp
A way to define the ramp up steps is to use the freeze power ramp command in M-logic.
Freeze power ramp active:
1. The power ramp will stop at any point of the ramp, and this setpoint will be kept as long as the function is
active.
2. If the function is activated while ramping from one delay point to the other, the ramp will be fixed until the
function is deactivated again.
3. If the function is activated while the delay timer is timing out, the timer will be stopped and will not contin-
ue until the function is deactivated again.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 51 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
52/88
7.8 ATS appl ications
Two possibilities are available; the mains unit can either be installed or not.
7.8.1 AGC mains installed
See single line diagram for " Parallel with mains plant" .
In an AMF application the AGC mains will normally operate the mains breaker and thereby make sure that
the supply is coming from the mains if this is healthy.
This function allows the AGC to be used in an application where an automatic transfer switch is installed. This
is known as an ATS.
In the applications shown as one-line diagrams in the chapter Functional description it can be seen that theATS will take care of the switching between the generator supply and the mains supply.
If ATS is selected, the AGC has no control over the ATS ("mains breaker").
Description
Normally the AGC detects a mains failure based on the voltage and frequency measurement on the mains.
However, when ATS is selected in menu 7085 it is necessary to use a digital input together with the position
feedbacks from the ATS. Thus, the mains failure is not detected by the AGC measurements but by the follow-
ing two requirements:
1. Alternative start input ON2. ATS (MB) feedback OFF
To make the AGC detect a mains failure, the alternative start input has to be ON and the MB OFF feedback
has to be active.
The input used as "Al ternative start" function is configured in the PC utility software (USW).
The mains unit will not try to operate the ATS (mains breaker) at all. But it is still necessary that position feed-
backs are wired up.
It is possible to have a tie breaker installed. This is useful if more gensets need to be started before supplying
the load, because the tie breaker will not close until the required number of gensets is available.
7.8.2 ATS island mode
See single line diagram for " Island operating plant".
If this application is needed, the gensets can be started by activating the "auto start/stop" input. The gensets
will be started and stopped according to the power demand. That is, they will operate in load-dependent start/
stop mode.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 52 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
53/88
Be aware that since no tie breaker is installed, it is important that the fir st genset to close on
the busbar can carry the load. If the load is too high, the genset will be overloaded.
This application can be combined with the multi start function .
7.9 Fail class
The fail classes described in the Designers Reference Handbook are still valid when the power management
option is selected. In addition to these fail classes the safety stop can be used in the AGC units with power
management.
This means that when a trip + stop alarm occurs, the faulty genset will stay on the busbar until the next priori-
ty genset is started and synchronised to the bus. When the incoming genset has taken the load, the faulty
genset will ramp down the power, followed by trip of the breaker, cooling down of the engine and finally stop.
If the faulty genset has the last priority, or no standby gensets are available, then it will stay on the busbar
and will not trip.
If no genset can start in a safety stop situation, then the faulty genset will no t be stopped.
Therefore it is important that the safety stop is backed up, e.g. by a trip and stop alarm or a
shutdown alarm.
7.10 Local/remote/timer operation
The plant can be adjusted to local, remote or timer operation (menu 8021). This selection is done in the com-
mand unit, i.e. one of the generator units.
The setting defines how the plant is started while it is in AUTO mode.
The settings can be changed in M-logic and via display or PC utility software.
Display Utility SW
(Parameter setup)
M-logic
Local X X X
Remote start X X X
Timer start X X -
The purpose of the selection is to decide whether the plant can be started from the display (local operator),
from remote (e.g. PLC) or by an internal timer. Remote means that the control can be carried out by activat-
ing the digital input or through Modbus/Profibus communication.
7.10.1 Local selectionAll operation is carried out on the display. In island operation any generator unit display can be used, and in
load takeover, mains power export and fixed power the mains unit display must be used. The plant mode
must be AUTO.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 53 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
54/88
7.10.2 Remote select ionThe plant is started using the digital input "auto start/stop" when "remote" is selected.
Island mode
In island mode the "auto start/stop" input on any of the generator AGCs can be used for starting the plant.
However, DEIF recommends to wire up the "auto start/stop" input to all of the AGCs to be sure that the auto-
matic operation is able to continue even though one of the DGs is taken out for service (power supply discon-
nected to the AGC).
In island mode any running mode (MAN, AUTO, SEMI, BLOCK) can be selected on the generator units, and
the remote start signal is still working for the remaining AGC which is still in AUTO mode.
Parallel to mains mode
In load takeover, mains power export and fixed power mode the "auto start/stop" input on the mains unit must
be used for starting the plant.
7.10.3 Plant operationThe table shows how the plant is started:
Plant mode Selection Local Remote
Island mode Display on generator units Auto start/stop on gen. units
Fixed power mode Display on mains unit Auto start/stop on mains unit
Mains power export Display on mains unit Auto start/stop on mains unit
Load takeover Display on mains unit Auto start/stop on mains unit
In peak shaving and AMF the automatic operation starts automatically depending on the impor-
ted power (peak shaving) or mains failures (AMF).
7.10.4 Timer selectionThe operation of the plant is controlled by up to eight internal command timers which are programmed using
the PC utility software (USW).
The function can be used in load takeover, mains power export and fixed power, and the mains unit has to be
in auto.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 54 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
55/88
7.10.5 Principle
Start
LocalNo
RemoteNo
Press stop
button
Plant runningPress start
button
Yes
No
Yes
Yes
Local mode
Stop plant
No
No
Yes
Start plantAuto
start/stop
ON
Plant running
Auto
start/stop
ON
Yes
Yes
No
Yes
Remote mode
Start plant
No
Yes
No
Stop plant
Timer ON
Plant running Timer ONYes
No
Yes
Timer mode
Start plant
No
Yes
No
Stop plant
Yes
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 55 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
56/88
7.11 Multi starting gensets
The multi-start function can be used to determine the number of gensets to start. This means that when the
start sequence is initiated through push-button, digital input or automatic start, then the adjusted numbers of
gensets will start.
This function is typically used e.g. together with applications where a certain number of gensets is required to
supply the load.
Example:
In an AMF application with a tie breaker, the tie breaker must not close before the maximum power is
available (power capacity setpoint).
The multi-start function is adjusted in menu 8922-8926.
7.11.1 Multi-start configurationThe multi-start function can be adjusted to operate with two different settings. These settings consist of set-
points for how many gensets to start and the minimum number of running gensets.
It is possible to switch between the settings using M-Logic or menu 8924.
Setpoint 1 Setpoint 2
Multi-start (numbers to start) 8922 8925
Min no. running 8923 8926
Default setting
Star t condi tion Setpoint 1 Setpoint 2 Default set ting of DGs to star t
Emergency operation Mains failure - X Start all DGs
Normal operation No mains failure X - Auto calculate
The default setting of the selection between setpoint 1 and setpoint 2 is made so the setpoint 1 is adjusted to
"Auto calculation" and is used in all modes except for AMF. Setpoint 2 will automatically be selected in case a
mains failure occurs (this is adjusted in M-logic). Setpoint 2 is adjusted to 16 gensets which means that all
available gensets will start when the mains failure occurs.
Option G4, G5 and G8, 4189340696 UK Power management functions
DEIF A/S Page 56 of 88
-
7/27/2019 Option G4, G5 and G8, 4189340696 UK_2012.07.13
57/88
The default setting can be changed, if convenient.
7.11.2 Numbers to startThe numbers to start (menu 8922/8925) can be selected depending on the number of DGs available. The
load-depending start and stop function will be active as soon as the generator breakers are closed or, if a tie
breaker is installed, as soon as the tie breaker is closed. It is possible to adjust the number of gensets, or an
auto calculation can be selected.
If it is needed to delay the load-dependent start and stop function, it can be done through the
M-logic funct ion.
Auto calculation
When auto calculation is selected, the sufficient number of gensets will be started as soon as the start com-
mand is given. This is not depending on the plant mode.
Example:
In a four DG plant each generator is rated with 1000 kW. The setpoint for load-dependent start (menu
8001) is adjusted to 100 kW.
If a start command is given in fixed power mode and the setpoint is 2000 kW, then three gensets will
be started immediately and the fourth genset will remain stopped. Three gensets will be started be-
cause two gensets are requested to supply the load (2*1000 = 2000 kW) and the load-dependent start
function requests the third genset.
7.11.3 Minimum numbers runningThe multi starting function can be combined with the setting of a minimum number of running gensets (menu
8923/8926). This means that the load-dependent stop function is disregarded when only the specific number
of gensets is running. This is also the situation even though the load would justify a load-dependent stop