Hydro-Optic UV Disinfection: New Concepts in Water Disinfection
Optimization for Disinfection Byproducts_11!15!2008
-
Upload
jeff-droll -
Category
Documents
-
view
217 -
download
0
Transcript of Optimization for Disinfection Byproducts_11!15!2008
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
1/119
Optimization of Treatment for Disinfection Byproducts Control 1
Optimization of Treatment for Disinfection Byproducts Control
Optimization of Treatment for Disinfection Byproducts Control
Jeffery L. Droll
Warren National University
FPPE490: Final Paper
Dr. Magdy Girgis PhD
November 12, 2008
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
2/119
Optimization of Treatment for Disinfection Byproducts Control 2
Abstract
In January, 2002 modifications to the Clean Water Act went into effect that lowered the
maximum level of specific contaminants associated with the disinfection of drinking
water with chlorine referred to as disinfection byproducts (DBPs). This rule had the
greatest impact on purveyors that treat water from surface sources such as rivers, lakes
and reservoirs
The reason for this impact is the presence of naturally occurring organic matter (NOM)
produced by the organisms living in the water or within the water shed from which the
water is collected. The NOM then reacts with the chlorine being applied for disinfection
producing undesirable byproducts. This essay will present a case study of one facility
where conventional treatment methods and each unit process was successfully optimized
to yield a finished water that met both the regulatory requirements and the aesthetic
demands of the customers.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
3/119
Optimization of Treatment for Disinfection Byproducts Control 3
Table of ContentsI) Introduction 7
A) The Ottawa Ohio Water Treatment Plant Case Study 7
B) What is Optimization 11
C) Disinfection Byproducts 12
1) What Are Disinfection Byproducts? 12
2) What is Naturally Occurring Organic Matter? 14
II) Optimization 16
A) Examination of Historical Records 16
1) Water Quality for the Previous Two Years 16
a) Raw Water Source and Raw Water Characteristics 18b) Water Quality after Treatment in the Clarifiers 17
c) Water Quality after Recarbonation 19
d) Water Quality after Filtration 21
e) Water Quality at the Plant Tap 22
2) Evaluation of Individual Unit Processes 24
a) Existing Pretreatment Capabilities 24
b) Raw Water Supply and Low Service Pumping 25
c) Rapid Mixing 26
d) Clarifiers (Coagulation, Flocculation,
Sedimentation)28
i) Coagulation 28
ii) Flocculation 29
iii) Sedimentation 31
e) Recarbonation Basins 34
f) Filtration 36
g) Transfer Pumping (Intermediate Pumping) 44
h) Clear Well Storage (Finished Water Storage) and
Disinfection44
i) High Service Pumping 46
3) Chemical Feed Systems 47
a) Potassium Permanganate 47b) Powdered Activated Carbon 48
c) Coagulant Feed System 49
d) Lime Feed System 50
e) Soda Ash Feed System 51
f) Carbon Dioxide Feed System 52
g) Phosphate Feed System 53
h) Chlorine Feed System 54
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
4/119
Optimization of Treatment for Disinfection Byproducts Control 4
III) Jar Testing 56A) Initial Phase (Establishing a Baseline) 56
1) Verification of Present Conditions and Treatment 56
a) Establish Rapid Mixer Energy Transfer Values 57
b) Establish Flocculation Detention Time 58
c) Establish Sedimentation Time 59
2) Pretreatment Chemical Dosages 60
3) Coagulant Dosages 61
4) Softening Chemical Dosages 61
5) Simulated Recarbonation (pH Adjustment) 63
6) Phosphate Dosages 63
7) Disinfection and Simulated Distribution System Testing 64B) Experimental Phase (Chemical) 64
1) Modification to Chemical Dosages 64
a) Pretreatment Chemical Dosages 65
i) Sequencing of Chemical Additions 66
b) Coagulant Dosages 67
i) Single Basin Treatment 68
ii) Split Treatment 68
c) Softening Chemical Dosages 70
d) Disinfection, Simulated Distribution System Testing 71
2) Compilation and Comparison 72
3) Modifications to Unit Processes 72
a) Addition of Reaction (Contact) Basins 72
b) Modifications to Rapid Mix Basins Required 73
c) Separation of Treatment between Clarifiers 74
d) Modifications to Sludge Recirculation Piping on
Clarifiers75
e) Control of Solids in the Clarifier Slurry Pool and
Reaction Zone76
IV) The Human Factor 77
V) Summary 79
A) Results of Optimization 79
1) Summary of Changes 79
a) Unit processes 79
b) Chemical Treatments 81
VI) Looking Forward 83
References 84
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
5/119
Optimization of Treatment for Disinfection Byproducts Control 5
Appendices 89
Abbreviations and Acronyms 90Tables 92
Figures 107
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
6/119
Optimization of Treatment for Disinfection Byproducts Control 6
I) Introduction
A) The Ottawa Water Treatment Plant Case Study
I chose the Ottawa Water Treatment Plant for this paper for several reasons, but primarily
because the success achieved demonstrates the effectiveness of process optimization on
obtaining compliance with the recently promulgated limits for specific contaminants in
drinking water.
The Ottawa Water Treatment Plant and its water source are typical of most surface water
treatment plants constructed during the 1960s and 1970s in Ohio. However, extra
thought was given to specific details of this treatment plants design by the engineers that
allowed it to be adapted and the treatment optimized with minimal physical modifications
during this process.
The water source for the Village of Ottawa is the Blanchard River. This source was
chosen when the demands for water within the village exceeded the capacity of the
aquifer in the region. According to the United States Geologic Survey (USGS)* the river
has an estimated drainage area (water shed) of approximately 350 square miles and an
average daily discharge of approximately 271 cubic feet per second (2,027 gallons per
second) (gps). This average daily flow combined with the 121 million gallon reservoir
along the north bank of the river which was constructed at the same time as the treatment
plant was, allows for an abundant supply of water at all times. Additionally, the reservoir
capacity allows the treatment plant operators to monitor the quality of the water in the
river and to be selective when impounding water from the river.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
7/119
Optimization of Treatment for Disinfection Byproducts Control 7
The Ottawa Water Treatment Plant is what is generally considered a conventional
treatment plant using chemical precipitation of suspended contaminants and excess
hardness. However, this particular treatment plant was designed with solids contact
clarification units installed at different elevations allowing for both series and parallel
operation of the units. The importance of this feature will be expanded upon later.
A general overview of the unit processes used and their purpose is as follows. Processes
added or found to need substantial modification as a result of this optimization are
denoted with an asterisk.
Low service pumping:
Low service pumping is used to supply the energy required to lift the raw water
into the treatment plant when the water elevation in the reservoir is not at a
sufficient height to accomplish this.
Pretreatment Basins:*
The pretreatment basins are used to provide contact time for the addition of
potassium permanganate (KMnO4) and powdered activated carbon (PAC) that are
used to condition and adsorb organic contaminants, respectively. Each basin
provides 30 minutes of residence time with mixing to assure that the chemicals
have been brought into contact with all of the water present and to allow adequate
time for the chemicals to fully react.
Rapid mixing:*
A rapid mixer is a small chamber in the influent channel equipped with a high
intensity mechanical mixer that is used to thoroughly disperse chemical
coagulants throughout the raw water before the chemicals can fully react with the
alkalinity in the water.
Clarification:
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
8/119
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
9/119
Optimization of Treatment for Disinfection Byproducts Control 9
Filtration is in essence the final polishing of the water before it is disinfected and
delivered to the distribution system. Here beds of sand particles of nearly uniform
size (approx. 0.5 mm) trap the small particles that would not settle in the clarifier
are removed along with a substantial number of bacteria and bacterial cysts.
Disinfection:
Disinfection is usually performed by injecting a solution carrying dissolved
chlorine gas or sodium hypochlorite (bleach) into the filtered water. The normal
dosage is approximately 4 milligram per liter (mg/L)
Clearwell Storage:The clearwell is the storage tank used to hold the filtered and disinfected water.
Here sufficient time is provided to allow the chlorine to subdue the disease
causing microorganisms. Additionally, the volume of the clearwell provides a
reserve for high demand periods and storage during low demand periods to reduce
variations in plant production. It may be likened to a warehouse. However, the
clearwell and the storage time it provides are both a blessing and a curse for
surface water treatment plants. This point will be expanded on in later sections.
High Service Pumping:
These pumps provide the energy required to move the treated water out into the
distribution system at the volume and the pressure required.
Distribution system storage:
Distribution system storage is a means of storing water at different locations out
in the community to provide the ability to maintain both pressure and volume in
locations where such could not be reliably accomplished by the high service
pumps at the treatment plant. This storage can be in the form of elevated tanks
commonly seen around communities or in the form of underground storage tanks
where the water is transferred back to the distribution system by pumps when
needed.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
10/119
Optimization of Treatment for Disinfection Byproducts Control 10
Each of these unit processes were looked at in detail during this study and a method was
developed to optimize the performance of each to reduce the production of disinfection
byproducts in the water without adding substantially to the operational complexity of the
facility.
B) What is Optimization?
One dictionary definition of optimization is to make something function at its best.
Another definition of optimization is to accomplish a task with the smallest amount ofeffort. The later definition is often confused with the concept of minimization. By either
definition, something must be given up.
In the past, disinfection byproducts (DBPs) were not considered when treating water.
Chemical dosages and process unit sizes were determined base on what would produce
an acceptable product for the smallest investment. When DBPs were found and
determined to pose a significant health risk to those consuming the water, (Chloral
Hydrate in Drinking Water (2007)) many previous treatment strategies and treatment
plants proved to be, for the most part, inadequate. (Hill, Fred (2007)), (World Health
Organization (2004)).
In optimizing a water treatment plant for DBP control it was found that there were
optimum chemical dosages and optimum methods of operating individual treatment units.
I some cases a study of the chemical dosages produced a Bell Curve while others reached
a point of diminishing return (Periio, M. (2006)). When studying the physical treatment
unit sizes, most often the principle of diminishing return was the determining factor.
However, the strategy for operating the treatment units often produced a Bell Curve
(Heinonen, Pekka and Pisto, Sannimaria -Lopez (2007)).
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
11/119
Optimization of Treatment for Disinfection Byproducts Control 11
In this study we will examine what was done to optimize chemical dosages and the
operation of the treatment units for DBP control.
C) Disinfection Byproducts
1) What Are Disinfection Byproducts?
Disinfection byproducts are produced when the chlorine that is added to the water for
disinfection reacts with the small amounts of organic matter that is left in the water aftertreatment. The terms applied to these contaminants are THMs and HAA5s (Weeks,
Daniel P., PhD (2003)). These terms are acronyms for Trihalomethane and the five Halo-
acetic acid compounds presently being tested for.
On the periodic table of elements, the elements in the column in which chlorine resides
are referred to as halogens. Therefore the term halo is applied to these compounds.
The chlorine compound most commonly used for disinfection is Hypochlorite. It is
produced when chlorine gas reacts with water. The hypochlorite molecule acts as an
anion with a charge of negative one (1-). The molecule consists of one chlorine atom, one
oxygen atom and depending upon the pH, a hydrogen atom or an alkali metal (as found in
bleach, sodium hypochlorite). The effectiveness of this molecule comes from the fact that
it contains two of the most highly active, negatively charged elements, oxygen and
chlorine (Weeks, Daniel P., PhD (2003), pg. 36). This combination disinfects by
disrupting the structure of the molecules that make up the outer membranes of
microorganisms and viruses, and then by upsetting metabolic activities within the cells.
Organic molecules can be generally classified as saturated and unsaturated. Saturated
organic molecules have hydrogen atoms at all locations on the carbon atom or carbon
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
12/119
Optimization of Treatment for Disinfection Byproducts Control 12
atom chain where substitution can take place. Unsaturated organic molecules have
something other than hydrogen at one or more of the available sites. (Basuray, Sagnik and
Chia Chang, Hsueh, (2007))
In the study of biology you will find that the molecules making up the membranes of
microorganisms are unsaturated organic molecules, therefore a reaction with hypochlorite
is possible. In the concentrations used for disinfection, hypochlorite will seldom react
with saturated organic molecules. The unsaturated organic molecules already have one
of the hydrogen atoms substituted by an oxygen atom or carbon atoms that are doublebonded to other carbon atoms. These substitutions upset the balance of charges
(electrons) around the carbon atom or carbon atom chain allowing the highly negatively
charged components of the hypochlorite molecule to remove the remaining hydrogen
atoms and substitute for them.
These molecules that are not fully saturated with hydrogen come from the metabolic
activities of other living things or from the remains of those living things that have died.
Since these substituted molecules tend to be slightly polar in nature because of the
presence of the oxygen or the double bond, they tend to be highly soluble in water. An
example of these molecules would be methanol alcohol, acetic acid (vinegar) and ethanol
alcohol. All of which are common precursors for disinfection byproducts.
Chlorine is not the only halogen element found in these DBP compounds. Small amounts
of bromine will be commonly found in natural waters with trace amounts of iodine being
occasionally found. These two elements are not normally found in a state that will allow
them to engage in substitution reactions. They are oxidized to hypobromite and
hypoiodite by the hypochlorite allowing them to engage in these reactions in the same
manner as the hypochlorite (Pascal Roche, Benanou, David. (2006)).
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
13/119
Optimization of Treatment for Disinfection Byproducts Control 13
Although it is said that several hundred halogenated organic compounds have been
identified, the compounds tested for in these two groups are produced in the largest
quantities and have been identified as posing a threat to the health of those who consume
the water.
The THM compounds tested for are Chloroform, Bromo-dichloro-methane, Dibromo-
chloro-methane and Bromoform. The HAA5 compounds tested for are Monochloroacetic
acid, Monobromoacetic acid, Dichloroacetic acid, Trichloroacetic acid, Bromo-
chloroacetic acid and Dibromoacetic acid.
2) What is Naturally Occurring Organic Matter?
Naturally occurring organic matter (NOM) consists of soluble and semi-soluble organic
(carbon based) molecules. The molecules are the remnants of organisms that have died,
were eaten, or were produced from the metabolic activities of the organisms that inhabit
the water and the surrounding water shed that provides the source of the water to be
treated. These molecules vary in size from single carbon (methyl) alcohols and
aldehydes, to massive humic acid molecules that may contain more that 10,000 carbon
atoms. These larger molecules are the ones that give healthy river and pond water its
characteristic earthy or musty smell (Prashant, Kumar (2003)).
In most natural systems the tendency is for the organisms to utilize the organic molecules
as food and successively break them down into ever smaller parts. Often these remaining
small molecules are utilized by bacteria as food and converted to a final mineral
(inorganic) state. However, small quantities of them often remain. These remaining
molecules are the molecules that provide the substrates (precursors) for THM and HAA5
compounds.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
14/119
Optimization of Treatment for Disinfection Byproducts Control 14
Often during treatment strong acidic, alkaline or oxidizing chemicals are applied to the
water. Some of these chemicals have been found to increase the number of precursors in
the water by breaking pieces off of the very large molecules during the treatment process.
These are some of the concerns we will be addressing during the optimization process.
Those are; how to remove the larger molecules without creating more precursors and to
utilize the chemical conditioning and adsorptive characteristics of certain treatment
chemicals to remove as many of the precursors already present as possible.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
15/119
Optimization of Treatment for Disinfection Byproducts Control 15
II) Optimization
A) Examination of Historical Records
The examination of historical operating records is a critical part of any optimization
work. This should include any information the plant operators have compiled over the
years. Most of the records will be the results of standardized laboratory tests. This type of
information is the most useful when comparing the performance of the processes toindustry benchmark standards. It allows for trending of critical parameters and the
building of relationships between operation of the plant and finished water quality.
However, the most often overlooked information is notes made by the operators
expressing subjective opinions about the performance of a piece of equipment, some
attribute of the water that is not tested for regularly such as the color or odor of the raw
water, weather conditions or an opinion pertaining to the quality of a treatment chemical.
Any of these personal insights have the potential to help direct energy in the most useful
direction. Many times this information is only available through lengthy conversations
with the staff or from operators logs that do not contain test data. Often these notes are
about events within the plant or the water shed. Although these notes may not directly
affect the data, they may explain anomalies and allow parsing of the data that would
otherwise tend to skew the analyses of the data.
1) Water Quality for the Previous Two Years
Because the amount of data collected on a daily basis at most water treatment plants can
be immense, it is necessary to limit it to a range that will provide the most useful
information for the work at hand. Experience has shown that the overall source water
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
16/119
Optimization of Treatment for Disinfection Byproducts Control 16
quality will change very little over time if there have been no major changes within the
watershed. Therefore two years of data will allow the observation and trending of both
seasonal and weather related changes along with changes in the process units
Table 1 is a listing of the average water quality data for the two years prior to this study.
a) Raw Water Source and Raw Water Characteristics
Initially the raw water source is looked at to determine if it is capable of supplyingenough water to meet the needs of the community. This is an important consideration
because the quality of the water in the stream will vary over the course of the year and if
the amount of water available in the stream at any given time is sufficient to allow
impounding; the plant operators can be selective and impound only when the water
quality is determined to be acceptable.
The basic parameters used to determine water quality are:
Turbidity
Organic content (determined by UV254 scan)
Alkalinity
Hardness
The first parameter directly affects the longevity of the reservoir since the turbidity in a
river is primarily composed of small suspended particles that will become sediment in the
reservoir. The other three parameters directly impact the economics of treating the water
by dictating the amounts of treatment chemicals required to achieve an acceptable
finished product.
The raw water source is the Blanchard River. According to the USGS the Blanchard
River serves a water shed of approximately 350 square miles (USGS 04189000
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
17/119
Optimization of Treatment for Disinfection Byproducts Control 17
Blanchard River) and the river has an average monthly flow of 271 cubic feet per second
(2,027 gallons per second), which equates to 175 million gallons per day. From the data
indicating an average flow past the treatment plant of this magnitude and the
communitys average need being less than 3 million gallons per day, the treatment plant
operators can be selective. Conversations with the operators indicated they were using
this to their advantage.
b) Water Quality after Treatment in the Clarifiers
The quality of treatment obtained through the clarifiers is probably the most critical stage
of the treatment process. The clarifiers are in essence large high rate chemical reaction
vessels. As with any chemical process there are several factors which will determine the
overall efficiency of the process.
The basic characteristics of the clarifiers and their average effluent water quality are
detailed in Table 2.
The operators perform laboratory tests on the clarified water to determine the
effectiveness of treatment. Although these tests are not mandated by any regulatory
agency, they are considered necessary by the operators to control the process. These tests
are:
Turbidity
Alkalinity
Hardness
pH
UV254
Turbidity on clarified water is an indicator of the effectiveness of treatment as it relates to
the removal of suspended and precipitated matter from the water. The largest portion of
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
18/119
Optimization of Treatment for Disinfection Byproducts Control 18
these vessels is designed to provide quiescent conditions with a decreasing flow velocity
as the waster rises through the outer portion.
The alkalinity of the water is a measure of the amounts of calcium and magnesium
present that is associated with a carbonate or hydroxide anion. Often times this is referred
to as the buffer capacity of the water.
The hardness of the water allows the operators to determine the total amount of calcium
and magnesium in the water and differentiate between the amount of calcium andmagnesium that is alkalinity (carbonate) and the amount of calcium and magnesium that
is associated with non-carbonate anions.
The pH of the water allows the operators to determine the species of the carbonate anions
present since the balance of carbonate and bicarbonate anions is critical to the stability
(corrosiveness) of the water; this allows them to determine the amount of adjustment that
is required in the recarbonation process.
The results of the UV254 analysis performed on the clarified water is compared to the
results of the UV254 analysis performed on the raw water to determine the processs
efficiency at removing organic material from the water.
As with the raw water, laboratory analyses records from the previous two year was
examined. The information shown in Table 2 reflects the averages of the clarified water
quality for the two years prior to this study.
c) Water Quality after Recarbonation
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
19/119
Optimization of Treatment for Disinfection Byproducts Control 19
During precipitative softening in the clarifier the pH of the water is raised by the addition
of calcium hydroxide (lime) to a level where all of the alkalinity is converted to either
carbonate or hydroxide species. These alkalinity species associated with calcium and
magnesium, respectively, have a low solubility at the elevated pH allowing them to come
out of solution (precipitate). Under these conditions the remaining alkalinity is barely
soluble and is just at equilibrium. This remaining alkalinity is considered unstable
because even slight changes in either temperature or pressure will cause it to plate out on
the inside of pipes and plumbing fixtures slowly plugging them.
More importantly, if this unstable water is applied to the filters, which immediately
follow recarbonation, this alkalinity will plate out on the filter sand increasing the
effective size of the sand grains. This increase in grain size will reduce the ability of the
filters to remove small particles.
Recarbonation is the process used to alter the alkalinity species and adjusted them to a
more soluble form. The process is the addition of carbon dioxide gas directly to the water.
Upon contact with the water, the carbon dioxide gas reacts with the water to form the
weak acid, carbonic acid, and dissolves. The carbonic acid first reacts with the hydroxide
anions to form carbonate and water. Once all of the hydroxide anions have been
converted, the remaining carbonic acid reacts with the carbonates to produce bicarbonate
anions, which are slightly acidic. (Edwards, M., Scardina, P. (2006))
A proper balance of the carbonate to bicarbonate alkalinity will produce finished water
that will neither corrode metal components nor deposit on the interior surfaces of pipes
and fixtures. At this point the water is considered chemically stable.
Here the operators performed laboratory analyses to monitor the process. These analyses
are:
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
20/119
Optimization of Treatment for Disinfection Byproducts Control 20
Alkalinity
pH
The alkalinity test indicates the species and concentrations of the alkalinity present. Since
at this point the pH is a function of the balance of the alkalinity species, (OTCO, 2007,
Precipitative Softening) it serves as an indicator of the correctness of the alkalinity tests.
d) Water Quality after Filtration
Following recarbonation, the treated water is applied to three high rate (rapid) sand
filters. Filtration is normally looked upon as a polishing process. However, the filtration
process, when operated correctly provides a highly efficient barrier against
microorganisms and the cysts of several pathogens.
Because of this process importance to the health of the systems users, the performance
of the filtration process is the most tightly regulated of all of the treatment processes.
There are three analyses performed of the filtered water. These are:
Turbidity
Alkalinity
pH
The overall performance of the filter and the preceding processes are evaluated by the
turbidity of the filtered water. By federal law, the filtered water turbidity must be less
than 0.3 Nephelometric Turbidity Units (NTU) in 95 percent of the samples taken every15 minutes and the turbidity may not exceed 0.5 NTU at any time.
The reason for this is that it has been found that microorganisms can live on and within
the small particles passing through the filter and possibly avoid deactivation by the
disinfection process in this way.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
21/119
Optimization of Treatment for Disinfection Byproducts Control 21
Therefore, when the filter operation records were examined, great attention was given to
any exceedances and the quality of the water being applied to the filters.
There are several other operating parameters that can be extracted from the basic filter
operating data pertaining to the economic efficiency of the filters. These parameters will
be elaborated on in Section II, 2, Evaluation of Individual Unit Processes.
The alkalinity of the filtered water is monitored closely. This parameter directly indicatesif carbonate deposits are being formed on the sand grains. If there is a decrease in the
alkalinity of the filtered water it would indicate that the water had not been fully
stabilized by the recarbonation process.
If deposition is determined to be occurring, the amount that is being deposited can be
estimated by converting the difference in alkalinity between the filtered and unfiltered
water to pounds per day. Deposition on the sand grains will increase the effective size of
the sand grains and reduce the filters effectiveness at removing smaller particles.
Again here pH is looked at to verify the accuracy of the alkalinity test.
e) Water Quality at the Plant Tap
The finished water at the plant tap is subjected to a battery of tests that are mandated by
the Ohio and US Environmental Protection Agencies (inclusive, EPA). A list of these tests
is shown in Table 1 and the two year average of these tests is shown in the Finished Water
column.
The parameters most frequently tested for are:
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
22/119
Optimization of Treatment for Disinfection Byproducts Control 22
Turbidity
Alkalinity pH
Hardness
Chlorine residual
Here again the turbidity of the finished water is the primary indicator of the success of the
preceding processes. Here also the same limits for turbidity are enforced that apply to the
filter effluent and for the same reasons.
The alkalinity, pH and hardness are used to determine the stability of the water. These
parameters combined with the water temperature, allow stability indexes to be calculated.
On Table 1 these indexes are the Langelier Index (LI) and the Calcium Carbonate
Precipitation Potential (CCPP). The Langelier Index is a non-dimensional number. Values
greater than zero (0) indicate a tendency for carbonates to precipitate and values less than
zero (0) indicate corrosive water.
The CCPP calculation is much more complex than the Langelier Index, and will give a
result that indicates in milligrams per liter how much alkalinity may be lost from the
water (precipitated) or gained by it (corrosion) to reach stability.
The chlorine residual present in the finished water is a measure of the chlorine left
following disinfection with chlorine gas or sodium hypochlorite. This parameter is also
regulated by the EPA (Formation of Chlorinated Organics in Drinking Water (2005)).
To remain in compliance with the regulations the amount of free chlorine (hypochlorite
ion) remaining in the water must be >0.2 mg/L at any point in the distribution system but
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
23/119
Optimization of Treatment for Disinfection Byproducts Control 23
One parameter closely studied in an optimization study is the chlorine demand. This is
the difference between the chlorine residual present in the finished water and the amount
of chlorine gas or hypochlorite ion applied to the water.
Since the primary focus of this optimization study is to reduce disinfection by product
and since the level of disinfection by product produced can be closely correlated to the
chlorine demand of the water; this parameter is of great interest and value.
2) Evaluation of Individual Unit Processes
During this phase each of the individual unit processes are evaluated from three
perspectives. These are:
1) Their average performance over the preceding two years
2) Physical characteristics in relationship to accepted minimum industry standards
3) Their present mode of operation.
a) Existing Pretreatment Capabilities
Pretreatment is generally used as a conditioning process. The most common chemicals
used for pretreatment are chemical oxidizers and adsorbents. The purpose of these
chemicals is to oxidize both organic and inorganic contaminants and to adsorb
contaminants and some of the contaminants conditioned by oxidation prior to them
entering the following treatment processes.
Currently there were no facilities dedicated to providing pretreatment.
There are two chemicals available for pretreatment. These are potassium permanganate
and powdered activated carbon (PAC) (Gaulinger, Siegfried. (2007)).
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
24/119
Optimization of Treatment for Disinfection Byproducts Control 24
b) Raw Water Supply and Low Service Pumping
The Blanchard River serves as the raw water source. An above ground reservoir,
constructed in 1971 is used to store raw water for the treatment plant. A river pumping
station is located adjacent to the Blanchard River. The pumping station contains screening
equipment and three pumps. Pump capacities are shown in Table 4.
The reservoir is a 28-acre impoundment basin that has a storage volume of 121 million
gallons at an average depth of 21 feet. The usable volume based on ODNR water
overflow restrictions is approximately 106 million gallons. The reservoir does not
provide sufficient storage volume based on current guidelines. According to current
guidelines, the Ohio EPA recommends that total raw water storage should provide a
minimum of 270 days based on the average plant production rate. The current average
plant production rate is approximately 1.6 MGD. Based on this the reservoir currently
only provides 66 days of storage. At the current plant design flow, the reservoir will
provide only approximately 35 days of storage. Additional raw water reservoir storage
should be considered. Any additional reservoir capacity needs to be evaluated based on
existing river flow data and Ohio EPA recommendations.
The elevation of the water in the reservoir is normally maintained at a height sufficient to
supply the head (pressure) necessary to move the water through the initial treatment
processes at a rate of 2,400 gpm. When the water elevation in the reservoir is below this
minimum, two raw water pumps provide the necessary head. Normally these pumps are
not used.
Each of these pumps has a capacity of 2,100 gpm at a head of 25 feet. Each is driven by a
20 horsepower motor. Firm raw water pumping capacity (capacity with one pump out of
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
25/119
Optimization of Treatment for Disinfection Byproducts Control 25
service) is 3.0 MGD. Any future plant expansion plans should address additional raw
water pumping capacity.
c) Rapid Mixing
One in-line mixer is located in the raw water inlet pipe, although it is currently not used.
The mixer is driven by a one horsepower motor. The estimated detention time in this
mixer is less than one second. The estimated velocity gradient (G value) for the mixer,
when used, is between 2,270 sec
-1
and 3,320 sec
-1
. High G values are necessary for in-linemixers particularly when charge neutralization coagulation is employed (Zeta-Meter Inc.
Fourth Edition).
Here however, sweep coagulation treatment is used rather than charge neutralization for
both turbidity removal and organics control. Mixing energies of this magnitude have been
found to be detrimental to sweep coagulation where the intent is to develop a large fragile
floc particle.
When the mixer is operating, the G value produced is greater than that required for sweep
coagulation and the detention time provided is too short. For these reasons, it appears that
the in-line mixer serves little purpose in the existing treatment process and should be
removed.
There are two rapid mix basins complete with mechanical mixers. The basins can be
configured for either series or parallel flow depending on treatment needs. One basin is
dedicated to each clarifier. The primary (west) rapid mixer currently was operated at
approximately 30 percent of its maximum speed. The east rapid mixer is currently not
used. Each rapid mix basin has a volume of approximately 1,500 gallons. This provides a
detention time of 43 seconds at the design flow rate under series operations. The
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
26/119
Optimization of Treatment for Disinfection Byproducts Control 26
detention time in each basin under parallel operations is 87 seconds. The current
recommended standard for rapid mixing establish a detention time of not more than 30
seconds (Recommended Standards for Water Works, (2003)). The existing rapid mixers
are five horsepower units that can produce an estimated velocity gradient (G value)
between 505 sec-1 and 740 sec-1 depending upon the raw water temperature. The primary
(west) rapid mixer currently is operated at a speed that produces a G value between 290
sec-1 and 424 sec-1 depending on the water temperature. The current recommended
standard is a minimum G value for rapid mixers of 900 sec-1 (Recommended Standards
for Water Works, (2003))
The existing rapid mix basins and mixers do not meet current recommended standards.
The excessively long detention time is most likely interfering with the coagulation
process because the newly formed floc particles are not taken away from the vicinity of
the mixer quickly enough and are being sheared prior to leaving the basin. Additionally,
the large cross sectional area of the basin in relationship to the diameter of the mixer
impeller is likely allowing substantial amounts of water to bypass the mixing process.
The existing basin flow configurations exhibit desirable rapid mix design characteristics.
Water flow enters the top of each rapid mix basin and is directed downward toward the
clarifier influent piping. Properly sized, each basin would be very beneficial to the
optimization efforts for coagulation treatment. Optimum rapid mixing conditions employ
the proper G value for mixing, pinpoint application of the coagulant chemical, and the
use of counter current mixing.
Coagulant dispersion is best accomplished when the coagulant is applied near the eye of
the mixer impeller. To take advantage of counter current mixing technology, the rapid
mixer is configured to push water against the flow through the basin. This is
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
27/119
Optimization of Treatment for Disinfection Byproducts Control 27
accomplished by setting the mixer drive unit for the correct rotation based on the impeller
design and water flow characteristics.
d) Clarifiers (Coagulation, Flocculation, Sedimentation)
i) Coagulation
At this time coagulation is provided by adding ferric chloride to the raw water through a
connection to the in-line mixer, even though the mixer is not operated. Coagulation isused to foster the gathering of suspended particles and colloids into a settleable floc
material. Coagulation also can be used to remove dissolved and suspended organics from
the water (Enhanced Coagulation for Surface Water (2006)).
The average dosage of ferric chloride presently applied for treatment (32 mg/L) indicates
that sweep coagulation is the mechanism of coagulation. Sweep coagulation is a term
used to indicate how particles and solids are removed from the water. In sweep
coagulation the coagulant reacts with the alkalinity in the water to form sticky hydroxide
floc particles. These hydroxide floc particles act like a net to sweep other particles and
solids from the water. Particles and solids absorbed into the floc particles materials are
later removed during sedimentation.
However, the G value produced in the rapid mixing appears to be insufficient for sweep
coagulation. As previously mentioned, new rapid mix units should be installed to match
the proposed basin modifications.
Enhanced coagulation, either by pH adjustment or by increased coagulant dosage, is most
likely needed to effectively reduce DBP precursor concentrations prior to chlorination of
the water (Enhanced Coagulation for Surface Water (2006)). DBP precursors are organic
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
28/119
Optimization of Treatment for Disinfection Byproducts Control 28
contaminants that create disinfection byproducts (DBPs) following chlorination of the
water. The DBPR established requirements for enhanced coagulation, TOC removal, and
maximum contaminant levels for DBPs. Bench-scale evaluations will be performed to
predict the needs for coagulation and to identify the needs for effective DBP precursor
and TOC removal (Garca, Indiana (2005)).
Currently, lime and soda ash are added to the raw water flume upstream of the primary
(west) rapid mix basin for softening. The lime may be acting as a coagulant aid for
improved turbidity removal. The current application of lime and soda ash at this locationare most likely interfering with coagulation treatment.
These two chemicals quickly increase the water pH well above the optimum pH for
coagulation. Since sweep coagulation is employed in treatment, lime and soda ash should
be applied at least 10 seconds downstream of the coagulant feed point.
ii) Flocculation
The flocculation zone of each clarifier was designed to aid in the development of floc
material from the chemically treated water to increase the removal of certain
contaminants. The existing flocculation mixing equipment has been out of service since
1973. It appears that lime scale accumulations on the mixers rendered them inoperative.
No mechanical mixing of the chemically treated water occurs at this time. For effective
flocculation, it is recommended that the mixing intensity (G value) be maintained
between 20 sec-1 and 70 sec-1. Adjustment of the flocculation mixer speeds is crucial to
the optimization of flocculation treatment. Mixer speeds must be adjusted based on floc
density, floc settling characteristics, and water temperature.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
29/119
Optimization of Treatment for Disinfection Byproducts Control 29
The original flocculation mixers had variable speed capabilities. New mixing equipment
is needed for flocculation and should have variable speed capabilities.
Floc settling rates and filterability index tests were performed as part of the evaluation of
existing treatment. The floc settling rate test helps determine the ability of floc material to
settle and allows the estimation of the clarifier up-flow rate necessary to allow effective
settling of the floc. The test results showed that the floc size (0.5 mm diameter) is
sufficient, but the floc density is too low for effective sedimentation.
Floc density is a function of coagulant dosage, mixing intensity, and detention time.
Variable speed mixingequipment is needed to enhance flocculation and to increase floc
density. The maximum clarifier up-flow rate determine from the test procedure was
estimated to be 0.63 gpm/ft2. On the day of the test, the actual up-flow rate was calculated
to be 0.66 gpm/ft2. More agitation (higher G value) is needed to increase the density of
floc material produced during the flocculation process.
Filterability index is a rough measure of the efficiency of particle removal from
treatment. Index values typically range between 1.05 and 1.3 in well optimized treatment
processes. A filterability index of 1.6 was determined for the settled water produced by
the primary (west) clarifier. A filterability index of 1.5 was determined for the settled
water produced by the secondary (east) clarifier. Index values greater than 1.3 indicate a
need to improve treatment.
Necessary improvements may include proper dosage control, changes in rapid mix and
flocculation mixing intensity, and the use of a polymer as a coagulant aid. Deficiencies in
rapid mixing and flocculation mixing were previously discussed. Polymer addition and
other coagulants will be evaluated to determine if they could improve floc density and
settling capabilities.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
30/119
Optimization of Treatment for Disinfection Byproducts Control 30
Recommended Standards establishes a detention time for flocculation at no less than 30
minutes at the design flow rate. The current rated design detention time for flocculation is
approximately 45 minutes using both clarifiers in parallel operation. At the normal
treatment flow rate (approx. 2.25 MGD), each clarifier provides a flocculation detention
time of approximately 30 minutes. Actual flocculation detention time is approximately 30
minutes since only the primary (west) clarifier is presently used for flocculation treatment
at 2.25 MGD. The secondary (east) clarifier is presently only used for additional settling.
Although the clarifiers appear to meet the detention time requirements for flocculation,
the mixers are inoperative. Flocculation, therefore, fails to create the proper floc density
for effective particle removal. New mixers are necessary to optimize flocculation and to
improve floc density.
An estimate of the solids concentration in the reaction (mixing) zone of the primary
(west) clarifier was determined to be 19 percent by volume. An estimate of the solids
concentration in the reaction zone of the secondary (east) clarifier was not determined
since its present function is only as a secondary sedimentation basin. Optimal
flocculation treatment occurs when the reaction zone solids concentration is between 5
percent and 25 percent by volume. It appears that an optimal solids concentration is
maintained in this clarifier for treatment.
Based on the evaluation of flocculation treatment in the existing clarifiers, improvements
are needed to optimize flocculation.
iii) Sedimentation
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
31/119
Optimization of Treatment for Disinfection Byproducts Control 31
The outer portion of the two up-flow clarifiers provides sedimentation for the treated
water. The clarifier design characteristics are shown in Table 5.
The existing clarifier design characteristics appear to meet current recommended
standards. Clarification and sedimentation detention time must be at least four hours
based on current recommended standards. The combined detention time for
sedimentation also exceeds the detention time recommended under current recommended
standards (Recommended Standards for Water Works, (2003)).
Each clarifier has an up-flow rate lower than current recommended standards. The
maximum up-flow rate for clarifiers using softening treatment is 1.75 gpm/ft2based on
recommended standards. Up-flow rates for clarifiers using coagulation treatment only is
1.0 gpm/ft2based on recommended standards using the present calculated up-flow rate of
0.66 gpm/ft2. The existing clarifiers currently meet the standards for coagulation
treatment established in the recommended standards (Recommended Standards for Water
Works, (2003)).
The weir overflow rate (WOR) for clarifiers is established in Recommended Standards at
not more than 20 gpm per linear foot of weir. Both the design and operational WOR are
less than the recommended standards. The WOR for each clarifier was calculated to be
1.8 gpm/ft and 3.6 gpm/ft at design flow for parallel and series operations, respectively.
These low flow velocities reduce the tendency for solids billowing and vortexing leading
to excessive solids carryover from the basins.
The settled solids concentration in the sludge withdrawal pipe from the primary (west)
clarifier was found to be 100percent by volume. Optimal treatment has been found to
occur when this solids concentration is maintained between 70 percent and 95 percent by
volume. It appears that settled solids are not removed from the clarifiers at an adequate
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
32/119
Optimization of Treatment for Disinfection Byproducts Control 32
rate. Improvements to the solids management practices and adjustment of the solids
removal schedule are needed for this clarifier. Adjustments to the solids removal schedule
for the secondary (east) clarifier were also found to be needed. The solids removal rate
must be adjusted to match the solids production rate during treatment. Estimating the
solids production rate could be added to the routine process control schedule. Results of
the calculations can be used to establish solids removal rates for each clarifier.
The sludge collector operating speed was measured as part of the evaluation. Based on
measurements, the tip speed of the sludge collector was determined to be 2.8 feet/minute.Recommended Standards establish the operating speed of sludge collector mechanisms at
no more than 10 feet/minute. The collector mechanism is operating at a speed
significantly lower than permitted by current recommended standards. This desirable
operating condition helps prevent solids billowing within the clarifiers.
The existing clarifiers can be operated either in a parallel or series flow mode. Ohio EPA
requires that both parallel and series operating conditions be available for solids contact
clarifiers. Currently, the clarifiers are operated in series flow with treatment only being
provided in the primary (west) clarifier. The secondary (east) clarifier is used only for
secondary sedimentation. The water quality produced by this operation meets current
drinking water standards. Compliance with anticipated drinking water standards should
be achieved utilizing some improvements or modifications. Proposed clarifier
improvements are discussed later.
Settled water turbidity averages 1.0 NTU with maximum turbidity levels at
approximately 2.3 NTU. Sedimentation should produce water having a turbidity level
less than 5 NTU and preferably less than 3 NTU, placing the present resulting turbidity
within acceptable parameters.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
33/119
Optimization of Treatment for Disinfection Byproducts Control 33
Lime is applied to the water for softening. The average alkalinity concentrations typically
produced in the treated water produces a total alkalinity and hydroxide alkalinity
concentration of 53 mg/L and 20 mg/L, respectively. An optimum total alkalinity
concentration for effective corrosion control is typically between 60 mg/L and 80 mg/L.
The hydroxide alkalinity concentration necessary for optimum softening treatment is a
function of the raw water magnesium concentration which determines the lime dosage
necessary for magnesium precipitation. Further discussion on optimum hydroxide
concentrations is provided under softening treatment.
Enhanced coagulation requirements under the DBPR were previously described. Current
TOC removal was determined to be approximately 37 percent. Although the minimum
TOC removal requirements appear to be met using the current treatment, additional TOC
removal is needed to achieve compliance with future THM requirements. However,
compliance with enhanced coagulation and TOC removal requirements does not assure
compliance with the maximum disinfection byproducts limits.
e) Recarbonation Basins
A recarbonation basin and carbon dioxide generating equipment were constructed as part
of original plant. In 1993, the carbon dioxide generating system was replaced with a
liquid carbon dioxide storage tank and a diffuser system.
The existing basin configuration has a mixing zone and a stabilization zone. The mixing
zone provides a detention time of three minutes, while the stabilization zone provides a
detention time of 31 minutes. Recommended Standards establishes a total recarbonation
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
34/119
Optimization of Treatment for Disinfection Byproducts Control 34
detention time of 20 minutes including a mixing detention time of at least three minutes
at design flow. The existing recarbonation basin provides a detention time that exceeds
current recommended standards.
The recarbonated water typically has average carbonate alkalinity and bicarbonate
alkalinity concentrations of 24 mg/L and 25 mg/L, respectively. Optimal recarbonation
for stability control should produce a water quality that is nearly equal in bicarbonate
alkalinity and carbonate alkalinity concentrations. Based on this guidance, it appears that
recarbonation of the settled water will produce adequate stability control. Water having
carbonate alkalinity concentrations greater than approximately 35mg/L will tend to plate
out on surfaces including the filter sand grains causing growth of the grains. Filter sand
growth can increase turbidity levels by allowing the smaller particles to pass through the
filter.
Recarbonation treatment is discussed further under chemical feed applications in this
section.
The existing recarbonation basin has no roof. Consequently, sunlight and warm water
conditions foster the growth of algae in the basin. Algae growth creates a distinct green
coloration in the treated water and may be producing additional organic contaminant
concentrations in the water applied to the filters. These organics, if left untreated before
chlorination, could contribute significantly to the disinfection byproduct (THM andHAA5) concentrations created by disinfection.
A roof should be constructed over the recarbonation basin to reduce algae growth during
warm weather months. This roof would provide additional protection against birds and
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
35/119
Optimization of Treatment for Disinfection Byproducts Control 35
other small animals that could enter the basin and cause bacterial contamination of the
treated water.
f) Filtration
There are three rapid sand dual media filters to remove fine particles for final polishing
treatment of the water. Each filter is provided with backwash and surface wash
capabilities.
Currently no equipment or piping is supplied for filter-to-waste operations.
Filtration typically is the last barrier to remove contaminants that may be present in the
treated water. Treatment ahead of the filters should remove a significant portion of the
contaminants so that the filters can be operated effectively for particulate and microbial
removal.
Each of the filters has a surface area of 351.5 ft2, providing an approved treatment
capacity of 1.0 MGD each at the current approved filtration rate of 2 gpm/ft 2. Each filter
bed consists of approximately 12-inches of gravel, 15-inches of sand, and 7.5-inches of
anthracite. The existing filter media and gravel was installed in 1989.
The filter bed was examined by probing and excavation to determine the media depth.
This examination indicated that approximately 4.5-inches of anthracite had been lost
since the media was installed.
The approved filtration rate of the filters is 2 gpm/ft2. This is in accordance with current
recommended standards. Current operating practices produce an average rate of
approximately 1.5 gpm/ft2.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
36/119
Optimization of Treatment for Disinfection Byproducts Control 36
Average filter run times are 86 hours, although the established maximum filter run time is
100 hours. Filter runs longer than 72 hours are desirable and usually indicate effective
filtration. Excessively long filter runs (greater than 150 hours) can deposit too many
solids deep into the media making it difficult to clean the filter media during backwash
cycles. It may be possible to increase filter run times without adversely affecting filtered
water quality. Any efforts to increase filter run times should be accompanied by careful
monitoring of the primary filtered water quality parameters.
Gross water production (GWP) is commonly used to help determine filtration efficiency
and filterability of the treated water. GWP of approximately 10,000 gal/ft2 per filter run is
accepted as indicating good filterability of the treated water. A typical GWP was
determined to be approximately 7,840 gal/ft2 per run. Based on the GWP determined, the
treated water appears to be filterable and the filters appear to be operating properly.
Increasing the filter run times would increase the GWP.
Filter performance can also be evaluated using filter efficiency calculations. These
calculations determine the percentage of water filtered versus wash water used to clean
the media. Filter efficiencies greater than 95 percent are accepted as indicating effective
treatment. Using this method, the filtration efficiency was determined to be 98 percent.
One backwash pump is used to supply wash water to the filters for cleaning. The
backwash pump has a capacity of 5,200 gpm. The typical wash water usage is
approximately 867,000 gallons per month or 1.8 percent of the monthly raw water
treated. Normal wash water usage should average approximately two percent to four
percent of the monthly raw water pumpage.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
37/119
Optimization of Treatment for Disinfection Byproducts Control 37
The filters are currently backwashed at a rate of approximately 12.0 gpm/ft2. This rate is
lower than the existing design backwash rate and current recommended standards for
backwash. Records indicate that plant personnel do not change the backwash rate based
on water temperatures. Some media loss has been noted based on data from the original
filter media records. The cause of this media loss may be due to excessively high
backwash rates during the winter months when the water is colder and therefore denser.
As a general guideline, for each 1oC change in water temperature, the wash water rate
should be adjusted by two percent. This would provide a higher flow as the water warms
and lower flow as the water cools. Adjustment to the backwash rate should improvebackwash efficiency.
The backwash pump is capable of providing a maximum rate of 5,200 gpm which is
approximately 15 gpm/ft2.
The actual filter media expansion was measured using a bed expansion device during a
typical backwash cycle. Results of the bed expansion test are given later in this section.
The backwash rate should be established by direct measurement of the bed expansion at
different water temperatures. The expansion of a filter bed should be at least 30 percent.
The average backwash cycle uses approximately 54,400 gallons of water. As a guideline,
a typical backwash cycle would range between 100 gallons and 150 gallons per square
foot of filter area. Using this guideline, each filter backwash should use between 35,200
gallons and 52,700 gallons of wash water. Based on this, it appears that the filters are
backwashed too long during a normal wash cycle. This excessive backwash duration may
in part be caused by the backwash rate being too low (12.0 gpm/ft2 vs. 15.0 gpm/ft2) for
proper cleaning of the media at certain water temperatures.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
38/119
Optimization of Treatment for Disinfection Byproducts Control 38
The condition of the existing filter beds, current filter operation, and current backwash
procedures were reviewed. The bed of Filter 2 was assumed to be representative of all of
the filters. It was probed to identify the position of the existing gravel layers. Probing
revealed that the gravel layers were intact with no significant mounding of the gravel.
Some areas of the filter bed, however, did show some disruption of the gravel.
Measurements of the gravel profile analysis revealed some areas of the filter bed had in
excess of 2-inches difference in media depth. A difference in media depth of more than
one-inch indicates potential problems with the gravel layer.
Filter 2 was cored using a coring tube to examine the media for particle retention and
backwash efficiency. Acid solubility testing and sieve analyses were performed to
evaluate the filter media to determine if the media is suitable for continued use or will
require replacement.
Core samples revealed that particle retention was close to normal. Identical quantities of
these core samples were washed with identical quantities of water. The turbidity of this
water was measured to give an indication of the quantity of particles being retained in the
media samples. Based on these turbidity measurements, particle retention was found to be
greater in the first 2-inches of the media than would be expected.
Particle retention turbidity measurements from below the top 15-inches of media should
be less than 150 NTU/100 grams. The existing filters showed a particle retention
measurement of less than this limit. A graph of the particle retention profile is shown in
Figure 1.
Core samples taken after backwash confirmed that the backwash efficiency was less than
required. Turbidity measurements taken from the media following a typical backwash
cycle show that the filter media retained a significant amount of particles in the top
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
39/119
Optimization of Treatment for Disinfection Byproducts Control 39
portion of the filter following the backwash cycle. As noted previously, the bottom media
layers were found to retain few particles. The top layers of the media had turbidity
measurements greater than the recommended 30 NTU/100 grams to 60 NTU/100 grams.
Turbidity measurements in this range indicate the filter media to be sufficiently clean.
Based on the turbidity profiles found, the filter examined is considered to be dirty at the
top and too clean at the bottom. This indicates improvements are needed in backwash
practices. Typical backwash profile criteria are shown in Table 5. Figure 2 is a graph of
the backwash profile found.
Current operating practice is to start the surface wash operation and then begin the
backwash flow at 3,200 gpm. Each filter is washed for approximately two minutes at
3,200 gpm along with the surface wash. The backwash flow is then increased to
approximately 4,200 gpm and continues for eight minutes. The surface wash is allowed to
operate approximately 1.5 minutes into the high rate wash period and is stopped. After
the eight-minute high rate wash, the backwash rate is reduced over three minutes from
4,200 gpm to zero gpm. Analysis of the wash water during a typical backwash period
revealed that the backwash appears to be too long and is at a rate too low for proper
cleaning of the media. It appears from the data that a shortened backwash cycle at a
higher rate is needed to improve filter media cleaning. Turbidity analyses obtained during
a typical backwash cycle are shown in Table 6.
Established operating criteria indicate that a backwash cycle is complete when the wash
water turbidity falls below 10 NTU. It is generally accepted that once the wash water
turbidity falls to 10 NTU, the backwash cycle should be terminated. Removing too many
solids from the filter media increases the filter ripening period and the initial filtered
water turbidity. The current backwash turbidities are reduced well below 10 NTU after a
typical backwash period. Based on the backwash turbidities collected, it appears that the
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
40/119
Optimization of Treatment for Disinfection Byproducts Control 40
filter media is clean after approximately 4.5 minutes. Periodic evaluations can easily be
made to adjust the backwash length as needed based on actual operating conditions.
A bed expansion test was performed during the filter inspection. During the test, the bed
expansion was measured to be 20.8 percent. Based on this low bed expansion, a higher
backwash rate is needed. A second test was performed at the maximum backwash rate
(5,277 gpm or 15 gpm/ft2). Bed expansion measured at the higher flow rate was found to
be 29 percent. The second test confirms that proper bed expansion can be achieved.
An acid solubility test was performed on the filter media to identify the calcium
carbonate deposition rate on the media. Calcium carbonate deposition increases the
diameter of the media grains and can increase filter effluent turbidities and particle
counts. Typical acid solubility should be no more than 2 percent per year. The acid
solubility for the anthracite and sand media were found to be 0.8 percent and 0.3 percent,
respectively. These values equate to 0.08 percent per year for the anthracite and 0.03
percent per year for the filter sand. Based on this analysis, it is apparent that
recarbonation is being used properly and is providing stable water to the filters
preventing excessive calcium carbonate deposition.
Representative samples of the filter media were analyzed using sieve analysis to identify
the current effective size (ES) and uniformity coefficient (UC) of the filter media. Sieve
analysis results showed the anthracite media has an ES of 0.39 mm and a UC of 3.85. The
1989 specifications for the anthracite during media replacement indicated an ES of 0.93
and a UC of 1.60. The anthracite media no longer meets its original specifications.
Sieve analysis results for the sand showed its ES to be 0.42 mm and its UC to be 2.06.
The 1989 specifications for filter sand were an ES of 0.492 and a UC of 1.44. The sand
media, like the anthracite, no longer meets its original specifications.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
41/119
Optimization of Treatment for Disinfection Byproducts Control 41
Current Recommended Standards for filter media establish an ES for anthracite at 0.8
mm to 1.2 mm and a UC less than 1.65. Recommended Standards establishes an ES for
filter sand at 0.45 mm to 0.55 mm and the UC to be less than 1.65. The existing filter
media does not meet the recommended design criteria.
The high uniformity coefficient indicates that a higher backwash rate is necessary to
properly clean the media. Based on computer modeling, the sand and anthracite exhibit
dissimilar backwash needs for proper bed expansion. The calculated backwash rateneeded for existing anthracite is 45 gpm/ft2. The calculated backwash rate needed for the
existing sand is 31 gpm/ft2. These backwash rates cannot be achieved using the backwash
equipment and piping available.
Replacement of the filter media is considered necessary at this time to meet turbidity
regulations. Sieve analysis and acid solubility analysis should be preformed at least every
two years to determine the condition of the filter media. If the ES of the sand changes
more than 10 percent from design specifications, the media should be replaced.
Media having a low uniformity coefficient should be considered for the next filter media
replacement to reduce the backwash rate needed. This would more closely match the
filter backwash requirements to the capabilities of the backwash pump.
The Surface Water Treatment Rule (SWTR) establishes criteria for filter ripening to
reduce turbidity and particle count spikes during the initial portion of a filter run. Filter
ripening is a method used to properly condition the media in a freshly washed filter to
achieve the lowest possible turbidity and solids in the water when a filter is initially
placed in service. One of the ripening techniques is the use of filter-to-waste operations.
Filter-to-waste is a procedure of wasting the first portion of water during a filter run until
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
42/119
Optimization of Treatment for Disinfection Byproducts Control 42
the effluent turbidity is within acceptable limits or goals. Current filter-to-waste goals
establish that the turbidity in the filtered (wasted) water should be at or below 0.1 NTU
after a 15-minute filter-to-waste period and should not result in turbidity spikes above 0.3
NTU.
A filter-to-waste simulation was performed by plant personnel following the initiation of
a filter run. An evaluation of this showed that a filter-to-waste period of 15 minutes could
not meet the turbidity goals for filter ripening.
The simulated filter-to-waste period showed that the turbidity did not spike above 0.2
NTU, but approximately 90 minutes was needed to reduce the filtered water turbidity to
0.1 NTU. Turbidity measurements taken during the simulated filter-to-waste period are
shown in Table 7. It is apparent that the solids necessary for proper filter ripening are
being removed during backwash.
Individual filter effluent turbidity meters are needed to optimize filtration. The Long
Term 1 ESWTR requires continuous monitoring of individual filter effluents for turbidity.
Filter wash water currently is drained to a waste wash water wet well below the
recarbonation basin. The wet well was installed as part of the original plant and has a
capacity of approximately 46,000 gallons, which currently is less than one filter wash.
Wash water is pumped back to the raw water reservoir for reuse. It is not recommended to
recycle wash water for reuse unless proper treatment of the wash water is provided. Wash
water typically contains microorganisms, suspended particles, and organic contaminants
that can be 20 times greater than the raw water concentrations. Recycling these
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
43/119
Optimization of Treatment for Disinfection Byproducts Control 43
contaminants can lead to difficulties in treatment especially while trying to meet
disinfection byproduct and enhanced coagulation requirements.
A significant amount of biological activity was observed in the filter media during the
evaluation. It is unknown at this time what effect this biological activity has on filtered
water quality (i.e. organics), however, any such contributions are believed to be
undesirable. Periodic chlorination of the filter influent at a dosage of approximately 0.5
mg/L should control the biological activity and could improve overall filtered water
quality.
g) Transfer Pumping (Intermediate Pumping)
Three transfer pumps currently are used to transfer filtered water from the plant to the
above ground storage tanks (clearwells). Each pump has a capacity of 1,050 gpm at a
head of 42 feet. The firm capacity for transfer pumping is 2,100 gpm (3 MGD, with one
pump out of service.) It appears that the existing transfer pumps are adequate to meet the
current needs of the treatment plant.
h) Clear Well Storage (Finished Water Storage) and Disinfection
Disinfection of the filtered water is accomplished by adding chlorine to the water and
allowing a period of contact for the chlorine to react with the contaminants.
Two above ground clearwells provide finished water storage and provide the necessary
detention time (contact time). One 0.5 million gallon (MG) clearwell and one 1.0 MG
clearwell currently are operated in series following chlorine addition. The clearwells
provide a hydraulic detention time of approximately 12.2 hours at the plant design flow
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
44/119
Optimization of Treatment for Disinfection Byproducts Control 44
rate. The Ohio EPA has assigned an effective volume factor (EVF) of 0.25 to each
clearwell. Typical EVFs in Ohio range from 0.1 to 0.6. The EVF is based on the design
of the clearwell and physical testing by tracer to determine how soon water delivered to
the clearwells appears at the outlet. This factor determines the effective contact time in
each clearwell for CT calculations. At the minimum clearwell operating level and
maximum production rate, the clearwells have an effective detention time of 112 minutes.
Based on plant records of chlorine residuals and calculated CT values, both the minimum
chlorine residuals are maintained and the required CT values are met. Historical data
showed that there were no maximum chlorine residuals above the maximum level of 4
mg/L established in the DBPR.
Future changes in the regulations may increase the required CT values significantly for
inactivation of Cryptosporidium (and/or other microbials). Additional clearwell storage is
not needed at this time to meet CT requirements.
Design standards require that CT values for disinfection be maintained during clearwell
cleaning and maintenance operations. This requirement is met when the clearwell still in
service is operated near its maximum water level.
Baffling within the clearwells would reduce short circuiting to provide a larger EVF and
aid in meeting future CT requirements that are expected to be more stringent. This would
allow the future regulations to be met using the existing clearwells.
Water industry practices are to maintain a free chlorine residual in the finished water of at
least 80 percent of the total chlorine residual. This practice prevents chlorinous tastes and
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
45/119
Optimization of Treatment for Disinfection Byproducts Control 45
odors in the drinking water caused by the partial oxidation of inorganic contaminants.
The ratio of the free to the total chlorine residual in the water produced here currently
averages 86 percent.
The Ohio EPA requires that provisions for chlorination be available for treating the raw
water, settled water, filtered water, and water entering the distribution system. There are
currently chlorination points available for raw water and filtered water. New chlorine
feed points are needed at the high service pump suction header and for the filter influent.
These additional feed points will allow compliance with current recommended standards.
i) High Service Pumping
Currently, there are three high service pumps and an auxiliary connection to provide wash
water from the high service pump header. Existing pump capacities are shown in Table 8.
Based on Recommended Standards, the high service pumping is adequate for the rated
plant capacity. Recommended Standards states that the high service pumps should be
capable of pumping the rated plant capacity with the largest pump out of service. There
also appears to be sufficient variation in pump capacities to allow a variety of pumping
rates. It may be beneficial at some future date to install variable frequency drives to allow
more flexibility in pumping rates. An additional high service pump may be needed to
match pumping capacity to a future plant capacity increase. Space was provided in the
original plant design to install a fourth high service pump.
3) Chemical Feed Systems
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
46/119
Optimization of Treatment for Disinfection Byproducts Control 46
The chemical feed systems are at the heart of any conventional water treatment plant.
These systems have to be capable of delivering the chemicals not only in sufficient
quantity but deliver them in very accurate dosages to the right location.
Recommended Standards specifies that at least a 30-day supply of chemicals be available
in storage based on the average plant production rates. An examination of chemical usage
records and the chemical storage facilities show that there is sufficient storage for all
existing chemicals.
Recommended Standards also recommends that redundant or backup feed equipment be
provided for each chemical feed system. Currently, only the lime feed system and
chlorination systems have this redundancy.
A list of the chemical feed equipment, their capacities and application points is given in
Table 9.
a) Potassium Permanganate
At the time of this study no potassium permanganate feed system was installed. It may be
beneficial to install a potassium permanganate feed system. Potassium permanganate is
primarily used as a taste and odor control chemical as well as an oxidizer. Potassium
permanganate is commonly used for the removal of taste and odor compounds that
cannot be adsorbed by activated carbon. Potassium permanganate can also be used to
oxidize various organic compounds and provide an oxygen bond between suspended
particles for improved coagulation treatment.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
47/119
Optimization of Treatment for Disinfection Byproducts Control 47
Previous to this study, the Village was granted approval by the Ohio EPA to install a
potassium permanganate feed system. The system has not been installed and should be
included in any plant improvements.
Potassium permanganate is usually added ahead of carbon pretreatment and coagulation.
It has been found that even small doses of permanganate can improve overall treatment
and water quality. Jar testing covered in Section III will bear out the viability of
potassium permanganate treatment.
Caution must be exercised when feeding potassium permanganate so that the chemical is
fully reacted prior to the application of activated carbon to avoided interference.
Activated carbon and potassium permanganate feed points must not be close to each
other.
b) Powdered Activated Carbon
Carbon dosages applied to the raw water appear to be in the normal range for a surface
water treatment plant. Carbon is typically applied for taste and odor control. Plant
personnel stated that taste and odor complaints are uncommon indicating that the
chemical dosages may be at the proper concentration for effective treatment of tastes and
odors. Use of a more reactive carbon product (higher iodine number) was recently
implemented for improved removal of taste and odor causing compounds.
It is believed that continuous carbon feed helps to control TOC concentrations which in
turn control the formation of disinfection byproducts after chlorination.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
48/119
Optimization of Treatment for Disinfection Byproducts Control 48
The current carbon feed point allows for minimal carbon contact time before other
treatment chemicals are added. Shortly after carbon treatment, lime and soda ash are
applied to the water, which quickly increases the pH. Carbon is most effective at lower
water pH values (below pH 8.5).
A pretreatment basin should be considered in the future to provide sufficient carbon
contact time for optimal treatment. Normally, a 15-minute to 30-minute contact time is
recommended for carbon pretreatment.
c) Coagulant Feed System
The current ferric chloride dosage appears to be sufficient for turbidity control based on
the filtered water turbidity levels and filter run hours. The treated water results in a low
turbidity filter effluent averaging about 0.09 NTU.
Jar testing was performed to determine the coagulant type and dosage needed for
optimum organics removal, particularly for DBP precursor control. It is expected that a
much higher coagulant dosage may be needed for organics control to meet future
drinking water standards.
The most effective application point for coagulant chemicals is to the water at or near the
rapid mix impeller. This provides the best dispersion into the water in the shortest amount
of time.
Ferric chloride is currently applied to the raw water at the in-line mixer upstream of the
primary (west) rapid mix basin. The feed point should be relocated to the rapid mix basin
and should discharge immediately above the mixer impeller.
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
49/119
Optimization of Treatment for Disinfection Byproducts Control 49
d) Lime Feed System
Lime is applied to the water for softening. It raises the pH through the addition of
hydroxide anions that convert the more soluble calcium bicarbonate to the less soluble
calcium carbonate form allowing a portion of the calcium to precipitate.
There are two identical lime feeders currently in operation. Both feeders are capable of
supplying substantially more than the required dosage individually. Since the feeders are
supplied by separate silos they are operated in rotation on approximately a 30 day cycle.As one silo goes empty, the other is placed in service until a new load of lime arrives.
Lime is applied to the raw water inlet flume ahead of the primary (west) rapid mix basin
for softening. Typically, lime and coagulant chemical applications should be separated to
allow the coagulation reactions to proceed to completion before the higher pH chemical
is added. The most effective treatment method is to add a coagulant to the water first to
take advantage of the lower raw water pH for more effective treatment. Additionally, lime
treatment can interfere with activated carbon treatment.
The lime feed point should be relocated to the mixing zone of the clarifiers since lime
does not need high intensity mixing for effective treatment like a coagulant. Relocation of
the lime feed point also should improve coagulation by providing a more effective pH for
coagulation reactions in the rapid mix basins. Minor lime feed system modifications and
the construction of an eductor box will allow lime to be fed to the existing clarifiers
where needed.
e) Soda Ash (Sodium Carbonate) Feed System
-
8/14/2019 Optimization for Disinfection Byproducts_11!15!2008
50/119
Optimization of Treatment for Disinfection Byproducts Control 50
Soda ash aids in softening because the sodium has a lower electronegativity than either
calcium or magnesium and will exchange with them on sulfate and chloride anions. This
exchange results in the formation of calcium or magnesium carbonate, depending upon
pH, which will then precipitate.
The soda ash is presently fed at the same point as the lime, and as with the lime, this
point should be relocated to the clarifier mixing zone. As with lime, soda ash does not
need high intensity mixing for effective treatment making the clarifier mixing (reaction)
zone a