Operating InstructionsCapacitive rod electrode for level detection
VEGACAP 63- contactless electronic switch
Document ID: 30009
2
Contents
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
Contents1 About this document
1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4
2 For your safety2.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 Safety label on the instrument .......................................................................................... 62.6 CE conformity ................................................................................................................... 62.7 Safety instructions for Ex areas ........................................................................................ 62.8 Environmental instructions ............................................................................................... 6
3 Product description3.1 Configuration .................................................................................................................... 73.2 Principle of operation........................................................................................................ 83.3 Operation ......................................................................................................................... 93.4 Packaging, transport and storage ..................................................................................... 93.5 Accessories and replacement parts ............................................................................... 10
4 Mounting4.1 General instructions ....................................................................................................... 124.2 Mounting instructions ..................................................................................................... 13
5 Connecting to power supply5.1 Preparing the connection ............................................................................................... 155.2 Connection procedure .................................................................................................... 155.3 Wiring plan, single chamber housing.............................................................................. 16
6 Setup6.1 General information ........................................................................................................ 196.2 Adjustment elements ...................................................................................................... 196.3 Function table ................................................................................................................. 22
7 Maintenanceandfaultrectification7.1 Maintenance .................................................................................................................. 237.2 Rectify faults ................................................................................................................... 237.3 Exchange of the electronics module ............................................................................... 257.4 How to proceed if a repair is necessary .......................................................................... 27
8 Dismount8.1 Dismounting steps.......................................................................................................... 288.2 Disposal ......................................................................................................................... 28
9 Supplement9.1 Technical data ................................................................................................................ 299.2 Dimensions .................................................................................................................... 329.3 Industrial property rights ................................................................................................. 349.4 Trademark ...................................................................................................................... 34
3
Contents
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
Supplementary documentationInformation:Supplementary documents appropriate to the ordered version come withthedelivery.Youcanfindthemlistedinchapter"Product descrip-tion".
Instructions manuals for accessories and replacement partsTip:ToensurereliablesetupandoperationofyourVEGACAP63,weofferaccessories and replacement parts. The corresponding documenta-tions are:
• 30174 - Electronics module VEGACAP series 60• 34296 - Protective cover• 31088 - Flanges according to DIN-EN-ASME-JIS-GOST
Editing status: 2016-02-19
4
1 About this document
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
1 About this document
1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectification.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.
1.2 Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.
1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applicationsThis symbol indicates special instructions for Ex applications.
SIL applicationsThis symbol indicates instructions for functional safety which must be taken into account particularly for safety-relevant applications.
• ListThe dot set in front indicates a list with no implied sequence.
→ ActionThis arrow indicates a single action.
1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.
Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.
5
2 For your safety
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
2 For your safety
2.1 Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.
2.2 Appropriate useThe VEGACAP 63 is a sensor for point level detection.Youcanfinddetailedinformationabouttheareaofapplicationinchapter"Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.
2.3 Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specifichazards,e.g.vesseloverfillordamagetosystemcomponents through incorrect mounting or adjustment.
2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.
6
2 For your safety
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must be observed.
2.6 CE conformityThisdevicefulfillsthelegalrequirementsoftheapplicableECguide-lines.ByattachingtheCEmark,VEGAprovidesaconfirmationofsuccessfultesting.YoucanfindtheCEconformitydeclarationinthedownloadareaof"www.vega.com".
2.7 Safety instructions for Ex areasPleasenotetheEx-specificsafetyinformationforinstallationandop-eration in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.
2.8 Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertifiedaccordingto DIN EN ISO 14001.Pleasehelpusfulfillthisobligationbyobservingtheenvironmentalinstructions in this manual:
• Chapter"Packaging, transport and storage"• Chapter"Disposal"
7
3 Product description
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
3 Product description
3.1 ConfigurationThe scope of delivery encompasses:
• VEGACAP 63 point level switch• Documentation
– This operating instructions manual – SafetyManual"Functional safety (SIL)"(optional) – Supplementaryinstructionsmanual"Plug connector for level
sensors"(optional) – Ex-specific"Safety instructions"(withExversions) – Ifnecessary,furthercertificates
The VEGACAP 63 consists of the components:
• Processfittingwithprobe• Housing with electronics• Housing cover, optionally available with display and adjustment
module
1
2
3
Fig. 1: VEGACAP 63 - rod version with plastic housing1 Housing cover with integrated display and adjustment module (optional)2 Housing with electronics3 Processfitting
Thetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:
Scope of delivery
Constituent parts
Type label
8
3 Product description
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
2
1
11
10
13
12
14
15
9
3
6
4
5
78
Fig. 2: Layout of the type label (example)1 Instrument type2 Product code3 Approvals4 Process and ambient temperature, process pressure5 Power supply and signal output, electronics6 Protection rating7 Probe length8 Order number9 Serial number of the instrument10 Material, wetted parts11 Symbol of the device protection class12 Reminder to observe the instrument documentation13 ID numbers, instrument documentation14 NotifiedauthorityforCEmarking15 Approval directives
With the serial number, you can access the delivery data of the instru-ment via www.vega.com,"VEGA Tools"and"serial number search".Youcanfindtheserialnumberontheinsideoftheinstrumentaswellas on the type label on the outside.
3.2 Principle of operationVEGACAP 63 is a point level sensor for use in non-abrasive liquids and bulk solids.The rod probe is fully insulated and the proven mechanical construc-tionoffershighfunctionalsafety.
Probe, measured product and vessel wall form an electrical capacitor. Thecapacitanceisinfluencedbythreemainfactors.
Area of application
Functional principle
9
3 Product description
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
1
2
3
Fig. 3: Functional principle - Plate capacitor1 Distance between the electrode surfaces2 Size of the electrode surfaces3 Type of dielectric between the electrodes
The probe and the vessel wall are the capacitor plates. The measured product is the dielectric. Due to the higher dielectric constant of the product compared to air, the capacitance increases as the probe is gradually covered.The capacitance change is converted by the electronics module into a switching command.
VEGACAP 63 is a compact instrument, i.e. it can be operated without external evaluation system. The integrated electronics evaluates the level signal and outputs a switching signal. With this switching signal, aconnecteddevicecanbeoperateddirectly(e.g.awarningsystem,apumpetc.).Thedataforpowersupplyarespecifiedinchapter"Technical data".
3.3 OperationThe probe can be adapted to the dielectric constant of the product directly on the electronics module.A switching command can be triggered when the probe is covered or laid bare.Ontheelectronicsmoduleyouwillfindthefollowingdisplayandadjustment elements:
• Signallampforindicationoftheswitchingcondition(green/red)• Potentiometer for switching point adaptation• DIL switch for measuring range selection• DIL switch for mode adjustment
3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE
Voltage supply
Packaging
10
3 Product description
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
foil is also used. Dispose of the packaging material via specialised recycling companies.
Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:
• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration
• Storageandtransporttemperatureseechapter"Supplement - Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
3.5 Accessories and replacement partsThe protective cover protects the sensor housing against soiling and intense heat from solar radiation.Youwillfindadditionalinformationinthesupplementaryinstructionsmanual"Protective cover"(Document-ID34296).
Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual"Flanges according to DIN-EN-ASME-JIS".
Therearedifferentreasonsfortheuseofascreeningtubeadapter.
CondensationIn case of strong condensation, the draining of condensed water can change the measurement accuracy. The suitable version is the Screening against condensation.Thecondensationcandrainoffoutside on the screening tube adapter.Typical applications of the screening tube adapters are e.g. for condensation or sockets. Apart from the standard version, there is a second version for vacuum with a sepcial seal. When the screen-ing tube adapter is submerged in liquid, we recommend the use of a vacuum-tight version.
Transport
Transport inspection
Storage
Storage and transport temperature
Protective cap
Flanges
Screening tube adapter
11
3 Product description
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
SocketIn case of long sockets, the screening tube can increase the sensitiv-ityoftheprobebycompensatingtheinfluencesofthesocket.Thesuitable version is Capacitive screening, vacuum-tight.When the probe is mounted laterally, buildup can accumulate in the socket. A screening tube makes the covered part of the probe inactive andhenceinsensitivetoinfluencefrombuildupandsocket.Hence,thescreeningtubeadapterexcludeschanginginfluencescausedbythe medium and ensures stable measurement conditions. The suit-able version is Capacitive screening, vacuum-tight.
12
4 Mounting
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
4 Mounting
4.1 General instructionsMake sure that all parts of the instrument coming in direct contact with the process, especially the sensor element, process seal and processfitting,aresuitablefortheexistingprocessconditions,suchas process pressure, process temperature as well as the chemical properties of the medium.Youcanfindthespecificationsinchapter"Technical data"andonthenameplate.
In general the level switch can be mounted in any position. The instru-ment must be mounted in such a way that the probe is at the height of the requested switching point.
Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling.Ground the probe before welding directly on the rod or cable.
With threaded versions, the housing must not be used to screw in the instrument. Applying tightening forces on the housing can damage its internal parts.Use the hexagon for screwing in.
Usetherecommendedcables(seechapter"Connecting to power supply")andtightenthecablegland.You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cableentry.Rainandcondensationwatercanthusdrainoff.Thisap-plies mainly to outdoor mounting as well as installation in areas where highhumidityisexpected(e.g.throughcleaningprocesses)oroncooled or heated vessels.
Fig. 4: Measures against moisture ingress
DonotholdVEGACAP63ontheprobe.Especiallywithheavyflangeversions or long rod versions, the sensor can be damaged simply by the weight of the instrument.
Suitability for the process conditions
Switching point
Welding work
Handling
Moisture
Transport
13
4 Mounting
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
Theprocessfittingmustbesealedifthereisgaugeorlowpressureinthe vessel. Before use, check if the seal material is resistant against the measured product and the process temperature.Themax.permissiblepressureisspecifiedinchapter"Technical data"oronthetypelabelofthesensor.
Metal vesselMake sure that the mechanical connection of the probe to the vessel iselectricallyconductivetoensuresufficientgrounding.Use conductive seals, such as those made of copper or lead, etc. Insulatingmeasures,suchascoveringthethreadwithTeflontape,can interrupt the necessary electrical connection with metal vessels. For this reason, ground the probe on the vessel or use a conductive seal material.Non-conductive vesselsIn non-conductive vessels, e.g. plastic tanks, the second pole of the capacitor must be provided separately, e.g. in the form of a concentric tube.
Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.
NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.
4.2 Mounting instructionsDuetotheeffectsofagitators,equipmentvibrationorsimilar,thelevelswitch can be subjected to strong lateral forces. For this reason, do not use an overly long electrode for VEGACAP 63, but check if you canmountashortlevelswitchonthesideofthevesselinhorizontalposition.Extreme vibration caused by the system, e.g. due to agitators or turbulenceinthevesselfromfluidisation,cancausetheprobeofVEGACAP 63 to vibrate in resonance. If a longer rod version is neces-sary, you can secure the probe by fastening a suitable brace or guy directly above the end of the rod.
Iftheinstrumentismountedinthefillingstream,unwantedfalsemeasurement signals can be generated. For this reason, mount the instrument at a position in the vessel where no disturbances, e.g. from fillingopenings,agitators,etc.,canoccur.This applies particularly to instrument versions with a longer probe.
Pressure/Vacuum
Vessel material
Cable entries - NPT threadCable glands
Agitatorsandfluidization
Inflowingmedium
14
4 Mounting
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
Fig.5:Inflowingmedium
The probe should protrude into the vessel to avoid buildup. For that reason,avoidusingmountingbossesforflangesandscrewedfittings.This applies particularly to use with adhesive products.
To compensate the normal voltage loss due to sealing materials, you havetoadditionallyusediscspringsforfasteningflangescrewsonPTFEcoatedflanges.Tightenthescrewsmoderatelywiththetorquestated in the technical data.
Socket
Torque with PTFE plated flanges
15
5 Connecting to power supply
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
5 Connecting to power supply
5.1 Preparing the connectionAlways keep in mind the following safety instructions:
Warning:Connect only in the complete absence of line voltage.
• The electrical connection must only be carried out by trained personnel authorised by the plant operator.
• Alwaysswitchoffpowersupply,beforeconnectingordisconnect-ing the instrument.
Note:Install a separating facility for the instrument which is easy to access. Theseparatingfacilitymustbemarkedfortheinstrument(IEC/EN61010).
Connect mains voltage according to the connection diagrams. Take note of the general installation regulations. The electronics module CP60C is designed in protection class I. To maintain this protection class, it is absolutely necessary that the ground conductor be con-nected to the internal ground conductor terminal. Take note of the corresponding installation regulations for Ex applications.Thedataforpowersupplyarespecifiedinchapter"Technical data".
The instrument is connected with standard three-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used.Use cable with round cross-section. A cable outer diameter of 5…9mm(0.2…0.35in)ensuresthesealeffectofthecablegland.Ifyouareusingcablewithadifferentdiameterorcross-section,exchange the seal or use a suitable cable gland.
5.2 Connection procedureWith Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present.
Proceed as follows:1. Unscrew the housing lid2. Loosen compression nut of the cable gland and remove blind
plug3. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.
1cm(0.4in)ofinsulationfromtheendsoftheindividualwires4. Insert the cable into the sensor through the cable entry5. Lifttheopeningleversoftheterminalswithascrewdriver(see
followingillustration)6. Insert the wire ends into the open terminals according to the wir-
ing plan
Note safety instructions
Voltage supply
Connection cable
16
5 Connecting to power supply
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
7. Press down the opening levers of the terminals, you will hear the terminal spring closing
8. Check the hold of the wires in the terminals by lightly pulling on them
9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable
10. If necessary, carry out a fresh adjustment11. Screw the housing lid back onTheelectricalconnectionisfinished.
Fig. 6: Connection steps 5 and 6
5.3 Wiring plan, single chamber housing
1
444
2 3
Fig. 7: Material versions, single chamber housing1 Plastic (not with dust-Ex)2 Aluminium3 Stainless steel4 Filter element for air pressure compensation
Housing overview
17
5 Connecting to power supply
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
4
5
6
3
2
1
Fig. 8: Electronics and terminal compartment1 Potentiometer for switching point adaptation2 DIL switch for measuring range selection3 DIL switch for mode adjustment4 Ground terminal5 Connection terminals6 Control lamp
We recommend connecting VEGACAP 63 in such a way that the switching circuit is open when there is a level signal, line break or failure(safestate).The contactless electronic switch is always shown in non-operative condition.
Warning:The instrument must not be operated without an intermediately connected load, because the electronics would be destroyed if con-nected directly to the mains. It is not suitable for connection to low voltage PLC inputs.
Examples for typical applications:
• Loadresistanceat24VDC:88…1800Ω• Rated power, relay 253 V AC: > 2.5 VA• Rated power, relay 24 V AC: > 0.5 VA
For direct control of relays, contactors, magnet valves, warning lights, horns etc.Domestic current is temporarily lowered below 1 mA after switching offtheloadsothatcontactors,whoseholdingcurrentislowerthanthe constant domestic current of the electronics, are reliably switched off.
Electronics and terminal compartment
Wiring plan
18
5 Connecting to power supply
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
WhenVEGACAP63isusedaspartofanoverfillprotectionsystemaccording to WHG, also note the regulations of the general type ap-proval.
1
Fig. 9: Wiring plan1 Voltage supply
19
6 Setup
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
6 Setup
6.1 General informationThefiguresinbracketsrefertothefollowingillustrations.
Ontheelectronicsmoduleyouwillfindthefollowingdisplayandadjustment elements:
• Potentiometer for switching point adaptation• DIL switch for measuring range selection• DIL switch for mode adjustment - min./max.• Control lamp
Note:Asarule,alwayssetthemodewiththemodeswitch(3)beforestart-ing setup VEGACAP 63. The switching output will change if you set themodeswitch(3)afterwards.Thiscouldpossiblytriggerothercon-nected instruments or devices.
6.2 Adjustment elements
4
5
6
3
2
1
Fig. 10: Oscillator - Contactless electronic switch1 Potentiometer for switching point adaptation2 DIL switch for measuring range selection (with compensation button)3 DIL switch for mode adjustment4 Ground terminal5 Connection terminals6 Control lamp
The switching status of the electronics can be checked with closed housing(onlyplastichousing),see"Function table".
Note:Screw the housing cover tightly up to the thread stop so that the inspectionglassisabovethecontrollamp(LED).
Function/Configuration
20
6 Setup
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
ToadjustVEGACAP63,firstofallremovethehousingcover.
You can adapt the switching point to the solid with the potentiometer.
Withthepotentiometer(1)andthemeasuringrangeselectionswitch(2)youcanchangethesensitivityoftheprobetotheelectricalproper-ties of the product and the conditions in the vessel. This is necessary so that the level switch can also reliably detect products e.g. with very loworveryhighdielectricfigure.range 1: 0 … 20 pFRange 2: 0 … 85 pFRange 3: 0 … 450 pF
Withthemodeswitch(3)youcanchangetheswitchingstatusoftheoutput. The required mode can be set according to the function table.max.-max.detectionoroverfillprotectionmin. - min. detection or dry run protection.We recommend connecting according to the idle current principle (contactlesselectronicswitchisopenwhentheswitchingpointisreached)becausethecontactlesselectronicswitchtakesonthesame(safe)stateifafailureisdetected.
Control lamp for indication of the switching status.
• green = switch closed• red = switch open• red(flashing)=failure
The adjustment of the switching point is only possible in installed condition.Thespecificationsinparenthesisrefertotheprecedingillustration.
Horizontallymountedprobes,angledprobes1. Setmodeswitch(3)tomodemax[min.].2. Setmeas.rangeselectionswitch(2)torange1.3. Make sure the probe is not covered by the medium.4. Turnthepotentiometer(1)to0,thecontrollamp(6)lightsred
[lightsgreen].5. Todeterminetheemptyswitchpoint,turnthepotentiometer(1)
veryslowlyclockwiseuntilthecontrollamplightsgreen[lightsred].Ifthecontrollampstilllightsred[lightsgreen],thenyouhavetosetthemeas.rangeselectionswitch(2)tothenexthigherstageandrepeatthesettingwiththepotentiometer(1)untilthecontrollamplightsgreen[lightsred].
6. Notethepositionofthepotentiometer(1).Insomecasesthelowestrange(range1=highestsensitivity)isnotsufficienttoadjustthefullswitchpoint.Thiswouldmakeanotherfillingprocedurenecessary.
Switching point adapta-tion (1)Measuring range selec-tion switch (2)
Mode adjustment (3)
Signal lamp (6)
Switching point adjust-ment
Mode max. [mode min.]
21
6 Setup
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
For this reason we recommend setting and noting the empty switching point in all three meas. ranges. Set the meas. range se-lectionswitch(2)tothenexthigherrangeandrepeatthesetting.Also note the values for the next ranges.
7. Resetmeas.rangeselectionswitch(2)tothenextlowerrangeinwhichthecontrollamplightsgreen[lightsred].
8. Fill the vessel until the probe is completely covered.9. Turnthepotentiometer(1)veryslowlyclockwiseuntilthecontrol
lamplightsgreen[lightsred].10. Notethepositionofthepotentiometer(1).Werecommenddocu-
menting the value of the empty switch point and the full switch point as well as the range.
11. Ifthecontrollampdoesnotlightgreen[lightred],thenyouhavetosetthemeas.rangeswitch(2)tothenexthigherstageandrepeat the setting with the potentiometer until the control lamp lightsgreen[lightsred].
12. Setthepotentiometer(1)totheaveragevalueofthetwonotedvalues.
The measuring system is now ready for operation.
Empty adjustment Full adjustment
range 1
range 2
range 3Tab. 1: Note the position of the potentiometer.
Note:Ifyoudonotfindthefullswitchpointinoneoftheranges,werecom-mendsettingthemeas.rangeselectionswitch(2)tothelowestrangein which you have found the empty switch point. Set the potentiometer (1)totheaveragevaluebetweenemptyswitchpointand10.
Vertically mounted probes1. Setmodeswitch(3)tomodemax.2. Setmeas.rangeselectionswitch(2)torange1.3. Fill the vessel up to the requested level.4. Turnpotentiometer(1)toposition10.
Whenthecontrollamp(6)lightsred:setthemeasuringrangeselectionswitch(2)tothenexthighermeasuringrange.Whenthecontrollamp(6)lightsgreen:continuewiththenextitem.
5. Turnthepotentiometer(1)veryslowlyanticlockwiseuntilthecontrollamp(6)lightsred.
The measuring system is now ready for operation.1. Setmodeswitch(3)tomodemin.2. Setmeas.rangeselectionswitch(2)torange1.3. Lower the level to the requested min. level.
Mode max. (max. level detection)
Mode min. (min. level detection)
22
6 Setup
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
4. Turnthepotentiometer(1)to0,thecontrollamp(6)lightsgreen.5. Turnthepotentiometer(1)veryslowlyclockwiseuntilthecontrol
lamp(6)lightsred.Ifthecontrollampdoesnotlightred,setthemeas.rangeselectionswitch(2)tothenexthigherstageandrepeatthesettingwiththepotentiometer(1)untilthecontrollamplights red.
The measuring system is now ready for operation.
6.3 Function tableThe following table provides an overview of the switching conditions depending on the set mode and the level.
Level Switching status Control lamp
Mode max.Overflowprotec-tion 21
Switch closed Green
Mode max.Overflowprotec-tion 21
Switch open Red
Mode min.Dry run protection
21
Switch closed Green
Mode min.Dry run protection
21
Switch open Red
Failure of the sup-ply voltage(min./max.mode)
any
21
Switch open
Fault any
21
Switch open flashesred
23
7Maintenanceandfaultrectification
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
7 Maintenanceandfaultrectification
7.1 MaintenanceIf the instrument is used properly, no special maintenance is required in normal operation.
7.2 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.
VEGACAP63offersmaximumreliability.Nevertheless,faultscanoc-cur during operation. These may be caused by the following, e.g.:
• Sensor• Process• Voltage supply• Signal processing
Thefirstmeasuretotakeistochecktheoutputsignal.Inmanycases,thecausescanbedeterminedthiswayandthefaultsquicklyrectified.
Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.Thehotlineismanned7daysaweekround-the-clock.Sinceweofferthis service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.
Reaction when malfunc-tion occurs
Causes of malfunction
Faultrectification
24 hour service hotline
24
7Maintenanceandfaultrectification
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
Error Cause Rectification
– The instrument signals covered without cover-ing with the medium
– The instrument signals covered with cover-ing with the medium
Wrong mode se-lected on the signal condition-ing instrument
Set the correct mode on the mode switch of the signal conditioning in-strument(A:overflowprotection,B:dryrunprotection).Wiringshouldbecarried out according to the idle cur-rent principle.
Operating voltage too low
Check operating voltage
Shortcircuit in the probe, e.g. be-cause of moisture in the housing
Remove the electronics module. Check the resistance between the marked plug connections. See the fol-lowing instructions.
Electronics de-fective
Pushthemodeswitch(A/B)onthesignal conditioning instrument. If the signal conditioning instrument then changes the mode, the probe may be mechanically damaged. Should the switching function in the correct mode still be faulty, return the probe for repair.Check if there is buildup on the probe, and if so, remove it.
Unfavourable in-stallation location
Check if the probe is covered by build-up on the socket.Mount the instrument at a location in the vessel where e.g. no mounds can form.
Signallampflash-es red
Electronics mod-ule has detected a failure
Exchange the instrument or send it in for repair
Remove the electronics module. Check the resistance between the two plug connections.Theremustnolongerbeaconnection(highimpedance).Ifthereisstill a connection - exchange the instrument or return it for repair
Checking the switching signal
Check the resistance in the probe
25
7Maintenanceandfaultrectification
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
1 2 3
Fig. 27: Check the resistance in the probe1 Shielding2 Measuring probe3 Ground potential
Depending on the reason for the fault and the measures taken, the stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.
7.3 Exchange of the electronics moduleIn general, all electronics modules of series CP60 can be inter-changed.Ifyouwanttouseanelectronicsmodulewithadifferentsignal output, you can download the corresponding operating instruc-tions manual from our homepage under Downloads.Proceed as follows:1. Switchoffpowersupply2. Unscrew the housing lid3. Lift the opening levers of the terminals with a screwdriver4. Pull the connection cables out of the terminals5. Loosenthetwoscrewswithascrewdriver(TorxsizeT10orslot
4)
Reaction after fault recti-fication
26
7Maintenanceandfaultrectification
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
2
1
Fig. 28: Loosen the holding screws1 Electronics module2 Screws (2 pcs.)
6. Pull out the old electronics module7. Compare the new electronics module with the old one. The type
label of the electronics module must correspond to that of the old electronics module. This applies particularly to instruments used inhazardousareas.
8. Compare the settings of the two electronics modules. Set the adjustment elements of the new electronics module to the same setting of the old one.
Information:Make sure that the housing is not rotated during the electronics ex-change.Otherwisetheplugmaybeinadifferentpositionlater.
9. Insert the electronics module carefully. Make sure that the plug is in the correct position.
10. Screw in and tighten the two holding screws with a screwdriver (TorxsizeT10orPhillips4)
11. Insert the wire ends into the open terminals according to the wir-ing plan
12. Press down the opening levers of the terminals, you will hear the terminal spring closing
13. Check the hold of the wires in the terminals by lightly pulling on them
14. Check cable gland on tightness. The seal ring must completely encircle the cable.
15. Mount the probe into the vessel. Make sure that the probe is uncovered.
27
7Maintenanceandfaultrectification
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
21
Fig. 29: Compensation key1 Measuring range selection switch (compensation key)2 Control lamp
16. Keepthemeasuringrangeselectionswitch(1)pusheduntilthecontrollamp(2)flashesgreen.
17. Carryouttheadjustmentagain.Seechapter"Set-up, adjustment elements".
18. Screw the housing lid back onTheelectronicsexchangeisnowfinished.
7.4 How to proceed if a repair is necessaryYoucanfindaninstrumentreturnformaswellasdetailedinfor-mation of the procedure in the download area on our homepage: www.vega.com.By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:
• Printandfilloutoneformperinstrument• Clean the instrument and pack it damage-proof• Attach the completed form and, if need be, also a safety data
sheet outside on the packaging• Please contact the agency serving you to get the address for
thereturnshipment.Youcanfindtheagencyonourhomepagewww.vega.com.
28
8 Dismount
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
8 Dismount
8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc.
Takenoteofchapters"Mounting"and"Connecting to power supply"and carry out the listed steps in reverse order.
8.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the parts to be easily separable.
WEEE directive 2002/96/EGThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a spe-cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.Correctdisposalavoidsnegativeeffectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.Materials:seechapter"Technical data"If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.
29
9 Supplement
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
9 Supplement
9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts
Ʋ Processfitting-thread 316L Ʋ Processfitting-flange 316L Ʋ Process seal Klingersil C-4400 Ʋ insulation(fullyinsulated) PTFE, PE Ʋ Probe(rodfullyinsulated:ø16mm/0.63in)
316L
Materials, non-wetted parts Ʋ Plastic housing plasticPBT(Polyester) Ʋ Aluminium die-casting housing Aluminium die-casting AlSi10Mg, powder-coated - basis:
Polyester Ʋ Stainless steel housing - precision casting
316L
Ʋ Stainless steel housing, electropol-ished
316L
Ʋ Seal between housing and housing lid NBR(stainlesssteelhousing,precisioncasting),silicone(aluminium/plastichousing;stainlesssteelhousing,electropolished)
Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland NBR Ʋ Blind plug, cable gland PA
Processfittings Ʋ Pipethread,cylindrical(DIN3852-A) G½, G¾, G1, G1½ Ʋ American pipe thread, conical (ASMEB1.20.1)
½ NPT, ¾ NPT, 1 NPT, 1½ NPT
Ʋ Flanges DINfromDN25,ASMEfrom1"Weight
Ʋ Instrumentweight(dependingonprocessfitting)
0.8…4kg(0.18…8.82lbs)
Ʋ Rodweight:ø16mm(0.63in) 1100g/m(12oz/ft)Sensorlength(L)
Ʋ Processfitting:threadandflanges 0.1…6m(0.328…19.69ft) Ʋ Processfitting:Flanges-PTFEplated 0.15…6m(0.492…19.69ft)
Max. lateral load 10Nm(7.4lbfft)Torqueoftheflangescrews(min.) 60Nm(44.25lbfft)Max.torque(processfitting-thread) 100Nm(74lbfft)
30
9 Supplement
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
Torque for NPT cable glands and Conduit tubes Ʋ Plastic housing max.10Nm(7.376lbfft) Ʋ Aluminium/Stainless steel housing max.50Nm(36.88lbfft)
Measuring frequency 430kHz
Output variableOutput Contactless electronic switchModes(switchable) Min./Max.Switching delay
Ʋ When immersed 0.7 s Ʋ When laid bare 0.7 s Ʋ In the event of a fault 1 s
Accuracy (according to DIN EN 60770-1)Reference conditions according to DIN EN 61298-1
Ʋ Temperature +18…+30°C(+64…+86°F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860…1060mbar/86…106kPa(12.5…15.4psig)
Deviation due to strong, high-frequency electromagneticfieldsacc.toEN61326
< 3 % of the adjusted measuring range1)
Influenceoftheambienttemperature < 0.15 %/10 K of the adjusted measuring range2)
Ambient conditionsAmbient temperature on the housing -40…+80°C(-40…+176°F)Storage and transport temperature -40…+80°C(-40…+176°F)
Process conditionsProcess pressure
Ʋ Threaded versions -1…64bar/-100…6400kPa(-14.5…928psig),de-pendingontheprocessfitting
Ʋ Flange version -1…64bar/-100…6400kPa(-14.5…928psig),de-pendingontheprocessfitting
Ʋ Flangeversion≥3"/DN80,plated -0.4…64bar/-40…6400kPa(-5.8…928psig),de-pendingontheprocessfitting
Process temperature VEGACAP 63 of 316L Ʋ Insulation PE -40…+80°C(-40…+176°F) Ʋ Insulation PTFE -50…+150°C(-58…+302°F)
Processtemperature(threadorflangetemperature)withtemperatureadapter(optionwithPTFE)
-50…+200°C(-58…+392°F)
1) Distancefromtheprocessfittingstothesetswitchingpoint2) Distancefromtheprocessfittingstothesetswitchingpoint
31
9 Supplement
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
1
23
-50°C(-58°F)
50°C(122°F)
40°C(104°F)
-40°C(-40°F)
80°C(176°F)
0°C(32°F)
100°C(212°F)
150°C(302°F)
200°C(392°F)
Fig. 30: Ambient temperature - Process temperature1 Process temperature2 Ambient temperature3 Temperature range with temperature adapter
Dielectric constant ≥1.5
Electromechanical dataCableentry/plug(dependentontheversion)
Ʋ Single chamber housing – 1xcableentryM20x1.5(cable:ø5…9mm),1xblindplugM20x1.5;attached1xcableentryM20 x 1.5
or: – 1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable entry ½ NPT
or: – 1xplugM12x1;1xblindplugM20x1.5
Spring-loaded terminals forwirecross-sectionupto1.5mm²(AWG16)
Adjustment elementsMode switch
Ʋ Min. Min. detection or dry run protection Ʋ Max. Max.detectionoroverflowprotection
DIL switch for measuring range selection Ʋ range 1 0 … 20 pF Ʋ range 2 0 … 85 pF Ʋ range 3 0 … 450 pF
Potentiometer Switching point adaptation
Voltage supplyOperating voltage 20…253VAC,50/60Hz,20…253VDCDomestic current requirement approximately3mA(vialoadcircuit)Load current
Ʋ Min. 10 mA
32
9 Supplement
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
Ʋ Max. 400mA(atI>300mAtheambienttemperaturecanbemax.60°C/140°F)max.4Aupto40ms
Electrical protective measuresProtection rating IP66/IP67(NEMA4X)Overvoltage category IIIProtection class I
ApprovalsInstrumentswithapprovalscanhavedifferenttechnicalspecificationsdependingontheversion.For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com,"VEGA Tools"and"Instrument search"aswellasinthegeneraldownloadarea.
9.2 Dimensions
VEGACAP 63, housing
321 4
~ 69 mm(2.72")
ø 79 mm(3.11")
117
mm
(4.6
1")
M20x1,5/½ NPT
~ 59 mm(2.32")
ø 80 mm(3.15")
112
mm
(4.4
1")
M20x1,5/½ NPT
~ 69 mm(2.72")
ø 79 mm(3.03")
112
mm
(4.4
1")
M20x1,5/½ NPT
~ 116 mm (4.57")
ø 86 mm (3.39")
116
mm
(4.5
7")
M20x1,5M20x1,5/½ NPT
Fig. 31: Housing versions1 Plastic housing2 Stainless steel housing, electropolished3 Stainless steel housing, precision casting4 Aluminium housing
33
9 Supplement
VEGACAP 63 • - contactless electronic switch
3000
9-EN
-160
331
ø 16mm (0.63")
L
G¾, G 1, G 1½
56 m
m(2
.21"
)22
mm
(0.8
6")
Fig. 32: VEGACAP 63, threaded version G1 (ISO 228 T1)L = Sensor length, see chapter "Technical data"
108
mm
(4.2
5")
ø 40 mm (1.58")
Fig. 33: Temperature adapter
34
9 Supplement
VEGACAP 63 • - contactless electronic switch
30009-EN-160331
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com。
9.4 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.
Printing date:
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany
3000
9-E
N-1
6033
1
All statements concerning scope of delivery, application, practical use and operat-ing conditions of the sensors and processing systems correspond to the information available at the time of printing.Subject to change without prior notice
© VEGA Grieshaber KG, Schiltach/Germany 2016
Phone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected]