ÖLFLEX XLSv

download ÖLFLEX XLSv

of 1

Transcript of ÖLFLEX XLSv

  • 7/30/2019 LFLEX XLSv

    1/1148 For current inormation see www.lappgroup.com/products

    SKINTOP

    SILVYN

    FLEXIMARK

    ACCESSORIES

    LFLEX

    UN

    ITRONIC

    ETHERLINE

    HITRO

    NIC

    EPIC

    APPENDIX

    Power and control cablesSpecial applicationsPhotovoltaic

    LFLEX SOLAR XLSvRobust solar cable with big conductor cross sections

    For high electrical power loads Suitable or direct burial

    Info

    Benefts

    Reinorcedoutersheathprotectswellagainst

    mechanicalstress

    Highthermalcapacityorlonglastingopera-

    tionothePVsystematallseasons

    Reducedspreadingoresourceandorma-

    tionotoxiccombustiongasesineventore

    Consideringuniversallyvalidinstallation

    guidelinesalsosuitableordirectburial

    Exactquantitycontrolduringinstallationby

    metermarkingonthecablesheath

    Application range

    Forcablingoindividualmodulestringsaswellasorxedsolargeneratorsandmoved

    trackingsystems

    Openlandsolareldplants

    Bigconductorcross-sectionsareusedas

    collectingmaintotransmithighpowerloads

    betweentheindividualpanel-stringsandas

    connectiontotheDC/ACinverterohugePV

    plantsrespectivelysolarelds

    Product eatures

    Excellentweather-,abrasion-,temperature-

    andUVresistance

    Goodheatpressureresistance

    Halogen-reeandfame-retardant.

    Approvals (Norm reerences)

    Weather-/UVresistantaccordingHD605/A1

    FlameretardantaccordingtoIEC60332-1-2

    HalogenreeinaccordancewithIEC60754-1

    OzoneresistantaccordingEN50396

    Acid-/BrineresistantaccordingEN60811-2-1

    Design

    Conductor:Finewiredtinnedcopperstrands

    Coreinsulation:Electronbeamcross-linked

    copolymer

    Outersheath:Electronbeamcross-linked

    Copolymer

    Outersheathcolourblack

    Technical dataCore identifcation codeBlack

    Conductor strandingFinewireinaccordancetoVDE0295

    Class5/IEC60228Class5

    Minimum bending radiusFixedinstallation:4xcablediameter

    Rated voltageACU

    0/U:600/1000V

    DCU0/U:900/1500V

    Max.permissibleoperatingvoltage:

    DC1800V

    Test voltageAC6500V

    Range o temperatureFixedinstallation:

    -40Cupto+100C

    Part number Conductor cross section in mm Outer diameter in mm approx. Copper indexkg/km

    Weightkg/km approx.

    LFLEX SOLAR XLSv0027110 4.0 8.0 38.4 104.0

    0027111 6.0 9.1 57.6 141.0

    0027112 10.0 10.5 96.0 201.0

    0027113 16.0 11.9 153.6 280.0

    0027114 25.0 13.2 240.0 386.0

    0027115 35.0 14.5 336.0 502.0

    0027116 50.0 17.7 480.0 698.0

    0027117 70.0 19.7 672.0 921.0

    0027118 95.0 22.0 912.0 1,210.0

    0027119 120.0 23.8 1,152.0 1,475.0

    0027120 150.0 28.0 1,440.0 1,868.0

    0027121 185.0 31.0 1,776.0 2,299.0

    0027122 240.0 34.0 2,304.0 2,910.0

    Copperpricebasis:EUR150/100kg;ForutilizationanddenitionoMetalpricebasisandMetalindexseeAppendixT17

    Pleasendourstandardlengthsat:www.lappkabel.de/en/cable-standardlengths

    Packagingsize:Coil100m;Drum(500;1000)m

    Consideringeconomicminimumlenghtsweproduceonrequestversionswithredrespectivelybluecoreinsulationcolouroranimprintedcodestripeontheblackoutersheathasdistinctiveeature

    Accessories SKINTOPST/SKINTOPCLICK-ApprovedcableglandsoruseorPVjunctionboxes,electricmetersandDC/ACconverters