NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2...
Transcript of NYC Department of Education - NYCSCA · Roofing ROOFING Instance on Modified Bitumen: Roof 2...
Asset: P.S. 228 (ECC) - QUEENS, 32-63 93RD STREET, New York, 11369
Inspection Id Inspection Type Time In Last Edited
SA : Q228 Architectural - Senior 2019-12-02 10:48 AM 2019-12-09 3:19 PM
AA : Q228 Architectural - Associate 2019-12-02 11:23 AM 2019-12-02 5:46 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Olga Guzman
Organization P.S. 228 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. Some thermostats are notworking. 2. The toilet in Principal's Toilet Room is leaking. 3. Thereare roof leaks in Room 312. 4. There is water infiltration through thewindows at Rooms 201 and 203.
Custodian Was not present
Fireman Salvatore Taibi
Building Square Footage 45,000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B+PH
Comments on the Number of Classrooms 16
Comments on the Year Built 2001
Student Population 290
Staff Population 80
Weather Fair
Facade Photo
Corner of 93rd Street and NorthernBoulevard - Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 1 of 27
Main Entrance Photo
Facade A - 93rd Street
Roof Photo
Roof 1 - North View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited Structural repairs
Year: 2018
Systems: Limited Roofing repairs; limited Window recaulking;limited waterproofing at Coping
Year: 2017
Systems: Limited Coping, Parapet, Roofing repairs
Year: 2012
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 2 of 27
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
DeterioratedSteel
Deterioratedmetal decking
INTERIOR |STRUCTURAL| FLOORSTRUCTURE
Basement -Boiler Roomabove BoosterPumps
Salvatore Taibi Fireman
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria 1st Floor Yes Yes Yes Yes
Classrooms 1st - 3rd Floor Yes Yes
Computer Rooms No
Gymnasium No
Library Room 215 Yes Yes
Main Office Room 121 Yes Yes
Multi-purpose Room 3rd Floor Yes Yes Yes Yes
Nurse's Room Room 217 Yes Yes
Pool No
Science Lab No
Toilet Rooms (Boys) 1st - 3rd Floor Yes Yes
Toilet Rooms (Girls) 1st - 3rd Floor Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 3 of 27
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Toilet Rooms (Staff) Basement - 2nd Floor Yes Yes
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1 - AW2
Instance Condition 2 - Between Good and Fair
Instance Quantity 2
Instance Quantity Uom EACH
Deficiency No deficiencies recorded
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Metal
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency CAST STONE: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 4 of 27
Question Response
EXTERIOR
COPING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Exit 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 5 of 27
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES Inspected
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Steel
Replacement Quantity 22,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 22,000
Instance Quantity Uom S.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 6 of 27
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade C
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 2,500
Replacement Uom C.F.
InspectedInstance on Roof 1
Instance Condition 4 - Between Fair and Poor
Instance Quantity 2,500
Instance Quantity Uom C.F.
Deficiency BRICK: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 7 of 27
Question Response
EXTERIOR
PARAPETS
Deficiency Photo1
Roof 1 - Facade A
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Facade C
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 11,500
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Does not Exist
ROOF BARRIER Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 8 of 27
Question Response
EXTERIOR
ROOF
Roofing
ROOF BARRIER
Condition 3 - Fair
Deficiency RAILINGS/PANELS: DETERIORATED, MINOR RUSTING
Roof Plan reference
Deficiency Quantity 280
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: Roof 1
Instance Condition 4 - Between Fair and Poor
Instance Quantity 7,500
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2001
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 9 of 27
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Room 312
Violations No violations recorded.
InspectedInstance on Modified Bitumen: Roof 2
Instance Condition 5 - Poor
Instance Quantity 4,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2001
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION
Roof Plan reference
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Center of Roof 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 10 of 27
Question Response
EXTERIOR
ROOF
Roofing
ROOFING Inspected
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 5 - Poor
Deficiency DETERIORATED
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
WINDOWS Inspected
Replacement Quantity 2,500
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 11 of 27
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Deficiency RUST - MINOR
Roof Plan reference
Elevation
Deficiency Quantity 900
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: Facades A, C, D
Instance Condition 3 - Fair
Instance Quantity 2,500
Instance Quantity Uom S.F.
Installation Year 2001
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: AIR AND WATERINFILTRATION, OPEN JOINTS WITH DAMAGED CAULKING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 12 of 27
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 4
Deficiency Photo1
Facade A - Room 203 shown, Facade A - Room 201 similar
Violations 35402546L
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: THRU CRACKS
Deficiency Location/Instance Basement - Mechanical Room B15
Deficiency Quantity 30
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 13 of 27
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Mechanical Room B15
Violations No violations recorded.
Deficiency METAL DECK AND CONCRETE: DETERIORATED
Deficiency Location/Instance Basement - Boiler Room above Booster Pumps
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Basement -Boiler Room above Booster Pumps
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Boiler Room, Corridor near Rooms B02, B23
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 14 of 27
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE Inspected
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near Center columns
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Center columns
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 15 of 27
Question Response
INTERIOR
CAFETERIA
Fixed Equipment
Does not ExistInstance on 1st Floor
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Room 101B
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Rear 101B
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Room 312
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 16 of 27
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 312
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Corridor near 1st Floor Staff Toilets, Corridor near Room 204
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near 1st Floor Staff Toilets
Violations No violations recorded.
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Main Entrance Lobby
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Lobby
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 17 of 27
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Main Entrance Vestibule, Corridor near Room 118, Room 212
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Vestibule
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 209
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 209
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 18 of 27
Question Response
INTERIOR
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Rooms 107A,108
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 108
Violations No violations recorded.
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 108
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 108
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 19 of 27
Question Response
INTERIOR
KITCHEN
Floor Finish
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 215
Built-in Furnishing
Does not ExistInstance on Room 215
Ceiling
InspectedInstance on Room 215
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 215
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 215
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 215
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near Stage
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 20 of 27
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Ceiling
Deficiency Photo1
Near Stage
Violations No violations recorded.
Door(s)
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on 3rd Floor
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
InspectedInstance on 3rd Floor
Stage Does not Exist
Does not ExistInstance on 3rd Floor
Stage Curtain Rigging Inspected
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 21 of 27
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Stair B/3
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/3
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STUDENTS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 22 of 27
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance Northern Boulevard
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Northern Boulevard
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 23 of 27
Question Response
SITE
FENCES
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Northeast Playground
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Northeast Playground
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Main Entrance
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 24 of 27
Question Response
SITE
PAVING
DOT Sidewalk
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance Northern Boulevard
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Northern Boulevard
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 93rd Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
93rd Street
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on East side
InspectedInstance on Northeast side
Benches
InspectedInstance on East side
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 25 of 27
Question Response
SITE
PLAYGROUNDS
Benches
InspectedInstance on Northeast side
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fence
InspectedInstance on East side
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Does not ExistInstance on Northeast side
Pavement
InspectedInstance on East side
Condition 3 - Fair
Deficiency CONCRETE: CRACKS - MAJOR
Deficiency Location/Instance Near entrance
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near entrance
Violations No violations recorded.
Play Equipment
InspectedInstance on East side
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Does not ExistInstance on Northeast side
Safety Surfacing
InspectedInstance on East side
Condition 3 - Fair
Deficiency DETERIORATED/MISSING
Deficiency Location/Instance North side
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 26 of 27
Question Response
SITE
PLAYGROUNDS
Safety Surfacing
Deficiency Photo1
North side
Violations No violations recorded.
Unpaved Area
InspectedInstance on East side
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Does not ExistInstance on Northeast side
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance East side Playground
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East side Playground
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q228
PB/A&W Print Date: 9/14/2020Page 27 of 27