Transcript of NXL Configurator Specification v0 997
PartnerWeb Project
NXL Configurator
Specification
March 2, 2012
Specification for Liebert NXLDate: 3/02/2012
Table of Contents
Introduction:.................................................................................................................................................10
Liebert NXL: “LiebertNXL250–1100kVA60Hz”.......................................................................................10
Revision History:.........................................................................................................................................10
Tab Names:..................................................................................................................................................11
Tab: “UPS Module”, Sub-Tab: “Main Unit”...............................................................................................14
Title:System Configuration Type............................................................................................................14
Title: Main Unit Quantity........................................................................................................................14
Title: Nominal Rating (kVA/kW)............................................................................................................14
Title: UPS Voltage 1................................................................................................................................16
Title: UPS Voltage 2................................................................................................................................16
Title: Rectifier and Filter Configuration..................................................................................................17
Title: Withstand Rating___......................................................................................................................17
Title: Circuit Breakers Included...............................................................................................................18
Title: Customer Interface Boards.............................................................................................................20
Title: HMI Options..................................................................................................................................21
Title: System Interfaces...........................................................................................................................21
Title: Monitoring Cards...........................................................................................................................22
Title: Energy Optimization Mode............................................................................................................23
Title: RASP Power Supply......................................................................................................................23
Title: Motor Operator...............................................................................................................................24
Title: Single Input Jumper.......................................................................................................................24
Tab: “UPS Module”, Sub-Tab: “Site Installed Options”.............................................................................25
Title: Web Intellislot Card.......................................................................................................................25
Title: MODBUS 485 Intellislot Card.......................................................................................................25
Title: MODBUS IP Intellislot Card.........................................................................................................25
Title: Remote Alarm Status Panel Quantity.............................................................................................26
Title: Remote Alarm Status Panel Type..................................................................................................26
Title: Module Floor Anchors...................................................................................................................27
Title: OSHPOD__....................................................................................................................................27
Title: Single Input Wiring Cabinet..........................................................................................................28
Tab: “UPS Module”, Sub-Tab: “Matching MBC”......................................................................................28
Title: MBC...............................................................................................................................................28
Page 2 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Checkbox........................................................................................................................................28
Title: Matching MBP Field Installed Options (Qty per Maintenance Bypass Cabinet)..........................29
Title: Matching MBP Floor Anchors.......................................................................................................29
Tab: “UPS Module”, Sub-Tab: “Buyout MBP (Panelboard)”.....................................................................30
Title: Select Rating..................................................................................................................................30
Title: Select Quantity...............................................................................................................................30
Title: Number of Devices.........................................................................................................................31
Title: Breaker Trip Rating........................................................................................................................32
Title: LDB Code......................................................................................................................................33
Title: Panelboard Rating ___ kA.............................................................................................................34
Title: Breaker Type..................................................................................................................................35
Title: Options...........................................................................................................................................36
Title: Custom Panelboard........................................................................................................................37
Title: Custom Panelboard Details............................................................................................................37
Tab: “UPS Module”, Sub-Tab: “Buyout MBS (Switchboard)”..................................................................37
Title: Select Rating..................................................................................................................................37
Title: Select Quantity...............................................................................................................................38
Title: Select Rating..................................................................................................................................39
Title: Number of Devices.........................................................................................................................39
Title: Breaker Trip Rating........................................................................................................................40
Title: Switchboard Rating ___ kA...........................................................................................................42
Title: Breaker Type..................................................................................................................................42
Title: Options...........................................................................................................................................43
Title: Custom Switchboard......................................................................................................................44
Title: Custom Switchboard Details..........................................................................................................44
Tab: “UPS Module”, Sub-Tab: “Buyout SP”..............................................................................................44
Title: Buyout SP (Switchgear).................................................................................................................44
Title: Number of modules in fully configured system____.....................................................................44
Title: Select Rating____..........................................................................................................................45
Title: Redundant System____..................................................................................................................45
Title: Configuration.................................................................................................................................46
Title: Bypass Voltage and Withstand Rating...........................................................................................46
Title: System Breaker Rating...................................................................................................................47
Page 3 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: MOB Rating...................................................................................................................................49
Title: BIB Rating......................................................................................................................................66
Title: RIB Rating......................................................................................................................................67
Title: Options...........................................................................................................................................67
Title: Manufacturer..................................................................................................................................67
Title: Custom SPG Switchgear................................................................................................................68
Title: Custom System Paralleling Switchgear.........................................................................................69
Title: Custom System Paralleling Switchgear details............................................................................69
Title: Custom Switchgear........................................................................................................................69
Title: Custom Switchgear Details............................................................................................................70
Tab: “UPS Module”, Sub-Tab: “Module Spare Parts”................................................................................70
Title: Module Spare Parts Level..............................................................................................................70
Title: Module Spare Parts........................................................................................................................70
Title: System Configuration Type...........................................................................................................71
Title: Nominal Rating (KVA)..................................................................................................................71
Title: UPS Voltage...................................................................................................................................72
Tab: “SCC”, Sub-Tab: “Main Unit”............................................................................................................72
Title: Number of Modules in Fully Configured System..........................................................................72
Title: Redundant System____..................................................................................................................73
Title: SCC Rating.....................................................................................................................................74
Title: System Breaker Configuration.......................................................................................................78
Title: MBP Configuration........................................................................................................................78
Title: Other System Breakers...................................................................................................................79
Title: Customer Interface Boards.............................................................................................................79
Title: HMI Options..................................................................................................................................80
Title: System Interfaces...........................................................................................................................81
Title: Monitoring Cards...........................................................................................................................81
Title: Energy Optimization Mode............................................................................................................82
Title: Optional Power Supply..................................................................................................................83
Title: RASP Power Supply......................................................................................................................83
Title: Harnesses........................................................................................................................................83
Tab: “SCC”, Sub-Tab: “Site Installed Options”..........................................................................................84
Title: Site Installed Options.....................................................................................................................84
Page 4 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Mounting__________....................................................................................................................84
Title: Floor Crane Quantity......................................................................................................................84
Tab: “SCC”, Sub-Tab: “Buyout SCC (Switchgear)”...................................................................................85
Title: SCC Sections..................................................................................................................................85
Title: SCC Drawout Breakers..................................................................................................................85
Title: Switchgear Manufacturer---...........................................................................................................85
Title: Custom Bypass Switchgear............................................................................................................86
Title: Custom Switchgear........................................................................................................................86
Title: Custom Switchgear Details............................................................................................................86
Tab: “SCC”, Sub-Tab: “SCC Spare Parts”..................................................................................................86
Title: SCC Spare Parts Quantity..............................................................................................................86
Title: SCC Spare Parts Level...................................................................................................................87
Tab: “PTC”, Sub-Tab: “Main Unit”............................................................................................................88
Title: Power Tie Basic Unit (First Unit)..................................................................................................88
Title:System Type....................................................................................................................................88
Title:Breaker Package..............................................................................................................................89
Title:Electrical Interlock..........................................................................................................................89
Title:PT Controls Mounting.....................................................................................................................91
Title: Customer Interface Boards.............................................................................................................92
Title: Monitoring Cards...........................................................................................................................92
Tab: “Batt Cab”, Sub-Tab: “Main Unit”......................................................................................................94
Title: Matching Battery Cabinet Basic Unit............................................................................................94
Title: Matching Battery Cabinet Basic Unit for X kW............................................................................95
Title: Cabinet Type..................................................................................................................................98
Title: UPS Module Rating.......................................................................................................................99
Title: Battery Model...............................................................................................................................100
Title: Cabinet Quantity..........................................................................................................................100
Title: Breaker Type................................................................................................................................100
Title: Connection...................................................................................................................................101
Tab: “Batt Cab”, Sub-Tab: “Site Installed Options”.................................................................................102
Title: Battery Cabinet Field Installed Options (QTY per Battery Systemt)..........................................102
Title: Battery Junction Cabinet..............................................................................................................102
Title: Mount...........................................................................................................................................103
Page 5 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Rear Cabinet Alignment Kit.........................................................................................................104
Tab: “Buy Batt”.........................................................................................................................................105
Title: Buyout Battery.............................................................................................................................105
Title: Battery Description......................................................................................................................105
Title: Battery System.............................................................................................................................106
Title: Battery System in Cabinets..........................................................................................................106
Title: Battery System Racks...................................................................................................................107
Title: Battery Rack Accessories.............................................................................................................107
Title: Stackable Battery System.............................................................................................................107
Title: Spill Containment Accessories.....................................................................................................108
Title: BIS Basic Unit..............................................................................................................................108
Title: Pick BIS Rating?..........................................................................................................................108
Title: BIS Rating....................................................................................................................................109
Title: Breaker Type................................................................................................................................111
Title: Enclosure......................................................................................................................................111
Title: MBD Basic Unit...........................................................................................................................112
Title: Pick MBD Rating.........................................................................................................................112
Title: MBD Rating.................................................................................................................................113
Title: Breaker Type................................................................................................................................115
Title: Operator........................................................................................................................................116
Title: Enclosure......................................................................................................................................116
Title: MBD and BIS Accessories...........................................................................................................117
Title: BIB Usage....................................................................................................................................117
Title: Temperature Sensor Usage...........................................................................................................117
Title: Battery Breaker Interface for MBD.............................................................................................118
Title: Quantity per UPS Module............................................................................................................118
Title: Battery Breaker Interface for BIS................................................................................................118
Title: Quantity per UPS Module............................................................................................................118
Title: Temperature Sensor......................................................................................................................119
Title: Quantity per UPS Module............................................................................................................119
Title: Stand Alone Junction Cabinet......................................................................................................121
Title: Battery Junction Cabinet Quantity per UPS Module...................................................................121
Title: Junction Cabinet Floor Anchors...................................................................................................121
Page 6 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Flywheel System (per Module)....................................................................................................122
Title: Flywheel Description...................................................................................................................122
Title: Flywheel Unit...............................................................................................................................122
Title: Agency Certification....................................................................................................................122
Title: Product Model..............................................................................................................................123
Title: Auxiliary Input Voltage for Controls...........................................................................................123
Title: Flywheel Factory Installed Options (one per PTC).....................................................................124
Title: Display Type................................................................................................................................124
Title: Exterior Panel Color.....................................................................................................................124
Title: Air Filter.......................................................................................................................................125
Title: Option Code.................................................................................................................................125
Title: Trip Type......................................................................................................................................126
Title: Flywheel Site Installed Options (Quantity per Flywheel Unit)....................................................127
Title: Flywheel Floor Stand...................................................................................................................127
Title: Flywheel Floor Stand Height.......................................................................................................127
Title: Flywheel Breaker Interface..........................................................................................................127
Tab: “Factory Testing”..............................................................................................................................128
Title: 1 + N Factory System Testing......................................................................................................128
Title: 1 + N Switchgear FWT Setup......................................................................................................128
Title: 1 + N Switchgear FWT Setup Shipping Splits.............................................................................129
Title: 1 + N Switchgear Drawout Breakers Shipped Separately...........................................................130
Title: N + 1 Factory System Testing......................................................................................................131
Title: N + 1 Switchgear FWT Setup......................................................................................................131
Title: 1 + N Switchgear FWT Setup Shipping Splits.............................................................................132
Title: 1 + N Switchgear Drawout Breakers Shipped Separately...........................................................133
Title: Factory Witness Testing...............................................................................................................134
Title: Level.............................................................................................................................................134
Title: Factory Burn-in............................................................................................................................136
Title: Burn-in Type................................................................................................................................136
Title: Hours............................................................................................................................................136
Title: Special Factory Setup...................................................................................................................141
Title: Special Factory Set-up.................................................................................................................141
Title: Special Factory Testing................................................................................................................141
Page 7 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “Services”..........................................................................................................................................142
Title: Site Startup Services.....................................................................................................................142
Title: Startup Services Type...................................................................................................................142
Title: UPS Module Startup.....................................................................................................................142
Title: BDSi Controller Startup...............................................................................................................143
Title: BDSi Load Module Startup..........................................................................................................144
Title: Module Site Acceptance...............................................................................................................144
Title: Matching MBP Startup.................................................................................................................145
Title: System Control Cabinet Setup.....................................................................................................145
Title: SCC Site Acceptance Package.....................................................................................................146
Title: Power Tie Control Cabinet Startup..............................................................................................146
Title: Power Tie Site Acceptance Package............................................................................................146
Title: Special Site Testing......................................................................................................................147
Title: Battery Installation Verification Service at Startup.....................................................................147
Title: Flywheel Startup..........................................................................................................................151
Title: Maintenance Services Type.........................................................................................................151
Title: UPS Module Maintenance Plan Annual PMs..............................................................................152
Title: Matching MBP Maintenance Plan...............................................................................................153
Title: SCC Maintenance Plan.................................................................................................................155
Title: PTC Maintenance Plan.................................................................................................................156
Title: BDSi Controller Maintenance Plan..............................................................................................157
Title: Maintenance Services Type.........................................................................................................157
Title: BDSi Load Module Maintenance Plan.........................................................................................157
Title: Battery PM Maintenance Plan......................................................................................................158
Title: Battery Maintenance Plan............................................................................................................158
Title: Battery Maintenance Services Type PM Visits............................................................................158
Title: Flywheel Maintenance Services...................................................................................................159
Title: Special Site Testing......................................................................................................................160
Title: Special Maintenance Services......................................................................................................160
Title: Special Maintenance Services......................................................................................................160
Tab: “SFA”................................................................................................................................................161
Title: SFA...............................................................................................................................................161
Tab: “Other Options”.................................................................................................................................161
Page 8 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title:.......................................................................................................................................................161
Tab: “Summary”........................................................................................................................................161
Title: Summary......................................................................................................................................161
Tab: “Internal”...........................................................................................................................................161
Title: UPS Module Configuration Digit Override.................................................................................161
Title: MBC Configuration Digit Override.............................................................................................161
Title: BC1 Configuration Digit Override...............................................................................................162
Title: BC2 Module Configuration Digit Override.................................................................................162
Title: BC3 Module Configuration Digit Override.................................................................................162
Title: BC4 Module Configuration Digit Override.................................................................................162
Title: BC5 Module Configuration Digit Override.................................................................................162
Title: BC6 Module Configuration Digit Override.................................................................................163
Title: Auto Config..................................................................................................................................163
Appendix:...................................................................................................................................................164
Right Hand Summary (RHS): Standard:................................................................................................164
SKU Base:..........................................................................................................................................164
Configured Base:...............................................................................................................................164
Proposal Section:...................................................................................................................................164
Line Item Detail (LID) Section:.............................................................................................................164
Submittal Section:..................................................................................................................................164
Part/Price Information Table:................................................................................................................164
SFA Keys:..............................................................................................................................................165
Document Section: Document ID’s:......................................................................................................165
Other Suggested Items:..........................................................................................................................165
Part Number Logic:............................................................................................................................165
Part Number Lookup:........................................................................................................................165
Filtering:.............................................................................................................................................165
Issues..........................................................................................................................................................166
Page 9 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Introduction:This template is an initial design and is meant to be a working document. If necessary, additional items can be added or modified as necessary for a particular configurator if it is relevant in assisting in the development and testing of the developed product.
Liebert NXL is a power configured product. It integrates with the Interface Cards (IntelliSlot) configurator (engine to engine), Auto config, Buyout Batteries, Freight, SFA and possibly the proposed Panelboard and proposed Switchboard. This is NOT a reseller or Quote to Var configurator.
Liebert NXL: “LiebertNXL250–1100kVA60Hz”
This is the identifier of the form in the PartnerWeb domain. This cannot be the same name as the active form and cannot contain spaces. Form Name can be the marketing name for the form. Also identify if this is 60hz, 50hz, or both.
Revision History:Date: Version Name: Revision11/04/2011 0.1 Roger Engle Initial Draft 11/07/2011 0.2 Roger Engle Add builds from 11/07 meeting with
Steve11/09/2011 0.3 Roger Engle Add builds from 11/09 meeting with
Rick et al.11/11/2011 0.4 Roger Engle Back up for work off site11/15/2011 0.5 Roger Engle Add builds from 11/15 meeting with
Rick et al.11/22/2011 0.6 Roger Engle Checks from MS Excel spreadsheet
review11/29/2011 0.7 Roger Engle Add builds from first tech review12/01/2011 0.8 Roger Engle Add builds from 11/30 meeting with
Rick et al.12/02/2011 0.9 Roger Engle Add builds from 12/1 meeting with
Rick.12/06/2011 0.91 Roger Engle Add builds from 12/5 meeting with
Rick.12/06/2011 0.92 Roger Engle Add builds from 12/8 meeting with
Rick.12/12/2011 0.93 Roger Engle Check against Rick’s current MS Excel
document12/16/2011 0.94 Roger Engle Add builds from 12/15 tech review with
Chad12/20/2011 0.95 Roger Engle Add builds from 12/15 tech review with
Chad12/21/2011 0.96 Roger Engle Add builds from 12/15 tech review with
Chad
Page 10 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
12/22/2011 0.97 Roger Engle Replace MBC section12/22/2011 0.98 Roger Engle Add Services12/29/2011 0.99 Roger Engle Shorten Services1/09/2012 0.991 Roger Engle Add builds from 1/06/2012 meeting1/09/2012 0.992 Roger Engle Add builds from third technical review1/19/2012 0.993 Roger Engle Add builds from 1/19/2012 meeting1/26/2012 0.994 Roger Engle Add builds from 1/25/2012 meeting1/30/2012 0.995 Roger Engle Add builds from 1/27/2012 changes2/23/2012 0.996 Roger Engle Add builds from 2/23/2012 changes2/27/2012 0.997 Roger Engle Add builds from 2/27/2012 changes
SAFM Number: SAFM-8540-PW36E
This is the form identification (quality number) assigned.
Tab Names:
The purpose of establishing this list is as a starting point in building out the base XML look of the configurator.
1) Main-Tab: “UPS Module”2) Main-Tab: “UPS Module”, Sub-Tab: “ Main Unit”3) Main-Tab: “UPS Module”, Sub-Tab: “Site Installed Options”4) Main-Tab: “UPS Module”, Sub-Tab: “Matching MBC”5) Main-Tab: “UPS Module”, Sub-Tab: “Buyout MBP”6) Main-Tab: “UPS Module”, Sub-Tab: “Buyout MBS”7) Main-Tab: “UPS Module”, Sub-Tab: “Buyout SPG”8) Main-Tab: “UPS Module”, Sub-Tab: “Module Spare Parts”9) Main-Tab: “SCC”10) Main-Tab: “SCC”, Sub-Tab: “ Main Unit”11) Main-Tab: “SCC”, Sub-Tab: “Site Installed Options” 12) Main-Tab: “SCC”, Sub-Tab: “Buyout SCC (Switchgear Parts)” 13) Main-Tab: “SCC”, Sub-Tab: “SCC SpareParts”14) Main-Tab: “PTC”15) Main-Tab: “PTC”, Sub-Tab: “ Main Unit” 16) Main-Tab: “Batt Cab”17) Main-Tab: “Batt Cab”, Sub-Tab: “ Main Unit” 18) Main-Tab: “Batt Cab”, Sub-Tab: “Site Installed Options”19) Main-Tab: “Buy Batt”20) Main-Tab: “Factory Testing”21) Main Tab: “Services”22) Main-Tab: “SFA”23) Main-Tab: “Other Options”24) Main-Tab: “Summary”25) Main-Tab: “Internal”
Page 11 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
26) Main-Tab: “Internal”, Sub-Tab: “UPS Module”27) Main-Tab: “Internal”, Sub-Tab: “MBC”28) Main-Tab: “Internal”, Sub-Tab: “BC1…6”29) Main-Tab: “Internal”, Sub-Tab: “Auto Config”
The following is a file showing the tabs graphically.
Abbreviations used on the tabs to conserve space include:
1. “Batt Cab” for “Battery Cabinet”2. “Buy Batt” for “Buyout Battery”3. “SCC” for “Switching Control Cabinet”4. “SCG” for “Switching Control Gear”5. “PTC” for “Power Tie Cabinet”6. “SFA” for “Special Feature Authorization”7. “SPG” for “System Paralleling Gear”8. “MBP” for “Maintenance Bypass Panel”9. “UPS” for “Uninteruptible Power Supply”10. “MBS” for “Maintenance Bypass Switchboard”11. “MBC” for “Maintenance Bypass Cabinet”12. “MBD” for “Maintenance Battery Disconnect”
The following instructions are used throughout the screen layouts below:
1. Quantity – text integer input2. On – radio button 3. Check box – multiple choices allowed4. List – drop down
The following terms occur throughout the document.
Model Type Identifier is a part number.
Page 12 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
This document has been reviewed and is approved.
Signatures
__________________________ Rick Caudill, Product Manager
__________________________Chad Pitchford, Technical Lead
__________________________ Tony Trubiani, Project Coordinator
__________________________ Jenna Stranges, Test Lead
__________________________ Roger Engle, Business Analyst
Page 13 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “UPS Module”, Sub-Tab: “Main Unit”Screen Layout:
Title:System Configuration Typeo On | SMSo On | 1+1o On | 1 + No On | N + 1
Business Rules:
1. There is no default.2. A selection is required.
Part Number Definition:
1. Digits 3 and 4 may be SA, SR, SN, MM in the model type identifier.
Filtering Table:
Selection Model type identifier digit 3 and 4“SMS” “SA”“1+1” “SR”“1+N” “SN”“N+1” “MM”
Title: Main Unit Quantityo Quantity | Main Unit Quantity
Business Rules:
1. The default is “1”2. Any quantity up to “6” may be input in whole numbers.
Model type identifier digit 4
Selection available
* “1”, “2”“A”, “N”, “M” “3”, “4”, “5”“A”, “M” “6”
Part Number Definition:
1. Digits 1 and 2 are always 40 in the model type identifier.
Title: Nominal Rating (kVA/kW)
Page 14 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 250 kVA/225 kWo On | 250 kVA/225kWo On | 300 kVA/270 kWo On | 300 kVA/270 kWo On | 400 kVA/360 kWo On | 400 kVA/360 kWo On | 500 kVA/450 kWo On | 500 kVA/500 kWo On | 625 kVA/562.5 kWo On | 625 kVA/625 kWo On | 750 kVA/675 kWo On | 750 kVA/750 kWo On | 1100 kVA/1100 kWo On | 1125 kVA/1125 kW
Business Rules:
1. There is no default.2. A selection is required.3. Expectations are that more selections will be available in the future. The expected values are
shown in the third column (Selections not currently available for digits 5, 6, 7) in the Filtering Table below.
Part Number Definition:
1. Digits 5, 6 and 7 may be 250, 25A, 300, 30A, 400, 40A, 500, 50M, 626, 62M, 750, 75M, 11M, 12M in the model type identifier.
Filtering Table:
Module Digit 3 Available Selection for digits 5, 6 and 7
Selections not currently available for digits 5, 6, 7
“S” 250, 300, 400, 500, 626, 62M, 750, 11M, 12M
25A, 30A, 40A, 50M, 75M
“S”, “M” 500, 626, 62M, 750, 11M, 12M 50M, 75M
Filtering Table:
Selection Model type identifier digit 5, 6 and 7
“250 kVA /225kW” “250”
“250 kVA /225 kW ” “25A”
“300 kVA /270 kW” “300”
“300 kVA /270 kW” “30A”
Page 15 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“400 kVA /360 kW” “400”
“400 kVA /360 kW” “40A”
“500 kVA /450 kW” “500”
“500 kVA /500 kW” “50M”
“625 kVA /562.5 kW” “626”
“625 kVA /625 kW” “62M”
“750 kVA /675 kW” “750”
“750 kVA /750 kW” “75M”
“1100 kVA /1100kW” “11M”
“1125 kVA /1125kW” “12M”
Title: UPS Voltage 1o On | 480 Vo On | 575 Vo On | 600 V
Business Rules:
1. There is no default.2. A selection is required.
Filtering Table:
Digit 5, 6 and 7 Available Selection Available Selection for digit 8
250, 300, 400, 500, 626, 62M, 750, 75M, 11M, 12M “480V” “A”25A, 30A, 40A, 50M, 62M, 750, 75M, 11M, 12M “575V” , “600V” “3” , “B”
Part Number Definition:
1. Digit 8 may be A, 3, or B in the model type identifier.
Page 16 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Filtering Table:
Selection Model type identifier digit 8
“480 V” “A”“575 V ” “3”“600 V” “B”
Title: UPS Voltage 2Business Rules:
1. All values are automatic. Value can’t be determined until after digit 20 is completed.2. No selection is possible.3. Digits 9 and 10 may be 0A, AA, 03, 33, 0B, BB in the model type identifier.
Filtering Table:
Digit 3 and 4 Digit 8 Digit 20 Selection for digit 9 and 10
“MM” “A” “1” “0A”“SA”, “SR”, “SN” “A” “N” “AA”“MM” “3” “1” “03”“SA”, “SR”, “SN” “3” “N” “33”“MM” “B” “1” “0B”“SA”, “SR”, “SN” “B” “N” “BB”
Title: Rectifier and Filter ConfigurationBusiness Rules:
1. All values are automatic.2. No selection is possible.3. Digit 11 may be A or I in the model type identifier.
Filtering Table:
Digit 5 Selection for digit 11
2, 3 ,4 “A”
5, 6, 7, 1 “I”
Title: Withstand Rating___
Page 17 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 35 kAo On | 65 kAo On | 100 kAo On | 125 kAo On | 150 kA
Business Rules:
1. There is no default.2. A selection is required.
Part Number Definition:
1. Digit 12 in the model type identifier is determined by the table below using this and prior input.
Filtering Table:
Digit 4 Digit 5 Digit 8 Available selection WR____kA
* 2, 3, 4, 5, 6, 7 “3” or “”B” 35* 2, 3, 4, 5, 6, 7 * 65
* 2, 3, 4, 5, 6, 7 “A” 100
* 1 * 100
* 1 “A” 125“M” * * 150
Title: Circuit Breakers Includedo On | Available Selection
Business Rules:
1. There is no default.2. A selection is required.
Part Number Definition:
1. Available Selection and Digit 12 in the model type identifier is determined by the table below using this and prior input.
Filtering Table:
Digit 3 and 4 Digit 5 Digit 8 WR---kA Available for selection Selection for Digit 12
* 2, 3, 4, 5, 6, 7 “A” “65” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“A”
Page 18 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
* 2, 3, 4, 5, 6, 7 “3” or “B” “35” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“A”
* 1 “A” “100” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“A”
* 1 “3” or “B” “65” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“A”
* 2, 3, 4, 5, 6, 7 “A” “100” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“B”
* 2, 3, 4, 5, 6, 7 “3” or “B” “65” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“B”
* 1 “A” “125” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“B”
* 1 “3” or “B” “100” CB1, CB2, BFB (SA, SN, SR) / CB1, CB2 (MM)
“B”
“SA”, “SR”, “SN” 5, 6, 7 “A” “65” RIB, CB2, BFB (SA, SN, SR) “C”“SA”, “SR”, “SN” 5, 6, 7 “3” or “B” “35” RIB, CB2, BFB (SA, SN, SR) “C”“SA”, “SR”, “SN” 1 “A” “100” RIB, CB2, BFB (SA, SN, SR) “C”“SA”, “SR”, “SN” 1 “3” or “B” “65” RIB, CB2, BFB (SA, SN, SR) “C”“SA”, “SR”, “SN” 5, 6, 7 “A” “100” RIB, CB2, BFB (SA, SN, SR) “D”“SA”, “SR”, “SN” 5, 6, 7 “3” or “B” “65” RIB, CB2, BFB (SA, SN, SR) “D”“SA”, “SR”, “SN” 1 “A” “125” RIB, CB2, BFB (SA, SN, SR) “D”“SA”, “SR”, “SN” 1 “3” or “B” “100” RIB, CB2, BFB (SA, SN, SR) “D” “SA” 2, 3, 4, 5, 6, 7 “A” “65” CB1, CB2, BFB with Attached
MBP (SA)“E”
“SA” 2, 3, 4, 5, 6, 7 “3” or “B” “35” CB1, CB2, BFB with Attached MBP (SA)
“E”
“SA” 2, 3, 4, 5, 6, 7 “A” “100” CB1, CB2, BFB with Attached MBP (SA)
“F”
“SA” 2, 3, 4, 5, 6, 7 “3” or “B” “65” CB1, CB2, BFB with Attached MBP (SA)
“F”
“MM” All All “150” RIB, CB2 (MM) “G”
“MM” 5, 6, 7 “A” “65” CB1, IOB (MM) “H”
“MM” 5, 6, 7 “3” or “B” “35” CB1, IOB (MM) “H”
“MM” 1 “A” “100” CB1, IOB (MM) “H”
“MM” 1 “3” or “B” “65” CB1, IOB (MM) “H”
Page 19 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“MM” 5, 6, 7 “A” “100” CB1, IOB (MM) “J”
“MM” 5, 6, 7 “3” or “B” “65” CB1, IOB (MM) “J”
“MM” 1 “A” “125” CB1, IOB (MM) “J”
“MM” 1 “3” or “B” “100” CB1, IOB (MM) “J”
“MM” All All “150” RIB, IOB (MM) “K”
“SA” 2, 3, 4, 5, 6, 7 “A” “65” RIB, CB2, BFB with Attached MBP (SA)
“M”
“SA” 2, 3, 4, 5, 6, 7 “3” or “B” “35” RIB, CB2, BFB with Attached MBP (SA)
“M”
“SA” 2, 3, 4, 5, 6, 7 “A” “100” RIB, CB2, BFB with Attached MBP (SA)
“N”
“SA” 2, 3, 4, 5, 6, 7 “3” or “B” “65” RIB, CB2, BFB with Attached MBP (SA)
“N”
Title: Customer Interface Boardso On | Programmable Relay Board (Qty 1) (“A”)o On | Input Contact Isolator Board (Qty 1) (“B”)o On | 1 "A" and 1 "B"o On | 2 "A"o On | 2 "B"o On | 2 "A" and 1 "B"o On | 1 "A" and 2 "B"o On | 2 "A" and 2 "B"o On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Page 20 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Part Number Definition:
1. Digit 13 may be A, B, C, D, E, F, G, H, or N in the model type identifier.
Filtering Table:
Available Selection Selection for Digit 13Programmable Relay Board (Qty 1) “A”Input Contact Isolator Board (Qty 1) “B”1 "A" and 1 "B" “C”2 "A" “D” 2 "B" “E” 2 "A" and 1 "B" “F”1 "A" and 2 "B" “G”2 "A" and 2 "B" “H”None “N”
Title: HMI Options
o On | Emergency Module Offo On | Display Keylocko On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Part Number Definition:
1. Digit 14 may be E, K or N in the model type identifier.
Filtering Table:
Available Selection Digit 14Emergency Module Off “E”Display Keylock “K”None “N”
Title: System Interfaceso On | Digital Load Bus Sync Interface - SMSo On | Digital Load Bus Sync Interface - MMU
Page 21 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | PowerTie and DLBS Interface - SMSo On | PowerTie and DLBS Interface - MMU o On | None
Business Rules:
1. The default is “N”.2. A selection is not required. There are some auto selections based on input in the “SCC” tab.
Part Number Definition:
1. Digit 15 may be A, B, C, D or N in the model type identifier.
Filtering Table:
Selection Module Quantity
Digit 4 Selection for Digit 15
Digital Load Bus Sync Interface - SMS
* “A” “A”
Digital Load Bus Sync Interface - MMU
* “R”, “N” “B”
PowerTie and DLBS Interface - SMS
1 “A” “C”
PowerTie and DLBS Interface - MMU
* “R”, “N” “D”
None * “N”
Title: Monitoring Cardso On | Web Intellislot Card (Qty 1) (“A”)o On | MODBUS 485 Intellislot Card (Qty 1) (“B”)o On | MODBUS IP (Qty 1) (“C”)o On | Sitescan 4 Intellislot Card (Qty 1) (“D”)o On | 1 "A" and "B"o On | 1 "A" and "C”o On | 1 "A" and "D"o On | 1 "B" and "C"o On | 1 "B" and "D"o On | 1 "C" and "D"o On | 1 "A", "B" and "C"
Page 22 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 1 "A", "B" and "D" o On | 1 "A", "C" and "D”o On | 1 "B", "C" and "D"o On | 1 "A", "B", "C" and "D"o On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Part Number Definition:
1. Digit 16 may be A, B, C, D, E, F, G, H, J, K, L, M, P, R, S or N in the model type identifier.
Filtering Table:
Available Selection Selection for Digit 16Web Intellislot Card (Qty 1) (“A”) “A”MODBUS 485 Intellislot Card (Qty 1) (“B”) “B”MODBUS IP (Qty 1) (“C”) “C”Sitescan 4 Intellislot Card (Qty 1) (“D”) “D”1 "A" and "B" “E”1 "A" and "C” “F”1 "A" and "D “G”1 "B" and "C" “H”1 "B" and "D" “J”1 "C" and "D" “K”1 "A", "B" and "C" “L”1 "A", "B" and "D" “M”1 "A", "C" and "D" “P”1 "B", "C" and "D" “R”1 "A", "B", "C" and "D" “S”None “N”
Title: Energy Optimization Mode
o On | Ecomode Operation (A)o On | Intelligent Paralleling Operation (B)o On | HRG Capability (C)o On | 1 "A" and "C" o On | 1 "B" and "C"o On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Page 23 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Part Number Definition:
1. Digit 17 may be A, B, C, D, E or N in the model type identifier.
Filtering Table:
Digit 4 Available for Digit 17
“R”, “N” or “M” “A”, “B”, “C”, “D”, “E”, “N”
“A” “A”, “C”, “D”, “N”
Title: RASP Power Supply
o On | Optional Power Supplyo On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Digit 18 = selection
Title: Motor Operator
o On | Motor Operated CB1o On | Motor Operated CB2o On | One of Motor Operated CB1 and Motor Operated CB2o On | MBD Motor Operator Interfaceo On | One Motor Operated CB1 and MBD Motor Operator Interfaceo On | One Motor Operated CB2 and MBD Motor Operator Interfaceo On | One of Motor Operated CB1 and Motor Operated CB2 and MBD Motor Operator Interfaceo On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Selection Selection for Digit 19
Motor Operated CB1 “A”Motor Operated CB2 “B”One of Motor Operated CB1 and Motor Operated CB2 “C”MBD Motor Operator Interface “E”
Page 24 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
One Motor Operated CB1 and MBD Motor Operator Interface “F”One Motor Operated CB2 and MBD Motor Operator Interface “G”One of Motor Operated CB1 and Motor Operated CB2 and MBD Motor Operator Interface “H”None “N”
Digit 19 = selection
Title: Single Input Jumper
o On | Single Input Jumpero On | None
Business Rules:
3. The default is “N”.4. A selection is not required.
Part Number Definition:
1. Digit 20 may be “1” or “N” in the model type identifier.
Filtering Table:
Digit 5 Digit 12 Selection for Digit 20Default * * “N”Manual “2”, “3”, “4” “A”, “B”, “E”, “F” “1”
Digit 21 = N
Digit 22 = N
Tab: “UPS Module”, Sub-Tab: “Site Installed Options”
Title: Web Intellislot Cardo Quantity | IS-WEBX Web Intellislot Card (field kit)
Business Rules:
1. The default is “0”.2. A selection is not required. Manual selection of any whole number between “0” and “9” is
allowed.3. IS-WEBX is the model type identifier.
Page 25 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
IS-WEBXWeb Intellislot Card (field kit)
Title: MODBUS 485 Intellislot Cardo Quantity | IS-485X MODBUS 485 Intellislot Card (field kit)
Business Rules:
1. The default is “0”.2. A selection is not required. Manual selection of any whole number between “0” and “9” is allowed.3. IS-485X is the model type identifier.
IS-485X MODBUS 485 Intellislot Card (field kit)
Title: MODBUS IP Intellislot Cardo Quantity | IS-IPBMX MODBUS IP (field kit)
Business Rules:
1. The default is “0”.2. A selection is not required. Manual selection of any whole number between “0” and “9” is allowed.3. IS-IPBMX is the model type identifier.
IS-IPBMX MODBUS IP (field kit)
If digit 18 is not “P”, then hide.
Title: Remote Alarm Status Panel Quantityo On | No Remote Alarm Status Panel o On | One Remote Alarm Status Panel o On | Two Remote Alarm Status Panelso On | Three Remote Alarm Status Panels o On | Four Remote Alarm Status Panels o On | Five Remote Alarm Status Panels o On | Six Remote Alarm Status Panels
Business Rules:
1. The default is “0”.2. Selections are manual.
Filtering Table:
Module “Quantity” Module Digit 4 Available Selection for Quantity
Page 26 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Default * 0
“1” “A”, “M” 1
“1” “R”, “N” 1
“0” * 2
“2” “A” 2
“2”, “3”, “4”, “5”, “6” “R”, “N”, “M” 2
“0” * 3
“3” “A” 3
“3”, “4”, “5”, “6” “R”, “N”, “M” 3
“0” * 4
“4” “A” 4
“4”, “5”, “6” “R”, “N”, “M 4
“0” * 5
“5” “A” 5
“5”, “6” “R”, “N”, “M 5
“0” * 6
“6” “A”, “R”, “N”, “M” 6
If Quantity is “0”, then hide.
Title: Remote Alarm Status Panel Type
o On | Remote Alarm Status Panel - Surface Mountedo On | Remote Alarm Status Panel - Flush Mounted
Business Rules:
1. There is no default.2. Selection is required. 3. NXLRAS and NXLRASF are the model type identifiers.
NXLRAS Remote Alarm Status Panel - Surface MountedNXLRASF Remote Alarm Status Panel - Flush Mounted
Page 27 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
If quantity is zero, then hide.
Title: Module Floor Anchorso Checkbox | Module Floor Anchors
Business Rules:
1. Selection is not required. 2. One floor anchor per module
Title: OSHPOD__o Checkbox | OSHPOD
Business Rules:
1. Hide if module floor anchors is not selected.2. A selection is not required. 3. OSHPOD Selection affects floor anchors part numbers as follows.
Part Number Table:
OSHPOD Module Digit 3
Module Digit 5, 6, 7
Module Digit 8
Selection for part number
“No” * 250, 25A “A” NXLFA250
“No” * 300, 30A “A” NXLFA300
“No” * 400, 40A “A” NXLFA400
“No” * 300, 30A “B” or “3” NXLFA400B
“No” * “500” * NXLFA500
“No” “S” “50M” * NXLFA50U
“No” “S” “62M” * NXLFA625S
“No” “M” “62M” * NXLFA625M
“No” “S” “626” or “750”
NXLFA750S
Page 28 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“No” “M” “626” or “750”
NXLFA750M
“No” “S” “75M” NXLFA75US
“No” “M” “75M” NXLFA75UM
“No” “S” “11M” * NXLFA11US
“No” “M” “11M” * NXLFA11UM
“Yes” * 250, 25A * NXLOSH250
“Yes” * 300, 30A * NXLOSH300
“Yes” * 400, 40A “A” NXLOSH400A
“Yes” * 400, 40A “B” or “3” NXLOSH400B
“Yes” * “500” * NXLOSH500
“Yes” * “50M” * NXLOSH50U
“Yes” “S” “62M” * NXLOSH62US
“Yes” “M” “62M” * NXLOSH62UM
“Yes” “S” “626” or “750” or “75M”
* NXLOSH75US
“Yes” “M” “626” or “750” or “75M”
* NXLOSH75UM
“Yes” “S” “110” * NXLOSH11US
“Yes” “M” * * NXLOSH11UM
Title: Single Input Wiring Cabinet
Business Rules:
1. One “single input wiring cabinet” per module if Module digit 4 = “A”, “N”, or “R”.2. NXLWC950 is the model type identifier if Module digit 5 = 5 or 6 or 7.
If Module digit 4 = “A” display next section, otherwise hide.
Page 29 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “UPS Module”, Sub-Tab: “Matching MBC”Title: MBC
Title: Checkbox o Checkbox | MBC
Business Rules:
1. Show if module digit 12 = “E”, “F”, “M” or “N” and Module digit 8 =”A”.2. MBC quantity is the same as the Module quantity.
Begin subsequent part number for Matching MBC.
Digits 1, 2, 3, 4
40MB NXL Matching Maintenance Bypass
Filtering Table:
Module Digit 5
Selection for Matching MBC digits 5, 6 and 7
“2” “250”“3” “300”“4” “400”“5” “500”“6” “625”“7” “750”
Business Rules:
1. Selection is automatic.
Digit 8,9,1000A Bypass and MBP from separate feeder Auto select
Business Rules:
1. The default is automatic.2. Selection is automatic.
Filtering Table:
Page 30 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Module digit 12
Selection for Matching MBC digit 11
“E”, “M” “A”“F”, “N” “B”
Title: Matching MBP Field Installed Options (Qty per Maintenance Bypass Cabinet)
Title: Matching MBP Floor Anchorso Checkbox | Matching MBP Floor Anchors
Business Rules:
1. Show section if Module Floor Anchors is selected.2. The default is “0”.3. Selection is not required. 4. One floor anchor per module if selected.
Part Number Table:
Manual or Automatic
Module Floor Anchors OSHPOD
Matching Maintenance Bypass Digit 5
Selection
Automatic “No” “2”, “3” “NXLFAMBC”Automatic “No” “4”, “5” “NXLFAMBC500”Automatic “No” “6”, “7” “NXLFAMBC750”Automatic “Yes” “2”, “3” “NXLOSHMB300”Automatic “Yes” “4”, “5” “NXLOSHMB500”Automatic “Yes” “6”, “7” “NXLOSHMB750”
If Module digit 4 = “A” do the next section, otherwise skip.
Page 31 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “UPS Module”, Sub-Tab: “Buyout MBP (Panelboard)”Title: Select Rating
o On | Automatico On | Manual
Business Rules:
1. Only available if filter table says “Selection Available”.2. There is no default.
Filtering Table:
Module Digit 4
Module Digit 5 Module Digit 12
Selection Available
“A” “2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “Automatic”, “Manual”,
“A” “5”, “6”, “7” “C”, “D” “Automatic”
Title: Select Quantityo On | Available Selection
Business Rules:
1. There is no default.2. Selection is manual if available.
Filtering Table:
Module Quantity
Module Digit 4
Module Digit 5 Module Digit 12
Selection Available
“1” “A” “5”, “6”, “7” “C”, “D”
“1”
“1” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“1”
“2” “A” “5”, “6”, “7” “C”, “D”
“2”
“2” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“2”
“3” “A” “5”, “6”, “7” “C”, “D”
“3”
“3” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“3”
“4” “A” “5”, “6”, “7” “C”, “D”
“4”
“4” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“4”
“5” “A” “5”, “6”, “7” “C”, “D”
“5”
Page 32 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“5” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“5”
“6” “A” “5”, “6”, “7” “C”, “D”
“6”
“6” “A” “2”, “3”, “4”, “5”, “6”, “7” “A”, “B”
“6”
Quantity is the same as module quantity.
Begin subsequent part number for Buyout MBP (Panelboard).
Digits 1, 2, 3MBP NXL
Title: Number of Deviceso On | MBB, MIBo On | BIB, MBB, MIB o On | RIB, BIB, MBB, MIB
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module digit 5
Available Selection for Buyout MBP (Panelboard) digit 4
* MBB, MIB “2”
* BIB, MBB, MIB
“3”
2, 3, 4 RIB, BIB, MBB, MIB
“4”
Title: Breaker Trip Ratingo On | 350Ao On | 400Ao On | 500A
Page 33 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 600Ao On | 700Ao On | 800A
Business Rules:
1. There is no default.2. Selection is automatic or manual.
Filtering Table:
Select Rating
Buyout MBP (Panelboard) Digit 4
Module Digit 5, 6 and 7
Module Digit 9
Selection for Buyout MBP (Panelboard) digit 5, 6, 7
“Manual” * * * “350”“Automatic”
“2”, “3” “250” “B”, “3”
“350”
“Manual” * * * “400”“Automatic”
“2”, “3” “250” “A” “400”
“Automatic”
“2”, “3” “300” “B”, “3”
“400”
“Automatic”
“4” “250” “B”, “3”
“400”
“Manual” * * * “500”“Automatic”
“2”, “3” “300” “A” “500”
“Automatic”
“2”, “3” “400” “B” “500”
“Automatic”
“4” “250” “A” “500”
“Automatic”
“4” “300” “B”, “3”
“500”
“Manual” * * * “600”“Automatic”
“2”, “3” “400” “3” “600”
“Automatic”
“4” “300” “A” “600”
“Manual” * * * “700”“Automatic”
“2”, “3” “400” “A” “700”
“Automatic”
“2”, “3” “500”, “50M”
“B”, “3”
“700”
“Automatic”
“4” “400” “B”, “3”
“700”
“Manual” * * * “800”
Page 34 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic”
“2”, “3” “500”, “50M”
“A” “800”
“Automatic”
“2”, “3” “626”, “62M”
“B”, “3”
“800”
“Automatic”
“4” “400” “A” “800”
Business Rules: (digit 8)
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digit 9
Description Selection for Buyout MBP (Panelboard) digit 8
“A” 480 V “A”“3”, “B”
600 V “B”
Title: LDB Codeo On | None o On | 2X250AFo On | 4X250AF o On | 2X400AFo On | 4X400AF, 2X250AF
Business Rules:
1. The default is “None”.2. Selection is manual.
Filtering Table:
Buyout MBP (Panelboard) Digit 5
Description Selection for Buyout MBP (Panelboard) digit 9 and 10
* None “00”“3”, “4”, “5”, “6”
2X250AF “05”
* 4X250AF “07”* 2X400AF “11”* 4X400AF,
2X250AF“13”
Page 35 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Filtering Table:
Buyout MBP (Panelboard) Digit 10
Number of LDBs
5, 1 27, 3 4
Filtering Table:
Manual or Automatic
Buyout MBP (Panelboard) Digit 10
Selection for LDB Frame size
LDB #1 Trip Rating
Automatic 5 “250A” 70, 90, 100, 125, 150, 175, 200, 225, 250
Automatic 1, 3 “400A” 175, 200, 225, 250, 300, 350, 400LDB #2 Trip Rating
Automatic 5 “250A” 70, 90, 100, 125, 150, 175, 200, 225, 250
Automatic 1, 3 “400A” 175, 200, 225, 250, 300, 350, 400LDB #3 Trip Rating
Automatic 7, 3 “250A” 70, 90, 100, 125, 150, 175, 200, 225, 250LDB #4 Trip Rating
Automatic 7, 3 “250A” 70, 90, 100, 125, 150, 175, 200, 225, 250
Title: Panelboard Rating ___ kAo On | 25 kAo On | 35 kAo On | 50 kAo On | 65 kAo On | 100 kA
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module Digit 9
Buyout MBP (Panelboard) Digits 5, 6
Available Choice
* * 25, 35, 50“A” * 65
Page 36 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“A” 80 100
Title: Breaker Typeo On | Molded Case Switcho On | Standardo On | High
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Buyout MBP (Panelboard) Digit 5
Buyout MBP (Panelboard) Digit 8
kA Available Choice
Selection for Buyout MBP (Panelboard) Digit 11
* “A” 25, 35, 50, 65
Molded Case Switch
“N”
* “B” 25, 35 Molded Case Switch
“N”
3, 4, 5, 6 “A” 25, 35 Standard “S”7, 8 “A” 25,
35, 50, 65
Standard “S”
* “B” 25 Standard “S”
3, 4, 5, 6 “A” 25, 35, 50, 65
High “H”
7, 8 “A” 25, 35, 50, 65, 100
High “H”
* “B” 25, 35, 50
High “H”
Digit 12, 13 = “40” NXL
Title: Options
Page 37 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | Noneo On | Key Interlock (A)o On | Auxiliary Contacts (B)o On | EPO (C)o On | 1 "A" and 1 "B"o On | 1 "A", 1 "B", and 1 "C" o On | 1 "A" and 1 "C"o On | 1 "B" and 1 "C"
Business Rules:
1. The default is “0”.2. Selection is manual.
Part Number Table:
Description Selection for Buyout MBP (Panelboard) digit 14
None “0”Key Interlock
“1”
Auxiliary Contacts
“2”
EPO “3”1 "1" and 1 "2"
“4”
1 "1", 1 "2", and 1 "3"
“5”
1 "1" and 1 "3"
“6”
1 "2" and 1 "3"
“7”
Digit 15 = “2” “Siemens”
Title: Custom Panelboard o Checkbox | Noo Checkbox | Yes
Business Rules:
1. The default is “No”.2. Selection is manual. 3. If “No” is selected, hide the next section.
Page 38 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Custom Panelboard Detailso Input | Part Numbero Input | Descriptiono Input | Price
Business Rules:
1. There is no default.2. Selection is manual and input. 3. Repeat this section until the user selects “no” for “Custom Panelboard”
If Module digit 4 = “A” display the next section, otherwise hide.
Tab: “UPS Module”, Sub-Tab: “Buyout MBS (Switchboard)”Title: Select Rating
o On | Automatico On | Manual
Business Rules:
1. Only available if filter table says “Selection available”.2. There is no default.
Filtering Table:
Module Digit 4
Module Digit 5
Module Digit 12
Selection Available
“A” “2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “Automatic”, “Manual”
“A” “5”, “6”, “7”
“C”, “D” “Automatic”
Title: Select Quantityo Quantity | Available Selection
Business Rules:
1. The default is “0”.2. Selection is manual if available.
Filtering Table:
Page 39 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Module Quantity
Module Digit 17
Module Digit 5
Module Digit 12
Selection AvailableTrue
“1” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “1”
“1” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “1”
“2” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “2”
“2” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “2”
“3” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “3”
“3” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “3”
“4” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “4”
“4” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “4”
“5” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “5”
“5” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “5”
“6” “A”, “B”, “N”
“5”, “6”, “7” “C”, “D” “6”
“6” “A”, “B”, “N”
“2”, “3”, “4”, “5”, “6”, “7”
“A”, “B” “6”
Quantity is the same as module quantity
Begin subsequent part number for Buyout MBS (Switchboard).
Digits 1, 2, 3
MBS NXL
Page 40 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Select Ratingo On | Manualo On | Automatic
1. Only available if Buyout MBP Switchboard is selected.2. There is no default.3. Selection is manual
Title: Number of Deviceso On | MBB, MIBo On | BIB, MBB, MIB o On | RIB, BIB, MBB, MIB
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module digit 5
Available Selection for Buyout MBS (Switchboard) digit 4
* MBB, MIB “2”
* BIB, MBB, MIB
“3”
2, 3, 4 RIB, BIB, MBB, MIB
“4”
Title: Breaker Trip Ratingo On | 500Ao On | 600Ao On | 700Ao On | 800Ao On | 900A o On | 1000Ao On | 1200Ao On | 1600A
Page 41 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Business Rules:
1. There is no default.2. Selection is automatic or manual.
Filtering Table:
Select Rating
Buyout MBS (Switchboard) Digit 4
Module Digit 5, 6, 7
Module Digit 9
Breaker Type
Selection for Buyout MBS (Switchboard) digit 5, 6, 7, 8
“Manual” * * * * “0500”“Automatic”
“2”, “3” “300” “A” * “0500”
“Automatic”
“2”, “3” “400” “B” * “0500”
“Automatic”
“4” “250” “A” * “0500”
“Automatic”
“4” “300” “B”, “3”
* “0500”
“Manual” * * * * “0600”“Automatic”
“2”, “3” “400” “3”, “B”
* “0600”
“Automatic”
“4” “300” “A”, “3”, “B”
* “0600”
“Automatic”
“2”, “3” “300” “A” * “0600”
“Automatic”
“4” “250” “A” * “0600”
“Manual” * * * * “0700”“Automatic”
“2”, “3” “400” “A” * “0700”
“Automatic”
“2”, “3” “500”, “50M”
“B”, “3”
* “0700”
“Automatic”
“4” “400” “B”, “3”
* “0700”
“Manual” * * * * “0800”“Automatic”
“2”, “3” “500”, “50M”
“A” * “0800”
“Automatic”
“2”, “3” “62M” “B”, “3”
* “0800”
“Automatic”
“4” “400” “A” * “0800”
“Automatic”
“4” “50M” “B”, “3”
* “0800”
“Automatic”
“2”, “3” “400” “A” “N” “0800”
“Automatic”
“2”, “3” “50M” “B”, “3”
“N” “0800”
Page 42 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic”
“4” “400” “B”, “3”
“N” “0800”
“Manual” * * * “S”, “H”
“0900”
“Manual” * * * “1000”“Automatic”
“4” “500”, “50M”
“A” “1000”
“Automatic”
“2”, “3” “626”, “62M”
“A” “1000”
“Automatic”
“2”, “3” “750”, “75M”
“B”, “3”
“1000”
“Automatic”
“4” “62M” “B”, “3”
“1000”
* * * * “1200”“Automatic”
“4” “62M” “A” “1200”
“Automatic”
“2”, “3” “750”, “75M”
“A” “1200”
“Automatic”
“4” “750”, “75M”
“B”, “3”
“1200”
“Automatic”
“4” “75M” “3” “1200”
“Automatic”
“2”, “3” “626”, “62M”
“A” “N” “1200”
“Automatic”
“2”, “3” “750”, “75M”
“B”, “3”
“N” “1200”
“Automatic”
“4” “500”, 50M”
“A” “N” “1200”
“Automatic”
“4” “62M” “B”, “3”
“N” “1200”
* * * * “1600”“Automatic”
“2”, “3” “11M”, “12M"
“B”, “3”
“1600”
“Automatic”
“4” “626”, “A” “1600”
“Automatic”
“4” “750” “3” “1600”
“Automatic”
“4” “75M”, “750”
“A” “1600”
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digit 9 Description Selection for Buyout MBS
Page 43 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
(Switchboard) digit 9
“A” 480 V “A”“3”, “B” 600 V “B”
Buyout MBS (Switchboard) Digit 10 = “R”
Title: Switchboard Rating ___ kAo On | 25 kAo On | 35 kAo On | 50 kAo On | 65 kAo On | 100 kA
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Manual or Automatic
Buyout MBS (Switchboard) Digit 5, 6
Module Digit 9
Available Choice
Manual * “A” “65”, “100”
Manual 10, 12, 16 “B”, “3” “65”Manual * * “25”,
“35”, “50”
Title: Breaker Typeo On | Molded Case Switcho On | Standardo On | High
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Manual or Buyout MBS Buyout MBS kA Available Selection for
Page 44 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Automatic (Switchboard) Digit 5, 6
(Switchboard) Digit 9
Choice Buyout MBS (Switchboard) Digit 11
Manual 05, 06, 07, 08, 09, 10, 12
“A” 25, 35, 50, 65
Molded Case Switch
“N”
Manual 05, 06, 07, 08 “B” 25, 35 Molded Case Switch
“N”
Manual * “A” 25, 35, 50, 65
Standard “S”
Manual 05, 06, 07, 08, 09, 10, 12
“B” 25 Standard “S”
Manual 16 “B” 25, 35, 50
Standard “S”
Manual * “A” * High “H”Manual 05, 06, 07, 08 “B” 25, 35,
50High “H”
Manual 10, 12, 16 “B” 25, 35, 50, 65
High “H”
Buyout MBS (Switchboard) Digit 12, 13 = 40
Title: Optionso On | Noneo On | Key Interlock (A)o On | Auxiliary Contacts (B)o On | EPO (C)o On | 1 "A" and 1 "B"o On | 1 "A", 1 "B", and 1 "C" o On | 1 "A" and 1 "C"o On | 1 "B" and 1 "C"
Business Rules:
1. The default is “0”.2. Selection is manual.
Filtering Table:
Description Selection for digit 14
None “0”Key Interlock
“1”
Auxiliary Contacts
“2”
EPO “3”
Page 45 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1 "1" and 1 "2"
“4”
1 "1", 1 "2", and 1 "3"
“5”
1 "1" and 1 "3"
“6”
1 "2" and 1 "3"
“7”
Digit 15 = “2” “Siemens” default
Title: Custom Switchboardo Checkbox | Noo Checkbox | Yes
Business Rules:
1. The default is “No”.2. Selection is manual. 3. If “No” is selected, hide the next section.
Title: Custom Switchboard Detailso Input | Part Numbero Input | Descriptiono Input | Price
Business Rules:
1. There is no default.2. Selection is manual and input. 3. Repeat this section until the user selects “no” for “Custom Switchboard”
If Module digit 4 = “R” or “N” display the next section, otherwise hide.
Tab: “UPS Module”, Sub-Tab: “Buyout SP”Title: Buyout SP (Switchgear)
Title: Number of modules in fully configured system____o On | 2
Page 46 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 3o On | 4o On | 5
Business Rules:
1. Show only if Selection Available. 2. There is no default.3. Manual selection is required.
Filtering Table:
Module digit 4
Module Quantity
Available Selection
“R”, “N” 1 ,2 “2” “N” 1, 2, 3 “3”“N” 1, 2, 3, 4 “4”“N” 1, 2, 3, 4, 5 “5”
Title: Select Rating____
o On | Automatico On | Manual
Business Rules:
1. Show only if “Number of Modules in fully Configured system” is selected.2. There is no default.3. Manual selection is required.
Filtering Table:
Selection“Automatic”“Manual”
Title: Redundant System____o Checkbox | Yeso Checkbox | No
Business Rules:
1. The default is “Yes”.2. Manual selection is required.
Page 47 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Buyout SP Digits 1, 2, 3, 4SP40 NXL
Title: Configurationo On | MBB, MIBo On | MBB, MIB, LBB
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module Digit 4
Available Selection for Buyout SP digit 5
“N”, “R” MBB, MIB “A”
“N”, “R” MBB, MIB, LBB
“B”
Title: Bypass Voltage and Withstand Ratingo On | 480V 65kAo On | 480V 100kAo On | 480V 125kAo On | 600V 35kA o On | 600V 65kAo On | 600V 100kA
Business Rules:
1. There is no default.2. Manual selection is required.
Filtering Table:
Select Rating
Module Digit 8
Withstand Rating
Choice Selection for digit 6
“Manual” * * 480V 65kA “A”“Automatic”
“A” 65 480V 65kA “A”
“Manual” * * 480V 100kA “B”“Automatic”
“A” 100 480V 100kA “B”
Page 48 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * 480V 125kA “C”“Automatic”
“A” 125 480V 125kA “C”
“Manual” * * 600V 35kA “D”“Automatic”
“3”, “B” 35 600V 35kA “D”
“Manual” * * 600V 65kA “E”“Automatic”
“3”, “B” 65 600V 65kA “E”
“Manual” * * 600V 100kA “F”“Automatic”
“3”, “B” 100 600V 100kA “F”
Title: System Breaker Ratingo On | 350Ao On | 400Ao On | 500Ao On | 600A o On | 700Ao On | 800Ao On | 1000Ao On | 1200Ao On | 1600Ao On | 2000A o On | 2500Ao On | 3000Ao On | 4000A
Business Rules:
1. There is no default.2. Manual selection is required.
Filtering Table:
Select Rating
Number of Modules
Redundant System
Module Digit 5
Module Digit 9
Choice Selection for digit 7
“Manual” * * * * * “P”“Automatic”
2 “Yes” “2” “3”,”B” “350A” “P”
“Manual” * * * * * “N”“Automatic”
2 “Yes” “2” “A” “400A” “N”
“Automatic 2 “Yes” “3” “3”,”B” “400A” “N”
Page 49 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
”“Manual” * * * * * “M”“Automatic”
2 “Yes” “3” “A” “500A” “M”
“Automatic”
2 “Yes” “4” “B” “500A” “M”
“Manual” * * * * * “L”“Automatic”
2 “Yes” “4” “3” “600A” “L”
“Manual” * * * * * “K”“Automatic”
2 “Yes” “4” “A” “700A” “K”
“Automatic”
2 “Yes” “5” “3”, “B” “700A” “K”
“Automatic”
2 “No” “2” “3”, “B” “700A” “K”
“Automatic”
3 “Yes” “2” “3”, “B” “700A” “K”
“Manual” * * * * * “J”“Automatic”
2 “Yes” “5” “A” “800A” “J”
“Automatic”
2 “Yes” “6” “3”, “B” “800A” “J”
“Automatic”
2 “No” “2” “A” “800A” “J”
“Automatic”
2 “No” “3” “3”, “B” “800A” “J”
“Automatic”
3 “Yes” “2” “A” “800A” “J”
“Automatic”
3 “Yes” “3” “3”, “B” “800A” “J”
“Manual” * * * * * “H”“Automatic”
2 “Yes” “6” “A” “1000A” “H”
“Automatic”
2 “Yes” “7” “3”, “B” “1000A” “H”
“Automatic”
2 “No” “4” “B” “1000A” “H”
“Automatic”
2 “No” “3” “A” “1000A” “H”
“Automatic”
3 “Yes” “4” “B” “1000A” “H”
“Automatic”
3 “Yes” “3” “A” “1000A” “H”
“Manual” * * * * * “G”“Automatic”
2 “Yes” “7” “A” “1200A” “G”
“Automatic”
3 “Yes” “4” “3” “1200A” “G”
“Automatic 2 “No” “4” “3” “1200A” “G”
Page 50 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
”“Automatic”
3 “No” “2” “A” “1200A” “G”
“Automatic”
3 “No” “3” “3”,”B” “1200A” “G”
“Automatic”
4 “Yes” “2” “A” “1200A” “G”
“Automatic”
4 “Yes” “3” “3”,”B” “1200A” “G”
“Manual” * * * * * “F”“Automatic”
2 “Yes” “1” “A”, “3”, “B”
“1600A” “F”
“Automatic”
3 “Yes” “4” “A” “1600A” “F”
“Automatic”
3 “Yes” “5” “A”, “3”, “B”
“1600A” “F”
“Automatic”
3 “Yes” “6” “A”, “3”, “B”
“1600A” “F”
“Automatic”
3 “Yes” “7” “3”, “B” “1600A” “F”
“Automatic”
2 “No” “4” “A” “1600A” “F”
“Automatic”
2 “No” “5” “A”, “3”, “B”
“1600A” “F”
“Automatic”
2 “No” “6” “A”, “3”, “B”
“1600A” “F”
“Automatic”
2 “No” “7” “3”, “B” “1600A” “F”
“Automatic”
3 “No” “3” “A” “1600A” “F”
“Automatic”
3 “No” “4” “A”, “3”,”B”
“1600A” “F”
“Automatic”
3 “No” “5” “3”,”B” “1600A” “F”
“Automatic”
4 “Yes” “3” “A” “1600A” “F”
“Automatic”
4 “Yes” “4” “A”, “3”,”B”
“1600A” “F”
“Automatic”
4 “Yes” “5” “3”,”B” “1600A” “F”
“Manual” * * * * * “E”“Automatic”
2 “No” “7” “A” “2000A” “E”
“Automatic”
3 “Yes” “7” “A” “2000A” “E”
“Automatic”
4 “Yes” “5” “A” “2000A” “E”
“Automatic”
4 “Yes” “6” “3”, “B” “2000A” “E”
“Automatic 3 “No” “5” “A” “2000A” “E”
Page 51 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
”“Automatic”
3 “No” “6” “3”, “B” “2000A” “E”
“Manual” * * * * * “D”“Automatic”
2 “No” “1” “3”, “B” “2500A” “D”
“Automatic”
3 “Yes” “1” “3”, “B” “2500A” “D”
“Automatic”
4 “Yes” “6” “A” “2500A” “D”
“Automatic”
4 “Yes” “7” “3”, “B” “2500A” “D”
“Automatic”
3 “No” “6” “A” “2500A” “D”
“Automatic”
3 “No” “7” “3”, “B” “2500A” “D”
“Automatic”
5 “Yes” “5” “A”, “3” “2500A” “D”
“Automatic”
5 “Yes” “6” “B” “2500A” “D”
“Automatic”
4 “No” “5” “A”, “3” “2500A” “D”
“Automatic”
4 “No” “6” “B” “2500A” “D”
“Manual” * * * * * “C”“Automatic”
2 “No” “1” “3” “3000A” “C”
“Automatic”
3 “Yes” “1” “3” “3000A” “C”
“Automatic”
4 “Yes” “7” “A” “3000A” “C”
“Automatic”
3 “No” “7” “A” “3000A” “C”
“Automatic”
5 “Yes” “7” “B” “3000A” “C”
“Automatic”
5 “Yes” “6” “3” “3000A” “C”
“Automatic”
4 “No” “7” “B” “3000A” “C”
“Automatic”
4 “No” “6” “3” “3000A” “C”
“Manual” * * * * * “B”“Automatic”
3 “No” “1” “A”, “3”,”B”
“4000A” “B”
“Automatic”
4 “Yes” “1” “A”, “3”,”B”
“4000A” “B”
“Automatic”
5 “Yes” “6” “A” “4000A” “B”
“Automatic”
4 “No” “6” “A” “4000A” “B”
Page 52 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic”
5 “Yes” “7” “A”, “3” “4000A” “B”
“Automatic”
4 “No” “7” “A”, “3” “4000A” “B”
Title: MOB Ratingo On | Available selectiono On | Available selectiono On | Available selectiono On | Available selectiono On | Available selectiono On | Available selection
Business Rules:
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Select Rating
Number of Modules
Buyout SP Digit 6
Buyout SP Digit 7
Module digits 5, 6, 7
Module digits 8
Available Selection Buyout SP digit 8, 9
“Manual” * * * * * “No MOB” “00”“Manual” * * * * * 2 each 2000A 100kA
@480V 2000A Main“AA”
“Automatic” 2 “B” “E” “12M” “A” 2 each 2000A 100kA @480V 2000A Main
“AA”
“Manual” * * * * * 2 each 2000A 100kA @480V 3000A Main
“AB”
“Automatic” 2 “B” “C” “12M” “A” 2 each 2000A 100kA @480V 3000A Main
“AB”
“Manual” * * * * * 3 each 2000A 100kA @480V 3000A Main
“AC”
“Automatic” 3 “B” “C” “12M” “A” 3 each 2000A 100kA @480V 3000A Main
“AC”
“Manual” * * * * * 2 each 2000A 125kA @480V 2000A Main
“AD”
“Automatic” 2 “C” “E” “12M” “A” 2 each 2000A 125kA @480V 2000A Main
“AD”
“Manual” * * * * * 2 each 2000A 125kA @480V 3000A Main
“AE”
“Automatic” 2 “C” “C” “12M” “A” 2 each 2000A 125kA @480V 3000A Main
“AE”
“Manual” * * * * * 3 each 2000A 125kA @480V 3000A Main
“AF”
Page 53 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 3 “C” “C” “12M” “A” 3 each 2000A 125kA @480V 3000A Main
“AF”
“Manual” * * * * * 2 each 1600A 100kA @480V 1600A Main
“AG”
“Automatic” 2 “B” “F” “11M” “A” 2 each 1600A 100kA @480V 1600A Main
“AG”
“Manual” * * * * * 2 each 1600A 100kA @480V 3000A Main
“AH”
“Automatic” 2 “B” “C” “11M” “A” 2 each 1600A 100kA @480V 3000A Main
“AH”
“Manual” * * * * * 3 each 1600A 100kA @480V 3000A Main
“AJ”
“Automatic” 3 “B” “C” “11M” “A” 3 each 1600A 100kA @480V 3000A Main
“AJ”
“Manual” * * * * * 3 each 1600A 100kA @480V 4000A Main
“AK”
“Automatic” 3 “B” “B” “11M” “A” 3 each 1600A 100kA @480V 4000A Main
“AK”
“Manual” * * * * * 4 each 1600A 100kA @480V 4000A Main
“AL”
“Automatic” 4 “B” “B” “11M” “A” 4 each 1600A 100kA @480V 4000A Main
“AL”
“Manual” * * * * * 2 each 1600A 125kA @480V 1600A Main
“AM”
“Automatic” 2 “C” “F” “11M” “A” 2 each 1600A 125kA @480V 1600A Main
“AM”
“Manual” * * * * * 2 each 1600A 125kA @480V 3000A Main
“AN”
“Automatic” 2 “C” “C” “11M” “A” 2 each 1600A 125kA @480V 3000A Main
“AN”
“Manual” * * * * * 3 each 1600A 125kA @480V 3000A Main
“AP”
“Automatic” 3 “C” “C” “11M” “A” 3 each 1600A 125kA @480V 3000A Main
“AP”
“Manual” * * * * * 3 each 1600A 125kA @480V 4000A Main
“AR”
“Automatic” 3 “C” “B” “11M” “A” 3 each 1600A 125kA @480V 4000A Main
“AR”
“Manual” * * * * * 4 each 1600A 125kA @480V 4000A Main
“AS”
“Automatic” 4 “C” “B” “11M” “A” 4 each 1600A 125kA @480V 4000A Main
“AS”
“Manual” * * * * * 2 each 1600A 65kA @600V 1600A Main
“AT”
“Automatic” 2 “E” “F” “11M”, “12M”
“3”, “B” 2 each 1600A 65kA @600V 1600A Main
“AT”
“Manual” * * * * * 2 each 1600A 65kA @600V 2500A Main
“AU”
“Automatic” 2 “E” “D” “11M”, “12M”
“3”, “B” 2 each 1600A 65kA @600V 2500A Main
“AU”
Page 54 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 3 each 1600A 65kA @600V 2500A Main
“AV”
“Automatic” 3 “E” “D” “11M”, “12M”
“3”, “B” 3 each 1600A 65kA @600V 2500A Main
“AV”
“Manual” * * * * * 3 each 1600A 65kA @600V 4000A Main
“AW”
“Automatic” 3 “E” “B” “11M”, “12M”
“3”, “B” 3 each 1600A 65kA @600V 4000A Main
“AW”
“Manual” * * * * * 4 each 1600A 65kA @600V 4000A Main
“AX”
“Automatic” 4 “E” “B” “11M”, “12M”
“3”, “B” 4 each 1600A 65kA @600V 4000A Main
“AX”
“Manual” * * * * * 2 each 1600A 100kA @600V 1600A Main
“AY”
“Automatic” 2 “F” “F” “11M”, “12M”
“3”, “B” 2 each 1600A 100kA @600V 1600A Main
“AY”
“Manual” * * * * * 2 each 1600A 100kA @600V 2500A Main
“AZ”
“Automatic” 2 “F” “D” “11M”, “12M”
“3”, “B” 2 each 1600A 100kA @600V 2500A Main
“AZ”
“Manual” * * * * * 3 each 1600A 100kA @600V 2500A Main
“BA”
“Automatic” 3 “F” “D” “11M”, “12M”
“3”, “B” 3 each 1600A 100kA @600V 2500A Main
“BA”
“Manual” * * * * * 3 each 1600A 100kA @600V 4000A Main
“BB”
“Automatic” 3 “F” “B” “11M”, “12M”
“3”, “B” 3 each 1600A 100kA @600V 4000A Main
“BB”
“Manual” * * * * * 4 each 1600A 100kA @600V 4000A Main
“BC”
“Automatic” 4 “F” “B” “11M”, “12M”
“3”, “B” 4 each 1600A 100kA @600V 4000A Main
“BC”
“Manual” * * * * * 2 each 1200A 65kA @480V 1200A Main
“BD”
“Automatic” 2 “A” “G”, “H”
“750”, “75M”
“A” 2 each 1200A 65kA @480V 1200A Main
“BD”
“Manual” * * * * * 2 each 1200A 65kA @480V 2000A Main
“BE”
“Automatic” 2 “C” “C” “750”, “75M”
“A” 2 each 1200A 65kA @480V 2000A Main
“BE”
“Manual” * * * * * 3 each 1200A 65kA @480V 2000A Main
“BF”
“Automatic” 3 “A” “E” “750”, “75M”
“A” 3 each 1200A 65kA @480V 2000A Main
“BF”
“Manual” * * * * * 3 each 1200A 65kA @480V 3000A Main
“BG”
“Automatic” 3 “A” “C” “750”, “75M”
“A” 3 each 1200A 65kA @480V 3000A Main
“BG”
“Manual” * * * * * 4 each 1200A 65kA @480V 3000A Main
“BH”
Page 55 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 4 “A” “C” “750”, “75M”
“A” 4 each 1200A 65kA @480V 3000A Main
“BH”
“Manual” * * * * * 4 each 1200A 65kA @480V 4000A Main
“BJ”
“Automatic” 4 “A” “B” “750”, “75M”
“A” 4 each 1200A 65kA @480V 4000A Main
“BJ”
“Manual” * * * * * 5 each 1200A 65kA @480V 4000A Main
“BK”
“Automatic” 5 “A” “B” “750”, “75M”
“A” 5 each 1200A 65kA @480V 4000A Main
“BK”
“Manual” * * * * * 2 each 1200A 100kA @480V 1200A Main
“BL”
“Automatic” 2 “B” “G”, “H”
“750”, “75M”
“A” 2 each 1200A 100kA @480V 1200A Main
“BL”
“Manual” * * * * * 2 each 1200A 100kA @480V 2000A Main
“BM”
“Automatic” 2 “C” “F” “11M” “A” 2 each 1200A 100kA @480V 2000A Main
“BM”
“Manual” * * * * * 3 each 1200A 100kA @480V 2000A Main
“BN”
“Automatic” 3 “B” “E” “750”, “75M”
“A” 3 each 1200A 100kA @480V 2000A Main
“BN”
“Manual” * * * * * 3 each 1200A 100kA @480V 3000A Main
“BP”
“Automatic” 3 “B” “C” “750”, “75M”
“A” 3 each 1200A 100kA @480V 3000A Main
“BP”
“Manual” * * * * * 4 each 1200A 100kA @480V 3000A Main
“BR”
“Automatic” 4 “B” “C” “750”, “75M”
“A” 4 each 1200A 100kA @480V 3000A Main
“BR”
“Manual” * * * * * 4 each 1200A 65kA @480V 4000A Main
“BS”
“Automatic” 4 “B” “B” “750”, “75M”
“A” 4 each 1200A 65kA @480V 4000A Main
“BS”
“Manual” * * * * * 5 each 1200A 65kA @480V 4000A Main
“BT”
“Automatic” 5 “B” “B” “750”, “75M”
“A” 5 each 1200A 65kA @480V 4000A Main
“BT”
“Manual” * * * * * 2 each 1000A 65kA @480V 1200A Main
“BU”
“Automatic” 2 “A” “G”, “H”
“626”, “62M”
“A” 2 each 1000A 65kA @480V 1200A Main
“BU”
“Manual” * * * * * 2 each 1000A 65kA @480V 1600A Main
“BV”
“Automatic” 2 “A” “F” “626”, “62M”
“A” 2 each 1000A 65kA @480V 1600A Main
“BV”
“Manual” * * * * * 3 each 1000A 65kA @480V 1600A Main
“BW”
“Automatic” 3 “A” “F” “626”, “62M”
“A” 3 each 1000A 65kA @480V 1600A Main
“BW”
Page 56 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 3 each 1000A 65kA @480V 2500A Main
“BX”
“Automatic” 3 “A” “D” “626”, “62M”
“A” 3 each 1000A 65kA @480V 2500A Main
“BX”
“Manual” * * * * * 4 each 1000A 65kA @480V 2500A Main
“BY”
“Automatic” 4 “A” “D” “626”, “62M”
“A” 4 each 1000A 65kA @480V 2500A Main
“BY”
“Manual” * * * * * 4 each 1000A 65kA @480V 4000A Main
“BZ”
“Automatic” 4 “A” “B” “626”, “62M”
“A” 4 each 1000A 65kA @480V 4000A Main
“BZ”
“Manual” * * * * * 5 each 1000A 65kA @480V 4000A Main
“CA”
“Automatic” 5 “A” “B” “626”, “62M”
“A” 5 each 1000A 65kA @480V 4000A Main
“CA”
“Manual” * * * * * 2 each 1000A 100kA @480V 1200A Main
“CB”
“Automatic” 2 “B” “G”, “H”
“626”, “62M”
“A” 2 each 1000A 100kA @480V 1200A Main
“CB”
“Manual” * * * * * 2 each 1000A 100kA @480V 2000A Main
“CC”
“Automatic” 2 “B” “F” “626”, “62M”
“A” 2 each 1000A 100kA @480V 2000A Main
“CC”
“Manual” * * * * * 3 each 1000A 100kA @480V 2000A Main
“CD”
“Automatic” 3 “B” “F” “626”, “62M”
“A” 3 each 1000A 100kA @480V 2000A Main
“CD”
“Manual” * * * * * 3 each 1000A 100kA @480V 3000A Main
“CE”
“Automatic” 3 “B” “D” “626”, “62M”
“A” 3 each 1000A 100kA @480V 3000A Main
“CE”
“Manual” * * * * * 4 each 1000A 100kA @480V 3000A Main
“CF”
“Automatic” 4 “B” “D” “626”, “62M”
“A” 4 each 1000A 100kA @480V 3000A Main
“CF”
“Manual” * * * * * 4 each 1000A 100kA @480V 4000A Main
“CG”
“Automatic” 4 “B” “B” “626”, “62M”
“A” 4 each 1000A 100kA @480V 4000A Main
“CG”
“Manual” * * * * * 5 each 1000A 100kA @480V 4000A Main
“CH”
“Automatic” 5 “B” “B” “626”, “62M”
“A” 5 each 1000A 100kA @480V 4000A Main
“CH”
“Manual” * * * * * 2 each 1000A 35kA @600V 1200A Main
“CJ”
“Automatic” 2 “D” “G”, “H”
“750”, “75M”
“3”, “B” 2 each 1000A 35kA @600V 1200A Main
“CJ”
“Manual” * * * * * 2 each 1000A 35kA @600V 1600A Main
“CK”
Page 57 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 2 “D” “F” “750”, “75M”
“3”, “B” 2 each 1000A 35kA @600V 1600A Main
“CK”
“Manual” * * * * * 3 each 1000A 35kA @600V 1600A Main
“CL”
“Automatic” 3 “D” “F” “750”, “75M”
“3”, “B” 3 each 1000A 35kA @600V 1600A Main
“CL”
“Manual” * * * * * 3 each 1000A 35kA @600V 2500A Main
“CM”
“Automatic” 3 “D” “D” “750”, “75M”
“B” 3 each 1000A 35kA @600V 2500A Main
“CM”
“Manual” * * * * * 4 each 1000A 35kA @600V 2500A Main
“CN”
“Automatic” 4 “D” “D” “750”, “75M”
“B” 4 each 1000A 35kA @600V 2500A Main
“CN”
“Manual” * * * * * 3 each 1000A 35kA @600V 3000A Main
“CP”
“Automatic” 3 “D” “C” “750”, “75M”
“3” 3 each 1000A 35kA @600V 3000A Main
“CP”
“Manual” * * * * * 4 each 1000A 35kA @600V 3000A Main
“CR”
“Automatic” 4 “D” “C” “750”, “75M”
“3” 4 each 1000A 35kA @600V 3000A Main
“CR”
“Manual” * * * * * 4 each 1000A 35kA @600V 4000A Main
“CS”
“Automatic” 4 “D” “B” “750”, “75M”
“3”, “B” 4 each 1000A 35kA @600V 4000A Main
“CS”
“Manual” * * * * * 5 each 1000A 35kA @600V 4000A Main
“CT”
“Automatic” 5 “D” “B” “750”, “75M”
“3”, “B” 5 each 1000A 35kA @600V 4000A Main
“CT”
“Manual” * * * * * 2 each 1000A 65kA @600V 1000A Main
“CU”
“Automatic” 2 “E” “G”, “H”
“750”, “75M”
“3”, “B” 2 each 1000A 65kA @600V 1000A Main
“CU”
“Manual” * * * * * 2 each 1000A 65kA @600V 2000A Main
“CV”
“Automatic” 2 “E” “F” “750”, “75M”
“3”, “B” 2 each 1000A 65kA @600V 2000A Main
“CV”
“Manual” * * * * * 3 each 1000A 65kA @600V 2000A Main
“CW”
“Automatic” 3 “E” “F” “750”, “75M”
“3”, “B” 3 each 1000A 65kA @600V 2000A Main
“CW”
“Manual” * * * * * 3 each 1000A 65kA @600V 2500A Main
“CX”
“Automatic” 3 “E” “B” “750”, “75M”
“3”, “B” 3 each 1000A 65kA @600V 2500A Main
“CX”
“Manual” * * * * * 4 each 1000A 65kA @600V 2500A Main
“CY”
“Automatic” 4 “E” “D” “750”, “75M”
“B” 4 each 1000A 65kA @600V 2500A Main
“CY”
Page 58 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 3 each 1000A 65kA @600V 3000A Main
“CZ”
“Automatic” 3 “E” “C” “750”, “75M”
“3” 3 each 1000A 65kA @600V 3000A Main
“CZ”
“Manual” * * * * * 4 each 1000A 65kA @600V 3000A Main
“DA”
“Automatic” 4 “E” “C” “750”, “75M”
“3” 4 each 1000A 65kA @600V 3000A Main
“DA”
“Manual” * * * * * 3 each 1000A 65kA @600V 4000A Main
“DB”
“Automatic” 4 “E” “B” “750”, “75M”
“3”, “B” 3 each 1000A 65kA @600V 4000A Main
“DB”
“Manual” * * * * * 5 each 1000A 65kA @600V 4000A Main
“DC”
“Automatic” 5 “E” “B” “750”, “75M”
“3”, “B” 5 each 1000A 65kA @600V 4000A Main
“DC”
“Manual” * * * * * 2 each 800A 65kA @480V 800A Main
“DD”
“Automatic” 2 “A” “J”, “K”
“500”, “50M”
“A” 2 each 800A 65kA @480V 800A Main
“DD”
“Manual” * * * * * 2 each 800A 65kA @480V 1600A Main
“DE”
“Automatic” 2 “A” “F” “500”, “50M”
“A” 2 each 800A 65kA @480V 1600A Main
“DE”
“Manual” * * * * * 3 each 800A 65kA @480V 1600A Main
“DF”
“Automatic” 3 “A” “F” “500”, “50M”
“A” 3 each 800A 65kA @480V 1600A Main
“DF”
“Manual” * * * * * 3 each 800A 65kA @480V 2000A Main
“DG”
“Automatic” 3 “A” “E” “500”, “50M”
“A” 3 each 800A 65kA @480V 2000A Main
“DG”
“Manual” * * * * * 4each 800A 65kA @480V 2000A Main
“DH”
“Automatic” 4 “A” “E” “500”, “50M”
“A” 4 each 800A 65kA @480V 2000A Main
“DH”
“Manual” * * * * * 4 each 800A 65kA @480V 2500A Main
“DJ”
“Automatic” 4 “A” “D” “500”, “50M”
“A” 4 each 800A 65kA @480V 2500A Main
“DJ”
“Manual” * * * * * 5 each 800A 65kA @480V 2500A Main
“DK”
“Automatic” 5 “A” “D” “500”, “50M”
“A” 4 each 800A 65kA @480V 2500A Main
“DK”
“Manual” * * * * * 2 each 800A 100kA @480V 800A Main
“DL”
“Automatic” 2 “B” “J”, “K”
“500”, “50M”
“A” 2 each 800A 100kA @480V 800A Main
“DL”
“Manual” * * * * * 2 each 800A 100kA @480V 1600A Main
“DM”
Page 59 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 2 “B” “F” “500”, “50M”
“A” 2 each 800A 100kA @480V 1600A Main
“DM”
“Manual” * * * * * 3 each 800A 100kA @480V 1600A Main
“DN”
“Automatic” 3 “B” “F” “500”, “50M”
“A” 3 each 800A 100kA @480V 1600A Main
“DN”
“Manual” * * * * * 3 each 800A 100kA @480V 2000A Main
“DP”
“Automatic” 3 “B” “E” “500”, “50M”
“A” 3 each 800A 100kA @480V 2000A Main
“DP”
“Manual” * * * * * 4 each 800A 100kA @480V 2000A Main
“DR”
“Automatic” 4 “B” “E” “500”, “50M”
“A” 4 each 800A 100kA @480V 2000A Main
“DR”
“Manual” * * * * * 4 each 800A 100kA @480V 2500A Main
“DS”
“Automatic” 4 “B” “D” “500”, “50M”
“A” 4 each 800A 100kA @480V 2500A Main
“DS”
“Manual” * * * * * 5 each 800A 100kA @480V 2500A Main
“DT”
“Automatic” 5 “B” “D” “500”, “50M”
“A” 5 each 800A 100kA @480V 2500A Main
“DT”
“Manual” * * * * * 2 each 800A 35kA @600V 800A Main
“DU”
“Automatic” 2 “D” “J”, “K”
“626”, “62M”
“3”, “B” 2 each 800A 35kA @600V 800A Main
“DU”
“Manual” * * * * * 2 each 800A 35kA @600V 1600A Main
“DV”
“Automatic” 2 “D” “F” “626”, “62M”
“3”, “B” 2 each 800A 35kA @600V 1600A Main
“DV”
“Manual” * * * * * 3 each 800A 35kA @600V 2000A Main
“DW”
“Automatic” 3 “D” “F” “626”, “62M”
“3”, “B” 3 each 800A 35kA @600V 2000A Main
“DW”
“Manual” * * * * * 3 each 800A 35kA @600V 2000A Main
“DX”
“Automatic” 3 “D” “E” “626”, “62M”
“3”, “B” 3each 800A 35kA @600V 2000A Main
“DX”
“Manual” * * * * * 4 each 800A 35kA @600V 2000A Main
“DY”
“Automatic” 4 “D” “E” “626”, “62M”
“3”, “B” 4 each 800A 35kA @600V 2000A Main
“DY”
“Manual” * * * * * 4 each 800A 35kA @600V 2500A Main
“DZ”
“Automatic” 4 “D” “D” “626”, “62M”
“B” 4 each 800A 35kA @600V 2500A Main
“DZ”
“Manual” * * * * * 5 each 800A 35kA @600V 2500A Main
“EA”
“Automatic” 5 “D” “D” “626”, “62M”
“B” 5 each 800A 35kA @600V 2500A Main
“EA”
Page 60 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 4 each 800A 35kA @600V 3000A Main
“EB”
“Automatic” 4 “D” “C” “626”, “62M”
“3” 4 each 800A 35kA @600V 3000A Main
“EB”
“Manual” * * * * * 5 each 800A 35kA @600V 3000A Main
“EC”
“Automatic” 5 “D” “C” “626”, “62M”
“3” 5 each 800A 35kA @600V 3000A Main
“EC”
“Manual” * * * * * 2 each 800A 65kA @600V 800A Main
“ED”
“Automatic” 2 “E” “J”, “K”
“626”, “62M”
“3”, “B” 2 each 800A 65kA @600V 800A Main
“ED”
“Manual” * * * * * 2 each 800A 65kA @600V 1600A Main
“EE”
“Automatic” 2 “E” “F” “626”, “62M”
“3”, “B” 2 each 800A 65kA @600V 1600A Main
“EE”
“Manual” * * * * * 3 each 800A 65kA @600V 1600A Main
“EF”
“Automatic” 3 “E” “F” “626”, “62M”
“3”, “B” 3 each 800A 65kA @600V 1600A Main
“EF”
“Manual” * * * * * 3 each 800A 65kA @600V 2000A Main
“EG”
“Automatic” 3 “E” “E” “626”, “62M”
“3”, “B” 3each 800A 65kA @600V 2000A Main
“EG”
“Manual” * * * * * 4 each 800A 65kA @600V 2000A Main
“EH”
“Automatic” 4 “E” “E” “626”, “62M”
“3”, “B” 4 each 800A 65kA @600V 2000A Main
“EH”
“Manual” * * * * * 4 each 800A 65kA @600V 2500A Main
“EJ”
“Automatic” 4 “E” “D” “626”, “62M”
“B” 4 each 800A 65kA @600V 2500A Main
“EJ”
“Manual” * * * * * 5 each 800A 65kA @600V 2500A Main
“EK”
“Automatic” 5 “E” “D” “626”, “62M”
“B” 5 each 800A 65kA @600V 2500A Main
“EK”
“Manual” * * * * * 4 each 800A 65kA @600V 3000A Main
“EL”
“Automatic” 4 “E” “C” “626”, “62M”
“3” 4 each 800A 65kA @600V 3000A Main
“EL”
“Manual” * * * * * 5 each 800A 65kA @600V 3000A Main
“EM”
“Automatic” 5 “E” “C” “626”, “62M”
“3” 5 each 800A 65kA @600V 3000A Main
“EM”
“Manual” * * * * * 2 each 700A 65kA @600V 800A Main
“EN”
“Automatic” 2 “A” “J”, “K”
“400” “A” 2each 700A 65kA @600V 800A Main
“EN”
“Manual” * * * * * 2 each 700A 65kA @600V 1600A Main
“EP”
Page 61 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 2 “A” “F” “400” “A” 2 each 700A 65kA @600V 1600A Main
“EP”
“Manual” * * * * * 3 each 700A 65kA @600V 1600A Main
“ER”
“Automatic” 3 “A” “F” “400” “A” 3 each 700A 65kA @600V 1600A Main
“ER”
“Manual” * * * * * 4 each 700A 65kA @600V 1600A Main
“ES”
“Automatic” 4 “A” “F” “400” “A” 4 each 700A 65kA @600V 1600A Main
“ES”
“Manual” * * * * * 4 each 700A 65kA @600V 2000A Main
“ET”
“Automatic” 4 “A” “E” “400” “A” 4 each 700A 65kA @600V 2000A Main
“ET”
“Manual” * * * * * 5 each 700A 65kA @600V 2000A Main
“EU”
“Automatic” 5 “A” “E” “400” “A” 5 each 700A 65kA @600V 2000A Main
“EU”
“Manual” * * * * * 2 each 700A 100kA @480V 800A Main
“EV”
“Automatic” 2 “B” “J”, “K”
“400” “A” 2each 700A 100kA @480V 800A Main
“EV”
“Manual” * * * * * 2 each 700A 100kA @480V 1600A Main
“EW”
“Automatic” 2 “B” “F” “400” “A” 2 each 700A 100kA @480V 1600A Main
“EW”
“Manual” * * * * * 3 each 700A 100kA @480V 1600A Main
“EX”
“Automatic” 3 “B” “F” “400” “A” 3 each 700A 100kA @480V 1600A Main
“EX”
“Manual” * * * * * 4 each 700A 100kA @480V 1600A Main
“EY”
“Automatic” 4 “B” “F” “400” “A” 4 each 700A 100kA @480V 1600A Main
“EY”
“Manual” * * * * * 4 each 700A 100kA @480V 2000A Main
“EZ”
“Automatic” 4 “B” “E” “400” “A” 4 each 700A 100kA @480V 2000A Main
“EZ”
“Manual” * * * * * 5 each 700A 100kA @480V 2000A Main
“FA”
“Automatic” 5 “B” “E” “400” “A” 5 each 700A 100kA @480V 2000A Main
“FA”
“Manual” * * * * * 2 each 700A 35kA @600V 800A Main
“FB”
“Automatic” 2 “D” “J”, “K”
“500”, “50M”
“3”, “B” 2 each 700A 35kA @600V 800A Main
“FB”
“Manual” * * * * * 2 each 700A 35kA @600V 1600A Main
“FC”
“Automatic” 2 “D” “F” “500”, “50M”
“3”, “B” 2 each 700A 35kA @600V 1600A Main
“FC”
Page 62 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 3 each 700A 35kA @600V 1600A Main
“FD”
“Automatic” 3 “D” “F” “500”, “50M”
“3”, “B” 3 each 700A 35kA @600V 1600A Main
“FD”
“Manual” * * * * * 4 each 700A 35kA @600V 1600A Main
“FE”
“Automatic” 4 “D” “F” “500”, “50M”
“3”, “B” 4 each 700A 35kA @600V 1600A Main
“FE”
“Manual” * * * * * 4 each 700A 35kA @600V 2000A Main
“FF”
“Automatic” 4 “D” “F” “500”, “50M”
“3”, “B” 4 each 700A 35kA @600V 2000A Main
“FF”
“Manual” * * * * * 5 each 700A 35kA @600V 2000A Main
“FG”
“Automatic” 5 “D” “E” “500”, “50M”
“B” 5 each 700A 35kA @600V 2000A Main
“FG”
“Manual” * * * * * 4 each 700A 35kA @600V 2500A Main
“FH”
“Automatic” 4 “D” “D” “500”, “50M”
“3” 4 each 700A 35kA @600V 2500A Main
“FH”
“Manual” * * * * * 5 each 700A 35kA @600V 2500A Main
“FJ”
“Automatic” 5 “D” “D” “500”, “50M”
“3” 5 each 700A 35kA @600V 2500A Main
“FJ”
“Manual” * * * * * 2 each 700A 65kA @600V 800A Main
“FK”
“Automatic” 2 “E” “J”, “K”
“500”, “50M”
“3”, “B” 2 each 700A 65kA @600V 800A Main
“FK”
“Manual” * * * * * 2 each 700A 65kA @600V 1600A Main
“FL”
“Automatic” 2 “E” “F” “500”, “50M”
“3”, “B” 2 each 700A 65kA @600V 1600A Main
“FL”
“Manual” * * * * * 3 each 700A 65kA @600V 1600A Main
“FM”
“Automatic” 3 “E” “F” “500”, “50M”
“3”, “B” 3 each 700A 65kA @600V 1600A Main
“FM”
“Manual” * * * * * 4 each 700A 65kA @600V 1600A Main
“FN”
“Automatic” 4 “E” “F” “500”, “50M”
“3”, “B” 4 each 700A 65kA @600V 1600A Main
“FN”
“Manual” * * * * * 4 each 700A 65kA @600V 2000A Main
“FP”
“Automatic” 4 “E” “F” “500”, “50M”
“B” 4 each 700A 65kA @600V 2000A Main
“FP”
“Manual” * * * * * 5 each 700A 65kA @600V 2000A Main
“FR”
“Automatic” 5 “E” “E” “500”, “50M”
“B” 5 each 700A 65kA @600V 2000A Main
“FR”
“Manual” * * * * * 4 each 700A 65kA @600V 2500A Main
“FS”
Page 63 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 4 “E” “D” “500”, “50M”
“3” 4 each 700A 65kA @600V 2500A Main
“FS”
“Manual” * * * * * 5 each 700A 65kA @600V 2500A Main
“FT”
“Automatic” 5 “E” “D” “500”, “50M”
“3” 5 each 700A 65kA @600V 2500A Main
“FT”
“Manual” * * * * * 2 each 600A 35kA @600V 600A Main
“FU”
“Automatic” 2 “D” “L”, “M”
“40A” “3” 2 each 600A 35kA @600V 600A Main
“FU”
“Manual” * * * * * 2 each 600A 35kA @600V 1200A Main
“FV”
“Automatic” 2 “D” “G”, “H”
“40A” “B” 2 each 600A 35kA @600V 1200A Main
“FV”
“Manual” * * * * * 3 each 600A 35kA @600V 1200A Main
“FW”
“Automatic” 3 “D” “G”, “H”
“40A” “B” 3 each 600A 35kA @600V 1200A Main
“FW”
“Manual” * * * * * 4 each 600A 35kA @600V 1600A Main
“FX”
“Automatic” 3 “D” “F” “40A” “B” 4 each 600A 35kA @600V 1600A Main
“FX”
“Manual” * * * * * 4 each 600A 35kA @600V 1600A Main
“FY”
“Automatic” 4 “D” “F” “40A” “B” 4 each 600A 35kA @600V 1600A Main
“FY”
“Manual” * * * * * 5 each 600A 35kA @600V 1600A Main
“FZ”
“Automatic” 5 “D” “F” “40A” “B” 5 each 600A 35kA @600V 1600A Main
“FZ”
“Manual” * * * * * 2 each 600A 65kA @600V 600A Main
“GA”
“Automatic” 2 “E” “L”, “M”
“40A” “B” 2 each 600A 65kA @600V 600A Main
“GA”
“Manual” * * * * * 2 each 600A 65kA @600V 1200A Main
“GB”
“Automatic” 2 “E” “G”, “H”
“40A” “B” 2 each 600A 65kA @600V 1200A Main
“GB”
“Manual” * * * * * 3 each 600A 65kA @600V 1200A Main
“GC”
“Automatic” 3 “E” “G”, “H”
“40A” “B” 3 each 600A 65kA @600V 1200A Main
“GC”
“Manual” * * * * * 4 each 600A 65kA @600V 1600A Main
“GD”
“Automatic” 3 “E” “F” “40A” “B” 4 each 600A 65kA @600V 1600A Main
“GD”
“Manual” * * * * * 4 each 600A 65kA @600V 1600A Main
“GE”
“Automatic” 4 “E” “F” “40A” “B” 4 each 600A 65kA @600V 1600A Main
“GE”
Page 64 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 5 each 600A 65kA @600V 1600A Main
“GF”
“Automatic” 5 “E” “F” “40A” “B” 5 each 600A 65kA @600V 1600A Main
“GF”
“Manual” * * * * * 2 each 500A 65kA @480V 600A Main
“GG”
“Automatic” 2 “A” “L”, “M”
“300” “A” 2 each 500A 65kA @480V 600A Main
“GG”
“Manual” * * * * * 2 each 500A 65kA @480V 1000A Main
“GH”
“Automatic” 2 “A” “H” “300” “A” 2 each 500A 65kA @480V 1000A Main
“GH”
“Manual” * * * * * 3 each 500A 65kA @480V 1200A Main
“GJ”
“Automatic” 3 “A” “H” “300” “A” 3 each 500A 65kA @480V 1200A Main
“GJ”
“Manual” * * * * * 4 each 500A 65kA @480V 1600A Main
“GK”
“Automatic” 3 “A” “F” “300” “A” 4 each 500A 65kA @480V 1600A Main
“GK”
“Manual” * * * * * 4 each 500A 65kA @480V 1600A Main
“GL”
“Automatic” 4 “A” “F” “300” “A” 4 each 500A 65kA @480V 1600A Main
“GL”
“Manual” * * * * * 5 each 500A 65kA @480V 1600A Main
“GM”
“Automatic” 5 “A” “F” “300” “A” 5 each 500A 65kA @480V 1600A Main
“GM”
“Manual” * * * * * 2 each 500A 100kA @480V 600A Main
“GN”
“Automatic” 2 “B” “L”, “M”
“300” “A” 2 each 500A 100kA @480V 600A Main
“GN”
“Manual” * * * * * 2 each 500A 100kA @480V 1000A Main
“GP”
“Automatic” 2 “B” “H” “300” “A” 2 each 500A 100kA @480V 1000A Main
“GP”
“Manual” * * * * * 3 each 500A 100kA @480V 1200A Main
“GR”
“Automatic” 3 “B” “H” “300” “A” 3 each 500A 100kA @480V 1200A Main
“GR”
“Manual” * * * * * 4 each 500A 100kA @480V 1600A Main
“GS”
“Automatic” 3 “B” “F” “300” “A” 4 each 500A 100kA @480V 1600A Main
“GS”
“Manual” * * * * * 4 each 500A 100kA @480V 1600A Main
“GT”
“Automatic” 4 “B” “F” “300” “A” 4 each 500A 100kA @480V 1600A Main
“GT”
“Manual” * * * * * 5 each 500A 100kA @480V 1600A Main
“GU”
Page 65 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 5 “B” “F” “300” “A” 5 each 500A 100kA @480V 1600A Main
“GU”
“Manual” * * * * * 2 each 500A 35kA @600V 600A Main
“GV”
“Automatic” 2 “D” “L”, “M”
“40A” “B” 2 each 500A 35kA @600V 600A Main
“GV”
“Manual” * * * * * 2 each 500A 35kA @600V 1000A Main
“GW”
“Automatic” 2 “D” “G”, “H”
“40A” “B” 2 each 500A 35kA @600V 1000A Main
“GW”
“Manual” * * * * * 3 each 500A 35kA @600V 1200A Main
“GX”
“Automatic” 3 “D” “G”, “H”
“40A” “B” 3 each 500A 35kA @600V 1200A Main
“GX”
“Manual” * * * * * 4 each 500A 35kA @600V 1600A Main
“GY”
“Automatic” 3 “D” “F” “40A” “B” 4 each 500A 35kA @600V 1600A Main
“GY”
“Manual” * * * * * 4 each 500A 35kA @600V 1600A Main
“GZ”
“Automatic” 4 “D” “F” “40A” “B” 4 each 500A 35kA @600V 1600A Main
“GZ”
“Manual” * * * * * 5 each 500A 35kA @600V 1600A Main
“HA”
“Automatic” 5 “D” “F” “40A” “B” 5 each 500A 35kA @600V 1600A Main
“HA”
“Manual” * * * * * 2 each 500A 65kA @600V 600A Main
“HB”
“Automatic” 2 “E” “L”, “M”
“40A” “B” 2 each 500A 65kA @600V 600A Main
“HB”
“Manual” * * * * * 2 each 500A 65kA @600V 1000A Main
“HC”
“Automatic” 2 “E” “G”, “H”
“40A” “B” 2 each 500A 65kA @600V 1000A Main
“HC”
“Manual” * * * * * 3 each 500A 65kA @600V 1200A Main
“HD”
“Automatic” 3 “E” “G”, “H”
“40A” “B” 3 each 500A 65kA @600V 1200A Main
“HD”
“Manual” * * * * * 4 each 500A 65kA @600V 1600A Main
“HE”
“Automatic” 3 “E” “F” “40A” “B” 4 each 500A 65kA @600V 1600A Main
“HE”
“Manual” * * * * * 4 each 500A 65kA @600V 1600A Main
“HF”
“Automatic” 4 “E” “F” “40A” “B” 4 each 500A 65kA @600V 1600A Main
“HF”
“Manual” * * * * * 5 each 500A 65kA @600V 1600A Main
“HG”
“Automatic” 5 “E” “F” “40A” “B” 5 each 500A 65kA @600V 1600A Main
“HG”
Page 66 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 2 each 400A 65kA @480V 400A Main
“HH”
“Automatic” 2 “A” “N”, “P”
“250” “A” 2 each 400A 65kA @480V 400A Main
“HH”
“Manual” * * * * * 2 each 400A 65kA @480V 800A Main
“HJ”
“Automatic” 2 “A” “J”, “K”
“250” “A” 2 each 400A 65kA @480V 800A Main
“HJ”
“Manual” * * * * * 3 each 400A 65kA @480V 800A Main
“HK”
“Automatic” 3 “A” “J”, “K”
“250” “A” 3 each 400A 65kA @480V 800A Main
“HK”
“Manual” * * * * * 3 each 400A 65kA @480V 1200A Main
“HL”
“Automatic” 3 “A” “G”, “H”
“250” “A” 3 each 400A 65kA @480V 1200A Main
“HL”
“Manual” * * * * * 4each 400A 65kA @480V 1200A Main
“HM”
“Automatic” 4 “A” “G”, “H”
“250” “A” 4 each 400A 65kA @480V 1200A Main
“HM”
“Manual” * * * * * 4 each 400A 65kA @480V 1600A Main
“HN”
“Automatic” 4 “A” “F” “250” “A” 4 each 400A 65kA @480V 1600A Main
“HN”
“Manual” * * * * * 5 each 400A 65kA @480V 1600A Main
“HP”
“Automatic” 5 “A” “F” “250” “A” 4 each 400A 65kA @480V 1600A Main
“HP”
“Manual” * * * * * 2 each 400A 100kA @480V 400A Main
“HR”
“Automatic” 2 “B” “N”, “P”
“250” “A” 2 each 400A 100kA @480V 400A Main
“HR”
“Manual” * * * * * 2 each 400A 100kA @480V 800A Main
“HS”
“Automatic” 2 “B” “J”, “K”
“250” “A” 2 each 400A 100kA @480V 800A Main
“HS”
“Manual” * * * * * 3 each 400A 100kA @480V 800A Main
“HT”
“Automatic” 3 “B” “J”, “K”
“250” “A” 3 each 400A 100kA @480V 800A Main
“HT”
“Manual” * * * * * 3 each 400A 100kA @480V 1200A Main
“HU”
“Automatic” 3 “B” “G”, “H”
“250” “A” 3 each 400A 100kA @480V 1200A Main
“HU”
“Manual” * * * * * 4each 400A 100kA @480V 1200A Main
“HV”
“Automatic” 4 “B” “G”, “H”
“250” “A” 4 each 400A 100kA @480V 1200A Main
“HV”
“Manual” * * * * * 4 each 400A 100kA @480V 1600A Main
“HW”
Page 67 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 4 “B” “F” “250” “A” 4 each 400A 100kA @480V 1600A Main
“HW”
“Manual” * * * * * 5 each 400A 100kA @480V 1600A Main
“HX”
“Automatic” 5 “B” “F” “250” “A” 4 each 400A 100kA @480V 1600A Main
“HX”
“Manual” * * * * * 2 each 400A 35kA @600V 400A Main
“HY”
“Automatic” 2 “D” “N”, “P”
“30A” “3”, “B” 2 each 400A 35kA @600V 400A Main
“HY”
“Manual” * * * * * 2 each 400A 35kA @600V 800A Main
“HZ”
“Automatic” 2 “D” “J”, “K”
“30A” “3”, “B” 2 each 400A 35kA @600V 800A Main
“HZ”
“Manual” * * * * * 2 each 400A 35kA @600V 800A Main
“JA”
“Automatic” 3 “D” “J”, “K”
“30A” “3”, “B” 2 each 400A 35kA @600V 800A Main
“JA”
“Manual” * * * * * 3 each 400A 35kA @600V 1200A Main
“JB”
“Automatic” 3 “D” “G”, “H”
“30A” “3”, “B” 3 each 400A 35kA @600V 1200A Main
“JB”
“Manual” * * * * * 4 each 400A 35kA @600V 1200A Main
“JC”
“Automatic” 4 “D” “G”, “H”
“30A” “3”, “B” 4 each 400A 35kA @600V 1200A Main
“JC”
“Manual” * * * * * 4 each 400A 35kA @600V 1600A Main
“JD”
“Automatic” 4 “D” “F” “30A” “B” 4 each 400A 35kA @600V 1600A Main
“JD”
“Manual” * * * * * 5 each 400A 35kA @600V 1600A Main
“JE”
“Automatic” 5 “D” “F” “30A” “B” 5 each 400A 35kA @600V 1600A Main
“JE”
“Manual” * * * * * 2 each 400A 65kA @600V 400A Main
“JF”
“Automatic” 2 “E” “N”, “P”
“30A” “3”, “B” 2 each 400A 65kA @600V 400A Main
“JF”
“Manual” * * * * * 2 each 400A 65kA @600V 800A Main
“JG”
“Automatic” 2 “E” “J”, “K”
“30A” “3”, “B” 2 each 400A 65kA @600V 800A Main
“JG”
“Manual” * * * * * 2 each 400A 65kA @600V 800A Main
“JH”
“Automatic” 3 “E” “J”, “K”
“30A” “3”, “B” 2 each 400A 65kA @600V 800A Main
“JH”
“Manual” * * * * * 3 each 400A 65kA @600V 1200A Main
“JJ”
“Automatic” 3 “E” “G”, “H”
“30A” “3”, “B” 3 each 400A 65kA @600V 1200A Main
“JJ”
Page 68 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Manual” * * * * * 4 each 400A 65kA @600V 1200A Main
“JK”
“Automatic” 4 “E” “G”, “H”
“30A” “3”, “B” 4 each 400A 65kA @600V 1200A Main
“JK”
“Manual” * * * * * 4 each 400A 65kA @600V 1600A Main
“JL”
“Automatic” 4 “E” “F” “30A” “B” 4 each 400A 65kA @600V 1600A Main
“JL”
“Manual” * * * * * 5 each 400A 65kA @600V 1600A Main
“JM”
“Automatic” 5 “E” “F” “30A” “B” 5 each 400A 65kA @600V 1600A Main
“JM”
“Manual” * * * * * 2 each 350A 35kA @600V 400A Main
“JN”
“Automatic” 2 “D” “N”, “P”
“25A” “3”, “B” 2 each 350A 35kA @600V 400A Main
“JN”
“Manual” * * * * * 2 each 350A 35kA @600V 800A Main
“JP”
“Automatic” 2 “D” “J”, “K”
“25A” “3”, “B” 2 each 350A 35kA @600V 800A Main
“JP”
“Manual” * * * * * 2 each 350A 35kA @600V 800A Main
“JR”
“Automatic” 3 “D” “J”, “K”
“25A” “3”, “B” 2 each 350A 35kA @600V 800A Main
“JR”
“Manual” * * * * * 3 each 350A 35kA @600V 1200A Main
“JS”
“Automatic” 3 “D” “G”, “H”
“25A” “3”, “B” 3 each 350A 35kA @600V 1200A Main
“JS”
“Manual” * * * * * 4 each 350A 35kA @600V 1200A Main
“JT”
“Automatic” 4 “D” “G”, “H”
“25A” “3”, “B” 4 each 350A 35kA @600V 1200A Main
“JT”
“Manual” * * * * * 4 each 350A 35kA @600V 1600A Main
“JU”
“Automatic” 4 “D” “F” “25A” “3”, “B” 4 each 350A 35kA @600V 1600A Main
“JU”
“Manual” * * * * * 5 each 350A 35kA @600V 1600A Main
“JV”
“Automatic” 5 “D” “F” “25A” “3”, “B” 5 each 350A 35kA @600V 1600A Main
“JV”
“Manual” * * * * * 2 each 350A 65kA @600V 400A Main
“JW”
“Automatic” 2 “E” “N”, “P”
“25A” “3”, “B” 2 each 350A 65kA @600V 400A Main
“JW”
“Manual” * * * * * 2 each 350A 65kA @600V 800A Main
“JX”
“Automatic” 2 “E” “J”, “K”
“25A” “3”, “B” 2 each 350A 65kA @600V 800A Main
“JX”
“Manual” * * * * * 2 each 350A 65kA @600V 800A Main
“JY”
Page 69 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” 3 “E” “J”, “K”
“25A” “3”, “B” 2 each 350A 65kA @600V 800A Main
“JY”
“Manual” * * * * * 3 each 350A 65kA @600V 1200A Main
“JZ”
“Automatic” 3 “E” “G”, “H”
“25A” “3”, “B” 3 each 350A 65kA @600V 1200A Main
“JZ”
“Manual” * * * * * 4 each 350A 65kA @600V 1200A Main
“KA”
“Automatic” 4 “E” “G”, “H”
“25A” “3”, “B” 4 each 350A 65kA @600V 1200A Main
“KA”
“Manual” * * * * * 4 each 350A 65kA @600V 1600A Main
“KB”
“Automatic” 4 “E” “F” “25A” “3”, “B” 4 each 350A 65kA @600V 1600A Main
“KB”
“Manual” * * * * * 5 each 350A 65kA @600V 1600A Main
“KC”
“Automatic” 5 “E” “F” “25A” “3”, “B” 5 each 350A 65kA @600V 1600A Main
“KC”
Title: BIB Ratingo On | No BIBo On | Available BIB
Business Rules:
1. There is no default.2. Selection is manual. 3. If “Available BIB” is selected, then digits 10 and 11 are the same as digits 8 and 9.4. If “No BIB” is selected, then digits 10 and 11are “00”.
Title: RIB Ratingo On | No RIB
Business Rules:
1. There is no default.2. Selection is manual. If selected, digit 12 and 13 = “00”
Title: Optionso On | Noneo On | Key Interlock
Page 70 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | EPOo On | one “Key Interlock” and “EPO”
Business Rules:
1. The default is “0”.2. A selection is required.
Part Number Table:
Selection Selection for digit 14
None “0”Key Interlock “1”EPO “3”one “Key Interlock” and “EPO”
“6”
Title: ManufacturerBusiness Rules:
1. Default is always “2”.2. A selection is not required.
Digit 15= “2”
Digit 16=N default
Digit 17=N default
Digit 18=N default
Digit 19=N default
Digit 20=N default
Digit 21=N default
Digit 22=N default
Title: Custom SPG SwitchgearTitle: Factory Test SPG
o On | Drop Shipo On | Test with UPS
Page 71 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Business Rules:
1. There is no default.2. A selection is required.
Title: SPG Sectionso Quantity | 0o Quantity | 1o …o Quantity | 20
Business Rules:
1. The default is “0”.2. A selection is not required. 3. Selection available is “0” through “20” if “Factory Test SPG” is “Test with UPS”
Title: SPG Drawout Breakers Shipped Separatelyo Quantity | 0o Quantity | 1o …o Quantity | 20
Business Rules:
1. The default is “0”.2. A selection is not required. 3. Selection available is “0” through “20” if “Factory Test SPG” is “Test with UPS”
Title: Custom System Paralleling Switchgearo Checkbox | Noo Checkbox | Yes
Business Rules:
1. The default is “No”.2. Selection is manual. 3. If “No” is selected, hide the next section.
Title: Custom System Paralleling Switchgear detailso Input | Part Numbero Input | Descriptiono Input | Price
Business Rules:
1. There is no default.2. Selection is manual and input.
Page 72 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
3. Repeat this section until the user selects “no” for “Custom System Paralleling Switchgear”
Title: Custom Switchgear o Checkbox | Noo Checkbox | Yes
Business Rules:
1. The default is “No”.2. Selection is manual. 3. If “No” is selected, hide the next section.
Title: Custom Switchgear Detailso Input | Part Numbero Input | Descriptiono Input | Price
Business Rules:
1. There is no default.2. Selection is manual and input. 3. Repeat this section until the user selects “no” for “Custom Switchgear”
Tab: “UPS Module”, Sub-Tab: “Module Spare Parts”Title: Module Spare Parts Level
o On | A Basico On | B Intermediateo On | C Comprehensiveo On | D International Depoto On | F Fuses and Air Filters
Business Rules:
1. There is no default.2. Selection is required. 3. Digit 15 = selection (A, B, C, D, F)
Title: Module Spare Partso On | 0o On | 1o On | 2o On | 3 o On | 4o On | 5o On | 6
Business Rules:
Page 73 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1. “0” is the default.2. Selection is not required.
Filtering Table:
Manual or Automatic SelectionManual “1”Manual “2”Manual “3”Manual “4”Manual “5”Manual “6”Manual “7”Manual “8”Manual “9”
Digits 1, 2, 3, 4 are always “40SK”
Title: System Configuration Type
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digit 4 Selection for digits 5, 6
“A” “SA”“N”, “R” “SN”“M” “MM”
Title: Nominal Rating (KVA)
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digits 5, 6, 7
Description Model type identifier digit 7, 8
Page 74 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
and 9250 “250 kVA /225kW” “250”25A “25A kVA /225 kW ” “25A”300 “300 kVA /270 kW” “300”30A “30A kVA /270 kW” “30A”400 “400 kVA /360 kW” “400”40A “400 kVA /360 kW” “40A”500 “500 kVA /450 kW” “500”50M “500 kVA /500 kW” “50M”626 “625 kVA /562.5 kW” “626”62M “625 kVA /625 kW” “62M”750 “750 kVA /675 kW” “750”75M “750 kVA /750 kW” “75M”11M, 12M “1100 kVA /1100kW” “11M”
Title: UPS Voltage Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module digit 8
Available Selection
Selection for digit 10
“A” “480V” “A”“3” “575V” “3” “B” “600V” “B”
Part Number Definition:
1. Digit 11, 12, 13, 14, 16, 17, 18, 19, 20, 21, 22 =”N”.
Note that digit 15 is selected at the beginning of this section.
If Module digit 4 = “M” display next section otherwise hide.
Tab: “SCC”, Sub-Tab: “Main Unit”Screen Layout:
Title: Number of Modules in Fully Configured System
Page 75 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 1o On | 2o On | 3o On | 4 o On | 5o On | 6
Business Rules:
1. There is no default.2. A selection is required.
Filtering Table:
Module Quantity
Selection
1 “1”1, 2 “2”1, 2, 3 “3”1, 2, 3, 4 “4”1, 2, 3, 4, 5 “5”1, 2, 3, 4, 5, 6 “6”
Title: Select Ratingo On | Automatico On | Manual
Business Rules:
1. The default is “Automatic”.2. A selection is not required.
Digits 1, 240 NXL
Title: Redundant System____o Checkbox | Redundanto Checkbox | Non-redundant
Business Rules:
1. There is no default.2. A selection is required.
Page 76 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Filtering Table:
Number of Modules in Fully configured System
Available
2, 3, 4, 5, 6 “Yes”1, 2, 3, 4, 5, 6 “No”
Digits 1 and 2 = “40”
Digits 3 and 4 = “CD”
Title: SCC Rating o On | 1600Ao On | 2000Ao On | 2500Ao On | 3000Ao On | 3200Ao On | 4000Ao On | 5000A
Business Rules:
1. There is no default.2. A selection is required.
Filtering Table:
Select Rating Digit 4
Number of Modules in Fully Configured System
Redundant System
Module Digit 5
Module Digit 9
Selection Selection for digit 5 and 6
“Manual” * * * * * “1600A” “16”“Automatic” * “2” “Yes” “5” “A”,
“3”, “B”
“1600A” “16”
“Automatic” * “2” “No” “5” “A”, “3”, “B”
“1600A” “16”
“Automatic” * “2” “No” “6” “A”, “1600A “16”
Page 77 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“3”, “B”
“Automatic” * “3” “Yes” “5” “A”, “3”, “B”
“1600A “16”
“Automatic” * “3” “Yes” “6” “A”, “3”, “B”
“1600A” “16”
“Automatic” * “4” “Yes” “5” “3”, “B”
“1600A” “16”
“Automatic” * “4” “Yes” “5” “3”, “B”
“1600A” “16”
“Automatic” * “3” “No” “5” “3”, “B”
“1600A” “16”
“Automatic” * “3” “No” “5” “3”, “B”
“1600A “16”
“Manual” * * * * * “2000A” “20”“Automatic” * “2” “No” “7” “A” “2000A” “20”“Automatic” * “3” “Yes” * * “2000A” “20”“Automatic” * “3” “No” “5” “A” “2000A” “20”“Automatic” * “3” “No” “6” “A”
“B”“2000A” “20”
“Automatic” * “4” “Yes” “5” “A” “2000A” “20”“Automatic” * “4” “Yes” “6” “A”
“B”“2000A” “20”
“Automatic” * “4” “No” * * “2000A” “20”“Automatic” * “5” “Yes” “5” “B” “2000A” “20”“Manual” * * * * * “2500A” “25”“Automatic” * “3” * * * “2500A” “25”“Automatic” * “3” “Yes” “1” “3”,
“B”“2500A” “25”
“Automatic” * “2” “No” “1” “3”, “B”
“2500A” “25”
“Automatic” * “4” “Yes” * * “2500A” “25”“Automatic” * “3” “No” “6” “A” “2500A” “25”“Automatic” * “4” “Yes” “6” “A” “2500A” “25”“Automatic” * “4” “Yes” “7” “3”,
“B”“2500A” “25”
“Automatic” * “3” “No” “7” “3”, “B”
“2500A” “25”
“Automatic” * “5” “Yes” * * “2500A” “25”“Automatic” * “4” “No” “5” “A”,
“3”“2500A” “25”
“Automatic” * “4” “No” “6” “B” “2500A” “25”“Automatic” * “6” “Yes” * * “2500A” “25”“Automatic” * “5” “No” “5” “B” “2500A” “25”“Manual” * * * * * “3000A” “30”“Automatic” * “2” “No” “1” “A” “3000A” “30”“Automatic” * “3” “Yes” “1” “A” “3000A” “30”
Page 78 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Automatic” * “4” “Yes” “7” “A”, “3000A” “30”“Automatic” * “3” “No” “7” “A”, “3000A” “30”“Automatic” * “5” “Yes” “6” “A” “3000A” “30”“Automatic” * “4” “No” “6” “A” “3000A” “30”“Automatic” * “5” “Yes” “7” “B” “3000A” “30”“Automatic” * “6” “No” “7” “B” “3000A” “30”“Automatic” * “6” “Yes” “5” “3” “3000A” “30”“Automatic” * “5” “No” “5” “3” “3000A” “30”“Automatic” * “6” “No” “5” “B” “3000A” “30”“Manual” * * * * * “3200A” “32”“Automatic” “D” “4” “Yes” * * “3200A” “32”“Automatic” * “3” “No” “1” “B” “3200A” “32”“Automatic” * “4” “Yes” “1” “B” “3200A” “32”“Automatic” * “4” “No” “7” “3”, “3200A” “32”“Automatic” * “4” “No” “7” “3”, “3200A” “32”“Automatic” * “5” “Yes” “6” “A” “3200A” “32”“Automatic” * “5” “Yes” “6” “A” “3200A” “32”“Automatic” * “5” “No” “5” “A” “3200A” “32”“Automatic” * “5” “No” “6” “A”,
“B”“3200A” “32”
“Automatic” * “6” “Yes” “5” “A” “3200A” “32”“Automatic” * “6” “Yes” “6” “A”,
“B”“3200A” “32”
“Automatic” * “6” “No” “5” “3” “3200A” “32”“Manual” * * * * * “4000A” “40”“Automatic” “C” “4” “Yes” * * “4000A” “40”“Automatic” * “3” “No” “1” “A”,
“3”, “B”
“4000A” “40”
“Automatic” * “4” “Yes” “1” “A”, “3”, “B”
“4000A” “40”
“Automatic” * “5” “Yes” “6” “A” “4000A” “40”
“Automatic” * “4” “No” “6” “A” “4000A” “40”
“Automatic” * “5” “Yes” “7” “A”, “3”
“4000A” “40”
“Automatic” * “4” “No” “7” “A” , “3”
“4000A” “40”
“Automatic” * “5” “No” “5” “A” “4000A” “40”“Automatic” * “6” “Yes” “5” “A” “4000A” “40”“Automatic” * “5” “No” “6” “A”,
“3”, “B”
“4000A” “40”
“Automatic” * “6” “Yes” “5” “A”, “3”, “B”
“4000A” “40”
“Automatic” * “5” “No” “7” “3”, “4000A” “40”
Page 79 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“B”“Automatic” * “6” “Yes” “7” “3”,
“B”“4000A” “40”
“Automatic” “D” “4” “Yes” * * “4000A” “40”“Automatic” * “6” “No” “5” “A”,
“3”“4000A” “40”
“Automatic” * “6” “No” “6” “3”, “B”
“4000A” “40”
“Manual” * * * * * “5000A” “50”“Automatic” “D” “6” “Yes” * * “5000A” “50”“Automatic” * “5” “Yes” “1” “3”,
“B”“5000A” “50”
“Automatic” * “4” “No” “1” “3”, “B”
“5000A” “50”
“Automatic” * “6” “Yes” “7” “A” “5000A” “50”“Automatic” * “5” “No” “7” “A” “5000A” “50”“Automatic” * “6” “No” “6” “A” “5000A” “50”“Automatic” * “6” “No” “7” “3”,
“B”“5000A” “50”
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Digit 4 Module Digit 10
Digit 5 and 6 Selection for digit 7
“D” “A” “16”, “20”, “25”, “30”, “”32”, “40”, “50”
“H”
“D” “3”, “B” “16”, “20”, “25”, “30”, “”32”, “40”
“H”
“D” “3”, “B” “50” “J”
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Number of Modules in Fully Configured
Selection for digit 8
Page 80 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
System“1” “1”“2” “2”“3” “3”“4” “4”“5” “5”“6” “6”
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digit 10
Selection Assigned to digit 9
“A” “480 V” “A”“3” “575 V” “3”“B” “600 V” “B”
Title: System Breaker Configuration o On | BFB, SBBo On | BFB o On | BFB, SBB, UOBo On | BFB, UOB
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module Quantity
Digit 4 Module Digit 12
System Breaker Configuration
Selection for digit 10
“0” * * “BFB, SBB” “A”
* “D” * “BFB, SBB” “A”
* “C” “A”, “G”, “H”, “J”
“BFB, SBB” “A”
“0” * * “BFB” “C”* “D” * “BFB” “C”* “C” “A”, “G”,
“H”, “J”“BFB” “C”
Page 81 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“0” * * “BFB, SBB, UOB”
“E”
* “D” * “BFB, SBB, UOB”
“E”
* “C” “A”, “G”, “H”, “J”
“BFB, SBB, UOB”
“E”
“0” * * “BFB, UOB” “G”* “D” * “BFB, UOB” “G”
* “C” “A”, “G”, “H”, “J”
“BFB, UOB” “G”
Title: MBP Configurationo On | Noneo On | MBB & MIB with separate input for bypass and MBP o On | MBB & MIB with single input for bypass and MBP
Business Rules:
1. “None” is the default.2. Selection is manual.
Filtering Table:
Selection Selection for digit 11
None “A”MBB & MIB with separate input for bypass and MBP
“B”
MBB & MIB with single input for bypass and MBP
“C”
Title: Other System Breakers o On | Noneo On | MOBo On | MOB, LBBo On | IOB o On | IOB, LBBo On | LBB
Business Rules:
1. The default is “none”.2. A selection is not required.
Filtering Table:
Page 82 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Module Quantity
Module Digit 12
Other System Breakers
Selection for digit 12
* * “None” “A”
“0” “A”, “B”, “G”
“MOB” “B”
“0” “A”, “B”, “G”
“MOB, LBB”
“C”
“0” “H”, “J” “IOB” “D”
“0” “H”, “J” “IOB, LBB” “E”
* * “LBB” “F”
Digit 13 = N
Title: Customer Interface Boards
o o On | Programmable Relay Board (Qty 1) (A)o On | Input Contact Isolator Board (Qty 1) (B)o On | 1 "A" and 1 "B"o On | 2 "A"o On | 2 "B"o On | 2 "A" and 1 "B"o On | 1 "A" and 2 "B"o On | 2 "A" and 2 "B"o On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Part Number Definition:
1. Digit 14 may be A, B, C, D, E, F, G, H, or N in the model type identifier.
Filtering Table:
Available Selection for digit 14
Programmable Relay Board (Qty 1) (A) “A” Input Contact Isolator Board (Qty 1) (B) “B” 1 "A" and 1 "B" “C” 2 "A" “D” 2 "B" “E”
Page 83 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2 "A" and 1 "B" “F” 1 "A" and 2 "B" “G” 2 "A" and 2 "B" “H” None “N”
Title: HMI Options
o On | Emergency Module Offo On | Display Keylocko On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Part Number Definition:
1. Digit 15 may be E, K or N in the model type identifier.
Filtering Table:
Manual or Automatic
Available Selection for digit 15
Manual Emergency Module Off “E”Manual Display Keylock “K”Manual None “N”
Title: System Interfaceso On | Noneo On | Power Tie Interface
Business Rules:
1. Selection is automatic.
Filtering Table:
Manual or Automatic
Available Module digit 15
Selection for digit 16
Automatic Digital Load “B” “B”
Page 84 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Bus Sync Interface
Manual PowerTie “N” “C”Automatic PowerTie and
DLBS Interface
“D” “D”
Manual None “N” “N”
Title: Monitoring Cardso On | Web Intellislot Card (Qty 1) (“A”)o On | MODBUS 485 Intellislot Card (Qty 1) (“B”)o On | MODBUS IP (Qty 1) “(C”)o On | Sitescan 4 Intellislot Card (Qty 1) (“D”)o On | 1 "A" and "B"o On | 1 "A" and "C”o On | 1 "A" and "D"o On | 1 "B" and "C"o On | 1 "B" and "D"o On | 1 "C" and "D"o On | 1 "A", "B" and "C"o On | 1 "A", "B" and "D" o On | 1 "A", "C" and "D”o On | 1 "B", "C" and "D"o On | 1 "A", "B", "C" and "D"o On | None
Business Rules:
1. The default is “N”.2. A selection is not required.
Part Number Definition:
1. Digit 17 may be A, B, C, D, E, F, G, H, J, K, L, M, P, R, S or N in the model type identifier.
Filtering Table:
Available Selection for digit 17
Web Intellislot Card (Qty 1) “A”MODBUS 485 Intellislot Card (Qty 1) “B”MODBUS IP (Qty 1) “C”Sitescan 4 Intellislot Card (Qty 1) “D”1 "A" and "B" “E”
Page 85 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1 "A" and "C” “F”1 "A" and "D" “G”1 "B" and "C" “H”1 "B" and "D" “J” 1 "C" and "D" “K” 1 "A", "B" and "C" “L” 1 "A", "B" and "D" “M” 1 "A", "C" and "D” “P”1 "B", "C" and "D" “R”1 "A", "B", "C" and "D" “S”None “N”
Title: Energy Optimization Mode
Business Rules:
1. The default is “N”.2. Selection is automatic.
Part Number Definition:
1. Digit 18 may be A, B, C, D, E or N in the model type identifier.
Filtering Table:
Digit 4 Available for Digit 18“R”, “N” or “M” “A”, “B”, “C”, “D”, “E”, “F”, “N”“A” “A”, “C”, “D”, “N”
Filtering Table:
Available Module digit 17
Selection for digit 18
Ecomode Operation A “A”
Intelligent Paralleling Operation
B “B”
HRG Capability C “C”
1 "A" and "C" D “D”
1 "B" and "C" E “E”
None N “N”
Title: Optional Power Supply
Page 86 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o Checkbox | Optional Power SupplyBusiness Rules:
1. There is no default.2. A selection is required.
Filtering Table:
SelectionFalse Bypass this section (Hide all entries)True Continue with this section
Title: RASP Power Supply
Business Rules:
1. The default is “N”.2. A selection is not required. 3. Digit 19 is “N” unless Site Installed Options "Remote Alarm Status Panel - Surface
Mounted" = Yes or "Remote Alarm Status Panel - Flush Mounted" = Yes, then it is “P”
Part Number Definition:
1. Digit 19 may be P or N in the model type identifier.
Title: HarnessesBusiness Rules:
1. Selection is automatic.
Filtering Table:
Digit 11 Selection for Digit 20
“B”, “C” “A”“A” “N”
Digit 21 = N
Digit 22 = N
Page 87 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “SCC”, Sub-Tab: “Site Installed Options”Title: Site Installed Options
o Checkbox | Remote Alarm Status PanelBusiness Rules:
1. Selection is manual. If not checked, hide the remainder of the section.
Title: Mounting__________o On | Remote Alarm Status Panel - Surface Mountedo On | Remote Alarm Status Panel - Flush Mounted
Business Rules:
1. Hide unless checkbox is selected.2. There is no default.3. Selection is manual.
Filtering Table:
Digit 19 Selection Part Number“P” “S” “NXLRAS”“P” “F” “NXLRASF”
Title: Floor Crane Quantityo Checkbox | Beech B-2000 series straddle crane 2000 LBS capacity
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Digit 4 Digit 5 Selection“D” “1”, “2”, “3” “NXL5KLIFTB”“D” “4”, “5” “NXL5KLIFTB”
Tab: “SCC”, Sub-Tab: “Buyout SCC (Switchgear)”Title: SCC Sections
o On | 0o On | 1o On | 2o On | 3 o On | 4o On | 5o On | 6o On | 7
Page 88 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 8o On | 9o On | 10o On | 11o On | 12o On | 13 o On | 14o On | 15o On | 16o On | 17o On | 18o On | 19o On | 20
Business Rules:
1. There is no default.2. Selection is required.
Title: SCC Drawout Breakers o Quantity | 0 through 20
Business Rules:
1. There is no default.2. Selection is required. Possible selections are “0” through “20.”
Title: Switchgear Manufacturer---o On | ASCOo On | Commercial Switchgearo On | Cutler-Hammero On | GEo On | Othero On | Russelectrico On | Siemenso On | SquareD
Business Rules:
1. There is no default.2. Selection is required.
Title: Custom Bypass Switchgear o Checkbox | Noo Checkbox | Yes
Business Rules:
1. The default is “No”.
Page 89 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2. Selection is manual.
Filtering Table:
SCC Quantity Digit 4 Selection
“1” “D” “1”
“0” “D” “0”
Title: Custom Switchgear o Checkbox | Noo Checkbox | Yes
Business Rules:
4. The default is “No”.5. Selection is manual. 6. If “No” is selected, hide the next section.
Title: Custom Switchgear Detailso Input | Part Number – Type (string), max length 50o Input | Description - Type (string), max length 4000o Input | Price - Type (decimal), min 0, max 1,000,000
Business Rules:
1. There is no default.2. Selection is manual and input. 3. “Custom Switchgear” should be a looping control.
Tab: “SCC”, Sub-Tab: “SCC Spare Parts”
Title: SCC Spare Parts Quantityo Quantity | 0 through 6
Business Rules:
1. “0” is the default.2. Selection is not required. 3. Any number from “0” to “6” is allowed.
Page 90 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: SCC Spare Parts Levelo On | A Basico On | B Intermediateo On | C Comprehensiveo On | D International Depoto On | F Fuses and Filters
Business Rules:
1. If quantity is zero, hide.2. There is no default.3. Selection is required.
Filtering Table:
Level SCC digit 4
SCC digit 5
SCC digit 9
Selection Part Number
“A” “D” 1, 2, 3
“A” “1” 40CD32HXAXXXSKA
“A” “D” 1, 2, 3
“3”, “B”
“1” 40CD30HXAXXXSKA
“A” “D” 4, 5 “A” “1” 40CD50HXAXXXSKA“A” “D” 4, 5 “3”,
“B”“1” 40CD40HXAXXXSKA
“A” “D” 1, 2, 3
“A” “2” 40CD32HXAXXXSKB
“A” “D” 1, 2, 3
“3”, “B”
“2” 40CD30HXAXXXSKB
“A” “D” 4, 5 “A” “2” 40CD50HXAXXXSKB“A” “D” 4, 5 “3”,
“B”“2” 40CD40HXAXXXSKB
“A” “D” 1, 2, 3
“A” “3” 40CD32HXAXXXSKC
“A” “D” 1, 2, 3
“3”, “B”
“3” 40CD30HXAXXXSKC
“A” “D” 4, 5 “A” “3” 40CD50HXAXXXSKC“A” “D” 4, 5 “3”,
“B”“3” 40CD40HXAXXXSKC
“A” “D” 1, 2, 3
“A” “4” 40CD32HXAXXXSKD
“A” “D” 1, 2, 3
“3”, “B”
“4” 40CD30HXAXXXSKD
“A” “D” 4, 5 “A” “4” 40CD50HXAXXXSKD“A” “D” 4, 5 “3”,
“B”“4” 40CD40HXAXXXSKD
“A” “D” 1, 2, 3
“A” “5” 40CD32HXAXXXSKF
“A” “D” 1, 2, 3
“3”, “B”
“5” 40CD30HXAXXXSKF
Page 91 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“A” “D” 4, 5 “A” “5” 40CD50HXAXXXSKF“A” “D” 4, 5 “3”,
“B”“5” 40CD40HXAXXXSKF
Tab: “PTC”, Sub-Tab: “Main Unit”Screen Layout:
Title: Power Tie Basic Unit (First Unit)o Quantity | Main Unit Quantity
Business Rules:
1. The default is “0”.2. Selection is manual. Available selection is “0” or “1”.
Filtering Table:
Manual or Automatic
Module Quantity
Module Digit 4 Module Digit 15
Available Selection
Manual 1 “A” “C”, “D”
“1”
Manual * “R”, “S”, “M” * “1”
Digits 1 and 2: always 40
Title:System Typeo On | Ring (Open) (Max. 2 systems)o On | Star
Business Rules:
1. There is no default.2. Selection is manual. 3. Hide remainder of section if quantity = “0”
Filtering Table:
Selection Selection for digits 3 and 4Ring (Open) (Max. 2 systems) “PR”Star “PS”
Title:Breaker Packageo On | SIB, TIE, MBB, MIB, LBBo On | SIB, TIE, MBB, MIBo On | SIB, TIE, MBB, LBBo On | SIB, TIE, MBB
Page 92 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | SIB, TIE, LBBo On | SIB, TIE
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Available Selection for digit 5
SIB, TIE, MBB, MIB, LBB “A”SIB, TIE, MBB, MIB “B”SIB, TIE, MBB, LBB “C”SIB, TIE, MBB “D”SIB, TIE, LBB “E”SIB, TIE “F”
Title:Electrical Interlocko On | Noneo On | MBB, MIB, LBBo On | MBB, MIBo On | SIB, MBB, LBBo On | SIB, MBBo On | SIB, LBB
Business Rules:
1. The default is “A”.2. Selection is manual.
Filtering Table:
Digit 5 Available Selection for digit 6
* None “N”“A” MBB, MIB,
LBB“A”
“B” MBB, MIB “B”
Page 93 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“C” SIB, MBB, LBB
“C”
“D” SIB, MBB “D”“E” SIB, LBB “E”
Business Rules:
1. Selection is automatic.
Filtering Table:
Manual or Automatic
Module Digit 10
Selection for digit 7
Automatic “A” “A”Automatic “3” “3”Automatic “B” “B”
Filtering Table:
Module “Quantity”
Buyout SPG Digits 5, 6, 7, 8
SCC Digits 5, 6, 7
Module Digit 4
Module Digit 5
Module Digit 10
Selection for digits 8, 9 and 10
* “0300”, ”0350”, “0400”
* * * * “400”
* * * “A” “2” * “400”* * * “A” “3” “3”,
“B”“400”
* “0500”, “0600”
* * * * “600”
* * * “A” “3” “A” “600”* * * “A” “4” “3”,
“B”“600”
* “0700”, “0800”
* * * * “800”
* * * “A” “4” “A” “800”* * * “A” “5” * “800”* * * “A” “6” “3”,
“B”“800”
* “1000” * * * * “10M”* * * “A” “6” “A” “10M”* * * “A” “7” “3”,
“B”“10M”
* “1200” * * * * “12M”* * “12M”,
“12H”* * * “12M”
* * * “A” “7” “A” “12M”
Page 94 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“1600” * * * * “16M”* * “16M”,
“16H”* * * “16M”
* * * “A” “1” “3”, “B”
“16M”
* “2000” * * * * “20M”* * “20M”,
“20H”* * * “20M”
* * “A” “1” “A” “20M”“2500” * * * * “25M”
* * “25M”, “25H”
* * * “25M”
* “3000” * * * * “30M”* * “30M”,
“30H”* * * “30M”
* “32H” * * * * “32M”* “4000” * * * * “40M”* * “40H” * * * “40M”* * “50H”,
“50J”* * * “50M”
Title:PT Controls Mountingo On | First system including HMIo On | Additional system mounted in same cabineto On | Additional system mounted in different cabinet
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Selection for digit 11
First system including HMI “A”Additional system mounted in same cabinet
“B”
Additional system mounted in different cabinet
“C”
Page 95 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Digit 12= A
Digit 13 = N
Digit 14 = N
Digit 15 = N
Title: Customer Interface Boards o On | Programmable Relay Board (Qty 1) (A)o On | Input Contact Isolator Board (Qty 1) (B)o On | 1 "A" and 1 "B"o On | 2 "A" o On | 2 "B"o On | 2 "A" and 1 "B"o On | 1 "A" and 2 "B"o On | 2 "A" and 2 "B"o On | None
Business Rules:
1. The default is “N”.2. Selection is manual.
Filtering Table:
Select if digit 11 Available Selection for Digit 16
“A” Programmable Relay Board (Qty 1) “A”“A” Input Contact Isolator Board (Qty 1) “B”“A” 1 "A" and 1 "B" “C”“A” 2 "A" “D”“A” 2 "B" “E”“A” 2 "A" and 1 "B" “F”“A” 1 "A" and 2 "B" “G”“A” 2 "A" and 2 "B" “H”* None “N”
Title: Monitoring Cards o On | Web Intellislot Card (Qty 1) (A)o On | MODBUS 485 Intellislot Card (Qty 1) (B)o On | MODBUS IP (Qty 1) (C)
Page 96 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | Sitescan 4 Intellislot Card (Qty 1) (D)o On | 1 "A" and "B"o On | 1 "A" and "C"o On | 1 "A" and "D"o On | 1 "B" and "C"o On | 1 "B" and "D"o On | 1 "C" and "D"o On | 1 "A", "B" and "C" o On | 1 "A", "B" and "D"o On | 1 "A", "C" and "D"o On | 1 "B", "C" and "Do On | 1 "A", "B", "C" and "D"o On | None
Business Rules:
1. The default is “N”.2. Selection is manual.
Filtering Table:
Select if digit 11
Available Selection for digit 17
“A” Web Intellislot Card (Qty 1) (A)
“A”
“A” MODBUS 485 Intellislot Card (Qty 1) (B)
“B”
“A” MODBUS IP (Qty 1) (C)
“C”
“A” Sitescan 4 Intellislot Card (Qty 1) (D)
“D”
“A” 1 "A" and "B" “E”“A” 1 "A" and "C" “F”“A” 1 "A" and "D" “G”“A” 1 "B" and "C" “H”“A” 1 "B" and "D" “J”“A” 1 "C" and "D" “K”“A” 1 "A", "B" and "C" “L”“A” 1 "A", "B" and "D" “M”“A” 1 "A", "C" and "D" “P”“A” 1 "B", "C" and "D “R”“A” 1 "A", "B", "C" and
"D"“S”
* None “N”
Page 97 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Digit 18 = N
Digit 19 = N
Digit 20 = N
Digit 21 = N
Tab: “Batt Cab”, Sub-Tab: “Main Unit”Screen Layout:
Title: Matching Battery Cabinet Basic Unit o Checkbox | Battery System Monitor = “Yes”o Checkbox | Battery System Monitor = “No”
Business Rules:
1. There is no default.2. Selection is required.
If “Battery System Monitor” = “No”, display with Z = “No”. If “No”, then the Cabinet Model Number digit 4 is “P” unless the Battery Model number begins with “16”, then digit 4 is “Q”.
If “Battery System Monitor” = “Yes”, display with Z = “Yes”. If “Yes”, then the Cabinet Model Number digit 4 is “A” unless the Battery Model number begins with “16”, then digit 4 is “B”.
Filtering Table:
Module digit 5, 6, 7
kW (X)
250 250300 300400 400500 50050U 500625 62562U 625750 75075U 75011U 110012U 1125
Get appropriate “minutes/selection list” from Minutes Table, “ugly table – Z”, “Selection Table”. “Selection” column in Minutes Table is summarized as “Possible Selections” in Selection Table.
Page 98 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Ugly table “No” (P and Q) and “Yes” (A and B) differ in Part Number fourth digit only.
Title: Matching Battery Cabinet Basic Unit for X kWo On | Minutes, Cabinets, Battery Model, Description, Cabinet model numbero On | repeat for each value in selection table “Possible Selection” (seventh)
columnWhere:
Minutes “Minutes Table” column for module digit 5, 6, 7Cabinets “Ugly Table - Z” Cabinets (second) columnBattery Model “Ugly Table - Z” Battery Model (third) columnDescription “Ugly Table - Z” Description (fourth) columnCabinet Model Number
“Ugly Table - Z” Generic Cabinet Model Number (fifth) column plus
module digits 5, 6, 7 (column1 ) of “Selection Table” as digits 5, 6, 7
Part Number Completion Table:
Cabinet Model Number
“Ugly Table” Generic Cabinet Model
Number (fifth) column plus module digits 5,
6, 7 (column1 ) of “Selection Table” as digits 5, 6, 7
Repetition Complete one part number for each unit in “Ugly Table” “Cabinets Quantity” (second) column with the next-to-last digit (14) corresponding to the increasing cabinet number (1, 2, 3, 4, 5, 6). Digits 13 and 15 are always “N”.
Selection Table
Module digit 5, 6, 7
Cabinet model number digit 5, 6, 7
Breaker Connection Battery System Monitor
Load kW Possible Sequence Number (order is important)
250 250 B, C L, R, S, C “Z” 225 1-14, 16- 30300 300 B, C L, R, S, C “Z” 270 2-31
400 400 B, C L, S, C “Z” 360 8-16, 18,17, 19-31
500 500 B, C L, S, C “Z” 450 4, 12, 13-15, 18, 16, 19-31
50U 500 B L, S “Z” 500 12-15, 18, 16, 19-31
625 625 B, C L, S, C “Z” 625 15, 14, 18, 16, 17, 19-31, 33
62U 625 B, C L, S, C “Z” 625 15, 14, 16, 20, 35, 21-31
Page 99 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
750 750 B, C L, S, C “Z” 675 34, 17, 20, 35, 23-31
75U 750 B, C L, S, C “Z” 750 35, 34, 23, 30, 25, 27, 26, 28-31
11U 11U B, C S, C “Z” 1100 28-33
12U 12U B, C S, C “Z” 1125 28-33
Ugly Table – (4th digit in Cabinet Model Number)
Seq
uenc
e N
umbe
r
Cab
inet
Q
uant
ity
Battery Model Description Generic Cabinet Model Number
Price (000)
1 2 HX300-FR 112.6” x 33.5” 40B?___XPX2BN1N 242 2 27HR3500 112.6” x 33.5” 40B?___XRA2BN1N 253 2 HX330-FR 112.6” x 33.5” 40B?___XRX2BN1N 274 2 31HR4000 112.6” x 33.5” 40B?___XUA2BN1N 285 2 HX400-FR 112.6” x 33.5” 40B?___XUX2BN1N 306 1 16HX800F-FR 63.8” x 33.5” 40B?___X2K1BN1N 627 1 16HX925F-FR 63.8” x 33.5” 40B?___X4K1BN1N 678 2 31HR5000 112.6” x 33.5” 40B?___XWA2BN1N 339 2 HX505-FR 112.6” x 33.5” 40B?___XWX2BN1N 3610 2 HX540-FR 112.6” x 33.5” 40B?___XXX2BN1N 3711 3 31HR4000 168.9” x 33.5” 40B?___XUA3BN1N 2812 3 HX400-FR 168.9” x 33.5” 40B?___XUX3BN1N 3013 3 31HR5000 168.9” x 33.5” 40B?___XWA3BN1N 3314 3 HX505-FR 168.9” x 33.5” 40B?___XWX3BN1N 3615 4 31HR4000 168.9” x 33.5” 40B?___XUA4BN1N 2816 3 HX540-FR 168.9” x 33.5” 40B?___XXX3BN1N 3717 5 27HR3500 281.5” x 33.5” 40B?___XRA5BN1N 2518 2 16HX800F-FR 127.4” x 33.5” 40B?___X2K2BN1N 6219 2 16HX925F-FR 127.4” x 33.5” 40B?___X4K2BN1N 6720 4 31HR5000 225.2” x 33.5” 40B?___XWA5BN1N 3321 4 HX505-FR 225.2” x 33.5” 40B?___XWX4BN1N 3622 4 HX540-FR 225.2” x 33.5” 40B?___XXX4BN1N 3723 5 31HR5000 281.5” x 33.5” 40B?___XWA5BN1N 3324 3 16HX800F-FR 191.4” x 33.5” 40B?___X2K3BN1N 6225 5 HX505-FR 281.5” x 33.5” 40B?___XWX5BN1N 3626 5 HX540-FR 281.5” x 33.5” 40B?___XXX5BN1N 3727 3 16HX925F-FR 191.4” x 33.5” 40B?___X4K3BN1N 6728 4 16HX800F-FR 254.8” x 33.5” 40B?___X2K4BN1N 6229 4 16HX925F-FR 254.8” x 33.5” 40B?___X4K4BN1N 6730 5 16HX800F-FR 318.8” x 33.5” 40B?___X2K5BN1N 6231 5 16HX925F-FR 318.8” x 33.5” 40B?___X4K5BN1N 6732 6 16HX800F-FR 382.8” x 33.5” 40B?___X2K6BN1N 62
Page 100 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
33 6 16HX925F-FR 382.8” x 33.5” 40B?___X4K6BN1N 6734 4 HX400-FR 225.2” x 33.5” 40B?___XUX4BN1N 3035 5 31HR4000 281.5” x 33.5” 40B?___XUA5BN1N 33
Minutes Table
250 300 400 500 50UMinutes Sequence
NumberMinutes Sequence
NumberMinutes Sequence
NumberMinutes Sequence
NumberMinutes Sequence
Number
6 1 5 2 5 8 6 4 5 127 2 6 3 7 9 6 12 5 138 3 7 4 8 10 8 13 8 1410 4 7 5 9 11 10 14 8 1510 5 6 6 9 12 10 15 7 1810 6 9 7 13 13 10 18 9 1613 7 10 8 14 14 11 16 10 1914 8 12 9 14 15 13 19 11 2016 9 13 10 15 16 14 20 13 2117 10 14 11 15 18 15 21 14 2218 11 14 12 15 17 17 22 17 2318 12 20 13 19 19 20 23 17 2426 13 21 14 20 20 20 24 18 2527 14 21 15 21 21 21 25 20 2628 16 22 16 22 22 22 26 20 2728 17 22 17 27 23 23 27 26 2831 18 23 18 28 24 31 28 30 2935 19 27 19 28 25 35 29 35 3037 20 31 20 31 26 39 30 39 3138 21 32 21 33 27 46 31 X X39 22 33 22 39 28 X X X X49 23 39 23 47 29 X X X X51 24 40 24 53 30 X X X X52 25 40 25 63 31 X X X X56 26 41 26 X X X X X X74 27 47 27 X X X X X X80 28 61 28 X X X X X X99 29 68 29 X X X X X X107 30 78 30 X X X X X XX X 90 31 X X X X X X
625 62U 750 75U 11U
Page 101 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Minutes Sequence Number
Minutes Sequence Number
Minutes Sequence Number
Minutes Sequence Number
Minutes Sequence Number
6 15 5 15 5 34 5 35 6 286 14 5 14 5 17 6 34 8 296 18 5 16 6 20 7 23 10 307 16 7 20 7 35 7 30 14 317 17 8 35 10 23 10 25 15 328 19 9 21 10 24 10 27 18 339 20 10 22 12 25 11 26 X X10 21 11 23 13 26 14 28 X X11 22 12 24 13 27 18 29 X X12 23 13 25 17 28 20 30 X X14 24 14 26 20 29 23 31 X X14 25 15 27 23 30 X X X X15 26 19 28 27 31 X X X X17 27 22 29 X X X X X X18 28 27 30 X X X X X X22 29 31 31 X X X X X X26 30 X X X X X X X X31 31 X X X X X X X X35 33 X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X XX X X X X X X X X X
12UMinutes Sequence
Number
5 288 2910 3013 3114 3218 33X XX X
Page 102 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Digits 1 2, and 3: always 40B NXL
Title: Cabinet Type
Business Rules:
1. Selection is automatic.
Filtering Table:
“Battery System Monitor”
Digits 9, 10 Selection for digit 4
“No” PX, RX, UX, XX, RA, UA, WA
“P”
“Yes” PX, RX, UX, XX, RA, UA, WA
“A”
“No” 2K, 4K “Q”“Yes” 2K, 4K “B”
Title: UPS Module Rating
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Digit 5, 6, 7
Selection for digit 5, 6 and 7
“250”, “25A” “250”“300”, “30A” “300”“400”, “40A” “400”“500” “500”“50M” “50U”“626” “626”“62M” “62U”“750” “750”“75M” “75U”“11M” “11U”Business Rules:
1. Digit 8 is “X”.
Page 103 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Battery Model
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Battery Model Selection for digits 9 and 10
HX300-FR “PX”HX330-FR “RX”HX400-FR “UX”HX505-FR “WX”HX540-FR “XX”16HX800F-FR “2K”16HX925F-FR “4K”27HR3500 “RA”31HR4000 “UA”31HR5000 “WA”
Title: Cabinet Quantity
Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Cabinets Selection for digit 11
“1” “1”“2” “2”“3” “3”“4” “4”“5” “5”“6” “6”“7” “7”“8” “8”
Title: Breaker Type o On | Circuit Breaker (MBD)
Page 104 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | Circuit Breaker with Motor Operator (MBD)
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module digit 19 Available Selection for digit 12
“A”, “B”, “C”, “N” Circuit Breaker (MBD) “B”“E”, “F”, “G”, “H” Circuit Breaker with Motor Operator (MBD) “M”
Title: Connection o On | Left Connected to Moduleo On | Right Connected to Module o On | Stand Alone Individual Cabinetso On | Stand Alone Interconnected Cabinets
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Module Digit 5 Selection for digit 13
“2”, “3”, “4”, “5”, “6”, “7”
“L”
“2”, “3”, “4” “R”
* “S”
* “C”
Digit 14 = N (Reserved for Cabinet Line Item)
Digit 15 = N
Digit 16 = N
Digit 17 = N
Page 105 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Digit 18 = N
Digit 19 = N
Digit 20 = N
Digit 21 = N
Tab: “Batt Cab”, Sub-Tab: “Site Installed Options”Screen Layout:
Title: Battery Cabinet Field Installed Options (QTY per Battery Systemt)o Quantity | Battery Cabinet Floor Anchors
Business Rules:
1. The default is “0”.2. Selection is manual.
Filtering Table:
Battery Cabinet Digit 11
Selection for Battery Cabinet Floor Anchors Quantity
“1” “1”“2” “2”“3” “3”“4” “4”“5” “5”“6” “6”Business Rules:
1. There is no default.2. Selection is automatic.
Filtering Table:
Module Floor Anchors OSHPOD
Battery Cabinet Digits 4
Selection for Battery Cabinet Floor Anchors Part Number
“No” “P”, “A” “NXLFATTBC”“No” “Q”, “B” “NXLFAFTBC”“Yes” “P”, “A” “NXLOSHTTBC”“Yes” “Q”, “B” “NXLOSHFTBC”
Page 106 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Battery Junction Cabineto Quantity | Battery Junction Cabinet
Business Rules:
1. The default is “0”.2. Selection is manual or automatic.
Filtering Table:
Battery Cabinet digit 13
Module digit 5
Battery Cabinet Digit 13
Selection
“C” 5, 6, 7, 1 * “1”* * “S” “1”
Title: Mounto On | Lefto On | Righto On | Stand Alone
Business Rules:
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Battery Cabinet Digit 13
Selection Available
“C” “Left”“C” “Right”“S” “Stand
Alone”
Business Rules:
1. There is no default.2. Selection is automatic.
Part Number Logic:
Mount Module Digit 5
Battery Cabinet Digits 4
Battery Cabinet Digit 13
Selection for Part Number
“Left” “5” “P”, “A” “C” “40JC500NC”
“Right” “5” “P”, “A” “C” “40JC500ND”
Page 107 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“Left” “5” “Q”, “B” “C” “40JC500PC”
“Right” “5” “Q”, “B” “C” “40JC500PD”
“Right” “2”, “3”, “4”, “5”
* “S” “40JC500NS”
“Left” “6”, “7” “P”, “A” “C” “40JC750NC”
“Right” “6”, “7” “P”, “A” “C” “40JC750ND”
“Left” “6”, “7” “Q”, “B” “C” “40JC750PC”
“Right” “6”, “7” “Q”, “B” “C” “40JC750PD”
* “6”, “7” * “S” “40JC750NS”
“Left” “1” “Q”, “B” “C” “40JC11UPC”
“Right” “1” “Q”, “B” “C” “40JC11UPD”
* “1” * “S” “40JC11UNS”
Business Rules:
1. The default is “0”.2. Selection is automatic if
a. Battery Junction Cabinet Quantity is “1”, and b. Battery Cabinet Floor Anchor Quantity is “1” through “6” .
Part Number Selection:
Floor Anchors OSHPOD
Junction Cabinet Selection
* * NXLFANJC* * NXLFAPJC
* * NXLFAWJC
“No” 40JC500NS, 40JC750NS, 40JC11UNS
NXLFAWJC
“Yes” 40JC500NC, 40JC500ND, 40JC750NC, 40JC750ND
NXLOSHNJC
“Yes” 40JC500PC, 40JC500PD, 40JC750PC, 40JC750PD, 40JC11UPC, 40JC11UPD
NXLOSHPJC
“Yes” 40JC500NS, 40JC750NS, 40JC11UNS
NXLOSHWJC
Page 108 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Rear Cabinet Alignment Kit
o On | 0, 1o On | 0, 2o On | 0, 3o On | 0, 4o On | 0, 5o On | 0, 6
Business Rules:
1. The default is “0”.2. Selection is manual. 3. NXLRCA is the model type identifier.4. If Module digit 5 = “4”, “5”, “6”, “7” then display this section, otherwise hide.
Filtering Table:
Module “Quantity”
Module Digit 5 Battery Cabinet digit 11
Allowed Selection for Quantity
“1” “4, “5”, “6”, “7” “L” or “R” 1, 0“2” “4, “5”, “6”, “7” “L” or “R” 2, 0“3” “4, “5”, “6”, “7” “L” or “R” 3, 0“4” “4, “5”, “6”, “7” “L” or “R” 4, 0“5” “4, “5”, “6”, “7” “L” or “R” 5, 0“6” “4, “5”, “6”, “7” “L” or “R” 6, 0
NXLRCARear Cabinet Alignment Kit
Tab: “Buy Batt”Screen Layout:
Title: Buyout BatteryTitle: Battery Description
o List | Energy Storage is_______o Text input | Operating time at specified load (100%) _____ minuteso Text input | Operating time at specified load (80%) _____ minuteso Text input | Critical load ____ kWo Text input | Battery load ____kWo Text input | Seismic Requirements SDS ___o List | Seismic Requirements Importance Factor ___
Page 109 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Filtering Table:
Line Item ListEnergy Storage is None, Vented lead acid battery on rack, VRLA battery on rack,
VRLA battery in cabinet, VRLA stackable batterySeismic Requirements Importance Factor ___
“1.0, “1.5”
Business Rules:
1. There is no default.2. Selection is manual.
Title: Battery Systemo List | Battery Vendor: ____________o Text input | Battery Model: ____________o Text input | End volts per cell: ____________o Text input | Number of cells per string: ____________o Text input | Number of strings in parallel: ____o List | Number of cells per jar: ____o List | Quantity of Jars: ____________o List | Container Material: ____________o List | Specific Gravity:_________o Text input | Battery Warranty Years ____ Fullo Text input | Battery Warranty Years ____ Proratedo Text input | Total battery system weight: ____ o Text input | FOB:_______
Filtering Table:
Line Item ListBattery Vendor C&D, East Penn, Enersys, Exide-GNB
Seismic Requirements Importance Factor ___
“1.0, “1.5”
Number of cells per jar 1, 2, 3, 4, 6, 8
Quantity of Jars 30, 40, 60, 80, 120, 240
Container Material standard, flame retardant, SAN, polycarbonate
Specific Gravity 1.215, 1.250, 1.280, 1.300
Page 110 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Battery System in Cabinetso List | Cabinet Vendor: ____________o Text input | Cabinet Model Number: ____________o List | Overcurrent device: ____________o Text input | Trip Amperage ____o List | Auxiliary Switches: _______A/Bo List | Motor Operator: ____o Text input | FOB ________
Filtering Table:
Line Item ListCabinet Vendor C&D, East Penn, Enersys, Exide-GNB, InterPack, alpha numeric field
xxxxxxxxxxxxxxxxx
Overcurrent device Standard MBD (48VDC UVR), BIS, MBD (48VDC ST)
Auxiliary Switches None, 1, 2
Motor Operator None, 120VAC
Title: Battery System Rackso List | Rack Vendor: ____________o List | Rack Tiers: ____________o Text input | Number: ____o Text input | Rack Model: ____o Text input | Dimensions: ____o List | Battery System Layout Attached: ____o List | Center Tap:________o Text input | FOB: ____________
Filtering Table:
Line Item ListRack Vendor C&D, East Penn, Enersys, Exide-GNB, InterPack, alpha numeric field
xxxxxxxxxxxxxxxxx
Rack Tiers 1, 2, 3, 4, 5, 6
Battery System Layout Attached
Yes, No
Center Tap required, not required
Title: Battery Rack Accessories
Page 111 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o List | Rack Accessories Vendor: ____________o Text input | Anchor Bolts Quantity as required Part Number: ____________o Text input | Post Cover Quantity as required Part Number: ________o Text input | Other: ____________ Part Number: ________
Filtering Table:
Line Item ListRack Accessories Vendor
None, C&D, East Penn, Enersys, Exide-GNB, InterPack, alpha numeric field xxxxxxxxxxxxxxxxx
Title: Stackable Battery Systemo Text input | Number: ____________o Text input | Modules in stack: ________o Text input | Dimensions: ________
Title: Spill Containment Accessorieso Text input | Spill Control System Vendor: ____________o Text input | Spill Control Barriers Part Number: ________o Text input | Floor Coating Part Number: ________o Text input | Spill Neutralizing Mats Part Number: ________o Text input | Acid Neutralization Kit (VRLA only)__________o Text input | Other: ____________ Part Number: ________o Text input | FOB: ____________
Filtering Table:
Line Item ListSpill Control System Vendor
C&D, East Penn, Enersys, Environguard, Exide-GNB, InterPack, alpha numeric field xxxxxxxxxxxxxxxxx
Title: BIS Basic Unito On | 1o On | 2o On | 3 o On | 4o On | 5o On | 6o On | 7o On | 8
Page 112 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Business Rules:
1. The default is “0”.2. Selection is manual. 3. If there is no cabinet vendor, then “Available Selection” is equal to the “Number of Strings in
Parallel.”
Title: Pick BIS Rating?o On | Automatico On | Manual
Business Rules:
1. There is no default.2. Selection is manual and required.
Digits 1, 2, 3 = “BIS”
Title: BIS Ratingo On | 250Ao On | 300Ao On | 450A o On | 600Ao On | 700Ao On | 800Ao On | 900Ao On | 1000Ao On | 1200A o On | 1400Ao On | 1600Ao On | 2000Ao On | 2500Ao On | 3000A
Business Rules:
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Page 113 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Pick BIS Rating
Module digits 5, 6, 7
Battery System Racks “Center Tap”
Optimal MCCB
Selection Available
Digits 4, 5, 6, 7, 8
Page 114 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
manual * * * “250A” “02503”automatic * * >=250<300 “250A” “02503”manual * * “300A” “03003”automatic * * >=300<450 “300A” “03003”manual * * “450A” “04503”automatic * * >=450<600 “450A” “04503”manual * * “600A” “06003”automatic * * >=600<700 “600A” “06003”manual 300, 30A, 400,
40A, 500, 50M, 626, 62M, 750, 75M, 11M, 12M
* * “700A” “07003”
automatic * * >=700<800 “700A” “07003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “800A” “08003”
automatic * * >=800<900 “800A” “08003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “900A” “09003”
automatic * * >=900<1000 “900A” “09003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “1000A” “10003”
automatic * * >=1000<1200 “1000A” “10003”manual 500, 50M, 626,
62M, 750, 75M, 11M, 12M
* “1200A” “12003”
automatic * * >=1200<1200 “1400A” “12003”manual 50M, 626,
62M, 750, 75M, 11M, 12M
* “1400A” “14002”
automatic * * >=1400<1600 “1400A” “14002”manual 50M, 626,
62M, 750, 75M, 11M, 12M
“not required”
“1400A” “14003”
automatic * “required” >=1400<1600 “1400A” “14003”manual 626, 62M, 750,
75M, 11M, 12M
* “1600A” “16002”
Page 115 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
automatic * * >=1600<2000 “1600A” “16002”manual 626, 62M, 750,
75M, 11M, 12M
“not required”
“1600A” “16003”
automatic * “required” >=1600<2000 “1600A” “16003”manual 62M, 750,
75M, 11M, 12M
* “2000A” “20002”
automatic * * >=2000<2500 “2000A” “20002”manual 62M, 750,
75M, 11M, 12M
“not required”
“2000A” “20003”
automatic * “required” >=2000<2500 “2000A” “20003”manual 11M, 12M * “2500A” “25002”automatic * * >=2500<3000 “2500A” “25002”manual 11M, 12M “not
required”“2500A” “25003”
automatic * “required” >=2500<3000 “2500A” “25003”manual 11M, 12M * “3000A” “30002”automatic * * >=3000 “3000A” “30002”manual 11M, 12M “not
required”“3000A” “30003”
automatic * “required” >=3000 “3000A” “30003”
Title: Breaker Typeo On | SqD MHL-DC Breakero On | SqD PAL-DC Breakero On | SqD NW-DC Breaker
Business Rules:
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Manual or Auto
Digits 4, 5 Selection Available
Digits 9, 10
Auto 02, 03, 04, 06, 07, 08, 10, 12
SqD MHL-DC Breaker
“MH”
Manual 14, 16, 20, 25
SqD PAL-DC Breaker
“PA”
Manual 14, 16, 20, 25
SqD NW-DC Breaker
“NW”
Auto 30 SqD NW- “NW”
Page 116 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
DC Breaker
Digit 11 = “M”
Title: Enclosureo On | Standardo On | Universal
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Digits 9, 10 Digits 12MH, PA, NW
“S”
PA “U”
Digit 13 = “N”
Digit 14 = “N”
Digit 15 = “N”
Digit 16 = “N”
Digit 17 = “N”
Digit 18 = “N”
Digit 19 = “N”
Digit 20 = “N”
Digit 21 = “N”
Title: MBD Basic UnitTitle: Pick MBD Rating
o On | Automatico On | Manual
Business Rules:
1. There is no default.
Page 117 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2. Selection is manual.
Filtering Table:
Cabinet Vendor
BIS Quantity
Number of Strings in Parallel
Quantity per UPS Module
Not selected * * 1* =>1 * 1* 0 1 1Not selected * * 2* =>1 * 2* 0 2 2Not selected * * 3* =>1 * 3* 0 3 3Not selected * * 4* =>1 * 4* 0 4 4Not selected * * 5* =>1 * 5* 0 5 5Not selected * * 6* =>1 * 6* 0 6 6Not selected * * 7* =>1 * 7* 0 7 7Not selected * * 8* =>1 * 8* 0 8 8
Digits 1, 2, 3=”MBD”
Title: MBD Ratingo On | 250Ao On | 300Ao On | 450A o On | 600Ao On | 700Ao On | 800Ao On | 900Ao On | 1000Ao On | 1200A o On | 1400Ao On | 1600A
Page 118 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | 2000Ao On | 2500Ao On | 3000A
Business Rules:
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Pick BIS Rating
Module digits 5, 6, 7
Battery System Racks “Center Tap”
Optimal MCCB
Selection Available
Digits 4, 5, 6, 7, 8
manual * * * “250A” “02503”automatic * * >=250<300 “250A” “02503”manual * * “300A” “03003”automatic * * >=300<450 “300A” “03003”manual * * “450A” “04503”automatic * * >=450<600 “450A” “04503”manual * * “600A” “06003”automatic * * >=600<700 “600A” “06003”manual 300, 30A, 400,
40A, 500, 50M, 626, 62M, 750, 75M, 11M, 12M
* * “700A” “07003”
automatic * * >=700<800 “700A” “07003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “800A” “08003”
automatic * * >=800<900 “800A” “08003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “900A” “09003”
automatic * * >=900<1000 “900A” “09003”manual 400, 40A, 500,
50M, 626, 62M, 750, 75M, 11M, 12M
* “1000A” “10003”
automatic * * >=1000<1200 “1000A” “10003”manual 500, 50M, 626, * “1200A” “12003”
Page 119 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
62M, 750, 75M, 11M, 12M
automatic * * >=1200<1200 “1400A” “12003”manual 50M, 626,
62M, 750, 75M, 11M, 12M
* “1400A” “14002”
automatic * * >=1400<1600 “1400A” “14002”manual 50M, 626,
62M, 750, 75M, 11M, 12M
“not required”
“1400A” “14003”
automatic * “required” >=1400<1600 “1400A” “14003”manual 626, 62M, 750,
75M, 11M, 12M
* “1600A” “16002”
automatic * * >=1600<2000 “1600A” “16002”manual 626, 62M, 750,
75M, 11M, 12M
“not required”
“1600A” “16003”
automatic * “required” >=1600<2000 “1600A” “16003”manual 62M, 750,
75M, 11M, 12M
* “2000A” “20002”
automatic * * >=2000<2500 “2000A” “20002”manual 62M, 750,
75M, 11M, 12M
“not required”
“2000A” “20003”
automatic * “required” >=2000<2500 “2000A” “20003”manual 11M, 12M * “2500A” “25002”automatic * * >=2500<3000 “2500A” “25002”manual 11M, 12M “not
required”“2500A” “25003”
automatic * “required” >=2500<3000 “2500A” “25003”manual 11M, 12M * “3000A” “30002”automatic * * >=3000 “3000A” “30002”manual 11M, 12M “not
required”“3000A” “30003”
automatic * “required” >=3000 “3000A” “30003”
Title: Breaker Typeo On | SqD MHL-DC Breakero On | SqD PAL-DC Breakero On | SqD NW-DC Breaker
Business Rules:
Page 120 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1. There is no default.2. Selection is manual or automatic.
Filtering Table:
Digits 4, 5 Selection Available
Digits 9, 10
02, 03, 04, 06, 07, 08, 10, 12
SqD MHL-DC Breaker
“MH”
14, 16, 20, 25
SqD PAL-DC Breaker
“PA”
14, 16, 20 SqD NW-DC Breaker
“NW”
30 SqD NW-DC Breaker
“NW”
Title: Operatoro On | Manualo On | Electrical
Business Rules:
1. The default is “M”.2. Selection is manual.
Filtering Table:
Selection Available for “Operator”
Module Digit 19
Selection for Digit 11
“Manual” * “M”“Electrical” “E” “E”“Electrical” “F” “E”“Electrical” “G” “E”“Electrical” “H” “E”
Title: Enclosureo On | Standardo On | Universal
Page 121 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Digits 9, 10 Digit 12PA “S”MH, NW “S”PA “U”
Digit 13 = “N”
Digit 14 = “N”
Digit 15 = “N”
Digit 16 = “N”
Digit 17 = “N”
Digit 18 = “N”
Digit 19 = “N”
Digit 20 = “N”
Digit 21 = “N”
Title: MBD and BIS AccessoriesTitle: BIB Usage
o On | UPS displays per battery string statuso On | UPS displays per battery system status
Business Rules:
1. There is no default.2. Selection is manual or automatic. 3. Selection is automatically “None” if no selections available.
Filtering Table:
MBD Quantity Number of Battery
BIS Quantity Available Selection
Page 122 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Cabinets* 1 through 8 * UPS displays per battery string status1 through 8 * * UPS displays per battery string status* * 1 through 8 UPS displays per battery string status1 * * UPS displays per battery system status
Title: Temperature Sensor Usageo On | Battery temperature compensation neededo On | Battery temperature not measured
Business Rules:
1. The default is “Battery temperature compensation needed”.2. Selection is manual.
Title: Battery Breaker Interface for MBD Title: Quantity per UPS Module
Filtering Table:
MBD Quantity
Number of Battery Cabinets
Automatic Selection
0 1 11 * 10 2 22 * 20 3 33 * 30 4 44 * 40 5 55 * 50 6 66 * 60 7 77 * 70 8 88 * 8
Filtering Table:
Page 123 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
MBD Quantity
MBD Digit 9
Battery Interface Board
1, 2, 3, 4, 5, 6, 7, 8
M, P NXLBIB
1, 2, 3, 4, 5, 6, 7, 8
N NXLBIBX
Title: Battery Breaker Interface for BISTitle: Quantity per UPS Module
Business Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
BIB Usage BIS Quantity
Number of Battery Cabinets
Automatic Selection
UPS displays per battery string status
* 1 1
UPS displays per battery string status
1 * 1
UPS displays per battery string status
* 2 2
UPS displays per battery string status
2 * 2
UPS displays per battery string status
* 3 3
UPS displays per battery string status
3 * 3
UPS displays per battery string status
* 4 4
UPS displays per battery string status
4 * 4
UPS displays per battery string status
* 5 5
UPS displays per battery string status
5 * 5
UPS displays per battery string status
* 6 6
UPS displays per battery string status
6 * 6
UPS displays per battery string status
* 7 7
UPS displays per battery 7 * 7
Page 124 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
string statusUPS displays per battery string status
* 8 8
UPS displays per battery string status
8 * 8
Title: Temperature SensorTitle: Quantity per UPS Module
Business Rules:
1. The default is “0”.2. Selection is manual.
Filtering Table:
Temperature Sensor Usage
BIS Quantity
MBD Quantity
Number of Battery Cabinets
Selection Available
Battery temperature compensation needed
0 1 * 1
Battery temperature compensation needed
1 * * 1
Battery temperature compensation needed
* * 1 1
Battery temperature compensation needed
0 2 * 2
Battery temperature compensation needed
2 * * 2
Battery temperature compensation needed
* * 2 2
Battery temperature compensation needed
0 3 * 3
Battery temperature compensation needed
3 * * 3
Battery temperature compensation needed
* * 3 3
Battery temperature compensation needed
0 4 * 4
Battery temperature compensation needed
4 * * 4
Battery temperature compensation needed
* * 4 4
Battery temperature compensation needed
0 5 * 5
Battery temperature 5 * * 5
Page 125 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
compensation neededBattery temperature compensation needed
* * 5 5
Battery temperature compensation needed
0 6 * 6
Battery temperature compensation needed
6 * * 6
Battery temperature compensation needed
* * 6 6
Battery temperature compensation needed
0 7 * 7
Battery temperature compensation needed
7 * * 7
Battery temperature compensation needed
* * 7 7
Battery temperature compensation needed
0 8 * 8
Battery temperature compensation needed
8 * * 8
Battery temperature compensation needed
* * 8 8
Title: Stand Alone Junction CabinetTitle: Battery Junction Cabinet Quantity per UPS Module
o On | 0o On | 1
Business Rules:
1. The default is “0”.2. Selection is manual.
Business Rules:
1. Selection is automatic.
Filtering Table:
Module Digit 5
Selection Available
2, 3, 4, 5 40JC500NS6, 7 40JC750NS1 40JC11UNS
Page 126 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Junction Cabinet Floor Anchorso On | 0o On | 1
Business Rules:
1. The default is “0”.2. Selection is manual.
Filtering Table:
Floor Anchors OSHPOD
Junction Cabinet
Selection
“No” 40JC500NS, 40JC750NS, 40JC11UNS
NXLFAWJC
“Yes” 40JC500NS, 40JC750NS, 40JC11UNS
NXLOSHWJC
Title: Flywheel System (per Module)Title: Flywheel Description
o List| Energy Storage is:_____o Text input | Operating time at specified load:____o Text input | Critical load:____kW
Business Rules:
1. There is no default.2. Selection is manual. 3. If selection is “None”, omit the rest of this section.
Filtering Table:
Line Item ListEnergy Storage is None, Flywheel
Title: Flywheel Unito Quantity | Flywheel Units
Business Rules:
Page 127 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1. There is no default.2. Selection is manual. 3. Available selection is any integer from “1” to “8”.
Title: Agency Certificationo On | UL Listedo On | UL Listed and seismic rated
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Digits 1 and 2UL Listed “UA”
UL Listed and seismic rated “US”
Title: Product Modelo On | VDCo On | VDC XEo On | VDC XEHC
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Digit 3VDC “1”
VDC XE “3”
VDC XEHC “4”
Digit 4 = “N”
Page 128 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Auxiliary Input Voltage for Controlso On | 600 Vo On | 480 Vo On | 208 V
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Digit 5600 V “G”
480 V “H”
208 V “L”
Digit 6 = “E”
Title: Flywheel Factory Installed Options (one per PTC)Title: Display Type
o On | Touch screen displayo On | 4-Line LCD Panel
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Digit 7Touch screen display “T”
4-Line LCD Panel “L”
Title: Exterior Panel Coloro On | Blacko On | Off-white (Putty)
Business Rules:
1. There is no default.2. Selection is manual.
Page 129 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Filtering Table:
Selection Digit 8Black “B”
4 Off-white (Putty) “P”
Digit 9 = “J”
Title: Air Filtero On | Noneo On | CM Filter
Business Rules:
1. The default is “CM Filter”.2. Selection is manual.
Filtering Table:
Selection Digit 10“None” “0”
CM Filter “7”
Title: Option Codeo Checkbox | Noneo Checkbox | REPO Interfaceo Checkbox | Customer Interface Boardo Checkbox | Customer Interface Board and REPO
Interfaceo Checkbox | MODBUSo Checkbox | REPO Interface and MODBUSo Checkbox | Customer Interface Board and MODBUSo Checkbox | Customer Interface Board, REPO Interface
and MODBUSo Checkbox | Auto Re-starto Checkbox | REPO Interface and Auto Re-starto Checkbox | Customer Interface Board and Auto Re-
starto Checkbox | Customer Interface Board, REPO Interface
and auto Re-starto Checkbox | MODBUS and Auto Re-start
Page 130 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o Checkbox | REPO Interface, MODBUS and Auto Re-start
o Checkbox | Customer Interface Board, MODBUS and Auto Re-start
o Checkbox | Customer Interface Board, REPO Interface, MODBUS and Auto Re-start
Business Rules:
1. The default is “None”.2. Selection is manual. 3. Show selections only if available in Filtering Table below.
Filtering Table:
Digit 7 Available Selection Digit 11 and 12
* “None” “00”
* “REPO Interface” “13”
* “Customer Interface Board” “17”
* “Customer Interface Board and REPO Interface”
“21”
“T” “MODBUS” “25”
“T” “REPO Interface and MODBUS”
“29”
“T” “Customer Interface Board and MODBUS”
“33”
“T” “Customer Interface Board, REPO Interface and MODBUS”
“37”
* “Auto Re-start” “38”
* “REPO Interface and Auto Re-start”
“39”
“T” “Customer Interface Board and Auto Re-start”
“40”
“T” “Customer Interface Board, REPO Interface and Auto Re-start”
“41”
“T” “MODBUS and Auto Re-start”
“42”
“T” “REPO Interface, MODBUS and Auto Re-start”
“43”
Page 131 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“T” “Customer Interface Board, MODBUS and Auto Re-start”
“44”
“T” “Customer Interface Board, REPO Interface, MODBUS and Auto Re-start”
“45”
Title: Trip Typeo On | 48 VDC Under Voltage Releaseo On | 48 VDC Shunt Trip
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Selection Digit 13“48 VDC Under Voltage Release”
“A”
“48 VDC Shunt Trip” “B”
Title: Flywheel Site Installed Options (Quantity per Flywheel Unit)Title: Flywheel Floor Stand
o Checkbox | Flywheel Floor Stand
Business Rules:
1. The default is “0”.2. Selection is manual.
Title: Flywheel Floor Stand Heighto On | Twelve inch (12”) high floor stando On | Eighteen inch (18”) high floor stando On | Twenty four inch (24”) high floor stando On | Thirty six inch (36”) high floor stando On | Forty eight inch (48”) high floor stand
Business Rules:
1. There is no default.2. Selection is manual.
Page 132 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
3. Subsequent part number is “FS-9000039-__” where the last two characters are the respective height, (“12”, “18”, “24”, “36”, “48”) for the selection.
Title: Flywheel Breaker Interfaceo Checkbox | Breaker Interface for Flywheel
Business Rules:
1. The default is “none”.2. Selection is manual. 3. Subsequent part number is “537760G3”
Tab: “Factory Testing”Title: 1 + N Factory System TestingBusiness Rules:
1. The default is “0”.2. Selection is automatic. 3. If “0” then hide this section.
Filtering Table:
Module Digit 4
Module Quantity
Selection for “Factory Testing”
“N”, “R” 2, 3, 4, 5, 6 “1”“A”, “M” * “0”
Module Quantity Selection2 “1+N2MODSYSTST-1”3 “1+N3MODSYSTST-1”4 “1+N4MODSYSTST-1”5 “1+N5MODSYSTST-1”6 “1+N6MODSYSTST-1”
Title: 1 + N Switchgear FWT SetupBusiness Rules:
Page 133 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1. The default is “0”.2. Selection is automatic.
Filtering Table:
Buyout SPG “Factory Test SPG”
Module Digit 4
Buyout SPG System Breaker Rating
Module Quantity
Selection
“Test with UPS” “N”, “R”
* 2, 3, 4, 5, 6“1”
Buyout SPG “Factory Test SPG”
Module Digit 4
Buyout SPG System Breaker Rating
Module Quantity
Selection
“Test with UPS” * 0350, 0400, 0500, 0600, 0700, 0800, 1000, 1200, 1600, 2000
*
1+NGEAR2KA-LBR
“Test with UPS” * 2500, 3000, 4000 * 1+NGEAR4KA-LBR
Title: 1 + N Switchgear FWT Setup Shipping Splits
Business Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
1+N Switchgear FWT and Setup
Buyout SPG Sections
Quantity
“1” 2 1“1” 3 2
“1” 4 3
“1” 5 4
“1” 6 5
“1” 7 6
Page 134 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“1” 8 7
“1” 9 8
“1” 10 9
“1” 11 10
“1” 12 11
“1” 13 12
“1” 14 13
“1” 15 14
“1” 16 15
“1” 17 16
“1” 18 17
“1” 19 18
“1” 20 19
1+NSPLT2KA-LBR Auto select if "1+N Switchgear FWT Setup" = 1+NGEAR2KA-LBR1+NSPLT4KA-LBR Auto select if "1+N Switchgear FWT Setup" = 1+NGEAR4KA-LBR
Title: 1 + N Switchgear Drawout Breakers Shipped Separately
Business Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
Buyout SPG “SPG Drawout Breakers Shipped Separately”
Quantity
1 1
Page 135 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2 2
3 34 45 56 67 78 89 910 1011 1112 1213 1314 1415 1516 1617 1718 1819 1920 20
DRWOTBKR-LBR Default part number
Title: N + 1 Factory System TestingBusiness Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
Module Digit 3 Selection“M” “1”“S” “0”
Module Digit 4
Module Quantity
Part Number
“M” “2” N+12MODSYSTST-1“M” “3” N+13MODSYSTST-1* “4” N+14MODSYSTST-1“M” “5” N+15MODSYSTST-1* “6” N+16MODSYSTST-1
Title: N + 1 Switchgear FWT Setup
Page 136 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Business Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
SCC Digit 7 Selection“M”, “H”, “J” “1”
SCC Digits 5, 6
SCC Switchgear Manufacturer Part Number
12, 16, 20 ASCO, Cutler-Hammer, GE, Square D N+1GEAR2KA-LBR Type 1
12, 16, 20 Commercial Switchgear, other, Russelectric N+1GEAR2KA-LBR Type 2
12, 16, 20 Siemens N+1GEAR2KA-LBR Type 325, 30, 32, 40, 50
ASCO, Cutler-Hammer, GE, Square D N+1GEAR5KA-LBR Type 1
25, 30, 32, 40, 50
Commercial Switchgear, other, Russelectric N+1GEAR5KA-LBR Type 2
25, 30, 32, 40, 50
SiemensN+1GEAR5KA-LBR Type 3
Title: 1 + N Switchgear FWT Setup Shipping Splits
Business Rules:
1. The default is “0”.2. Selection is automatic.
Filtering Table:
SCC Sections Selection2 13 2
4 35 46 57 68 79 810 911 1012 1113 12
Page 137 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
14 1315 1416 1517 1618 1719 1820 19
N+1 Switchgear FWT Setup Selection N+1GEAR2KA-LBR Type 1 N+1SPLT2KA-LBR Type 1N+1GEAR2KA-LBR Type 2 N+1SPLT2KA-LBR Type 2N+1GEAR2KA-LBR Type 3 N+1SPLT2KA-LBR Type 3 N+1GEAR5KA-LBR Type 1 N+1SPLT5KA-LBR Type 1N+1GEAR5KA-LBR Type 2 N+1SPLT5KA-LBR Type 2 N+1GEAR5KA-LBR Type 3 N+1SPLT5KA-LBR Type 3
Title: 1 + N Switchgear Drawout Breakers Shipped Separately
Business Rules:
1. The default is “0”.2. Selection is automatic.
SCC Drawout Breakers Shipped Separately
Selection Selection
1 1 DRWOTBKR-LBR2 2 DRWOTBKR-LBR3 3 DRWOTBKR-LBR4 4 DRWOTBKR-LBR5 5 DRWOTBKR-LBR6 6 DRWOTBKR-LBR7 7 DRWOTBKR-LBR8 8 DRWOTBKR-LBR9 9 DRWOTBKR-LBR10 10 DRWOTBKR-LBR11 11 DRWOTBKR-LBR12 12 DRWOTBKR-LBR13 13 DRWOTBKR-LBR14 14 DRWOTBKR-LBR15 15 DRWOTBKR-LBR16 16 DRWOTBKR-LBR17 17 DRWOTBKR-LBR
Page 138 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
18 18 DRWOTBKR-LBR19 19 DRWOTBKR-LBR20 20 DRWOTBKR-LBR
DRWOTBKR-LBR Auto select if "SCC Drawout breakers" = 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20
Title: Factory Witness Testingo Checkbox | No System Factory Witness Testingo Checkbox | System Factory Witness Testing
Business Rules:
1. The default is “No”.2. Selection is manual.
Title: Levelo Quantity |
Business Rules:
1. There is no default.2. Selection is manual. 3. Selection may be “1”, “2”, or “3”.
Filtering Table:
Selection“1”“2”“3”
Level Module Quantity
Module Digit 4
Selection
1 * “A” UPSWITNESS-1-11 “1” “N”, “R” UPSWITNESS-1-12 * “A” UPSWITNESS-2-12 “1” “N”, “R” UPSWITNESS-2-1
Page 139 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
3 * “A” UPSWITNESS-3-13 “1” “N”, “R” UPSWITNESS-3-11 “2”, “3” “A” UPSWITNESS-1-22 “2”, “3” “A” UPSWITNESS-2-23 “2”, “3” “A” UPSWITNESS-3-21 “4”, “5” “A” UPSWITNESS-1-32 “4”, “5” “A” UPSWITNESS-2-33 “4”, “5” “A” UPSWITNESS-3-31 “6” “A” UPSWITNESS-1-42 “6” “A” UPSWITNESS-2-43 “6” “A” UPSWITNESS-3-41 “2” “N” NXL1+NWIT-1-22 “2” “N”, “R”
NXL1+NWIT-2-23 “2” “N”, “R”
NXL1+NWIT-3-21 “3” “N”, “R”
NXL1+NWIT-1-32 “3” “N”, “R”
NXL1+NWIT-2-33 “3” “N”, “R”
NXL1+NWIT-3-31 “4”, “5” “N”, “R”
NXL1+NWIT-1-42 “4”, “5” “N”, “R”
NXL1+NWIT-2-43 “4”, “5” “N”, “R”
NXL1+NWIT-3-41 “6” “N”, “R”
NXL1+NWIT-1-52 “6” “N”, “R”
NXL1+NWIT-2-53 “6” “N”, “R”
NXL1+NWIT-3-51 “1” “M” NXLN+1WIT-1-12 “1” “M” NXLN+1WIT-2-1
3 “1” “M” NXLN+1WIT-3-1
1 “2” “M” NXLN+1WIT-1-2
2 “2” “M” NXLN+1WIT-2-2
3 “2” “M” NXLN+1WIT-3-2
1 “3” “M” NXLN+1WIT-1-32 “3” “M” NXLN+1WIT-2-3
3 “3” “M” NXLN+1WIT-3-3
1 “4”, “5” “M” NXLN+1WIT-1-4
2 “4”, “5” “M” NXLN+1WIT-2-4
3 “4”, “5” “M” NXLN+1WIT-3-4
1 “6” “M” NXLN+1WIT-1-5
2 “6” “M” NXLN+1WIT-2-5
3 “6” “M” NXLN+1WIT-3-5
Page 140 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Factory Burn-ino On | Yeso On | No
Business Rules:
1. The default is “No”.2. Selection is manual.
Title: Burn-in Typeo On | Heat Run Onlyo On | Factory Burn-ino On | Factory Burn-in with Data Logging
Business Rules:
1. There is no default.2. Selection is manual. 3. Display only if “Factory Burn-in” is “Yes”.
Title: Hourso List | Hours
Business Rules:
1. There is no default.2. Selection is manual.3. Valid values are 2, 4, 6, 8, 10, 12, 24, 48
Filtering Table:
Module Quantity
Burn-in Type Hours Selection
1 Heat Run Only 2 HEATRUN-2-11 Heat Run Only 4 HEATRUN-4-11 Heat Run Only 6 HEATRUN-6-11 Heat Run Only 8 HEATRUN-8-11 Heat Run Only 10 HEATRUN-10-11 Heat Run Only 12 HEATRUN-12-11 Heat Run Only 24 HEATRUN-24-11 Heat Run Only 48 HEATRUN-48-12 Heat Run Only 2 HEATRUN-2-22 Heat Run Only 4 HEATRUN-4-22 Heat Run Only 6 HEATRUN-6-22 Heat Run Only 8 HEATRUN-8-2
Page 141 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2 Heat Run Only 10 HEATRUN-10-22 Heat Run Only 12 HEATRUN-12-22 Heat Run Only 24 HEATRUN-24-22 Heat Run Only 48 HEATRUN-48-23 Heat Run Only 2 HEATRUN-2-33 Heat Run Only 4 HEATRUN-4-33 Heat Run Only 6 HEATRUN-6-33 Heat Run Only 8 HEATRUN-8-33 Heat Run Only 10 HEATRUN-10-33 Heat Run Only 12 HEATRUN-12-33 Heat Run Only 24 HEATRUN-24-33 Heat Run Only 48 HEATRUN-48-34 Heat Run Only 2 HEATRUN-2-44 Heat Run Only 4 HEATRUN-4-44 Heat Run Only 6 HEATRUN-6-44 Heat Run Only 8 HEATRUN-8-44 Heat Run Only 10 HEATRUN-10-44 Heat Run Only 12 HEATRUN-12-44 Heat Run Only 24 HEATRUN-24-44 Heat Run Only 48 HEATRUN-48-45 Heat Run Only 2 HEATRUN-2-55 Heat Run Only 4 HEATRUN-4-55 Heat Run Only 6 HEATRUN-6-55 Heat Run Only 8 HEATRUN-8-55 Heat Run Only 10 HEATRUN-10-55 Heat Run Only 12 HEATRUN-12-55 Heat Run Only 24 HEATRUN-24-55 Heat Run Only 48 HEATRUN-48-56 Heat Run Only 2 HEATRUN-2-66 Heat Run Only 4 HEATRUN-4-66 Heat Run Only 6 HEATRUN-6-66 Heat Run Only 8 HEATRUN-8-66 Heat Run Only 10 HEATRUN-10-66 Heat Run Only 12 HEATRUN-12-66 Heat Run Only 24 HEATRUN-24-66 Heat Run Only 48 HEATRUN-48-61 Burn-in 2 BURNIN-2-11 Burn-in 4 BURNIN-4-11 Burn-in 6 BURNIN-6-11 Burn-in 8 BURNIN-8-11 Burn-in 10 BURNIN-10-11 Burn-in 12 BURNIN-12-11 Burn-in 24 BURNIN-24-11 Burn-in 48 BURNIN-48-12 Burn-in 2 BURNIN-2-22 Burn-in 4 BURNIN-4-22 Burn-in 6 BURNIN-6-22 Burn-in 8 BURNIN-8-22 Burn-in 10 BURNIN-10-2
Page 142 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2 Burn-in 12 BURNIN-12-22 Burn-in 24 BURNIN-24-22 Burn-in 48 BURNIN-48-23 Burn-in 2 BURNIN-2-33 Burn-in 4 BURNIN-4-33 Burn-in 6 BURNIN-6-33 Burn-in 8 BURNIN-8-33 Burn-in 10 BURNIN-10-33 Burn-in 12 BURNIN-12-33 Burn-in 24 BURNIN-24-33 Burn-in 48 BURNIN-48-34 Burn-in 2 BURNIN-2-44 Burn-in 4 BURNIN-4-44 Burn-in 6 BURNIN-6-44 Burn-in 8 BURNIN-8-44 Burn-in 10 BURNIN-10-44 Burn-in 12 BURNIN-12-44 Burn-in 24 BURNIN-24-44 Burn-in 48 BURNIN-48-45 Burn-in 2 BURNIN-2-55 Burn-in 4 BURNIN-4-55 Burn-in 6 BURNIN-6-55 Burn-in 8 BURNIN-8-55 Burn-in 10 BURNIN-10-55 Burn-in 12 BURNIN-12-55 Burn-in 24 BURNIN-24-55 Burn-in 48 BURNIN-48-56 Burn-in 2 BURNIN-2-66 Burn-in 4 BURNIN-4-66 Burn-in 6 BURNIN-6-66 Burn-in 8 BURNIN-8-66 Burn-in 10 BURNIN-10-66 Burn-in 12 BURNIN-12-66 Burn-in 24 BURNIN-24-66 Burn-in 48 BURNIN-48-61 Burn-in with data
logging2
BURNINDATA-2-11 Burn-in with data
logging4
BURNINDATA-4-11 Burn-in with data
logging6
BURNINDATA-6-11 Burn-in with data
logging8
BURNINDATA-8-11 Burn-in with data
logging10 BURNINDATA-10-
11 Burn-in with data
logging12 BURNINDATA-12-
11 Burn-in with data
logging24 BURNINDATA-24-
1
Page 143 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
1 Burn-in with data logging
48 BURNINDATA-48-1
2 Burn-in with data logging
2BURNINDATA-2-2
2 Burn-in with data logging
4BURNINDATA-4-2
2 Burn-in with data logging
6BURNINDATA-6-2
2 Burn-in with data logging
8BURNINDATA-8-2
2 Burn-in with data logging
10 BURNINDATA-10-2
2 Burn-in with data logging
12 BURNINDATA-12-2
2 Burn-in with data logging
24 BURNINDATA-24-2
2 Burn-in with data logging
48 BURNINDATA-48-2
3 Burn-in with data logging
2BURNINDATA-2-3
3 Burn-in with data logging
4BURNINDATA-4-3
3 Burn-in with data logging
6BURNINDATA-6-3
3 Burn-in with data logging
8BURNINDATA-8-3
3 Burn-in with data logging
10 BURNINDATA-10-3
3 Burn-in with data logging
12 BURNINDATA-12-3
3 Burn-in with data logging
24 BURNINDATA-24-3
3 Burn-in with data logging
48 BURNINDATA-48-3
4 Burn-in with data logging
2BURNINDATA-2-4
4 Burn-in with data logging
4BURNINDATA-4-4
4 Burn-in with data logging
6BURNINDATA-6-4
4 Burn-in with data logging
8BURNINDATA-8-4
4 Burn-in with data logging
10 BURNINDATA-10-4
4 Burn-in with data logging
12 BURNINDATA-12-4
4 Burn-in with data logging
24 BURNINDATA-24-4
4 Burn-in with data logging
48 BURNINDATA-48-4
Page 144 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
5 Burn-in with data logging
2BURNINDATA-2-5
5 Burn-in with data logging
4BURNINDATA-4-5
5 Burn-in with data logging
6BURNINDATA-6-5
5 Burn-in with data logging
8BURNINDATA-8-5
5 Burn-in with data logging
10 BURNINDATA-10-5
5 Burn-in with data logging
12 BURNINDATA-12-5
5 Burn-in with data logging
24 BURNINDATA-24-5
5 Burn-in with data logging
48 BURNINDATA-48-5
6 Burn-in with data logging
2BURNINDATA-2-6
6 Burn-in with data logging
4BURNINDATA-4-6
6 Burn-in with data logging
6BURNINDATA-6-6
6 Burn-in with data logging
8BURNINDATA-8-6
6 Burn-in with data logging
10 BURNINDATA-10-6
6 Burn-in with data logging
12 BURNINDATA-12-6
6 Burn-in with data logging
24 BURNINDATA-24-6
6 Burn-in with data logging
48 BURNINDATA-48-6
Title: Special Factory Setup o Checkbox | Noo Checkbox | Yes
Business Rules:
1. There is no default.2. Selection is manual and input. 3. Repeat this section until the user selects “no” for “Special Factory Setup”
Page 145 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Special Factory Set-upo On | 0o On | 1
Business Rules:
1. The default is “0”.2. Selection is manual. 3. Manual fill part number and price
Title: Special Factory Testingo On | 0o On | 1
Business Rules:
1. The default is “0”.2. Selection is manual. 3. Manual fill part number and
price
Tab: “Services”Screen Layout:
Title: Site Startup Serviceso Checkbox | Site Startup Services needed? (Domestic Only)
Business Rules:
1. There is no default.
Page 146 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2. Selection is manual. 3. If “Startup Services” not checked, don’t display this section.
Title: Startup Services Typeo On | Startup 8x5o On | Startup 24x7o On | Startup Plus 8x5o On | Startup Plus 24x7o On | Essentialo On | Preferredo On | Preferred Plus
Business Rules:
1. There is no default.2. Selection is manual.
Filtering Table:
Manual or Automatic
Battery Cabinets “Cabinets”
Battery Cabinets Digit 4
Installation Location
Selection Available
Manual * * Domestic PM Only 8x5PM Only 24x7Basic 8x5Basic 24x7EssentialPreferred
Auto * * International NoneManual 1 through 8 “A”, “B” Domestic Preferred Plus
Title: UPS Module StartupBusiness Rules:
1. There is no default.2. Selection is automatic. 3. Quantity is equal to module quantity.
Filtering Table:
Startup Services Type
Module Digit 4
Module Digit 5
Selection
Startup 8x5 “A” 2, 3, 4 “SUNXL250-400MF”Startup 24x7 “A” 2, 3, 4 “SUNXL250-400U7”Startup Plus 8x5 “A” 2, 3, 4 “SUPNXL250-400MF”
Page 147 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Startup Plus 24x7 “A” 2, 3, 4 “SUPNXL250-400P7”Startup 8x5 “A” 5, 6, 7 “SUNXL450-750MF”Startup 24x7 “A” 5, 6, 7 “SUNXL450-750U7”Startup Plus 8x5 “A” 5, 6, 7 “SUPNXL450-750MF”Startup Plus 24x7 “A” 5, 6, 7 “SUPNXL450-750P7”Startup 8x5 “A” 1 “SUNXLSMS1100KMF”Startup 24x7 “A” 1 “SUNXLSMS1100KU7”Startup Plus 8x5 “A” 1 “SUPNXLSMS1100KF”Startup Plus 24x7 “A” 1 “SUPNXLSMS1100K7”Startup 8x5 “R”, “N” 2, 3, 4 “SUNXLPLL25-40MF”Startup 24x7 “R”, “N” 2, 3, 4 “SUNXLPLL25-40U7”Startup Plus 8x5 “R”, “N” 2, 3, 4 “SUPNXLPL25-40MF”Startup Plus 24x7 “R”, “N” 2, 3, 4 “SUPNXLPL25-40U7”Startup 8x5 “R”, “N” 5, 6, 7 “SUNXLPLL45-75MF”Startup 24x7 “R”, “N” 5, 6, 7 “SUNXLPLL45-75U7”Startup Plus 8x5 “R”, “N” 5, 6, 7 “SUPNXLPL45-75MF”Startup Plus 24x7 “R”, “N” 5, 6, 7 “SUPNXLPL45-75U7”Startup 8x5 “R”, “N” 1 “SUNXLPLL1100KMF”Startup 24x7 “R”, “N” 1 “SUNXLPLL1100KU7”Startup Plus 8x5 “R”, “N” 1 “SUPXLPLL1100KF”Startup Plus 24x7 “R”, “N” 1 “SUPXLPLL1100K7”Startup 8x5 “M” 5, 6, 7 “SUNXL450-750MMF”Startup 24x7 “M” 5, 6, 7 “SUNXL450-750MU7”Startup Plus 8x5 “M” 5, 6, 7 “SUPXL450-750MPF”Startup Plus 24x7 “M” 5, 6, 7 “SUPXL450-750MP7”Startup 8x5 “M” 1 “SUNXLMMS1100KMF”Startup 24x7 “M” 1 “SUNXLMMS1100KU7”Startup Plus 8x5 “M” 1 “SUPXLMMS1100KF”Startup Plus 24x7 “M” 1 “SUPXLMMS1100K7”
Title: BDSi Controller Startupo Checkbox | 0o Checkbox | 1
Business Rules:
1. The default is 0.2. Selection is manual or automatically “1” if Battery Cabinet digit 4 = “A”, or “B”.3. If “1” then part number is “SBBDSICON24” if “Startup Services Type” = Startup 24x7.4. If “1” then part number is “SBBDSICON24P” if “Startup Services Type” = Startup Plus
24x7.
Title: BDSi Load Module Startup
Business Rules:
1. The default is 0.
Page 148 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2. Selection is automatic and equal to Battery Cabinet digit 11 if Battery Cabinet digit 4 is “A” or “B”.
3. If “1” through “6” then part number is “SBBDSIDCMLM24” if “Startup Services Type” = Startup 24x7.
4. If “1” through “6” then part number is “SBBDSIDCMLM24P” if “Startup Services Type” = Startup Plus 24x7.
Title: Module Site Acceptanceo On | Site Acceptance Test without Load Banko On | Site Acceptance Test with Load Banko On | None
Business Rules:
1. The default is “None”.2. Selection is manual.
Filtering Table:
Module Digit 4
Module Digit 5
Selection Available
Part Number
“A”, “R”, “N”
2, 3, 4 Site Acceptance Test without Load Bank
SUSATNXL250-450
“A”, “R”, “N”
2, 3, 4 Site Acceptance Test with Load Bank
SUSATNXL25-45LB
“A”, “R”, “N”
5, 6, 7 Site Acceptance Test without Load Bank
SUSATNXL4575S
“A”, “R”, “N”
5, 6, 7 Site Acceptance Test with Load Bank
SUSATNXL4575SLB
“M” 5, 6, 7 Site Acceptance Test without Load Bank
SUSATNXL4575M
“M” 5, 6, 7 Site Acceptance Test with Load Bank
SUSATNXL4575MLB
“A”, “R”, “N”
1 Site Acceptance Test without Load Bank
SUSATNXL1100S
“A”, “R”, 1 Site SUSATNXL1100SLB
Page 149 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“N” Acceptance Test with Load Bank
“M” 1 Site Acceptance Test without Load Bank
SUSATNXL1100M
“M” 1 Site Acceptance Test with Load Bank
SUSATNXL1100MLB
Title: Matching MBP StartupBusiness Rules:
1. The default is “0”.2. Selection is automatic. 3. Quantity is equal to Matching MBP quantity.
Filtering Table:
Startup Services Type
Module Digit 5
Selection
Startup 8x5 2, 3, 4 “SUNXLMBC250-40MF”Startup 24x7 2, 3, 4 “SUNXLMBC250-40U7”Startup Plus 8x5 2, 3, 4 “SUPNXLMBC2540MF”Startup Plus 24x7 2, 3, 4 “SUPNXLMBC2540P7”Startup 8x5 5, 6, 7 “SUNXLMBC45-75MF”Startup 24x7 5, 6, 7 “SUNXLMBC4575U7”Startup Plus 8x5 5, 6, 7 “SUPNXLMB4575MF”Startup Plus 24x7 5, 6, 7 “SUPNXLMB45-75P7”
Title: System Control Cabinet Setupo Checkbox | Setup Services?
Business Rules:
1. The default is “0”.2. Selection is automatically “1” if SCC Quantity is “1”.
Filtering Table:
Startup Services Type
SCC Digit 5
Selection
Startup 8x5 1, 2, 3 “SUNXLSCC3000MF”
Page 150 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Startup 24x7 1, 2, 3 “SUNXLSCC3000U7”Startup Plus 8x5 1, 2, 3 “SUPNXLSCC3000MF”Startup Plus 24x7 1, 2, 3 “SUPNXLSCC3000P7”Startup 8x5 4, 5 “SUNXLSC3000+MF”Startup 24x7 4, 5 “SUNXLSC3000+U7”Startup Plus 8x5 4, 5 “SUPNXLSC3000+MF”Startup Plus 24x7 4, 5 “SUPNXLSC3000+P7”
Title: SCC Site Acceptance Packageo Quantity | SCC Site Acceptance Package
Business Rules:
1. The default is “0”.2. Selection is manual if SCC Quantity is “1”. 3. Part Number is “SUSATNXLSCCB”.
Title: Power Tie Control Cabinet Startup
Business Rules:
1. The default is “0”.2. Auto Select “1” if Power Tie Quantity is “1”.
Filtering Table:
Startup Services Type
Selection
Startup 8x5 “SUNXLPT1MF”Startup 24x7 “SUNXLPT24”Startup Plus 8x5 “SUPNXLPT1MF”Startup Plus 24x7 “SUPNXLPT24”
Title: Power Tie Site Acceptance Package
Business Rules:
1. The default is “0”.2. Selection is “1” if Power Tie Quantity is “1”. 3. Part Number is “SUSATNXLPWRTIE”.
Page 151 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: Special Site Testingo Checkbox | “Yes”o Checkbox | “No”
Business Rules:
1. The default is “No”.2. Selection is manual.3. If selection is “No”, this section is complete.4. If selection is “Yes”, provide an input field for a part number and a description. Repeat
until selection is “No.”
Title: Battery Installation Verification Service at Startupo On | IEEE VRLA 10 Year – 1 stringo On | IEEE VRLA 10 Year – 2 stringso On | IEEE VRLA 10 Year – 3 stringso On | IEEE VRLA 10 Year – 4 stringo On | IEEE VRLA 10 Year – 5 stringo On | IEEE VRLA 10 Year – 6 stringo On | IEEE VRLA 10 Year – 7 stringo On | IEEE VRLA 10 Year – 8 stringo On | IEEE VRLA 20 Year – 1 stringo On | IEEE VRLA 20 Year – 2 stringo On | IEEE VRLA 20 Year – 3 stringo On | IEEE VRLA 20 Year – 4 stringo On | IEEE VRLA 20 Year – 5 stringo On | IEEE VRLA 20 Year – 6 stringo On | IEEE VRLA 20 Year – 7 stringo On | IEEE VRLA 20 Year – 8 string o On | IEEE Flooded 20 Year – 1 stringo On | IEEE Flooded 20 Year – 2 stringo On | IEEE Flooded 20 Year – 3 stringo On | IEEE Flooded 20 Year – 4 stringo On | IEEE Flooded 20 Year – 5 stringo On | IEEE Flooded 20 Year – 6 stringo On | IEEE Flooded 20 Year – 7 stringo On | IEEE Flooded 20 Year – 8 string
Business Rules:
1. The default is “0”. 2. Selection is manual.
Filtering Table:
Buyout Battery Buyout Buyout Buyout Selection Part
Page 152 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Battery “Number of Battery Cabinets”
Cabinets “Cabinets” quantity
Battery “Number of Strings in Parallel”
Battery “Cell Type / Container Material”
Battery “Battery Warranty Years__Full”
Available Number
* 1 * * * “IEEE VRLA 10 Year – 1 string”
* * “1” “VRLA” “10” “IEEE VRLA 10 Year – 1 string””
“1” * * * * “IEEE VRLA 10 Year – 1 string””
* 2 * * * “IEEE VRLA 10 Year – 2 strings”
* * “2” “VRLA” “10” “IEEE VRLA 10 Year – 2 strings”
“2” * * * * “IEEE VRLA 10 Year – 2 strings”
* 3 * * * “IEEE VRLA 10 Year – 3 strings”
* * “3” “VRLA” “10” “IEEE VRLA 10 Year – 3 strings”
“3” * * * * “IEEE VRLA 10 Year – 3 strings”
* 4 * * * “IEEE VRLA 10 Year – 4 strings”
* * “4” “VRLA” “10” “IEEE VRLA 10 Year – 4 strings”
Page 153 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“4” * * * * “IEEE VRLA 10 Year – 4 strings””
* 5 * * * “IEEE VRLA 10 Year – 5 strings”
* * “5” “VRLA” “10” “IEEE VRLA 10 Year – 5 strings”
“5” * * * * “IEEE VRLA 10 Year – 5 strings””
* 6 * * * “IEEE VRLA 10 Year – 6 strings”
* * “6” “VRLA” “10” “IEEE VRLA 10 Year – 6 strings”
“6” * * * * “IEEE VRLA 10 Year – 6 strings”
* 7 * * * “IEEE VRLA 10 Year – 7 strings”
* * “7” “VRLA” “10” “IEEE VRLA 10 Year – 7 strings”
“7” * * * * “IEEE VRLA 10 Year – 7 strings”
* 8 * * * “IEEE VRLA 10 Year – 8 strings”
* * “8” “VRLA” “10” “IEEE VRLA 10 Year – 8 strings”
“8” * * * * “IEEE VRLA 10
Page 154 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Year – 8 strings”
* * “1” “VRLA” “20” “IEEE VRLA 20 Year – 1 string”
* * “2” “VRLA” “20” “IEEE VRLA 20 Year – 2 strings”
* * “3” “VRLA” “20” “IEEE VRLA 20 Year – 3 strings”
* * “4” “VRLA” “20” “IEEE VRLA 20 Year – 4 strings”
* * “5” “VRLA” “20” “IEEE VRLA 20 Year – 5 strings”
* * “6” “VRLA” “20” “IEEE VRLA 20 Year – 6 strings”
* * “7” “VRLA” “20” “IEEE VRLA 20 Year – 7 strings”
* * “8” “VRLA” “20” “IEEE VRLA 20 Year – 8 strings”
* * “1” “Flooded” “20” “IEEE Flooded 20 Year – 1 string””
* * “2” “Flooded” “20” “IEEE Flooded 20 Year – 2 strings”
* * “3” “Flooded” “20” “IEEE Flooded 20 Year – 3 strings”
* * “4” “Flooded” “20” “IEEE Flooded 20 Year – 4 strings”
Page 155 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
* * “5” “Flooded” “20” “IEEE Flooded 20 Year – 5 strings”
* * “6” “Flooded” “20” “IEEE Flooded 20 Year – 6 strings”
* * “7” “Flooded” “20” “IEEE Flooded 20 Year – 7 strings”
* * “8” “Flooded” “20” “IEEE Flooded 20 Year – 8 strings”
Title: Flywheel Startupo On | Startup Plus 8x5o On | Startup Plus 24x7
1. There is no default.2. Selection is manual. 3. Flywheel Startup quantity equals “Module quantity” times “Buyout Battery Flywheel
Unit quantity” which should give an integer between “0” and “48”.4. Subsequent part number is “SFFSS1201P_” where the last character is “M” for “Startup
Plus 8x5” and “7” for “Startup Plus 24x7”.
Title: Maintenance Services Typeo On | PM Only 8x5o On | PM Only 24x7o On | Basico On | Essentialo On | Preferredo On | Total Assuranceo On | None
Business Rules:
5. The default is “None”.6. Selection is manual.
Page 156 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Title: UPS Module Maintenance Plan Annual PMso On | “Maintenance Service Type”, “Annual PMs”, “Selection Available”o On | “Maintenance Service Type”, “Annual PMs”, “Selection Available”o On | “Maintenance Service Type”, “Annual PMs”, “Selection Available”o On | “Maintenance Service Type”, “Annual PMs”, “Selection Available”
Business Rules:
1. The default is “None”. Auto select if “Maintenance Service Type = “Basic”2. Selection is manual or automatic. 3. Manual selection of 1, 2, 4, or 12 is allowed.4. Quantity is equal to the number of Modules (1-6).5. Display items from table below for the Maintenance Service Type selected.
Filtering Table:
Filtering Table:
Maintenance Services Type
Annual PMs
Module Digit 5
Selection Available
PM Only 8x5 “1” 2, 3, 4 “MUNXL25-401PM85”PM Only 8x5 “2” 2, 3, 4 “MUNXL25-402PM85”PM Only 8x5 “3” 2, 3, 4 “MUNXL25-403PM85”PM Only 8x5 “4” 2, 3, 4 “MUNXL25-404PM85”PM Only 24x7 “1” 2, 3, 4 “MUNXL25-401PM24”PM Only 24x7 “2” 2, 3, 4 “MUNXL25-402PM24”PM Only 24x7 “3” 2, 3, 4 “MUNXL25-403PM24”PM Only 24x7 “4” 2, 3, 4 “MUNXL25-404PM24”Basic * 2, 3, 4 “MUNXL250-400BAO”Essential “1” 2, 3, 4 “MUNXL250-400ES1”Essential “2” 2, 3, 4 “MUNXL250-400ES2”Essential “3” 2, 3, 4 “MUNXL250-400ES3”Essential “4” 2, 3, 4 “MUNXL250-400ES4”Preferred “1” 2, 3, 4 “MUNXL250-400PR1”Preferred “2” 2, 3, 4 “MUNXL250-400PR2”Preferred “3” 2, 3, 4 “MUNXL250-400PR3”Preferred “4” 2, 3, 4 “MUNXL250-400PR4”Total Assurance “1” 2, 3, 4 “MUNXL250-400TA1”Total Assurance “2” 2, 3, 4 “MUNXL250-400TA2”Total Assurance “3” 2, 3, 4 “MUNXL250-400TA3”Total Assurance “4” 2, 3, 4 “MUNXL250-400TA4”PM Only 8x5 “1” 5, 6, 7 “MUNXL45-751PMF”PM Only 8x5 “2” 5, 6, 7 “MUNXL45-752PMF”PM Only 8x5 “3” 5, 6, 7 “MUNXL45-753PMF”PM Only 8x5 “4” 5, 6, 7 “MUNXL45-754PMF”PM Only 24x7 “1” 5, 6, 7 “MUNXL45-751PM7”
Page 157 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
PM Only 24x7 “2” 5, 6, 7 “MUNXL45-752PM7”PM Only 24x7 “3” 5, 6, 7 “MUNXL45-753PM7”PM Only 24x7 “4” 5, 6, 7 “MUNXL45-754PM7”Basic * 5, 6, 7 “MUNXL450-750BAO”Essential “1” 5, 6, 7 “MUNXL450-750ES1”Essential “2” 5, 6, 7 “MUNXL450-750ES2”Essential “3” 5, 6, 7 “MUNXL450-750ES3”Essential “4” 5, 6, 7 “MUNXL450-750ES4”Preferred “1” 5, 6, 7 “MUNXL450-750PR1”Preferred “2” 5, 6, 7 “MUNXL450-750PR2”Preferred “3” 5, 6, 7 “MUNXL450-750PR3”Preferred “4” 5, 6, 7 “MUNXL450-750PR4”Total Assurance “1” 5, 6, 7 “MUNXL450-750TA1”Total Assurance “2” 5, 6, 7 “MUNXL450-750TA2”Total Assurance “3” 5, 6, 7 “MUNXL450-750TA3”Total Assurance “4” 5, 6, 7 “MUNXL450-750TA4”PM Only 8x5 “1” “1” “MUNXL11001PMF”PM Only 8x5 “2” “1” “MUNXL11002PMF”PM Only 8x5 “3” “1” “MUNXL11003PMF”PM Only 8x5 “4” “1” “MUNXL11004PMF”PM Only 24x7 “1” “1” “MUNXL11001PM7”PM Only 24x7 “2” “1” “MUNXL11002PM7”PM Only 24x7 “3” “1” “MUNXL11003PM7”PM Only 24x7 “4” “1” “MUNXL11004PM7”Basic * “1” “MUNXL1100BAO”Essential “1” “1” “MUNXL1100ES1”Essential “2” “1” “MUNXL1100ES2”Essential “3” “1” “MUNXL1100ES3”Essential “4” “1” “MUNXL1100ES4”Preferred “1” “1” “MUNXL1100PR1”Preferred “2” “1” “MUNXL1100PR2”Preferred “3” “1” “MUNXL1100PR3”Preferred “4” “1” “MUNXL1100PR4”Total Assurance “1” “1” “MUNXL1100TA1”Total Assurance “2” “1” “MUNXL11000TA2”Total Assurance “3” “1” “MUNXL1100TA3”Total Assurance “4” “1” “MUNXL1100TA4”
Title: Matching MBP Maintenance Plan Business Rules:
1. The default is “None”. 2. Selection is automatic. 3. Selection is equal to “Matching MBP Quantity.”
Maintenance Annual Module Selection
Page 158 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Services Type PMs Digit 5PM Only 8x5 “1” * “MBCNXL25401PM85”PM Only 8x5 “2” * “MBCNXL25402PM85”PM Only 8x5 “3” * “MBCNXL25403PM85”PM Only 8x5 “4” * “MBCNXL25404PM85”PM Only 24x7 “1” * “MBCNXL25401PM24”PM Only 24x7 “2” * “MBCNXL25402PM24”PM Only 24x7 “3” * “MBCNXL25403PM24”PM Only 24x7 “4” * “MBCNXL25404PM24”Basic * * “MBCNXL25-40BAO”Essential “1” * “MBCNXL25-40ES1”Essential “2” * “MBCNXL25-40ES2”Essential “3” * “MBCNXL25-40ES3”Essential “4” * “MBCNXL25-40ES4”Preferred “1” * “MBCNXL2540PR1”Preferred “2” * “MBCNXL2540PR2”Preferred “3” * “MBCNXL2540PR3”Preferred “4” * “MBCNXL2540PR4”Total Assurance
“1” * “MBCNXL2540TA1”
Total Assurance
“2” * “MBCNXL2540TA2”
Total Assurance
“3” * “MBCNXL2540TA3”
Total Assurance
“4” * “MBCNXL2540TA4”
PM Only 8x5 “1” 5 “MBNXL45-751PMF”PM Only 8x5 “2” 5 “MBNXL45-752PMF”PM Only 8x5 “3” 5 “MBNXL45-753PMF”PM Only 8x5 “4” 5 “MBNXL45-754PMF”PM Only 24x7 “1” 5 “MBNXL45-751PM7”PM Only 24x7 “2” 5 “MBNXL45-752PM7”PM Only 24x7 “3” 5 “MBNXL45-753PM7”PM Only 24x7 “4” 5 “MBNXL45-754PM7”Basic * 5 “MBNXL450-750BAO”Essential “1” 5 “MBNXL450-750ES1”Essential “2” 5 “MBNXL450-750ES2”Essential “3” 5 “MBNXL450-750ES3”Essential “4” 5 “MBNXL450-750ES4”Preferred “1” 5 “MBNXL450-750PR1”Preferred “2” 5 “MBNXL450-750PR2”Preferred “3” 5 “MBNXL450-750PR3”Preferred “4” 5 “MBNXL450-750PR4”Total Assurance
“1” 5 “MBNXL450-750TA1”
Total Assurance
“2” 5 “MBNXL450-750TA2”
Total Assurance
“3” 5 “MBNXL450-750TA3”
Page 159 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Total Assurance
“4” 5 “MBNXL450-750TA4”
Title: SCC Maintenance Plan Business Rules:
1. The default is “0”. 2. Selection is automatic. 3. Auto select if “SCC Quantity = “1”.
Filtering Table:
UPS Module Maintenance Plan
SCC Digit 5 Selection
“MUNXL25-401PM85” 1, 2, 3 “MNXSCC30001PMF”“MUNXL25-402PM85” 1, 2, 3 “MNXSCC30002PMF”“MUNXL25-403PM85” 1, 2, 3 “MNXSCC30003PMF”“MUNXL25-404PM85” 1, 2, 3 “MNXSCC30004PMF”“MUNXL25-401PM24” 1, 2, 3 “MNXSCC30001PM7”“MUNXL25-402PM24” 1, 2, 3 “MNXSCC30002PM7”“MUNXL25-403PM24” 1, 2, 3 “MNXSCC30003PM7”“MUNXL25-404PM24” 1, 2, 3 “MNXSCC30004PM7”“MUNXL250-400BAO” 1, 2, 3 “MNXSCC3000BAO”“MUNXL250-400ES1” 1, 2, 3 “MNXSCC3000ES1”“MUNXL250-400ES2” 1, 2, 3 “MNXSCC3000ES2”“MUNXL250-400ES3” 1, 2, 3 “MNXSCC3000ES3”“MUNXL250-400ES4” 1, 2, 3 “MNXSCC3000ES4”“MUNXL250-400PR1” 1, 2, 3 “MNXSCC3000PR1”“MUNXL250-400PR2” 1, 2, 3 “MNXSCC3000PR2”“MUNXL250-400PR3” 1, 2, 3 “MNXSCC3000PR3”“MUNXL250-400PR4” 1, 2, 3 “MNXSCC3000PR4”“MUNXL250-400TA1” 1, 2, 3 “MNXSCC3000TA1”“MUNXL250-400TA2” 1, 2, 3 “MNXSCC3000TA2”“MUNXL250-400TA3” 1, 2, 3 “MNXSCC3000TA3”“MUNXL250-400TA4” 1, 2, 3 “MNXSCC3000TA4”“MUNXL45-751PMF” 4, 5 “MNXSCC3000+1PMF”“MUNXL45-752PMF” 4, 5 “MNXSCC3000+2PMF”“MUNXL45-753PMF” 4, 5 “MNXSCC3000+3PMF”“MUNXL45-754PMF” 4, 5 “MNXSCC3000+4PMF”“MUNXL45-751PM7” 4, 5 “MNXSCC3000+1PM7”“MUNXL45-752PM7” 4, 5 “MNXSCC3000+2PM7”“MUNXL45-753PM7” 4, 5 “MNXSCC3000+3PM7”“MUNXL45-754PM7” 4, 5 “MNXSCC3000+4PM7”“MUNXL450-750BAO” 4, 5 “MNXSCC3000+BAO”
Page 160 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“MUNXL450-750ES1” 4, 5 “MNXSCC3000+ES1”“MUNXL450-750ES2” 4, 5 “MNXSCC3000+ES2”“MUNXL450-750ES3” 4, 5 “MNXSCC3000+ES3”“MUNXL450-750ES4” 4, 5 “MNXSCC3000+ES4”“MUNXL450-750PR1” 4, 5 “MNXSCC3000+PR1”“MUNXL450-750PR2” 4, 5 “MNXSCC3000+PR2”“MUNXL450-750PR3” 4, 5 “MNXSCC3000+PR3”“MUNXL450-750PR4” 4, 5 “MNXSCC3000+PR4”“MUNXL450-750TA1” 4, 5 “MNXSCC3000+TA1”“MUNXL450-750TA2” 4, 5 “MNXSCC3000+TA2”“MUNXL450-750TA3” 4, 5 “MNXSCC3000+TA3”“MUNXL450-750TA4” 4, 5 “MNXSCC3000+TA4”
Title: PTC Maintenance Plan Business Rules:
1. The default is “0”. 2. Selection is automatic. 3. Auto select if “Power Tie Quantity = “1”. Otherwise, do not display this section.
Filtering Table:
UPS Module Maintenance Plan
Selection
“MUNXL25-401PM85” “MPRTNXL1PM85”“MUNXL25-402PM85” “MPRTNXL2PM85”“MUNXL25-403PM85” “MPRTNXL3PM85”“MUNXL25-404PM85” “MPRTNXL4PM85”“MUNXL25-401PM24” “MPRTNXL1PM24”“MUNXL25-402PM24” “MPRTNXL2PM24”“MUNXL25-403PM24” “MPRTNXL3PM24”“MUNXL25-404PM24” “MPRTNXL4PM24”“MUNXL250-400BAO” “MPRTNXLBAO”“MUNXL250-400ES1” “MPRTNXLES1”“MUNXL250-400ES2” “MPRTNXLES2”“MUNXL250-400ES3” “MPRTNXLES3”“MUNXL250-400ES4” “MPRTNXLES4”“MUNXL250-400PR1” “MPRTNXLPR1”“MUNXL250-400PR2” “MPRTNXLPR2”“MUNXL250-400PR3” “MPRTNXLPR3”“MUNXL250-400PR4” “MPRTNXLPR4”“MUNXL250-400TA1” “MPRTNXLTA1”“MUNXL250-400TA2” “MPRTNXLTA2”“MUNXL250-400TA3” “MPRTNXLTA3”
Page 161 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“MUNXL250-400TA4” “MPRTNXLTA4”
Title: BDSi Controller Maintenance Plan o Checkbox | BDSi Controller Maintenance Plan
Business Rules:
1. The default is “None”. If not selected, hide this section.2. Selection is manual if Battery Cabinet digit 4 = “A” or “B”.
Title: Maintenance Services Typeo On | PM Only o On | Basic o On | Essential o On | Preferred
Business Rules:
1. The default is none.2. Selection is manual.
Filtering Table:
Selection Part NumberPM Only “PMBDSICONTPMON1”Basic “PMBDSICONTPBAS1”Essential “PMBDSICONTPESS1”Preferred “PMBDSICONTPPREF1”
Title: BDSi Load Module Maintenance Plan Business Rules:
1. The default is “0”.2. Selection is Automatic. 3. The selection is the same value as Battery Cabinet digit 11 if “BDSi Controller
Maintenance Plan” quantity is “1”.
Filtering Table:
BDSi Controller Maintenance Plan
Part Number
“PMBDSICONTPMON1” “PMBDSIDCMLMPM1”“PMBDSICONTPBAS1” “PMBDSIDCMLMBAS1”
Page 162 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
“PMBDSICONTPESS1” “PMBDSIDCMLMESS1”“PMBDSICONTPPREF1” “PMBDSIDCMLMPRF1”
Title: Battery PM Maintenance Plan o Checkbox | Battery PM Maintenance Services
Business Rules:
4. The default is “None”. If not selected, hide this section.5. Selection is manual.
Title: Battery Maintenance Plano On | PM Only 8x5o On | PM Only 24x7o On | Basic 8x5o On | Basic 24x7o On | Essential 8x5o On | Preferred 24x7o On | Preferred Pluso On | None
Business Rules:
1. The default is none.2. Selection is manual. 3. Manual select if Battery Cabinets “Cabinets” quantity is “1” through “8” and Buyout
Battery “Number of Strings in Parallel” is “1” through “8” and Buyout Battery “Number of Battery Cabinets is “1” through “8”.
Title: Battery Maintenance Services Type PM Visitso On | 1 PM per yearo On | 2 PMs per yearo On | 4 PMs per yearo On | 12 PMs per year
Business Rules:
1. There is no default.2. Selection is manual or auto.
Filtering Table:
Manual or Automatic
Startup Services Type
Years from “Battery Sizing” input
Selection Available
Manual PM Only 8x5 10 1 PM per year
Page 163 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
PM Only 24x7Basic 8x5Basic 24x7
2 PMs per year4 PMs per year
Manual PM Only 8x5PM Only 24x7Basic 8x5Basic 24x7
20 1 PM per year4 PMs per year
Automatic EssentialPreferredPreferred Plus
20 12 PMs per year
The following stuff is needed to drive part numbers when we get to it.Part numbers need:
1. Battery PM Startup Services Type (Above)2. Battery PM Startup Services Type PM Visits (Above)3. One of first three fields in table below4. VRLA or Flooded from Battery Sizing input5. Years from Battery Sizing input6. Number of cells (voltage) from Battery Sizing input or one of first three fields in table below
Buyout Battery “Number of Cabinets”
Battery Cabinets Quantity
Buyout Battery “Number of Strings in Parallel”
Voltage = X * 240 where the following values are possible (Field V)
0 1-8 0 240, 480, 720, 960, 1200, 1440, 1680, 1920
0 0 1-8 240, 480, 720, 960, 1200, 1440, 1680, 1920
1-8 0 0 240, 480, 720, 960, 1200, 1440, 1680, 1920
Title: Flywheel Maintenance Serviceso On | PM Only 8x5o On | PM Only 24x7o On | Basic 8x5o On | Basic 24x7o On | Essential 8x5
Page 164 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
o On | Preferred 24x7o On | None
Business Rules:
1. The default is “None”.2. Selection is manual. 3. Manual select if Battery Cabinets “Cabinets” quantity is “1” through “8” or Buyout
Battery “Number of Strings in Parallel” is “1” through “8” or Buyout Battery “Number of Battery Cabinets is “1” through “8”.
4. Flywheel Maintenance quantity is the same as “Flywheel Startup quantity”.
Title: Special Site Testingo Checkbox | “Yes”o Checkbox | “No”
Business Rules:
1. The default is “No”.2. Selection is manual.3. If selection is “No”, this section is complete.4. If selection is “Yes”, provide an input field for a part number and a description. Repeat
until selection is “No.”
Title: Special Maintenance Serviceso Checkbox | Yeso Checkbox | No
1. There is no default.2. Selection is manual and input. 3. Repeat this section until the user selects “no” for “Special Maintenance Services”
Title: Special Maintenance Serviceso On | 0o On | 1
Business Rules:
1. The default is “0”.2. Selection is manual. 3. Manual fill part number and price
Page 165 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Tab: “SFA”Screen Layout:
Title: SFAPlaceholder
Tab: “Other Options”Screen Layout:
Title: Placeholder
Tab: “Summary”Screen Layout:
Title: Summaryo Quantity | Main Unit Quantity
Tab: “Internal”Screen Layout:
Title: UPS Module Configuration Digit Overrideo
Existing A E A
Override
UPS digit 13 14 15
Title: MBC Configuration Digit Overrideo
Existing A N N N
Override
UPS digit 12 13 14 15
Business Rules:
1. Do “BC Configuration Digit override” for each “Cabinet Quantity” (page 96) up to six.
Page 166 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
2. Input is manual.
Title: BC1 Configuration Digit Overrideo
Existing L N N
Override
UPS digit 13 14 15
Title: BC2 Module Configuration Digit Overrideo
Existing L N N
Override
UPS digit 13 14 15
Title: BC3 Module Configuration Digit Overrideo
Existing L N N
Override
UPS digit 13 14 15
Title: BC4 Module Configuration Digit Overrideo
Existing L N N
Override
UPS digit 13 14 15
Title: BC5 Module Configuration Digit Overrideo
Page 167 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Existing L N N
Override
UPS digit 13 14 15
Title: BC6 Module Configuration Digit Overrideo
Existing L N N
Override
UPS digit 13 14 15
Title: Auto Config
Page 168 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
Appendix:Right Hand Summary (RHS): Standard:The following standard will be used in building the right hand summary. There are two standards based on the type of configurator (SKU based or Configured based)
SKU Base:
o Tab name becomes a header on the RHS: (This follows the flow of the tabs and is only shown if
an item is selected on the Tab)o (QTY): Part number
Configured Base:
o Model Number: (Top item 15 digit)
o Main Unit: (Section for building out the header on the RHS:)
o X – Option Description (These should flow in the order of the model number sequence of
digits)o Tab name becomes a header on the RHS: (This follows the flow of the tabs and is only shown if
an item is selected on the Tab)o (Qty) : Part Number
o Internal Use: (Use when applicable)
o 25 digit configuration number
o ICOM Code
Proposal Section: Match Existing Text and Convert Logic to SystemX (Include old document in specification)
Take old document, re-tag and port to new development.
Line Item Detail (LID) Section:Match output for current LID: [paste code here]
Take old document, re-tag and port to new development.
Submittal Section:List logic related to Submittals for this configurator. Take old document, re-tag and port to new development. Include and identify if “Scopes of Work” is necessary for service items.
Part/Price Information Table:If it is a made up (fake) part number, please place a “Y” in the field “Fake Number ID”.
Part Number Fake Number ID
Part Description Price Weight Ship Plant
XXOHDSJKH This is a part type thingy $1,250.50 2.5 lbs 014
Page 169 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
FFDSIUYSD Y This is a part thingy of type
$1,200.00 4 lbs 007
SFA Keys:SFA Keys: (Example)
sSFAFieldIdent_Array(2, 1) = "Knurr DCM"sSFAFieldIdent_Array(3, 1) = "156"
Document Section: Document ID’s:Document ID’s can be found in the activeX form by looking at the following code:
Locate the file “docopts.asp” for the EL.Net configurator The “Call DisplaySupportDocuments(#)” the # is the document number.
Other Suggested Items:These items are highly recommended for building out the logic/function of the configurator.
Part Number Logic:
Static Rack Qty Static Redundancy State EntryXXX 3 0 C X T
4 Y S5
Part Number Lookup:
Voltage Amperage Part NumberA 100 Jbox 100 AB 100 Jbox 100 B
Filtering:
Voltage Amperage BreakerA 100 AA 100 BA 100 CB 100 AA 250 B
Page 170 of 171Version 0.997
Specification for Liebert NXLDate: 3/02/2012
IssuesThe business wants to display prices to help users make decisions.
Page 171 of 171Version 0.997