September 2014
NU-WALL EXTRUDED ALUMINIUM CLADDING
Installation Specifications – Vertical orientation (over cavity)
1. NW-V001C; Cavity batten layout 2. NW-V002C; Battening options 3. NW-V002C; Battening options – steel framing 4. NW-V003C; Base channel & fixing detail 5. NW-V004C; Base channel over timber floor 6. NW-V005C; Base channel over waterproof deck 7. NW-S004; Base channel mitred corner detail 8. NW-V006C; Base channel / external 90˚ corner isometric 9. NW-V007C; External 90˚ corner 10. NW-V008C; Internal 90˚ corner 11. NW-V009C; Horizontal joint 12. NW-V010C; Window sill section 13. NW-V011C; Window jamb section 14. NW-V012C; Window head section 15. NW-V013C; Window head & sill soaker flashing detailing 16. NW-V014C; Window head flashing end detail 17. NW-V015C; Meter box sill section 18. NW-V016C; Meter box jamb section 19. NW-V017C; Meter box head section 20. NW-V018C; Soffit trim section 21. NW-V019C; Pipe penetration 22. NW-V020C; Roof / wall junction 23. NW-V021C; Parapet flashing 24. NW-V022C; Deck junction 25. NW-V023C; Gutter / wall junction
NW-V001C - Vertical Cladding over Drained & Vented Cavity Batten LayoutScale NTS
© Nu-Wall Aluminium Cladding www.nu-wall.co.nz www.nu-wall.com.au August 2014
Meter Box
Window Maximum nogspacing at 600mm
Horizontal cavity battens.Refer to Drawing NW-V002Cfor suitable batten options.
600mm
600mm
600mm
100mmCavity battens under the opening mustbe located no closer than 100mm tothe edge of the opening.
NC
134Base C
hannel - Drill 5m
mdrainage holes @
500mm
centres
NC
227Plastic Soaker
Window
Head Flashing
Jamb Flashing
Base & Cap
NC
138 / 139
Soaker formed into Base C
hannel
NW
-V013C - Vertical C
ladding over Drained & Vented C
avity - Window
Head & Sill Soaker D
etails
Scale NTS
© N
u-Wall Alum
inium C
ladding w
ww
.nu-wall.co.nz
ww
w.nu-w
all.com.au BASE
August 2014
Top of soaker located behind head flashing
Top of batten chamfered to ease path of soaker
Soaker formed over batten
Soaker located behind Jamb Flashing
Cut Soakers to length
Trim to suit
Form into Base C
hannelat bottom
of cladding
Trim
SILL
HEAD
Junction prior to cladding around window
headJunction after cladding around w
indow head
Plastic Soaker continued tofinish in Base C
hannel orhorizontal joint
Ref N
W-V012C
forsectional draw
ing
NW
-V014C - Vertical C
ladding over Drained & Vented C
avity - Head Flashing End D
etailScale N
TS
August 2014©
Nu-W
all Aluminium
Cladding
ww
w.nu-w
all.co.nz w
ww
.nu-wall.com
.au
Head flashing stop-ended
and sealed with silicon
NC
227
Jamb Flashing C
apN
C139
Base Channel - D
rill 5mm
drainage holes @ 500m
mcentres
NC
134
Window
Head Flashing
Seal slot around endof head flashing andBase C
hannel
Board slotted aroundhead flashing andBase C
hannel
NW-V015C - Vertical Cladding over Drained & Vented Cavity - Meter Box Sill DetailScale 1:2
© Nu-Wall Aluminium Cladding www.nu-wall.co.nz www.nu-wall.com.au August 2014
NC226Impervious barrier (MDPE orsimilar) between batten & cladding
10mm
Drained & vented cavity perNZBC Clause E2/AS1 (section 9.1.8)
Plastic Soaker Flashing locatedbehind Jamb Flashing Basecontinued to finish in Base Channel
NC227
Jamb Flashing Base
Jamb Flashing CapNC139
NC138
50mm x 20mmaluminium angle sealedand riveted to meter box
Metal Meter Box
Air seal over PEF rod aroundall sides of meter box
Wall Underlayfolded into opening
Flexible flashing tapeto sill and jambs
Impervious barrier (MDPE or similar)between batten & cladding
Continuous horizontalbatten to close off cavity
Scale 1:1NW-V018C - Vertical Cladding over Drained & Vented Cavity - Soffit Trim
© Nu-Wall Aluminium Cladding www.nu-wall.co.nz www.nu-wall.com.au August 2014
Soffit Lining
Drained & vented cavityper NZBC Clause E2/AS1(section 9.1.8)
Wall Underlay
NC226
Closed-Cell PVC foam tapeNC229
Jamb Flashing CapNC139
Jamb Flashing BaseNC138
© N
u-Wall Alum
inium C
ladding w
ww
.nu-wall.co.nz
ww
w.nu-w
all.com.au
NW
-V019C - Vertical C
ladding over Drained & Vented C
avity - Pipe PenetrationScale N
TS
August 2014
0.7mm
Aluminium
SoakerFlashing tappered to fit insidePlastic Soaker Flashing
Flexible Flashing Tapeapplied to soaker and pipe
Proprietary flashing installed tom
anufacturer's specifications
A = Pipe diameter
+ 100mm
A
Flexible flashing tape over underlay100m
m all round pipe and 25m
mw
ide around pipe
Drained & vented cavity per N
ZBCC
lause E2/AS1 (section 9.1.8)
NC
226
Wall U
nderlay carefullycut to suit pipe
Impervious barrier (M
DPE or sim
ilar)betw
een batten & cladding
Pipe to have minim
um5° fall to outside
Plastic Soaker Flashing continuedto finish in Base C
hannel
NC
227
NW-V022C - Vertical Cladding over Drained & Vented Cavity - Deck JunctionScale NTS
© Nu-Wall Aluminium Cladding www.nu-wall.co.nz www.nu-wall.com.au August 2014
Deck joistImpervious barrier (MDPE or similar)between batten & cladding
H3.2 treated timber packer12mm thick at fixing locations
H3.2 treated timberribbon plate
50x50x3mm thick EPDM washerto suit, hole to be tight fit around bolt
12mm minimum
Drained & vented cavity perNZBC Clause E2/AS1 (section 9.1.8)
NC226
Structural blocking asper Engineering design
Fixings as perEngineering deign
Wall Underlay