NTPC BHEL PACK, AT-02.06.10.xls

download NTPC BHEL PACK,  AT-02.06.10.xls

of 4

Transcript of NTPC BHEL PACK, AT-02.06.10.xls

  • 8/10/2019 NTPC BHEL PACK, AT-02.06.10.xls

    1/4

    Customer:- BHEL/NTPC

    MDCC No.

    S.NO. Drum No. Accepted Length

    (Mtrs)

    1 A-247 491

    2 A-248 480

    3 A-249 4894 A-250 504

    5 A-251 507

    6 A-252 489

    7 A-253 484

    8 A-254 504

    9 A-255 514

    10 A-256 506

    10 Drums 4968

    For NTPC

    Size:-1CX630 Sq.mm 6.35/11 KV (A2XY) Unarmoured FRLS Cable

    KRISHNA ELECTRICAL INDUSTRIES LTD.

    30-B, Industrial Area Banmore (M.P.)

    Packing List

    P.O. NO.: PE/MM/PRG/P-978/08 DT. 05.03.2009 & AMENDMENT No.2

    PRAGATI -III, POWER PROJECT.

  • 8/10/2019 NTPC BHEL PACK, AT-02.06.10.xls

    2/4

    Customer:- BHEL/NTPC

    CHP NO: 01021346

    S.NO. Drum No. Offered LengthLength

    ConsumedFinal Length

    (Mtrs) in testing (Mtrs) (Mtrs)

    1 A-247 491 491

    2 A-248 480 4803 A-249 489 489

    4 A-250 508 4 504

    5 A-251 507 507

    6 A-252 489 489

    7 A-253 503 19 484

    8 A-254 504 504

    9 A-255 514 514

    10 A-256 510 4 506

    10 Drums 4995 27 4968

    Size:-1CX630 Sq.mm 6.35/11 KV (A2XY) Unarmoured FRLS Cable

    For Krishna Electrical Industries Ltd.

    KRISHNA ELECTRICAL INDUSTRIES LTD.

    30-B, Industrial Area Banmore (M.P.)

    Packing List

    P.O. NO.: PE/MM/PRG/P-978/08 DT. 05.03.2009 & AMENDMENT No.2

    PRAGATI -III, POWER PROJECT.

  • 8/10/2019 NTPC BHEL PACK, AT-02.06.10.xls

    3/4

    Page 3 of 4

    Customer:- BHEL/NTPC

    P.O. NO.: PE/MM/PRG/P-978/08 DT. 05.03.2009 PRAGATI -III, POWER PROJECT. CHP NO: 01021346

    Size:-1CX630 Sq.mm 6.35/11 KV (A2XY) Unarmoured FRLS Cable Date of Inspection: 10.06.2010 & 22.06.2010

    1) App.Overall Diameter of Cable

    (mm)

    452

    2) Laying up of cores NA

    3) Core Identification Natural

    4) Colour of outer sheath Black

    5) TEST ON CONDUCTOR

    Shape of ConductorStranded Compacted

    Circular

    No. of Strands 58 No. wires (App)

    Tensile Strength (N/mm) 100 to 150 (H2 grade)

    Wrapping Test Wire shall not break

    6) THICKNESS (mm)

    Insulation

    Nom 3.60 (Nom)

    Min 3.14 (Min)

    Inner semicon

    (Conductor Screen)0.30 (App)

    Outer semicon

    (Insulation Screen)0.30 (App)

    Copper Tape (Metallic Screen)40x0.0600.004 mm x2

    Nos. Min 10% over lap

    Outer Sheath (Type-ST2) FRLS 1.72 (Min)/2.40 (Nom)

    7) Mechanical Test

    a) on XLPE Insulation

    i)Tensile Strength (N/mm) 12.5 (Min)

    ii) Elongation at break (%) 200 (Min)

    b) On outer sheath (ST2)

    i) Tensile Strength (N/mm) 12.5 (Min)

    ii)Elongation at break % 150 (Min)

    13.62

    18.50

    487.5

    212.5

    0.50

    0.60 0.50 0.50

    NA NA

    NA as per clause no. 6.2.2 of IS:8130/84

    2.73/2.89 2.80/2.95 2.80/2.98

    3.83 3.80 3.78

    3.80

    KRISHNA ELECTRICAL INDUSTRIES LTD.30- B, Industrial Area Banmore

    Acceptance Test ReportAs Per IS: 7098(Pt-II)/1985 with latest amendment & GTP

    Black Black

    Natuaral Natuaral Natuaral

    NA

    SPECIFIED VALUE

    46.48

    DESCRIPTION OF TEST

    Black

    OBSERVATION

    Drum No.A-250 Drum No.A-253 Drum No.A-256

    45.98 46.47

    50x0.060x2 Nos.

    14% overlap

    58 58 58

    3.70 3.70

    NA as per clause no. 6.2.1 of IS:8130/84

    0.50 0.40

    21.49

    512.5

    50x0.060x2 Nos.

    14% overlap

    50x0.060x2 Nos.

    15% overlap

    15.58

    250

    15.65

    262.5

    20.37

    500

  • 8/10/2019 NTPC BHEL PACK, AT-02.06.10.xls

    4/4

    Page 4 of 4

    Size:-1CX630 Sq.mm 6.35/11 KV (A2XY) Unarmoured FRLS Cable Date of Inspection: 10.06.2010 & 22.06.2010

    SPECIFIED VALUEDESCRIPTION OF TESTOBSERVATION

    Drum No.A-250 Drum No.A-253 Drum No.A-256

    8) AGEING TEST

    (Expressed as % variation after

    168 hrs.)

    a) On Insulation at 13530C

    i) Tenslie Strength (N/mm2) --

    ii) % Variation 25% (Max)

    iii) Elongation at break % --

    iv) % Variation 25% (Max)

    b) On Outer Sheath (ST2)

    at 10020C

    i) Tenslie Strength (N/mm2) 12.5 (Min)

    ii) % Variation 25% (Max)

    iii) Elongation at break % 150 (Min)

    iv) % Variation 25% (Max)

    9) HOT SET TEST ON XLPE

    INSULATION

    i) Elongation under load 175% (Max)

    ii)Permanent Elongation aftercooling

    15% (Max)

    10) VOLUME RESISTIVITY on

    XLPE insulation (ohm-cm)

    at 27 c 1.0 x 1014

    (Min)

    at 90 c 1.0 x 1012

    (Min)

    11) THERMAL STABILITY TEST

    On Outer Sheath at 2000.50C 80 minutes (Min)

    12) Special Tests for FRLS

    property

    a) Flammability Test

    i) As per IEC-332-Pt-3(Cat-B)

    e a ec e por on o ca e

    shall not exceed 2.5 mtr

    above the bottom edge of the

    ii) Swidish Chimmney Test

    as per SS-424 1475

    (Fire resistance)

    NA due to Cable dia.more

    than 35 mm

    b)Oxygen index test

    as per ASTMD-2863 on outer

    sheath29% (Min)

    c)Halogen Acid Gas Generation

    Test

    on outer sheath as per IEC 754-1 20% (Max)

    d) Smoke Density Test on

    Outer sheath as per ASTMD-

    2843

    i) Max. Smoke Density Rating 60% (Max)

    ii) Min. Light Transmission 40% (Min)

    13) High Voltage Test at 3 U0for

    4 hrs.at 19.05 KVTo Withstand

    (Rahul Shrivastava) (Vikas Lata )

    DGM (IS) Manager- Quality

    NTPC BHEL -PEM

    For Krishna Electrical Industries Ltd

    (Vinod Gupta)

    Manager(QA & I)

    ----

    ----

    ----

    ----

    47.0

    3.6 X 1015

    4.6 X 1014

    Witnessed By

    3.9 X 1014

    3.9 X 1015

    4.6 X 1014

    Embossing Details: MPCAB/KRISHNA ELECTRIC 6.35/11 KV 2010 1CX630 SQMM FRLS A2XY .

    Note: Drum No. A-253 Selected for length measurement and surface finish checking, No defect observed.

    -----94

    -2.56

    ----

    13.71----

    -0.660

    ----

    ---- -11.76

    237.5

    21.4----

    ----

    ----

    ----

    Withstood Withstood Withstood

    ----- 49.99 -----

    18.93 -----

    ----- 34.7 -----

    The affected portion of

    cable 1.05 mtr above the

    bottom edge of the burner.

    -------

    -----

    ----- 50.01 -----

    64.5

    2.6 X 1015

    ----- NA -----

    -------

    ----

    ----

    ----

    ----

    -----

    -14.64

    500

    1.05

    53.5

    0.65 1.65