Omaha Public Power District1623 HARNEY OMAHA, NEBRASKA 68102 * TELEPHONE S3C
,, ,, , ,
July 17, 1980
Mr. K. V. Seyfrit, DirectorU. S. Nuclear Regulatory ComissionOffice of Inspection and EnforcementRegion IV611 Ryan Plaza DriveSuite 1000Arlington, Texas 76011
Peference: Docket No. 50-285
Dear Mr. Seyfrit:
The Omaha Public Power District submitted a response to IE Bulletin79-01B dated April 17, 1980, which indicated that additional aging datafor electrical cables for the Fort Calhoun Station was forthcoming.Accordingly, the attached pages, C-9 through C-13, are provided.Several change pages are also provided to update information containedin the District's original submittal. Specifically, valve HCV-545 isdeleted from page C-28 and resubmitted as page C-28A, due to its failedposition being improperly identified. In addition, page C-0 is cor-rected to indicate a " Note 2", which was previously omitted.
Sincerely,. \
'i Q'.
W. C. JonesDivis' ion ManagerProduction Operations
WCJ/KJM/BJH/PRT:jmm
Attachments
cc: U. S. Nuclear Regulatory CommissionOffice of Inspection and EnforcementWashington, D. C. 20555
LeBoeuf, Lamb, Leiby & MacRae1333 New Hampshire Avenue, N. W.Washington, D. C. 20036
.8008280o16
. - - .- _ _ - - - - ._
Facility: Fort Calhoun 1Docket No.: 50-285 "
C-9*
SYSTEM COMPONENT EVALUATON WORK SIIEET
ENVIRONMENT DOCllMI'.NTATOM REF. QUALIFI- OUTSTAND-,
CATION INGEQUIPt!ENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- MET 110D ITEMS
Parameter cation cation cation cation
System: Electrical Equipment Operatingi Time Note 1 Note 1 1,2 2 Sequential NONE
Item No.: W-57 & W-59 CableTempera- Same astuce *F 286*F Oper time 1,2 2 Sequential NONE,
i
Component: N/A PressurePSlg 60 PSIg 60 PSIg 1,2 2 Sequential NONE
!!anu f ac tu re r : Cerro Wire &'
Cable Co. (Rockbestos) 1(elative
fluile l flo. : N/A flumidity % 100% 100% 1,2 2 Sequential NONE
Function: lustrument cable for Chemical 1900 ppm 1900 ppmtemp, flow & press indication Spray Boric Acid Boric Acid 1,2 Sequential NONE'
Accuracy - Spec: N/A6 6
Demon: N/A Radiation 3x10 R 3x10 R 1,2 2,3 Sequential NONEService: See functionLocation: Containment & Aging
Aux Bldg. N/A 40 yrs N/A 4 4 NONE
flood Level Elev: 1000.9' Submer-,
Above Flood Level: Yes gence N/A N/A N/A N/A N/A NONE
Documentation References: Notes:<
1) Contract #765, Pg 112-11 Para 15.08 & Pg 112-3, Pa ra 4.01 of 1) 20 minutes at 286*F, 50 minutes attech, spec No. 2. 240*F and continuous at 122*F.
; 2) Qualification, tech spec #2, Cerro Wire & Cable Co. Dated 2) Greater than 20 minutes at 286*F,i 9/20/71, pg 2 of qualification - Post Containment Environmental 240 minutes at 240*F and continuousj Tests. at 122*F.j 3) Franklin Institute Research Lab, Report F-C3050 Dated Hay, 1971.
4) Rockbestos Co. letter dated S/19/80.
.
Facility: Fort Calhoun 1Docket No.: 50-285 -
C-10SYSTEll COMFONENT EVALUATON WORK SiiEET
OtfrSTAND-|F.NVIRONMENT DOCUMENTATON REF. QUALIFI-CATION ING
EQUIPMENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- HETil0D ITEMSParameter cation cation cation cation-
bSystem: Electrical Equipment Operating
Time Note 1 Note 1 1,2 2 Sequential NONEItem No.: W-37,38,39,40,41
42 Cable Tempera- Same asture *F 286*F Oper time 1,2 2 Sequential NONE
Component: N/A PressurePSig 60 PSIg 60 PSIg 1,2 2 Sequential NONE
fianufacturer: Cerro Wire &Cable Co. (Hockhes to:;) Relative
*
flode l No. . N/A litunidity % 100% 100% 1,2 2 Sequential NONE:
Function: Control & Indication Chemical 1900 ppm 1900 ppmfor valves & limit switches Spray Boric Acid Boric Acid 1,2 2 Sequential NONE
Accuracy - Spec: N/ADemon: N/A Radiation 3x10 R 3xlM,R 1,2 2,3 Sequential NONE
6
| Service: See function
Location: Containment & Aux illdg Aging N/A 40 yrs N/A 4 4 NONE
Flood Level Elev: 1000.9' Submer-Above Flood I.evel: Yes gence N/A N/A N/A N/A N/A NONE
Document Lion References: Notes:1) Contract //765, Pg 112-11 Para 15.08 & Pg 112-3, Para 4.01 of 1) 20 mfnutes at 286*F, 50 minutes at
tech. spec No. 2. 240*F and continuous at 122*F.2) Qualification, tech spec //2, Cerro Wire & Cable Co. Dated 2) Greater than 20 minutes at. 286*F,
9/20/71, pg 2 of qualification - Post Containment Environmental 240 minutes at 240*F and continuousTests. at 122*F.
3) Franklin Institute Research Lab, Report F-C3050 Dated May, 1971.4) Rockbestos Co. letter dated 5/19/80.
.
. _ _ __ _ _ ._. ._ __ _ ____ _ _ .
Facility: Fort Calhoun 1'
'
Docket No.: 50-285C-12
,
SYSTEM COMPONENT EVALUATON WORK SilEET,
ENVIRONMENT DOCUMENTATO7 HEF. QUALIFI- OUTSTAND-CATION ING
EQUIPMENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- NET 110D ITEMSPa ramete r cation cation cation cation
System: Electrical Equipment Operating 2Time Note 2 Note 3 1,2 (Note 1) Sequential NOME-
; Item No.: W10 CableTempera- Same asd
ture *F 286 F Oper time 1,2 2 Sequential NONE: '
Component: N/A PressurePSlg 60 PSIg 60 PSIg 1,2 2 Sequential NONE
!!anu f act u re r : Cerro Wire &*
Catele Co. (Rockbestos) Relative
llodel No.: N/A ilumidity % 100% 100% 1,2 2 Sequential NONE
Function: Power cable Chemical 1900 ppm 1900 ppmSpray Boric Acid Boric Acid 1,2 2 Sequeutial NONE
,
'Accuracy - Spec: N/A 6 6
Demon: N/A Radiation 3x10 R 3x10 R 1,2 2,3 Sequential NONE,
Service: !! PSI PPs, cont. vent. &
.; CLG fans, cont. spray PPS.; Location: Containment & Aux Bldg Aging N/A 40 yrs N/A 4 4 NONE
Flood Level Elev: 1000.9' Submer- !'
Above Flood Level: Yes gence N/A N/A N/A N/A N/A NONE
Documentation References: Notes:
1) Contract #765, Pg 112-11 Para 15.08 & Pg 112-3, Para 4.01 of 1) Cable is certified for centinuous duty at;
tech. spec No. 2. cated current to a max. ambient temp of
2) Qualification, tech spec #2, Cerro Wire & Cable Co. Dated 122*F. The cable is rated to operate at
9/20/71, pg 2 of qualification - Post Containment Environmental an emergency overload temp of 240* F forTests. 100 hours /yr or up to 500 hours over the
3) Franklin Institute Research Lab, Report F-C3050 Dated May, 1971. cable life and exhibited no degradation
4) Rockbestos Co. Letter dated 5/19/80. to cable insulation when tested at 286*F.,
,
2) 20 minutes at 286*F, 50 minutes at 240*Fand continuous at 122*F.
'
3) Greater than 20 minutes at 286*F, 500hours at 240*F and continuous at 120*F.
Facility: Fort Calhoun 1Docket No.: 50-285
'
,
l C 2.3SYSTEM COMPONENT EVALUATON WORK SilEET
ENVIRONMENT DOCUMENTATON REF. QUALIFI- OUTSTAND-CATION ING
EQUIPMENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- MET 110D ITEMSPa ramete r cation cation cation cation
System: Electrical Equipment Operating Continuous SequentialTime at 122 F Note 1 1 2,4 Test NONE
Item No.: W-3 CableTempera- Sequentialture *F 286 F 288*F 1 2,4 Test NONE
Component: TRIPLEXED, 1/C-2/0 Pressure Sequential
SKV power cable PSlg 60 PSIg 60 PSIg 1 2,4 Test NONE
flanu f a c tu re r: Anaconda Wire &Calele Co. Relative Sequential'
flodel No. : N/A llumidity % 100% 100% 1 2,4 Test NONE
: Function: Power cable Chemical 1700 ppm 1700 ppm SequentialSpray Boric Acid Boric Acid 1 2.4 Test NONE
Accuracy - Spec: N/A "9"#" '"6 6
Demon: N/A Radiation 3x10 R 3x10 R 1 2.3.4 Test NONE
Service: Lo Press Saf. Inj.PPs & Aux FW pp.
Location: Aux. Bldg. Aging N/A 40 year N/A 5 5 NONE
Flood Level Elev: N/A Submer-Above Flood Level: Yes gence N/A N/A N/A N/A N/A NONE
Documentation References: Notes:1) Enclosure #1 1) Cable has been LOCA qualified but has2) Anaconda certificate of compliance and been installed outside the containment.
Test report #12779 as revised, 9/17/71. Cable is required to operate in the LPSI3) Franklin Institute Research Labs F-C3033, April,1971 pp rooms gt an ambient of 122*F,100%4) Anaconda letter dated 9/16/71 Ril and 10 RADS /IIR.S) Anaconda letter dated S/23/80.
._. . - - -_-. - - - - - -
i| Facility: Fort Calhoun 1
'
Dacket'No.: 50-285
SYSTEM C011PONENT EVALUATON WORK SilEET Enclosureh528
ENVIRONMENT DOCUMENTATON REF. QUALIFI- OUTSTAhD-CATION ING
EQUIPflENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- HETil0D ITEMSParameter cation cation cation cation
System: Note 1 Operating
i Time Note 3 Note 3 1 2 Type Test NONE| Item No.: Note II
! Tempera-ture *F 288*F 346*F 1 2 Type Test NONE
Component: Solenoid PressurePSIg 60 PSIg 110 PSIg 1 2 Type Test NONE
flanufacturer: ASCORelative
Model No.: NP8320A185E Ilumidity % 100% 100% 1 2 Type Test NONE__
Function: Remote Operation of Chemical 1700 ppm 3000 ppevalves Spray Boric Acid Boron 1 2 Type Test NONE
.
Accuracy - Spec: N/A 3x10 R (Ai r) 815x10 R 1 2 Type Test Note 4Demon: N/A Radiation gggg,g{l Rd i
Service: See Function
Location: Containment Aging N/A 4.4 yrs N/A 2 Type Test Note 5
|l Flood Level Elev: 1000.9' Submer-
Above Flood Level: See Note 4 gence Note 4 Note 4 N/A N/A Note 4 NONE ;
Documentation References: Notes:
| 1) Enclosure #1. 1) Systems: Chemical & Volume Control System, liigh Pressurei 2) Asco test report No. AQS21678/TR Safety Injection System, Component Cooling System, Con-'
tainment IIVAC, Steam Generator Feedwater & Blowdown,Sampling System, Nitrogen & Nydrogen System.
NOTES (cont): 2) Item No.: TVC-202 - IICV-238,239,240, 241,2936,2916,2936,2956,2976, 467A,467C,746A, 1387A,1388A,2603B,
4-cont) qualified for submergence. ASCO test 2604B,425A, 425C,204,205, - PCV-742E,742Greports demonstrate that no seat leakage will 3) Once, on receipt of an isolation signaloccur if the valve is deenergized even if the 4) The underlined components listed above may be subject
; solenoid fails. All of the above valves are to submergence. An evaluation is being conducted toi deenergized on receipt of an isolation signal. determine radiation exposure and suitability for the
5) See Enclosure #12. subsequent environment. These valves are considered|
Fecility: Fort Calhoun 1Docket No.: 50-285 .
Enclosureh5 ^SYSTEtt C0t1PONENT EVALUATON WORK SilEET-
--
ENVIRON!!ENT DOCUllENTATON REF. QUALIFI- OUTSTAtt f-CATION ING
EQUIPl!ENT DESCRIPTION Specifi- Qualif- Specifi- Qualifi- METil0D 11 Ells
Parameter cation cation cation cation
Hurmally
System: Waste Disposal Operating LockedTime Closed 2 1 2,3 Type Test NONE
Item No.: ilCV 545~
Tempera-ture *F 268*F 346*F 1 2,3 Type Test NONE
Component: Solenoid PressurePSIg 60 PSIg 110 PSIg 1 2,3 Type Test NONE
Manufacturer: ASCORelative
Model No.: NP8320A185E llumidity % 100% 100% 1 2,3 Type Test NONE
Function: Remote Operation of Chemical 1700 ppm 3000 ppmvalves Spray Boric Acid Horon 1 2,3 Type Test NONE*
---
Accuracy - Spec: N/A 8Demon: N/A Radiation 3x10 R (Air i 15x10 R 1 2,3 Type Test NONE
Service: SI check leakage .
to RC DTLocation: Containment Aging N/A 4.4 yrs N/A 2,3 Type Test NOME
_
Flood Level Elev: 1000.9' Submer-Above Flood Level: Yes gence N/A N/A N/A N/A N/A' NOIII'
_.J
Documentation Referenen: Notes:
1) Enclosure //1.2) Asco test report No. AQS21678/TR3) ASCO repov 177
.
-- _g - , - -- - - - , - , , , , , _ - - -.__ - - +--k.-
'
Fccility: Fort Calhoun 1- Docket No.: 50-285 e
C-0 *
,
SYSTEM COMPONENT EVALUATON WORK SIIEF,T^
lENVIRONMENT DOCUMENTATON REF. QUALIFI- OUTSTANU-'
'CATION ING
EQU(PMENTDESCRIPTION Specifi- Qualif- Specifi- Qualifi- METil0D ITEMS,
Pa rame te r cation cation cation cation
System: liigh Pressure Safety OperatingInjection System Time Continuous Continuous 1 2,3 Synergistic NONE
Item No.: FT 313, FT 316,FT 319, FT 322 Tempera-
t: re *F 288*F 318*F 1 2 Synergistic NONE
Component: Flow Transmitters PressurePSIg 60 PSIg 90 PSIg 1 2 Synergistic NONE
Manufacturer: Foxboro- Relative
Model No.: E13Dit llumidity % 100% 100% 1 2 Synergistic NONENOle 4
Function: . Flow transmitters Chemical 1700 ppm 1700 ppm MaterialllPSI Loops 1A,1B, 2A,2B Spray Boric Acid Boric Acid 1 3 Analysis NONE .
! Accur$cy-Spec: N/A "P'#"
'
6 7Demon: N/A Radiation 3x10 R 1x10 R 1 4 Test NONE
Service: !! PSI Flow Indication
Location: Containment Aging N/A Note 1 N/A Note 1 Note 1 NONE
Flood Level Elev: 1000.9' Submer- Sepa ra teAbove Flood Level: No gence Yes Yes N/A 5 Test NONE
Documentation References: Notes:1) Enclosure #1. 1) See Euclosure #12.2) Foxboro Co. Test Report No. Q9-6005 April 1971 2) See Enclosure #7 Footnote No. 2
' 3) Foxboro Co. Test Report No. T3-10134) Foxboro Co. Test Report No. T3-1097 November 19735) Foxboro Co. Tes.t Report No. T4-6061 -
.
4