NOx and Efficiency Solutions for Boilers -...
Transcript of NOx and Efficiency Solutions for Boilers -...
![Page 1: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/1.jpg)
1
NOx and EfficiencyNOx and EfficiencySolutions for BoilersSolutions for Boilers
Energy Solutions CenterEnergy Solutions CenterLow NOx WorkshopLow NOx Workshop
Cambridge / Markham, OntarioCambridge / Markham, OntarioNovember 13 / 14, 2002November 13 / 14, 2002
![Page 2: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/2.jpg)
2
Presentation OutlinePresentation Outline
¡ Peabody Introduction¡ NOx Trends¡ Peabody NOx Solutions¡ Impact on Efficiency¡ Burner Development Goals¡ Burner Design Features¡ Sample Field Results
Peabody EngineeringPeabody Engineering
• Locations:
• Founded 1920
• Mexico City (JV)
• Toronto, ON
• Norwich, NY
• Shelton, CT
![Page 3: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/3.jpg)
3
Offices, Subsidiaries, Joint Ventures and Licensees
USA
CANADA
MEXICO
BRAZIL
ENGLAND
FRANCE GERMANY
HOLLAND
ITALYSPAIN
SOUTHAFRICA AUSTRALIA
SINGAPORE
KOREA
INDIA
ProductsProductsUtility/Industrial Burners
Low NOx BurnersLow Excess Air Burners
![Page 4: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/4.jpg)
4
ProductsProductsLow Btu Gas/Coal/Kiln Burners
Ignition Systems
Flame ScanningSystems
Fuel Preparation Sets
Air Heaters /Incinerators
In Line Duct Burners
ProductsProductsPackage Burners –
Envirojet
![Page 5: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/5.jpg)
5
Trends in NOx EmissionsTrends in NOx Emissions
Avg. NOx Requirement
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
1998 1999 2000 2001 2002
NO
x,
#/M
MB
TU
Trends in NOx EmissionsTrends in NOx Emissions
Applications Requiring FGR or Steam / Water Injection
0
10
20
30
40
50
60
70
80
90
100
1998 1999 2000 2001 2002
%
![Page 6: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/6.jpg)
6
Factors Influencing NOXFactors Influencing NOXEmissionsEmissions
¡ Heat Input
¡ Combustion Air Temperature
¡ Furnace Volume
¡ Furnace Dimensions
¡ Burner Spacing
¡ Fuel Composition
¡ Fuel Bound Nitrogen
¡ Other Emission Criteria
NONOXX Solutions Solutions
¡Low NOX Burners
¡System Solutions:–Flue Gas Recirculation
–Water/Steam Injection
¡Re-engineering Existing Burner Systems
¡Combination of Above
¡Solution is Boiler Specific
![Page 7: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/7.jpg)
7
Low Emissions = Low EfficiencyLow Emissions = Low EfficiencyLow NOx Burners:
Higher Burner RDLMay operate at higher O2 levelsIncreased fan horsepower
Flue Gas Recirculation:Increased mass flowIncreased system pressure lossesIncreased fan horsepowerBoiler heating surface considerations
Water / Steam Injection:Water/Steam not recoverableLower boiler efficiency
Efficiency ImpactEfficiency Impact
¡ Example:
– For a typical 40,000 PPH Packaged Boiler:
– Fan Motor BHP:– With 15% FGR: 45– Without FGR: 29
– ~50% Horsepower Penalty for FGR
![Page 8: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/8.jpg)
8
Efficiency ImpactEfficiency Impact
¡ What is the cost of:
– 10 Fan HP per installation for FGR• Additional Electrical Costs• Additional Demand for the power provider (and
associated power provider stack emissions)
– 1% Boiler efficiency loss per installation• Additional fuel costs
– Safety issues• Additional controls to assure flame stability
Burner Development GoalsBurner Development Goals¡ Applicable to Firetube or Watertube Boilers
¡ Dual Fuel (Natural Gas and/or Light Oil)
¡ Low NOx capability (30 ppm – natural gas)
¡ Minimize System Pressure Losses (RDL, No FGR)
¡ Maximize Motor Efficiency
¡ Minimize Power Consuming Accessories (Air compressors,silencers, fuel pressure requirements)
¡ Compact Design (Easy fit on the boiler front)
![Page 9: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/9.jpg)
9
ENVIROjet NOx ControlENVIROjet NOx Control
n Primary Combustion Zone
n Vitiation Zone
n Secondary Combustion Zone
n Main Flame
Low NOx Emissions
FLAMEPLATE
FLAMEPLATE
FLAME STABILITY AND GAS JET MIXING ZONES OF THE SL GAS BURNER
IIIIIIIIIIIIIHAMWORTHY
PRIMARY FLAME COMBUSTION PRODUCTSENTRAINED INTO MAIN FLAME ROOT ZONE
VISIBLE MAIN FLAME ENVELOPE
PRIMARY FLAME ENVELOPE
SECONDARY AIR
PRIMARY AIR
PRIMARY
SECONDARY
PRIMARY GAS JETS
MAIN GAS JETENTRAINMENT OF COMBUSTIONPRODUCTS ON OUTSIDE EDGE
OF FLAME ENVELOPE
HOT GASES FROM THE PRIMARY FLAME
PROVIDE A CONTINOUS SOURCE OFIGNITION FOR MAIN FLAME STABILITY
![Page 10: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/10.jpg)
10
EnvirojetEnvirojet
EnvirojetEnvirojet
![Page 11: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/11.jpg)
11
EnvirojetEnvirojet
Envirojet Fan / Motor DesignEnvirojet Fan / Motor Design
¡ Slip Stream Motor Design
– More Efficient– Combustion air passes over motor– No motor cooling fan required
![Page 12: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/12.jpg)
12
Envirojet Fan / Motor DesignEnvirojet Fan / Motor Design
¡ Acoustically Lined Motor Housing
– Provides Noise Levels <85 @ 3 ft.
– Less pressure drop than conventionaldesigns
– More compact
LAYSHAFT BEARINGS
FAN IMPELLER
FAN INLET CONE
AIR INLET
SILENCER
FAN MOTOR
COARSE DAMPER
COUPLING
AIR TO WINDBOX
ENVIROjetENVIROjet
![Page 13: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/13.jpg)
13
Compact DesignCompact Design
¡ “Monoblock” Design
– Integral Fan / Windbox Housing
– Combined Motor Housing / Fan Silencer
– Fan / Windbox Orientation is Rotatable
ENVIROjet BurnerENVIROjet Burner
ELECTRICAL JUNCTION BOX
COMBINED FAN INLET
AND MOTOR SILENCER
OIL PUMP
IGNITION ASSEMBLY
OIL VALVEASSEMBLY
GAS MANIFOLD
SIGHT GLASS
BURNERCOVER
MODULATION MOTOR
![Page 14: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/14.jpg)
14
A I R F L O W F R O MC O M B I N E D F A N A S S E M B L Y
SL DUAL FUEL BURNER COMBUSTION HEAD DIAGRAM
BURNER MOUNTING FLANGE
PRIMARY FLAMEPLATE
OIL NOZZLES
SECONDARYFLAMEPLATE
GAS SPUD
BLAST TUBE
GAS/ELECTRIC IGNITER
PRIMARY AIRSECONDARY AIR
GAS MANIFOLDBURNER COVER
OIL TUBE ASSEMBLY
IGNITER GASCONNECTION
GAS MANIFOLDINLET
WINDBOXIIIIIIIIIIIIIHAMWORTHY
ENVIROjet BurnerENVIROjet Burner
![Page 15: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/15.jpg)
15
Minimize Power ConsumingMinimize Power ConsumingAccessoriesAccessories
¡ Cascade Mechanical Oil Atomizer
– Eliminates Atomizing Steam
– Eliminate Atomizing Air Compressor (HTHWapplications)
Field Results – Park PlaceField Results – Park Place
¡ Park Place Resorts /Las Vegas, NV
– 25,875 PPH WatertubeBoiler
– 33 MMBTU/HR Heat Input
– NOx Requirement: 30 ppm(Natural Gas)
– Fuel Fired: Natural Gas
![Page 16: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/16.jpg)
16
Park PlacePark Place
¡ Equipment Performance:
– NOx Emissions: 24 ppm– FGR: 0 %– CO Emissions: <50 ppm– Fan Motor HP: 25– Noise Level: < 83 dBA @ 3’
Field Results – United HospitalField Results – United Hospital
¡ United Hospital /Clarksburg, WV
– 12,000 PPH WatertubeBoiler
– 16.3 MMBTU/HR Heat Input
– NOx Requirement: 30 ppm(Natural Gas)
– Fuels Fired: Natural Gas / No. 2 Oil
![Page 17: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/17.jpg)
17
United HospitalUnited Hospital
¡ Equipment Performance:
– NOx Emissions (NG): 24 ppm
– NOx Emissions (Oil): 55 ppm– FGR: 0 %– CO Emissions: <25 ppm– Fan Motor HP: 10– Noise Level: < 81 dBA @ 3’
United HospitalUnited Hospital
United HospitalNOx vs. Load
0
5
10
15
20
25
30
10 20 30 40 50 60 70 80 90 100
% MCR
NO
x, p
pm
@3%
O2
![Page 18: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/18.jpg)
18
Field Results - BridgestoneField Results - Bridgestone
¡ Bridgestone Tire / Japan (Retrofit)
– 600 HP Firetube Boiler– 24.6 MMBTU/HR Heat Input– NOx Requirement: 35 ppm (Natural Gas)– Fuels Fired: Natural Gas / No. 2 oil– Variable Speed Drive Fitted
Bridgestone TireBridgestone Tire
¡ Equipment Performance:
– NOx Emissions: 30 ppm (50% Reduction)
– FGR: 0 %– CO Emissions: <50 ppm– Electrical Consumption: 35 % reduction
![Page 19: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/19.jpg)
19
Motor Power Consumption Comparison (Bridgestone Tire)
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60 70 80 90 100
Burner Load %
Fan
Po
wer
(kW
)Envirojet SL8 10 MW Burner fitted
with Variable Speed Fan MotorOriginal Burner
Absorbed Power (kW)
Envirojet SL8/10 Absorbed Power (kW)
NOTES! Information supplied by Independent Source. Tests carried out and reported by end user.Power saving at 100% is due to improved performance by Envirojet fan system over conventional fan system with TEFC motor.
Typical SL8/10 with Conventional Damper
Bridgestone TireBridgestone Tire
SummarySummary
¡ Low NOx possible without FGR or water injection– No Efficiency Penalty:
– Minimal Motor Horsepower– Maximum Motor Efficiency– No Wasted Steam / Water– Maximum Boiler Efficiency
![Page 20: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/20.jpg)
20
Low NOLow NOXX Burner Retrofit Burner RetrofitConsiderationsConsiderations
¡ Fan Static Capability
¡ Furnace Dimensions
¡ Burner Spacing
¡ Windbox Dimensions
¡ Air Flow Distribution
¡ Waterwall Openings
¡ Furnace Conditions
¡ Air / Flue Gas Ductwork Arrangement
MSC LOW NOMSC LOW NOxx BURNER BURNER
¡ Fuel Staging
¡ Air Staging
¡ Precise Flame Fit
![Page 21: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/21.jpg)
21
MSC BurnerMSC BurnerPrecise Flame FitPrecise Flame Fit
¡ Custom Design Flame Geometry to Specific FurnaceDimensions/Burner Spacings
¡ Larger Flame Volume Minimizes Localized HighTemperature Zones
¡ Longer Burnout Minimizes CO Emissions
MSC BurnerMSC BurnerFuel / Air StagingFuel / Air Staging
¡ Creates Fuel/Air Rich and Lean Zones
¡ Reduces Flame Temperature
¡ Minimizes Oxygen Availability to Reduce Thermal NOX
![Page 22: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/22.jpg)
22
MSC BurnerMSC BurnerFeaturesFeatures
¡ Fixed Geometry– No modulating parts
– Cannot be “accidentally” adjusted out of compliance
¡ External Gas Manifold– Eliminates potential for internal ring cracking
– Gas spuds can be removed while firing oil
Case HistoryCase History
¡ Norfolk Naval Station– Background:
• Package Boiler - 150,000 PPH, 250 PSIG, 700OF Steam
• Conversion of an Existing Low NOX Burner Retrofit
• Existing Burner:
– Used 20% Forced FGR
– Could not meet Specified NOX Requirements
– Caused excessive boiler vibration
– Experienced frequent flame instability
![Page 23: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/23.jpg)
23
Norfolk Naval StationNorfolk Naval Station
¡ Peabody Solution– New Precision Flame Shape Low NOx Burner
– Eliminated FGR Fan
– Modified FGR Ducting
Norfolk Naval StationNorfolk Naval StationResultsResults
Guarantees NOx CONatural Gas 66 ppm 134 ppm
No. 2 Oil 78 ppm 128 ppm
Note: Original burner designed for 20% Forced FGR
Actual NOx CONatural Gas (10% IFGR) 20 ppm 9 ppm
Natural Gas (No IFGR) 36 ppm 11 ppm
No. 2 Oil (10% IFGR) 39 ppm 17 ppm
![Page 24: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/24.jpg)
24
Case History:Case History:System SolutionSystem Solution
¡ Background:– Louisiana Paper Mill
• 225 K PPH Stoker Fired Boiler
• Natural Gas Fired
• Four Burners (Arranged 2 over 2)
• 4250F Combustion Air
• Existing NOX Emissions 0.38 #/MMBTU
Louisiana Paper MillLouisiana Paper Mill
¡ Peabody Solution– Installed Four New Low NOX Burners
– Added Steam Atomized Water Injection
![Page 25: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/25.jpg)
25
Louisiana Paper MillLouisiana Paper Mill
¡ Results:– Reduced NOX to 0.23 #/MMBTU with New Burners (39%
Reduction)
– Reduced NOX to .135 #/MMBTU by Adding Water Injection(42% Reduction)
– Overall NOX Reduction of 64%
Case History:Case History:
¡ 705,000 PPH Field Erected Boiler– 963 MMBTU/HR Heat Input
– Six Burners (3 over3)
– Natural Gas
– Ambient Combustion Air
– Replaced Existing Register Style Burners OriginallyFurnished with the Boiler
![Page 26: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/26.jpg)
26
Case HistoryCase History
¡ Peabody Solution– Installed Six New Low NOx Burners
– Reused Existing Windbox (w/o Modeling)
– Reused Existing Waterwall Openings
– Reused Existing Forced Draft Fan (Original Burner RDL lessthan 6” WC)
Case StudyCase Study
¡ Results:– Actual Measured NOX: 0.063 #/MMBTU
– Actual Measured CO: 0.034 #/MMBTU
– Actual Burner RDL: 5.5” WC (@ 10% XS Air)
![Page 27: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/27.jpg)
27
BASF / Beaumont, Texas15% FGR Design - 8% FGR Actual
3334
35363738394041
4243
10 20 30 40 50 60 70 80 90
NO
x, p
pm c
orr.
3%
O2
NOx Guarantee
NOx Actual
Steam Flow, lb/hr
Case History:Case History:
MSC Burner
90,000 PPH
Natural Gas Only
SPSA / Portsmith, VA15% FGR Design / 12% FGR Actual
30
40
50
60
70
80
90
25 50 75 100% MCR
NO
x, p
pm
cor
r. t
o 3%
O2
NOx Guarantee
NOx Actual120,000 PPH BoilerNo. 2 Oil Only
Case History:Case History:
MSC Burner
![Page 28: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/28.jpg)
28
Re-engineeringRe-engineering
¡ Reuse:
– FD / ID Fans
– Windbox
– Register / Ignitor
– Waterwall Openings
– Throat Configuration¡ New:
– Fuel Manifold
– Fuel Nozzles
– Swirler
Re-engineeringRe-engineering
¡ Approach NOX Levels of New Burners
¡ Minimal Impact to Existing Operation
¡ Installation By In-House Personnel
¡ Lowest Installed Cost
¡ Ideal when SCR is a necessity
![Page 29: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/29.jpg)
29
SummarySummary
¡ Low NOX Solution is Boiler Specific
¡ Burner Solutions Can Meet Most Low NOX requirements
¡ Burners / Burner Modifications Can Minimize NOXEntering Post Combustion Apparatus (SCR), thusMinimizing Size of SCR
Contact InformationContact Information
¡ Peabody Engineering Corporation
1000 Bridgeport Avenue
Shelton, CT 06484
Lawrence Berry
National Sales Manager
203-926-1111
www.peabodyengineering.com
![Page 30: NOx and Efficiency Solutions for Boilers - Cleancleanboiler.org/files/2016/09/WS_Smoker_Peabody.pdfGAS SPUD BLAST TUBE GAS/ELECTRIC IGNITER PRIMARY AIR SECONDARY AIR GAS MANIFOLD BURNER](https://reader034.fdocuments.us/reader034/viewer/2022050716/5e39712f962167328276072e/html5/thumbnails/30.jpg)
30
NOx and EfficiencyNOx and EfficiencySolutions for BoilersSolutions for Boilers
Energy Solutions CenterLow NOx Workshop
Cambridge / Markham, OntarioNovember 13 / 14, 2002