NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
SCADA Master
Engineering Workstation
Running WinECP
RS485 Multidrop
DNP3.0 Connection for SCADA Data10-Byte Connection for WinECP
Alternate Configuration
10-Byte RS232 pass through connection for
WinECP
Connection for SCADA Data
Application Note #1004-01R2
Orion Serial-to-Serial Pass-Through to DPU/TPU2000R Relays
The following slides detail how Orion and WinECP must be configured to set up a pass through connection
as shown here
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
Using NovaTech Communication Director (NCD) offline, set up one of the rear ports as an “MMI Interface” port. This is required because the front port on Orion is fixed at 19.2kB and WinECP cannot support a baud rate that high.
Note: Accessing Orion via dial-up or Ethernet is also possible. This note details only direct physical connection via RS232.
Set the comm parameters of the MMI Interface port to the same parameters as the comm port on the PC.
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
Set the comm parameters of the Passthru port to the same parameters as the comm port on the DPU2000R relay
Select “Passthru Interface” on the port where the DPU2000R relay will be attached. Some versions of NCD refer to “Passthru Interface” as “Direct Interface Client”.
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
Pass Through configuration complete. Now download configuration to Orion.
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
While online with Orion in a terminal emulation session, make selections to get to Pass Through mode. Select the port desired for pass through.
When in Pass Through Mode, close out the session, but not using CTRL-X. This will leave the port open for pass through.
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
Open WinECP, select Direct Access
Make sure comm parameters match the ones set on Orion.
Connect.
Note: If multiple DPU2000R units are connected to the Pass Through port on Orion, select desired unit number.
NovaTech Utility Solutions 15541 West 110th Street Lenexa, KS 66219 913-451-1880 www.novatechweb.com
Headquarters Office 3998 Schelden Circle Bethlehem, PA 18017 610-814-2610
DPU2000R should come up on-line, as shown here.