Tel. +48 (12) 636 98 11, 636 12 90, +48 (602) PPGECO Fax. +48 (12) 636 20 02 e-mail: [email protected], http://www.geco.pl GH21PB GH21PB GH21PB GH21PB APPLICATION INSTALATION ON THE BOILER R HEATING CONTROLLERS CHLODNICTWO OGRZEWANIE PROPERTIES The controller for central heating boilers with pellets burners The GH21PB is a controller for central heating boilers with burners prepared to burn wooden pellets. It feeds fuel precisely and controls air flow into the process of burning. With the inclusion of the heater device, flue gas sensor and flame sensor the controller allows automatic flame ignition in case of a fuel burnout. Controller supervises the process of preparing domestic hot water (DHW) and allows to operate main heating circuit (central heating - CH cycle). The GH21PB controller has been fitted for full communication with the GA03HA room panel (manufactured by GECO). Functional visualisation of casing and large readable graphic LCD display. Single-module construction enables comfortable installation on the boiler . Possible to meassure flue gas temperature (PT 1000) Possible of control over two screw feeders: the burner feeder and the container feeder Anit-stagnation protection for the executive devices - ANTI STOP function Desinfection of the DHW cycle (Anti Legionella), DHW priority, Summer mode function. Co-operation with room panel GA03HA (full control of boiler operation from apartament). Adaptation mode regulation which adjust fan rotation to individual boiler dynamics. Control temperature in the burner feeder and flame sensor to ignition mode (option). Sound and text alarm signals. Built -in temperature limiter in standard (STB). Many language versions. Boiler operational parameters archiving function, among others alarm controller record. Soft start of the fan. Possibility of selecting type of controller regulation: ADAPTATION MODE, GRATE MODE. Fan STB Temperature limiter Feeder temp. sensor °C GA03HA Room panel A Flame moving back detection Anti-Legionella 70°C LE ANTY STOP Lighter LE Feeder container Flame sensor DHW Pump °C Flue Gas Temp. °C P.P.U.H. “GECO” Sp. z o.o. Cholerzyn 376 32-060 Liszki, Poland

Transcript of Nota katalogowa GH21PB w01 EN - geco.plFan Temp. limiter (STB) Fan Temp. limiter (STB) Boiler outlet...

Page 1: Nota katalogowa GH21PB w01 EN - geco.plFan Temp. limiter (STB) Fan Temp. limiter (STB) Boiler outlet temp. sensor 59 60 61 +12 V DC Room panel GA03HA A+ GND Controls P1 P2 P4 P3 P5

Tel. +48 (12) 636 98 11, 636 12 90, +48 (602) PPGECO

Fax. +48 (12) 636 20 02

e-mail: [email protected], http://www.geco.pl

GH

21P

BG

H21P

BG

H21P

B

GH21PB

APPLICATION

INSTALATION ON THE BOILER

R

HEATING CONTROLLERSCHŁODNICTWO

OGRZEWANIE

PROPERTIES

The controller for central heatingboilers with pellets burners

The GH21PB is a controller for central heating boilers with burners

prepared to burn wooden pellets. It feeds fuel precisely and controls air

flow into the process of burning.

With the inclusion of the heater device, flue gas sensor and flame sensor

the controller allows automatic flame ignition in case of a fuel burnout.

Controller supervises the process of preparing domestic hot water (DHW)

and allows to operate main heating circuit (central heating - CH cycle).

The GH21PB controller has been fitted for full communication with the

GA03HAroom panel (manufactured by GECO).

Functional visualisation of casing and large readable graphic LCD display.

Single-module construction enables comfortable installation on the boiler .

Possible to meassure flue gas temperature (PT 1000)

Possible of control over two screw feeders: the burner feeder and the container feeder

Anit-stagnation protection for the executive devices - ANTI STOP function

Desinfection of the DHW cycle (Anti Legionella), DHW priority, Summer mode function.

Co-operation with room panel GA03HA (full control of boiler operation from apartament).

Adaptation mode regulation which adjust fan rotation to individual boiler dynamics.

Control temperature in the burner feeder and flame sensor to ignition mode (option).

Sound and text alarm signals.

Built -in temperature limiter in standard (STB).

Many language versions.

Boiler operational parameters archiving function, among others alarm controller record.

Soft start of the fan.

Possibility of selecting type of controller regulation: ADAPTATION MODE, GRATE MODE.

Fan

STB

Temperaturelimiter

Feeder temp.sensor

°C

GA03HARoom panel

A

Flame movingback detection

Anti-Legionella

70°CLE

ANTY

STOP

Lighter

LE

Feeder container

Flame sensor

DHWPump

°C

FlueGasTemp.

°C

P.P.U.H. “GECO” Sp. z o.o.

Cholerzyn 376

32-060 Liszki, Poland

Page 2: Nota katalogowa GH21PB w01 EN - geco.plFan Temp. limiter (STB) Fan Temp. limiter (STB) Boiler outlet temp. sensor 59 60 61 +12 V DC Room panel GA03HA A+ GND Controls P1 P2 P4 P3 P5

DIAGRAM OF CONNECTIONS

THE CONTROL AND HEATING SYSTEM

TECHNICAL DATA

GH

21P

BG

H21P

BG

H21P

B

Diagram of electric connections

Outputs Inputs

50,51

52,53

54,55

56,57

58

Flue gas temp. sensor

B-

Feeder temp. sensor/Thermostat

DHW/Return/Flame sensor/Reed relay

03

01

Lighter

Power supply 230V

04

02

05

06

07

08

09

11

12 15

14 16

Lighter

Power supply 230V

CH pump

CH pump

DHW Pump/Mix Pump

DHW Pump/Mix Pump

Burner feeder

Burner feeder

N

L

L

N

N

L

N

L

N

L

L

N

Fan Temp. limiter (STB)

Fan Temp. limiter (STB)

Boiler outlet temp. sensor

59

60

61 +12 V DC

RoompanelGA03HA

A+

GND

Controls

P1

P2

P4

P3

P5

CH Pump

HUW Pump

Container feeder

Fan

Lighter

Sensors

T1

T2

T4

T3

Boiler temperature

Flue gas temperature

HUW temp./Flame

Feeder temperature

Watercontainer

P5

T1

T3Boiler

cycle DHW cycle CH

T4

P2

P1

Fuelcontainer

P4M

P3

T2

230V AC +10%/ -15%

od +5°C do + 40°C

20% ÷ 80% RH

NTC - range: od 0°C do +100°C

3,15A

°C W

0

10

20

30

40

50

60

70

80

90

100

7174,89

4374,83

2747,10

1774,91

1172,09

795,08

547,95

384,62

275,86

202,37

149,16

1A

1A

1A

1A

3A

250W

250W

250W

250W

750W

Temp. sensor.(PT1000)

°C W

0

50

100

150

200

250

300

350

400

450

500

1000,00

1194,00

1385,10

1573,30

1758,60

1941,00

2120,50

2297,20

2470,90

2641,80

2809,80

550 2974,90

600 3137,10

650 3296,40

700 3452,80

750 3606,40

1000 - ran.:od 0°C do +750°CPT

1) boiler temperature sensor2) flue gas temperature

GH21PB equipment

Standard equipment:

Power supply voltage

Working temperature

Relative humidity

Sensor type

Fan and feeder protection

CH pump

DHW pump/Mix pump/Feeder Container

Burner feeder

Fan

Lighter

Optional equipment:

1) DHW temperature sensor/ Flame sensor2) GA03HA Room panel3) supplying wire4) burner feeder temperature sensor

Controls:

1) CH pump2) DHW pump/ Mix pump/ Container feeder3) fan4) lighter5) burner feeder

Temp. sensor

(NTC) 2,2 kW

Output Constatnt load

Temperaturelimiter

STB

PE stripGH21PB

5058

01

5159 5260 5361 54 55 56 57

02 0503 0604 07 08 1109 10 1312 14 15 16

230V AC

Fuse.

N LN LL N NN LL N L

NTCB- A+ +12VGND

F 3,15A/250V

Imax=10A

01-02 - Power03-04 - Lighter05-06 - C.H. Pump07-08 - D.H.W. Pump/

Mix Pump/Feeder

09-11 - Feeder/Container Feeder

12-14 - Fan15-16 - STB

50-51 - Boiler temp. sensor52-53 - Feeder temperature sensor/

Room thermostat54-55 -56-57 - D.H.W. temp./Return temp.

/Flame sensor/Reed relay58-59-60-61 - Room panel GA03HA

Flue gas temp. sensor