Niky line interactive
Ideal protectionfor all applications
such asSmall-Office
Home-Office. They represent the offer with the best quality/price ratio for the safety of data within the office, your own business and the home PC.Equipped with CPU control, integrated AVR and interfacefor intelligent communication, ensuring optimal protection management.
Advanced management of battery dischargeAVR stabiliser Integrated self-diagnostic functionCold start-up functionIntelligent microprocessor controlRS232 or USB interface for managing the UPSMODEM/LAN telephone protection
®
WWW.UPS.LEGRAND.COM
Niky S line interactive
Sinusoidal outputControl using intelligent microprocessorMODEM/LAN telephone protectionRS-232 and USB interface for managing the UPSCold start-up functionProtection from voltage peaksSelf-test function for the Uninterruptable power unitIntelligent battery managementProtection from overload and short-circuitExcellent voltage adjustment
3 100 133 100 02
NikyUPS Line Interactive - Single-phase VI
600-800 VA 1000-1500 VA
SITE WIRING
FAULT RS232USB
IN OUT
SITE WIRING
FAULT RS232USB
IN OUT
SITE WIRING FAULT
AC INPUT AC OUTPUT
SITE WIRING FAULT
AC INPUT AC OUTPUT
IN OUT
NOTE: back up time values, expressed in minutes, are measured during optimal operating conditions.
Pack. Item UPS with Standard German oUtPUt SocketSNomINAL
PowEr VA
PowEr: ActIVE
w
BAck UP tImE (mIN.)
No. of SockEtS
IEc
No. of SockEtS StANDArD
GErmAN
PortS for
commUNIcAtIoN
3 100 00 600 300 5÷30 - 1 USB3 100 01 800 400 5÷30 - 1 USB
UPS with Standard German oUtPUt SocketS + iec Socket
NomINAL PowEr
VA
PowEr: ActIVE
w
BAck UP tImE (mIN.)
No. of SockEtS
IEc
No. of SockEtS StANDArD
GErmAN
PortS for
commUNIcAtIoN
3 100 09 600 300 5÷30 1 1 USB3 100 10 800 400 5÷30 1 1 USB3 100 13 1000 600 5÷30 2 2 RS2323 100 14 1500 900 5÷30 2 2 RS232
UPS with mUltiPle iec oUtPUt SocketSNomINAL
PowEr VA
PowEr: ActIVE
w
BAck UP tImE (mIN.)
No. of SockEtS
IEc
No. of SockEtS StANDArD
GErmAN
PortS for
commUNIcAtIoN
3 100 02 600 300 5÷30 3 - USB3 100 03 800 400 5÷30 3 - USB3 100 04 1000 600 5÷30 6 - USB3 100 05 1500 900 5÷30 6 - USB
item3 100 003 100 023 100 09
3 100 013 100 033 100 10
3 100 013 100 043 100 13
3 100 053 100 14
General Features
Nominal power (VA) 600 800 1000 1500
Active power (W) 300 400 600 900
Technology Line-interactive VI
Waveform Pseudo-Sinusoidal
input
Input voltage 230 V
Input frequency 50-60 Hz
Input Voltage Range 160V-290V
Output
Output voltage 230V ± 10%
Output frequency (nominal) 50/60 Hz +/-1%
THD Output voltage ‹ 3% with linear load
Batteries
Number of batteries 1 1 2 2
Battery series Type/Voltage 12V, 7Ah 12V, 9Ah 12V, 7Ah 12V, 9Ah
Configuration and Management
Display and SignalsOne push button and 2 LED to monitor UPS
status in real-time.
One push button and 4 LED to monitor UPS
status in real-time
Telephone protection RJ11/RJ45
Remote Management available
Mechanical Features
Dimensions H x W x D (mm) 171x95x349 239x147x354
Net Weight (kg) 7 7,5 13 16
Environmental Conditions
Operating temperature (°C) 0 ÷ 40°C
Relative humidity (%) 0÷95 % non-condensing
Noise level at 1 m (dBA) ‹40
Certifications
Standards EN62040-1, EN62040-2, EN62040-3
Warranty
Standard Warranty 2 years
Pack. Item UPSNomINAL
PowEr VA
PowEr: ActIVE
w
BAck UP tImE (mIN.)
No. of SockEtS
IEc
PortS for
commUNIcAtIoN
3 100 06 1000 600 9 6 USB-RS2323 100 20 1500 900 8 6 USB-RS232 3 100 07 2000 1200 9 6 USB-RS2323 100 08 3000 1800 8 6 USB-RS232
WWW.UPS.LEGRAND.COM
Niky SUPS Line Interactive - Single-phase VI-SS
3 100 06
1000-1500-2000 VA 3000 VA
IN OUT USB RS232 IN OUT USB RS232
NOTE: back up time values, expressed in minutes, are measured during optimal operating conditions.
item 3 100 06 3 100 20 3 100 07 3 100 08
General Features
Nominal power (VA) 1000 1500 2000 3000
Active power (W) 600 900 1200 1800
Technology Line-interactive VI-SS
Waveform Sinusoidal
input
Input voltage 230 V ± 12% on network ± 5% on battery
Input frequency 50-60 Hz
Input Voltage Range 160V-290V
Output
Output voltage 230V ± 10%
Output frequency (nominal) 50/60 Hz +/-0.2%
THD Output voltage ‹ 3% with linear load
Batteries
Number of batteries 2 2 4 4
Type/Voltage battery series 12V, 7Ah 12V, 9Ah 12V, 7Ah 12V, 9Ah
Configuration and Management
Display and Signals Three buttons and three LEDs to monitor the status of the UPS in real time
Telephone protection RJ11/RJ45
Remote Management available
Mechanical Features
Dimensions H x W x D (mm) 242x169x361 242x169x464
Net Weight (kg) 13 15 22 24
Environmental Conditions
Operating temperature (°C) 0 ÷ 40°C
Relative humidity (%) 0÷95 % non-condensing
Noise level at 1 m (dBA) ‹40
Certifications
Standards EN62040-1, EN62040-2, EN62040-3
Warranty
Standard Warranty 2 years