NFPA 780 simplified risk assessment
-
Upload
jose-dariel-arcila -
Category
Technology
-
view
357 -
download
6
description
Transcript of NFPA 780 simplified risk assessment
![Page 1: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/1.jpg)
Designing Lightning Protection Systems
using Sparkta
NFPA 780 Simplified Risk Assessment
http://www.spartalightning.com/
![Page 2: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/2.jpg)
Four Steps
Step 1: Physical modeling
Step 2: Risk assessment without lightning protection. Calculate the yearly lightning strike frequency Nd and the tolerable
lightning frequency Nc. If Nd > Nc the installation of a lightning protection system is recommended. If you decide to install it go
to step 3.
Step 3: Identify the most likely lightning strike points and add air terminals at these points.
Step 4: Calculate the yearly lightning strike frequency to the structure Nd. If Nd > Nc repeat steps 3 and 4.
Lightning Protection Systems Optimal Design (Add… and Evaluate…)
Optimal design is an iterative process which consists of adding one or few air terminals and evaluates the lightning strike
frequency each time.
The air terminals are added in the most likely lightning strike points.
The process stops when the lightning strike frequency is tolerable.
![Page 3: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/3.jpg)
Example 1
Industrial facility with multiple buildings
Isolated structure
Non metallic roofs
Non metallic structures
2 flashes/km2/year
![Page 4: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/4.jpg)
Physical data
Roofs are modeled as quadrilaterals
Other shapes consist of two or more quadrilaterals
Hexagon: 2 quadrilaterals
Octagon: 3 quadrilaterals
Settings for the simulation
![Page 5: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/5.jpg)
Plan view
![Page 6: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/6.jpg)
3D view
![Page 7: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/7.jpg)
Graphic Results
![Page 8: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/8.jpg)
Results
Strikes per year for each range of current Strikes per year for each roof
![Page 9: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/9.jpg)
NFPA 780 Simplified Risk Assessment Using Collection Area Formulas
Collection area calculated for the
highest structure
Collection area calculated for an
equivalent rectangle
![Page 10: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/10.jpg)
NFPA 780 Simplified Risk Assessment Using flashes per year
Flashes per year calculated using the
results of the simulation
The yearly lightning strike frequency Nd is greater than the tolerable lightning frequency Nc – Nd > Nc
Installing a lightning protection system is recommended!!
![Page 11: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/11.jpg)
Identify the most likely lightning strike roofs
Add 4 air terminals and simulate
![Page 12: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/12.jpg)
Graphic Results
![Page 13: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/13.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 14: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/14.jpg)
Identify the most likely lightning strike roofs
Add 18 air terminals and simulate
![Page 15: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/15.jpg)
Graphic Results
![Page 16: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/16.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 17: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/17.jpg)
Identify the most likely lightning strike roofs
Add 3 air terminals and simulate
![Page 18: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/18.jpg)
Graphic Results
![Page 19: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/19.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 20: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/20.jpg)
Identify the most likely lightning strike roofs
Add 2 air terminals and simulate
![Page 21: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/21.jpg)
Graphic Results
![Page 22: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/22.jpg)
Evaluate results
Nd < Nc
No more air terminals are required
![Page 23: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/23.jpg)
Example 1 Final Design
![Page 24: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/24.jpg)
Example 2
The same example 1 facility
Isolated structure
Non metallic roofs
Non metallic structures
10 flashes/km2/year
Settings for the simulation
The design for 10 flashes/km2/year requires more air terminals than the design for 2 flashes/km2/year. So we can begin with the
example’s 1 final design.
![Page 25: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/25.jpg)
Graphic Results
![Page 26: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/26.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 27: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/27.jpg)
Identify the most likely lightning strike roofs
Add 11 air terminals and simulate
![Page 28: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/28.jpg)
Graphic Results
![Page 29: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/29.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 30: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/30.jpg)
Identify the most likely lightning strike roofs
Add 2 air terminals and simulate
![Page 31: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/31.jpg)
Graphic Results
![Page 32: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/32.jpg)
Evaluate results
Nd < Nc
No more air terminals are required
![Page 33: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/33.jpg)
Example 2 Final Design
![Page 34: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/34.jpg)
Example 3
The same example 1 facility
Isolated structure
Non metallic roofs
Non metallic structures
40 flashes/km2/year
Settings for the simulation
The design for 40 flashes/km2/year requires more air terminals than the design for 10 flashes/km2/year. So we can begin with
the example’s 2 final design.
![Page 35: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/35.jpg)
Graphic Results
![Page 36: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/36.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 37: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/37.jpg)
Identify the most likely lightning strike roofs
Add 9 air terminals and simulate
![Page 38: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/38.jpg)
Graphic Results
![Page 39: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/39.jpg)
Evaluate results
Nd > Nc
It is required to install more air
terminals
![Page 40: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/40.jpg)
Identify the most likely lightning strike roofs
Add 5 air terminals and simulate
![Page 41: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/41.jpg)
Graphic Results
![Page 42: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/42.jpg)
Evaluate results
Nd < Nc
No more air terminals are required
![Page 43: NFPA 780 simplified risk assessment](https://reader034.fdocuments.us/reader034/viewer/2022042423/55651862d8b42a08498b46f0/html5/thumbnails/43.jpg)
Example 3 Final Design