NFPA 780 simplified risk assessment

44
Designing Lightning Protection Systems using Sparkta NFPA 780 Simplified Risk Assessment http://www.spartalightning.com/ [email protected]

description

Simplified lightning risk assessment based on NFPA 780 using Sparkta Software.

Transcript of NFPA 780 simplified risk assessment

Page 1: NFPA 780 simplified risk assessment

Designing Lightning Protection Systems

using Sparkta

NFPA 780 Simplified Risk Assessment

http://www.spartalightning.com/

[email protected]

Page 2: NFPA 780 simplified risk assessment

Four Steps

Step 1: Physical modeling

Step 2: Risk assessment without lightning protection. Calculate the yearly lightning strike frequency Nd and the tolerable

lightning frequency Nc. If Nd > Nc the installation of a lightning protection system is recommended. If you decide to install it go

to step 3.

Step 3: Identify the most likely lightning strike points and add air terminals at these points.

Step 4: Calculate the yearly lightning strike frequency to the structure Nd. If Nd > Nc repeat steps 3 and 4.

Lightning Protection Systems Optimal Design (Add… and Evaluate…)

Optimal design is an iterative process which consists of adding one or few air terminals and evaluates the lightning strike

frequency each time.

The air terminals are added in the most likely lightning strike points.

The process stops when the lightning strike frequency is tolerable.

Page 3: NFPA 780 simplified risk assessment

Example 1

Industrial facility with multiple buildings

Isolated structure

Non metallic roofs

Non metallic structures

2 flashes/km2/year

Page 4: NFPA 780 simplified risk assessment

Physical data

Roofs are modeled as quadrilaterals

Other shapes consist of two or more quadrilaterals

Hexagon: 2 quadrilaterals

Octagon: 3 quadrilaterals

Settings for the simulation

Page 5: NFPA 780 simplified risk assessment

Plan view

Page 6: NFPA 780 simplified risk assessment

3D view

Page 7: NFPA 780 simplified risk assessment

Graphic Results

Page 8: NFPA 780 simplified risk assessment

Results

Strikes per year for each range of current Strikes per year for each roof

Page 9: NFPA 780 simplified risk assessment

NFPA 780 Simplified Risk Assessment Using Collection Area Formulas

Collection area calculated for the

highest structure

Collection area calculated for an

equivalent rectangle

Page 10: NFPA 780 simplified risk assessment

NFPA 780 Simplified Risk Assessment Using flashes per year

Flashes per year calculated using the

results of the simulation

The yearly lightning strike frequency Nd is greater than the tolerable lightning frequency Nc – Nd > Nc

Installing a lightning protection system is recommended!!

Page 11: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 4 air terminals and simulate

Page 12: NFPA 780 simplified risk assessment

Graphic Results

Page 13: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 14: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 18 air terminals and simulate

Page 15: NFPA 780 simplified risk assessment

Graphic Results

Page 16: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 17: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 3 air terminals and simulate

Page 18: NFPA 780 simplified risk assessment

Graphic Results

Page 19: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 20: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 2 air terminals and simulate

Page 21: NFPA 780 simplified risk assessment

Graphic Results

Page 22: NFPA 780 simplified risk assessment

Evaluate results

Nd < Nc

No more air terminals are required

Page 23: NFPA 780 simplified risk assessment

Example 1 Final Design

Page 24: NFPA 780 simplified risk assessment

Example 2

The same example 1 facility

Isolated structure

Non metallic roofs

Non metallic structures

10 flashes/km2/year

Settings for the simulation

The design for 10 flashes/km2/year requires more air terminals than the design for 2 flashes/km2/year. So we can begin with the

example’s 1 final design.

Page 25: NFPA 780 simplified risk assessment

Graphic Results

Page 26: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 27: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 11 air terminals and simulate

Page 28: NFPA 780 simplified risk assessment

Graphic Results

Page 29: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 30: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 2 air terminals and simulate

Page 31: NFPA 780 simplified risk assessment

Graphic Results

Page 32: NFPA 780 simplified risk assessment

Evaluate results

Nd < Nc

No more air terminals are required

Page 33: NFPA 780 simplified risk assessment

Example 2 Final Design

Page 34: NFPA 780 simplified risk assessment

Example 3

The same example 1 facility

Isolated structure

Non metallic roofs

Non metallic structures

40 flashes/km2/year

Settings for the simulation

The design for 40 flashes/km2/year requires more air terminals than the design for 10 flashes/km2/year. So we can begin with

the example’s 2 final design.

Page 35: NFPA 780 simplified risk assessment

Graphic Results

Page 36: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 37: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 9 air terminals and simulate

Page 38: NFPA 780 simplified risk assessment

Graphic Results

Page 39: NFPA 780 simplified risk assessment

Evaluate results

Nd > Nc

It is required to install more air

terminals

Page 40: NFPA 780 simplified risk assessment

Identify the most likely lightning strike roofs

Add 5 air terminals and simulate

Page 41: NFPA 780 simplified risk assessment

Graphic Results

Page 42: NFPA 780 simplified risk assessment

Evaluate results

Nd < Nc

No more air terminals are required

Page 43: NFPA 780 simplified risk assessment

Example 3 Final Design

Page 44: NFPA 780 simplified risk assessment

http://www.spartalightning.com/

[email protected]