NFPA 70E COMPLIANCE GUIDE - Electrical Safety...

1
NFPA 70E COMPLIANCE GUIDE The guide shall only be used in conjunction with performing the necessary calculations contained in a flash hazard analysis to determine the proper cal/cM. If the results of the calculations exceed the cal/cM that correspond to the HRC found on this guide, you must use clothing that complies with the calculation. Panelboards Rated 240 V and Below 600 V Class Swithgear (with power circuit NEMA E2 (fused contractor) Motor Starters, Notes 1 breakers or fused switches) Note 5 2.3 kV through 7.2 kV 1 TASK (equipment is energized & work is Y-Rated Y-Rated HRC TASK (equipment Is energized & work Is Y-Rated Y-Rated HRC TASK (equipment is energized & work is Y-Rated Y-Rated I done within the flash protection boundary) Gloves Tools done within the flash protection boundary) Gloves Tools done within the flash protection boundary) Gloves Tools Circuit Breaker (CB) or fused switch CB or fused switch operation with 0 eOnlaClor oneralion with enclosure doors closed N N >tt=O' operation with covers on N N 0 enclosure doors closed N N Reading a panel meter while operating a 0 mo'or <witch N N CB or fused switch operation with covers off N N 0 Reading a panel meter while operating a N N 0 Work on control circuits with exposed live Openinq hinqed covers {to expose live parts N N 0 meter switch parts 120 V or below, exposed Y Y 0 Work on control circuits with exposed live Removal of bolted covers (to expose live parts) N N - parts 120 V or below, exposed Y Y 0 Insertion or removal (racking) a starters N N 4 from cubicles, open or doors closed Perform infrared thermography and other CB or fused switch operation with Contactor operation with enclosure non-contact inspection outside the N N 0 enclosure doors open N N doors open N N 2* restricted approach boundary Remove or install CB's or fused switches Y Y Insertion or removal (racking) of CB's N N 4 Opening hinged covers (to expose live parts N N 3 from cubicles, doors closed Application of safety qrounds, after voltaqe test N N 3 Work on exposed live parts, including voltage testing y y Opening hinged covers (to expose live N N 2 Work on control circuits with exposed live Work on exposed live parts of utilization parts parts> 120 V Y N 3 equipment fed directly by a branch circuit y y Application of safety grounds, after voltage y N 2" Work on exposed live parts, including y y 4 ;:; of the panelboard test voltage testing Panelboards I Switchboards Rated 240 V to 600 V Work on exposed live parts, including y y 2' Removal of bolted covers (to exposed all V voltage testing live parts y (with molded case or insulted case CB's) " Notes 1 Periorm infrared thermography and other TASK (equipment is energized & work Is Y·Rated V-Rated Work on control circuits with exposed live y y 2" non-contact inspection outside the done within the flash protection boundary) Gloves Tools HRC parts> 120 V exposed restricted aocroach boundary N N 3 CB or fused switch ooeration with covers on N N .. Removal of bolted covers (to exposed all N N Insertion or removal (racking) of starter from CB or fused switch oaeration with covers off V N live parts 4 N N 0 Perform infrared thermography and other Perform infrared thermography and other non-contact inspection outside the Metal Clad Switchgear, 1 kV and Aboye restricted aocroach boundarv N N non-contact inspections outside the resisted 2 Work on exposed live parts, including approach boundary N N 2' TASK (equipment is energized & work is Y-Rated Y-Rated HRC voltage testing y y done within the flash protection boundary) Gloves Tools Work on exposed live parts a utilization Reading a panel meter while operating a 0 equipment fed directly by a branch circuit y y 2" Other 600 V Class (277 V to 600 V, nominal) Equipment - Note 2 motor <w;'ch N N of the oanelboard or switchboard I (except as indicatedi Lighting or small ower transformer (600V Max CB operation with enclosure doors closed N N 2 600 V Class Motor Control Centers (MCC's) TASK (equipment is energized & work is Y-Rated Work on control circuits with exposed live y y 2 parts 120 V or below, exposed Notes 2 (expect as indicated I done within the flash protection boundary) Gloves Tools Openinq hinqed covers to expose live parts) N N 3 TASK (equipment is energized & work is Y-Rated V-Rated HRC Opening hinged covers (to expose bare, CB operation with enclosure doors open N N 4 done within the flash protection boundary) Gloves Tools energized parts N N 4 CB or fused switch or starter operation Removal of bolted covers (to expose bare N N with enclosure doors closed N N 0 energized parts N N 2" Removal of bolted covers to exoose live arts N N 4 Reading a panel meter while operating a Application of safely grounds, after ! upenlng vo tage trans ormer or .I.,,;onlro N N 4 N N 0 ower transformer comoartments meter switch voltage test y N 2' Ap Jication of safety arounds, after voltaae test Y N 4 Work on control circuits with exposed live y y 0 Work on exposed live parts, including :Work on exposed ive parts, Inc udlng 4 parts 120 V or below, exposed voltage testing Y y CB or fused switch or starter operation I voltage testing y y 2" on control Circuits with exposed live 4 with enclosure doors open N N Other 600 V Class (277 V to 600 V, Nom.) Equip. Revenue arts> 120 V exposed y y Opening hinged covers (to expose live parts) N N Perform infrared thermography and other meters (kWH at primary voltage & current) non-contact inspections outside the 0 Perform infrared thermography and other TASK (equipment Is energized & work is Y-Rated restricted approach boundary N N non-contact inspection outside the restricted approach boundary N N done within the ftash protection boundary) Gloves Tools Are Resistant Swichgear type 1 or 2(For clearing time of <0.5 sec wiirr..J Removal of bolted covers (to expose live parts) N N Cable trough or tray cover removal or perspective faull current not to exceed the Arc Resistant rating of the equipment) Application of safet f grounds, after voltage test V N 2' installation N N TASK {equipment is energized & work is Y-Rated Y·Rated Work on exposed live parts, including Miscellaneous equipment cover removal done within the flash protection boundary} Gloves Tools HRC voltaae testina Y Y 2" or installation N N 8 operation with door closed N N 0 Work on control circuits with live parts y y Application of safety grounds, after 2" Insertion or removal (racking) of CBs from -- > 120 V exposed 2" voltage test Y N cubicles door closed N N Insertion or removal of individual starter 4 Work on exposed live parts, inclUding Insertion or removal (racking) of CBs from "buckets" from MCC - Note 4 y N Y Y 2' cubicles, door ooen N N Work on exposed live parts of utilization voltage testing Work on control circuits with exposed live equipment fed directly by a branch circuit y y 2" Insertion or removal y N 2" Iparts 120V or below Y Y .2 of the motor control center Insertion or removal (racking) of ground 0 to<t rlAV;CO wi' h <innr do"orl N N Minimum Clothing Requirement Insertion or removal (racking) of voltage N N 0 HRC Protective Clothing Minimum PPE (Safety glasses, leather safety shoes required for all) Other Equipment 1kV and Aboye Metal enclosed Cal/cm 2 Natural fiber long·sleeved shirt and pants OR 1 layer, interrupter switch gear, fused or unfused 0 Non-melting, flammable materials (i.e., untreated cotton, N/A Hard Hat TASK (equipment is energized & work is Y-Rated Y-Rated HRC wool, rayon, or silk, or blends of these materials) with a done within the flash protection boundary) Gloves Tools fabric weight at least 4.5 oZ.lyd2 See 130.7(C)(11). witch operation, doors closed N N 2 Denim jeans and FR long-sleeved shirt OR Jacket, 4 Hard Hat, Arc-Rated Face Shield" Leather Gloves Outdoor disconnect switch operation 2 parka or rainwear (gang-operated, from grade) y N FR 10nQ-sleeved shirt and pants OR FR coveralls Insulated cable exam, in open area y N :.! FR long-sleeved shirt and pants OR FR coveralls Hard Hat, Arc-Rated Face Shield, OR Flash Suit Hood, Hearing Opening hinged covers (to exposed 2 Jacket, parka or ralnwear 8 Protection, Leather Gloves live parts) N N 3 2' FR long-sleeved shirt and pants OR FR coveralls 8 switc operatlOn 'I Jacket, parka or rainwear (hookstick operated) y y Multi-Layer flash suit over FR long-sleeved shirt and bOlted covers (to expose 4 3 pants over natural fiber short-sleeved T-shirt and pants Hard Hat, Multi-Layer SWitching Hood, Hearing Protection, Leather live parts N N OR Multi-Layer flash suit over FR coveralls over natural in manhole or fiber short-sleeved T-shirt and pants, OR 3 layers, Cotton 25 Gloves y N 4 underwear Ius two FR coveralls. See 130. 7(C)(11) Work on exposed live parts, including Multi-Layer flash suit Jacket & Pants (overalls) over FR voltaae testina Y y 4 I'. 4 long-sleeved shirt and pants over natural fiber short-sleeved Hard Hat, Multi-Layer Switching Hood, Hearing Protection, Leather T-shirt and pants OR Multi-Layer flash suit Jacket & Pants Gloves Switch operation of arc-resistant (overalls) over FR coveralls over natural fiber short-sleeved 40 construction, tested in accordance ttflli T-shirt and pants, OR 3 layers, Cotton underwear plus FR with IEEE C37.20.7, doors closed only N N shirt & FR oanls olus multi-laver flash suit. See 130.7IC111 * If Ib' nel" Sannel be ,atjf'jed, werk my" bp pertgrwsd ds.eDsrgi,od Rs'ip"iep'· y=!e, 'Repyjred) V-Rated Gloves: gloves rated and tested for the maximum line-to-Iine voltage upon Note 1 Maximum of 25 kA short circuit current available, 'and maximum of 0.03 second (2 cycle) fault clearing time. which work will be done. Leather protectors must be worn externally if v-rated rubber Note 2 Maximum of 65 kA short circuit current available, • and maximum of 0.03 second (2 cycle) fault clearing time. gloves could be damaged. Note 3 For < 10 kA short circuit current available, the HRC required may be reduced by one category. V-Rated Toofs : tools rated and tested for the maximum line -to-line voltage pon which work will be done, if manufactured and tested in accordance w· h ASTM F" .... - Note 4 Maximum of 42 kA short circuit current available, ' and maximum of 0.33 second (20 cycle) fault clearing time. For systems rated Jess than 1000 volts, the fault currents and upstream protective u.Te Note 5 Maximum of 35 kA short circuit current available, "< and maximum of 0.5 second (30 cycle) fault clearing time. based on an l8-inch working distance. - For systems rated 1 KV and greater, The HazardlAisk Categories are based on a 36·incn Vt'OOOng :leE: Note 6 For < 25 kA short circuit current available, the HRC required may be reduced by one category. For equipment protected by upstream current lirnitirlQ fuses with arcing fault current III 'Circuits over 40cal/cm2 should only be worked de-energized. range (112 cycle fault clearing time or less), the hazardfrisk category required may be reaucsrl ':Jy HRC : Hazard Risk Cat""orv Y:Yes N:No FR:Ra I

Transcript of NFPA 70E COMPLIANCE GUIDE - Electrical Safety...

Page 1: NFPA 70E COMPLIANCE GUIDE - Electrical Safety Supplyelectricalsafetysupply.com/ckfinder/userfiles/files/NFPA... · 2017-01-16 · NFPA 70E COMPLIANCE GUIDE The guide shall only be

NFPA 70E COMPLIANCE GUIDE The guide shall only be used in conjunction with performing the necessary calculations contained in a flash hazard analysis to determine the proper cal/cM. If the

results of the calculations exceed the cal/cM that correspond to the HRC found on this guide, you must use clothing that complies with the calculation.

Panelboards Rated 240 V and Below 600 V Class Swithgear (with power circuit NEMA E2 (fused contractor) Motor Starters, • Notes 1 breakers or fused switches) • Note 5 2.3 kV through 7.2 kV

1TASK (equipment is energized & work is Y-Rated Y-Rated HRC TASK (equipment Is energized & work Is Y-Rated Y-Rated HRC TASK (equipment is energized & work is Y-Rated Y-Rated Idone within the flash protection boundary) Gloves Tools done within the flash protection boundary) Gloves Tools done within the flash protection boundary) Gloves Tools

Circuit Breaker (CB) or fused switch CB or fused switch operation with 0 eOnlaClor oneralion with enclosure doors closed N N >tt=O'

operation with covers on N N 0 enclosure doors closed N N Reading a panel meter while operating a 0mo'or <witch N N

CB or fused switch operation with covers off N N 0 Reading a panel meter while operating a N N 0 Work on control circuits with exposed live

Openinq hinqed covers {to expose live parts N N 0 meter switch parts 120 V or below, exposed Y Y 0 Work on control circuits with exposed live

Removal of bolted covers (to expose live parts) N N - parts 120 V or below, exposed Y Y 0 Insertion or removal (racking) a starters N N 4from cubicles, open or doors closed

Perform infrared thermography and other CB or fused switch operation with Contactor operation with enclosure non-contact inspection outside the N N 0 enclosure doors open N N doors open N N 2*restricted approach boundary

Remove or install CB's or fused switches Y Y Insertion or removal (racking) of CB's

N N 4 Opening hinged covers (to expose live parts N N 3 from cubicles, doors closed Application of safety qrounds, after voltaqe test N N 3

Work on exposed live parts, including voltage testing y y Opening hinged covers (to expose live N N 2 Work on control circuits with exposed live Work on exposed live parts of utilization parts parts> 120 V Y N 3 equipment fed directly by a branch circuit y y Application of safety grounds, after voltage y N 2" Work on exposed live parts, including

y y 4 ;:;of the panelboard test voltage testing

Panelboards I Switchboards Rated 240 V to 600 V Work on exposed live parts, including y y 2'

Removal of bolted covers (to exposed all V 4"~voltage testing live parts y

(with molded case or insulted case CB's) " Notes 1 Periorm infrared thermography and other

TASK (equipment is energized & work Is Y·Rated V-Rated Work on control circuits with exposed live y y 2" non-contact inspection outside the

done within the flash protection boundary) Gloves Tools HRC parts> 120 V exposed restricted aocroach boundary N N 3 CB or fused switch ooeration with covers on N N .. Removal of bolted covers (to exposed all N N Insertion or removal (racking) of starter from

CB or fused switch oaeration with covers off V N live parts 4 ~u~~~~~~r.~~r~~~~~n~~~~2~r~c~~~ t~~~~~ N N 0 Perform infrared thermography and other

Perform infrared thermography and other non-contact inspection outside the Metal Clad Switchgear, 1 kV and Aboyerestricted aocroach boundarv N N non-contact inspections outside the resisted 2 Work on exposed live parts, including approach boundary N N

2' TASK (equipment is energized & work is Y-Rated Y-Rated HRCvoltage testing y y done within the flash protection boundary) Gloves Tools Work on exposed live parts a utilization Reading a panel meter while operating a 0equipment fed directly by a branch circuit y y 2" Other 600 V Class (277 V to 600 V, nominal) Equipment - Note 2 motor <w;'ch N N of the oanelboard or switchboard I(except as indicatedi Lighting or small ower transformer (600V Max CB operation with enclosure doors closed N N 2

600 V Class Motor Control Centers (MCC's) TASK (equipment is energized & work is Y-Rated v.~~. Work on control circuits with exposed live y y 2parts 120 V or below, exposed

• Notes 2 (expect as indicated I done within the flash protection boundary) Gloves Tools Openinq hinqed covers to expose live parts) N N 3 TASK (equipment is energized & work is Y-Rated V-Rated HRC Opening hinged covers (to expose bare, CB operation with enclosure doors open N N 4 done within the flash protection boundary) Gloves Tools energized parts N N f~~~rt~~~i6re~d~~~ ~~~n'~~)cf~s~~·s 4 CB or fused switch or starter operation Removal of bolted covers (to expose bare N N with enclosure doors closed N N 0 energized parts N N 2" Removal of bolted covers to exoose live arts N N 4

Reading a panel meter while operating a Application of safely grounds, after !upenlng vo tage trans ormer or .I.,,;onlro

N N 4 N N 0 ower transformer comoartments

meter switch voltage test y N 2' Ap Jication of safety arounds, after voltaae test Y N 4 Work on control circuits with exposed live

y y 0 Work on exposed live parts, including :Work on exposed ive parts, Inc udlng 4parts 120 V or below, exposed voltage testing Y y CB or fused switch or starter operation

I voltage testing y y 2"

Wo~k on control Circuits with exposed live 4with enclosure doors open N N Other 600 V Class (277 V to 600 V, Nom.) Equip. Revenue

arts> 120 V exposed y y Opening hinged covers (to expose live parts) N N Perform infrared thermography and other

meters (kWH at primary voltage & current) non-contact inspections outside the 0Perform infrared thermography and other TASK (equipment Is energized & work is Y-Rated

V~-i restricted approach boundary N N

non-contact inspection outside the restricted approach boundary N N done within the ftash protection boundary) Gloves Tools Are Resistant Swichgear type 1or 2(For clearing time of <0.5 sec wiirr..J Removal of bolted covers (to expose live parts) N N Cable trough or tray cover removal or perspective faull current not to exceed the Arc Resistant rating of the equipment) Application of safet f grounds, after voltage test V N 2' installation N N TASK {equipment is energized & work is Y-Rated Y·Rated Work on exposed live parts, including Miscellaneous equipment cover removal done within the flash protection boundary} Gloves Tools HRC voltaae testina Y Y 2" or installation N N 8 operation with door closed N N 0 Work on control circuits with live parts y y Application of safety grounds, after 2" Insertion or removal (racking) of CBs from -­> 120 V exposed 2" voltage test Y N cubicles door closed N N Insertion or removal of individual starter 4 Work on exposed live parts, inclUding Insertion or removal (racking) of CBs from "buckets" from MCC - Note 4 y N Y Y 2' cubicles, door ooen N N Work on exposed live parts of utilization

voltage testing Work on control circuits with exposed live

equipment fed directly by a branch circuit y y 2" Insertion or removal y N 2" Iparts 120V or below Y Y .2 of the motor control center Insertion or removal (racking) of ground 0

to<t rlAV;CO wi' h <innr do"orl N N Minimum Clothing Requirement Insertion or removal (racking) of voltage

N N 0

HRC Protective Clothing Minimum PPE (Safety glasses, leather safety shoes required for all) Other Equipment 1kV and Aboye • Metal enclosedCal/cm2

Natural fiber long·sleeved shirt and pants OR 1 layer, interrupter switch gear, fused or unfused

0 Non-melting, flammable materials (i.e., untreated cotton, N/A Hard Hat TASK (equipment is energized & work is Y-Rated Y-Rated HRC

wool, rayon, or silk, or blends of these materials) with a done within the flash protection boundary) Gloves Tools fabric weight at least 4.5 oZ.lyd2 See 130.7(C)(11). witch operation, doors closed N N 2 Denim jeans and FR long-sleeved shirt OR Jacket,

4 Hard Hat, Arc-Rated Face Shield" Leather Gloves Outdoor disconnect switch operation 2

parka or rainwear (gang-operated, from grade) y N FR 10nQ-sleeved shirt and pants OR FR coveralls Insulated cable exam, in open area y N :.! FR long-sleeved shirt and pants OR FR coveralls Hard Hat, Arc-Rated Face Shield, OR Flash Suit Hood, Hearing Opening hinged covers (to exposed

2 Jacket, parka or ralnwear 8 Protection, Leather Gloves live parts) N N 3 2' FR long-sleeved shirt and pants OR FR coveralls

8 ~~~d8~~~ic~:~ng:~~I~~~i(~~~~Ch~~? 6~c~~~~t~v;re~~i~~h?~~V~~d ~ut~oo~ ~llsconnect switc operatlOn

'IJacket, parka or rainwear (hookstick operated) y y ~ Multi-Layer flash suit over FR long-sleeved shirt and f.lemov~~t bOlted covers (to expose

4

~ 3 pants over natural fiber short-sleeved T-shirt and pants

Hard Hat, Multi-Layer SWitching Hood, Hearing Protection, Leather live parts N N

OR Multi-Layer flash suit over FR coveralls over natural ~~~~~a6~~fT;~~es~~~~ination, in manhole or fiber short-sleeved T-shirt and pants, OR 3 layers, Cotton 25 Gloves y N 4

underwear Ius two FR coveralls. See 130.7(C)(11) Work on exposed live parts, including Multi-Layer flash suit Jacket & Pants (overalls) over FR voltaae testina Y y 4 I'.

4 long-sleeved shirt and pants over natural fiber short-sleeved Hard Hat, Multi-Layer Switching Hood, Hearing Protection, Leather T-shirt and pants OR Multi-Layer flash suit Jacket & Pants Gloves

Switch operation of arc-resistant (overalls) over FR coveralls over natural fiber short-sleeved

40 construction, tested in accordance

ttflliT-shirt and pants, OR 3 layers, Cotton underwear plus FR with IEEE C37.20.7, doors closed only N Nshirt & FR oanls olus multi-laver flash suit. See 130.7IC111 •

* If Ib' nel" Sannel be ,atjf'jed, werk my" bp pertgrwsd ds.eDsrgi,od Rs'ip"iep'· y=!e, 'Repyjred) V-Rated Gloves: gloves rated and tested for the maximum line-to-Iine voltage upon

Note 1 Maximum of 25 kA short circuit current available, 'and maximum of 0.03 second (2 cycle) fault clearing time. which work will be done. Leather protectors must be worn externally if v-rated rubber

Note 2 Maximum of 65 kA short circuit current available, • and maximum of 0.03 second (2 cycle) fault clearing time. gloves could be damaged.

Note 3 For < 10 kA short circuit current available, the HRC required may be reduced by one category. V-Rated Toofs : tools rated and tested for the maximum line -to-line voltage pon which work will be done, if manufactured and tested in accordance w· h ASTM F" .... ­

Note 4 Maximum of 42 kA short circuit current available, ' and maximum of 0.33 second (20 cycle) fault clearing time. For systems rated Jess than 1000 volts, the fault currents and upstream protective devies~.,anng u.Te

Note 5 Maximum of 35 kA short circuit current available, "< and maximum of 0.5 second (30 cycle) fault clearing time. based on an l8-inch working distance. ~ - For systems rated 1KV and greater, The HazardlAisk Categories are based on a 36·incn Vt'OOOng :leE:

Note 6 For < 25 kA short circuit current available, the HRC required may be reduced by one category. For equipment protected by upstream current lirnitirlQ fuses with arcing fault current III J"~d

'Circuits over 40cal/cm2 should only be worked de-energized. range (112 cycle fault clearing time or less), the hazardfrisk category required may be reaucsrl ':Jy _tlJ!'"~

HRC : Hazard Risk Cat""orv Y:Yes N:No FR:Ra

~ ~

I