NFPA 4-7

download NFPA 4-7

of 2

Transcript of NFPA 4-7

  • 8/12/2019 NFPA 4-7

    1/2

    SECTION 4.7* FIRE DRILLS

    4.7.1 Where Required. Emergency egress and relocation drills conforming to the

    provisions of this Codeshall be conducted as specified by the provisions of Chapters 11

    through 42, or by appropriate action of the authority having jurisdiction. Drills shall be

    designed in cooperation with the local authorities.

    4.7.2* Drill Frequency. Emergency egress and relocation drills, where required by

    Chapters 11 through 42 or the authority having jurisdiction, shall be held with sufficient

    frequency to familiarize occupants with the drill procedure and to establish conduct of the

    drill as a matter of routine. Drills shall include suitable procedures to ensure that all persons

    subject to the drill participate.

    4.7.3 Competency. Responsibility for the planning and conduct of drills shall be

    assigned only to competent persons qualified to exercise leadership.

    4.7.4 Orderly Evacuation. In the conduct of drills, emphasis shall be placed on

    orderly evacuation rather than on speed.4.7.5* Simulated Conditions. Drills shall be held at expected and unexpected

    times and under varying conditions to simulate the unusual conditions that can occur in an

    actual emergency.

    4.7.6 Relocation Area. Drills participants shall relocate to a predetermined

    location and remain at such location until a recall or dismissal signal is given.

    14.7.1 Emergency Egress and Relocation Drills.

    14.7.1.1*Emergency egress and relocation drills shall be conducted in accordancewith Section 4.7 and the applicable provisions of 14.7.1.2.

    14.7.1.2Emergency egress and relocation drills shall be conducted as follows:

    1. Not less than one emergency egress and relocation drill shall be conducted everymonth the facility is in session.

    Exception: In climates where the weather is severe, the monthly emergency egress

    and relocation drills shall be permitted to be deferred, provided that the required

    number of emergency egress and relocation drills in achieved and not less than

    four are conducted before the drills are deferred.2. All occupants of the building shall participate in the drill.3. One additional emergency egress and relocation drill, other than for educational

    occupances that are open on a year-round basis, shall be required within the first

    30 days of operation.

  • 8/12/2019 NFPA 4-7

    2/2

    14.7.1.3All emergency and relocation drill alarms shall be sounded on the fire alarm

    system.

    101-12814.7.2 Inspection.

    14.7.2.1*It shall be the duty of principals and teachers to inspect all exit facilities

    daily to ensure that all stairways, doors, and other exits are in proper condition.

    14.7.2.2Open plan buildings shall require extra surveillance to ensure that exit paths

    are maintained clear of obstruction and are obvious.

    14.7.3 Furnishings and Decorations.

    14.7.3.1Draperies, curtains, and other similar furnishings and decorations in

    educational occupancies shall be in accordance with the provisions of 10.3.1.

    14.7.3.2Clothing and personal effects shall not be stored in corridors.

    Exception No. 1: This requirement shall not apply to corridors protected by an

    automatic sprinkler system in accordance with Section 9.7.

    Exception No. 2: This requirement shall not apply to corridor areas protected by asmoke detection system in accordance with Section 9.6.

    Exception No. 3: This requirement shall not apply to storage in metal lockers,

    provided that the required egress width is maintained.

    14.7.3.3Artwork and teaching materials shall be permitted to be attached directly to

    the walls and shall not exceed 20 percent of the wall area.