NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section...

8
TECHNOLOGY DRAWING LIST T100 DWG# TITLE COVER PAGE T101 EXISTING DEVICES T102 NEW COUNCIL CHAMBER LAYOUT T103 SECTIONS T104 WORKSPACE DETAILS T105 EQUIPMENT DETAILS T200 AV SYSTEMS SCHEMATIC 1. ELECTRICAL NON-METALLIC TUBING (ENT, COMMONLY REFERRED TO AS "CORELINE") IS NOT ACCEPTABLE. 2. CONTRACTOR TO PROVIDE COVERS ON ALL JUNCTION BOXES, A PULL STRING IN ALL INSTALLED CONDUITS, AND NYLON GROMMETS ON ALL CONDUIT STUBS. 3. PROVIDE NYLON BUSHINGS FOR CONDUITS, COVERS FOR ALL JUNCTION BOXES AND PULLSTRINGS IN ALL EMPTY CONDUITS. 12 025( 7+$1 %(1'6 %(7:((1 -81&7,21 %2;(6 )25 $// $9 &21'8,76 5()(5 TO TIA STANDARDS FOR MINIMUM BEND RADIUS ON ALL CONDUITS. 5. PROVIDE SEISMIC RESTRAINT AS REQUIRED BY LOCAL BUILDING CODE. PROVIDE SEISMIC REVIEW BY SEISMIC PROFESSIONAL ENGINEER. SUBMIT SIGNED AND SEALED REVIEW REPORT WITH OPERATIONS AND MAINTENANCE MANUALS. 6. PROVIDE FIRE STOPPING AS REQUIRED BY LOCAL BUILDING CODE. FIRE STOPPING ASSEMBLY MUST BE RATED AS SUCH TO MAINTAIN THE FIRE RATING WHERE THE PENETRATION OCCURS. CONSULT WITH FIRE STOPPING EXPERT TO REVIEW FIRESTOPPING INSTALLATION. SUBMIT REVIEW REPORT WITH THE OPERATIONS AND MAINTENANCE MANUAL. 7. ALL SURFACE MOUNT AV EQUIPMENT REQUIRES SUFFICIENT BACKING. INSTALLATION MUST CONFORM TO BC BUILDING CODE. TYPICAL VOICE/DATA WALL OUTLET. TECHNOLOGY SYMBOL SCHEDULE 1. FREE AIR RUNNING OF CABLES WITHIN ACCESSIBLE DROP CEILING SPACES IS ACCEPTABLE. PROVIDE J-HOOKS TO SUPPORT THE CABLES. ALL CABLES MUST BE FT6 RATED. 2. ALL CABLING FOR AV AND AV CONTROL SYSTEM DEVICES TO BE SUPPLIED AND INSTALLED BY AV CONTRACTOR. AV WIRING NOTES FB CAM EXISTING PTZ CAMERA EXISTING FLOORBOX EXISTING CEILING MOUNT PROJECTOR EXISTING CEILING MOUNT PROJECTOR SCREEN IP CAM EXISTING IP CAMERA WIDE ANGLE PTZ CAMERA CEILING MOUNT PROJECTOR CEILING MOUNT PROJECTOR SCREEN LONG THROW PTZ CAMERA EXISTING IP CAMERA TO REMAIN GENERAL NOTES MICROPHONE STATION BACKUP MICROPHONE TOUCH PANEL AV INPUT PLATE T FLOORBOX 1 3 IP 80" LCD MONITOR 1. ALL FASTENING LOCATIONS MUST HAVE SCANS TO LOCATE. RE-BAR PRIOR TO INSTALL. 2. FOR SCANNING OF ALL FASTENING BOLT LOCATIONS, CUTTING AND CORING, AV CONTRACTOR MUST BE CO-ORDINATE WITH SCANNING CONTRACTOR. 3. ALL MOUNTING LOCATIONS MUST BE APPROVED BY STRUCTURAL ENGINEER. AV MOUNTING NOTES 1. LOCATIONS OF AV DEVICES IN MILLWORK MUST BE CONFIRMED ON SITE WITH OWNER'S REPRESENTATIVE. 2. MILLWORK CUTOUTS ARE TO BE COMPLETED BY MILLWORK CONTRACTOR. MILLWORK NOTES NAME OF PROJECT: NEW WESTMINSTER CITY HALL COUNCIL CHAMBER CIVIC ADDRESS: 511 ROYAL AVENUE NEW WESTMINSTER, BC V3L 1H9. PROJECT INFORMATION T201 AV CONTROL SYSTEMS CEILING SPEAKER COUNCIL CHAMBERS NEW WESTMINSTER CITY HALL AV SYSTEMS REV DESCRIPTION BY DATE Drawing scale may be affected by printing, scanning or copying. - ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council Chambers CITY OF NEW WESTMINSTER - ISSUED FOR 95% REVIEW ACUMEN 2015-06-17 - ISSUED FOR TENDER ONLY ACUMEN 2015-06-19 650-2700 PRODUCTION WAY BURNABY, BC V5A 4X1 PH.604.676.9545 ACUMENENGINEERING.CA THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTY OF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT; AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT AND DESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD. COVER COUNCIL CHAMBERS T100

Transcript of NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section...

Page 1: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

TECHNOLOGYDRAWING LIST

T100

DWG# TITLE

COVER PAGE

T101 EXISTING DEVICES

T102 NEW COUNCIL CHAMBER LAYOUT

T103 SECTIONS

T104 WORKSPACE DETAILS

T105 EQUIPMENT DETAILS

T200 AV SYSTEMS SCHEMATIC

1. ELECTRICAL NON-METALLIC TUBING (ENT, COMMONLY REFERRED TO AS "CORELINE") ISNOT ACCEPTABLE.

2. CONTRACTOR TO PROVIDE COVERS ON ALL JUNCTION BOXES, A PULL STRING IN ALLINSTALLED CONDUITS, AND NYLON GROMMETS ON ALL CONDUIT STUBS.

3. PROVIDE NYLON BUSHINGS FOR CONDUITS, COVERS FOR ALL JUNCTION BOXES ANDPULLSTRINGS IN ALL EMPTY CONDUITS.

4. NO MORE THAN (3) 90° BENDS BETWEEN JUNCTION BOXES FOR ALL A/V CONDUITS. REFERTO TIA STANDARDS FOR MINIMUM BEND RADIUS ON ALL CONDUITS.

5. PROVIDE SEISMIC RESTRAINT AS REQUIRED BY LOCAL BUILDING CODE. PROVIDE SEISMICREVIEW BY SEISMIC PROFESSIONAL ENGINEER. SUBMIT SIGNED AND SEALED REVIEWREPORT WITH OPERATIONS AND MAINTENANCE MANUALS.

6. PROVIDE FIRE STOPPING AS REQUIRED BY LOCAL BUILDING CODE. FIRE STOPPINGASSEMBLY MUST BE RATED AS SUCH TO MAINTAIN THE FIRE RATING WHERE THEPENETRATION OCCURS. CONSULT WITH FIRE STOPPING EXPERT TO REVIEW FIRESTOPPINGINSTALLATION. SUBMIT REVIEW REPORT WITH THE OPERATIONS AND MAINTENANCEMANUAL.

7. ALL SURFACE MOUNT AV EQUIPMENT REQUIRES SUFFICIENT BACKING.INSTALLATION MUST CONFORM TO BC BUILDING CODE.

TYPICAL VOICE/DATA WALL OUTLET.

TECHNOLOGY SYMBOL SCHEDULE

1. FREE AIR RUNNING OF CABLES WITHIN ACCESSIBLE DROP CEILING SPACES ISACCEPTABLE. PROVIDE J-HOOKS TO SUPPORT THE CABLES. ALL CABLES MUST BEFT6 RATED.

2. ALL CABLING FOR AV AND AV CONTROL SYSTEM DEVICES TO BE SUPPLIED ANDINSTALLED BY AV CONTRACTOR.

AV WIRING NOTES

FB

CAM EXISTING PTZ CAMERA

EXISTING FLOORBOX

EXISTING CEILING MOUNT PROJECTOR

EXISTING CEILING MOUNT PROJECTORSCREEN

IPCAM

EXISTING IP CAMERA

WIDE ANGLE PTZ CAMERA

CEILING MOUNT PROJECTOR

CEILING MOUNT PROJECTOR SCREEN

LONG THROW PTZ CAMERA

EXISTING IP CAMERA TO REMAIN

GENERAL NOTES

MICROPHONE STATION

BACKUP MICROPHONE

TOUCH PANEL

AV INPUT PLATE

T

FLOORBOX

1

3

IP

80" LCD MONITOR

1. ALL FASTENING LOCATIONS MUST HAVE SCANS TO LOCATE. RE-BAR PRIOR TOINSTALL.

2. FOR SCANNING OF ALL FASTENING BOLT LOCATIONS, CUTTING AND CORING, AVCONTRACTOR MUST BE CO-ORDINATE WITH SCANNING CONTRACTOR.

3. ALL MOUNTING LOCATIONS MUST BE APPROVED BY STRUCTURAL ENGINEER.

AV MOUNTING NOTES

1. LOCATIONS OF AV DEVICES IN MILLWORK MUST BE CONFIRMED ON SITE WITHOWNER'S REPRESENTATIVE.

2. MILLWORK CUTOUTS ARE TO BE COMPLETED BY MILLWORK CONTRACTOR.

MILLWORK NOTES

NAME OF PROJECT: NEW WESTMINSTER CITY HALL COUNCIL CHAMBER

CIVIC ADDRESS: 511 ROYAL AVENUE NEW WESTMINSTER, BC V3L 1H9.

PROJECT INFORMATION

T201 AV CONTROL SYSTEMS

CEILING SPEAKER

COUNCIL CHAMBERS

NEW WESTMINSTER CITY HALLAV SYSTEMS

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

COVERCOUNCIL CHAMBERS T100

Page 2: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

FOR REFERENCE ONLY

FB

FBFB FB

FB

CAM

+76" AFF

CAM+95" AFF

CAM+84" AFF

CAM

IPCAM

EXISTING WALLMOUNT AV RACK

EXISTING MOVABLEPRODUCTION RACK

EXISTING LIGHTINGCONTROL INTERFACE

EXISTING CORING

CAMCAM

7'-1

1"

7'-0

"

CAM

6'-4

"

SYMBOL SCHEDULE

FB

CAM EXISTING PTZ CAMERA

EXISTING FLOORBOX

EXISTING CEILING MOUNTPROJECTOR

EXISTING CEILING MOUNTPROJECTOR SCREEN

NOTE:

EXISTING DEVICES SHOWN ON THE DRAWING IS FORINFORMATION ONLY. EXACT LOCATION TO BE CONFIRMED BYCONTRACTOR ON SITE.

IPCAM EXISTING IP CAMERA

CAM IPCAM

9'-6

1/4

"

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

EXISTING DEVICESCOUNCIL CHAMBERS T101

2COUNCIL NORTH WALL SECTION1/4" = 1'

3COUNCIL SOUTH WALL SECTION1/4" = 1'

4COUNCIL EXISTING DEVICES PLAN1/4" = 1'

1COUNCIL EAST WALL SECTION1/4" = 1'

Page 3: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

3

1

1

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

8'-6

"

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BECONFIRMED ON SITE.

EXISTING IP CAMERA TOREMAIN

NEW WALL MOUNT RACK

NEW PRODUCTION RACK

EXISTING CRESTRON LIGHTINGCONTROL INTERFACE

AV

AV

AV

AV

AV

AV

AV

AV

AV

T

T

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

WALL MOUNT TOUCH PANEL+ 60" AFF . CONFIRM EXACT

LOCATION ON SITE.

AV80" LCD MONITOR

AV

IP

T

3

T103

5

6

SYMBOL SCHEDULE

WIDE ANGLE PTZ CAMERA

CEILING MOUNT PROJECTOR

CEILING MOUNTPROJECTION SCREEN

LONG THROW PTZ CAMERA

EXISTING IP CAMERA TOREMAIN

MICROPHONE STATION

BACKUP MICROPHONE

T

AV

TOUCH PANEL

AV INPUT PLATE

FLOORBOX

1

3

IP

80" LCD MONITOR

CEILING SPEAKER

TEL.

SERVER ROOM

LEGISLATIVESTORAGE

NEW AV RACKLOCATION TO BECO-ORDINATED ON SITE

1REFER TO ELECTRICAL DRAWINGFOR ROUTING OF CONDUIT

3

1

1

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

8'-6

"NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

NEW CORING LOCATION.LOCATION TO BECONFIRMED ON SITE.

EXISTING IP CAMERA TOREMAIN

NEW WALL MOUNT RACK

NEW PRODUCTION RACK

EXISTING CRESTRON LIGHTINGCONTROL INTERFACE

AV

AV

AV

AV

AV

AV

AV

AV

AV

T

T

NEW CORING LOCATION.LOCATION TO BE CONFIRMEDON SITE.

WALL MOUNT TOUCH PANEL+ 60" AFF . CONFIRM EXACT

LOCATION ON SITE.

AV80" LCD MONITOR

AV

IP

T

3

T103

5

6

19'-8"

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

NEW COUNCIL CHAMBER LAYOUT T102

COUNCIL CHAMBER PLAN - COUNCIL MEETING1/4" = 1'-0"

SERVER ROOM PLAN1/4" = 1'-0"

COUNCIL CHAMBER PLAN - COMMITTEE OF WHOLE1/4" = 1'-0"

COUNCIL CHAMBER REFLECTED CEILING PLAN1/4" = 1'-0"

T102

1T102

2

T102

3T102

4

Page 4: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

19'-8"

1'-0

"

1'-0"

11°

16°

7'-0

"

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

1

19'-8"

1'-0

"

1'-0"

6'-4

"

NEW PTZ CAMERA ATEXISTING CAMERA LOCATION

5'-0"

6'-8

"

12

7'-0

"

8'-6"3'-0"

7'-0

"

NEW DIGITAL CLOCK

10'-11 3/16"

6'-6

9/1

6"

7'-5

1/2

"

3

NEW PTZ CAMERA AT EXISTINGCAMERA LOCATION

EXISTING IP CAMERA TO REMAIN

NEW DIGITAL CLOCK

9'-0

"

3'-0"

IP3

5'-0

"

WALL MOUNTRACKFRONT VIEW

PRODUCTION RACKCONSOLE

ROLLINGPRODUCTION RACKSIDE VIEW

MONITOR MOUNTATTACHED TOPLATE

22" MONITOR

5'-0

"

WALL MOUNT RACKSIDE VIEW

PRODUCTION RACKCONSOLEWITH 22" MONITOR

ROLLINGPRODUCTION RACKFRONT VIEW

AV

T103

5

6

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

NORTH WALL SECTION1/4" = 1'-0"

SOUTH WALL SECTION1/4" = 1'-0"

WEST WALL SECTION1/4" = 1'-0"

EAST WALL SECTION1/4" = 1'-0"

AV CLOSET SOUTH ELEVATION1/2" = 1'-0"

AV CLOSET WEST ELEVATION1/2" = 1'-0"

SECTIONSCOUNCIL CHAMBERS T103

AV CLOSET WEST ELEVATION1/2" = 1'-0"

T103

1T103

2T103

3

T103

7T103

6T103

5T103

4

Page 5: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

CITY CLERK

AV INPUT

POWER/DATA/USBCHARGING

AV INPUT

CABLE TRAY

CONF.STATION TABLE TOPTOUCHSCREENFOR CITY CLERK

MAYORCHAMBER CLERK

CABLING FORTOUCHSCREEN

TOGGLE SWITCH

TABLE TOPTOUCHSCREENFOR MAYOR

CABLE TRAY

DISPLAY MONITORCONF. STATIONTOGGLE SWITCH

POWER/DATA/USBCHARGING

AV INPUT PLATE

HATCH

CABLE TRAY(TYPICAL OF 2)

(2) 1.5" CONDUITSTO AV CABLING SPACE

BACKUP MIC

PRESENTATION DESK SECTIONPRESENTATION DESK ELEVATION

HATCH

CABLE TRAY(TYPICAL OF 2)

(2) 1.5" CONDUITSTO AV CABLING SPACE

CABLE TRAY

AUDIO INPUT

AV INPUT PLATE

PRESENTATION DESK PLAN PRESENTATION DESK SIDE ELEVATION

FOR CONNECTION OF PTTMICROPHONE SYSTEM. PLATE &CONNECTOR ON BOTH SIDE OFTABLE

5U

10U

15U

20U

25U

30U

35U

40U

44U CRESTRON CP 3SWITCH

OWNER SUPPLIED

CRESTRON AV MATRIX

WEPRESENT SENNHEISER

ADN CU 1

BIAMP AUDIAOWNER SUPPLIED

BIAMP TESIRAFORTE

TOA DA 250

SENNHEISER ADN CU 1

SERVER ROOM EQUIPMENT RACK BTU CALC

DESCRIPTION MANUFACTURER MODELRACKUNITS

POWERCONSUMPTION

QTY TOTALPOWER

EFFICIENCY BTU/Hr

CONTROL PROCESSOR CRESTRON CP3 1 24 1 24 5.00% 50OWNER SUPPLIED SWITCH N/A N/A 2 100 1 100 5.00% 325AV MATRIX CRESTRON DM-MD32X32 14 1100 1 1100 6.00% 3000WIRELESS PRESENTATION WEPRESENT WIPG1000 1 50 1 50 0.00% 171DISCUSSION CENTRAL UNIT SENNHEISER ADN CU1 2 245 2 490 0.00% 1673OWNER SUPPLIED DSP BIAMP AUDIA 2 100 1 100 0.00% 342DSP BIAMP TESIRA FORTE 2 100 1 100 0.00% 342POWER AMPLIFIER TOA DA 250 1 1200 1 1200 0.00% 4096

25 3164W 0W 9,999BTU/Hr

5U

10U

12U

RDL RU-MX4

EXTRON SMP351LISTEN LT-800

O/S (2) SHURE SLX4O/S SHURE UA844O/S POWER BAR

NETWORK SWITCH

AV PANEL

2 RU RACKMOUNT DRAWER

AV CLOSET WALL MOUNT RACK BTU CALC

DESCRIPTION MANUFACTURER MODELRACKUNITS

POWERCONSUMPTION

QTY TOTALPOWER

EFFICIENCY BTU/Hr

ANTENNA DISTRIBUTION SHURE UA844 1 25 1 25 50.00% 43DIVERSITY RECEIVER SHURE SLX44 1 10 1 10 50.00% 18STREAMING MEDIA PROCESSOR EXTRON SMP351 1 30 1 30 - 96AUDIO MIXER RDL RU-MX4 2 10 1 10 0.00% 35

5 75W 0W 192BTU/Hr"O/S" DENOTED "OWNER SUPPLIED"

5U

10U

14U

QCCUQCCUQCCUQCCUUPS

POWER BAR

2 RU RACKMOUNT DRAWER

AV CLOSET PRODUCTION RACK BTU CALC

DESCRIPTION MANUFACTURER MODELRACKUNITS

POWERCONSUMPTION

QTY TOTALPOWER

EFFICIENCY BTU/Hr

UPS N/A N/A 1 15 1 15 5.00% 49CAMERA CONTROL UNIT VADDIO ROBOSHOT 4 100 4 400 5.00% 1297

5 415W 0W 1,346BTU/Hr

CONNECT TOPRESENTATIONTABLE

MOVABLE TABLE PLAN

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

WORKSPACE DETAILSCOUNCIL CHAMBERS T104

CHAMBER CLERK / CITY CLERK / MAYOR ELEVATION3/4" = 1'-0"

TYPICAL COUNCILOR WORKSPACE ELEVATION3/4" = 1'-0"

TYPICAL WORKSPACE SECTION3/4" = 1'-0"

PRESENTATION PODIUM DETAILS3/4" - 1'-0"

SERVER ROOM RACK LAYOUTNTS

AV CLOSET WALL MOUNT RACK LAYOUTNTS

AV CLOSET PRODUCTION RACK LAYOUTNTS

T104

1

T104

3

T104

2

T104

5

T104

6

T104

7

T104

8

COMMITTEE OF WHOLE MOVABLE TABLES3/4" = 1'-0"T104

4

Page 6: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

SIDE VIEW 2

REAR VIEWFRONT VIEW

BOTTOM VIEW

TOP VIEW

SIDE VIEW 1

7.0" [178.76]

6.7" [170.75] 1/4" x 20INSERT

7.0" [178.21]

2.2" [56.45]

4.8" [121.92]

3.5" [87.87] 3.459 [87.87]

5.4" [137.01]

7.0" [178.76]

5.5" [139.89]

4 1/

8"

3 1/2"

2 5/

8"

1 5/16"

4 1/2"

1 3/

4"

3 1/2"

1 7/

16"

10 1/8"

8 9/16"

6 7/

16"

5 3/

8"

2 1/4"

1/2"

2"

3 3/8"

3 3/8"

2 3/8"

WALL MOUNT BACK VIEW

WALL MOUNT BOTTOM VIEW

WALL MOUNT FRONT VIEW

WALL MOUNT TOP VIEW

WALL MOUNT SIDE VIEW

FINISHED WALL

4"

3"

5 5/16"

4 13

/16"

TABLE TOP SIDE VIEW

10 1/8"

TABLE TOP FRONT VIEW

4 13

/16"

GROUND

60"

3'-7

1/1

6"

1'-8

7/8

"

5'-10"

3'-3

1/2

"

2'-3"

6'-1 9/16"

6'-8

"

5'

9 1/2"

4 5/

8" 2

COUNCIL CHAMBER FINISHED FLOOR

VARIABLE AUDIO OUTPUT FIXED AUDIO OUTPUT

HD/SDI SDICOMPOSITECOMPOSITECOMPOSITEARCHIVERECORD

1'-1 13/16"

1'-5

5/1

6"

1'-3

5/1

6"

4 1/

8"

5 1/4"

4 1/

2"

7 7/

8"

ALL CABLING TO BE SECURED/CONCEALED TO PROVIDEA CLEAN INSTALL.

10 9

/16"

NOTE:ROUGH-INS BY DIV. 26CABLING AND TERMINATIONS BY DIV. 27

4"[103mm] SQUARE DEEP BOX

3-1/2"

35mm CONDUIT STUBBED-OUTTO ACCESSIBLE CEILING SPACE.PROVIDE NYLON BUSHINGAND PULL STRING.(BY DIV.26)

DIV.26 TO PROVIDE J-HOOKSAND/OR CONDUIT(S).

USE FLAT RECTANGULAROPENING (TILE) MUDRINGS

NOTES:

1. PATHWAYS FOR TECHNOLOGY CABLES SHALL BE PARALLEL TO BUILDING LINES. HORIZONTAL CABLING SHALL BE SUPPORTED BY J-HOOKS(BY DIV.27), CABLE TRAYS AND/OR PLACED IN CONDUIT.

2. THE NUMBER OF CABLES SUPPORTED BY J-HOOKS AND THE SPACING BETWEEN THE J-HOOKS SHALL FOLLOW MANUFACTURERS RECOMMENDATIONS.

3. CABLES OF DIFFERENT SYSTEMSSHALL BE BUNDLED SEPARATELY.

MAXIMUM 3 FEET

FASTENER

J-HOOK

VELCRO WRAPS FOREVERY 2 METER

A/VCABLE

WHITE (COMMON)BLACK (HOT)

GREEN120VAC 60Hz

GROUND MUST BECONNECTED TOBUILDING GROUND

GREEN

GROUNDTO CASE

MOTOR

UP

+5V

CO

MD

N

SPLITTERDRY CONTACTS

SUPPLIED ANDINSTALLED BYELECTRICALCONTRACTOR

SUPPLIED ANDINSTALLED BY

AVCONTRACTOR

TO 3-POSITIONLOW-VOLTAGEWALL SWITCH

4-CONDUCTORCABLING

ELECTRIC PROJECTION SCREEN WIRING DETAIL

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

EQUIPMENT DETAILSCOUNCIL CHAMBERS T105

PROJECTOR SCREEN DETAILS1/2" = 1'-0"

PTZ CAMERA DETAILS3" = 1'-0"

TYPICAL AV TRANSMITTER DETAILS6" = 1'-0"

TOGGLE SWITCH DETAILS3" = 1'-0"

TOUCHSCREEN CONTROL PANELNTS

80" LCD TV ELEVATION1/2" = 1'-0"

AV PRODUCTION AUDIO / VIDEO OUTPUT PLATE6" = 1'-0"

PRESS FEED FLOOR BOX DETAILS3" = 1'-0"

COUNCILLOR STATION AV INPUT DETAIL6" = 1'-0"

PROJECTOR MOUNTING DETAILS1" = 1'-0"

T105

1

T105

5

T105

2T105

4

T105

9

T105

11

T105

13

T105

3

T105

8T105

7

TYPICAL WALLMOUNTED AV BOX1-1/2" = 1'-0"T105

10

TYPICAL WALLMOUNTED AV DEVICE1-1/2" = 1'-0"T105

12

ELECTRICAL PROJECTION SCREEN WIRING DETAILNTST105

6

PRESENTATION TABLE AUDIO INPUT DETAIL6" = 1'-0"T105

14 PTT CONNECTION PLATE DETAIL6" = 1'-0"T105

15

Page 7: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

AV SCHEMATICCOUNCIL CHAMBERS T200

Page 8: NEW WESTMINSTER CITY HALL AV SYSTEMS€¦ · presentation desk elevation presentation desk section hatch cable tray (typical of 2) (2) 1.5" conduits to av cabling space cable tray

REV DESCRIPTION BY DATE

Drawing scale may be affected by printing, scanning or copying.

- ISSUED FOR 75% REVIEW ACUMEN 2015-06-09 Council ChambersCITY OF NEW WESTMINSTER

- ISSUED FOR 95% REVIEW ACUMEN 2015-06-17- ISSUED FOR TENDER ONLY ACUMEN 2015-06-19

650-2700 PRODUCTION WAYBURNABY, BC V5A 4X1PH.604.676.9545

ACUMENENGINEERING.CA

THIS DRAWING AND ALL ASSOCIATED DOCUMENTS ARE AN INSTRUMENT OF SERVICE AND ARE, AND WILL, AT ALL TIMES REMAIN EXCLUSIVE PROPERTYOF ACUMEN ENGINEERING LTD. ALL DESIGNS AND OTHER INFORMATION SHOWN ON THIS DRAWING ARE FOR USE ONLY ON THE SPECIFIED PROJECT;AND MAY BE USED ONLY FOR THE ISSUED PURPOSE AS STATED HEREIN. PAYMENT OF ALL SUMS DUE TO ACUMEN ENGINEERING LTD. UP TO THE DATE

OF THE INTENDED USE OF THIS DRAWING IS A CONDITION PRECEDENT TO THE USE THEREOF. COPYRIGHT OF THIS DRAWING, ITS CONTENT ANDDESIGN ARE RESERVED BY ACUMEN ENGINEERING LTD. THE DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED IN

WHOLE, OR IN PART, WITHOUT PRIOR WRITTEN PERMISSION FROM ACUMEN ENGINEERING LTD.

AV CONTROL SYSTEMCOUNCIL CHAMBERS T201