MAKING MODERN LIVING POSSIBLE
New photo
VLT® HVAC DriveFor HVAC it has to be VLT®
![Page 2: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/2.jpg)
2
The HVAC Drives Specialists
The VLT® HVAC Drive includes: • >98%basicenergyefficiency• AutomaticEnergyOptimisation• User-friendlyoperation• Programmingin27languages
Save moneyThemodulardesignenablestheusergreaterflexibilitytoselectfromarangeoffunctionalperformancerequirementstosecurethebestcostadvantagefortheirapplicationneeds.
Easy commissioning• Applicationmenus• Quickmenu• MotorRotationCheck• PID-autotuning
High ambient temperatureTherobustVLT®HVACDriveisdesignedtoworkatmaximumoutputinanambienttemperatureupto 50°C.Athighertemperatures,thedrive will continue operation with lowerperformance.AutomaticderatingenablesreducedoperationforaperiodoftimestillathigherambienttemperaturestomaintainoperationoftheHVACsystem.
Danfoss has been at the forefront of the drives industry for more than 40 years and was the first to develop a comprehensive understanding of the HVAC market and its drive needs. Danfoss was the first drives provider to develop drives dedicated to HVAC applications and a dedicated HVAC organisation applying drive technology to save energy and reduce C02 emissions in HVAC applications. VLT® drives therefore meet the ever increasing demands for intelligent solutions, comfort and energy saving within the HVAC market sector.
In everything we do, Danfoss is a clean tech company.
![Page 3: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/3.jpg)
3
Maintenance freeDuetoaseriesofself-protecting andmonitoringfeaturesandahighlydurablemechanicaldesign,the VLT®HVACDriveismaintenancefree,exceptforgeneralcleaning. Noreplacementofinternalfansorcapacitorsisrequired.
Save spaceDuetoitscompactdimensions,theVLT®HVACDriveiseasilymountedinsideaHVACunitorpanel,reducingoverallenclosurecostsandfreeinguppanelbackspaceforotherdevices.
Fire Override ModeFireOverrideModehelpskeepfireescaperoutesfreeofsmoke,over-ridesthedrive’sself-protectingfeaturesandkeepsthedrivenequip-mentrunningaslongaspossibleintheeventoffire.
ActivatingFireOverrideModewillensuretheVLT®HVACDriveignores“soft“faultsandalarmstocontinueoperationduringessentialservicessuchasa“fire”command.
Save cabinetWeofferastandard&integratedIP55protectionclassequaltothatofthemotor.
Thiseliminatesthecostofaseparateenclosure and saves on the additional installation costs associated with installationinaremotelocation.
IP 66 for harsh environments IP66enclosureoptionforharshenvironments.Thistoocaneliminatethecostofaseparateenclosureandreduce the installation costs associ-atedwithremoteinstallation.
EMC & network protectionFullyintegratedEMCfilterseliminatethecostofinstallingexternalEMCfiltersandsecurethehighestintegrity&fullytestedEMCperformance.
AllversionsofVLT®HVACDrivecom-plyasstandardwithEMClimitsA2accordingtotheEN55011norm.AllA1andBfilteroptionsareavail-ablefactorybuilt-in.
ThestandardintegratedDCcoilsalsoensurelowharmonicloadonthenetworkwithinEN61000-3-12andincreasethelifespanoftheDClinkcapacitors.Theyalsoensurethatthedrivecanoperatemotorstotheirfullperformance.
Forfurtherprotectionagainsthar-monicdisturbancesofthesupplygrid,Danfossprovidespassivesolu-tionssuchas12/18pulsesolutionsandAdvanvedHarmonicFilters(AHF)aswellasactiveharmonicmitigation.
Active solutionsDanfossalsoprovidesactivesolutionssuchasLowHarmonicDrives,com-biningstandarddriveswithanactivefilterandstand-aloneVLT®AdvancedActiveFilters.
1968 1983 1988 1989 1993 1996 1998 2000 2004 2006-
VLT® 5 VLT®100 VLT®1000 VLT® 3000 HVAC VLT® 2000VLT® 3500 HVAC
VLT® Drive Motor FCM 300
VLT® 6000 HVAC VLT®2800 VLT® FCD 300 VLT®AutomationDrive VLT® HVAC DriveVLT®AQUADrive
VLT® Micro Drive
ThefirstVLT®HVACDrive–the VLT®100from1983–hasproven thereliabilityofVLT®drives.
ProvenreliabilityOriginalVLT®HVACDrivesinstalledin1983arestillfunctioningreliablyover20yearslater.
VLT® 5000 VLT®5000book
VLT®HighPower Drives
![Page 4: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/4.jpg)
4
VLT®HVACDriveforGreenBuildings
Danfoss commitmentDanfoss’longexperienceinapplyingdrivesinHVACsystemshasenhanceditsabilitytooffera“BestinClass”technicalexpertiseinintegratingthedriveintotheoverallsystemdesigntoextractthemaximumvaluefromyourinitialinvestmentandoptimisetheoperationalsavingsperformance.
The21stCenturyfocusonenergyefficiencyisnotnewasregardsenergysavingbuttheemphasisontheconsequencesofwastedenergyandtheover-useoffossilfuelstopro-duceenergyistopoftheagenda.
ClimateChangeisseenasacosttothehumanracemorethansimplyafinancialcost.
Save energy and CO2 emissionVLT®frequencyconverterssavemorethan20millionMWhenergyglobally
eachyear.Thisisequivalenttothe annualelectricityconsumptionof 5millionhouses.
Thisenergysavinghasanimpactonthe annual CO2emissions−areduc-tionof12milliontons!
Performance of the buildingTodaytheprimefocusisontheoverallperformanceofbuildingsand thisincludesdesign,construction,efficiency,sustainabilityandtheenvironmentalimpactofthesebuildingsinthefuture.
Energyefficientproductsformpartofthisoverallplan.Inmostcountriesaround the world this is now realised intheevaluationofhighperformancebuildingsunderthebannerLEED.
A wealth of knowledgeThe various applications incorporated withinhighperformancebuildingsarewellunderstoodbyDanfossandasglobalmarketleaderwehavebuiltawealthofknowledgeandunder-standingoftheapplicationsanddevelopedproductsandtechnologytoensurewemeetanddeterminefuturetrendsinthisindustry.40yearsofexperienceinthisbusinesshasmadetheVLT®HVACDrivetheindustrybenchmark.
Premier drive in the marketTheefficiencyoftheVLT®driveanditsbuilt-infeaturesmaketheVLT®HVACDrivethepremierdriveinthemarkettoday.
Danfossapplicationandindustryknowledgewillensurethattheinvest-mentmadeinVLT®drivesprovidesaqualifiedreturn.
![Page 5: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/5.jpg)
5
Financial incentives are just as importantasmoralincentivestomakepeoplechooseenergyefficientsolutions.
Reliable and cost effective Correct drive selection is critical to reliability.ProductsthatintroduceunacceptablelevelsofRFIorharmon-icsintoabuildingcanprovehighlyproblematicandcostlyinadditiontobreakinglegislativeregulations.
Danfoss’manyyearsofexperienceintheapplicationofVLT®drivesandintheHVACindustryinparticular,hasresultedinaglobalteamfocusedondeliveringthebestdrivessolution,ensuringtotalsecurityofyourinvest-ment.
Minimum impact on the environmentHavingchosentofitaVLT®driveaspartofthebuildingcontrolarchitec-ture,thelifetimesustainabilityofthisproductisanimportantaspect.
Cleanpowersupply
VLT® HVAC Drive introduces a minimumofRFIorharmonicpollutionintothebuildingandavoidsproblematicand,insomecountries/regions,performanceoutsideoftheirregulations.
VLT®HVACDriveisareliableandcosteffectiveinvestment.
DC coils reduce harmonic noise and protect the drive. Also EMC filters are integrated
(meets EN 55011 A2, A1 or B).
Newregulationsareforcingmanufac-turerstolookathowtheymanufac-ture,whattheymanufactureandwithwhatmaterials.
Aretheyharmfultomake?Aretheyharmfultodisposeofattheirend-of-life?RoHS,WEEEDirectives,ISO14001are all standards and directives cre-atedtoensuretheminimumimpactontheenvironment.
Energy monitoring The VLT® HVAC Drive provides a completerangeofenergyconsump-tioninformation.Choosetodivideabsoluteenergyconsumptionintohours,daysorweeksorchoosetomonitoraloadprofilefortheapplica-tion.
OptimisedEMCenvironment
Optimum EMC protection coupled with integrated harmonic filters ensures that the optimum EMC environment and cleanest power supplies are maintained through-out the operational lifetime of the system, negating any reduction in lifecycle costs.
VLT®HVACDrivemeetstheprod-uctstandardEN61800-3regardingEMCwithoutadditionalexternalcomponentsevenwithlongmotor
Limits according to EN 55011 Class B ClassA1 Class A2 ExceedingclassA2
Categories according to EN 61800-3 C1 C2 C3 C4
Comparison of limits EN 55011/61800-3
cables–andcorrespondstotheEMCguidelines2004/108/EC,offeringper-formancesuperiortootherdrives.
Criticalforpracticaluseiscompliancewiththeenvironmentstandard EN55011,ClassB(residential)andClassA1(industrialarea).
ThisensuresreliableplantoperationthroughfullcompliancewithallEMCrequirementsandproductstandards,prescribedwarningsandrestrictions.
Onthepowerside,integratedchokesminimisethenetworkeffectsdrama-ticallyandthusmaintainoperationwithinthelimitsofEN61000-3-12.
ThefullydimensionedintermediatecircuitmakestheVLT®HVACDrivestableandhighlydynamicevenduringshortsupplyvoltagedropsorotherpoornetworkconditions.
![Page 6: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/6.jpg)
6
Benefitsofownership
Total Cost of Ownership is an organisation’s total cost of acquir-ing, operating and maintaining a system through a given lifecycle.
TotalCostofOwnershipincludesinitialacquisitioncostandoperatingcost.Throughitstechnologyandexperience,Danfosscantransformthisintothe“BenefitofOwnership”.
Weunderstandtheneedsofourcustomersoperatingtheirfacilitiesinacompetitiveenvironmentwhich requirestotalsystemcosteffective-nessandhighestefficiencyindaily operationswithenvironmentalsustainability.
Dedicated HVAC organisation CustomerassurancestemsfromDanfoss’dedicatedandhighlyexperi-encedHVACsupportteam.
IthasthedepthofunderstandinginHVAC applications that ensures the maximumbenefitisextractedfromthecustomers’investmentinVLT®drivesystems.
Reducing acquisition costs• FullyintegratedEMC&Harmonic
compliantsolution• IP55/66
• ExtensiveHVACfunctionstoreduceothersystemcomponents
• ExtendableI/Otoreducetotal BAS costs
• Easeofinstallationandset-up
Reducing operating costs• Minimum98%efficiency• Energymetering• AutomaticEnergyOptimisation• Designlifetimeof10years• Danfosslegacyandhistoryin
HVAC applications• IPenclosuresandoptional
conformalcoatingtoprovide robust&reliableperformancein theharshestofenvironments
• 50°Cambienttemperaturewithoutderating
• Autoderatefunctions• Broadestrangeofdrive
andmotorprotection• Maintenancefreedrive• Systemdiagnostics
Investment
Operationandmaintenance
Energycosts
Time
Cos
ts
Disposal costs
![Page 7: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/7.jpg)
7
Enhanced advanced monitoringEnhanced advanced application monitoringfunctionalityforfansallowsyoutokeeptrackofthestatusofpumpsandcompressors.Thiscanmeanincreasedlifetime,reducedmaintenancecosts,andlessdown-time.
Supporting software toolSoftwaretoolsareavailabletohelpdesignasystemwithminimalhar-monicsandbestenergyefficiency. Protection modeAssoonasthesystemdetectsacriticalstatus(e.g.over-currentorovervoltage)thefrequencyoftheVLT®HVACDrivewillautomaticallybereducedandthemodulationprocessadjusted.
Duetoitsabilitytolimititsswitch-ingoperationstheVLT®HVACDriveisextremelyreliableandrobust.
Theprotectionmodewill–ifallow-able–endafter10secondsandthefrequencywillberestoredundercontrol.
Minimum 98% efficiency The VLT® HVAC Drive sets new stand-ardswithaminimum98%efficiencyatfullload.Thisreducesinitialcostsandoperatingcostsduetothesmallerheatload/airconditioningrequirementintheswitchroom/plant-room,therebymaximisingenergyefficiency.EverykWoflossesrequiresanother~0.5kWofenergytoremovetheheat.
Installed in an air conditioned switch-room,lowerlossescaneasilyresultinoperatingcostsavings>5%–10%ofthecostofthedriveeveryyear(basedonatypicalloadprofile,withthedriveoperating24/7).AlsoenergyconsumptionandCO2emissionisreduced.
High Ambient TemperaturesVLT®HVACDriveisdesignedtooperateinambienttemperatures up to 50o C with an autoderate capa-bilityforhighertemperaturesinordertomaintainreducedoperationinextremeclimateconditions.
Inmostcases,theVLT®HVACDrivewill handle the situation without needingattention.
VLT®HVACDrivewillmanagethelossofamainsphaseorahighmainsimbalancebyautoderatingspeedandloadtomaintainaperiodofreducedoperation,enablingtechnicianstorespondtothesituation.
Our goal is the highest efficiency with the lowest energy consumption and with the lowest overall system cost for our customers = “The Benefit of Ownership”.
![Page 8: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/8.jpg)
8
ThemodularVLT®HVACDrive
TheVLT®HVACDriveisbuiltonDanfoss’modularconcept.Realplug-and-playaddingandexchang-ingofoptions.Justupgradeinsteadofbuyinganewdrive.
1 Fieldbus option • BACnet
• LonWorks • Profibus • DeviceNet
2 Local Control Panel (LCP) Choosenumerical, graphicalornodisplay
3 I/O option • GeneralPurposeI/O
(3DI+2AI+2DO+1AO) • AnalogueI/Ooption (3AI(0–10V/PT1000/
NI1000)+3AO(0–10V)) • Relayoutput(3xrelays)
4 24 V supply option
5 RFI filter Built-inRFIfilterforlong motorcablescompliantwith theIEC61800-3andEN55011standards.
6 AC mains disconnect (Factorymountedoption)
7 Input mains option Variousinputplateconfigura-tionsareavailableincludingfuses,mainsswitch(disconnect),orRFIfilter.Inputplatesarefieldadapt-ableifoptionsneedtobeaddedafterinstallation.
8 Unique cooling concept • Noambientairflowoverthe
electronicsupto90kW • Above90kW,designedwith
backchannelcooling(85%heatdissipatedviabackchannel)
9 Durable in aggressive environments InsomeHVACapplications,itisrecommendedtoprotectthedrivewithcoatedPCB’s.VLT®HVACDriveisdesignedforlevel3C2accordingtoIEC60721-3-3.Protectionlevel3C3isoptionallydeliveredfromfactory.
Theoptionofferssignificantlyimprovedprotectionagainstchlorine,hydrogensulphide,ammoniaandothercorrosiveenvironments.
VLT® quality up to 1.2 MWTheVLT®HVACDriveisavailablefrom1.1kWto1.2MW.
Driveexperiencesince1968liesbehindtheintelligentdesignofVLT®drives. Allenclosuresaremechanicallydesignedwithfocuson:• Robustness• Easyaccessandinstallation• Intelligentcooling• Highambienttemperatures
The modular design of the VLT® HVAC Drive allows even
highly customised drives to be mass produced and factory
tested. Plug-and-play options make upgrading easy and
ensure flexibility.
12
9
7
5
8
3
4
6
![Page 9: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/9.jpg)
9
OptimisingEnergySavings
Automatic Energy OptimisationThestandardfeatureAEOprovidesoptimisedmotormagnetisationatallspeedsandloads.Thisoptimisationprogramincreasestheenergysavingsgainedbyapply-ingvariablespeedcontrol.
Automatic Motor AdaptationEnterthenameplatedata,andVLT®HVACDriveautomaticallyadjuststothemotor.
Suitable for “follower” operationThedrive’smodularstructuremakesitsuitablefor“follower”operationmasteredbyBMS,PLC’sorDDCs.
Theopencommunicationsdrive
Motor current
Speed
Motorvoltage
Automaticloadadjustment
AEO-adjustmentStartwithhighacceleration
Automatic Energy Optimisation
TheVLT®HVACDriveintegratesandcommunicatesseamlesslywithallHVACdevices,masteredbyBuildingManagementSystemsviathefield-bus.HVAC-specificfeaturesmakeiteconomical,flexibleanduser-friendlyandmakeHVACoperationsimple.
Improve system performanceVLT®HVACDriveuseslimitednet-workbandwidth,anditrequireslessresources in the DDC controller due tothesupportofalarmandeventnotification.
Thiscanreducetrafficbymorethan50%comparedtootherdrives.
ForVLT®HVACDriveitispossibletoread all inputs and control all the outputsonI/Ooptions.Availableasstandardaswellasintheoptions.
ThismeansthatwhenintegratingaVLT® HVAC Drive into the controlsystemitispossibletosavemorephysicalI/Opoints.
Detailed information about warnings and alarmsVLT®HVACDrivehaspointsgivingdetailedinformationaboutalarmsandwarnings.DDCcontrollerscanmonitortheseandseewhenanalarmorwarningoccursandwhyitoccurred.
BACnet®TheVLT®BACnetoptionisaplug-and-playsolutionthatoptimisestheuseofVLT®HVACDrivetogetherwithbuildingmanagementsystemsusingtheBACnet®fieldbus.
VLT®HVACDrivehasobjectsdefinedtoaccept3separatefeedbackstransmittedoverBACnet.
ThisoptionmakesiteasytocontrolormonitorpointsrequiredintypicalHVACapplications.
Listed by BTLListingbyBTLmeanspassingcomprehensiveandlong-lastingtestsattheBTLlaboratories,whichensuresthatthefunctionwillworktogetherwithanyotherBLT-listedequipment.
Embedded fieldbuses• ModbusRTU(std.)• FCprotocol• N2Metasys• FLNApogee
Optional fieldbuses• BACnet• Profibus• Devicenet• LonWorks
![Page 10: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/10.jpg)
10
Perfectforallconditions
Theinstallationvolumeand/orthemountingsurfacesarereducedbyupto60%comparedtothepreviousseries.
Thefunctionalsectionsneverthelessfulfilthehighestrequirementsevenforapplicationswithhighoverload,longmotorcablesandambienttemperaturesupto50°C(55°Cwithderating).
Optimised design Optimisedefficiencyandintelligentcoolingtechnologymakeforacompactandservice-friendlydesign.SupplementaryequipmentsuchasEMCfilters,harmonicssuppressionandbrakemodulesareintegratedintotheenclosure.
Save installation timeTheIP20seriesisdesignedforeasyaccessibilityandtime-savinginstal-lation.Mechanicalfasteningpointsareeasytoaccessfromthefrontevenwithautomatictools.
Allterminalsaresufficientlydimen-sionedandclearlymarked.Oneneedsonlyloosenafewscrewstogettotheterminals.
Accessoriesforbondingofscreenedcablesareincluded.Thecompactenclosuresareeasiertoinstall.Thisisimportantespeciallywithinexistinginstallationswithpooraccessibility.Anextensiverangeofoptionsandac-cessoriesisavailable,optimisingthedrivefortherespectiveapplication.
VLT®drivesareavailableinIP20enclosures,optimisedforinstallationinpanels
Totalseparationbetweencoolingairand electronics protects the electron-icsandallowsforsolutionswhereheatisremovedfromoutsideofthecabinets.
WithVLT®HVACDrive,aflangedheatsinkkitisavailableformountingthedriveinthebackplateofacabinetwithoutaccessingtheelectronics.
Eliminatingairflowovertheelectron-icsincreaseslifetimeandcontami-nantsareexcludedfromthedrive.
Backchannelcoolingminimisesheatlossincreasingenergyefficiency,asignificantbenefitathighpowers.
IntelligentheatmanagementVariablecoolingmethodsfordifferentbenefits
![Page 11: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/11.jpg)
11
Highreliabilityeveninharshenvironments
An external watertight USB
plug connected to the control card
inside IP 55/66 enclosures makes
USB access easy.
The VLT® HVAC Drive is also
available with a mains switch
option. This switch interrupts the
mains supply and has a free useable auxiliary contact.
All VLT® HVAC Drive versions have manganesephosphorrearbodies.IP66encloseddrivesaresuitableforinstallationindemandingenviron-ments(e.g.coolingtowers).
Coolingairiskeptoutsidethedevicetopreventanypollutionoftheelec-tronics.Thesurfacesaresmoothandcaneasilybecleaned.
Becauseofthehigh-densityintegra-tion,thetighthousingsofVLT®HVACDrivearesignificantlysmallerwhencomparedtootherdrivesofthesameperformance.
Thecablesaremountedsecurelythroughglandsinthebaseplate.
TheIP55/66seriesaredesignedforeasyaccessibilityandtime-savinginstallation.
Furthermore,allcomponentssuchasEMCfiltersforcompliancewith EN55011,classA1/B,aswellasthe DCcoils,areprotectedinsidethedrive.
![Page 12: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/12.jpg)
12
VLT® Energy Box software is the most modern and advanced energy calculation tool available.
Itallowsenergyconsumptioncalcula-tionsandcomparisonsofHVACfans,pumpsandcoolingtowerapplica-tionsdrivenbyDanfossdrivesandalternativemethodsofflowcontrol.
TheprogramcomparesthetotaloperationcostsofvarioustraditionalsystemscomparedtooperationofthesamesystemwithaVLT®HVACDrive.
Withthisprogramitiseasytoevalu-atethesavingsbyinstallingaVLT®HVACDriveoverothertypesofcapacitycontrolsystemsinbothnewinstallationsaswellasretrofitsitua-tions.
Complete financial analysisVLT®EnergyBoxprovidesacompletefinancialanalysisincluding:• Initialcostforthedrivesystemand
thealternativesystem• Installationandhardwarecosts• Annualmaintenancecostsand
anyutilitycompanyincentivesforinstallationofenergyconservationproducts
• Paybacktimeandaccumulatedsavingsarecalculated
• Uploadofrealenergyconsumption(kWh)anddutycyclefromthe VLT® HVAC Drive
VLT®EnergyBoxmakesitpossibletocapturerealenergydatafromthedrivesandtomonitorenergyconsumptionandoverallsystemefficiency.
Energy auditThe VLT® HVAC Drive coupled with theEnergyBoxsoftwareenablesthepackagetobeusedastheEnergyAuditequipmentforbothestimationandvalidationofsavings.
VLT®HVACDrivecanbeinterrogatedremotelyforfullenergydata,makingiteasytomonitoryourenergysavingsandreturnoninvestment.Monitor-ingviafieldbusoftenmakesenergymetersomissible.
Realisingthetruesavingspotential
![Page 13: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/13.jpg)
13
ManagingHarmonics
Harmonicdistortionofthesupplygridisanincreasingproblem,causedmainlybyelectronicpowerdevices,includingfrequencyconverters,drawingnon-sinusoidalcurrentfromthemainssupplyandcreatingharmonicdistortionofthesupplyvoltageasaresultofthesupplyimpedance.
Danfoss’HarmonicCalculationSoft-waremakesitpossibletocalculatetheextentoftheseharmoniccurrentsattheplanningstageandtoplancountermeasures.
Thiscanbeparticularlyvaluablewherethepowersupplyisbackedupwithemergencygenerators,whichhavepoorertolerancetonon-sinusoi-dalcurrents.
Typicalwithoutfilter
Withoutfilter
With AHF
With AHF
Datacanbeentered,storedandre-calledprojectbyproject.Ataclickthesoftwarepresentsaclearoverviewofeach project and data is presented in bothtabularandbar-chartformats.
Currentstandards(EN50106)areincludedinthesoftwareanalysis andthesoftwareitselfcanquicklyandeasilybedownloadedfrom www.drives.danfoss.com.
Harmonic disturbance with and without AHF filter.
![Page 14: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/14.jpg)
14
Theuserinterface– developed with HVAC user participation
1 Graphical display– Internationallettersandsigns– Graphicaldisplaywithbar-charts– Easyoverview– 27languagesselection– iFawardeddesign
2 Menu structure– Basedonthewellknownmatrix-
systemintoday’sVLT®drives– Easyshortcutsfortheexperienced
user– Editandoperateindifferent
set-upssimultaneously
3 Other benefits– Demountableduringoperation– Up-anddownloadfunctionality– IP65ratingwhenmounted
in a panel door– Upto5differentvariables
visibleatatime– Manualspeed/torquesetting– 100%userdefinedinformation
and size
4 Illumination– Relevantbuttonsareilluminated
when active– OtherLEDsindicatethestatusof
the drive
5 Quick Menus– ADanfoss-definedQuickMenu– Auser-definedQuickMenu– AChangesMademenulists
theparametersuniquetoyour application
– AFunctionSetupmenuprovidesquickandeasyset-upforspecificapplications
– ALoggingmenuprovidesaccesstooperationhistory
6 Intuitive functions– Info(“onboardmanual”)– Cancel(“undo”)– Alarmlog(quickaccess)
Theuserinterfacemaybemountedremotelyonacontrolpanelfascia.ThisenablesfulladvantagetobetakenoftheLCP,eliminatingtheneedforadditionalswitchesandinstrumentation.
1
3
4
2
5
6
The VLT® HVAC Drive can be remote-commissioned and monitored via a USB cable or fieldbus communication. Special software is available: Wizards, Data transfer tool, VLT® Set-up Software MCT 10, and Language changer.
Three panel options: Graphical, numerical, blind cover. The VLT® HVAC Drive is controlled locally via a control panel. This is plugged in directly or connected via a cable.
![Page 15: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/15.jpg)
15
VLT®MotionControlToolMCT10
Set-upsoftwareprovideseasycontrolofdetailsaswellasageneralover-viewofdrivesystems,largeorsmall.Thetoolhandlesalldrives-relateddata.
Explorer-like interfaceTheMCT10softwarefeaturesanexplorer-likeinterfacedesignandfunctionalitytoeasebothuseandlearningofthefacilities.
More efficient service organisation • Scope&logging:Analyse problemseasily• Readoutalarms,warningsand faultloginoneview• Compareasavedprojectwithan
on-linedrive
More efficient commissioning • Off-linecommissioningoffsite• Save/send/mailprojectsanywhere• Easyfieldbushandling,multiple drivesinprojectfile.Enablesservice organisationtobemoreefficient
Basic• Scope&Graph• Alarmhistoryinsavedprojects• GraphicalTimebasedActions,
Preventive Maintenance and Basic Cascade Controller
• Multiplefieldbussupport
Advanced• Nolimitationinnumberofdrives• Motordatabase• Real-timeloggingfromdrive• Sensorlesspumpcontrol
Two modesOn-line and off-line modeIntheonlinemode,youworkwiththeactualsetupofthedrivesinquestion.Youractionswillhaveimmediateeffectontheperformanceofthedrive(s).
Project orientedInprojectmodeyouworkwiththedriveparametersasa“virtual”set-up.Thisallowsyoutoadjustthewholesystembeforeyouimplementitintothedrivesandputitinaction.Inprojectmodeyoucansetthesystemupevenbeforethedrivesareinstalled.Asinglecommandwillupdatethewholesystem.Incaseadriveisexchanged,itiseasilysetuptoperformexactlyasitspredecessor.
Connections• USB• RS485
![Page 16: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/16.jpg)
16
Enhancedsafetybuilt-in
Speed
Differential pressure
Easy to open doors
Fresh air in
Mains switch optionThisswitchinterruptsthemainssup-plyandhasafreeuseableauxiliarycontact.Themainsswitchensuresthesafetyofstaffduringmaintenanceandcleaningoperations.
Themainsswitchoptionalsoreducestheassemblycost.Theswitchcanbesecuredagainstunauthorisedaccesswiththreedifferentlocks.
Fire Override ModeActivatingthefunction“Fire-mode”within the VLT® drive ensures secure and continued operation withinapplicationssuchasstair-wellpressurisation,carparkexhaustfans,smokeexhaustandessentialservicefunctions.
Clearly indicatedThefiremodeisclearlyindicatedinthedisplaytopreventanyconfusion.Whenset,thedrivewilloverrideselfprotection and will continue opera-tiondespitethepossibilityofperma-
nentdamageincaseofover-heatingoroverload.Thevitalgoalistokeepthemotorrunningevenifitmeansself-destruction.
Mains bypassIfamainsbypassisavailable,theVLT®HVACDrivewillnotonlysacrificeitselfincaseofanextremecondition,butisabletobypassitselfandconnectthemotordirectlytomainsandthiswaykeepoperationgoingaslongaspowerisprovidedandthemotorisfunctioning.
Typical application Smokeextractionfromtraffictunnels,subwaystations,stairwells.
![Page 17: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/17.jpg)
17
Dedicatedpumpfeatures
1 Dry Pump Protection and End of Curve
DryPumpProtectionandEndofCurve relate to situations where thepumprunswithoutcreatingthedesiredpressure–aswhenawellrunsdryorapipeleaks.Thedrivesetsoffanalarm,shutsoffthepump,orperformsanotherpre-programmedaction.
2 Auto tuning of the PI controllers WithautotuningofthePIcontrol-
lers,thedrivemonitorshowthesystemreactsoncorrectionsmadebythedrive–andlearnsfromit,calculatethe“P”and“I”valvessothatpreciseandstableoperationisachievedquickly. This applies to each PI controller in the4-menusetsindividually.ExactPandIsettingsatstart-upwillnotbenecessary–whichlowersthecommissioningcosts.
3 Flow compensation Significantenergysavingsand
reduced installation costs are providedbyflowcompensationinbothfanandpumpssystems. Apressuresensormountedclosetothefanorpumpprovidesareferenceenablingpressuretobekeptconstantatthedischargeendofthesystem.Thedriveconstantlyadjuststhepressurereferencetofollowthesystemcurve.
4 No/low flow Anoperatingpumpwillnormally
consumemorepowerthefasteritruns–accordingtoacurvedeterminedbythepumpandapplicationdesign.VLT®HVACDrive will detect situations where thepumprunsfastbutisnotfullyloaded–andtherebynotconsum-ingadequatepower.Thisisthecasewhenwatercirculationstops,thepumprunsdryorwhenpipesleak.
The VLT® HVAC Drive offers a vast numberofpump-specificfeaturesdevelopedincooperationwithOEMs,contractorsandmanufacturersaroundtheworld.
Embedded Pump Cascade ControllerThePumpCascadeControllerdistrib-utesrunninghoursevenlyacrossallpumps,keepswearandtearonindividualpumpstoaminimumandensuresthatallpumpsareingreatshape.
Vital water supplyVitalwatersupplycanbeassuredintheeventofleakageorabrokenpipe.Forexampleoverloadisprevented byreducingspeed–andsupplyis securedatlowerflow.
Sleep Mode InSleepModethedrivedetectssitua-tionswithlowornoflow.Insteadofcontinuousoperationitbooststhesystempressureandthenstopstosaveenergy.Thedrivestartsauto-maticallywhenthepressurefallsbelowthelowersetpoint.
1 2 3 4
![Page 18: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/18.jpg)
18
Dedicatedfanfeatures
• Weekendandworking-day operations• CascadedP-PIfortemperature control• Multi-zone“3”control• Flowbalancingbetweenfresh and outlet air• Beltmonitoring
Fire Override Mode Fire Override Mode prevents the VLT®HVACDrivefromstoppingforself-protectingreasons.Inthismodeitwillcontinuevitalfanoperationregardlessofcontrolsignals,warningsoralarms.
Extends BMS capacityWhenintegratedintotheBMSnet-work,alltheHVACDriveI/OpointsareavailableasremoteI/OstoextendthecapacityoftheBMS.Forexample,roomtemperaturesensors(Pt1000/Ni1000)canbedirectlyconnected.
Resonance Monitoring BypressingafewbuttonsontheLocalControlPanelthedrivecanbesettoavoidfrequencybandsatwhichconnectedfanscreateresonancesintheventilationsystem.Thisimprovesbuildingcomfort.
Stairwell PressurisationIntheeventoffire,theVLT®HVACDrivecanmaintainahigherlevelofair pressure in stairwells than in other partsofthebuildingandensurethatfireescapesremainfreeofsmoke.
Lower AHU costsTheVLT®HVACDriveisfittedwithabuilt-inSmartLogicControllerand4auto tune PID controllers and can controlairhandlingfunctionswithfans,valvesanddampers.Thebuild-ingmanagement’sDDCsaretherebyreleasedandvaluabledatapoints(DP) aresaved.
User-friendly,distributedintelligenceandreducedpowerconsumptionarebeneficialforfanapplications.
Velocity-to-flow conversionTheVLT®HVACDriveisabletoconvertvelocitypressuresensorvaluesintoflowvalues.Operatorscanthereforesetthedriveuptoprovideafixedfloworfixeddifferentialflow.Thiswaybothcomfortandenergyconsump-tionareoptimised.Usingapressuresensorinsteadofaflowsensorsavesmoney.
Intelligent AHU functionsTheVLT®HVACDrivehandleslogicalrulesandinputsfromsensors,real- timefunctionality,andtime-relatedactions.ThisenablestheHVACDrivetocontrolawiderangeoffunctions,including:
4xPIDcontroller • ProvidesflexibilityfortheBMSandreduces the load on the central BMS
The drive controller uses an input sensorthatmeasurespressure,tem-perature,orothervariablestochangethespeedonthemotorconnectedtotheVLT®HVACDrive,byadjustingtheoutputfrequencytomatchthevaryingload.The additional 3 PID controllers can beusedforexternalsensors(i.e.pres-sure,temperature,flow)tocontrolheating/coolingcoilvalves,outside/return/exhaustdampersorotherexternalHVACcomponents.
(Individualsetpoints/feedbacks)• 1PIDfortheclosedloopcontrolof
themotorconnectedtothedrive• 3PIDforexternalclosedloopcon-
trolofHVACequipment• Auto-tuningofall4PIDloops• Eliminatestheneedfor
other controllers
![Page 19: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/19.jpg)
19
Dedicatedcompressorfeatures
Alternativlyusethebuilt-incascadecontrollertooperatetheleadcom-pressorwithvariablespeed,whileusingtheVLT®HVACDrivetomanageon/offcontrolofuptotwoadditionalcompressors.
Set point in temperature The VLT® HVAC Drive calculates the actualrefrigeranttemperaturefromthepressuremeasuredandrefinescompressoroperationaccordinglyusingthebuilt-inPIDcontroller.
Thiscalculationisalsoapplicabletothesetpointaswell,sothedesiredtemperatureissetindegreesviatheLocalControlPanelorMCT10–andnotaspressurevalue.
Fewer starts and stopsAmaximumnumberofstart/stopcycleswithinagivenperiodoftimecanbesetviatheLCPorMCT10.Sincestart-upisthemostcriticalpartofcompressoroperationthisextendscompressorlifetime.
Quick start-upTheVLT®HVACDriveoffersafeaturetoopenabypassvalveandletthecompresserstartquicklywithoutload.
The VLT® HVAC Drive provides increasedbreakawaytorqueandcangive110%torquefor60secondsinnormaloperation.
Improving energy efficiency… continuouslyTraditionalcommercialaircondition-ingsystemsaredesignedforefficientoperationatpeakloadconditions,sosystemsareactuallyoversizedabout85%ofthetimeormore.Consequent-lyatpartloadconditions,thesystemsdeliverexcesscapacity,withsignifi-cantandcostlyenergywaste.Vari-ablespeedwillcontributetoahigherCOPandlowerenergyconsumptionwithloadmatchedtoactualdemandwhilstdeliveringasolidreturnoninvestment(ROI).
TheVLT®HVACDrivehasbeendesignedtoofferflexible,intelligentcontrolofcompressors,makingiteveneasiertooptimisecoolingcapacitywithconstanttemperatureandpressurelevelsforwaterchillers,andothertypicalcompressorapplica-tionsinHVAC.
Replace a cascade with a single compressorThe VLT® HVAC Drive provides the samelevelofflexibilitywithonelargecompressorinsteadofacascadeof2or3smallercompressors.TheVLT®HVACDriveoperatesallcom-pressorsatafarmorerefinedrangeofspeedsthannormal–evenabovenominalspeed–meaningthatonelargecompressorissufficient.
![Page 20: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/20.jpg)
20
VLT® HVAC Drive projects
Tropical Islands Resort near Berlin, GermanyAsteady25°Cairtemperature,31°Cwatertemperature,norain,andapleasant40%to60%humidityfortheresort’stropicalplants.Everyone’sideaofperfectweather!AllthisispossiblewithafirstclassclimateandwatercontrolsystemdrivenbyVLT®HVACDrives.
Opera House in Sydney, AustraliaTheSydneyOperaHouseisoneofthearchitecturalwondersoftheworld,andperhapsthebestknownbuildingofthe20thcentury.In2001,theNSWGovernmentprovided$69millionforseveralprojectstoimprovethefacilitiesandenvironmentforperformingartscompanies,patronsandvisitors.Danfossprovidedthedrives.
Shanghai General Motors, ChinaShanghaiGeneralMotorsCoLtd.isa50-50%joint venturebetweenGeneralMotorsandtheShanghaiAutomotiveIndustryCorporationGroup(SAIC).ShanghaiGMhasanannualproductioncapacityof200,000vehicles.DanfossprovidestheVLT®HVACdrivestomaintaintheproductionenvironment.
Dubai MetroDanfossDrivesdeliveratotalof176drivesratedfrom90to325kWforthenewmetroinDubai,UnitedArabEmirates,tooperateexhaustfansandtunnelventilation.DubaiMetroisprojectedtocarryapproximate-ly1.2millionpassengersonanaverageday,and355millionpassengersperyear.
Torre Mayor, Mexico CityWithits55floorsandaheightof225mtheTorreMayoristhehighestbuildinginLatinAmerica.Danfossdrivescontroltheheatingandventilation.
Orlando Medical Center, Florida, USADanfossdrivesarepartoftheeconomicalandenergysmartsolutionthathelpskeepstaff and patientscoolandcomfortableinthe20,000m2 OrlandoRegionalMedicalCenterinthemiddleofsunnyFlorida.
![Page 21: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/21.jpg)
21
Specifications(Basicunitwithoutextensions)
Main supply (L1, L2, L3)
Supplyvoltage 200–240V±10%
Supplyvoltage 380–480V±10%
Supplyvoltage 525–600V±10%
Supplyvoltage 525–690V±10%
Supplyfrequency 50/60Hz
Displacementpowerfactor(cosф)nearunity >0.98
SwitchingoninputsupplyL1,L2,L3 1–2times/min.
Harmonicdisturbance MeetsEN61000-3-12
Output data (U, V, W)
Outputvoltage 0–100%ofsupplyvoltage
Outputfrequency 0–1000Hz
Switchingonoutput Unlimited
Ramptimes 1–3600sec.
Digital inputs
Programmabledigitalinputs 6*
Changeabletodigitaloutput 2(terminal27,29)
Logic PNP or NPN
Voltagelevel 0–24VDC
Maximumvoltageoninput 28VDC
Inputresistance,Ri Approx.4kΩ
Scan interval 5ms
* 2 can be used as digital outputs
Analogue inputs
Analogueinputs 2
Modes Voltageorcurrent
Voltagelevel 0to+10V(scaleable)
Current level 0/4to20mA(scaleable)
Accuracyofanalogueinputs Max.error:0.5%offullscale
Pulse inputs
Programmablepulseinputs 2*
Voltagelevel 0–24VDC(PNPpositivelogic)
Pulseinputaccuracy(0.1–1kHz) Max.error:0.1%offullscale
* Utilize some of the digital inputs
Digital outputs
Programmabledigital/pulseoutputs 2
Voltagelevelatdigital/frequencyoutput 0–24VDC
Max.outputcurrent(sinkorsource)
40mA
Maximumoutputfrequencyatfrequencyoutput 0to32kHz
Accuracyonfrequencyoutput Max.error:0.1%offullscale
Analogue output
Programmableanalogueoutputs 1
Currentrangeatanalogueoutput 0/4–20mA
Max.loadtocommonatanalogueoutput(clamp30) 500Ω
Accuracyonanalogueoutput Max.error:1%offullscale
Control card
USBinterface 1.1(FullSpeed)
USBplug Type“B”
RS485interface Upto115kBaud
Max.load(10V) 15mA
Max.load(24V) 200mA
Relay output
Programmablerelayoutputs 2
Max.terminalload(AC)on1-3(break),1-2(make),4-6(break)powercard
240VAC,2A
Max.terminalload(AC)on4-5(make)powercard 400VAC,2A
Min.terminalloadon1-3(break),1-2(make),4-6(break),4-5(make)power card
24VDC10mA,24VAC20mA
Surroundings/external
Enclosure IP00,IP20,IP21,IP54,IP55,IP66
Vibrationtest 1.0g(D,E&F-enclosures:0.7g)
Max.relativehumidity 5%–95%(IEC721-3-3;Class3K3(non-condensing)duringoperation
Ambienttemperature Max.50°C
Galvanicisolationofall I/OsuppliesaccordingtoPELV
Aggressiveenvironment Designedforcoated/uncoated3C3/3C2(IEC60721-3-3)
Fieldbus communication
Standardbuilt-in:FC Protocol N2MetasysFLNApogeeModbusRTU
Optional:Profibus(MCA101)DeviceNet(MCA104)LonWorks(MCA108)BACnet(MCA109)
Protection mode for longest possible up-time
• Electronicthermalmotorprotectionagainstoverload
• Temperaturemonitoringoftheheatsinkensuresthatthefrequencyconvertertripsifthetemperaturereaches95°C±5°C.
• Thefrequencyconverterisprotectedagainstshort-circuitsonmotorterminalsU,V,W.
• ThefrequencyconverterisprotectedagainstearthfaultsonmotorterminalsU,V,W.
• Protectionagainstmainsphaseloss
GlobalMarine
![Page 22: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/22.jpg)
22
Power,currentsandenclosures
Dimensions [mm]A2 A3 A5 B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4
H 268 420 480 650 399 520 680 770 550 660 1209 1589 1046 1327W 90 130 242 165 230 308 370 308 370 420 408D 205 200 260 249 242 310 335 333 380 375H+ 375 475 670 755 950W+ 90 130 165 255 329 391
H and W dimensions are with back-plate. H+ and W+ are with IP upgrade kit. D dimensions are without option A/B.
T2 200 – 240 V T4 380 – 480 V T6 525 – 600 V T7 525 – 690 V
FC102 kW Amp. IP 2
0
IP21
IP 5
5
IP 6
6Amp. Amp.
IP 0
0
IP 2
0
IP21
IP 5
4
IP 5
5
IP 6
6
Amp.
IP 2
0
IP21
IP 5
5
IP 6
6
Amp.
IP 0
0
IP21
IP54/
55
≤440 V >440V 400 V ≥460 V ≤550 V >550V 550 V 690V
P1K1 1.1 6.6
A2 A2
A5 A5
3 2.7
A2 A2 A5 A5
2.6 2.4
A3 A3 A5 A5P1K5 1.5 7.5 4.1 3.4 2.9 2.7
P2K2 2.2 10.6 5.6 4.8 4.1 3.9
P3K0 3 12.5A3 A3
7.2 6.3 5.2 4.9
P3K7 3.7 16.7
P4K0 4.0 10 8.2 A2 A2
A5 A5
6.4 6.1
A3 A3 A5 A5P5K5 5.5 24.2
B3 B1 B1 B1
13 11A3 A3
9.5 9
P7K5 7.5 30.8 16 14.5 11.5 11
P11K 11 46.2 24 21
B3 B1 B1 B1
19 18
B3 B1 B1 B1P15K 15 59.4B4
B2 B2 B2 32 27 23 22
P18K 18 74.8
C1 C1 C1
37.5 34 28 27
P22K 22 88C3
44 40
B4B2 B2 B2
36 34
B4B2 B2 B2
P30K 30 115 61 52 43 41
P37K 37 143C4 C2 C2 C2
73 65
C1 C1 C1
54 52
C1 C1 C1P45K 45 170 90 80C3
65 62C3
56 54
D3 D1 D1
P55K 55 106 105 87 83 76 73
P75K 75 147 130C4 C2 C2 C2
105 100C4 C2 C2 C2
90 86
P90K 90 177 160 137 131 113 108
P110 110 212 190D3 D1 D1
137 131
P132 132 260 240 162 155
P160 160 315 302
D4 D2 D2
201 192
P200 200 395 361 253 242D4 D2 D2
P250 250 480 443 303 290
IP00/Chassis IP20/Chassis IP21/NEMAType1 Withupgradekit* IP54/NEMAType12 IP55/NEMAType12 IP 66/NEMAType4X
* MCF 101 – IP 21 upgrade kit
![Page 23: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/23.jpg)
23
Ordering type code for VLT® HVAC Drive
FC-102 – – – – – – – – – – X – SXX X – X – – – CX – X – XX –
[1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18]
Based on your selection, Danfoss manufac-tures the desired VLT® HVAC Drive. You will receive a fully assembled frequency converter, tested under full load conditions.
[9] Mains Input
X No option
1 Mains disconnect
3 Mains disconnect and fuses
5 Mains disconnect, fuses and load sharing
7 Fuses
A Fuses & load sharing terminals
D Load sharing terminals
[10] Cable
X Standard Cable Entries
O Metric Cable Entries
[13] A Option (Fieldbus)
AX No fi eldbus option
A0 MCA 101 – Profi bus DPV1
A4 MCA 104 – DeviceNet
AG MCA 108 – LonWorks
AJ MCA 109 – BACnet
[14] B Option (Application)
BX No application option
BK MCB 101 – General Purpose I/O
BP MCB 105 – Relay Expansion
B0 MCB 109 – Analog I/O
[18] D Option (Control Power Backup Input)
DX No DC input installed
D0 MCB 107 24 VDC backup input
Please beware that not all combinations are possible. Find help confi guring your drive with the online confi gurator found under: driveconfi g.danfoss.com
[1] Application
102 VLT® HVAC Drive FC 102
[2] Power Size
P1K1
See ratings data on page 16for power ratings
P1K5
P2K2
P3K0
P3K7
P4K0
P5K5
P7K5
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
P110
P132
P160
P200
P250
P315
P355
P400
P450
P500
P560
P630
P710
P800
P900
P1M0
P1M2
[3] AC Line Voltage
T2 3 x 200/240 V AC (1.1 – 45 kW)
T4 3 x 380/480 V AC
T6 3 x 525/600 V AC (1.1 – 90 kW)
T7 3 x 525/690 V AC (45 kW – 1.2 MW)
[4] Enclosure
For cabinet mounting:
E00 IP 00 (enclosure D3, D4)
E20 IP 20 (enclosure A2, A3, B3, B4, C3, C4)
Standalone:
E21 IP 21 (enclosure B1, B2, C1, C2, D1, D2, E, F)
E54 IP 54 (enclosure D1, D2, E, F)
E55 IP 55 (enclosure A5, B1, B2, C1, C2)
E66 IP 66 (enclosure A5, B1, B2, C1, C2)
Special designs:
C00IP 00 (enclosure E00 – air duct in stainless steel)
P20 IP 20 (enclosure B4, C3, C4 – Back Plate)
E2M IP 21 (enclosure D1, D2 – protective cover)
P21 IP 21 (enclosure as E21 – Back Plate)
E5M IP 54 (enclosure D1, D2 – protective cover)
P55 IP 55 (enclosure as E55 – Back Plate)
[5] RFI Filter (EN 55011)
H1 RFI-Filter Class A1/B (A, B, C)
H2 RFI-Filter, Class A2 (A, B, C, D, E, F)
H3 RFI -Filter Class A1/B (A, B, C)
H4 RFI-Filter, Class A1 (D, E, F)
H6 RFI-Filter für Marine
HX No RFI-Filter (A, B, C, 525 – 600 V)
[6] Braking & Safety
X No brake IGBT
B Brake IGBT mounted
T Safe stop without brake
U With brake and Safe Stop
[7] Display (Local Control Panel)
X Blank faceplate, no LCP installed
G LCP 102 – Graphic LCP installed
N LCP 101 – Numeric LCP installed
[8] Conformal Coating (IEC 721-3-3)
X No conformal coating
C Conformal coating on all PCBs
![Page 24: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/24.jpg)
24
3 Phasepowerinput
91 (L1)92 (L2)93 (L3)
PE
88 (-)89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
18 (D IN)
20 (COM D IN)
Switch ModePower Supply10Vdc15mA 200mA
+ - + -
(U) 96(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
Analog Output0/4-20 mA
RS-485RS-485Interface
DC-Bus
03
Motor
0-10Vdc
+10Vdc
0-10Vdc0/4-20 mA
240Vac, 2A
24Vdc
02
01
05
04
06240Vac, 2A
24V (NPN) 0V (PNP)
0V (PNP)24V (NPN)
19 (D IN)
24V (NPN) 0V (PNP)27
24V
0V
(D IN/OUT)
0V (PNP)24V (NPN)
(D IN/OUT)
0V
24V29
24V (NPN) 0V (PNP)
0V (PNP)24V (NPN)
33 (D IN)
32 (D IN)
12
ON
S201
ON2
1S202ON=0-20mAOFF=0-10V
95
400Vac, 2AP 5-00
21 O
N
S801ON=TerminatedOFF=Open
relay2
relay1
Brakeresistor
(R+) 82
(R-) 81
37 (D IN)(NPN) = Sink(PNP) = Source*
Par. 6 - 50
ConnectionexamplesThenumbersrepresenttheterminalsonthedrive
Thisdiagramshowsatypicalinstalla-tionoftheVLT®HVACDrive.Powerisconnectedtotheterminals91(L1),92(L2)and93(L3)andthemotoriscon-nectedto96(U),97(V)and98(W).
Terminals88and89areusedforloadsharingbetweendrives.Analogueinputscanbeconnectedto
the53(VormA),54(VormA)terminals.
Theseinputscanbesetuptoeitherreference,feedbackorthermistor.Thereare6digitalinputstobecon-nectedtoterminals18,19,27,29,32,and33.Twodigitalinput/outputterminals(27and29)canbesetup
asdigitaloutputstoshowanactualstatusorwarning.Theterminal42analogueoutputcanshowprocessvaluessuchas0-Imax.
Onthe68(P+)and69(N-)terminals’RS485interface,thedrivecanbecontrolledandmonitoredviaserialcommunication.
* Safe Stop optional
![Page 25: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/25.jpg)
25
EnclosureIP 20 (IP 21*)/Chassis B3 B4 C3 C4
IP 21/NEMA 1, IP 55 + IP 66/NEMA 12 B1 B2 C1 C2P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical Shaft Output [kW] 5.5 7.5 11 15 18.5 22 30 37 45Typical Shaft Output at 208 V [HP] 7.5 10 15 20 25 30 40 50 60
Output Current (3x200–240V)
Continuous [A] 24.2 30.8 46.2 59.4 74.8 88.0 115 143 170Intermittent [A] 26.6 33.9 50.8 65.3 82.3 96.8 127 157 187
Output Power(208VAC) Continuous [kVA] 8.7 11.1 16.6 21.4 26.9 31.7 41.4 51.5 61.2
Max. cable size Mains,motor,brake
[mm2]([AWG]) 10(7) 35(2) 50(1/0)
(B4=35(2)) 95(4/0)120(250MCM)
Max. cable size mainsWithmainsdisconnectswitchincluded
[mm2]([AWG]) 16(6) 35(2) 35(2) 70(3/0)
185(kcmil350)
Max. Input Current(3x200–240V)
Continuous[A]
22.0 28.0 42.0 54.0 68.0 80.0 104.0 130.0 154.0Intermittent 24.2 30.8 46.2 59.4 74.8 88.0 114.0 143.0 169.0
Max. pre-fuses [A] 63 63 63 80 125 125 160 200 250EnvironmentEstimated power loss at rated max. load [W] 269 310 447 602 737 845 1140 1353 1636WeightIP 20 [kg] 12 12 12 23.5 23.5 35 35 50 50IP21,IP55,IP66 [kg] 23 23 23 27 45 45 45 65 65Efficiency 0.96 0.96 0.96 0.96 0.96 0.97 0.97 0.97 0.97
200–240VAC
EnclosureIP 20 (IP 21*)/Chassis A2 A2 A2 A3 A3
IP 55 + IP 66 /NEMA 12 A5 A5 A5 A5 A5P1K1 P1K5 P2K2 P3K0 P3K7
Typical Shaft Output [kW] 1.1 1.5 2.2 3 3.7Typical Shaft Output at 208 V [HP] 1.5 2.0 2.9 4.0 4.9
Output Current(3x200–240V)
Continuous [A] 6.6 7.5 10.6 12.5 16.7Intermittent [A] 7.3 8.3 11.7 13.8 18.4
Output Power(208VAC) Continuous [kVA] 2.38 2.70 3.82 4.50 6.00
Max. cable size(Mains,motor,brake)
[mm2]([AWG]) 4(10)
Max. Input Current(3x200–240V)
Continuous [A] 5.9 6.8 9.5 11.3 15.0Intermittent [A] 6.5 7.5 10.5 12.4 16.5
Max. pre-fuses [A] 20 20 20 32 32EnvironmentEstimated power loss at rated max. load [W] 63 82 116 155 185WeightIP 20 [kg] 4.9 4.9 4.9 6.6 6.6IP21 [kg] 5.5 5.5 5.5 7.5 7.5IP55,IP66 [kg] 13.5 13.5 13.5 13.5 13.5Efficiency 0.96 0.96 0.96 0.96 0.96
* (A2, A3, B3, B4, C3 and C4 may be converted to IP21 using a conversion kit. (Please see also items Mechanical mounting in Operating Instructions and IP 21/ Type 1 Enclosure kit in the Design Guide.))
![Page 26: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/26.jpg)
26
380–480VAC
EnclosureIP 20 (IP 21*)/Chassis A2 A2 A2 A2 A2 A3 A3
IP 55 + IP 66 /NEMA 12 A5 A5 A5 A5 A5 A5 A5P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output [kW] 1.1 1.5 2.2 3 4 5.5 7.5Typical Shaft Output at 460 V [HP] 1.5 2.0 2.9 4.0 5.0 7.5 10
Output Current(3x380–440V)
Continuous [A] 3 4.1 5.6 7.2 10 13 16Intermittent [A] 3.3 4.5 6.2 7.9 11 14.3 17.6
Output Current(3x441–480V)
Continuous [A] 2.7 3.4 4.8 6.3 8.2 11 14.5Intermittent [A] 3.0 3.7 5.3 6.9 9.0 12.1 15.4
Output Power(400VAC) Continuous [kVA] 2.1 2.8 3.9 5.0 6.9 9.0 11.0
Output Power(460VAC) Continuous [kVA] 2.4 2.7 3.8 5.0 6.5 8.8 11.6
Max. cable size(Mains,motor,brake)
[mm2]([AWG]) 4(10)
Max. Input Current(3x380–440V)
Continuous [A] 2.7 3.7 5.0 6.5 9.0 11.7 14.4Intermittent [A] 3.0 4.1 5.5 7.2 9.9 12.9 15.8
Max. Input Current(3x441–480V)
Continuous [A] 2.7 3.1 4.3 5.7 7.4 9.9 13.0Intermittent [A] 3.0 3.4 4.7 6.3 8.1 10.9 14.3
Max. pre-fuses [A] 10 10 20 20 20 32 32EnvironmentEstimated power loss at rated max. load [W] 58 62 88 116 124 187 255WeightIP 20 [kg] 4.8 4.9 4.9 4.9 4.9 6.6 6.6IP55,IP66 [kg] 13.5 13.5 13.5 13.5 13.5 14.2 14.2Efficiency 0.96 0.97 0.97 0.97 0.97 0.97 0.97
* (A2, A3, B3, B4, C3 and C4 may be converted to IP21 using a conversion kit. Please contact Danfoss. (Please see also items Mechanical mounting in Operating Instructions and IP 21/ Type 1 Enclosure kit in the Design Guide.))
1) Withbrakeandloadsharing95(4/0)
EnclosureIP 20 (IP 21*)/Chassis B3 B4 C3 C4
IP 21/NEMA 1, IP 55 + IP 66/NEMA 12 B1 B2 C1 C2P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 11 15 18.5 22 30 37 45 55 75 90Typical Shaft Output at 460 V [HP] 15 20 25 30 40 50 60 75 100 125
Output Current (3x380–439V)
Continuous [A] 24 32 37.5 44 61 73 90 106 147 177Intermittent [A] 26.4 35.2 41.3 48.4 67.1 80.3 99 117 162 195
Output Current (3x440–480V)
Continuous [A] 21 27 34 40 52 65 80 105 130 160Intermittent [A] 23.1 29.7 37.4 44 61.6 71.5 88 116 143 176
Output Power(400VAC) Continuous [kVA] 16.6 22.2 26 30.5 42.3 50.6 62.4 73.4 102 123
Output Power(460VAC) Continuous [kVA] 16.7 21.5 27.1 31.9 41.4 51.8 63.7 83.7 104 128
Max. cable size Mains,motor,brake
[mm2]([AWG]) 10(7) 35(2) 50(1/0)
(B4=35(2)) 95(4/0)120(250
MCM)1)
Max. cable size mainsWithmainsdisconnectswitchincluded
[mm2]([AWG]) 16(6) 35(2) 70(3/0)
185(kcmil350)
Max. Input Current(3x380–439V)
Continuous[A]
22 29 34 40 55 66 82 96 133 161Intermittent 24.2 31.9 37.4 44 60.5 72.6 90.2 106 146 177
Max. Input Current(3x440–480V)
Continuous[A]
19 25 31 36 47 59 73 95 118 145Intermittent 20.9 27.5 34.1 39.6 51.7 64.9 80.3 105 130 160
Max. pre-fuses [A] 63 63 63 63 80 100 125 160 250 250EnvironmentEstimated power loss at rated max. load [W] 278 392 465 525 698 739 843 1083 1384 1474WeightIP 20 [kg] 12 12 12 23.5 23.5 23.5 35 35 50 50IP21,IP55,IP66 [kg] 23 23 23 27 27 45 45 45 65 65Efficiency 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.99
![Page 27: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/27.jpg)
27
525–600VAC
EnclosureIP 20 Chassis
A3 A3B3 B4 C3 C4
IP 21/NEMA 1B1 B2 C1 C2
IP 55, IP 66/NEMA 12 A5P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90Output CurrentContinuous(3x525–550V) [A] 2.6 2.9 4.1 5.2 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 137
Intermittent(3x525–550V) [A] 2.9 3.2 4.5 5.7 7.0 10.5 12.7 21 25 31 40 47 59 72 96 116 151
Continuous(3x525–600V) [A] 2.4 2.7 3.9 4.9 6.1 9.0 11.0 18 22 27 34 41 52 62 83 100 131
Intermittent(3x525–600V) [A] 2.6 3.0 4.3 5.4 6.7 9.9 12.1 20 24 30 37 45 57 68 91 110 144
Output PowerContinuous (525VAC) [kVA] 2.5 2.8 3.9 5.0 6.1 9.0 11.0 18.1 21.9 26.7 34.3 41 51.4 61.9 82.9 100 130.5
Continuous(575VAC) [kVA] 2.4 2.7 3.9 4.9 6.1 9.0 11.0 17.9 21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5
Max. cable size IP21/55/66(mains,motor,brake)
[mm2]([AWG])
4(10) 10(7) 35(2) 50(1/0) 95(4/0)
120(250MCM)
Max. cable size IP 20(mains,motor,brake)
[mm2]([AWG])
4(10) 10(7) 35(2) 50(1/0) 95(4/0)
150(250
MCM)1)
Max. cable size mainsWithmainsdisconnectswitch included
[mm2]([AWG])
4(10) 16(6) 35(2) 70(3/0)
185(kcmil350)
Max. Input CurrentContinuous(3x525–600V) [A] 2.4 2.7 4.1 5.2 5.8 8.6 10.4 17.2 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3
Intermittent(3x525–600V) [A] 2.7 3.0 4.5 5.7 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 137
Max. pre-fuses [A] 10 10 20 20 20 32 32 63 63 63 63 80 100 125 160 250 250EnvironmentEstimated power loss at rated max. load [W] 50 65 92 122 145 195 261 300 400 475 525 700 750 850 1100 1400 1500
WeightIP 20 [kg] 6.5 6.5 6.5 6.5 6.5 6.6 6.6 12 12 12 23.5 23.5 23.5 35 35 50 50IP21,IP55,IP66 [kg] 13.5 13.5 13.5 13.5 13.5 14.2 14.2 23 23 23 27 27 27 45 45 65 65Efficiency 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
1) Withbrakeandloadsharing95(4/0)
![Page 28: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/28.jpg)
28
380–480VACand525–690VACHighPower
380 – 480 VAC
EnclosureIP 21, IP 54 D1 D2
IP 00 D3 D4P110 P132 P160 P200 P250
Typical Shaft Output at 400 V [kW] 110 132 160 200 250Typical Shaft Output at 460 V [HP] 150 200 250 300 350Output Current Continuous(at400V) [A] 212 260 315 395 480Intermittent(60secoverload)(at400V) [A] 233 286 347 435 528Continuous(at460/480V) [A] 190 240 302 361 443Intermittent(60secoverload)(at460/480V) [A] 209 264 332 397 487Output PowerContinuous(at400V) [kVA] 147 180 218 274 333Continuous(at460V) [kVA] 151 191 241 288 353Max. Input Current Continuous(at400V) [A] 204 251 304 381 463Continuous(at460/480V) [A] 183 231 291 348 427Max. cable size Mainsmotor,brakeandloadshare
[mm2]([AWG])
2x70(2x2/0)
2x150(2x300mcm)
Max. external pre-fuses [A] 300 350 400 500 630Estimated power loss at rated max. load – 400 V [W] 3234 3782 4213 5119 5893Estimated power loss at rated max. load – 460 V [W] 2947 3665 4063 4652 5634
WeightIP21,IP54 [kg] 96 104 125 136 151IP 00 [kg] 82 91 112 123 138
Efficiency 0.98Output Frequency [Hz] 0–800Heatsink overtemp. trip [°C] 85 90 105 105 115Power card ambient trip [°C] 60
525 – 690 VAC
EnclosureIP 21, IP 54 D1 D2
IP 00 D3 D4P45K P55K P75K P90K P110 P132 P160 P200 P250
Typical Shaft Output at 550 V [kW] 37 45 55 75 90 110 132 160 200Typical Shaft Output at 575 V [HP] 50 60 75 100 125 150 200 250 300Typical Shaft Output at 690 V [kW] 45 55 75 90 110 132 160 200 250Output Current Continuous(at3x525–550V) [A] 56 76 90 113 137Continuous(at550V) [A] 162 201 253 303Intermittent(60secoverload)(at550V) [A] 62 84 99 124 151 178 221 278 333Continuous(at3x551–690V) [A] 54 73 86 108 131Continuous(at575/690V) [A] 155 192 242 290Intermittent(60secoverload)(at575/690V) [A] 59 80 95 119 144 171 211 266 319Output PowerContinuous(at550V) [kVA] 53 72 86 108 131 154 191 241 289Continuous(at575V) [kVA] 54 73 86 108 130 154 191 241 289Continuous(at690V) [kVA] 65 87 103 129 157 185 229 289 347Max. Input Current Continuous(at550V) [A] 60 77 89 110 130 158 198 245 299Continuous(at575V) [A] 58 74 85 106 124 151 189 234 286Continuous(at690V) [A] 58 77 87 109 128 155 197 240 296Max. cable size Mains,motor,loadshareandbrake
[mm2]([AWG])
2x70(2x2/0)
2x70(2x2/0)
2x150(2x300mcm)
Max. external pre-fuses [A] 125 160 200 200 250 315 350 350 400Estimated power loss at rated max. load – 600 V [W] 1398 1645 1827 2157 2533 2963 3430 4051 4867Estimated power loss at rated max. load – 690 V [W] 1458 1717 1913 2262 2662 3430 3612 4292 5156
WeightIP21,IP54 [kg] 96 104 125 136IP 00 [kg] 82 91 112 123
Efficiency 0.97 0.98Output Frequency [Hz] 0–600Heatsink overtemp. trip [°C] 85 90 110Power card ambient trip [°C] 60
![Page 29: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/29.jpg)
29
DimensionsVLT®HVACDriveInmm
Min.1
00
Exha
ust
Inle
tM
in.1
00
∅ 5,5
Rear View
∅ 5,5205(220)
7090
257
268
341
Exhaust
Inlet
Depth220mmwithA/B-Options
341
Min.1
00
Exha
ust
Inle
t
Min.1
00 ∅ 5,5
Rear View
∅ 5,5
205(220)
268
257
Exhaust
Inlet
Depth220mmwithA/B-Options
110130
A1
Geh
äuse
180
A2
Encl
osu
res
A3
Geh
äuse
A3
Encl
osu
res
![Page 30: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/30.jpg)
30
DimensionsVLT®HVACDriveInmm
A5
Encl
osu
res
B1
Encl
osu
res
B2
Encl
osu
res
Min.1
00
Exha
ust
Inle
t
Min.1
00
∅ 6,5 Rear View
∅ 6,5
200215
402
420
Exhaust
Inlet
242
Inle
tM
in.1
00
∅ 9Rear View
∅ 9
260
210
454
480
650
Exhaust
Inlet
Min.2
00
Exha
ust
Inle
t
Min.2
00 ∅ 9Rear View
∅ 9
260
242
624
Exhaust
Inlet
210
Min.1
00
Exha
ust
242
![Page 31: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/31.jpg)
31
A1
Geh
äuse
180
B3
Encl
osu
res
B4
Encl
osu
res
A3
Geh
äuse
C1
Encl
osu
res
DimensionsVLT®HVACDriveInmm
Min.2
00
Exha
ust
Inle
t
Min.2
00
∅ 6,8 Rear View
∅ 6,8
249(262) 165
140
399
380
419
Exhaust
Inlet
Depth262mmwithA/B-Options
Min.2
00
Exha
ust
Inle
tM
in.2
00
∅ 8,5Rear View
∅ 8,5242
200
231
495
520
460
595
35
680
Exhaust
Inlet
Min.2
00
Exha
ust
Inle
t
Min.2
00
∅ 9 Rear View
∅ 9310308
648
Exhaust
Inlet
272
![Page 32: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/32.jpg)
32
DimensionsVLT®HVACDriveInmm
C2
Encl
osu
res
C3
Encl
osu
res
C4
Encl
osu
res
Min.2
25
Exha
ust
Inle
t
Min.2
25
∅ 9Rear View
∅ 9
335
334
739
770
Exhaust
Inlet
370
Inle
tM
in.2
00
∅ 8,5Rear View
∅ 8,5334 308
270
21052
1
550
630
3636
488
Exhaust
Inlet
Min.2
25
Exha
ust
Inle
t
Min.2
25 ∅ 8,5
Rear View
∅ 8,5Exhaust
Inlet
Min.2
00
Exha
ust
631
660
800
598
334370330
![Page 33: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/33.jpg)
33
A1
Geh
äuse
180
D1
Encl
osu
res
(Flo
or-
or
cab
inet
Mo
un
t)
A3
Geh
äuse
D2
Encl
osu
res
(Flo
or-
or
cab
inet
Mo
un
t)
DimensionsVLT®HVACDriveInmm
Optional pedestal 176F1827 availablefor stand-alone floor mount installations
(adds 200 mm to height)
Min.2
25In
let
Min.2
2Ex
haus
t
420
1166
310
417
380
1209
765m3/hr
170m3/hr
74
163
Optional pedestal 176F1827 availablefor stand-alone floor mount installations
(adds 200 mm to height)
Drives shown with optional disconnect switch
Min.2
25In
let
Min.2
25Ex
haus
t
420
1547
423
417
380
1589
765m3/hr
170m3/hr
72
1362
157
981
![Page 34: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/34.jpg)
34
D3
Encl
osu
res
(Cab
inet
Mo
un
t)D
4 En
clo
sure
s (C
abin
et M
ou
nt)
DimensionsVLT®HVACDriveInmm
Equus 3100 Innova Diagnostic Code Reader
Drives shown with optional disconnect switch
Min.2
25In
let
Min.2
25Ex
haus
tM
in.2
25In
let
Min.2
25Ex
haus
t
408
997
147
417
375
1046
765m3/hr 255m3/hr66
818
157
408
1280
161
417
375
1327
765m3/hr 255m3/hr66
1099
151
![Page 35: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/35.jpg)
35
VLT® HVAC Drive Options
Typec
odePo
sitio
n
VLT® PROFIBUS DP V1 MCA 101• PROFIBUSDPV1givesyouwidecompatibility,ahighlevelofavailability,supportforallmajorPLCvendors, andcompatibilitywithfutureversions
• Fast,efficientcommunication,transparentinstallation,advanceddiagnosisandparameterisationand auto-configurationofprocessdataviaGSD-file
• A-cyclicparameterisationusingPROFIBUSDPV1,PROFIdriveorDanfossFCprofilestatemachines,PROFIBUSDPV1,MasterClass1and2
Ordering number 130B1100 uncoated – 130B1200 coated (Class 3C3/IEC 60721-3-3) 13
VLT® DeviceNet MCA 104• Thismoderncommunicationsmodelofferskeycapabilitiesthatletyoueffectivelydetermine whatinformationisneededandwhen
• YouwillalsobenefitfromODVA’sstrongconformancetestingpolicies,whichensurethatproductsareinteroperableOrdering number 130B1102 uncoated – 130B1202 coated (Class 3C3/IEC 60721-3-3)
13
VLT® LonWorks MCA 108LonWorksisafieldbussystemdevelopedforbuildingautomation.Itenablescommunicationbetweenindividualunitsinthesamesystem(peer-to-peer)andthussupportsdecentralisingofcontrol.• Noneedforbigmainstation(master-follower)• Unitsreceivesignalsdirectly• SupportsEchelonfree-topologyinterface(flexiblecablingandinstallation)• SupportsembeddedI/OsandI/Ooptions(easyimplementationofde-centralI/Os)• Sensorsignalscanquicklybemovedtoanothercontrollerviabuscables• CertifiedascompliantwithLonMarkver.3.4specificationsOrdering number 130B1106 uncoated – 130B1206 coated (Class 3C3/IEC 60721-3-3)
13
VLT® BACnet MCA 109Theopencommunicationsprotocolforworldwidebuildingautomationuse.TheBACnetprotocolisaninternationalproto-colthatefficientlyintegratesallpartsofbuildingautomationequipmentfromtheactuatorleveltothebuildingmanage-mentsystem.• BACnetistheworldstandardforbuildingautomation• InternationalstandardISO16484-5• Withnolicensefees,theprotocolcanbeusedinbuildingautomationsystemsofallsizes• TheBACnetoptionletsthedrivecommunicatewithbuildingmanagementsystemsrunningtheBACnetprotocol• TypicalareaswhereBACnetisusedincludeheating,ventilation,coolingandclimateequipmentcontrol• TheBACnetprotocoliseasilyintegratedintoexistingcontrolequipmentnetworksOrdering number 130B11446 uncoated – 130B1244 coated (Class 3C3/IEC 60721-3-3)
13
A
![Page 36: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/36.jpg)
36
VLT® HVAC Drive Options
Typec
odePo
sitio
n
14
VLT® General Purpose I/O MCB 101 TheI/Ooptionoffersanextendednumberofcontrolinputsandoutputs.• 3digitalinputs0-24V:Logic‘0’<5V;Logic‘1’>10V• 2analogueinputs0-10V:Resolution10bitplussign• 2digitaloutputsNPN/PNPpushpull• 1analogueoutput0/4-20mA• Springloadedconnection• SeparateparametersettingsOrdering number 130B1125 uncoated – 130B1212 coated (Class 3C3/IEC 60721-3-3)
14
VLT® Relay Option MCB 105Letsyouextendrelayfunctionswith3additionalrelayoutputs.Max.terminalload:• AC-1Resistiveload...........................................................240 V AC 2 A• AC-15Inductiveload@cosф0.4..............................240VAC0.2A• DC-1Resistiveload............................................................. 24VDC1A• DC-13Inductiveload@cosф0.4...............................24VDC0.1A
Min.terminalload:• DC5V................................................................................................. 10mA• Maxswitchrateatratedload/min.load.............. 6min-1/20sec-1
Ordering number 130B1110 uncoated – 130B1210 coated (Class 3C3/IEC 60721-3-3)
14
VLT® Analog I/O Option MCB 109 Thisanalogueinput/outputoptioniseasilyfittedinthefrequencyconverterforupgradingtoadvancedperformanceandcontrolusingtheadditionalin/outputs.Thisoptionalsoupgradesthefrequencyconverterwithabatteryback-upsupplyfortheclockbuiltintothefrequencyconverter.Thisprovidesstableuseofallfrequencyconverterclockfunctionsastimedactionsetc.
• 3analogueinputs,eachconfigurableasbothvoltageandtemperatureinput• Connectionof0-10VanaloguesignalsaswellasPT1000andNI1000temperatureinputs• 3analogueoutputseachconfigurableas0-10Voutputs• Incl.back-upsupplyforthestandardclockfunctioninthefrequencyconverter
Theback-upbatterytypicallylastsfor10years,dependingonenvironment.Ordering number 130B1143 uncoated – 130B1243 coated (Class 3C3/IEC 60721-3-3)
B
Installation of options is a matter of plug-and-play
![Page 37: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/37.jpg)
37
LCP
D
VLT® HVAC Drive Options
Typec
odePo
sitio
n
VLT® 24 V DC Supply Option MCB 107TheoptionisusedtoconnectanexternalDCsupplytokeepthecontrolsectionandanyinstalledoptionactivewhenmainspowerisdown. • Inputvoltagerange24VDC+/-15%(max.37Vin10sec.)• Max.inputcurrent..................................................2.2A• Max.cablelength...................................................75m• Inputcapitanceload.........................................<10uF• Power-updelay.....................................................<0.6s• Easytoinstallindrivesinexistingmachines• Keepsthecontrolboardandoptionsactiveduringpowercuts• KeepsfieldbusesactiveduringpowercutsOrdering number 130B1108 uncoated – 130B1208 coated (Class 3C3/IEC 60721-3-3)
14
Typec
odePo
sitio
n
LCP 102 Graphical Local Control Panel• Multi-languagedisplay• Statusmessages• QuickMenuforeasycommissioning• Parametersettingandexplanationofparameterfunction• Adjustmentofparameters• Fullparameterbackupandcopyfunction• Alarmlogging• Infobutton–explainsthefunctionoftheselecteditemondisplay• Hand-operatedstart/stop,orautomaticmodeselection• Resetfunction• TrendgraphOrdering number 130B1107
15 & 17
LCP 101 Numerical Local Control PanelThenumericalcontrolpaneloffersanexcellentMMIinterfacetothedrive.• Statusmessages• Quickmenuforeasycommissioning• Parametersettingandadjustment• Hand-operatedstart/stopfunctionorautomaticmodeselect• ResetfunctionOrdering number 130B1124
15
LCP Panel Mounting KitForeasyinstallationoftheLCP101andLCP102ine.g.acabinet.• IP65(front)• Thumbscrewsfortool-freeinstallation• Incl.3metersofcablesinindustryquality(alsoavailableseparately)• WithorwithoutLCPoperatingunit• EachtimeeasytoinstallOrdering number 130B1117 (Mounting kit for all LCP’s including fasteners, 3 m cable and gasket) Ordering number 130B1113 (Incl. graphical LCP, fasteners, 3 m cable and gasket)Ordering number 130B1114 (Incl. numerical LCP, fasteners and gasket)Ordering number 130B1129 (LCP front mounting IP55/IP66) – Ordering number 175Z0929 (cable only)Ordering number 130B1170 (Panel Mouting Kit for all LCP w.o. cable)
16
Installation of options is a matter of plug-and-play
![Page 38: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/38.jpg)
38
Profibus Adapter Sub-D9 ConnectorTheadaptermakeslinkingoffieldbusconnectionspluggable.ForusewithoptionA.• OptiontouseprefabricatedProfibuscabling• Forretrofit
Screw terminalsScrewterminalsasanalternativetothestandardspringloadedterminals.• Pluggable• TerminalnameisdescribedOrdering number 130B1116
IP 21/Type 12 (NEMA1) KitTheIP21/Type12(NEMA1)kitisusedforinstallationofVLT®drivesindryenvironments.TheenclosurekitsareavailableforframesizesA1,A2,A3,B3,B4,C3andC4• SupportsVLT®drivesfrom1.1to90kW• UsedonstandardVLT®driveswithorwithoutmountedoptionmodules• IP41ontopside• PG16andPG21holesforglands130B1122 for frame size A2, 130B1123 for frame size A3, 130B1187 for frame size B3, 130B1189 for frame size B4, 130B1191 for frame size C3, 130B1193 for frame size C4
Kit for panel through mountMountingkitforexternalcoolingoftheheatsinkforapplianceswithA5,B1,B2,C1andC2housing.• Theairconditionedinstallationspacecanbereduced.• Additionalcoolingmaybeomitted• Nocontaminationofelectronicsbyforcedventilation• Facilitatesintegratedassembly• Reducedcabinetdepth/lessspace
VLT® Brake ResistorsEnergygeneratedduringbrakingisabsorbedbytheresistors,protectingelectricalcomponentsfromheatingup.Danfossbrakeresistorscoverthefullpowerrange.• Quickbrakingofheavyloads• Brakingenergyisonlyabsorbedintothebrakeresistor• Externalmountingmakesitpossibletousethegeneratedheat• Allnecessaryapprovalsareavailable
USB ExtensionUSBextensionforIP55andIP66enclosures.MakestheUSBconnectoravailableoutsidethedrive.TheUSBextensionisdesignedformountinginacableglandinthebottomofthedrive,whichmakesPCcommunicationveryeasyevenindriveswithhighIPrating.USB extension for A5-B1 enclosures, 350 mm cable , ordering number 130B1155USB extension for B2-C enclosures, 650 mm cable , ordering number130B1156
VLT® HVAC Drive Accessories
Please refer to the product and design manuals for selection and dimensioning
![Page 39: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/39.jpg)
39
VLT® Harmonic Filter AHF 005/010 MCE Easy,effectiveharmonicdistortionreductionbyconnectingtheAHF005/010harmonicfilterinfrontofaDanfossfrequencyconverter.• AHF005reducestotalharmoniccurrentdistortionto5%• AHF010reducestotalharmoniccurrentdistortionto10%• Smallcompacthousingthatcanbefittedintoapanel• Easytouseinretrofitapplications• User-friendlystart-up–noadjustmentnecessary• Noroutinemaintenancerequired
VLT® Sine-Wave Filters MCC 101Sine-wavefiltersareplacedbetweenthefrequencyconverterandthemotortooptimisethemotorpowercurrent.Itprovidesasinusoidalphase-to-phasemotorvoltage.Thefiltersreducemotorinsulationstress,acousticnoisefromthemotor,andbearingcurrents(especiallyinlargemotors).• Reducesmotorinsulationstress• Reducesacousticnoisefromthemotor• Reducesbearingcurrents(especiallyinlargemotors)• Enablesuseoflongermotorcables• Reduceslossesinthemotor• Prolongsservicelifetime• IP20orIP21
VLT® dU/dt filter MCC 102VLT®dU/dtfiltersareplacedbetweenthefrequencyconverterandthemotortoeliminateveryfastvoltagechanges.Themotorterminalphase-to-phasevoltageisstillpulseshapedbutitsdU/dtvaluesarereduced.• Thesefiltersreducestressonthemotor’sinsulationandarerecommendedinapplicationswitholdermotors,aggressiveenvironmentsorfrequentbrakingwhichcauseincreasedDClinkvoltage.
• IP20orIP21
SVCD – regenerative braking Transferringthegeneratedpowerfromadeceleratingmotorbackintothepowersupplyenablesbrakingofvirtuallyunlimitedduration.• Energyefficientbraking• Self-synchronisation• DC-DCcouplingofmultipledrivespossible• HighefficiencythroughIGBTtechnology• Simpleoperation• Overloadprotectioninregenerativeoperation
VLT® HVAC Drive Accessories
Note: Missing numbers can be found in the design manual or can be delivered on request
![Page 40: New photo - chongda-yes.com.tw€¦ · Danfoss also provides active solutions such as Low Harmonic Drives, com-bining standard drives with an active filter and stand-aloneVLT® Advanced](https://reader035.fdocuments.us/reader035/viewer/2022070918/5fb8157aca851c78ba2608f6/html5/thumbnails/40.jpg)
Environmentallyresponsible
VLT®productsaremanufacturedwithrespectforthesafetyandwell-beingofpeopleandtheenvironment.
All activities are planned and per-formedtakingintoaccounttheindivid-ualemployee,theworkenvironmentandtheexternalenvironment.Produc-tiontakesplacewithaminimumofnoise,smokeorotherpollutionandenvironmentallysafedisposaloftheproductsispre-prepared.
UN Global CompactDanfosshassignedtheUNGlobalCompactonsocialandenvironmentalresponsibilityandourcompaniesactresponsiblytowardslocalsocieties.
EU Directives AllfactoriesarecertifiedaccordingtoISO14001standard.AllproductsfulfiltheEUDirectivesforGeneralProductSafetyandtheMachinerydirective.DanfossDrivesis,inallproductseries,implementingtheEUDirectivecon-cerningHazardousSubstancesinElec-tricalandElectricalEquipment(RoHS)andisdesigningallnewproductseriesaccordingtotheEUDirectiveonWasteElectricalandElectronicEquipment(WEEE).
Impact on energy savingsOneyear’senergysavingsfromouran-nualproductionofVLT®driveswillsavetheenergyequivalenttotheenergyproductionfromamajorpowerplant.Betterprocesscontrolatthesametimeimprovesproductqualityandreduceswasteandwearonequipment.
WhatVLT®isallaboutDanfoss Drives is the world leader among dedicated drives providers – and still gaining market share.
Dedicated to drivesDedicationhasbeenakeywordsince1968,whenDanfossintroducedtheworld’sfirstmassproducedvariablespeeddriveforACmotors–andnameditVLT®.
Twentyfivehundredemployees develop,manufacture,sellandservicedrivesandsoftstartersinmorethanonehundredcountries,focusedonlyondrivesandsoftstarters.
Intelligent and innovative DevelopersatDanfossDriveshavefullyadoptedmodularprinciplesindevelopmentaswellasdesign,productionandconfiguration.
Tomorrow’sfeaturesaredevelopedinparallelusingdedicatedtechnologyplatforms.Thisallowsthedevelop-mentofallelementstotakeplaceinparallel,atthesametimereducingtimetomarketandensuringthatcustomersalwaysenjoythebenefitsofthelatestfeatures.
Rely on the expertsWetakeresponsibilityforeveryelementofourproducts.Thefactthatwe develop and produce our own features,hardware,software,powermodules,printedcircuitboards,andaccessoriesisyourguaranteeofreliableproducts.
Local backup – globallyVLT®motorcontrollersareoperatingin applications all over the world and DanfossDrives’expertslocatedinmorethan100countriesarereadytosupportourcustomerswithapplica-tionadviceandservicewherevertheymaybe.
DanfossDrivesexpertsdon’tstop untilthecustomer’sdrivechallengesaresolved.
DKDD.PB.36.A1.02 VLT®isatrademarkofDanfossA/S ProducedbySMC/AO2009.03
Melbourne:Tel.(03)97035100,Fax.(03)97035159•Sydney: Tel.(02)88451800,Fax.(02)96386088•Brisbane:Tel.(07)36901899,Fax.(07)36302122Adelaide:Tel.(08)81507400,Fax.(08)84438033•Perth:Tel.(08)93333800,Fax.(08)94797200•Auckland:Tel.(09)2702110,Fax.(09)2702112•Christchurch:Tel.(03)3794365,Fax.(03)3794365www.danfoss.com/pacific•EmailAustralia:[email protected]•EmailNewZealand:[email protected]