New LSN SEISMIC CERTIFIED - hubbellcdn · 2017. 5. 30. · LSN with SEISMIC KIT • CBC 2007,...
Transcript of New LSN SEISMIC CERTIFIED - hubbellcdn · 2017. 5. 30. · LSN with SEISMIC KIT • CBC 2007,...
DUAL-LITE.COM
LSN SE ISMIC CERTIF IEDCENTRAL L IGHTING INVERTER
Rugged , shaker tab le tested des ign
Phys ica l l y w i thstands se ismic events and earthquakes
Cont inues normal and emergency operat ion dur ing and a f ter se ismic events and earthquakes
OSHPD Cert i f i ed
Type S standard 10 year l i f e VRLA batter ies
SEISMIC PERFORMANCE TESTED AND PROVEN
LSN SEISMIC OPTIONS
STANDARD LSN• No seismic certifications
or qualifications
LSN with SEISMIC KIT• CBC 2007, Category D• Certified through calculations only• SDS = 1.15g
LSN - SEISMIC CERTIFIED• UBC-1997, IBC-2012, CBC 2013 (OSHPD
OSP-0365-10), and ASCE7-10• Certified through table shaker test and
calculations• SDS = 2.0g for z/h=1 and SDS=2.5g for z/
h=0,Ip=1.5
LSN SEISMIC CERTIFIEDCENTRAL LIGHTING INVERTER
Due to our continued efforts to improve our products, specifications are subject to change without notice. Copyright © 2013 Hubbell Lighting All Rights Reserved.
For more information visit our web site: http://www.dual-lite.com/Phone: 1-864-678-1000
0603575 LSN Seismic Sell Sht -B 2/16
• Suits installation specifications calling for continued operation during
and after a seismic event
• CBC Category D seismic installations, NEMA Type 1 cabinetry
• Uninterruptible emergency lighting AC power system
• “No break” design transfers the load instantaneously when normal
power is interrupted
• 100% load compatible with any lighting source, including LED
• Off line design for high efficiency - up to 98%
• 90 minute emergency operation standard
• Single-phase, 60 Hz operation
• UL 924 / UL1778 Listed (with alternate run time options)
• NFPA 101 (Life Safety Code) / NFPA 70 (National Electrical Code)
• 2 year unit warranty w/ factory startup; 1 year full, 9 year prorated battery warranty