Your Source for HVAC&R Professional Development ASHRAE • 1791 Tullie Circle NE • Atlanta, GA 30329 • www.ashrae.org New Developments in Lower GWP Refrigerants (MENA) ASHRAE Professional Development

Transcript of New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with...

Page 1: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Your Source for HVAC&R Professional Development

ASHRAE • 1791 Tullie Circle NE • Atlanta, GA 30329 • www.ashrae.org

New Developments in Lower GWP Refrigerants (MENA)

ASHRAE Professional Development

Page 2: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

New Developments in Lower GWP Refrigerants (MENA)

Omar Abdelaziz, Ph.D.Clean Energy Air and Water Technologies FZE

Page 3: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Copyright

Copyright 2018 by ASHRAE. All rights reserved. No part of this presentation may be reproduced without written permission from ASHRAE, nor may any part of this presentation be reproduced, stored in a retrieval system or transmitted in any form or by any means (electronic, photocopying, recording, or other) without written permission from ASHRAE.

ASHRAE has compiled this presentation with care, but ASHRAE has not investigated and ASHRAE expressly disclaims any duty to investigate any product, service, process, procedure, design or the like, that may be described herein. The appearance of any technical data or editorial material in this presentation does not constitute endorsement, warranty or guaranty by ASHRAE of any product, service, process, procedure, design or the like. ASHRAE does not warrant that the information in this publication is free of errors. The user assumes the entire risk of the use of the use of any information in this presentation.

2

Page 4: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

AIA/CES Registered Provider

• ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Attendance for non-AIA members are available on request.

• This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Page 5: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

GBCI cannot guarantee that course sessions will be delivered to you as submitted to GBCI. However, any course found to be in violation of the standards of the program, or otherwise contrary to the mission of GBCI, shall be removed. Your course evaluations will help us uphold these standards.

Course ID: 920017564

New Developments in Lower GWP Refrigerants (MENA)

By ASHRAE

Approved for:

1General CE hours

0LEED-specific hours

Page 6: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Learning Objectives

Alternative Lower Global Warming Potential (GWP) Refrigerants are widely sought as sustainable solutions for Heating Ventilation Air Conditioning and Refrigeration (HVAC&R) applications. At the end of this course; participants will be able to

• Understand the transition landscape

• Describe the proposed refrigerants and how they can be used in different HVAC&R applications

• Understand the challenges and opportunities associated with the different types of refrigerants

• Differentiate between different related standards and codes5

Page 7: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Outline/Agenda

• Background Information

• Proposed Alternatives for Different Applications—Theoretical and Empirical Analyses

• Related Standards and Codes of Systems and Substances

• Challenges and Opportunities

• Systems Perspective—Energy Efficiency with New Refrigerants

6

Page 8: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Defining the Refrigerants

• A refrigerant is a substance or mixture of substances, used for either providing cooling (usually air conditioning or refrigeration) or heating (heat pumps), while usually undergoing liquid-to-vapor or vapor-to-liquid phase transition respectively

7

O

H H

H2O or R718

• Refrigerants are all around you• Sometimes referred to “natural” refrigerants• Most refrigerants are engineered to provide the required safety

and efficiency for specific applications at an adequate cost

• One of the most commonly used refrigerants is that used by your body to keep you cool! You drink it everyday

• R718 or water

Page 9: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

History of HVAC&R Refrigerants1st Generation

“Whatever works”

2nd Generation “Safety and

Stability”

3rd Generation “Ozone

Protection”

4th Generation “Global

Warming”

8

1830’s – 1930’s

1930’s – 1990’s

1990’s – 2010’s

2010’s - ?

Limited applications –IndustryPoor Safety and cost

Enabled innovation Preserved 2nd gen.innovations, safety,stability and efficiency

Limited optimal choicesSafety and design challenges

• NH3

• CO2

• Hydrocarbons• H2O• SO2

• Methyl Chloride (R-40)

• NH3• CFCs: R-11, R-12 • HCFCs: R-22, R-502

• NH3

• HCFCs: R-22, R-123• HFCs:

• R-134a• R-410A• R-404A• Other blends

• NH3• Low GWP HFCs, HFOs, and

HCFOs: R-1234yf, R-1234ze(E), R-1233zd(E), R-32, and their blends

• Renewed interest in natural refrigerants: CO2, Hydrocarbons

Page 10: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Regulatory Landscape—Growing Pressure on HFCs

• Global: phase-down of HFCs through the Kigali amendments to the Montreal Protocol

• Japan: Kyoto Protocol—METI/NEDO promoting development and use of fluids with low GWP. Extensive risk assessment study for use of Class 2L flammable refrigerants (5 years).

• EU: F-gas regulations. Regulations on stationary refrigerants starting in 2020, now 2015!

• Australia: Australian Carbon Trading Scheme proposed high carbon tax, starting (including HFCs). Currently under debate.

• U.S.: EPA rulemaking/SNAP9

Page 11: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Phasing Down HFCs

• Based on equivalents CO2 emissions (mass * GWP)• No ban on specific refrigerants• The higher the GWP and the larger mass used, the higher its impact

would be on the collective country quota and thus pressure for phase-down

• Focus of phase-down:• Reduce GWP of refrigerant used• Reduce refrigerant charge size • Reduce leakages• Recover, recycle and reclaim refrigerants

10

$190 in USA$70 in India!

$190 in USA$113 in India!

Page 12: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Kigali Amendment Proposals

• Adopted by the 28th Meeting of Parties to the Montreal Protocol on October 15th 2016 in Kigali, Rwanda. It includes the following :

• Agreement in principle by all 197 member countries to focus on reduction of HFC use to reduce net warming by 0.5°C

• Adds HFCs to the list of substances controlled under the Montreal Protocol.• Phase-down HFCs under the Montreal Protocol as their use is increasing

rapidly as substitutes for ozone-depleting substances.• Four major, separate phase-out timelines; several exceptions.• Obviously some clean-up work and final ratifications are necessary and in

process

11

Page 13: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Kigali’s Impact

• Phase-down, not a phase-out, of HFCs

• Avoids over 80 billion metric tons of carbon dioxide equivalent cumulatively through 2050

• According to UNEP: • HFC phase-down is expected to

avoid up to 0.5 degree Celsius of global temperature rise by 2100

• Continue to protect the ozone layer

12

Sour

ce: h

ttps

://w

ww

.epa

.gov

/site

s/pr

oduc

tion/

files

/201

6-11

/doc

umen

ts/n

ewbe

rg_k

igal

iam

end_

1220

16.p

df

Page 14: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Kigali’s HFC Phase-Down Schedule

13

Source: Kujak, S., “Flammability and New Refrigerant Options”, ASHRAE Journal May 2017

A2 exceptions: Belarus, Russian Federation, Kazakhstan, Tajikistan, Uzbekistan • 25% HCFC component of baseline • 5% reduction in 2020 • 35% reduction in 2025

A5 exceptions (Group 2): GCC, India, Iran, Iraq, Pakistan

Technology review in 2022 and every 5 years

Technology review 4–5 years before 2028 to consider the compliance deferral of 2 years from the freeze of 2028 of A5 Group 2 to address growth

Page 15: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Technology Pull

• A2 countries have already stopped production of HCFCs and are limiting its use

• HFC market is very mature• Alternative refrigerants are already being extensively evaluated

• These development in developing countries would be available to A5 countries via “international pull-through”

• Potential for leapfrogging from HCFC to alternative lower GWP refrigerants

• Additional regulations and rules in developments for A2 countries such as leak reduction, technician training, and refrigerant recovery could be considered by A5 countries

14

Page 16: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Kigali’s Ratifications

15

https://treaties.un.org/pages/ViewDetails.aspx?src=TREATY&mtdsg_no=XXVII-2-f&chapter=27&clang=_en

Australia Ecuador Luxembourg RwandaAustria Estonia Malawi SamoaBarbados European Union Maldives SenegalBelgium Finland Mali SlovakiaBenin France Marshall Islands Sri LankaBulgaria Gabon Mexico Sweden

Burkina Faso Germany Micronesia TogoCanada Greece Netherlands 1 Tonga

Chile Grenada NigerTrinidad and Tobago

Comoros Hungary Niue TuvaluCosta Rica Ireland Norway Uganda

Côte d'Ivoire

Lao People's Democratic Republic Palau

United Kingdom of Great Britain and Northern Ireland

Czech Republic Latvia Panama UruguayDemocratic People's Republic of Korea Lithuania Portugal Vanuatu

Page 17: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

GWP of Common Refrigerants

16

1

10

100

1000

10000

Page 18: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

New Required Properties for Refrigerant Gas

• Boiling point between –40°F and 32°F (–40°C and 0°C)

• Nonflammable?

• Considerably less toxic (nontoxic)

• Chemical stability (inside a refrigeration machine but breaks down to harmless products if released into the atmosphere)

• Nice if pungent odor for leak detection

• Nice if inexpensive (more difficult to achieve)

• Cannot contain chlorine, bromine, or iodine, all of which deplete ozone

• Must have short atmospheric lifetime to minimize GWP

17

Page 19: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

4th Generation Refrigeration

• React with common atmospheric species to shorten life span

• Couple of chemistry approaches• Increase the number of hydrogens• Include oxygen or others• Reduce chemical stability—add bromine or Iodine• Unsaturations (double or triple bonds; i.e. using olefins)

• Best approach• Unsaturation and hydrogen (HFO, HCFO, HCO, HBFO)

• Problem: flammability increases

18

Page 20: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Representative Alternative Low GWP Refrigerant Molecules

19

R-1224yd(Z)- A1 R-1123R-1233zd(E) – A1R-1234ze(E)- A2L R-1234yf –A2L

Page 21: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Olefin Molecules Proposed as Refrigerants

Designation ASHRAE Designation Chemical BP °CHO-1150 R-1150 Ethene –104°CHO-1270 R-1270 Propene –48°CHFO-1234yf R-1234yf 1,1,1,2-tetrafluoropropene –29 .4 °CHFO-1234ze R-1234ze 1,1,1,3-tetrafluoropropene –19 °C

HFO-1336mzz(Z) R-1336mzz(Z) 1,1,1,4,4,4-hexafluoro-2-butane 33.4 °C

HFO-1233zd(E ) R-1233zd(E) t-1-chloro-3,3,3-trifluoropropene 19 °C

HCO-1130(E) R-1130 (E) t-dichloroethene 47.7 °CHFO-1123 Trifluoroethene* Trifluoroethylene –56 °C

HCFO-1224ydChlorotetrafluoro-propene*

1-chloro-2,3,3,3-tetrafluoropropene 16 °C

HFO-1132a Difluoroethene* 1,1-difluoroethylene (vinylidenefluoride) –86.7 °C

20

Page 22: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Refrigerant Selection: A Trade-Off

• Environmental performance (~0 ODP and reduced GWP)

• Safety for consumers (flammability and toxicity)

• Energy efficiency (reduced indirect CO2 emissions, especially at high ambient operations)

• Intellectual property considerations

• Transition costs (industry and consumers)

• Product sustainability

Flammability

Toxicity

Operating Pressure

Stability ODP, GWP

Material Compatibility

Glide

Compatibility Discharge Temperature

Lubricant Selection

Properties

Heat Transfer Capacity

Efficiency

HAT performance

Cost

21

Page 23: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

HFO-1234yf—Low-GWP Option to Replace R-134a

• HFO-1234yf is the first in a growing family of olefin molecules

• Met timing mandated by European MAC Directive to replace R-134a

• Excellent environmental properties• Very low GWP of 1, zero ODP, good LCCP• Atmospheric chemistry determined and published

• Low toxicity: Acute and chronic toxicity superior to R-134a

• System performance very similar to R-134a• Excellent COP and capacity, no glide• Thermally stable and compatible with R-134a components• Potential for direct substitution of R-134a

22

Page 24: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

HFO-1234yf Properties

Property R-134a R-1234yf

Boiling Point –26°C –29°C

Molecular weight

102 114

Formula CF3CH2F CF3CF=CH2

GWP 1300 1

23

0

0.5

1

1.5

2

2.5

3

3.5

-20 0 20 40 60 80 100

Vapo

r Pre

ssur

e, M

Pa

Temperature, °C

R-134a R-134a

Page 25: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

HFO Development Trend as per ASHRAE Standard 34

First HFO Molecule in Standard 34 2008 – HFO-1234yf

First HFO Blend in Standard 34 2012 – Class 2L

First Non Flammable HFO Blend 2013

HFO Status as of Mid 2017 (Includes refrigerants proposed, but not necessarily listed)

• 8 distinct molecules• 37 refrigerant blends (21

flammable, 16 non-flammable)

24

Page 26: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Proposed Alternatives for Different ApplicationsTheoretical and Empirical Analyses

25

Page 27: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

R-22/R-407C Alternatives

Refrigerant GWP100years, AR5 ODP Standard 34 Designation

R-22 1760 0.06 A1

R-407C 1624 0 A1

DR-93 1147 0 A1

N-20b 904 0 A1

R-449B 1296 0 A1

ARM-20b 251 0 A2L

DR-3 146 0 A2L

R-444B 295 0 A2L

26

Page 28: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Relative Performance Compared with Baseline Refrigerant: R-22

27

Page 29: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

R-404A Alternatives

Refrigerant GWP100years, AR5 ODP Standard 34 Designation

R-404A 3943 0 A1

ARM-35 2019 0 A1

R-452A 1945 0 A1

R-448A 1273 0 A1

ARM-20a 139 0 A2L

HDR110 146 0 A2L

ARM-32a 1445 0 A1

DR-33 1293 0 A1

N-40a 1235 0 A128

Page 30: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

R-404A Alternatives

Refrigerant GWP100years, AR5 ODP Standard 34 Designation

N-40b 1222 0 A1

ARM-30a 197 0 A2L

ARM-31a 463 0 A2L

D-2Y65 238 0 A2L

DR-7 244 0 A2L

L-40 285 0 A2L

R-32 677 0 A2L

R-32/R-134a 989 0 A2L

R-290 3 0 A329

Page 31: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Relative Performance Compared with Baseline Refrigerant: R-404A

30

Page 32: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

R-134a AlternativesRefrigerant GWP100years, AR5 ODP Standard 34 Designation

R-134a 1300 0 A1

AC5X 568 0 A1

ARM-41a 860 0 A1

D-4Y 521 0 A1

N-13a,N-13b 547 0 A1

XP-10 573 0 A1

AC5 89 0 A2L

ARM-42a 107 0 A2L

R-1234yf,R-1234ze 1 0 A2L

R-600a, R-290/R-600a 3 0 A331

Page 33: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Relative Performance Compared with Baseline Refrigerant: R-134a

32

Page 34: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

R-410A AlternativesRefrigerant GWP100years, AR5 ODP Standard 34 Designation

R-410A 1924 0 A1

ARM-70a 469 0 A2L

D2Y60 271 0 A2L

DR-5 491 0 A2L

HPR1D 407 0 A2L

L-41a, L-41b 494 0 A2L

R-32 677 0 A2L

R-32/R-134a 708 0 A2L

R-32/R-152a 650 0 A2L

L-41-1, L-41-2 461, 572 0 A2L33

Page 35: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Relative Performance Compared with Baseline Refrigerant: R-410A

34

Page 36: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Market Fragmentation

• R-134a• Refrigerators: HCs and R-1234yf• MAC: R-1234yf• Chillers/refrigeration: R-513A, R-1234ze(E), R-1234yf

• R-404A/R407C• Transport: R-452A and CO2

• Stationary: R-448A, R-449A/B, transcritical CO2, cascaded cycles

• R-410A• Small charge: HCs and R-32• Splits: R-32 and R-452B

35

Page 37: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Related Standards and Codes of Systems and Substances

36

Page 38: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Standards

ASHRAE Industry Consensus Standards

• ASHRAE Standard 34—Safety classification

• ASHRAE Standard 15—Application rules, large equipment

• ASHRAE Standard 15.2—Residential and light commercial AC and HP

General Standards

• ISO 817—Safety classification

• ISO 5149—Application rules

• European Norms (EN) EN378—Design guide for AC, heat pump, and refrigeration equipment, with required safety

37

Page 39: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Standards

ASHRAE Product Standards

• Underwriter’s Laboratories standards for certification of specific equipment uses:

• UL 471—Commercial refrigeration and freezers,

• UL 484—Room air conditioners,• UL 250—Domestic refrigerators,

and• More for other equipment types

Product Standards

• EC and IEC product and equipment standards, which have precedence in many venues:

• EN/IEC 60335-2-89—Commercial refrigeration and freezing,

• EN/IEC 60335-2-40—Electrical AC and heat pumps,

• EN/IEC-60335-2-24—Domestic refrigerators, and

• more for other equipment types38

Page 40: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

ASHRAE Standard 34• A listing of refrigerants that have been

reviewed and evaluated for safety.

• An evergreen document subject to continuous maintenance.

• New refrigerants can be added to this standard after a new refrigerant application is submitted to and reviewed by the Standing Standards Process Committee that oversees this standard—SSPC34.

• As necessary, new refrigerant safety classification rules can be added.

Page 41: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

ASHRAE Standard 34

Safety classification depends on flammability and toxicity

• Toxicity depends on the occupational exposure limit (OEL)

• > 400 ppm is class A• < 400 ppm is class B

• Flammability depends on lower flammability limit (LFL) determination, flame velocity determination, and heat of combustion

• 1: Nonflammable• 2L: Feeble, slow flame, slow low-pressure rise←• 2:Burns faster, low heat of combustion• 3:Burns at explosive speed, high heat of combustion

40

Page 42: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

ASHRAE Standard 15

• Safety classification information developed and published in ASHRAE Standard 34 is, in turn, used in ASHRAE Standard 15

• ASHRAE Standard 15 is an application standard. It gives basic rules for how and where a refrigerant can be used, based on the safety classification developed by ASHRAE Standard 34 for that refrigerant

• Building code agencies, government agencies, architects, and designers use the application guidelines that are developed by ASHRAE Standard 15 41

Page 43: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

ASHRAE Standard 15—Purpose and Scope

• Purpose: Specifies safe design, construction, installation, and operation of refrigeration systems

• Scope: Establishes safeguards for life, limb, health, and property and prescribes safety requirements

• Applies to:• Design, construction, test, installation, operation, and inspection of

mechanical and absorption refrigeration systems, including heat-pump systems used in stationary applications;

• Modifications, including replacement of parts or components if they are not identical in function and capacity; and

• Refrigerant substitutions with a different designation

42

Page 44: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Standards and their Impact on Flammable Refrigerant Charge Limit

Standard Title Application Factors that dictate allowable charge limit

Flammable Ref. Charge Limit

IEC 60335-2-24ANSI/UL 60335-2-24 (6th)

Particular requirements for refrigerating appliances, ice-cream appliances and ice-makers

Domestic refrigeration Up to 150g of flammablerefrigerant per circuit

IEC 60335-2-89ANSI/UL 60335-2-89 (1st)

Particular requirements for commercial refrigerating appliances with an incorporated or remote condensing unit or compressor

Any refrigeration appliances used in commercial situations

Minimum room size, leak detection sensors, fan circulation

Current: Up to 150g of flammable refrigerant per circuitFuture: A2L ~1.2 kg

A3 ~ 0.5 kg

IEC 60335-2-40 (6th) Particular requirements for electrical heat pumps, air conditioners and dehumidifiers

Any air conditioning and heat pump applications

Minimum room size, LFL, lowest release height, maximum releasable charge, leak detection sensors, ventilation

A2L ~ 80 kgA3 ~ 1 kg

ISO 5149 Mechanical refrigeration systems used for cooling and heating - safety requirement

Any refrigeration, air conditioning and heat pumps: domestic, commercial and industrial

Varies by access category and location classification

Current: A2L ~ 39 x LFLA3 ~ 1.5 kg

Future: A2L ~ 60-80 kgA3 ~ 1.5 kg

43

Page 45: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Safety Standards and Building Codes—US Example

ASHRAE 34 - 2016

SNAP Approval

ASHRAE 15 -2019

Model Codes (ICC/IAPMO)

44

Page 46: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

SAFE USE OF REFRIGERANTS

45

Page 47: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Assessing Risks when Using Flammable Refrigerants• Evaluate and quantify the hazards

• Make reasonable assumptions and ask relevant questions• For example: What is the probability of a leak occurring?• If a leak or loss of refrigerant does occur, what is the probability that it might

ignite?• If an ignition occurs, what are the consequences?• What leak scenarios can be imagined and quantified?

46

Page 48: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Flammability—Controlling and Designing for Key Factors

• Fuel air mixture:• Select refrigerant with higher concentration (LFL) to

minimize the chance of having a “combustible cloud”

• Ignition sources• Restrict or enclose• Select refrigerants requiring highest minimum ignition

energy

• Severity of event• Design application to handle pressure rise (venting)• Design refrigerant to minimize potential secondary issues• Select refrigerants with lowest possible burning velocity

47

Fuel air mixture: is it above LFL and less

than UFL?

Severity of Event

Ignition Energy

Page 49: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Considerations for Using Flammable Refrigerants

• Determine if the refrigerant might be used in a space occupied by humans

• Residential? Factory? Business (e.g., supermarket )?

• Is the space used for working or as a living space for ordinary citizens, some of whom may have limited or impaired mobility?

• Limit the amount of refrigerant per machine, based on the risk posed by the particular refrigerant, and/or the size of the room that contains the machine

48

Page 50: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Considerations for Using Flammable Refrigerants

• Depending on the amount of flammable refrigerant being used, there may be requirements for overpressure relief venting to the outside of the building or requirements for direct mechanical venting of escaped gas by use of fans. For larger systems, the requirements may include limiting the equipment that contains hazardous refrigerants to specially designed and access-controlled machine rooms or even machine placement outside of the building altogether.

• These measures are already used for such refrigerants as propane, ammonia, HCFC-123, and hydrocarbons, as used in chiller systems per ASHRAE Standard 15 and ISO 5149. These same safety measures are being reviewed and extended to fit the new Class 2L lower-risk, flammable refrigerants. 49

Page 51: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

How Does One Use a Flammable Refrigerant?

• Apply the rules in relevant standards• ASHRAE Standard 15—primarily for commercial and industrial applications • ASHRAE Standard 15.2P—domestic and light commercial AC equipment in the

United States• This standard is under development

• IEC/UL standards for specific applications• Standards are being updated and harmonized globally • IEC/UL/60335–x-xx

50

Page 52: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Information Available for Users, Designers, and Installers on Low-GWP Refrigerants (See also the references at the end of these charts for links to manufacturer safety information.)

51

Page 53: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Safety Information Available Now:Material Safety Data Sheets• Manufacturers are legally responsible for providing safety information

about products they make and sell (safety data sheets [SDS]/material safety data sheets [MSDS]). These are on manufacturer web sites and searchable.

• Third-party regulatory bodies also provide safety limits and usage guidelines (e.g., UL in the United States).

• Some consideration had already been given to using flammable refrigerant gases (propane, butane, isobutane, etc.), particularly for domestic refrigerators and other small systems; more detailed in European ISO, EN, and EC standards.

52

Page 54: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Refrigerant MSDSand Safe-Handling Instructions

• http://www51.honeywell.com/sm/lgwp-fr/common/documents/FP_LGWP_FR_1234yf-Use-and-Handling-guidelines_Literature_document.pdf

• https://www.chemours.com/Opteon_Stationary/en_GB/assets/downloads/Safety-of-Opteon-XL.pdf

• http://www.achrnews.com/articles/128201-the-professors-lesson-on-hfo-hc-refrigerants?v=preview

• Search online for MSDS for the product(s) of interest

• Search terms: “Refrigerant Safety”, “Refrigerant Handling”, “Product_Name” Safe Handling

53

Page 55: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Rigorous Refrigerant Safety are Required

• Use leak monitors but now not just on large systems.

• Use oxygen monitors in enclosed spaces or low areas like basements.

• Be sure that pressure relief devices and any overpressure vents exhaust to the outside of the building.

• Use active mechanical venting if equipment is indoors.

54

Page 56: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

New Rules Apply for Flammable Refrigerants

• Determine the flammability of the refrigerant being used.

• Do not use flammable refrigerants in equipment not designed for or rated for flammable refrigerants.

• Use vacuum pumps and recovery machines rated for use with flammable refrigerants, with non-sparking switches and non-sparking motors.

• Be aware of charge size limitations, as prescribed by safety codes and regulations.

55

Page 57: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Be Aware of Common Hazards

• Do not smoke or allow others to smoke if flammable refrigerants are being used, transferred, charged, or recovered.

• Be alert for any potential ignition source—heaters, sparking motors or switches, static electricity, etc.

• When brazing, or welding, be sure all refrigerant has first been evacuated from the system.

• Not a new concern but much more important with flammable refrigerants

56

Page 58: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Challenges and Opportunities

57

Page 59: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Global Cooling Demand

0

2

4

6

8

10

12

14

16

18

2010 2020 2030 2040 2050

Glo

bal B

uild

ing

Cool

ing

Cons

umpt

ion,

EJ

6DS 4DS 2DS

0

2

4

6

8

10

12

1990 est 2013 BAU 2050 2DS 2050

Glo

bal B

uild

ing

Cool

ing

Cons

umpt

ion,

EJ

OECD Countries OECD Non-Members

http://www.iea.org/Textbase/nppdf/stud/16/ETP2016.pdf

Page 60: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Green House Gas Emissions• Stationary A/C account for ~700 MMTCO2e annually

• 74% Indirect emissions from electricity generation • Direct emissions: 7% HFC and 19% HCFC

Page 61: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Cost Implications of New Refrigerants

• Global cost-effectiveness is key to the transition to sustainable A/C

• Since the 1970s, U.S. manufacturers have steadily reduced the inflation-adjusted cost of residential central-ducted A/C systems while maintaining or improving performance, even while transitioning away from ODS to today’s HFC refrigerants

• Performance improvements and charge minimization efforts supporting transition towards low-GWP can offset upfront cost increased through life-cycle energy savings

Page 62: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

HAT Performance—Experimental Assessment

61

Page 63: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Split Units: 5.28 kW Capacity• Unit designed for high ambient performance up to 55°C

• Rated Capacity at ISO T1 (~AHRI A) = 5.28 kW (18 kBtu)

• COP: R-22 unit = 2.78 (EER ~ 9.5); R-410A unit =

R-22 unit

• COP = 2.78 (EER ~ 9.5)

R-410A unit

• COP = 3.37 (EER ~ 11.5)

Page 64: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Performance Relative to Baseline at 55°C

L-20a (R-444B)

DR-3

N-20b

ARM-…

R-290/POE

DR-93

80%

85%

90%

95%

100%

105%

110%

80% 85% 90% 95% 100% 105%

COP

Cooling Capacity

R-22 w/ mineral

oil

R-32

DR-55

L-41 (R-447A)

ARM-71a

HPR-…

90%

95%

100%

105%

110%

80% 90% 100% 110%CO

PCooling Capacity

R-410A

R-22 Baseline R-410A Baseline

Page 65: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Packaged AC Units

• R-22 Unit (SKM PACL-51095Y)• 380/415V, 3 Ph, 50 Hz• Capacity*(T1) = 92.8 kBtu/h (27.2 kW) • EER = N/A

• R-410A Unit (Petra PPH4 115)• 460V, 3 Ph, 60 Hz• Capacity*(T1) = 132 kBtu/h (~ 38.68 kW)• EER* = 10.66 (COP ~ 3.12)

Page 66: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Performance Relative to Baseline at 52°C

R-22 Baseline R-410A Baseline

Page 67: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Low-GWP AREP Phase II HAT MatrixUnit No. Equipment Type

Baseline Refrigerant Refrigerants Tested Test type Test Standard

AREP Report No.

1 3-ton air source, split R-410A R-32 soft-opt. AHRI Standard 210/240 42

2 3-ton air source, split R-410A ARM-71a, DR-5A, HPR2A, L-41-1, L-41-2 drop-in AHRI Standard 210/240 52

3 3-ton air source, split R-410A R-32, DR-5A, L-41-2 drop-in AHRI Standard 210/240 54

4 5-ton air source, RTU R-410AR-32, ARM-71a, DR-5A, DR-55, HPR2A, L-41-2 drop-in AHRI Standard 210/240

47 & 53

5 6-ton air source, RTU R-410A R-32 soft-opt. AHRI Standard 340/360 55

6 4-ton air source, RTU R-410A R-32, DR-5A, DR-55 soft-opt. AHRI Standard 210/240 56

7 2.5-ton air source, RTU R-22, R410A R-32 soft-opt. AHRI Standard 210/240 57

8 1.5-ton air source, mini-split R-410A R-32, ARM-71a, DR-55, HPR2A, L-41-2 soft-opt. AHRI Standard 210/240 62

9 1.5-ton air source, mini-split R-22N-20b, DR-3, ARM-20b, L-20a, DR-93, R-290 soft-opt. AHRI Standard 210/240 62

10 2-ton air-to-water chiller R-410A R-32, DR-5A, L-41-1, L-41-2 drop-in Tester defined conditions 46

11 split system commercial ice machine R404A ARM-20b, N-40c drop-in AHRI Standard 810 and 29 45

66Source: Karim Amrane and Xudong Wang, “Low-GWP Alternative Refrigerants Evaluation Program Phase II -Testing Results at High-Ambient Temperature Conditions”, International Roundtable Meeting on Risk Assessment Model for the use of low-GWP Refrigerants in High Ambient Temperature Countries, October 3-4, 2017, Kuwait

Page 68: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

AC at High Ambient Conditions

67

Page 69: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Summary

• Large global pull towards sustainable refrigerant use by governments, industry, and end users

• Several new molecules in new risk classes have been developed or proposed and are being evaluated

• Some “old refrigerants” (hydrocarbons, CO2, ammonia) are also being considered or reconsidered for various applications but with new regulations for their use on a wider basis

• The risk and hazard evaluations of using flammable refrigerants in applications where they have not been used before or using 2L refrigerants is still a work in progress. Liability and public safety concerns are powerful forces that must be settled.

68

Page 70: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Summary (continued)

• Using small charge amounts (150 gm) is one strategy to enable use of flammable refrigerants, such charges are used in domestic refrigerators

• Limited amounts of Class 2L (300 gm to 500 gm) refrigerants are being used in small room AC units in Asia

• Around the world, safety standards for the use of flammable refrigerants are still being finalized. This is work in progress

• ASHRAE Standard 15, ASHRAE Standard 15.2 for domestic AC• EN378, IEC 60335-2-NN, ISO 817, and ISO 5149 internationally• Building codes in the United States and internationally must be updated, and this is

expected to occur 2020 to 2023

69

Page 71: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Setting the Stage for New Refrigerants

• Non-flammable alternatives limits for different baselines• R-123: <10 GWP available• R-134a: 400 to 600 GWP• R-404A: 1200–1400 GWP

• R-410A: all 2L class

• Need to work with flammability as a new design variable

• Harness additional opportunities from zeotropic mixtures

• Don’t fear product fragmentation by refrigerants—we are at the age of customized industry (3-D printing)

70

Page 72: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

71

Although every effort has been made to ensure that the information in this report is correct, neither the author nor ASHRAE assumes, and hereby disclaim any liability to users of this information for any loss, damage, or injury caused by errors or omissions, whether such errors or omissions result from negligence, accident, changing regulations, or any other cause.

Page 73: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Questions?Omar Abdelaziz, Ph.D.

Managing Director, Clean Energy Air and Water Technologies FZE

[email protected]

72

Page 74: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Evaluation and Certificate

You will receive your Certificate of Attendance and course materials

from the HVAC R Expo organizers.

If you have any questions about ASHRAE or ASHRAE courses, please

contact Ayah Said at [email protected].

73

Page 75: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Explore ASHRAE Learning InstituteCourses

https://www.ashrae.org/instructor-led-courses

Find a Topic that Fits YouCommissioningEnergy EfficiencyEnvironmental QualityHVAC&R Applications Standards and Guidelines

See all the ways to learn and grow with ASHRAE at https://www.ashrae.org/professional-development/learning-portal

Page 76: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

ASHRAE CertificationOver 2750 certifications earned to date.

Validation. Recognition. Pride. Advance Your Career Today

Visit www.ashrae.org/certification to learn more about these seven programs:

Building Commissioning Professional (BCxP) Building Energy Assessment Professional (BEAP) Building Energy Modeling Professional (BEMP) High-Performance Building Design Professional (HBDP) Healthcare Facility Design Professional (HFDP) Certified HVAC Designer (CHD) Operations and Performance Management Professional (OPMP)

Page 77: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

Background Information

76

The presentation has ended. The following charts are for your information going forward. References and links to internet-based information are provided to enable the user to find updated information going forward as the regulatory environment solidifies.

Page 78: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• ACHR News. The Professor’s Lesson on HFO, HC Refrigerants: Next-Gen Fluids Each Offer Unique Traits, Characteristics.

http://www.achrnews.com/articles/128201-the-professors-lesson-on-hfo-hc-refrigerants?v=preview.

• ASHRAE. 2007. ASHRAE Standard 97-2007, Sealed glass tube method to test the chemical stability for materials for use within refrigeration systems. Atlanta: ASHRAE.

• ASHRAE. 2016. ANSI/ASHRAE Standard 15-2016, Safety standard for refrigeration systems. Atlanta: ASHRAE.

• ASHRAE. 2016. ANSI/ASHRAE Standard 34-2016, Designation and classification of refrigerants. Atlanta: ASHRAE.

• ASTM. 2009. ASTM E681-09, Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors and Gases ). ASTM International: West Conshohocken, PA.

• EU. 2014. EU F-Gas Regulation, Regulation (EU) No 517/2014 of the European Parliament and of the council 16 April 2014 on fluorinated greenhouse gases and repealing regulation (EC) No 842/2006. European Union: Brussels, Belgium.

77

Page 79: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• EPA. Refrigeration and air conditioning. https://www.epa.gov/snap/refrigeration-and-air-conditioning.

• EPA. 2015. Protection of stratospheric ozone : Change of listing status for certain substitutes under the Significant New Alternatives Policy Program: Final Rule. Federal Register 80(138):42870–959. Washington, DC: U.S. Environmental Protection Agency.

• EPA. 2016. Protection of stratospheric ozone : New listings of substitutes: Changes of listing status and reinterpretation of unacceptability for closed cell foam products under Significant New Alternatives Policy Program; and revision of Clean Air Act Section 608 Venting Prohibition for Propane: Final Rule. Federal Register 81(231):86778–895. Washington, DC: U.S. Environmental Protection Agency.

• EPA. 2016. Protection of stratospheric ozone: Update to the refrigerant management requirements under the Clean Air Act: Final Rule. Federal Register 81(223):82272–395. Washington, DC: U.S. Environmental Protection Agency.

• UN. 2016. Amendment to the Montreal Protocol on Substances that Deplete the Ozone Layer. Decisions XXVIII/1 and XXVIII/2. New York: United Nations.

78

Page 80: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• IPCC. 2007. B.P. Jallow, L. Kajfez-Bogataj, R. Bojaru, D. Hawkins, S. Diaz, H. Lee, A. Allali, I. Elgizouli, D. Wratt, O.

Hohmeyer, D. Griggs, and N. Leary (eds.). Intergovernmental Panel on Climate Change Fourth Assessment Report—Climate Change 2007: Synthesis Report. https://www.ipcc.ch/publications_and_data/publications_ipcc_fourth_assessment_report_synthesis_report.htm.

• IPCC. 2013. G. Myhre, D. Shindell, F. M. Bréon, W. Collins, J. Fuglestvedt, J. Huang, D. Koch, J. F. Lamarque, D. Lee, B. Mendoza, T. Nakajima, A. Robock, G. Stephens, T. Takemura, and H. Zhang; Anthropogenic and Natural Radiative Forcing. In: Climate Change 2013: The Physical Science Basis Contribution of Working Group I to the Fifth Assessment Report of the Intergovernmental Panel on Climate Change, Cambridge University Press, Cambridge, United Kingdom and New York, NY, U.S.

• Hughes, J., and T. Leck. 2015. Novel reduced GWP refrigerant compositions for stationary air conditioning. Proceedings of the 24th IIR International Congress of Refrigeration, Yokohama, Japan, August 16–22.

• EPA. 2016. Fact Sheet; Final Rule 20 – Protection of Stratospheric Ozone: Change of Listing Status for Certain Substances under the Significant New Alternatives Policy Program, Revised December 11, 2016. Washington, DC: U.S. Environmental Protection Agency.

79

Page 81: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• Chemours. 2016. Safety of Chemours OPTEON™XL Refrigerants. Safe Use and Handling Guidelines.

https://www.chemours.com/Opteon_Stationary/en_GB/assets/downloads/Safety-of-Opteon-XL.pdf.

• Honeywell. 2014. Guidelines for Use and Handling of Solstice® yf. https://www.honeywell-refrigerants.com/americas/?document=solstice-yf-refrigerant-use-handling-guidelines&download=1.

• Honeywell. nd. Guidelines for Use and Handling of HFO-1234yf. http://www51.honeywell.com/sm/lgwp-fr/common/documents/FP_LGWP_FR_1234yf-Use-and-Handling-guidelines_Literature_document.pdf.

• Danfoss. 2017. Why ammonia in industrial refrigeration. http://industrialrefrigeration.danfoss.com/refrigerants/ammonia/why-ammonia /#/.

• Emerson. 2015. “CO2 as a refrigerant—Five potential hazards of R744. https://emersonclimateconversations.com/2015/07/02/co2-as-a-refrigerant-five-potential-hazards-of-r744/.

• GIZ/Proklima International. 2012. Guidelines for safe use of hydrocarbon refrigerants.https://www.giz.de/expertise/downloads/giz2010-en-guidelines-safe-use-of-hydrocarbon.pdf.

80

Page 82: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• Chemours. 2016. Safety of Chemours OPTEON™XL Refrigerants. Safe Use and Handling Guidelines.

https://www.chemours.com/Opteon_Stationary/en_GB/assets/downloads/Safety-of-Opteon-XL.pdf.

• Honeywell. 2014. Guidelines for Use and Handling of Solstice® yf. https://www.honeywell-refrigerants.com/americas/?document=solstice-yf-refrigerant-use-handling-guidelines&download=1.

• Honeywell. nd. Guidelines for Use and Handling of HFO-1234yf. http://www51.honeywell.com/sm/lgwp-fr/common/documents/FP_LGWP_FR_1234yf-Use-and-Handling-guidelines_Literature_document.pdf.

• Danfoss. 2017. Why ammonia in industrial refrigeration. http://industrialrefrigeration.danfoss.com/refrigerants/ammonia/why-ammonia /#/.

• Emerson. 2015. “CO2 as a refrigerant—Five potential hazards of R744. https://emersonclimateconversations.com/2015/07/02/co2-as-a-refrigerant-five-potential-hazards-of-r744/.

81

Page 83: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• Abdelaziz, O.A, Shrestha, S, Munk, J., Linkous, R., Goetzler, W, Guernsey, M., Kassuga, T., 2015, Alternative Refrigerant

Evaluation for High-Ambient-Temperature Environments: R-22 and R-410A Alternatives for Mini-Split Air Conditioners, ORNL/TM-2015/536, available online at: http://info.ornl.gov/sites/publications/Files/Pub59157.pdf.

• Abdelaziz, O.A, Shrestha, S, Shen, B., Elatar, A., Linkous, R., Goetzler, W, Guernsey, M., Bargash, Y., 2016, Alternative Refrigerant Evaluation for High-Ambient-Temperature Environments: R-22 and R-410A Alternatives for Rooftop Air Conditioners, ORNL/TM-2016/513, available online at: http://info.ornl.gov/sites/publications/Files/Pub69980.pdf.

• AHRI 2008. ANSI/AHRI Standard 210/240 Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment

• AHRI 2015. ANSI/AHRI Standard 340/360 Performance Rating of Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment

• Goetzler, W, Guernsey, M., Young, J., Fuhrman, J, Abdelaziz, O., 2016, The Future of Air Conditioning for Buildings,

82

Page 84: New Developments in Lower GWP Refrigerants (MENA) cover · • ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned

References• IPCC, 2013. Myhre, G., D. Shindell, F.-M. Bréon, W. Collins, J. Fuglestvedt, J. Huang, D. Koch, J.-F. Lamarque, D. Lee, B.

Mendoza, T. Nakajima, A. Robock, G. Stephens, T. Takemura and H. Zhang, 2013: Anthropogenic and Natural Radiative Forcing. In: Climate Change 2013: The Physical Science Basis. Contribution of Working Group I to the Fifth Assessment Report of the Intergovernmental Panel on Climate Change [Stocker, T.F., D. Qin, G.-K. Plattner, M. Tignor, S.K. Allen, J. Boschung, A. Nauels, Y. Xia, V. Bex, and P.M. Midgley (eds.)]. Cambridge University Press, Cambridge, United Kingdom and New York, NY, USA. Available: https://www.ipcc.ch/pdf/assessment-report/ar5/wg1/WG1AR5_Chapter08_FINAL.pdf.

• ISO 5151:2010, Non-ducted air conditioners and heat pumps—Testing and rating for performance, http://www.iso.org/iso/home/store/catalogue_tc/catalogue_detail.htm?csnumber=54063.

• Mark O. McLinden, J. Steven Brown, Riccardo Brignoli, Andrei F. Kazakov & Piotr A. Domanski, “Limited options for low-global-warming-potential refrigerants”, Nature Communications 8, Article number: 14476 (2017),doi:10.1038/ncomms14476

83