New age adsorption cooling & recuperative power Enwave ...

16
Brandon Oyer, P.E. New age adsorption cooling & recuperative power Enwave District Energy – Pacific Northwest National Laboratory June 2016

Transcript of New age adsorption cooling & recuperative power Enwave ...

Page 1: New age adsorption cooling & recuperative power Enwave ...

Brandon Oyer, P.E.

New age adsorption cooling & recuperative power Enwave District Energy – Pacific Northwest National Laboratory June 2016

Page 2: New age adsorption cooling & recuperative power Enwave ...

Objectives

Basic adsorption chilling process overview

Discuss the materials science advances that have lead to this change in this technology

Describe metal organic framework (MOF)

Identify the differences in MOF and silica

Describe the benefits of MOF

Show the effect of technology change on a district energy system

Calculate the potential CO2e reductions from electric chillers

Next steps

Page 3: New age adsorption cooling & recuperative power Enwave ...

Uses waste or solar

heat to drive a thermal

vapor-liquid cycle

Machines are big and heavy

5000 lbs silica gel

300,000 fins

33,000 lbs total weight

≈4.5 miles of copper tubing

Low COP ≈0.5

Adsorption Chiller Technology: The Basics

Technical Challenges

Few moving parts Technical Solutions

Replace silica gel

with high

performance MOF

sorbents

Enable operation

with more

refrigerants

But - new

architecture for

adsorption modules

required

44⁰F

53⁰F

85⁰F

100⁰F

194⁰F

182⁰F

Adsorption

Chamber 1

Adsorption

Chamber 2

Evaporator

Chamber Cold Water

Cool Water Hot

Water

“Flapper valves”

Condenser Chamber

Silica gel Silica gel MOF MOF

Page 4: New age adsorption cooling & recuperative power Enwave ...

New Materials Offer New Opportunities

Metal Organic Framework (MOF) materials are a new type of hybrid organic-inorganic porous crystalline solid

The properties of MOFs are easier to tune synthetically than those of analogous materials (zeolites)

MOF structures are controllable by the choice of molecular building blocks

Thermally stable up to 300C and sometimes higher

Highest surface area material known to date (>8,000 m2/g)

Can we exploit these properties for heat transfer applications? Yes!

Page 5: New age adsorption cooling & recuperative power Enwave ...

Superhydrophilic MOF for Water Refrigerant Chiller

P/Po

0.0 0.1 0.2 0.3 0.4 0.5

Mass%

0

10

20

30

40

50

25°C

40°C

50°C

70°C

90°C

SG 25°C

SG 90°C

HMOF-3

Ad

so

rptio

n

De

so

rptio

n

8 wt% Lift

16 w

t% L

ift

Outperforms silica gel by 2 to 3X depending upon deployment

environment. Enables air-cooled chiller operation under high

ambient temperatures where silica gel chiller output goes to zero.

Page 6: New age adsorption cooling & recuperative power Enwave ...

Crystal density = 0.77 g/cm3 Crystal density = 0.84 g/cm3

• Ultra-high sorption capacities enable brand new chiller design

running with standard refrigerants (i.e. R134a)

• Sraightforward extension to refrigeration and freezing applications

difficult or impossible to do with water-based systems

Superfluorophilic Sorbents

Page 7: New age adsorption cooling & recuperative power Enwave ...

Re-inventing the Adsorption Chiller

Using these new materials gives

dramatic bed size reductions that result

in heat transfer limitations with standard

tube-fin heat exchanger designs

New HX architectures are also needed to take maximum advantage of MOF sorbent properties

Maximize heat exchange area per unit volume of sorbent

Enable operation at higher regeneration temperature

More efficient heat recuperation between adsorption beds

Obtain COP>1 for first time in solid state cooling device

Unified design for both water and fluorocarbon chillers

MOF HX

channel

Refrigerant

HX

Fluid

SCP (kW/kg)

0.0 0.1 0.2 0.3 0.4 0.5 0.6

CO

P

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Standard Module

Integrated MCA

Integrated MCA10X Heat Transfer

Integrated MCA10X Heat Transfer2X Thermal Mass

Page 8: New age adsorption cooling & recuperative power Enwave ...

Re-Inventing the Adsorption Chiller

• No rotating parts – valve actuators do the bed switching

• Integral heat recuperation coupled with microchannel

architecture boosts COP

Page 9: New age adsorption cooling & recuperative power Enwave ...

Demonstration Systems

¾ RT Capacity Unit for U.S. Navy Water refrigerant system provides

opportunity to cut fuel use at forward

operations bases by 30 to 40%

PNNL 2 kW Demonstration System Runs on R134a and designed for transport

to conferences, trade shows, etc.

Page 10: New age adsorption cooling & recuperative power Enwave ...

Hybrid Adsorption Vapor Compression (HAVAC) System for Buildings

Drop-in retrofit for mechanical vapor compression system used today

Adaptable to heat source characteristics including natural gas, low-cost solar, and low grade steam

Reduces peak electrical demand

Compatible with future low GWP refrigerant replacements

Page 11: New age adsorption cooling & recuperative power Enwave ...

Integration into district energy

Allows the opportunity to more efficiently leverage waste heat for cooling

Due to the immense surface area of the sorbent, combined with the advanced heat exchange technology, the size and weight of these machines will be closer to that of electric driven chillers

Can leverage existing steam and hot water systems, to turn district heating systems into district cooling. Avoiding redundant distribution piping systems.

Increasing the energy throughput of an existing system, without adding distribution piping will increase the overall efficiency and lower is carbon intensity

Reduces peak electrical demand and diversifies the fuel portfolio of an existing system

Page 12: New age adsorption cooling & recuperative power Enwave ...

Energy cost and carbon???

Assumptions:

Base case electric chiller plant operating at .6kW/ton

Cost of electricity $.08/kWh, eGrid CO2e intensity (national average) 1,238 lbm/MWh

Unitized cost of energy $5.50/MMBTU and 117 lbm CO2e /MMBTU

Dual acting system COP 2

Results in a: 64% reduction in cooling energy costs

Most conservative approach would be 6% reduction in CO2 if fired from natural gas, but the ability to utilize into existing district systems with renewable components will dive this number down.

Page 13: New age adsorption cooling & recuperative power Enwave ...

Integration into existing system

0

50

100

150

200

250

300

350

1/1 2/1 3/1 4/1 5/1 6/1 7/1 8/1 9/1 10/1 11/1 12/1

PP

H (

1,0

00

)

Date

Opportunity to

increase energy

throughput =>

increase system

efficiency

Page 14: New age adsorption cooling & recuperative power Enwave ...

Next Steps

Enwave Seattle has applied for a research and development grant, through the Washington State Department of commerce.

Grant is intended to bridge the initial capital gap for scaling up unit

Determine commercial market and capital costs to implement

Page 15: New age adsorption cooling & recuperative power Enwave ...

Conclusion

Materials science has advanced, resulting in an efficient adsorption chiller that has historically been inefficient (both in space and energy usage)

Even with fossil fuel carbon intensity, there is a reduction in CO2e emissions

Utilizing renewable thermal energy or waste heat recovery will drive CO2e emissions lower than possible with electric chiller

Cooling energy costs should easily be reduced

More work left to determine the scalability and capital cost

Page 16: New age adsorption cooling & recuperative power Enwave ...

Thank you!

Brandon Oyer

Enwave Seattle

(206) 658-2027

[email protected]

Pete McGrail

Pacific Northwest National Laboratory

(509) 371-7077

[email protected]