NETWORK FIRE ALARM CONTROL PANEL FX-2003-12NDS Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. Description Mircom’s FleX-Net TM FX-2003-12NDS Network Fire Alarm Control Panel offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the FX-2003-12NDS allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability. The FX-2003-12NDS is based on the proven and reliable FX-2000 Series platform. Each base panel consists of one intelligent signaling line circuit (SLC) capable of supporting 99 analog sensors and 99 addressable modules. In addition the base panel includes Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a large 4 x 20 back-lit alphanumeric LCD display. The network configuration allows the FX-2003-12NDS control panel to be connected to a Mircom network to provide additional input circuits, visual zones, programmable notification appliance circuits, and relays. Each panel can be configured using standard FX-2000 components. The network interface module allows the panels to communicate on a peer-to-peer network via a Proprietary Arcnet Network Communications protocol. The network capabilities allow site specific customization and the ability to meet local and national requirements. Features Fire Alarm Control One expandable to nine Intelligent Signaling Line Circuits (SLC) Modular design Each SLC Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Style 6 or 7 (Class A) or Style 4 (Class B) Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each Large 4 by 20 character Back-lit LCD Display with user friendly menu Supported languages: English, French, Arabic* and Hebrew* (*960 character back-lit LCD display only) Correlatable Switch Inputs which allow for multi- functional outputs Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble Group bypass with built-in false alarm prevention technology RS-232 output for remote system printer or CRT Two Event History Logs comprised of a 6000 event alarm history log for alarm related events and a 6000 event log for all events Supports three configuration files (current, previous and next configuration) with “hot swap” support Supports Conventional Hardwire Adder Modules Built-in One Man Walk Test operation Configurable for Canadian Two Stage operation Provision for two programmable modules Configurable for Coded Operation Capability to adjust Intelligent Smoke Detector sensitivity levels Real time 3D graphical monitoring and control using Mircom’s Open Graphic Navigator™ BACnet support Supports Boolean logic functions Built-in Ethernet port Remote diagnostics via a built-in web server UL listed for Smoke Control Network Features Up to 63 nodes Peer-to-peer network communications Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration Proprietary Arcnet Network Communications protocol Supports copper and/or fiber optic network cable 5941 NOT TO BE USED FOR INSTALLATION PURPOSES. S7010 S7010 7165-1477:111 CATALOG NUMBER NYC Fire Dept. COA# 6064 APPROVED

Transcript of NETWORK FIRE ALARM CONTROL PANEL FX-2003-12NDS

NETWORK FIRE ALARM CONTROL PANEL FX-2003-12NDS
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Description Mircom’s FleX-NetTM FX-2003-12NDS Network Fire Alarm Control Panel offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the FX-2003-12NDS allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability. The FX-2003-12NDS is based on the proven and reliable FX-2000 Series platform. Each base panel consists of one intelligent signaling line circuit (SLC) capable of supporting 99 analog sensors and 99 addressable modules. In addition the base panel includes Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each and a large 4 x 20 back-lit alphanumeric LCD display. The network configuration allows the FX-2003-12NDS control panel to be connected to a Mircom network to provide additional input circuits, visual zones, programmable notification appliance circuits, and relays. Each panel can be configured using standard FX-2000 components. The network interface module allows the panels to communicate on a peer-to-peer network via a Proprietary Arcnet Network Communications protocol. The network capabilities allow site specific customization and the ability to meet local and national requirements.
Features Fire Alarm Control • One expandable to nine Intelligent Signaling Line Circuits
(SLC) • Modular design • Each SLC Loop is capable of supporting 99 Analog Sensors
and 99 Addressable Modules which can be wired in Style 6 or 7 (Class A) or Style 4 (Class B)
• Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each
• Large 4 by 20 character Back-lit LCD Display with user friendly menu
• Supported languages: English, French, Arabic* and Hebrew* (*960 character back-lit LCD display only)
• Correlatable Switch Inputs which allow for multi- functional outputs
• Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor
• Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
• Group bypass with built-in false alarm prevention technology • RS-232 output for remote system printer or CRT • Two Event History Logs comprised of a 6000 event alarm
history log for alarm related events and a 6000 event log for all events
• Supports three configuration files (current, previous and next configuration) with “hot swap” support
• Supports Conventional Hardwire Adder Modules • Built-in One Man Walk Test operation • Configurable for Canadian Two Stage operation • Provision for two programmable modules • Configurable for Coded Operation • Capability to adjust Intelligent Smoke Detector sensitivity
levels • Real time 3D graphical monitoring and control using Mircom’s
Open Graphic Navigator™ • BACnet support • Supports Boolean logic functions • Built-in Ethernet port • Remote diagnostics via a built-in web server • UL listed for Smoke Control Network Features • Up to 63 nodes • Peer-to-peer network communications • Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration • Proprietary Arcnet Network Communications protocol • Supports copper and/or fiber optic network cable
5941 NOT TO BE USED FOR INSTALLATION PURPOSES.
S7010 S7010 7165-1477:111
NYC Fire Dept. COA# 6064 APPROVED
FX-2003-12NDS Compact Network Main Control Unit The FX-2003-12NDS Compact Network Main Control Unit complete with one Intelligent Signaling Line Circuit (Style 4, 6 or 7), Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each, a 4 line by 20 character back-lit LCD display and a 12 Amp Power Supply. The FX- 2003-12NDS provides space for the FNC-2000 Network Controller Module, two internal adder modules and two programmable modules.
FleX-NetTM FX-2003-12NDS Network Series Fire Alarm Control Panels
NOT TO BE USED FOR INSTALLATION PURPOSES. CAT. 5941 page 2 of 6
FNC-2000 Fire Network Controller Module The FNC-2000 provides network capability to the FX- 2003-12NDS panels. One Fire Network Controller Module is required per network node panel. In addition the FNC-2000 provides an interface for adding an optional FOM-2000-SP Fiber Optic Network Adder Module. The FNC-2000 mounts in the FX-2003-12NDS.
FOM-2000-SP Fiber Optic Network Adder Module The FOM-2000-SP Fiber Optic Network Adder Module allows for the use of fiber optic cabling on the FX-2000N Series panels. It seamlessly connects to the interface on the FNC-2000 Fire Alarm Network Controller Module.
Fire Network Controller Modules Adder Loop Controller Modules
DOX-1024DS(R) Door The DOX-1024DS mounts on the UB-1024DS backbox. The door features the universal CAT-30 lock and is available in a white (DOX-1024DS) or red exterior (DOX- 1024DSR).
ALCN-792M Quad Loop Controller Module The ALCN-792M Quad Loop Controller Module provides two Signaling Line Circuits (SLC) to the FleX- NetTM system consisting of 99 Analog Sensors and 99 Addressable Modules per loop. The ALCN-792M can be expanded with the use of the ALCN-792D Daughter Board Module. The ALCN-792M occupies one module slot.
ALCN-792D Daughter board for Quad Loop Controller Module The ALCN-792D Daughter Board provides an additional two SLC when connected to the ALCN-792M Quad Loop Controller Module. The daughter board mounts on top of the ALCN-792M.
UB-1024DS Universal Backbox The UB-1024DS Universal backbox houses the FX- 2003-12NDS and provides space to mount up to 17 AH batteries. A DOX-1024DS(R) door is ordered separately. Dimensions (minus built-in trim ring): 26”H x 14.5”W x 4.2”D
UB-1024DS DOX-1024DSR
Primary Input Power 120V 60Hz / 240V, 50Hz 4 Amps / 2 Amp (primary)
Power Supply Ratings 12 Amps. max. (secondary) For NAC Circuits 24VDC unfiltered, 10 Amps. max. Battery Type 24VDC, Gel-Cell/Sealed Lead-Acid Battery Charging Capability 17-65 AH batteries
Electrical Specifications
Adder Hardwire Modules
DM-1008A Eight Initiating Circuit Module The DM-1008A provides 8 Style B (Class B) or 4 Style D (Class A) Initiating Circuits configurable for Alarm, Supervisory or Trouble zones. The DM-1008A occupies one module slot in the FX-2003-12NDS.
RM-1008A Eight Relay Circuit Module The RM-1008A provides the FX-2003-12NDS with eight individual configurable relays per module. Each relay provides one Form C contact rated at 28 VDC @1 Amp (resistive load) as well as a Green LED to indicate that the relay is active. The RM-1008A occupies one module slot in the FX-2003-12NDS.
SGM-1004A Four Notification Appliance Circuit Module The SGM-1004A provides 4 Style Z/Y(Class A/B) Notification Appliance Circuits configurable as Silenceable or Non-Silenceable. Each NAC circuit is rated at 1.7 Amps. The SGM-1004A occupies one module slot in the FX-2003-12NDS.
CAT. 5941 page 3 of 6
Adder Auxiliary Modules
PR-300 Polarity Reversal/City Tie Module The PR-300 Polarity Reversal/City Tie Module provides the system with a supervised City Tie (24 VDC/200 mA max.) and Polarity Reversal connection (24 VDC (open circuit), 8 mA max. (shorted)). The PR-300 occupies one module slot in the FX-2003-12NDS.
UDACT-300A Digital Alarm Communicator Module The UDACT-300A Digital Alarm Communicator Module allows the FX-2003-12NDS to transmit addressable point information to a central station. The UDACT-300A occupies one module slot in the FX-2003-12NDS.
IPS-2424DS Programmable Input Switches Module The IPS-2424DS provides 24 programmable switches that can be configured for ancillary functions such as zone bypass or added common control functions. The IPS-2424DS connects to the main panel or the RAXN- LCD when mounted remotely. The IPS-2424DS occupies one display position in the FX-2003-12NDS, BB-1000 or BB-5000 Series enclosures.
FDX-008 Fan Damper Control Module The FDX-008 Fan Damper Control Module provides individually programmed circuits which can be used for fan or damper control. The FDX-008 connects to the main panel or the RAXN-LCD and occupies one display position in the FX-2003-12NDS, BB-1000 or BB-5000 Series enclosures.
Programmable Modules
Graphics Software
Open Graphic Navigator (OpenGN) Mircom’s Open Graphic Navigator (OpenGN) software is an advanced fire alarm management and warning system that provides building ready monitoring, control and software management solutions that allows a user to monitor remote sites from multiple operator workstations located anywhere in the world. The OpenGN software is available in two versions: Network (OPENGN-ENT) and Non-Network (OPENGN-MINI).
RAX-1048TZDS Programmable LED Annunciator Module The RAX-1048TZDS Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDS connects to the main panel or either the RAXN-LCD or RAM-1032TZDS when mounted remotely. The RAX-1048TZDS occupies one display position in the FX-2003-12NDS,BB-1000 or BB-5000 Series enclosures.
RAXN-LCD Remote LCD Annunciator The RAXN-LCD Remote LCD Annunciator is equipped with a 4 line x 20 character back-lit LCD display that provides the same functions as the main display on the fire alarm control panel. The RAXN-LCD occupies one display position in the BB-1000 or BB-5000 Series enclosures.
Remote LCD Annunciators
Graphic Annunciator Driver Modules
AGD-048 Adder Graphic Driver Module The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 to support an additional 48 supervised outputs. The AGD-048 mounts in a graphic annunciator wallbox or in the BB-5000 enclosures.
MGD-32 Master Graphic Driver Module The MGD-32 Master Graphic Driver Module provides common control inputs for the common control switches such as System Reset, Signal Silence, Auxiliary Disconnect, Fire Drill, Lamp Test, Acknowledge and General Alarm. The MGD-32 can also drive up to 32 supervised outputs. These output points are capable of driving LEDs or incandescent lamps. The MGD-32 mounts in a graphic annunciator wallbox or in the BB- 5000 enclosures. An external power supply is required for incandescent lamps and lamp test.
RAXN-LCDG Remote Graphic LCD Annunciator The RAXN-LCDG Remote Graphic LCD Annunciator is equipped with a 24 line x 40 character back-lit graphical LCD display that is used to display 9 events per page. Each event is displayed over 2 lines with 40 characters per line allowing emergency information to be displayed in an easy to read format. The RAXN-LCDG occupies one display position in the BB-1000 or BB-5000 Series enclosures.
RAM-1032TZDS Main Remote LED Annunciator The RAM-1032TZDS Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM-1032TZDS has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. The RAM-1032TZDS occupies one display position in the BB-1000 or BB-5000 enclosures.
Remote LED Annunciators
NOT TO BE USED FOR INSTALLATION PURPOSES. CAT. 5941 page 4 of 6
Dimensions for Annunciator Module Enclosures Model Dimensions BB-1001 9”H x 12.75”W x 1.2”D BB-1002 18”H x 12.75”W x 1.2”D BB-1003 26.4”H x 12.75”W x 1.2”D BB-1008 33”H x 22.5”W x 1.25”D BB-1012 45”H x 22.5”W x 1.25”D
RAXN-LCD in a BB-1001R
Node 5 FX-2003-12NDS in a UB-1024DS backbox
with a DOX-1024DSR door
with a DOX-1024DSR door
with a DOX-1024DSR door
RAXN-LCD and two RAX-1048TZDS
backbox with a DOX-1024DSR door
Node 2 FX-2003-12NDS in a UB-1024DS backbox
with a DOX-1024DSR door
OpenGN Graphics Software
Typical FleX-NetTM FX-2003-12NDS Networked System Configuration
NOT TO BE USED FOR INSTALLATION PURPOSES. CAT. 5941 page 5 of 6
Model Number Description Standby Alarm FX-2003-12NDS Network Compact Main Control Unit (12 Amp) 0.310 0.733 ALCN-792M Dual Analog Loops 0.130 0.145 ALCN-792M/D Quad Analog Loops 0.130 0.145 FNC-2000 Fire Network Controller Module 0.190 0.0190 FOM-2000-SP Fiber Optics Module 0.015 0.015 DM-1008A 8 Initiating Circuit Module 0.080 1 zone active: 0.125
2 zone active: 0.170 4 zone active: 0.275 6 zone active: 0.370 8 zone active: 0.465
SGM-1004A 4 Notification Appliance Circuit Module 0.060 0.258 RM-1008A 8 Relay Circuit Module 0.025 0.150 FDX-008 Fan Damper Control Module 0.015 0.035 UDACT-300A Dialer Module 0.045 0.120 PR-300 City Tie Module 0.035 0.300 RAX-1048TZDS Adder Annunciator Chassis 0.022 1 zone active: 0.026
2 zone active: 0.030 3 zone active: 0.035 4 zone active: 0.039 48 zone active: 0.262
RAM-1032TZDS Adder Annunciator Chassis 0.050 32 zone active: 0.300 AGD-048 Adder Graphic Driver Board 0.035 # of LEDs x 4mA IPS-2424DS Programmable Input Switches Module 0.010 0.015
Current Consumption
Canada 25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: (905) 660-4655 Fax: (905) 660-4113
Web page: http://www.mircom.com Email: [email protected]
Distributed by:
NOT TO BE USED FOR INSTALLATION PURPOSES.
U.S.A. 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Toll Free: (888) 660-4655 Fax Toll Free: (888) 660-4113
Model Description
Network Fire Alarm Control Panel
FX-2003-12NDS Network Compact Main Control Unit with 12 Amp power supply. Mounts in the UB-1024DS backbox.
UB-1024DS Universal black backbox. Requires DOX-1024DS(R) door.
DOX-1024DS White door for UB-1024DS backbox
DOX-1024DSR Red door for UB-1024DS backbox
Network Controller Modules
FOM-2000-SP Fiber Optic Network Adder Module
Adder Loop Controller Modules
ALCN-792D Daughter board for ALC-792M Quad Loop Controller Module
Adder Hardwire Modules
DM-1008A Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module
SGM-1004A Four Class A/B (Style Z/Y) Notification Appliance Circuit Module (Rated at 1.7 Amps per circuit)
RM-1008A Eight Relay Circuit Module c/w eight form C relays (Rated for 28 VDC @ 1 Amp max. per relay)
Adder Auxiliary Modules
PR-300 Polarity Reversal and City Tie Module
Remote Annunciators
RAM-1032TZDS Main Remote LED Annunciator c/w 32 Bi-Colored LEDs
RAX-1048TZDS Programmable LED Annunciator Module c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs
Programmable Modules
IPS-2424DS Programmable Input Switches Module c/w 24 selector switches and 24 bi-coloured LEDs
FDX-008 Fan Damper Control Module
Enclosures for Remote Annunciators / Programmable Modules
BB-1001 Remote Enclosure. Houses one module. Add suffix “R” for red door.
BB-1002 Remote Enclosure. Houses two modules. Add suffix “R” for red door.
BB-1003 Remote Enclosure. Houses three modules. Add suffix “R” for red door.
BB-1008 Remote Enclosure. Houses eight modules. Add suffix “R” for red door.
BB-1012 Remote Enclosure. Houses twelve modules. Add suffix “R” for red door.
Graphic Driver Modules
Graphics Software
Ordering Information