NEPAL ELECTRICITY AUTHORITY
(An Undertaking of Government of Nepal)
Project Management Directorate
SASEC: Power System Expansion Project
KALIGANDAKI TRANSMISSION CORRIDOR PROJECT
ADDENDUM
FOR
Procurement of Plant for Kusma – New Butwal 220 kV Transmission Line
(Design, Supply, Installation & Commissioning)
Single-Stage, Two-Envelope
Bidding Procedure
August 2017
Kaligandaki Transmission Corridor Project
Project Management Directorate
Satungal – Bauthali Chowk Marga,
Chandragiri Municipality, Matatirtha, Kathmandu, Nepal
Telephone: + 977-1- 5164099,5164091
Facsimile number: +977-1-5164091
Electronic mail address: [email protected],
Telephone: +977-1-5164091, 5164099 Fax: +977-1-5164091
Issued on:
Invitation for Bids No.: RE:ICB-PMD-KGTCP–072/73-04
ICB No.: RE:ICB-PMD-KGTCP-072/73-04
Employer: Nepal Electricity Authority
Country: Nepal
ADDENDUM-II
AMENDMENT-II
RE: ICB-PMD-KGTCP-072/73-04
Procurement of Plant for
Kusma-New Butwal 220kV Transmission Line
(Design, Supply, Installation & Commissioning)
Amendment-II
RE:ICB-PMD-KGTCP-072/73-04 Page 1 of 1
Amendment-II to Bidding Documents
Clause No. Existing Proposed Changes
Volume II,
Section I, Page
5
2.3.1 with disc insulators
SI No.
Particulars Triple Tension
1 No of Standard
Insulator Discs
3 x 17
2 Size of Disc
280 x 170
3 E& M Strength of each disc KN
160
4 Size and
Designation of pin ball shank (mm)
20
5 Creepage distance of each disc (mm)
315
2.3.1 with disc insulators
SI No.
Particulars Single ‘I’ Suspension
1 No of Standard
Insulator Discs 1 x 16
2 Size of Disc
255/280 x
145
3 E& M Strength of each disc KN 120
4 Size and
Designation of pin ball shank (mm) 20
5 Creepage distance of each disc (mm)
315
RE: ICB-PMD-KGTCP-072/73-04
Procurement of Plant for
Kusma-New Butwal 220kV Transmission Line
(Design, Supply, Installation & Commissioning)
CLARIFICATION-II
RE:ICB-PMD-KGTCP-072/073-04 Clarification-II
Page 1 of 3
NEPAL ELECTRICITY AUTHORITY
PROJECT MANAGEMENT DIRECTORATE
KALIGANDAKI TRANSMISSION CORRIDOR PROJECT
RE:ICB-PMD-KGTCP-072/073-04: Design, Supply, Installation and Commissioning of Kusma-New Butwal220 kV Transmission Line
Responses to the Bid Queries
CLARIFICATION - II
S.
No.
Clause of
Reference
for the
required
Clarification
Bidder's Request NEA Response
Volume – 1
of Tender,
Section 3 -
Clause
2.5.2(v)
Offered HTLS conductor including the core
should have been fully type tested and the test
should have been carried out in a reputed
independent Internationally Accredited
Laboratory. All the type tests should have been
carried out as specified in Vol-II Chapter V
Annexure A within the last 5 years. In case the
bidder does not have a type test of the offered size
of Conductor, type test of a higher sized HTLS
Conductor of the same technology can also be
accepted provided the bidder carries out type test
at its own cost for
the offered sized.
In order to decide higher size of conductor, kindly
confirm which one of criteria will be applicable: -
Case 1: - A conductor shall be considered of
higher size if cross-section area of conductor is
1. Please refer Clause 1. 3, Section VA, Volume II Technical Particulars
of HTLS Conductor.
The HTLS conductor shall meet the following minimum
requirements:
Overall diameter of
complete conductor
Maximum 28.62 mm
Not less than 25 mm
Not less than 28.00 (applicable for
Carbon Fibre Composite Core only)
Approx. mass of
complete conductor
(kg/km)
Less than or equal to 1621
kg/km
Direction of lay of outer
layer
Right Hand
For Carbon Fibre Composite Core only:
Overall diameter of
Core of HTLS
More than or equal to 9.5 mm
RE:ICB-PMD-KGTCP-072/073-04 Clarification-II
Page 2 of 3
more than 400 Sqmm irrespective of core size &
overall diameter.
Case 2: - A conductor shall be considered of
higher size if diameter of core is more than 9.5mm
& overall diameter of conductor is more than
25mm as specified in Table 1.3 od Section VA
Volume – 2.
Case 3: - A conductor shall be considered of
higher size if diameter of core is less than 9.5mm
& stranded conductor diameter is more than
25mm.
Case 4: - A conductor shall be considered of
higher size if diameter of core is more than 9.5mm
& stranded conductor diameter is less than 25mm.
Case 5: - A conductor shall be considered of
higher size if it meets all the criteria mentioned
above.
2. Please refer Item No. 3 Clause (iv), 2.5 Subcontractors, Section 3,
Volume I
Offered core should have been fully type tested in reputed
independent accredited testing laboratory for the size offered. All the
type test should have been carried out as specified in Annexure A of
Vol-II, Chapter V.
3. Please refer Item No. 2 Clause (v), 2.5 Subcontractors, Section 3,
Volume I
Offered HTLS conductor including the core should have been fully
type tested and the test should have been carried out in a reputed
independent Internationally Accredited Laboratory. All the type tests
should have been carried out as specified in Vol-II Chapter V
Annexure A within the last 5 years. In case the bidder does not have a
type test of the offered size of Conductor, type test of a higher sized
HTLS Conductor of the same technology can also be accepted
provided the bidder carries out type test at its own cost for the offered
sized.
4. In case the bidder does not have a type test of the offered size of core,
type test of any other size HTLS Core other than the offered size shall
not be considered for evaluation.
RE:ICB-PMD-KGTCP-072/073-04 Clarification-II
Page 3 of 3
107 Clariifcation
- I, S.No. 99
As per above NEA response, Tower Design is as
per Latest Edition. While Loading Trees furnished
as per IS :802 (part I-1995).
According to IS: 802 (Part – I:1995) for Security
Condition Wind load on Wire & Conductor
Tension is as per 32°C 100% (Full Wind) wind
Condition. But according to IS: 802 (Part –
I:2015) for Security Condition Wind load on Wire
& Conductor Tension is as per 32°C 75% wind
Condition.
Kindly Confirm, we have to adopt Loading Trees
Furnished in Specification for Tower Design and
Wind Pressure on tower to be 100% under
security condition
Please confirm.
Tower shall be Designed as per the Loading Trees furnished along with
the bidding document and as per IS :802 (part I-1995), i.e. for Security
Condition Wind load on Wire & Conductor Tension is as per 32°C
100% (Full Wind) Condition.
The Loading Tree Diagram provided along with the bid is in order.
108
Table No.
2.1, Section-
IVB of
Volume-II
Soil Classification
SANDY SOIL
(a) Ultimate Bearing Capacity KN/M2 (Kg/M2)
498 (50800)
(b) Weight KN/M3 (Kg/M3) 14.12 (1440)
(c) Angle of Repose Degrees 20
Ultimate Bearing Capacity of Sandy Soil seem
incorrect, as per Latest CBIP, it is SBC = 25000
Kg/m2.
Please confirm.
The Soil Investigation is in the scope of the contractor and the actual
value as per Soil Investigation report shall be considered for civil design
during execution.