.o -- Reproduced By GLOBAL &- ENGINEERING DOCUMENTS -= - -E Wm l h e Permission of NEMA -. Under Royalty Agreement -= ? .,/ Guide to Code Requirements for Fire Alarm and Detection Systems 2nd Edition September 1999 National Electrid Manufacturen Association 1300 North 17th Street, Suite 1847 Rosslyn, Virginia 22209 www.nema.org Copyright: NEMA Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100 No reproduction or networking permitted without license from IHS --```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Transcript of NEMA GUIDE CODE Fire Alarm & Detection System

Page 1: NEMA GUIDE CODE Fire Alarm & Detection System

.o -- Reproduced By GLOBAL &- ENGINEERING DOCUMENTS -= - -E Wm lhe Permission of NEMA

-. Under Royalty Agreement -= ? .,/

Guide to Code Requirements for Fire Alarm and Detection Systems

2nd Edition September 1999

National Electrid Manufacturen Association 1300 North 17th Street, Suite 1847 Rosslyn, Virginia 22209 www.nema.org Copyright: NEMA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 2: NEMA GUIDE CODE Fire Alarm & Detection System

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 3: NEMA GUIDE CODE Fire Alarm & Detection System

FOREWORD

This Guide to Code Requirements for Fire Alarm and Detection Systems has been published by the National Electrical Manufacturers Association (Signaling, Protection, and Communication Section -3SB). The research was performed by the National Conference of States on Building Codes and Standards (NCSBCS, Herndon, Virginia).

About the NEMA Signaling, Protection, and Communication Section (3-SB): The objective of the Section is to be the principal source of technical, training, and educational materials essential for the specification and manufacture of reliable life safety products, their installation, performance, and inspection.

The Section currently represents over 40 U.S., U.K., and Japanese manufacturers. The products are life safety/fire alarm products that provide early warning of an impending or actual fire or gaseous hazard. The products detect, noti& and initiate control functions in case of hazard to life or property.

About the National Electrical Manufacturers Association (NEMA):

For more than 70 years, the National Electrical Manufacturers Association has been developing standards for the electrical manufacturing industry and is today one of the leading consensus standards development organizations in the world. NEMA contributes to an orderly marketplace and helps promote improved public safety.

NEMA, with headquarters in Rosslyn, Virginia, has nearly 500 member companies, including large, medium, and small businesses. The organization is divided into eight divisions: Industrial Automation, Lighting Equipment, Electronics, Building Equipment, Insulating Materials, Wire and Cable, Power Equipment, and Diagnostic Imaging and Therapy Systems. Within these divisions are over 50 product-specific sections. The Signaling Section is one such Section in the Electronics Division.

For more information on NEMA and the Signaling Section, go to www.nema.org and search for the “Signaling Section” or “Fire Alarm”.

1 Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 4: NEMA GUIDE CODE Fire Alarm & Detection System

TABLE OF CONTENTS

Page

FOREWORD ...................................................................................................................... i

TABLE OF CONTENTS ....................................................................................................... ii

CHAPTER 1: Introduction/Background and Summary ............................................................................................ 1-1

Purpose ........................................................................................................................................................................ 1-1 Background ................................................................................................................................................................. 1-1 Organization and Content ......................................................................................................................................... 1-1 Glossary of Terms ...................................................................................................................................................... 1-2 State Code Summary Table ...................................................................................................................................... 1-5 CityiCounty Codes Summary Tables ..................................................................................................................... 1-7

CHAPTER 2: Code Relations and Development ........................................................................................................... 2-1

Building Regulations ................................................................................................................................................. 2-1 Code Writing Organizations .................................................................................................................................... 2-1 National Code Uniformity ........................................................................................................................................ 2-2

summary ..................................................................................................................................................................... 2-4 Map of General Areas of Building Construction Code Influence ..................................................................... 2-5

The Code Change Process ........................................................................................................................................ 2-3

States with Mandatory Statewide Building Codes ............................................................................................... 2-6

CHAPTER 3: Model Code Regulations ........................................................................................................................... 3-1

Introduction and Explanation ................................................................................................................................... 3-1

BOCA Use Group Classifications ........................................................................................................................... 3-3 1999 BOCA Codes .................................................................................................................................................... 3-7 1996 BOCA Codes .................................................................................................................................................. 3-16 1993 BOCA Codes .................................................................................................................................................. 3-25 1990 BOCA Codes ................................................................................................................................... 3-34 1987 BOCA Codes .................................................................................................................................................. 3-41 ICBO Organizational information ........................................................................................................................ 3-49 ICBO Use Group Classifications .......................................................................................................................... 3-50 1997 ICBO Codes .................................................................................................................................................... 3-55 1994 ICBO Codes .................................................................................................................................................... 3-64 1991 ICBO Codes .................................................................................................................................................... 3-73

BOCA Organizational Information ........................................................................................................................ 3-2

..............

SBCCI Organizational Information ...................................................................................................................... 3-81 SBCCi Use Group Classifications ........................................................................................................................ 3-82 1997 SBCCI Codes .................................................................................................................................................. 3-85 1994 SBCCI Codes .................................................................................................................................................. 3-94

U

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 5: NEMA GUIDE CODE Fire Alarm & Detection System

Table of Contents (continued) .......................................................................................................................... Page

NFPA Organizational Information ..................................................................................................................... 3- 103 NFPA 101 Use Group Classifications ................................................................................................................ 3-104 1997 NFPA 101 ...................................................................................................................................................... 3-106 1994 NFPA 101 ...................................................................................................................................................... 3-115 1991 NFPA 101 ...................................................................................................................................................... 3-123 1988 NFPA 101 ..................................................................................................................................................... 3-131 1985 NFPA 101 ...................................................................................................................................................... 3-137

CHAPTER 4: State Codes and Regulations .................................................................................................................... 4-1

Introduction and Explanation ................................................................................................................................... 4-1 Alabama ....................................................................................................................................................................... 4-2 Alaska .......................................................................................................................................................................... 4~ Arizona ........................................................................................................................................................................ 4-6 Arkansas .................................................................................................................................................................... 4-14 California ................................................................................................................................................................... 4-16 Colorado .................................................................................................................................................................... 4-36 Connecticut ............................................................................................................................................................... 437 Delaware .................................................................................................................................................................... 4-63 Florida ........................................................................................................................................................................ 4-68 Georgia ...................................................................................................................................................................... 4-71 Hawaii ........................................................................................................................................................................ 4-85 Idaho ........................................................................................................................................................................... 4-92 Illinois ........................................................................................................................................................................ 4-93 Indiana ....................................................................................................................................................................... 4-95 Iowa .......................................................................................................................................................................... 4-110 Kansas ...................................................................................................................................................................... 4-122 Kentucky ................................................................................................................................................................. 4-124 Louisiana ................................................................................................................................................................. 4140 Maine ....................................................................................................................................................................... 4142 Maryland ................................................................................................................................................................. 4-144 Massachusetts ......................................................................................................................................................... 4-146 Michigan .................................................................................................................................................................. 4-162 Minnesota ................................................................................................................................................................ 4-164 Mississippi .............................................................................................................................................................. 4-182 Missouri ................................................................................................................................................................... 4-183 Montana ................................................................................................................................................................... 4-184 Nebraska .................................................................................................................................................................. 4-186 Nevada ..................................................................................................................................................................... 4-188 New Hampshire ..................................................................................... ,. ................................................................ 4-198 New Jersey .............................................................................................................................................................. 4200 New Mexico ............................................................................................................................................................ 4202 New York: ............................................................................................................................................................... 4-204 North Carolina ........................................................................................................................................................ 4-215 North Dakota .......................................................................................................................................................... 4-23 1 Ohio .......................................................................................................................................................................... 4-233 Oklahoma ................................................................................................................................................................ 4-235 Oregon ..................................................................................................................................................................... 4-237

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 6: NEMA GUIDE CODE Fire Alarm & Detection System

Table of Contents (continued) .......................................................................................................................... Page

Pennsylvania ........................................................................................................................................................... 4-254 Rhode Island ........................................................................................................................................................... 4-260 South Carolina ........................................................................................................................................................ 4266 South Dakota ........................................................................................................................................................... 4-268 Tennessee ................................................................................................................................................................ 4269 Texas ........................................................................................................................................................................ 4-27 1 Utah .......................................................................................................................................................................... 4-272 Vermont ................................................................................................................................................................... 4-274 Virginia .................................................................................................................................................................... 4-276 Washington ............................................................................................................................................................. 4-278 West Virginia .......................................................................................................................................................... 4-280 Wisconsin ................................................................................................................................................................ 4-288 Wyoming ................................................................................................................................................................. 4-297

CHAPTER 5: City and County Codes and Regulations .............................................................................................. 5-1

Introduction and Explanation ................................................................................................................................... 5-1

Baltimore, Maryland ................................................................................................................................................. 5-3 Boston, Massachusetts .............................................................................................................................................. 5-4

Cincinnati, Ohio ....................................................................................................................................................... 5-16 Cleveland, Ohio ........................................................................................................................................................ 5-17 Dallas, Texas ........................................................................................................................................................... 5-18 Denver, Colorado ..................................................................................................................................................... 5-27 Detroit, Michigan ..................................................................................................................................................... 5-43 District of Columbia ................................................................................................................................................ 5~ Houston, Texas ......................................................................................................................................................... 5-53 Las Vegas, Nevada ................................................................................................................................................. 5-63 Los Angeles (City), California .............................................................................................................................. 5-74 Los Angeles (County), california ......................................................................................................................... 5-75 Miami, Florida .......................................................................................................................................................... 5-76 Minneapolis, Minnesota ......................................................................................................................................... 5-87 Montgomery County, Maryland ............................................................................................................................ 5-88 New Orleans, Louisiana .......................................................................................................................................... 5-99 New York City, New York .................................................................................................................................. 5-100

Philadelphia, Pennsylvania ................................................................................................................................... 5-109 Phoenix, Arizona .................................................................................................................................................... 5-124 Pittsburgh, Pennsylvania ...................................................................................................................................... 5-125

Seattle, Washington ............................................................................................................................................... 5-127

Atlanta, Georgia ......................................................................................................................................................... 5-2

Chicago, Illinois ......................................................................................................................................................... 5-5

Orange Counîy, Florida ........................................................................................................................................ 5-108

San Francisco, California ..................................................................................................................................... 5-126

iv

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 7: NEMA GUIDE CODE Fire Alarm & Detection System

CHAPTER 1 INTRODUCTION, BACKGROUND AND SUMMARY

PURPOSE

The purpose of this report is to develop an analysis of building regulatory criteria applicable to fire alarm and detection systems. This document outlines and compares the administrative and technical requirements for installation of such systems, how the regulations are promulgated and applied, and who is responsible for these activities.

BACKGROUND

In the United States, building construction is regulated by state and local government agencies using a variety of codes, standards, and regulations. In many cases, building construction regulations are based on codes and standards developed by private organizations (i.e., SBCCI, BOCA, ICBO, NFPA). They are then adopted and enforced by state or local jurisdictions. Adopting and enforcing agencies often amend these documents to further regulate building design, safety, and construction. In some states and local jurisdictions, codes are developed independent of the previously mentioned model codes as "homegrown codes."

The requirements for fire alarm and detection systems vary greatly among the states and local jurisdictions because of differences in code adoption and enforcement. In addition, such systems are subject to the provisions of several codes, specifically the building, fire prevention, and life safety codes which, in many cases, are adopted and enforced by "competing agencies." With such diversity, it is appropriate to analyze the building regulatory criteria of all 50 states and various major cities to get a realistic sense of provisions applicable to fire alarm and detection systems and how those provisions are enforced and revised.

ORGANIZATION AND CONTENT

In order to provide a comprehensive analysis of the vast amount of applicable data, the report is separated into three sections containing summaries of the codes and regulations from model, state, and city codes as they relate to fire alarmidetection systems. Each summary is organized giving the following information as applicable.

Organizational Information (Model Codes only) - Specifics about the code organization such as address and phone number, their publications, areas covered, and other related information.

Administration Requirements (States and Cities) - Details of what codes are used, who to contact, and enforcement applications.

Use Group Classifications - Provides a breakdown of building classifications by use as applicable.

Table of Requirements - Summarizes where fire alarmidetection systems are required by building use type.

Requirements and Exceptions - Provides summaries of code regulations affecting fire alarmidetection systems.

The state and city summaries provide the information from the model code edition adopted or from their own written codes. Changes to model code requirements are noted in italics. Where a model code is adopted with no changes, the user should refer back to the proper model code.

1-1 Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 8: NEMA GUIDE CODE Fire Alarm & Detection System

GLOSSARY OF TERMS USED

The following phrases, words, and terms used within this report are defined below as used or referenced herein.

ANSI: American National Standards Institute.

Approved: Approved by the code official or other authority having jurisdiction.

AS- American Society of Heating, Refrigerating and Air-conditioning Engineers, Inc.

ASME: American Society of Mechanical Engineers.

ASTM: American Society of Testing and Materials.

Automatic Fire Alarm System: A device or system providing an emergency function without human intervention and activated by a predetermined temperature rise, rate of rise of temperature, or increase in the level of combustion pïo&uL-$.,

Automatic Fire Detector: A device, which automatically detects heat, smoke or other products of combustion.

Automatic Fire Extinguishing System: An approved system of devices and equipment which automatically detects fire and discharges an approved fire extinguishing agent on or in the area of a fire.

Automatic Fire Suppression System: An engineered system to detect automatically and suppress a fire through fixed piping and nozzles.

Automatic Sprinkler System: An automatic fire extinguishing system which automatically detects a fire and discharges water on or in the area of a fire.

BOCA: Building Officials and Code Administrators International.

Central Station Signaling System: A system consisting of electrically operated circuits and equipment which transmits alarms from buildings and structures equipped with a fire protection system to a central station. The central station is controlled and operated by a Department approved person or firm whose business is furnishing and maintaining such a system and where qualified personnel are in attendance at all times to notify the fire department of any alarm received.

Dwelling Unit: Any building or portion of which contains living facilities, including provisions for sleeping, eating, cooking, and sanitation for not more than one family.

Fire Alarm System: A system of electrical devices and circuits or mechanical devices installed, arranged, and maintained to form, transmit, or emit signals indicating an emergency requiring immediate action to safeguard life and property.

Fire Protection Equipment: Any appliance, device, or system provided or installed in the event of fire. It may include, but is not limited to, fire assemblies, fire hydrants, fire department connections, and fire protection systems.

Fire Protection System: Any fire alarm device or system, fire extinguishing device or system, or their combination for the premises which is designed and installed for detecting, controlling, or extinguishing a fire or otherwise alerting occupants of the premises that a fire is in progress or has occurred.

1-2

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 9: NEMA GUIDE CODE Fire Alarm & Detection System

Fire Suppression System: A mechanical system designed and equipped to detect a fire, actuate an alarm, and suppress a fire.

Guest Room: Any room or rooms used or intended to be used by a guest for sleeping purposes only.

HPM: Hazard production materials.

WAC: Heating, ventilating and air conditioning.

IAPMO: International Association of Plumbing and Mechanical Officials.

ICBO: International Conference of Building Officials.

ICC: International Code Council

Local Jurisdiction: County, city, or regional governments,

Manual Fire Alarm System: An interior alarm system composed of sending stations and signaling devices in building, operated on an electric circuit, so arranged that the operation of any one station will ring all signals throughout the building and at one or more approved locations.

NBC: National Building Code (BOCA).

NCSBCS: National Conference of States on Building Codes and Standards, Inc.

NFC: National Fire Codes.

NFPA National Fire Protection Association.

NFPC: National Fire Prevention Code (BOCA).

Occupancy: The purpose for which a building, or part of, is used or intended to be used.

Occupant Load: The total number of persons that may occupy a building, portion of a building, or premises at any one time for assembly purposes.

SBC: Standard Building Code.

SBCCI: Southern Building Code Congress International.

SFBC: South Florida Building Code.

SFPC: Standard Fire Prevention Code.

Smoke Detector: An approved device, which senses visible or invisible particles of combustion. 1-3

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 10: NEMA GUIDE CODE Fire Alarm & Detection System

Sprinkler Alarm System: An alarm activated by waterflow from a sprinkler system.

UBC: Uniform Building Code.

UFC: Uniform Fire Code.

Use Group: The classification of a building or structure based on the purpose for which it is intended to be used.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 11: NEMA GUIDE CODE Fire Alarm & Detection System

CODE BASIS FOR STATE CODES AND REGULATIONS

Arizona

Arkansas

California

Colorado

Connecticut

Delaware

Florida

Life Safety I Fire I Building I State

None 1988 UFC None

1997 SBC 1997 SFPC 1997 NFPA 101

1997 UBC 1997 UFC None

None None None

1996 NBC None 1997 NFPA 101

None State 1997 NFPA 101

1997 SBC State 1994NFPA 101

Alabama I 1994 SBC I 1994 SFPC I 1994NFPA 101

Georgia

Hawaii

Alaska I 1997UBC I 1997UFC I None

1994 SBC State 1997 NFPA 101

None 1990 UFC None

Indiana

Iowa

1997 UBC 1997 UFC None

1994 UBC State State

~

Idaho I 1997 UBC I 1997 UFC I 1997NFPA 101

Kansas

Kentucky

Louisiana

Illinois I None I State I 1991 NFPA 101

1997 UBC State 1991 NFPA 101

1996 NBC 1997 NFPA 1 1997 NFPA 101

1994 SBC 1997 NFPA 1 1997 NFPA 101

Maine

Maryland

Massachusetts

None NFPA 1994NFPA 101

1996 NBC 1997 NFPA 1 1997NFPA 101

1993 NBC State None

Mississippi

Missouri

Michigan I 1996NBC I None I None

1997 SBC 1997 SFPC 1985 NFPA 101

None None None

Minnesota I 1997 UBC I 1997 UFC I 1997NFPA101

1-5

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 12: NEMA GUIDE CODE Fire Alarm & Detection System

I 1 Montana I 1997uBC I 1994UFC I None

Nevada

New Hampshire

New Jersey

New Mexico

New York

North Carolina

North Dakota

I I Nebraska I 1991UBC 1 State I 1994NFPA101

1991 UBC 1991 UFC 1994NFPA 101

1999 NBC 1997 NFPA 1 1997NFPA 101

1996 NBC State None

1997 UBC 1991 UFC 1997NFPA 101

State State 1991 NFPA 101

1994 SBC 1994 SFPC None

1994 UBC 1994 UFC 1997NFPA 101

Ohio 1996 Nl3C 1996 NFPC None

I ~~

' I Oklahoma I None I 1996NFpC 1 1997NFPA 101

1997 SBC

None

1997 UBC

1987 NBC

1996 NBC

1997 UBC

1996 NBC

State

1997 UBC

I 1 Oregon I 1997UBC I 1997 UFC 1 None

1997 NFPA 1997NFPA 101

None 1997NFPA 101

1997 UFC 1997NFPA 101

1992 NFPA 1 1994NFPA 101

1996 NFPC None

1997 UFC None

NFPA 1997 NFPA 101

State None

1997 UFC None

I I Pennsylvania I None I State I State

I I RhodeIsland I 1996Nl3C 1 1997 NFPA 1 I 1997NFPA 101

I I South Carolina I 1997 SBC I 1997 SFF'C I None

I I South Dakota I 1994UBC I 1994UFC I 1994NFPA101

Tennessee

Texas

Utah

Vermont

Virginia

Washington

West Virginia

Wisconsin

Wyoming

1-6

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 13: NEMA GUIDE CODE Fire Alarm & Detection System

CODE BASIS FOR CITY AND COUNTY CODES AND REGULATIONS

Baltimore

Boston

Chicago

Cincinnati

Cleveland

I Life Safety I Fire I Building I Locality

1996 NBC 1996 NFPC

1993 NBC City

City City

1996 NBC 1996 NFPC

1996 NBC 1996 NFPC

I Atlanta I 1994 SBC I 1994 SFPC I 1997NFPA 101

Dallas 1991 UBC 1991 UFC

1997 UBC Denver 1997 UFC

Pittsburgh

San Francisco

' Seattle

Washington, D.C.

1996 NBC

1996 NBC 1996 NFPC

1997 UBC 1997 UFC

1997UBC 1997 UFC

1990 NBC 1990 NFPC

I city

1997 NFPA 101

1997 NFPA 101

None

1981 NFPA 101

None ~

None

1994NFPA 101

NFPA 101

I Houston 1 1994UBC 1 1994UFC 1 None

I Las Vegas I 1997UBC I 1997UFC I None

I Los Angeles City I 1997 UBC 1 None

Los Angeles County

Miami

Minneapolis

Montgomery County

New Orleans

New York City

1997 UBC

SFBC

1997 UBC

1996 NBC

1997 SBC ~~

City

1997 UFC

1994 NFPA 101

1997 UFC None

1997 NFPA 101

1994 SFPC 1997 NFPA 101

û&ge county (FL) I 1997 SBC I 1990SFPC 1 1994NFPA101 I I Philadelphia 1 1996NBC 1 1993 NFF'C 1 None

I Phoenix I 1997 UBC I 1997 UFC I None

1-7

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 14: NEMA GUIDE CODE Fire Alarm & Detection System

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 15: NEMA GUIDE CODE Fire Alarm & Detection System

CHAPTER 2 CODE REGULATIONS AND DEVELOPMENT

BUILDING REGULATIONS

The best answer to the question "What's in the codes?" is "Anything that addresses health, life safety, welfare of buildings, and building construction." This includes the individual products, materials, systems, and equipment that are designed, manufactured, tested, and assembled to make a building and its spaces. Code provisions focus on two different aspects of buildings: 1) Conceptual aspects such as egress, ventilation, air quality, energy conservation, lighting, and things that one cannot touch-and material aspects such as products, materials, systems, devices, and other items which make up the building construction and 2) things that are finite and touchable.

Buildmg regdations are a mixture of regulations, standards, and procedures covering the different aspects of building construction, plumbing, mechanical systems, electrical, fire protection, life safety, accessibility, and energy. These documents may appear as one complete text covering all of these aspects or may be an assortment of separate texts or standards, which together regulate construction and compliance.

CODE WRITING ORGANIZATIONS

Three code-writing organizations are the Building Officials and Code Administrators International (BOCA), Intemational Conference of Building Officials (ICBO), and the Southern Building Code Congress International (SBCCI). These code-writing organizations publish model codes, which may be adopted by units of state and local government or be used voluntarily by others where no building regulations exist.

The National Fire Protection Association (NFPA) promulgates the National Fire Codes and Standards (NFC), which are a series of issue and building-type specific documents covering areas associated with fire safety and fire prevention. The most prominent of documents used in the building regulatory process are the NFPA 70, National Electrical Code, and NFPA 101 Life Safety Code; although others, such as NFPA 72 on protective signaling systems, NFPA 3 1 on fuel oil, NFPA 54 on natural gas, and NFPA 58 on LPG systems, are widely used in the codes community.

Numerous other associations and trade groups develop standards applicable to their general area of interest and many of those documents are introduced into and used as supporting infomiation and documentation in the various codes. There is a significant reliance by organizations, other than state and local jurisdictions that write their own code provisions, on the model code organizations, BOCA, ICBO, ICC, NFPA, and SBCCI, for the criteria contained in state and local codes.

2- 1

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 16: NEMA GUIDE CODE Fire Alarm & Detection System

Many of the voluntary standards, other industry guidelines and handbooks, are modified into code language or referenced and are included in the model codes or NFC. They are then used as part of the codes for the regulation of building design and construction.

Recent initiatives at the state level have created more statewide codes and eliminated local government options to develop their own codes or amend codes themselves. (See Figures 1 and 2.) Such initiatives wiü not change what is covered in the codes but the differences in requirements from jurisdiction to jurisdiction will become more uniform as time goes on.

It must be recognized that several states and many units of local government do not use the model codes and standards that have been developed on the national level. Because of historic perspectives, many jurisdictions have maintained their ability or desire to update and maintain their own regulations. Wisconsin and New York were early leaders in the development of statewide codes and still maintain this ability. Major cities such as New York and Chicago continue to develop their own codes, as do Broward and Dade Counties in South Florida. This type of code promulgation was more prevalent in the past, but now more state and local governments are looking to the model codes and other national standards as the basis for their building and construction regulations.

NATIONAL CODE UNIFORMITY

Common Code Format The three model code organizations, BOCA, ICBO, and SBCCI, along with CABO (now ICC), united to move toward a single national building code. As a first step, the 1993 BOCA National Codes, the 1994 ICBO Uniform Codes, the 1994 SBCCI Standard Codes, and the 1995 CABO One and Two Family D w e h g Code were reorganized and published in a common code format. Although technical content was not considered in this effort, users can now turn to the same chapter in all documents to find any given topic.

The International Code Council Continuing in the direction of a single national code system, the International Code Council (ICC) was formed in December 1994. The ICC was organized to function as an umbrella organization to support common code development; it consists of representatives from each of the model code groups. The purpose of the ICC is to handle the development and maintenance of the International Codes and to support training and product evaluation activities.

The first two ICC codes-the International Plumbing Code (IPC) and the International Private Sewage Disposal Code, were published in late 1994. The memberships of both BOCA and ICBO approved the IPC as the plumbing code document at their respective 1994 mua1 business meetings. The third ICC code, the International Mechanical Code (IMC), was published at the beginning of 1996.

2-2

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 17: NEMA GUIDE CODE Fire Alarm & Detection System

Since then, other International Codes have been developed and published and it is expected the first edition of the International Building Code will be available by the year 2000.

These codes will be maintained through a joint hearing process that still allows participation by the membership of each organization. The ICC will conduct a single initial hearing. Each organization will then conduct separate final hearings, with members voting at the respective annual meetings in the f d . The final disposition of each proposed change will be derived from the cumulative results of the three hearings.

THE CODE CHANGE PROCESS

BOCA, ICBO, SBCCI, and the ICC accept proposed code changes annually. Comments on proposed changes may be made by any individual or organization and are accepted at a public hearing or submitted in writing for the record. A committee of experts fi-om the code organization is given the responsibility for hearing testimony and arguments for and against each particular change to the codes. These proposed changes, with the technical rationale for the changes, are published by the model code organizations and made available for review by interested and affected parties.

Based on such discussions, at the meeting a code change is recommended for acceptance, rejection, or in some cases held for further study. The changes are published yearly as supplements to the codes and new code editions are published every three years.

The NFPA accepts comments or proposed changes to its specific documents by holding hearings and debates. Membership votes are taken, the changes are recorded, and subsequent editions are published. Unlike the model codes, NFPA does not issue yearly supplements but reprints the documents at specific intervals, usually every three years or more often as necessary. NFPA does publish tentative interim amendments, which are essentially minor changes to specific provisions of the documents.

When states and units of local government adopt the model codes and other standards, they may develop amendments to these codes as necessary to address particular state or local situations. These amendments are usually administrative and are intended to address fees, permits, plan review, and other aspects associated with code administration. In addition, these amendments may delete or modi@ major portions of these codes to address regional differences in construction requirements for seismic, climatic, or design variations peculiar to that region.

Statewide code revisions are usually developed by the state agency responsible for development and administration of the code. They are made available for public review and comment and then finalized through state adoption processes. When local governments are allowed to adopt codes, they generally provide for the adoption of codes in their municipal ordinances. The appropriate officials are then responsible for maintaining andor enforcing these provisions as detailed in their municipal codes.

2-3

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 18: NEMA GUIDE CODE Fire Alarm & Detection System

Inconsistencies in model codes arise when state and local government adopt model codes from a specific edition of a model code or standard. When the edition is updated or revised, the state model code is not subsequently revised. In many cases, the model codes adopted are changed from year to year and the amendment to the code may not be applicable to the new edition.

A major error made by state and local governments adopting model codes occur when revising a section of the regulations which adopt a particular edition of a model code or standard, is that they update to a later edition without revising subsequent portions of their codes that amend that document. In many cases, the model codes adopted are changed from year to year but the amendments to the code may not be applicable to the later edition subsequently adopted. This can result in erroneous substitutions or omissions in critical code provisions. Many of these adopting ordinances and regulations may not be written by the building official, but by a city clerk, attorney, or other individual responsible for administration and not enforcement.

SUMMARY

Building codes and regulations in the United States are as varied and individual as the subjects covered within them. To determine what rules to follow, one must consider the state, regional, county, or city regulations, how they interGace, and who has the final authority. Adoption of model codes helps provide consistency as will a single national code system. The adoption and enforcement of a single code throughout the country is probably still a long way OE

2 -4

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 19: NEMA GUIDE CODE Fire Alarm & Detection System

& 5 O 8 m

v) o Z

L

rc O c3 > n v) a, a o v)

Q) m O o

v) Q) 'CI O o -

Q) 'CI

P a, I? 2

L 5 8 n

6 uj c, (II

h S m -

W D PL0 a w

a u o v) Q) m O o i o o cn

(II 'CI C (II

m

-e

uj

v

v) Q) m O o ô m 2 Y

v) Q) m O o

- (u o O - Y- O â a, Cu v)

.c.,

.c.,

o O m Y

e 0

hJ=

> o

r c n & S t

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 20: NEMA GUIDE CODE Fire Alarm & Detection System

STATES WITH MANDATORY STATE WI DE

BUJLDING CODES

Mandatory Statewide Codes, All Buildings

Mandatory Statewide Codes, Commercial Buildings Only n* ‘l Codes Adopted at Local Level

Note: States with no building code may have a voluntary code, or may have codes that apply to other applications, e.g. fire, plumbing, and life safety. To be sure your project is in compliance with the codes applicable to your area, always check with your state or local building department.

2-6

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 21: NEMA GUIDE CODE Fire Alarm & Detection System

CHAPTER 3 INTRODUCTION A N D EXPLANATION

This chapter contains summaries of requirements and regulations from the latest editions of the model codes as they affect fire alarm/detection systems. Each model code section provides information about the model code organization, explanation of the building use group classifications, a table summarizing the areas where fire suppression, protection and detection systems are needed, and an explanation of the code requirements and exceptions as they apply to the building types.

Because the code requirements are complex and varied, the tables have been set up to indicate when there are code provisions for fire protection systems in each of the use groups. Where possible, the tables indicate the key item (i.e., building height or number of occupants) that dictates using fire protection systems. Where no specific item exists but fire protection systems may be needed, the tables will have the word "required." This alerts the user to review the appropriate listings of code requirements and explanations following the table. The code requirements and explanations are a brief synopsis of the appropriate code text and should be used in conjunction with the actual code for exact details.

3-1

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 22: NEMA GUIDE CODE Fire Alarm & Detection System

MODEL CODE ORGANEATION

ORGANIZATION:

ADDRESS:

KEY STAFF:

PURPOSE:

PUBLICATIONS:

SERVICES

AREAS OF INFLUENCE:

CODE REVISION PROCESS :

Building Officials and Code Administrators International (BOCA)

405 1 West Flossmoor Road Country Club Hills, IL 60478-5795 (708) 799-2300

Chief Executive Officer, Paul Heilstedt, PE Vice President, Member Services, Terrence Leppellere, PE Vice President, Codes and Standards, Kenneth Schoonover, PE

Founded in 19 15 to exchange knowledge and ideas concerning building safety and construction regulation. Promotes establishment of minimum unbiased building codes and provides services for keeping them up to date.

National Building Code International Mechanical Code Inrernarional Plumbing Code National Fire Prevention Code National Existing Structures Code BOCA Magazine Research Reports International Codes

Training Audio -visual programs Textbooks and manuals Codes publishing Seminars and workshops Computer software Certification programs Consultation and advisory services

The Northeastern and North Central United States and parts of Texas including Maine, Vermont, New Hampshire, Rhode Island, Massachusetts, Connecticut, Pennsylvania, Maryland, New Jersey, Delaware, Virginia, West Virginia, Kentucky, Ohio, Michigan, Illinois, and Missouri.

The BOCA codes are revised and updated annually with editions published every third year. Proposals for code changes must be submitted by November 1, which will be considered and reviewed by democratic process for approval by September of the following year.

3-2

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 23: NEMA GUIDE CODE Fire Alarm & Detection System

1999 BOCA USE GROUP CLASSIFICATIONS

GROUP A - ASSEMBLY

Buildings used for assembly with greater than 50 occupants. Sub-classify as follows:

A-1 Theaters - Theaters and other buildings for theatrical or operatic performances and exhibitions with raised stage and fixed seats, proscenium curtain, fixed or portable scenery loft, lights, motion picture booth, mechanical appliances, and other theatrical accessories and equipment.

A-2 Nightclubs, Dance Halls - Buildings and public assembly places including rooms, lobbies, and other spaces connected thereto with common means of egress and entrance without theatrical stage accessories and designed for use as dance hall, night club, or similar.

A-3 Restaurants, Recreation - Buildings with or without auditorium and without theatrical stage other than raised platform where people assemble for amusement, entertainment, or recreation and incidental motion picture, dramatic, or theatrical presentations including art galleries, exhibition halls, museums, lecture halls, libraries, restaurants other than nightclubs, recreation centers, and passenger terminals.

A 4 Churches -Buildings used as churches and for similar religious purposes.

A-5 Stadiums - Outdoor assembly structures including grandstands, bleachers, coliseums, stadiums, tents, and similar structures.

GROUP B - BUSINESS

Buildings or parts thereof used for busmess transactions, rendering of professional services, or for other services involving stocks of goods, wares, or merchandise in limited quantities for use incidental to office uses or sample purposes including: data processing, animal hospitals and kennels, automobile showrooms, banks, beauty and barber shops, car washes, civic administration and post offices, laboratories for testinghesearch, telephone exchanges, laundries and dry cleaning and self-service and pick-up/delivery stations, outpatient clinics, radio/TV stations, fire and police stations, florists and nurseries, print shops, and professional services.

GROUP E - EDUCATIONAL

Buildings or parts thereof used by more than five persons at one time for educational purposes through twelfth grade including schools, academies, and day-care facilities providing care for more than 16 persons over two-and-one-half years of age for less than 24 hours per day.

GROUP F - FACTORY/INDUSTRIAL.

Buildings or parts thereof; including among others, factories, assembling plants, industrial laboratories, and all other industrial and manufacturing uses where occupants engaged in fabricating, assembling, or processing of products or materials. Sub-classify as follows:

F-1 Moderate Hazard - Moderate hazard factory and industrial uses for manufacturing processes including aircraft, automobiles, appliances, boats, and RVs, bakeries, alcoholic beverages, boilers works, canneries, clothing, machinery, dry cleaning using other than flammables, electronics and electric light plants, food processing, film, furniture, tanneries, woodworking, paper mills, plastic, publishing, printing, refuse incinerators, shoes, soap, sugar, tobacco, upholstery, textile mills, and laundries.

3-3

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 24: NEMA GUIDE CODE Fire Alarm & Detection System

F-2 Low Hazard - Factory and industrial uses involving fabrication or manufacturing of noncombustible materials which during finishing, packing, or processing, do not involve significant fire hazard including nonalcoholic beverages, brick, masonry, ceramic, glass, and gypsum, foundries, ice, metal fabrication and assembly, and water pumping plants.

GROUP H - HAZARDOUS

Buildings or parts thereof used for manufacturing, processing, generation, or storage of corrosive, highly toxic, highly cohustible, flammable, or explosive materials including loose combustible fibers, dust, and unstable materials that constitute high fire or explosion hazard. Sub-classify as follows:

H-1 -Buildings and structures or parts thereof containing materials, which present a detonation hazard.

H-2 - Buildings and structures; or parts thereof, which contain materials presenting a deflagration hazard or a hazard from accelerated burning.

__ ii-3 - Buildings and structures or parts thereof which contain materials rhat readily suppurl conibustiuri or pieseiii a physical hazard.

H-4 - Buildings and structures or parts thereof containing materials that are a health hazard.

3-4

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 25: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL

Buildings or parts thereof where people suffering from physical limitations due to health or age harbored for medical or other care or treatment, where people detained for penal or correction purposes, or where liberty of inmates is restricted. Sub-classify as follows:

1-1 Supervised - Facilities for children, aged persons, mentally impaired and convalescents including group homes, mentally retarded care facilities, nursing homes, and orphanages, housing more than 16 individuals who, because of age, mental disability, or other reasons, must live in supervised environment but who are physically capable of responding to emergency situation without personal assistance.

1-2 Incapacitated -Use for persons with physical limitations including hospitals, day nurseries, sanitariums, infirmaries, orphanages, and homes for aged and infirm. This group includes care facilities accommodating for any length of time more than 16 occupants two and one-half years of age or less or occupants not capable of responding to emergency situations.

1-3 Restrained - Buildings or parts thereof including prisons, jails, reformatories, insane asylums, and similar uses, inhabited by occupants under some restraint.

GROUP M - MERCANTILE

Buildings or parts thereof used for display and sales purposes and accessible to public including retail stores, motor fuel service stations, shops, salesrooms, and markets.

GROUP R - RESIDENTIAL

Buildings or parts thereof where families or households live or where sleeping accommodations provided for individuals with or without dining facilities. Sub-classify as follows:

R-1 HotelsNotels - Hotels, motels, boarding houses, and similar buildings arranged for shelter and sleeping accommodations for more than five occupants primarily transient in nature who use facilities for less than 30 days.

R-2 Multifamily -Dwellings with more than two dwelling units including boarding houses and similar buildings arranged for shelter and sleeping accommodations for occupants primarily not transient in nature. This also includes dormitories accommodating more than five persons older than 2-1/2 years of age.

3-5

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 26: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTUL. ícontinued]

R-3 One and Two Family and Multiple Single-family -Buildings arranged for use as one- or two-family dwelling units with maximum five lodgers or boarders per family and multiple single-family dwellings where each unit has its own means of egress. This also includes a childcare facility accommodating five or less children of any age. This group includes residential care facilities, unless classified as Group R-2.

GROUP S - STORAGE

Buildings or parts thereof including warehouses, storehouses, and freight depots used primarily for storage of goods, wares, or merchandise. Sub-classify as follows:

S-1 Moderate Hazard - Storage buildings for contents likely to bum with moderate rapidity, but not producing poisonous gases, fumes, or explosives.

S-2 Low Hazard - Storage buildings for noncombustible materials and low hazard wares that do not ordinarily burn rapidly such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings but with negligible amount ofplastic trim such as h o b s , handles, or film wrapping.

GROUP U - UTILITY AND MISCELLANEOUS

Accessory buildings and miscellaneous structures not classified in any specific use group per Building Code requirements commensurate with fire and life hazard incidental to use. This group is to include structures accessory to a residential occupancy.

3-6

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 27: NEMA GUIDE CODE Fire Alarm & Detection System

1999 NATIONAL CODES (BOCA) Fire AlarmDetection Systems

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants

Group F - Factory F-1 - Moderate Hazard

Group H - High Hazardous

Group I - Institutional

Group M - Mercantile

Group R - Residential R-1 - HotelMotels R-2 - Multifamily

S-1 - Moderate Hazard Group S - Storage

Covered Mails

Hazardous Production Materials Facilities

Automatic Fire Sprinkler Systems

> 12,000 sq. ft.

> 12,000 sq. ft. 12,000 sq. ft.

> 5,000 sq. ft.

> 20,000 sq. ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required

Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. fi. total

Required

Required

Required

Fire Alarm Systems

Required > 2 stories

Required

Required

Required

Required > 3 stories

> 2 stories

Required

Automatic Detection Systems

Required

Required

Required Required

> 30 ft. ceiling

Required

Required

3-7

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 28: NEMA GUIDE CODE Fire Alarm & Detection System

High-rise Buildings

Required

Public Garages

Required

Required

Special Amusement Building

Underground Structures

> 75 ft.

> 3 stories or 12,000 sq. fi. or

> 24,000 sq. ft. total Required

Required

3-8

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 29: NEMA GUIDE CODE Fire Alarm & Detection System

1999 NATIONAL CODES (BOCA) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout Groups A-I, A-3, and A-4 occupancies that exceed 12,000 square feet as follows: entire story or floor level where Groups A-I, A-3, or A-4 occupancies are located; all stories and floors below Groups A-I, A-3, or A-4; and all stories and floor levels between Groups A-1, A-3, or A-4 and the level of exit discharge. Exception: Groups A-1 or A-3 auditoriums, Group A 4 naves and chancels, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance. These requirements also apply to Group A-2 occupancies, which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy.

Section 918.4.1 (Building Code) areas of churches.

Provide f i e alarm system in Group A 4 occupancies except in sanctuary and nave

GROUP B - BUSINESS

Section 918.4.2 (Building Code)

Provide fire alarm system in Group B occupancies, which are two or more stories above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code)

Provide automatic fire suppression system throughout Group E occupancies, unless floor area is less than 20,000 square feet

Section 918.4.1 (Building Code)

Provide fire alarm system in all Group E occupancies.

Section F-503.5 (Fire Code)

Provide fire alarm system in all existing Group E occupancies per Building Code.

3-9

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 30: NEMA GUIDE CODE Fire Alarm & Detection System

GROUPF-FACTORYENDUSTRIAL

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in area, or more than 24,000 square feet total area on all floors, or more than three stories above grade.

GROUP H - HAZARDOUS

Sections 904.5 and 417.1 (Building Code)

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code. Also excepted are grain storage tanks, silos, and bins.

Section F-503.2 (Fire Code)

Provide automatic fire suppression system throughout all high-hazard occupancies, including all structures occupied for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic.

Section 419.3 (Building Code)

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Section 2808.4 (Building Code)

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Section 417.5.3 (Building Code)

Provide automatic fire detection system per NFPA 72 throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high- hazard materials are used and stored.

Section 918.4.3 (Building Code)

Provide a fire alarm system in Groups H-2, H-3, and H-4 occupancies.

GROUP I - INSTITUTIONAL

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I Occupancies. Exception: Group 1-2 child-care facilities accommodating 1 O0 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

3-10

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 31: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTfTzTTIONAL (continued)

Section 918.4.4 (Building Code)

Section F-503.5 (Fire Code)

Section 919.4 (Building Code)

Section 920.3.3 (Building Code)

Section 409.5.1 (Building Code)

Section F-503.4 (Fire Code)

GROUP M - MERCANTILE

Section 904.7 (Building Code)?

GROUP R - RESIDENTIAL

Sections 904.8 and 906.2.1 (Building Code)

Section 904.9 (Building Code)

Section 904.10 (Building Code)

Provide fire alarm systems in all Group I Buildings.

Provide fire alarm system in all existing Groups 1-2 and 1-3 occupancies.

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide automatic fire detection system and smoke detectors throughout all resident housing areas. Smoke detectors are not required in sleeping rooms with not more than four occupants.

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery-power backup.

In Group 1-2, provide automatic fire detection system in corridors and spaces open to the corridors in nursing homes and detoxification facilities. Exception 1: Not required if patient sleeping rooms have smoke detectors permanently connected to the building?s power supply and have a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station attending the rooms. Exceptions 2: Not required if patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function.

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Use Group 1-1 occupancies. Power source for smoke detector may be either AC or battery.

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade. Exception: Public garages.

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Provide automatic fire suppression system throughout all Group R-2 occupancies other than residential care facilities and buildings two stories or less, including basements, and with 12 or less dwelling units and each dwelling unit has a least one door of direct access to exit.

Provide automatic sprinkler system throughout fire area of Groups R-2 and R-3 residential care facility. Install sprinkler system per NFPA 13R or approved quick- response sprinklers per NFPA 13. Excepted is R-1 residential care facilities where every floor level has direct access to exterior.

3-1 1

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 32: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIALíconthued)

Section 918.4.5 (Building Code)

Section 918.4.6 (Building Code)

Section 919.4.4 (Building Code)

Section 920.3.1 (Building Code)

Section F-503.4 (Fire Code)

GROW S - STORAGE

Section 904.7 (Building Code)

Provide fire alarm system in all Group R-1 occupancies.

Provide fire alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

Provide single- or multiple-station smoke detectors in Groups R-1, R-2, and R-3 occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery-power backup.

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Group R-I occupancies and in dwelling units in Groups R-2 and R-3 occupancies.

Provide automatic fire suppression system throughout in Group S-1 occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stones above grade.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Section 404.6 (Building Code)

Section 922.4.2 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atium.

Provide a smoke control system in all atriums that connect more than two stories.

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alarm signaling system.

In a smoke control area with ceiling height over 30 feet, provide smoke detectors to detect smoke above highest floor open to an atrium or at highest point of another smoke control space.

3-1 2

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 33: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 402.10 and 402.14.2 (Building Code) the mall.

Provide automatic sprinkler system throughout covered mall building and all connected buildings, including kiosks and similar structures that are covered and located within

Section 402.7.1 (Building Code)

In anchor store, provide smoke control system to be activated by smoke detectors installed in return air portion of heating and cooling system, automatic sprinkler system, and manual controls provided in an approved location.

HAZARDOUS PRODUCTION MATERIALS FACILITES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 416.9.2 (Building Code) control station.

Install smoke detectors in re -circulating air stream to initiate a signal at the emergency

Section 416.14.5 (Building Code)

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

“ R I S E BUILDINGS

Section 403.1 (Building Code)

Section 403.2 (Building Code)

Section 403.4 (Building Code)

PUBLXC GARAGES

Section 408.3.1 (Building Code)

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-1, H-2 or H-3; and low-hazard special occupancies.

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

SPECIAL AMUSEMENT BUILDDIGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

3-1 3

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 34: NEMA GUIDE CODE Fire Alarm & Detection System

SPECIAL AMUSEMENT BUILDINGS (continued)

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

Section 411.7 and 412.8 (Building Code)

Provide automatic sprinkler system in all buildings or portions used as sound stages for ínütiûn picture or television production and over 1,000 square feet.

UNDERGROUND STRUCTURES

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for f re department use.

UNDERGROUND STRUCTURES

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voiceialarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

3-1 4

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 35: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1020.3 (Building Code)

Section 2805.2.3 (Building Code)

Section 2809.6 (Building Code)

Section 2810.4 (Building Code)

Section 904.10 (Building Code)

Section 3006.2 (Building Code)

Section 918.5 (Building Code)

Section F-503.6 (Fire Code)

When an exit stairway discharges into an interior exit discharge lobby located at the level of exit discharge, provide automatic sprinkler system throughout the story containing the exit discharge lobby.

Provide automatic fire suppression system over and immediately beneath building’s equipment platform(s). Defined by this code, equipment platform is an unoccupied elevated platform used for building’s mechanical systems or industrial process equipment.

Provide approved automatic fire suppression system at the top and at alternate floor levels in a waste or linen chute and in the termination and incinerator rooms. System not required if incinerator burns only Type 4 waste.

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.1 O. Exception: Group R-3 occupancies.

Provide smoke detectors in each elevator lobby at each floor and associated machine/equipment room. Install smoke detector to activate emergency operation.

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

In existing structures, provide approved smoke or heat detectors in return air ducts or plenums in each re-circulating air system with a capacity of 2,000 cfm or more and serving more than one floor in building exceeding six stories in height. If not part of an approved smoke control system, install so that actuation of the detector automatically stops the fans.

3-1 5

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 36: NEMA GUIDE CODE Fire Alarm & Detection System

1996 NATIONAL CODES (BOCA) Fire Alarm/Detection Systems

Hazardous Production Materials Facilities

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A-4- Churches

Required

Group B -Business

Automatic Fire Sprinkler Systems

> 12,000 sq. ft.

> 12,000 sq. ft. > 12,000 sq. ft.

> 5,000 sq. fi.

Group E - Educational

F-1 - Moderate Hazard

> 20,000 sq. ft.

> 3 stories or 12,000 sq. i?. er

Group R - Residential R-1 - Hotel/Motels R-2 - Multifmilv

Group S - Storage S-1 - Moderate Hazard

Required Required

> 3 stories or > 12,000 sq. fi. or > 24,000 sq. ft. total

Required

Required

Fire Alarm Systems

Required

> 2 stories

Required

Required

Required

Required > 3 stories

> 2 stories

Required

Automatic Detection Systems

Required

~~

Required

Required Required

> 30 ft. ceiling

Required

Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 37: NEMA GUIDE CODE Fire Alarm & Detection System

High-rise Buildings

Public Garages

Special Amusement Building

Underground Structures

> 75 ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required

Required

> 75 ft. > 75 ft. L Required

3-17

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 38: NEMA GUIDE CODE Fire Alarm & Detection System

1996 NATIONAL CODES (BOCA) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout Groups A-1, A-3, and A-4 occupancies that exceed 12,000 square feet as follows: entire story or floor level where Groups A-I, A-3, or A 4 occupancies are located; all stories and floors below Groups A-I, A-3, or A-4; and all stories and floor levels between Groups A-1, A-3, or A 4 and the level of exit discharge. Exception: Groups A-1 or A-3 auditoriums, Group A-4 naves and chancels, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance. These requirements also apply to Group A-2 occupancies, which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy.

Section 918.4.1 (Building Code)

Provide fire alarm system in Group A 4 occupancies except in sanctuary and nave areas of churches.

GROUP B - BUSINESS

Section 918.4.2 (Building Code)

Provide fire alarm system in Group B occupancies, which are two or more stories above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code)

Provide automatic fire suppression system throughout Group E occupancies, unless floor area is less than 20,000 square feet

Section 918.4.1 (Building Code)

Provide fire alarm system in all Group E occupancies.

Section F-503.5 (Fire Code)

Provide fire alarm system in all existing Group E occupancies per Building Code.

GROUP F - FACTORY/lNDUSTRIAL

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in area, or more than 24,000 square feet total area on all floors, or more than three stories above grade.

3-18

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 39: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS

Sections 904.5 and 417.1 (Building Code)

Section 503.2 (Fire Code)

Section 419.3 (Building Code)

Section 2806.4 (Building Code)

Section 417.5.3 (Building Code)

Section 918.4.3 (Building Code)

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code.

Provide automatic fire suppression system throughout all high-hazard occupancies, including all structures occupied for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic.

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Provide automatic fire detection system per NFPA 72 throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high- hazard materials are used and stored.

Provide a fire alarm system in Groups H-2, H-3, and H-4 occupancies.

GROUP I - INSTITUTIONAL

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I Occupancies. Exception: Group 1-2 child-care facilities accommodating 100 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

Section 918.4.4 (Building Code)

Section 503.5 (Fire Code)

Provide fire alarm systems in all Group I Buildings.

Provide fire alarm system in all existing Groups 1-2 and 1-3 occupancies.

3-19

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 40: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSITIZTTIONAL (continued)

Section 919.4 (Building Code)

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide automatic fire detection system and smoke detectors throughout all resident housing areas. Smoke detectors are not required in sleeping rooms with not more than four occupants.

Section 920.3.3 (Building Code)

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery-power backup.

Section 409.5.1 (Building Code)

In Group 1-2, provide automatic fire detection system in corridors and spaces open to the corridors in nursing homes and detoxification facilities. Exception 1 : Not required if patient sleeping rooms have smoke detectors permanently connected to the building’s power supply and have a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station attending the rooms. Exceptions 2: Not required if patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function.

Section F-503.4 (Fire Code)

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Use Group 1-1 occupancies. Power source for smoke detector may be either AC or battery.

GROUP M - MERCANTILE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade. Exception: Public garages.

GROUP R - RESIDENTIAL

Sections 904.8 and 906.2.1 (Building Code)

Section 904.9 (Building Code)

Section 918.4.5 (Building Code)

Section 918.4.6 (Building Code)

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Provide automatic fire suppression system throughout all Group R-2 occupancies except buildings two stories or less, including basements, and with 12 or less dwelling units and each dwelling unit has a least one door of direct access to exit.

Provide fire alarm system in all Group R-1 occupancies.

Provide fire alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest levei of exit discharge.

3-20

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 41: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 919.4.4 (Building Code)

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

Section 920.3.1 (Building Code)

Provide single- or multiple-station smoke detectors in Groups R-I, R-2, and R-3, occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery -power backup.

Section F-503.4 (Fire Code)

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Group R-1 occupancies and in dwelling units in Groups R-2 and R-3 occupancies.

GROUP S - STORAGE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout in Group S-1 occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 404.2 (Building Code) atrium.

Provide automatic sprinkler system in atrium and all stories and floors connected to the

Section 404.4 (Building Code)

Provide a smoke control system in all atriums that connect more than two stories.

Section 404.6 (Building Code)

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alarm signaling system.

Section 922.4.2 (Building Code)

In a smoke control area with ceiling height over 30 feet, provide smoke detectors to detect smoke above highest floor open to an atrium or at highest point of another smoke control space.

3-21

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 42: NEMA GUIDE CODE Fire Alarm & Detection System

COWRED MALLS

Section 402.10 and 402.14.2 (Building Code) the mall.

Provide automatic sprinkler system throughout covered mall building and all connected buildings, including kiosks and similar structures that are covered and located within

Section 402.7.1 (Building Code)

In anchor store, provide smoke control system to be activated by smoke detectors installed in return air portion of heating and cooling system, automatic sprinkler system, and manual controls provided in an approved location.

HAZARDOUS PRODUCTION MATERIALS PACLlTIES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 416.9.2 (Building Code) control station.

Install smoke detectors in re-circulating air stream to initiate a signal at the emergency

Section 416.14.5 (Building Code)

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

HíGHREZ BUILDINGS

Section 403.1 (Building Code)

Section 403.2 (Building Code)

Section 403.4 (Building Code)

PUBLIC GAFWGES

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-I, H-2 or H-3; and low-hazard special occupancies.

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system

Section 408.3.1 (Building Code)

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

3-22

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 43: NEMA GUIDE CODE Fire Alarm & Detection System

SPECIAL AMUSEMENT BUILDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

Section 411.7 and 412.8 (Building Code)

Provide automatic sprinkler system in all buildings or portions used as sound stages for motion picture or television production and over 1,000 square feet.

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.5.2 (Building Code)

Section 405.6 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Provide a fire alarm system, which includes a voice/alarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

3-23

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 44: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1020.3 (Building Code)

Section 2807.6 (Building Code)

Section 2808.4 (Building Code)

Section 904.10 (Building Code)

Section 918.5 (Building Code)

Section 503.6 (Fire Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Provide approved automatic fire suppression system at the top and at altemate floor levels in a waste or linen chute and in the termination and incinerator rooms. System not required if incinerator bums only Type 4 waste.

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.10. Exception: Group R-3 occupancies.

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

In existing structures, provide approved smoke or heat detectors in return air ducts or plenums in each re-circulating air system with a capacity of 2,000 cfin or more and serving more than one floor in building exceeding six stories in height. If not part of an approved smoke control system, install so that actuation of the detector automaticaily stops the fans.

3-24

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 45: NEMA GUIDE CODE Fire Alarm & Detection System

1993 NATIONAL CODES (BOCA) Fire AlarnúDetection Systems

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A-4- Churches

Automatic Fire Sprinkler Systems

> 12,000 sq. ft.

> 12,000 sq. fi. > 5,000 sq. ft.

> 12.000 sa. fi.

I Group B -Business

Group M - Mercantile

Group R - Residential R-1 - HotelíMotels R-2 - Multifamily

S-1 - Moderate Hazard Group S - Storage

Group E - Educational

Group F - Factory F-1 - Moderate Hazard

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Group H - High Hazardous

Atriums

Covered Malls

Group I - Institutional

Required

Required

> 20,000 sq. ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required

Required

Fire Alarm Systems

Reauired > 2 stories

Requked

Required

Required

Required > 3 stories

2 stories

Automatic Detection Systems

Required

Required

Required Reauired

> 30 fi. ceiling

Required

3-25

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 46: NEMA GUIDE CODE Fire Alarm & Detection System

Hazardous Production Materials Facilities

Required Required Required

High-rise Buildings > 1 5 fi.

3-26

> 75 ft. > 75 fi.

Public Garages

Special Amusement Building

Underground Structures

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required Required

Required Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 47: NEMA GUIDE CODE Fire Alarm & Detection System

1993 NATIONAL CODES (BOCA) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Section 917.4.1 (Building Code)

Provide automatic fire suppression system throughout Groups A-1, A-3, and A-4 occupancies that exceed 12,000 square feet as follows: entire story or floor level where Groups A-1, A-3, or A-4 occupancies are located; all stories and floors below Groups A-1, A-3, or A-4; and all stories and floor levels between Groups A-1, A-3, or A-4 and the level of exit discharge. Exception: Groups A-1 or A-3 auditoriums, Group A 4 naves and chancels, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance. These requirements also apply to Group A-2 occupancies, which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy.

Provide fire alarm system in Group A-4 occupancies except in sanctuary and nave areas of churches.

GROW B - BUSINESS

Section 917.4.2 (Building Code)

Provide fire alarm system in Group B occupancies, which are two or more stories above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code)

Provide automatic fire suppression system throughout Group E occupancies, unless floor area is less than 20,000 square feet

Section 917.4.1 (Building Code)

Provide fire alarm system in all Group E occupancies.

Section F-503.5 (Fire Code)

Provide fire alarm system in all existing Group E occupancies per Building Code.

GROUP F - FACTORY/INDUSTRIAL

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in area, or more than 24,000 square feet total area on all floors, or more than three stories above grade.

3-27

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 48: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Sections 904.5 and 417.1 (Building Code)

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code.

Section 503.2 (Fire Code)

Provide automatic fire suppression system throughout all high-hazard occupancies, including all structures occupied for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic.

Section 419.3 (Building Code)

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Section 2806.4 (Building Code)

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Section 417.5.3 (Building Code)

Provide automatic fire detection system per NFPA 72 and NFPA 72E throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high-hazard materials are used and stored.

Section 917.4.3 (Building Code)

Provide a fire alarm system in Groups H-2, H-3, and H-4 occupancies.

GROUPI - INSmzTTIONAL

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I Occupancies. Exception: Group 1-2 child-care facilities accommodating 1 O0 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

Section 917.4.4 (Building Code)

Section 503.5 (Fire Code)

Provide fire alarm systems in all Group I Buildings.

Provide fue alarm system in all existing Groups 1-2 and 1-3 occupancies.

3-28

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 49: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 918.4.3 (Building Code)

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide smoke detectors throughout all resident housing areas except sleeping rooms with not more than four occupants.

Section 919.3.3 (Building Code)

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery -power backup.

Section 409.5.1 (Building Code)

In Group 1-2, provide smoke detectors with a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station in nursing homes and detoxification facilities. Exceptions: Patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function and sleeping rooms of a child-care facility.

Section F-503.4 (Fire Code)

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Use Group 1-1 occupancies. Power source for smoke detector may be either AC or battery.

GROUP M - MERCANTILE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade. Exception: Public garages.

GROUP R - RESIDENTIAL

Sections 904.8 and 906.2.1 (Building Code)

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Section 904.9 (Building Code)

Provide automatic fire suppression system throughout all Group R-2 occupancies except buildings two stories or less, including basements, and with 12 or less dwelling units and each dwelling unit has a least one door of direct access to exit.

Section 917.4.5 (Building Code)

Provide fire alarm system in all Group R-1 occupancies.

Section 917.4.6 (Building Code)

Provide fire alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Section 918.4.4 (Building Code)

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

3-29

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 50: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 919.3.1 (Building Code)

Section F-503.4 (Fire Code)

GROUP S - STORAGE

Section 904.7 (Building Code)

Provide single- or multiple-station smoke detectors in Groups R-1, R-2, and R-3 occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery-power backup.

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Group R-1 occupancies and in dwelling units in Groups R-2 and R-3 occupancies.

Provide automatic fire suppression system throughout in Group S-1 occupancies which are more than 12,000 square feet in area, mort: íhari 2,000 syuatt: fwi in íoíal area ori all floors, or more than three stories above grade.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Section 404.6 (Building Code)

Section 921.4.2 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atrium.

Provide a smoke control system in all atriums that connect more than two stories.

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alann signaling system.

In atriums where the height of the atrium ceiling exceeds 30 feet above the floor, provide smoke detectors to detect smoke above the highest floor level open to the atrium.

3-30

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 51: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 402.10 (Building Code)

Section 402.12 (Building Code)

Provide automatic sprinkler system throughout covered mall building and all connected buildings.

Provide smoke control system in covered mall and adjacent tenant spaces activated by smoke detectors per NFPA 72E, automatic sprinkler system, and manual controls provided for fire department use.

HAZARDOUS PRODUCTION MATERIALS FACILITIES

Section 416.4 (Building Code)

Section 416.9.2 (Building Code)

Section 416.14.5 (Building Code)

HíGHRISE BUILDINGS

Section 403.1 (Building Code)

Section 403.2 (Building Code)

Section 403.4 (Building Code)

PUBLIC GARAGES

Section 408.3.1 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Install smoke detectors in re-circulating air stream to initiate a signal at the emergency control station.

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-1, H-2 or H-3; and low-hazard special occupancies.

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

3-31

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 52: NEMA GUIDE CODE Fire Alarm & Detection System

SPECIAL AMUSEMENT BUILDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall ofthe stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

UNDERGROUND STRUCTURES

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voiceíalarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Section 1020.3 (Building Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Section 2807.6 (Building Code)

Provide approved automatic fire suppression system at the top and at alternate floor levels in a waste or linen chute and in the termination and incinerator rooms.

Section 2808.4 (Building Code)

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

3-32

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 53: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL. REOUíREMENTS (continued)

Section 904.10 (Building Code)

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.10. Exception: Group R-3 occupancies.

Section 917.5 (Building Code)

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

Section 503.6 (Fire Code)

In existing structures, provide approved smoke or heat detectors in return air ducts or plenums in each re-circulating air system with a capacity of 2,000 cfm or more and serving more than one floor in building exceeding six stories in height. If not part of an approved smoke control system, install so that actuation of the detector automatically stops the fans.

3-33

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 54: NEMA GUIDE CODE Fire Alarm & Detection System

1990 NATIONAL CODES (BOCA) Fire AlarrdDetection Systems

Required Required

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A A - Churches

Group B - Business

Required > 4 stories

Group E - Educational

F-1 - Moderate Hazard

> 75 ft.

Group H - High Hazard

> 75 ft.

Group M - Mercantile

Group R - Residential R-1 - HotelMotels R-2 - Multifamily

S-1 - Moderate Hazard Group S - Storage

Covered Malls

High-rise Buildings

Automatic Fire Sprinkler Systems

Required > 5,000 sq. ft. > 12,000 sq. ft.

Fire Alarm Systems

Required > 3 stories

> 3 stories or > 12,000 sq. ft. or > 24.000 sa. fi. total

Required

Required

Required Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

I

Automatic Detection Systems

Required

Required Reauired

Required

> 75 ft.

3-34

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 55: NEMA GUIDE CODE Fire Alarm & Detection System

Public Garages

3-35

Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 56: NEMA GUIDE CODE Fire Alarm & Detection System

1990 BOCA CODES Requirements and Exceptions

GROUP A - ASSEMBLY

Section 1002 (Building Code)

Provide fir-e suppression systems in assembly buildings as follows: Group A-1 - Throughout entire story or floor level where Group A-1 located, all

stories and floors below Group A-1 and all stories and floor levels between Group A-1 and level of exit discharge. Exception: Auditoriums. t> Group A-2 - When more than 5,000 square feet in area, provide throughout entire story or floor level where Group A-2 located, all stories and floors below Group A-1 and all stories and floor levels between Group A-2 and level of exit discharge. Exception: Auditoriums.

story or floor level where Group A-3 located, all stories and floors below Group A-1 and all stories and floor levels between Group A-3 and level of exit discharge. Exception: Auditoriums.

Group A-3 - When more than 12,000 square feet in area, provide throughout entire

Section 1016.4.1 (Building Code)

Provide fue alarm system in new and existing Group A 4 (churches) except in sanctuary and nave areas.

Section 404.5 (Fire Code)

Provide manual fire alarm system in all existing buildings used as churches or for educational use except sanctuary and nave areas of churches and similar religious buildings.

GROUP B - BUSINESS

Section 1016.4.2 (Building Code) of exit discharge.

Provide fire alarm systems in Group B when two or more stories above or below level

GROUP E - EDUCATIONAL

Section 1016.4.1 (Building Code)

Provide fire alarm systems in all Group E occupancies.

3-36

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 57: NEMA GUIDE CODE Fire Alarm & Detection System

GROWF-FACTORYIINDUSTRIAL

Section 1002.7 (Building Code)

Provide fire suppression system in Group F-1 buildings more than 12,000 square feet in area; or more than 24,000 square feet total area on all floors; or more than three stories high. Exception: Public garages.

GROUP H - HAZARDOUS

Section 1002.5 (Building Code)

Provide fire suppression systems in all Group H buildings or portions thereof.

GROW I - INSTITUTIONAL

Section 610.5 (Building Code)

Provide automatic fire alarm system in patient sleeping rooms, corridors, and common spaces open to corridors in Group 1-2 occupancies. Provide automatic smoke detection system interconnected to fire alarm system in corridors of Group 1-2 not equipped with automatic fire suppression systems. Provide smoke detector in patient sleeping rooms except when rooms equipped with automatic door closing devices with integral smoke detectors on room sides. Provide heat detectors in un-sprinkled areas per Section 610.2 of Building Code.

Section 1002.6 (Building Code)

Section 1016.4.3 (Building Code)

Provide fire suppression system in all Group I buildings or portions except:

five stories;

than three stories; t> Group 1-2 nursing homes of Types 1,2A, or 2B construction not more than one story;

Group 1-2 hospitals of Type 1 construction not more than 75 feet and not more than

Group 1-2 hospitals of Type 2A construction not more than 45 feet and not more

Group 1-2 hospitals of Type 2B construction not more than one story; Group 1-2 child care facilities not more than one story with maximum 1 O0 children

Group 1-1 not more than two stories and having maximum 20 occupants; and with each room having direct exit outside;

Provide fire alarm systems in all Group I Buildings.

3-37

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 58: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTI7zTTIONAL ícontinued)

Section 1017.4 (Building Code)

Provide automatic fire detection systems in all Group 1-1, automatic fire detector system per 610.5 in Group 1-2, and automatic smoke detectors in 1-3 throughout all resident sleeping areas except sleeping rooms with not more than four occupants in Use Condition II or 111 or when protected with approved automatic fire suppression systems.

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

Section 1018.3.4 (Building Code)

Provide at least one single station smoke detector in each guest room, suite, or sleeping area in Group I- 1.

GROW M - MERCANTILE

Section 1002.7 (Building Code)

Provide fire suppression system in Group M buildings more than 12,000 square feet in area or more than 24,000 square feet in total area on all floors; or more than three stories. Exception: Public garages.

GROUP R - RESIDENTIAL

Section 1002 (Building Code)

Provide fire suppression systems throughout Group R-1 except guest rooms which have their own exit directly to outside at grade and throughout R-2; except in bathrooms not more than 55 square feet in area.

Section 1016.4.4 (Building Code)

Section 1016.4.5 (Building Code)

Section 1017.5 (Building Code)

Provide fire alarm systems in all Group R-I.

Provide fire alarm systems in Group R-2 where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

3-38

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 59: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 1017.4.4 (Building Code)

Provide automatic fire detection systems in Group R-1 except units without interior corridors and direct exterior exit access from each sleeping room.

Section 1018.3 (Building Code)

Provide at least one single station smoke detector in all sleeping areas, areas of egress and on each story within each guest room or suite, in Group R-1, in dwelling units in immediate vicinity of bedrooms, on every story including basements in Group R-2 and R-3, and in all bedrooms in Group R-2.

GROUP S - STORAGE

Section 1002.7 (Building Code)

PUBLIC GARAGES

Section 609.2.1 (Building Code)

COVERED MALLS

Section 601.9 (Building Code)

Section 1019.3 (Building Code)

HIGHRISE BUILDINGS

Section 602.1 (Building Code)

Section 602.3 (Building Code)

Section 602.6 (Building Code)

Section 602.7 (Building Code)

Provide fire suppression system in Group S-1 when more than 12,000 square feet in area; more than 24,000 square feet in total area on all floors; or more than three stories.

Provide fire suppression system as follows: ta Group I public garages more than 10,000 square feet in area, more than 7,500 square feet and more than one story, more than 5,000 square feet and more than two stories, more than three stories, when located in buildings with other uses on upper stories, in any story more than 50 percent below grade, and in fuel dispensing areas. ta Group 2 public garages when more than 10,000 square feet and more than one story, more than two stories, and when located in buildings with other uses on upper stories. Exception: Open parking structures. ta Bus garages per above or when used as passenger terminals or for storage and Ioading of four or more buses.

Provide automatic fire suppression throughout covered mall building and all connected buildings. Electrically supervise all sprinkler control valves.

Provide smoke control system in covered malls activated by smoke detectors per NFPA 72E-1987.

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers, open parking structures, and Group A-5.

Provide automatic fire suppression throughout high-rise buildings. Exception: Open parking structures.

Provide automatic fire detection system in rooms per Building Code and in ducts serving two or more floors.

Provide voice alarm and communication systems.

3-39

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 60: NEMA GUIDE CODE Fire Alarm & Detection System

HIGH-FUSE BUILDINGS (continued)

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but mu st provide manual fire alarm system. Exception does not apply to Group 1-2 and Group 1-3 and single station smoke detectors in sleeping areas and dwelling units.

HAZARDOUS PRODUCIION MATERZALS FACILITES

Section 603.1.2.1 (Building Code)

Provide automtic sprinkler system throughout HPM facilities.

Section 603.1.7.2 (Building Code)

Install smoke detectors in re-circulating air stream.

Section 603.4.5 (Building Code)

Provide local manual alarm pull station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

AIRPORT TRAFF'IC CONTROL TOWERS

Section 617.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

SPECIAL NOTES

Section 606.2 (Building Code)

Provide an electrically supervised automatic sprinkler system.

Section 606.4 (Building Code)

Provide a smoke control system in accordance with Section 1019.4 in all atriums that connect more than two stories.

Section 1019.4.3 (Building Code)

Provide smoke detectors in the atrium and on the ceiling of floors opening into the atrium within 15 feet of the atrium.

Section 606.6 (Building Code)

Provide a f r e alarm system in all buildings with an atrium. In Use Groups A, E, or M the system is required to be a voice alarm signaling system.

3-40

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 61: NEMA GUIDE CODE Fire Alarm & Detection System

1987 NATIONAL CODES (BOCA) Fire AlarmIDetection Systems

Group F - Factory F-1 - Moderate Hazard

Group H - High Hazard

Group I - Institutional

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A-4- Churches

Group B -Business

> 3 stories or > 12,000 sq. fi. or > 24,000 sq. fi. total Required

Required

Group E - Educational

Group R - Residential R-1 - HotelMotels R-2 - Multifamily

S-1 - Moderate Hazard Group S - Storage

Covered Maiis

Automatic Fire Sprinkler Systems

Required > 1 story or >5,000 sq. ft. > 12,000 sq. ft.

> 12 stories or 150 ft.

> 12 stories or 150 fi. > 12 stories or 150 ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required

I

High-rise Buildings

Public Garages Group B, R-1, R-2 > 75 fi.

Required

Group M - Mercantile > 3 stories or > 12,000 sq. fi. or > 24,000 sq. ft. total

Fire Alarm Svstems

Required > 3 stories

Required

Required

Required > 4 stories

> 7.5 fi.

Automatic Detection Svstems

Required

Required > 75 ft.

Required

> 75 ft Required

3-41

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 62: NEMA GUIDE CODE Fire Alarm & Detection System

1987 BOCA CODES Requirements and Exceptions

GROUP A - ASSEMBLY

Section 1002 (Building Code)

Provide fire suppression systems in assembly buildings as follows: 9 Group A-1 - Throughout building except in auditoriums, foyers, lobbies, and toilet rooms. 9 Group A-2 - In all buildings more than one story high or when more than 5,000 square feet in area. 9 Group A-3 - In all buildings more than 12,000 square feet in area.

Section 1017.3.1 (Building Code)

Section 404.5 (Fire Code)

GROUP B - BUSINESS

Section 1002 (Building Code)

Section 1017.3.2 (Building Code)

Section 1018.3.4 (Building Code)

Section 1018.4 (Building Code)

Section 1002.22 (Building Code)

Provide fire alarm system in new and existing Group A 4 (churches) except in sanctuary and nave areas.

Provide manual fire alarm system in all existing buildings used as churches or for educational use except sanctuary and nave areas of churches and similar religious buildings.

Provide fire suppression systems in all Group B buildings more than 12 stories or more than 150 feet high.

Provide fire alarm systems in Group B when three or more stories except buildings less than seven stories and equipped with automatic fire suppression systems.

Provide automatic fire detection systems in ail Group B having floors for human occupancy located more than 75 feet above lowest level of fire department vehicle access.

Automatic fire detection system not required when building equipped with automatic fire suppression system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

3-42

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 63: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 1002.22 (Building Code)

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

Section 1017.3.1 (Building Code)

Provide fire alarm systems in all new and existing Group E occupancies.

Section 1018.4 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire alarm system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

GROUP F - FACTORYLNDUSTRJAL

Section 1002 (Building Code)

Provide fire suppression system in Group F-1 buildings more than 12,000 square feet in area; or more than 24,000 square feet total area on all floors; or more than three stories high.

Section 1002.22 (Building Code)

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

GROUP H - HAZARDOUS

Section 1002 (Building Code)

Section 1002.22 (Building Code)

Provide fire suppression systems in all Group H buildings or portions thereof.

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

3-43

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 64: NEMA GUIDE CODE Fire Alarm & Detection System

Section 610.6 (Building Code)

Provide automatic fire alarm system in patient sleeping rooms, corridors, and common spaces open to corridors in Group 1-2 occupancies. Provide automatic smoke detection system interconnected to fire alarm system in corridors of Group 1-2 not equipped with automatic fire suppression systems. Provide smoke detector in patient sleeping rooms except when rooms equipped with automatic door closing devices with integral smoke detectors on room sides. Provide heat detectors in un-sprinkled areas per Section 610.2 of Building Code.

Section 1002.8 (Building Code)

Section 1002.22 (Building Code)

Section 1017.3.3 (Building Code)

Section 1018.3 (Building Code)

Section 1018.3.5 @Building Code)

Provide fire suppression system in all Group I buildings or portions except: ta Group 1-2 hospitals of Type 1 construction not more than 75 feet and not more than five stories; ta Group 1-2 hospitals of Type 2A construction not more than 45 feet and not more than three stories; ta Group 1-2 nursing homes of Types 1,2A, or 2B construction not more than one story;

ta Group 1-2 child-care facilities not more than one story with maximum 100 children and with each room having direct exit outside;

LX Group 1-3 with less than six occupants.

Group 1-2 hospitals of Type 2B construction not more than one story;

Group 1-1 not more than two stories and having maximum 20 occupants;

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

Provide fire alarm systems in all Group I Buildings.

Provide automatic fire detection systems in all Group 1-1, fire alarm systems in Group 1-2, and automatic smoke detectors in Group 1-3 throughout all resident sleeping areas except sleeping rooms with not more than four occupants in Use Condition II or III or when protected with approved automatic fire suppression systems.

Provide at least one single station smoke detector in each guest room, suite, or sleeping area in Group 1-1.

3-44

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 65: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1018.4 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

GROUP M - MERCANTILE

Section 1002 (Building Code)

Section 1002.22 (Building Code)

GROUP R - RESIDENTIAL

Section 1002 (Building Code)

Section 1002.22 (Building Code)

Section 1017.3.5 (Building Code)

Section 1018.3 (Building Code)

Section 1018.3.5 (Building Code)

Provide fire suppression system in Group M buildings more than 12,000 square feet in area; more than 24,000 square feet in total area on all floors; or more than three stories.

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

Provide fire suppression systems in Group R-1 and R-2 more than 12 stories or more than 150 feet except in bathrooms not more than 55 square feet in area.

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

Provide fire alarm systems in all Group R-1 and Group R-2 four stories or more.

Provide automatic fire detection systems in Group R-1 except motelhotel units without interior corridors and direct exterior exit access from each sleeping room and Group R- 2 not more than 75 feet.

Provide at least one single station smoke detector in each guest room, suite, or sleeping area in Group R-1 and 1-1, in dwelling units in immediate vicinity of bedrooms in Group R-2 or R-3, in basements in Group R-1 and R-2, and on every story including basements in Group R-3.

3-45

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 66: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL ícontinued)

Section 1018.4 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

GROUP S - STORAGE

Section 1002 (Building Code)

Section 1002.22 (Building Code)

Provide fire suppression system in Group S-1 when more than 12,000 square feet in area; more than 24,000 square feet in total area on all floors; or more than three stories.

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

PUBLE GARAGES

Section 1002 (Building Code)

Provide fire suppression system as follows: Group 1 public garages more than 10,000 square feet in area, more than 7,500

square feet and more than one story, more than 5,000 square feet and more than two stories, more than three stories, when located in buildings with other uses on upper stories, in any story more than 50 percent below grade, and in fuel dispensing areas.

Group 2 public garages when more than 10,000 square feet and more than one story, more than two stories, and when located in buildings with other uses on upper stones. Exception: Open parking structures. e Bus garages per above or when used as passenger terminals or for storage and loading of four or more buses.

Section 1002.22 (Building Code)

May substitute automatic fire alarm system in lieu of fire suppression system where such system may be detrimental or dangerous to specific use or occupancy.

3-46

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 67: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 601.9 (Building Code)

Section 1019.4 (Building Code)

HIGHRISE BUILDINGS

Section 602.1 (Building Code)

Section 602.3.1 (Building Code)

Section 602.3.2.5 (Building Code)

Section 602.4 (Building Code)

Section 602.5 (Building Code)

Section 1018.4 (Building Code)

Provide automatic fire suppression throughout covered mall building and all connected buildings. Electrically supervise all sprinkler control valves.

Provide smoke control system in covered malls activated by smoke detectors per NFPA 72E-1984.

Apply to Group B, R-1, and R-2 buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access.

Provide automatic fire suppression throughout high-rise buildings. Areas of refuge may be substituted for fire suppression systems when less than 12 stories or less than 150 feet but also provide manual alarm system.

.

Provide manual fire alarm system.

Provide smoke detection system in rooms per Building Code and in ducts serving two or more floors.

Provide alarm and communication systems.

Automatic fire detection system not required when building equipped with automatic fire suppression system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

HAZARDOUS PRODUCTION MATERIALS FACILITIES

Section 603.1.7.2 (Building Code)

Install smoke detectors in re-circulating air stream.

Section 603.4.5 (Building Code)

Provide local manual alarm pull station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

AIRPORT TRAFFIC CONTROL TOWERS

Section 616 (Building Code)

Section 1018.4 (Building Code)

Provide automatic fire alarm systems in all such buildings.

Automatic fire detection system not required when building equipped with automatic fire suppression system but shall provide manual fire alarm system. Exception does not apply to Group 1-2 and single station smoke detectors in sleeping areas and dwelling units.

3-47

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 68: NEMA GUIDE CODE Fire Alarm & Detection System

SPECIAL NOTES

Section 606.1.1 (Building Code)

Section 606.2.1 (Building Code)

Section 1019.5.3 (Building Code)

Section 606.2.3 (Building Code)

Provide an electrically supervised automatic fire suppression system.

Provide a smoke control system in accordance with Section 1019.5 in all atriums that connect more than two stories.

Provide smoke detectors in the atrium and on the underside of each floor level that is open to the atrium space.

Provide a fire alarm system in all buildings with an atrium. In Use Groups A, E, or M, the system is required to be a voice alarm signaling system.

3-48

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 69: NEMA GUIDE CODE Fire Alarm & Detection System

MODEL CODE ORGANIZATION

ORGANIZATION: International Conference of Building Officials (ICBO)

ADDRESS: 5360 South Workman Mill Road Whittier, CA 90601 (562) 699-0541

KEY STAFF: President, Jon Traw Vice President of Technical Services, Rick Okawa Publications, Edward Giles

PURPOSE: Publishes, maintains, and promotes the Uniform Building Code series; researches principles underlying safety to life and property in the construction, use, and location of buildings and related structures; develop and promulgate uniformity in regulations pertaining to building construction; educate the building official; formulate guidelines for the administration of building inspection departments. Founded in 1922.

PUBLICATIONS: Uniform Building Code International Mechanical Code International Plumbing Code Uniform Housing Code Uniform Fire Code Uniform Code for Abatement of Dangerous Buildings Uniform Sign Code Uniform Administrative Code Uniform Code for Building Construction Building Standards Magazine Newsletter International Codes

SERVICES:

AREAS OF I " C E

CODE REVISION PROCESS:

Training programs and seminars Certification programs Speakers Bureau Evaluation service

The State of Indiana and most states west of the Mississippi River except Oklahoma, Missouri, Illinois, Arkansas, and Louisiana.

The ICBO codes are revised and updated annually with new editions published every three years. Code updating is a continuous process with changes acted upon by ICBO membership at its annual business meeting.

3-49

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 70: NEMA GUIDE CODE Fire Alarm & Detection System

1997 ICBO USE GROUP CLASSIFICATIONS

GROUP A -ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1

A-2

A-2.1

A-3

A 4

An Assembly building with a stage and an occupant load of 1,000 or more.

Building or portion thereof; having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Building or portion thereof; with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUP E - EDUCATIONAL

Sub-classify in divisions as follows:

El Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

E 2 Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

E 3 Buildings used for day-care purposes for more than six persons.

3- 50

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 71: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORY AND INDUSTRIAL

A building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repairing or processing operations. Sub-classify in divisions as follows:

F-1 Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F- 2.

F-2 Low-hazard factory and industrial occupancies including facilities producing noncombustible or non- explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1 Buildings with quantity of material in excess of building code limitations, which present high explosion hazard, including but not limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days.

Unclassified detonatable organic peroxides. 6 Manufacturing of Class 1.4G fireworks.

LX Class 4 oxidizers. 6 Class 4 or Class 3 detonatable unstable (reactive) materials.

H-2 Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to:

Class I organic peroxides. Class 3 non-detonatable unstable (reactive) materials. Pyrophoric gases. Flammable or oxidizing gases.

closed containers pressurized at more than 1 Spsi gauge. Exception: aerosols. Class 3 oxidizers.

e Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in

+ Class 3 water-reactive materiais.

3-51

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 72: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

H-3 Buildings with quantity of materials in excess of building code limitations, which present high fire or physical hazard, including but not limited to: +a Class II, III, or IV organic peroxides. +a Class 1 or 2 oxidizers. +a Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed

+a Class III-B combustible liquids. +a Pyrophoric liquids or solids. ta Class 1 or 2 water-reactive materials. +a Flammable solids in storage. +a Flammable or oxidizing cryogenic fluids (other than inert). ta Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

containers or systems and containers pressurized at 15 psi gauge or less, and aerosols.

H-4 Repair garages not classified as Group S-3.

H-5 Aircraft repair hangars and heliports not classified as Group S-5.

H-6 Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

H-7 Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to: + Corrosives, except stationary lead-acid battery systems. +a Highly toxic materials. +Irritants. 3 Sensitizers. +a Other health hazards.

GROW I - INSTlTUTIONAL

Sub-classiSr in divisions as follows:

1-1.1 Nurseries for fill-time care of children under the age of six, hospitals, sanitariums, nursing homes with non-ambulatory patients, and similar buildings, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

3-52

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 73: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

1-1.2 Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

1-2 Nursing homes for ambulatory patients, homes for children six years old or over, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

1-3 Mental hospitals, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates are similarly restrained, except buildings used only for private residential purposes for family group.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL

Sub-classify in divisions as follows:

R-1 Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

R-2 Classification not used.

R-3 Dwellings, lodging houses, and congregate residences, each accommodating ten persons or less.

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

S-1 Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

S-2 Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

S-3 Repair garages and parking garages not classified as S-4.

S-4 Open parking garages.

S-5 Aircraft hangars and helistops.

3-53

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 74: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP U - UTILITY

Sub-classify in divisions as follows:

U1

U 2

Private garages, carports, sheds and agricultural buildings.

Fences over six feet high, tanks and towers.

3-54

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 75: NEMA GUIDE CODE Fire Alarm & Detection System

1997 UNIFORM CODES (ICBO) Fire AlarmíDetection Systems

Group E - Educational

Group F- Factory Industrial

Group H - Hazardous H-1 - Flammables/

H-2 - Moderate

H-3 - HighHazard H-4 - Repair Garages H d - Semiconductor Facilities

~ H-7 - Health Hazards

Explosives

Explosion Hazard

Occupancy Type Automatic Fire

Sprinkler Systems

Required Required Required

Group A - Assembly Amusement Buildings Group B - Business

Fire Alarm Systems

Required Required Required

> 3 stories

Required

> 3 stories > 3 stories

Required 50 occupants

Required

Required

Required Required

Required Required > 3,000 sq. ft. Required Required

Required

Required

Required

Required

__ Automatic

Detection Systems

Required Required

Required

Required

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group M - Mercantile

Group R - Residential R-1 - HoteVMultifamily

Group S - Storage

Required Required Required

Required Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. ft. total

High-rise -New and Existing Construction B-2 - Offices R-1 - Hotelhíultifamily

Covered Maus

Aviation Control Towers

> 75 ft. > 75 ft.

> 75 ft. > 75 ft.

3-55

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 76: NEMA GUIDE CODE Fire Alarm & Detection System

1997 UNIFORM CODES (ICBO) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

GROUP B - BUSINESS

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area. G Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A-4. Multi-theater complexes.

ta Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. G All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages. ta Smoke-protected assembly seating, except press boxes, storage less than 1,000 square feet, or in conjunction with outdoor seating.

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is 1,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems. In areas where ambient conditions will cause smoke detector to alam, an approved alternate type of automatic detector may be substituted.

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

3-56

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 77: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code)

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Section 1007.3.4 (Building Code) and Section 1007.2.4.2 (Fire Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide automatic fire sprinkler system throughout all Group E.1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two- hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2 ) When enclosures forming interior rooms are less than two -thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTFUAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire -sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

3-57

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 78: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Section 307.11 (Building Code)

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

GROUP I - INSTITUTIONAL

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Provide approved manual and automatic fire alarm system in all Group I Occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups I-1.1,I-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

3-58

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 79: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and 1-2.

Appendix Chapter 3, Division 1 (Building Code) alarm system.

Alternative provisions for Group 1-3 housing with more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and Section 1003.2.8 than three stories. (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer's instructions and receiving primary power from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in a high- rise building provide a fire alarrdcommunication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Building with approved supervised fire sprinkler system throughout and with local alarm system.

3-59

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 80: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick-response standard sprinklers in dwelling units and guest rooms.

Section 1007.2.9.1.3 & .4 (Fire Code)

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES

Section 403.2 (Building Code)

Provide approved automatic sprinkler system; smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction.

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Provide fire alarm, emergency voice/alarm signaling system and f i e department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Buildings with atriums: Provide smokecontrol system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Section 1007.2.12.4 and Article 81 (Fire Code)

Provide automatic firedetection system throughout high-piled combustible storage uses as required by Article 81. Provide approved automatic fire sprinkler system when required by Table 81-A.

3-60

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 81: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE, NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES (continued)

Section 1007.2.12.5 (Fire Code)

Provide automatic smoke -detection system throughout building when special egress- control devices are installed on exit doors.

Section 1007.2.12.6 (Fire Code)

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

Section 1007.2.12.7 (Fire Code)

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Section 1007.2.12.8 (Fire Code)

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smoke-control system.

Section 1007.2.12.9 (Fire Code)

Provide manual fire alarm system in lumber, plywood, and veneer mills.

HIGHRISE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix Chapter 34 Division II (Building Code) and Appendix 1-B (Fire Code)

Provide approved automatic sprinkler system in Type II-N, III-N, or V-N construction in all required corridors, stairwells, elevator lobbies, public assembly areas for 100 or more persons, and commercial kitchens.

Provide fire department communication system and occupant voice notification system.

Provide approved manual fire alarm system connected to approved central, proprietary or remote station service, or a system, which will provide an audible signal at a constantly attended location.

Provide single station smoke detectors in dwelling units and guest rooms, which may be battery powered.

3-61

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 82: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Appendix Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACíLITES (GROUP R DIVISION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

3-62

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 83: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER G E N E U REOUIREMENTS (continuecl)

Appendix Chapter 34 Division 1, detection. Section 3408 (Building Code) and Appendix 1-A (Fire Code)

Protect openings into interior shafts in existing buildings, other than high-rise buildings, by self-closing one-hour fire assemblies or by automatic closing by smoke

Appendix Chapter 34 Division 1, Section 3409 (Building Code) and Appendix 1-A (Fire Code)

Appendix Chapter 34 Division 1, Section 3411 (Building Code) and Appendix 1 -A (Fire Code)

Section 713 (Building Code)

Section 3003.2 (Building Code)

Provide approved automatic sprinkler system in basements of existing buildings, other than high-rise buildings, with more than 1,500 square feet in area and meeting other criteria as established in the 1997 UBC and 1997 UFC.

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging house guest rooms used for sleeping purposes in existing other than high-rise buildings. Install smoke detectors to receive primary power source from building wiring if from commercial source or by battery power.

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

3-63

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 84: NEMA GUIDE CODE Fire Alarm & Detection System

1994 UNIFORM CODES (ICBO) Fire AlarmDetection Systems

Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business

Automatic Fire Sprinkler Systems

Required Required Required

Fire Alarm Systems

Required Required Required

I Required II Group F - Factory Industrial

Automatic Detection Systems

Required Required

Group H - Hazardous H-1 - Flammables/

H-2 - Moderate

H-3 - HighHazard H-4 - Repair Garages H d - Semiconductor Facilities H-7 - Health Hazards

Explosives

Explosion Hazard

Group E - Educational

Required

Required Required > 3,000 sq. ft. Required Required

Required

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

> 3 stories

Required Required Required

> 3 stories

Group M - Mercantile

Group R - Residential R-1 - HoteVMultifamily Il

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. fi. total

> 3 stories

Group S - Storage

High-rise - New and Existing Construction B-2 - Offices R-1 - HoteVMultifamily

Covered Malls

Required

> 75 ft. > 75 ft.

Required

Aviation Control Towers

> 75 ft. > 75 ft.

Required

Required

~

> 75 fi. > 75 ft.

Required

Required

I Required > 50 occupants

Required

Required Required

Required Required Required

Required Required Required

3-64

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 85: NEMA GUIDE CODE Fire Alarm & Detection System

1994 UNIFORM CODES (ICBO) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code)

Provide automatic sprinkler systems in Group A as follows:

when used for consumption of alcoholic beverages. Rooms and un-separated accessory uses more than 5,000 square feet in total area

Basements more than 1,500 square feet in floor area. Exhibition and display rooms more than 12,000 square feet

ta Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A-4. Multi-theater complexes. Amusement buildings, except if temporary with floor area less than 1,000 square

All stages more than 1,000 square feet in area and 50 feet in height, dressing feet and exit travel distance is less than 50 feet from any point.

rooms, workshops, storerooms, and other accessory spaces adjoining such stages.

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system, which activates prerecorded announcement using an approved electrically supervised voice communication or public address system. Exception: Occupancies with automatic fire-extinguishing system installed to activate prerecorded message.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUP E - EDUCATIONAL

Section 305.2.2 (Building Code)

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

3-65

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 86: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code)

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Section 1017.4 (Building Code)

Provide approved fire alarm system when the occupant load is more than 50 persons. When automatic sprinkler or smoke detectors provided, install to automatically activate fire a i m .

Provide automatic fire extinguishing system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Ekeption also allowed when area separation walls or occupancy separation has two- hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) Mihen enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1,5102.3, and Article 80 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Section 307.11 (Building Code)

Provide approved manual alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

3-66

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 87: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

GROUP I - I N S m O N A L

Section 308.9 (Building Code) and Section 1007.1.7 (Fire Code)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Appendix Chapter 3, Division 1 (Building Code)

GROUP M - MERCANTILE

Provide approved manual and automatic fire alarm system in all Group I Occupancies.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups I-1.1,I-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke -detection system throughout resident housing areas.

Provide automatic fire extinguishing system throughout.

Alternative provisions for Group 1-3 housing more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire alarm system.

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Provide automatic sprinkler system in retail stores if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

3-67

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 88: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code)

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Section 904.2.8 (Building Codej and Section 1003.2.8 (Fire Code)

Section 1007.2.9.1.3 (Fire Code)

Provide smoke detectors in dwelling units, congregated residences, and hotel or lodging houseguest rooms installed per manufacturer's instructions.

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings; provide a fire aladcommunication system. Exceptions: i) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2 ) Building with automatic sprinkler system throughout and with local alarm system.

Provide automatic sprinkler system in apartment houses three or more stories or containing more than i 5 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more.

In Group R-1, provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

3-68

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 89: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 403.2 (Building Code)

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 402.2 (Bugding Code) and Section 1007.2.12.3 (Fire Code)

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning retum-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voiceíalarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic smoke detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 8 1 -A.

Provide automatic smoke-detection system throughout building when special egress- control devices are installed on exit doors.

In corridors, which are not of fire-resistive construction located in office spaces with less than 100 occupants, provide smoke detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

3-69

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 90: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES {continued)

Section 1007.2.12.8 (Fire Code)

Provide approved automatic smoke -detection system when required by the Building Code for automatic control of a smoke-control system.

HIGHRISE, GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRU-S

Appendix Chapter 34 Division II (Building Code)

Provide approved automatic sprinkler system in Type II-N, III-N, or V-N construction and areas occupied by 100 or more persons and commercial kitchens. Provide fire department communication system and occupant voice notification system. Provide manual fire alarm system except may be waived when approved automatic sprinkler system installed throughout building. Provide single station smoke detectors in dwelling units and guest rooms. Provide automatic elevator recall system except may be waived when approved automatic sprinkler system installed throughout building.

Appendix 1-B (Fire Code)

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, and public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide approved manual fire alarm system connected to approved central, proprietary or remote station service, or a system, which will provide an audible signal at a constantly attended location. Provide single-station smoke detectors in dwelling units and guest rooms.

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

3-70

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 91: NEMA GUIDE CODE Fire Alarm & Detection System

AVIATION CONTROL TOWERS

Appendix Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROW CARE FACIJATIES (GROUP R. DMSION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1994 UBC; at top of rubbish andlinen chutes and their terminal rooms, in rooms where nitrate film is stored or handled; or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

Appendix Chapter 34 Division 1, Section 3408 (Building Code) and Appendix 1 -A (Fire Code)

Protect openings'into interior shafts in existing buildings other than Group R-3, M, and high-rise buildings by self-closing one-hour fire assemblies or by automatic closing by smoke detection.

3-71

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 92: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REOUIREMENTS ícontinued)

Appendix Chapter 34 Division 1, Section 3409 (Building Code) and Appendix 1 -A (Fire Code)

Provide approved automatic sprinkler system in basements of existing buildings other than Group R-3, M, and high-rise buildings with more than 1,500 square feet in area and meeting other criteria as established in the 1994 UBC and 1994 UFC.

Appendix Chapter 34 Division 1, Section 3411 (Building Code) and Appendix 1 -A (Fire Code)

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging-house guest rooms used for sleeping purposes in existing buildings of existing buildings.

Section 713 (Building Code)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper as required by the 1994 UBC.

3-72

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 93: NEMA GUIDE CODE Fire Alarm & Detection System

1991 UNIFOIUM CODES (ICBO) Fire AlarmlDetection Systems

Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business B-2 - RetaiiíDrinking

Group E - Educational

Group H - Hazardous H-1 - Flammables/

Explosives 8 2 - Moderate

Explosion Hazard H-3 - HighHazard H-4 - Repair Garages 1 H-ó - Semiconductor Facilities

I H-7 - HealthHazards

Group I- Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group R - Residential R-1 - HoteVMultifamily

Highrise -New and Existing Construction B-2 - Offices R-1 - HoteiíMultifamily

Covered Malis

Automatic Fire Sprinkler Systems

Required Required

Required

Required ~

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Fire Alarm Systems

Required Required

Required

> 50 occupants

Required

Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Required

Automatic Detection Systems

Required

Required

Required

Required

Required Required Required

> 3 stories

Required

Required

3-73

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 94: NEMA GUIDE CODE Fire Alarm & Detection System

1991 UNIFORM CODES (ICBO) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 3802 (Building Code) and Section 10.507(c) (Fire Code)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area. ta Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A-4. Multi-theater complexes.

ta Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. ta Under roof and gridiron, tie and fly galleries, proscenium walls of stages, piatforms more than 500 square feet, dressing rooms, workshops, and storerooms.

Section 609 (Building Code)

Section 14.104(b) (Fire Code)

Section 610 (Building Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system, which activates prerecorded announcement using an approved electrically supervised voice communication or public address system. Exception: Occupancies with automatic he-extinguishing system installed to activate prerecorded message.

In amusement buildings, provide approved automatic sprinkler, smoke detection, and supervised alarm and/or public address systems.

GROUP B - BUSINESS

Section 3802(d) (Building Code) and more than three stories. Section 10.507(d) (Fire Code)

Provide automatic fire extinguishing system in Group B-2 retail sales areas where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or when

Section 14.104(c)(l) (Fire Code)

Provide fire alarm systems in Group B-2 occupancies as set forth in the following subsections of this code.

3-74

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 95: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP B - BUSINESS (continued)

Section 14.104(~)(2) and Article 81 (Fire Code)

Provide automatic smoke -detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire-extinguishing system when required by Table 81.105-A.

Section 14.104(~)(3) (Fire Code)

Provide automatic smoke-detection system throughout building when special egress- control devices are installed on exit doors.

Section 14.104(~)(4) (Fire Code)

Provide automatic smoke-detection system in corridors, which are not of one hour fire- resistive construction located in office spaces with less than 100 occupants.

Section 14.104(~)(5) (Fire Code)

Provide fire alarm and communication systems in high-rise office occupancies.

Section 14.104(~)(6) (Fire Code)

Provide approved manual alarm system when required by, Article 88 of this code for aerosol storage rooms and general purpose warehouses containing aerosols.

See also specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUP E - EDUCATIONAL

Section 809 (Building Code) and Section 14.104(d) (Fire Code)

Provide an approved fire alarm system when the occupant load is more than 50 persons. When automatic sprinkler system or smoke detectors provided, install to automatically activate school fire alarm.

Section 802(b) (Building Code)

Section 3802(e) (Building Code) and Section 10.507(e) (Fire Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Provide automatic sprinkler system in basements more than 1,500 square feet in floor area and in enclosed usable space below or over a stairway.

3-75

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 96: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 3318(d) (Building Code)

Provide smoke detectors throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP H - HAZARDOUS

Section 909 (Building Code) Sections 14.104(e), 50.113, Article 51 and Article üU (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Section 911 (Building Code)

Provide alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

Section 3802(f) (Building Code) and Section 10.507(î) area. (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor

GROUP I - INSTITUTIONAL

Section 1002(b) (Building Code)

Provide smoke detector operated damper(s) at each point where ducts penetrate smoke barrier except where openings in ducts are limited to single smoke compartment and ducts are of steel construction.

Section 1009 (Building Code) and Section 14.104(f) (Fire Code)

Provide manual and automatic fire alarm system in Group I occupancies.

3-76

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 97: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1010 (Building Code) and Section 14.104(f)(5) (Fire Code) required alerting functions.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs

Section 3802(g) (Building Code) and Section 10.507(g) (Fire Code)

Provide automatic fire extinguishing system throughout.

Section 14.104(f)(3) (Fire Code)

Provide smoke detectors at automatic closing doors in smoke barriers and in ducts penetrating smoke barriers and in waiting areas, which are open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

GROUP R - RESIDENTIAL

Section 1210 (Building Code) and Section 14.104(g)(6 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging- house guest rooms installed per manufacturer's instructions.

Section 1211 (Building Code) and Section 14.104(g) (Fire Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings; provide a fire alarm/communication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Buildings with automatic sprinkler system throughout and with local alarm system.

3-77

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 98: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 14.104(g) (Fire Code)

In Group R-1 occupancies, provide: Manual fire alarm boxes.

Smoke detectors in all common areas and interior corridors serving as required exit

Heat detectors in common areas such as recreational rooms, laundry rooms, furnace for ten or more occupants.

rooms, and similar areas. t3 Install alarm-initiating devices to activate an alarm signal audible throughout designated portions of building.

Section 3802(h) (Building Code) and Section 10.507(h) (Fire Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more.

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 1807 (Building Code)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems when buildings have floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Section 14.104(g) (Fire Code)

Provide fire alarm and communication systems for Group B-2 offices and Group R-1 occupancies with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

HIGHRISE. GROUP B-2 OFFICES ANI) GROUP R-1 OCCWl'ANCIES. EXISTING STRUCTURES

Appendix Chapter 1 Division II (Building Code)

Provide automatic sprinkler system in Type II-N, III-N, or V-N construction and areas occupied by 100 or more persons. Provide fire department communication system and occupant voice notification system. Provide manual fire alarm system except may be waived when approved automatic sprinkler system installed throughout building. Provide single station smoke detectors in dwelling units and guest rooms, and automatic elevator recall.

3-78

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 99: NEMA GUIDE CODE Fire Alarm & Detection System

HIGJBUSE. GROUP B-2 OFFICES AND GROW R-1 OCCUPANCIES. EXISTING STRUCTURES {continued)

Appendix 1 -B (Fire Code)

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide approved manual fire alarm system connected to central, proprietary or remote station service, or a system, which will provide an audible signal at a constantly attended location. Provide fire department communication system and occupant voice notification system. Provide single-station smoke detectors in dwelling units and guest rooms.

COVERED MALLS

Section 5603 (Building Code)

ATRIA

Section 1716(b) (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system.

Provide smoke control system that operates automatically upon actuation of automatic sprinkler system within atrium and areas open to atrium. Provide smoke detectors that will automatically operate atrium smoke-control system.

AVIATION CONTROL TOWERS

Appendix Chapter 7 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES (GROW R DMSION 4)

Appendix Chapter 12 Division II, Section 1232 (Building Code)

Provide approved automatic or manual alarm system.

3-79

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 100: NEMA GUIDE CODE Fire Alarm & Detection System

Section 3802(a) (Building Code) and Section 10.507(f) (Fire Code)

Except in Group R-3 and M occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 3802 of 199 1 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults.

Appendix Chapter 1 Division 1 smoke detection. Section 112 (Building Code)

Protect openings into interior shafts in existing buildings other than Group R-3, M, and high-rise buildings by self-closing one-hour fire assemblies or by automatic closing by

Appendix Chapter 1 Division 1 Section 115 (Building Code)

Section 4306(f) (Building Code)

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging-house guest rooms used for sleeping purposes in existing buildings.

Provide smoke detectors to activate closing device of an automatic closing fire assembly.

3-80

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 101: NEMA GUIDE CODE Fire Alarm & Detection System

MODEL CODE ORGANIZATION

ORGANIZATION: Southern Building Code Congress International (SBCCI)

ADDRESS: 900 Montclair Road Bimi ingh~~~~, AL 35213-1206 (205) 591-1853

KEY STAFF:

PURPOSE:

Chief Executive Officer, William Tangye, PE Vice President of Technical Services, John Battles, PE, CBO Director of Examination Services, Bruce Burdette, PE Director of Publications, Karla Price Higgs

Founded in 1940 to provide forum for governments, design professionals, universities, and industry to democratically promulgate and maintain a set of model regulatory construction codes. Encourages uniformity in building regulations through the Standard codes and their application and enforcement.

PUBLICATIONS: Standard Amusement Device Code Standard Building Code Standard Excavation and Grading Code Standard Fire Prevention Code Standard Gas Code Standard Housing Code Standard Plumbing Code Standard Swimming Pool Code Standard Unsafe Building Abatement Code Southern Building Magazine International Codes

SERVICES: Certification programs Education and training Technical code services Administrative code support Product evaluation

AREAS OF INFLUENCE:

The Southeastern United States including areas of Florida, Alabama, Georgia, Tennessee, South Carolina, Louisiana, Mississippi, Texas, and North Carolina.

CODE REVISION PROCESS:

The Standard codes are revised and updated annually with new editions published every third year. Changes are made by a democratic process; with submittals for changes due March 1 and the changes approved based on letter ballot in December and January.

3-81

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 102: NEMA GUIDE CODE Fire Alarm & Detection System

1997 SBCCI USE GROUP CLASSIFICATIONS

GROUP A - ASSEMBLY BUILDINGS

Buildings or portions thereof used for civic, social or religious functions, for recreation, for food or drink consumption, or for awaiting transportation. Sub-classify as follows:

A-1 :

A-2:

Large Assembly. Theaters and other places of assembly without a stage with capacity of 1,000 or more persons and theaters and assembly places with working stage having capacity of 700 or more persons. Small assembly. Theaters and other places of assembly with or without working stage requiring proscenium opening protection with capacity of 100 or more persons but having a capacity less than large assembly.

GROUP B - BUSINESS

Buildings or portions thereof used for office, professional or service-type transactions including normal accessory storage and keeping of records and accounts. These include:

Office Buildings Service Stations Bowling Alleys Educational occupancies above 12th grade

Greenhouses Banks Libraries (other than school) Radio and television stations

GROUP E - EDUCATIONAL

Buildings or space used by six or more persons at any one time for educational purposes through 12th grade. Child- care facilities accommodating six or more children of any age who stay less than 24 hours per day.

GROUP F - FACTORYLNDUSTRIAL

Building or space used for assembly, repairing, fabricating, finishing, manufacturing, and packaging, or for processing operations not otherwise classified in Building Code. Group F includes:

Manufacturing Plant Processing Plant Assembly Plant

Factory Mill

3-82

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 103: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORYíINDUSTRIAL (continued)

Group F does not include buildings principally involving highly combustible, inflammable, or explosive products or materials.

GROUP H - HAZARDOUS

A building or space whose principal use involves the manufacturing, processing, generation, storage, or other use of hazardous materials in excess of quantities exempt by this code. Subdivide as follows:

Hi:

H2:

H3:

H4:

Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which present a detonation hazard. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which present a deflagration hazard or a hazard from accelerated burning. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which readily support combustion or present a physical hazard. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which are health hazards.

GROUP I - INSTITUTIONAL

Group I buildings are sub-classified into two categories:

Group I restrained: Buildings or portions thereof used to provide sleeping facilities for six or more persons under some degree of restraint or security, such as jail, detention center, correctional institution, and reformatory.

Group I unrestrained: Buildings or portions thereof used for medical, surgical, psychiatric, nursing, or custodial care on a 24-hour basis of six or more persons who are not capable of self-preservation and shall include among others: Hospitals, nursing homes (both intermediate care facilities and skilled nursing facilities), mental hospitals and detoxification facilities.

GROUP M - MERCANTILE

Buildings or portions thereof used for display and sale of merchandise including stocks of goods, wares or merchandise incidental to such purposes and accessible to the public.

3-83

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 104: NEMA GUIDE CODE Fire Alarm & Detection System

Buildings or portions thereof used for sleeping accommodations when not classed as Group I. follows:

Subdivide as

R1:

R2:

R3:

R4:

Residential occupancies where the occupants are primarily transient in nature (less than 30 days) including: hotels, motels, boarding housing (transient). Multiple dwellings where the occupants are primarily permanent in nature, including: apartment houses, boarding houses (not transient), convents, fraternities and sororities, monasteries, rectories, dormitory facilities which accommodate six or more persons of more than two and one-half years of age who stay more than 24 hours.. One and two family dwellings where the occupants are primarily permanent in nature and not classified as R1, R2, or I. Child-care facilities, which accommodate five or less children of any age for any time period, shall be classified as Group R3. Residential care/assisted living facilities housing six or more occupants on a 24-hour basis including: congregate care facilities, assisted living facilities, group homes.

GROUP S - STORAGE

Buildings or portions thereof used for storage not classed as Group H, or for sheltering animals. Subdivide as follows:

S1:Moderate Hazard Storage shall include buildings used for the storage of combustible materials when not classified as S2 Low Hazard or Group H.

S2:Low Hazard Storage shall include buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings. Such products may have a negligible amount of plastic trim such as knobs, handles, or film wrapping. S2 Low Hazard Storage shall include but not be limited to the following:

Metal desks with plastic tops and trim Electric coils Electrical motors Dry cell batteries Metal parts Empty cans Stoves Washers and dryers Metal cabinets Glass bottles; empty or filled with

Mirrors Foods in noncombustible containers Frozen foods

non-combustible liquids

Meats Fresh fruit and vegetables in non-plastic

Dairy products in non-waxed coated

Beer or wine up to 12% alcohol in

Oil filled and other types of

Cement in bags

Gypsum board Inert Pigments Dry insecticides

trays or containers

paper containers

metal, glass or ceramic containers

distribution transformers

Electrical insulators

3-84

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 105: NEMA GUIDE CODE Fire Alarm & Detection System

1997 STANDARD CODES (SBCCI) Fire Alarfletection Systems

i

Group B -Business

Group F - Factory/Industrial i

Group M - Mercantile

Group R - Residential

oup S - Storage

Atriums

Covered Maiis

High-rise Buildings Group B Group R Special Amusement Buildings

Automatic Fire Snrinkler Svstems

Required

Required

Required

Required

Required

Required

> 15,000 sq. ft.

> 3 stories

'Required

Required

Required

> 75 ft. > 75 ft. Required

Fire Alarm Svstems

Manual when > 1,000 persons Required

Required

Manual when > 2 stories or > 500 persons Required

Required

Manual when > 500 persons

Required

Required

Required

> 75 ft. > 75 ft.

Automatic Detection Svstems

Required

Required

Required

Required - residential hangars Required

Required

> 75 ft. > 75 ft. Required

3-85

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 106: NEMA GUIDE CODE Fire Alarm & Detection System

Underground Buildings

1997 STANDARD CODES (SBCCI) Requirements and Exceptions

Required Required Required

GROUP A - ASSEMBLY

Section 903.7.2 (Building Code)

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Section 3102 (Fire Code)

GROUP B - BUSINESS

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide approved automatic sprinkler system in Group A-1 occupancies in areas over 15,000 square feet used for display, sale, or storage of combustible materials. Also provide throughout stages and in dressing rooms, workshops, storerooms and other accessory spaces contiguous to stage, and sound stages for motion picture or television productions over 1,000 square feet in area.

Provide manual alarm system in Group A occupancies with 1,000 or mo re persons. May omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

Provide approved automatic sprinkler system in all enclosed areas of assembly occupancy permanent, temporary or portable seating facilities. Exception: If floor area used for entertainment is restricted to low fire hazard use and roof is more than 50 feet above floor level, or if press boxes and storage facilities less than 1,000 square feet open to the outside.

Provide manual fire alarm system in Group B occupancies with 500 or more persons or more than 100 persons located above or below street floor. May omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the f i e alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

GROUP E - EDUCATIONAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manuai fire alarm system throughout Group E occupancies. May omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

GROUP F - FACTORY/INDUSTRIAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual fire alarm system in Group F two or more stories or having total capacity of 500 or more persons above or below street floor level. May omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

3-86

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 107: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS

Section 407.1.3 (Building Code) and Chapter 22 (Fire Code)

Section 407.2.5 (Building Code) and Chapter 22 (Fire Code)

Provide approved automatic sprinkler system throughout Group H indoor storage areas, storage buildings and areas or rooms in which hazardous materials are dispensed or used. Provide internal sprinklers in gas cabinets and exhausted enclosures for the storage of cylinders of highly toxic and toxic compressed gas and provide automatic sprinkler system for roof structures provided for the storage of highly toxic or toxic compressed gases.

Provide a local manual fire alarm box or approved emergency signal device outside of each interior egress door to a storage room. Also provide an approved supervised smoke detection system in rooms or areas where highly toxic compressed gases, liquid or solid oxidizers or unclassified detonatable, Class I or Class II organic peroxides are stored, and where Class III or Class IV organic peroxides are stored in quantities exceeding exempt amounts specified by this code. Activation of detection system shall sound a local alarm. Exception: Detached storage buildings with an automatic fire extinguishing system. Provide supervision by an approved central, proprietary or remote station service of fire detection or extinguishing systems.

Section 903.7.4 8 z 903.8.2 (Building Code) tamper switches.

Provide approved supervised automatic sprinkler system throughout Group H Hazardous Production Material (HPM) facilities. Provide all valves with supervisory

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual fue alarm system throughout Group H except may omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

3-87

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 108: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

Section 3102 (Fire Code)

Provide approved automatic sprinkler system in all enclosed areas of assembly occupancy permanent, temporary or portable seating facilities. Exception: If floor area used for entertainment is restricted to low fire hazard use and roof is more than 50 feet above floor level, or if press boxes and storage facilities less than 1,000 square feet open to the outside.

Section 1303.2 (Fire Code) organic coatings.

Provide approved fire alarm system in all Group H buildings used for manufacture of

Section 3605 (Fire Code)

Provide automatic fire extinguishing system and smoke detection system where Class I-V materials stored in quantities per Fire Code.

GROUP I - INSTITUTIONAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual fire alarm system throughout Group I occupancies.

Grouu I Unrestrained OccuDancv:

Section 409.1.1.1 (Building Code)

Provide with an approved automatic sprinkler system. Protect smoke compartments containing patient rooms with quick response sprinklers. Standard sprinklers may be used if patient room is equipped with smoke detectors permanently connected to house current.

Section 409.1.2.5 (Building Code) barriers.

Provide smoke detectors to activate automatic closing devices on doors in smoke

Section 409.1.6 (Building Code)

Provide supervised fire alarm system, which is activated by manual fire alarm boxes, by sprinkler activation, and by smoke detection.

Grouu I Restrained Occuuancv:

Section 409.2.10 (Building Code)

Provide manual and automatic fire alarm system per NFPA 7 2 .

Section 409.2.12 (Building Code)

Provide approved automatic fire detection system with smoke detectors per NFPA 7 2 throughout all resident housing areas, including common spaces, except in sleeping rooms with four or less occupants in a building protected throughout with an approved automatic sprinkler system.

3-88

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 109: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - KNSIITIZTTIONAL (continued)

Section 409.2.13 (Building Code)

Provide an electrically supervised approved automatic sprinkler system per NFPA 13 when required by Table 500 of this code.

Section 409.2.14.6 (Building Code) barriers.

Provide smoke detectors to activate automatic closing devices on doors in smoke

Section 409.2.17.4 (Building Code)

Provide automatic extinguishing protection per NFPA 13 in any trash chute or linen chute, including pneumatic rubbish and linen systems.

GROUP M - MERCANTILE

Section 903.7.1 (Building Code)

Provide approved supervised automatic sprinkler systems in Group M occupancies where combustible storage and story floor area exceeds 15,000 square feet.

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual fire alarm system when total occupancy is 500 or more persons or more than 1 O0 persons located above or below street floor. May omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

GROUP R - RESIDENTIAL

Section 903.7.5 (Building Code)

Provide approved supervised automatic sprinkler system throughout Group RI occupancies three or more stories except when exterior exitway stairs are provided for the guest rooms.

Section 903.7.6 (Building Code)

Provide approved supervised automatic sprinkler system throughout Group R2 occupancies three or more stories except when not required by other provisions of this code or when exterior exitway stairs are provided.

Section 903.7.7 (Building Code)

Provide approved supervised automatic sprinkler system throughout Group R4 occupancies. Install quick-response or residential sprinklers per NFPA 13.

3-89

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 110: NEMA GUIDE CODE Fire Alarm & Detection System

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Section 905.2 (Building Code)

Section 410.2.2 (Building Code)

Section 603.6 (Fire Code)

GROUP S - STORAGE

Section 411.7.7 (Building Code)

Section 411.7.8.5 (Building Code)

Provide manual fire alarm system in R1 occupancies having accommodations for more than 15 guests; R2 occupancies having four or more stories, and dormitories or rooming houses with more than 15 sleeping accommodations; and R4 occupancies. Exception allowed if guest rooms in Group R1, dormitories and rooming houses have a direct exit to outside and building is three stories or less. Also may omit manual fire alarm system when building equipped throughout with automatic fire detection or automatic sprinkler system, which will activate the fire alarm system. Also a centrally located station must be provided to manually activate fire alarm system.

Provide approved single -station or multiple -station smoke detector in every dwelling, dwelling unit in apartment house, condominium or townhouse, and every guest or sleeping room in motel, hotel, or dormitory. Install per NFPA 72. Smoke detectors connected to a fire alarm system should be installed per NFPA 72. Smoke detectors in dwelling, dwelling units, and sleeping room in residential careíassisted living occupancies should be hardwired into building’s electrical power source and equipped with monitored battery backup in all new construction. Monitored battery power is permitted in existing construction.

In residential care/assisted living facilities provide smoke detectors to activate automatic closing devices on doors in hazardous areas.

Provide approved smoke detector in every new and existing dwelling, including one- and two-family dwellings, dwelling unit within an apartment house, condominium, or townhouse, and every guest or sleeping room in a motel, hotel, or dormitory. Install per NFPA 72.

Provide aircraft hangars with fire suppression as required by NFPA 409.

Provide at least one approved smoke detector within a residential aircraft hangar which is hardwired into the residential smoke alarm or other sounding device to be audible in all sleeping areas of the dwelling.

3-90

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 111: NEMA GUIDE CODE Fire Alarm & Detection System

Section 414.3 & .6 (Building Code)

Provide approved automatic sprinkler system, smoke control system, and smoke detection throughout. Install smoke detectors to activate atrium smoke removal system and sound alarm at a constantly supervised station.

COVERED MALLS

Section 413.4.5.2 (Building Code)

Provide smoke detectors to activate automatic closing devices on doors.

Section 413.8 (Building Code)

Provide automatic fire sprinkler system throughout.

Section 413.10 (Building Code)

Provide smoke detectors within return air portion of air conditioning system to shut down air supply to the zone where fire occurs.

HAZARDOUS PRODUCïïON MATERIAL O FACILITIES

Section 408.1.2 (Building Code)

Provide approved automatic sprinkler system throughout all buildings containing HPM facilities, such as semiconductor fabrication and areas of comparable research and development.

Section 408.3.6.3 (Building Code)

Provide smoke detectors in the re-circulating air stream of ventilation system. Install to initiate a signal at the emergency control station.

Section 408.6.6 (Building Code)

Provide an emergency telephone system or local manual alarm pull station outside of each interior egress door from W M cutoff rooms.

HIGHRISE BUILDINGS, GROUPS B AND R

Section 412.1.1 (Building Code)

Provide an approved automatic sprinkler system or areas of refuge (compartmentation) in all Group B buildings having floor surfaces used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access. Group B buildings more than 12 stories or 150 feet high must be provided with approved automatic sprinkler system.

Provide approved automatic sprinkler system in all Group R buildings having floor surfaces used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access.

3-91

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 112: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS, GROUPS B AND R (continued)

Section 412.2 (Building Code)

Provide at least one smoke detector in every room for mechanical equipment, electrical, transformer, telephone equipment, and elevator machine; in every elevator lobby; in re- circulating air systems serving more than one story; in each connection to a return air vertical duct or riser serving a re-circulating air system of more than one story. Exception: In Group R occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5,000 cfm and serving not more than ten air inlet openings. See Group R for other requirements for smoke detectors. Install detectors to operate voice alarm system and equipment to prevent the re-circulation of smoke. A one-way voice alarm system, and two-way fire department communication system shall be provided.

Section 412.9 (Building Code) alarm system.

If area of refuge provided in lieu of automatic sprinkler system, provide a manual fire

SPECMI. AMLJSEMENT BUILDINGS

Section 403.5.3 (Building Code)

Provide an automatic fire detection system with smoke detectors. An approved alternate type of automatic fire detector may be installed in areas where the ambient conditions may cause a smoke detector to alarm. Install detection device to sound alarm at a constantly supervised station.

Section 403.5.4 & .5 (Building Code)

Provide an automatic sprinkler system throughout except when building is temporary with total floor area of 1,000 square feet or less and the exit travel distance from any point is 50 feet or less. Install automatic sprinkler system, single smoke detector, or any other automatic fire detection device to sound alarm at a constantly attended station.

UNDERGROUND BUILDJNGS

Section 415.1 (Building Code)

Applies to building spaces having a floor level used for human occupancy more than 30 feet or more than one story below the lowest level of exit discharge. Exceptions: Fixed guideway transit system, grandstands, parking garages with automatic fire suppression system, buildings which qualify but have an area not more than 1,500 square feet and have under ten occupants, and sprinkled one- and two-family dwellings.

Section 415.3 (Building Code)

Provide automatic fire sprinkler system in the highest level of exit discharge serving the underground portion of the building and all levels below.

3-92

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 113: NEMA GUIDE CODE Fire Alarm & Detection System

UNDERGROUND BUILDINGS (continued)

Section 415.4.2 (Building Code) compartments.

Provide smoke detectors to activate automatic closing devices on doors between

Section 415.5.2 (Building Code)

Provide at least one smoke detector in every room for mechanical equipment, electrical, transformer, telephone equipment, and elevator machine; in every elevator lobby; in the main return and exhaust air plenum of each air conditioning system serving more than one story; in each connection to a vertical duct or riser serving two or more stories from return air ducts or plenums of W A C system. Exception: In Group R occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5,000 cfm and serving not more than 10 air inlet openings. Smoke exhaust system must be activated by smoke detectors, automatic suppression system, and manual controls.

Section 415.6 (Building Code)

Provide fire alarm system throughout when the lowest level of building is more than 60 feet below the lowest level of exit discharge. Alarm to be activated by smoke detectors, automatic fire sprinkler system, and manual pull station.

OTHERGENERALBUILDINGAREAS

Section 903.5 (Building Code)

Provide approved automatic sprinkler system in the following: Basements more than 2,500 square feet used to manufacture, repair, sell or store

combustible material or when used as lounge or night club regardless of size. In buildings without suitable access per this code. Spray finishing booth, area or room. Enclosed parking garage more than 65 feet high and more than 10,000 square feet per

floor. Repair garages two or more stories high and more than 10,000 square feet in single

floor area. Single story repair garages more than 15,000 square feet Basement garages or repair garages in basement except R3 occupancies. Commercial truck storage garage more than 5,000 square feet Bus garages for four or more buses.

Section 903.7.3 (Building Code) and Chapter 36 (Fire Code)

Provide approved automatic sprinkler system with high-piled combustible stock as required by fire prevention code.

3-93

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 114: NEMA GUIDE CODE Fire Alarm & Detection System

1994 STANDARD CODES (SBCCI) Fire AlarndDetection Systems

II Occupancy Type I' Group A - Assembly

Automatic Fire Sprinkler Systems

Required

Group B -Business

Fire Alarm Systems

Manual when > 1,000 persons

II Group F - FactoryíIndustrial

Required

Required

> 75 ft. > 75 ft.

Group H - Hazardous

Group I- Institutional

Group M - Mercantile

Group R - Residential

Group S - Storage

Required

Required

> 75 ft. > 75 ft.

1) Atriums

Covered Maiis

High-rise Buildings Group B Group R Special Amusement Buildings

Required Required

stories or > 500

Required

> 15,000 sq. ft.

> 3 stories

Required

Manual when > 500 persons

Required

Required

Automatic Detection Systems

Required

Required

Required

Required - residential hangars Required

Required

75 ft. > 75 ft. Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 115: NEMA GUIDE CODE Fire Alarm & Detection System

Underground Buildings Required Required '

3-95

Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 116: NEMA GUIDE CODE Fire Alarm & Detection System

1994 STANDARD CODES (SBCCI) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 903.7.2 (Building Code)

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

GROUP B - BUSINESS

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide approved automatic sprinkler system in Group A-1 occupancies in areas over 15,000 square feet used for display, sale, or storage of combustible materials. Also provide throughout stages and in dressing rooms, workshops, storerooms and other accessory spaces contiguous to stage, and sound stages for motion picture or television productions over 1,000 square feet in area.

Provide manual alarm system in Group A occupancies with 1,000 or more persons. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic sprinkler system throughout.

Provide manual fire alarm system in Group B occupancies with 500 or more persons or more than 1 O0 persons located above or below street floor. May omit manual fire alarm when building equipped with automatic f r e alarm or automatic sprinkler system throughout.

GROUP E - EDUCATIONAL

Section 905.1 (Building Code) and Section 603.7 sprinkler system throughout. (Fire Code)

Provide manual fire alarm system throughout Group E occupancies. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic

GROUPF-FACTORY/INDUSTRIAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code) system throughout.

Provide manual fire alarm system in Group F two or more stories or having total capacity of 500 or more persons above or below street floor level. May omit manual fire alarm when building equipped with automatic fire alarm or automatic sprinkler

3-96

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 117: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Section 407.1.3 (Building Code) and Chapter 22 (Fire Code)

Section 407.2.5 (Building Code) and Chapter 22 (Fire Code)

Section 903.7.4 (Building Code)

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Section 1303.2 (Fire Code)

Section 3605 (Fire Code)

Provide approved automatic sprinkler system throughout Group H indoor storage areas, storage buildings and areas or rooms in which hazardous materials are dispensed or used. Provide internal sprinklers in gas cabinets and exhausted enclosures for the storage of cylinders of highly toxic and toxic compressed gas and provide automatic sprinkler system for roof structures provided for the storage of highly toxic or toxic compressed gases.

Install a local fire alarm manual pull station or approved emergency signal device outside of each interior egress door to a storage room. Also provide an approved supervised smoke detection system in rooms or areas where highly toxic compressed gases, liquid or solid oxidizers or unclassified detonatable, Class I or Class II organic peroxides are stored, and where Class III or Class IV organic peroxides are stored in quantities exceeding exempt amounts specified by this code. Activation of detection system shall sound a local alarm. Exception: Detached storage buildings with an automatic fire extinguishing system. Provide supervision by an approved central, proprietary or remote station service of fire detection or extinguishing systems.

Provide approved supervised automatic sprinkler system throughout Group H Hazardous Production Material (HPM) facilities.

Provide manual fire alarm system throughout Group H except may omit when building equipped with automatic fire alarm or automatic sprinkler system.

Provide approved fire alarm system in all Group H buildings used for manufacture of organic coatings.

Provide automatic fire extinguishing system and smoke detection system where Class I-V materials stored in quantities per Fire Code.

3-97

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 118: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual fire alarm system throughout Group I occupancies.

Grout, I Unrestrained OccuDancv:

Section 409.1.1.1 (Building Code)

Provide with an approved automatic sprinkler system. Protect patient rooms with quick response sprinklers. Standard sprinklers may be used if patient room is equipped with smoke detectors permanently connected to house current.

Section 409.1.2.5 (Building Code)

Provide smoke detectors to activate automatic closing devices on doors in smoke barriers and hazardous areas.

Section 409.1.6 (Building Code)

Provide electrically supervised fire alarm system, which is activated by manual pull stations, by sprinkler activation, and by smoke detection.

Grout, I Restrained OccuDancv:

Section 409.2.10 (Building Code)

Provide a manual and automatic fire alarm system per NFPA 72A.

Section 409.2.12 (Building Code)

Provide approved automatic fire detection system with smoke detectors per NFPA 72A and 72E throughout all resident housing areas, including common spaces, except in sleeping rooms with four or less occupants in a building protected throughout with an approved automatic sprinkler system.

Section 409.2.13 (Building Code)

Provide an electrically supervised approved automatic sprinkler system per NFPA 13 when required by Table 500 of this code.

Section 409.2.1 4.6 (Building Code) barriers.

Provide smoke detectors to activate automatic closing devices on doors in smoke

Section 409.2.17.4 (Building Code)

Provide automatic extinguishing protection per NFPA 13 in any trash chute or linen chute, including pneumatic rubbish and linen systems.

3-98

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 119: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP M - MERCANTILE

Section 903.7.1 (Building Code)

Provide supervised automatic sprinkler systems in Group M occupancies where combustible storage and story floor area exceeds 15,000 square feet

Section 905.1 (Building Code) and Section 603.7 (Fire Code) throughout.

Provide manual fire alarm system when total occupancy is 500 or more persons or more than 100 persons located above or below street floor. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic sprinkler system

GROUP R - RESIDENTIAL

Section 903.7.5 (Building Code)

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Section 905.2 (Building Code)

Section 603.6 (Fire Code)

GROUP S - STORAGE

Section 411.7.7 (Building Code)

Section 411.7.8.5 (Building Code)

Provide approved supervised automatic sprinkler system throughout Groups R1 and R2 occupancies three or more stories except when exterior exitway stairs are provided for the guest rooms.

Provide manual fire alarm system in hotels for more than 15 guests, apartment houses four or more stories, and dormitories, lodging houses, or rooming houses with more than 15 sleeping accommodations. May omit manual fire alarm system when building equipped with automatic f i e alarm or automatic sprinkler system. Also may omit if each guest room or apartment has direct exit to the outside and the building is three stories or less.

Provide approved single-station or multiple-station smoke detector in every dwelling, dwelling unit in apartment house, condominium or townhouse, and every guest or sleeping room in motel, hotel, or dormitory. Install per NFPA 74. Smoke detectors connected to a fire alarm system should be installed per NFPA 72 and 72E.

Provide approved smoke detector in every new and existing dwelling, including one- and two-family dwellings, dwelling unit within an apartment house, condominium, or townhouse, and every guest or sleeping room in a motel, hotel, or dormitory. Install per NFPA 74 and 72E.

Provide aircraft hangars with fire suppression as required by NFPA 409.

Provide at least one approved smoke detector within a residential aircraft hangar which is hardwired into the residential smoke alarm or other sounding device to be audible in all sleeping areas of the dwelling.

3-99

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 120: NEMA GUIDE CODE Fire Alarm & Detection System

ATRIUMS

Section 414.3 (Building Code)

Provide approved automatic sprinkler system, smoke control system, and smoke detection throughout. Install smoke detectors to activate smoke control system and sound alarm at a constantly supervised station.

COVERED MALLS

Section 413.4.5.2 (Building Code)

Provide smoke detectors to activate automatic closing devices on doors.

Section 413.8 (Building Code)

Provide automatic fire sprinkler system throughout.

Section 413.10 (Building Code) down air supply.

Provide smoke detectors within return air portion of air conditioning system to shut

HAZARDOUS PRODUCTION MATERIAL í"M) FACTLITIES

Section 408.1.2 (Building Code)

Provide approved automatic sprinkler system throughout all buildings containing HPM facilities, such as semiconductor fabrication and areas of comparable research and development.

Section 408.3.6.3 (Building Code)

Provide smoke detectors in the re-circulating air stream of ventilation system. Install to initiate a signal at the emergency control station.

Section 408.6.6 (Building Code)

Provide an emergency telephone system or local manual alarm pull station outsde of each interior egress door from HPM cutoff rooms.

HIGHRISE BUILDINGS, GROUPS B AND R

Section 412.1.1 (Building Code)

Provide an approved automatic sprinkler system or areas of refuge (compartmentation) in all Group B buildings having floor surfaces used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access. Group B buildings more than 12 stories or 150 feet high must be provided with approved automatic sprinkler system.

Provide approved automatic sprinkler system in all Group R buildings having floor surfaces used for human occupancy located more than 75 feet above the lowest level of fire department vehicle access.

3-1 O0

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 121: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS. GROUPS B AND R (continued)

Section 412.2 (Building Code)

Provide at least one smoke detector in every room for mechanical equipment, electrical, transformer, telephone equipment, and elevator machine; in every elevator lobby; in re- circulating air systems serving more than one story; in each connection to a return air vertical duct or riser serving a re-circulating air system of more than one story. Exception: In Group R occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5,000 cfin and serving not more than ten air inlet openings. See Group R for other requirements for smoke detectors. Install detectors to operate voice alarm system and equipment to prevent the re-circulation of smoke. A voice alarm system, public address system, and fire department communication system shall be provided.

Section 412.9 (Building Code) alarm system.

If area of refuge provided in lieu of automatic sprinkler system, provide a manual fire

SPECIAL AMUSEMENT BUILDINGS

Section 403.5.3 (Building Code)

Provide an automatic fire detection system with smoke detectors. An approved alternate type of automatic fire detector may be installed in areas where the ambient conditions may cause a smoke detector to alarm. Install detection device to sound alarm at a constantly supervised station.

Section 403.5.4 (Building Code)

Provide an automatic sprinkler system throughout except when building is temporary with total floor area of 1,000 square feet or less and the exit travel distance from any point is 50 feet or less. Install automatic sprinkler system to sound alarm at a constantly supervised station.

UNDERGROUND BUILDINGS

Section 415.1 (Building Code)

Applies to building spaces having a floor level used for human occupancy more than 30 feet or more than one story below the lowest level of exit discharge. Exceptions: Fixed guideway transit system, grandstands, parking garages with automatic fire suppression system, buildings which qualify but have an area not more than 1,500 square feet and have under ten occupants.

Section 415.3 (Building Code)

Provide automatic fire sprinkler system in the highest level of exit discharge serving the underground portion of the building and all levels below.

3-101

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 122: NEMA GUIDE CODE Fire Alarm & Detection System

UNDERGROUND BUILDINGS (continued)

Section 415.4.2 (Building Code) compartments.

Provide smoke detectors to activate automatic closing devices on doors between

Section 415.5.2 (Building Code)

Provide at least one smoke detector in every room for mechanical equipment, electrical, transformer, telephone equipment, and elevator machine; in every elevator lobby; in the main return and exhaust air plenum of each air conditioning system serving more than one story; in each connection to a vertical duct or riser serving two or more stories from return air ducts or plenums of W A C system. Exception: In Group R occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5,000 cfm and serving not more than 10 air inlet openings. Smoke exhaust system must be activated by smoke detectors, automatic suppression system, and manual controls.

Section 415.6 (Building Code)

Provide fire alarm system throughout when the lowest level of building is more than 60 feet below the lowest level of exit discharge. Alarm to be activated by smoke detectors, automatic fire sprinkler system, and manual pull station. Provide supervised voice communication system in underground portion of building.

OTHER GENERAL BUILDING AREAS

Section 903.5 (Building Code)

Provide approved automatic sprinkler system in the following:

Basements more than 2,500 square feet used to manufacture, repair, sell or store combustible material or when used as lounge or night club regardless of size.

In buildings without suitable access per Section 703.2 of this code. Spray finishing booth, area or room. Enclosed parking garage more than 65 feet high and more than 10,000 square feet per

floor. Repair garages two or more stories high and more than 10,000 square feet in single

floor area. Single story repair garages more than 15,000 square feet Basement garages or repair garages in basement except R3 occupancies. Commercial truck storage garage more than 5,000 square feet Bus garages for four or more buses.

Section 903.7.3 (Building Code) and required by fire prevention code. v

Chapter 36 (Fire Code)

Provide approved automatic sprinkler system with high-piled combustible stock as

3-102

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 123: NEMA GUIDE CODE Fire Alarm & Detection System

MODEL CODE ORGANIZATION

ORGANIZATION:

ADDRESS:

KEY STAFF:

PURPOSE:

PUBLICATIONS:

SERVICES:

AREAS OF I " c E :

CODE REVISION PROCESS:

National Fire Protection Association (NFPA)

One Batterymarch Park Quincy, MA 02269-9101 (6 17) 770-3000

President, George D. Miller Vice President, Anthony O'Neill Director of Public Affairs, Julie Reynolds Director Codes & Standards, Art Cote

Founded in 1881 to promote the science and improve the methods of fire protection and prevention; to obtain and circulate information on these subjects; and to secure the cooperation of its members and the public in establishing proper safeguards against loss of life and property by fire.

National Electrical Code NFPA 72 National Fire Alarm Code NFPA 101 Life Safety Code NFPA 501A Fire safety Criteria for Manufactured Home Installations,

National Fire Codes and Standards Fire safety materials Fire Command Fire Journal Fire Technology

Sites & Communities

Fire safety programs Education and training programs Fire experience database Research Fire investigation

Nationwide and International

NFPA does not issue yearly supplements but does republish the various documents at specific intervals.

3-1 03

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 124: NEMA GUIDE CODE Fire Alarm & Detection System

1997 NFPA 101 USE GROUP CLASSIFICATIONS

ASSEMBLY

Buildings or portions thereof used for gathering at 50 or more people for deliberation, worship, entertainment, eating, drinking, amusement, or awaiting transportation. Includes special amusement buildings regardless of occupancy.

EDUCATIONAL.

Buildings used for gathering groups of at least six people through the 12th grade for purposes of instruction for at least four hours per day or more than 12 hours per week.

"CARE

Buildings used for medical, treatment, or care purposes for persons having physical or mental problems as well as care of infants, infirm aged, and convalescents which provide sleeping facilities for four or more occupants generally incapable of self-preservation, such as hospitals, nursing homes, and limited care facilities.

DETENTION AND CORRECTIONAL

Buildings used to house those under some degree of restraint and who are mostly incapable of self-preservation due to security measures beyond their control.

RESIDENTIAL

Buildings where sleeping accommodations provide for normal residential purposes, except health care or detention and correction facilities. Includes hotels, motels, dormitories, apartments, lodging or rooming houses, board and care facilities, and one- and two-family dwellings. Sub-classify as follows:

Hotels, Motels and Dormitories - Buildings or groups of building under same management with more than 16 sleeping accommodations for hire or providing group sleeping accommodations for more than 16 persons not in same family group without individual cooking facilities.

Apartments - Buildings with more than three living units with individual cooking and bathroom facilities.

RESIDENTIAL (contlliued)

Lodging or Rooming Houses - Buildings with separate sleeping rooms for less than 16 people without separate cooking facilities.

Residential Board and Care - Buildings used to provide lodging, boarding, and personal care for four or more residents unrelated by blood. Classify small facilities as used for 5-16 persons and large facilities as used for more than 16 persons.

One- and Two-Family Dwellings - Buildings containing maximum two dwelling units.

3-104

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 125: NEMA GUIDE CODE Fire Alarm & Detection System

Buildings or structures for display and sale of merchandise. Minor incidental mercantile operations in buildings of different occupancy subject to exit requirements of main occupancy.

1

BUSINESS

Buildings, other than mercantile, used for maintaining accounts, records, and similar purposes. When minor and incidental to another occupancy, apply provisions applicable to that occupancy.

INDUSTRIAL

Factories making all kinds of products and properties devoted to processing, assembling, mixing, finishing, packaging, and repairing. Includes laboratories involving hazardous chemicals, laundries, power plants, pumping stations, etc.

STORAGE

Buildings or structures used primarily for storage and sheltering of goods, products, animals, or vehicles. Treat minor incidental storage in another occupancy as part of that occupancy.

DAY CARE

Buildings or portions of buildings where four or more clients receive care, maintenance and supervision by a non- relative for less than a 24-hour period.

3-105

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 126: NEMA GUIDE CODE Fire Alarm & Detection System

1997 NFPA 101 Fire Alarm/Detection Systems

NFPA - Occupancy Assembly

Underground Special Amusement

Educational

Health Care

Detention and Correctional

HotelslDormitories

Automatic Fire Sprinkler Systems

Required

Required Required

Required

Required

Required

Apartments

Ahiums

Business

Required

Required

Lodging Houses

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Malis

Required

Required Required > 3 sales levels or > 30,000 sq. fi. Required

Il Industria' I Highhazard

Fire Alarm Svstems

Required Required

Required

Required ~

Required

Required

> 3 stories

Required

Required Required Required

Required

Required

> 300 persons

Required

Au tomatic Detection Systems

Hazardous areas Required Required Required

Required

Required

Required

Required

Required

Required Required

Required

3-106

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 127: NEMA GUIDE CODE Fire Alarm & Detection System

Storage

High-rise Buildings

Day-care

3-107

Required

> 75 ft. > 75 ft.

Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 128: NEMA GUIDE CODE Fire Alarm & Detection System

1997 NFPA 101 Requirements and Exceptions

ASSEMBLY OCCUPANCTES

8-4.5.5

8-4.5.10

8-3.4.1

8-3.4.2.2

8-3.5.1

84.3.3.4

84.3.5

84.2.1

8-7.5.3.7

In proscenium opening, provide emergency ventilation to remove smoke and independently activated by sprinkler system in stage area, smoke detectors over stage area, and by manually operated switch at approved location.

Provide approved automatic sprinkler system for stages, in permanent dressing rooms, storerooms and workshops, and other accessory spaces contiguous to stage. Exception: Stages 1,000 square feet or less in area and 50 feet or less in height and under stage areas less than four feet in height.

Provide approved fire alarm system in assembly occupancies with occupant load of 300 or more and in theaters with more than one audience-viewing room. Initiate alarm by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of assembly occupancies with occupant load of 300 or more unless protected by automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout story of assembly occupancy with occupant load of 300 or more, throughout the story below assembly occupancy, and when below level of exit discharge, throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Participant sports areas with audience less than 300 people.

Provide automatic smoke detection throughout each smoke compartment of underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved, automatic sprinkler system in all enclosed areas with walls and ceilings in buildings or structures containing smoke -protected assembly seating.

Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling.

3-108

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 129: NEMA GUIDE CODE Fire Alarm & Detection System

ASSEMBLY OCCUPANCIES (continued)

8-4.7.2 & .3 Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

EDUCATIONAL

10-3.2.1

10-3.4.1

10-3.5

10-4.1.3 & .6

10-4.1.3.4

"CARE

12-2.2.2.6

12-3.4.1.1 & 12-3.4.2

12-3.4.5.3

12-3.5.1

Provide automatic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies unless maximum area is 1,000 square feet with single classroom and not location to another building not less than 50 feet. Exception: May omit manual pull stations in locations per administrative authority in buildings with two-way communication between normally occupied spaces and constantly attended receiving station, and when conditions of Section 10-3.4.2.3 are met.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Provide smoke detection system throughout each smoke compartment.

The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

Provide fire alarm system equipped with a secondary power supply and initiated by manual means and by required sprinkler and detection systems.

In nursing homes, provide approved automatic smoke detection systems in corridors throughout smoke compartments containing patient sleeping rooms and in spaces open to corridors unless excepted by this section. Detection systems are to be provided with a secondary power supply.

Provide approved, supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

3-1 O9

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 130: NEMA GUIDE CODE Fire Alarm & Detection System

HEALTH CARE ícontinueà)

12-6.3.4.1 & .2 Provide fire alarm system in all ambulatory health-care centers initiated by manual means and by means of any required detection devices or system.

12-6.3.7.7 Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or comp lete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

DETENTION AND CORRECTIONAL

14-3.4.1.1 & .2 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4 Provide approved automatic smoke detection throughout all resident sleeping areas and adjacent day rooms, activity rooms, and contiguous common spaces. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from sleeping rooms with more than four occupants.

14-3.5.2 Provide automatic sprinkler system according to type of construction used.

16-3.4.1 & .2 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system. Exception: Sleeping room smoke detectors need not initiate fire alarm system.

16-3.4.4.1 & .2

16-3.5.2

Provide corridor smoke detection except when protected throughout by approved, supervised automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite.

Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest sleeping rooms have a door that opens directly outside at ground level. Install quick response or listed residential sprinklers throughout guest rooms and suites.

3-110

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 131: NEMA GUIDE CODE Fire Alarm & Detection System

APARTMENTS

18-3.4.1 & e2

18-3.4.4.1

18-3.5.2

Provide fire alarm system for buildings more than three stories or with more than 11 living units except where each living unit is separated from other units by fire barriers with not less than I-hour rating and has independent exit, exit stairway, or ramp discharging to grade or in buildings not more than four stories or 16 dwelling units protected with an automatic sprinkler system. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single-station smoke detectors powered by house electrical service on all levels and in and outside sleeping rooms of every living unit within apartment buildings. Excepted are buildings protected throughout by an approved, supervised automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings where every living unit has either an exit door opening directly to ground level, direct access to an outside stair that serves no more than two units on same floor, or direct access to an interior stair serving only that unit with a one-hour fire resistance rating fire barrier from other portions of building. Install quick response or listed residential sprinklers throughout all living units.

LODGING OR ROOMING HOUSES

20-3.3.1 Provide fire alarm system except when equipped with smoke detection system that includes at least one manual fire alarm station.

20-3.3.4

20-3.5.2

Provide approved single-station smoke detectors powered by building's electrical service in every sleeping room.

Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway.

ONE- AND TWO-FAMILY D W " G S

21-3.3.1 Provide approved single-station smoke detectors powered by building's electrical system in all sleeping rooms, outside and in the immediate vicinity of sleeping rooms, and on each additional story including basement.

3-1 11

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 132: NEMA GUIDE CODE Fire Alarm & Detection System

Small Facilities 22-2.3.4.1-3

22-2.3.5.1

Large Facilities 22-3.3.4.1 & .2

2 2-3.3.4.1

22-3.3.4.8

22-3.3.5.1

MERCANTILE

24-3.4.1 & .2

24-3.5.1 & .2

Provide manual fire alarm system and approved smoke detectors powered by house electrical system throughout every area. Each sleeping room must be provided with approved, listed single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

Provide approved automatic sprinkler system using quick response or residential sprinklers.

Provide fire alarm system to be initiated by manual means, by a manual fire alarm station located at a supervised central location, and by any automatic sprinkler and detection systems.

Provide approved single-station smoke detectors in each sleeping room of large facilities powered from building electrical system.

Provide smoke detectors in all living areas and corridors unless protected by approved automatic sprinkler system.

Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

Provide fire alarm system in Class A mercantile occupancies. Initiate by manual means.

Provide approved, supervised automatic sprinkler system as follows:

Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

3-112

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 133: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

244.4.3.1 & .2

ATRIUMS

6-2.4.6

BUSINESS

26-3.4.1 & .2

26-3.2.1

INDUSTRIAL

28-3.2

28-3.4.1

STORAGE

29-3.4

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system. This requirement also applies to bulk merchandising retail buildings.

Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the atrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

Provide fire alarm system when two or more stories above level of exit discharge or 50 or more occupants above or below level of exit discharge; 300 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system.

Provide automatic extinguishing system in hazardous locations.

In high hazard industrial occupancies, provide automatic extinguishing systems or other protection appropriate to the particular hazard.

I

Provide fire alarm system except if total capacity of building is less than 1 O0 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided. Initiate by either manual or automatic means.

3-1 13

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 134: NEMA GUIDE CODE Fire Alarm & Detection System

STORAGE (continued)

29-8.3.4 Provide fire alarm system in parking garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

DAY CARE

30-3.4.1 & .2

30-3.4.5

3 O -6.3.4

Provide fire alarm system in day-care occupancies housed in more than one room. Fire alarm to be initiated by manual means and by operation of required smoke detectors, except single-station, and required sprinkler systems.

Provide smoke detection system in each story and in the corridors of all floors occupied by day-care occupancy if housed in more than one room.

In day-care homes, smoke detectors are required to be installed in all rooms used for sleeping and in any corridors serving a day-care home.

SPECIAL STRUCTURES AND HIGHRISE BUILDINGS

3 -2 Apply provisions to all buildings more than 75 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

Provide approved automatic sprinkler system in all areas and floor levels traversed in traveling to the exit discharge throughout windowless and underground structures with an occupant load of 50 or more. Exception: Existing structures with an occupant load of 100 or less.

32-7.3.1

32-8.2.1 & 3 2 -8.3.1

In high-rise buildings, provide approved, supervised automatic sprinkler system and a fire alarm system with an approved emergency voice/aiam communication system throughout.

OTHERGENERALREOUREMWE3

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from the hazard in most occupancies, provide an automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

5-2.3.10.1 & .2 Provide smoke detectors to activate both mechanical ventilation and pressurized stair enclosure systems.

3-114

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 135: NEMA GUIDE CODE Fire Alarm & Detection System

1994 NFPA 101 Fire Alarm/Detection Systems

Automatic Fire Sprinkler Systems

Required Required

Required

Required Required Required Required

NFPA - Occuoancv Fire Alarm Automatic

Systems Detection Systems

Required Hazardous areas Required Hazardous areas Required Required

Required

Required Required Required Required Required Required Required Required

Assembly Class A Class B Underground Special Amusement

Educational Day Care Group Day Care Family Day Care

Health Care

Detention and Correctional

HotelsíDormitories

Apartments

Lodging Houses

I L

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Malls

Atriums

Required

Required

Required

Required

Required Required > 3 stories or > 12,000 sq. ft. Required

Required

Required

Required

> 3 stories

Required

Required Required Required

Required

Required

> 300 persons

Required

Required

Required

Required

Required

Required Required

Required

3-1 15

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 136: NEMA GUIDE CODE Fire Alarm & Detection System

Storage

Highrise Buildings

3-116

Required

> 75 fi. > 75 fi.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 137: NEMA GUIDE CODE Fire Alarm & Detection System

1994 NFPA 101 Requirements and Exceptions

ASSEMBLY OCCUPANCIES

8-3.2.1.9 Provide approved automatic sprinkler system for stages, in permanent dressing rooms, storerooms and workshops, and other accessory spaces contiguous to stage. Exception: Stages 1,000 square feet or less in area and 50 feet or less in height and under stage areas less than four feet in height.

8-3.4.1

8-3.4.2

8-3.5.1

8 4 1 . 3

8-4.1.5

8.4.3

8-4.4.3.7

84.6

Provide approved fire alarm system in Class A and B occupancies and theaters with more than one viewing audience. Initiate alarm by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of Class A and B assembly occupancies unless protected by automatic sprinkler system.

Provide automatic sprinkler system throughout story containing Class A and B assembly occupancies, story below assembly occupancy and when below level of exit discharge throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Sports areas with audience less than 300 people.

Provide automatic smoke detection throughout underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved, automatic sprinkler system in all enclosed areas with walls and ceilings in buildings or structures containing smoke-protected assembly seating.

Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling.

Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

3-117

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 138: NEMA GUIDE CODE Fire Alarm & Detection System

EDUC ATiONAL

10-3.2.1

1 0-3.4.1

10-3.5

104.1.3

10-7.3.4.1

10-7.3.4.5

10-8.3.4

HEALTHCARE

12-2.2.2.6

12-3.4

Provide automatic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies unless maximum area is 1,000 square feet with single classroom. Exception: May omit manual pull stations in locations per administrative authority in buildings with two -way communication between normally occupied spaces and constantly attended receiving station.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Day-care centers - Provide fire alarm system except day-care centers housed in one room. Initiate fire alarm by manual means and by any required smoke detector.

Install smoke detection system in day-care centers except centers housed in only one room.

Day-care homes - Provide smoke detectors except homes for clients more than six years old with no sleeping facilities. Provide single station smoke detectors powered by building electrical system or system detectors with integral sounding devices in rooms used for sleeping. Provide smoke detection system in corridors serving day-care home if located within building of another occupancy.

The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

Provide electrically supervised fire alarm system initiated by manual means and by required sprinkler and detection systems. Provide an approved automatic smoke detection system in corridors of nursing homes and limited care facilities unless fully sprinkled. Provide an automatic smoke detection system in areas and spaces open to corridors.

HEALTH CARE ícontinued)

12-3.5 Provide approved supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

12-6.3.4 Provide fire alarm system in all ambulatory health-care centers initiated by manual means and by means of any required detection devices or system.

12-6.3.7.7 Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or complete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

3-1 18

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 139: NEMA GUIDE CODE Fire Alarm & Detection System

DETENTION AND CORRECïIONAL

14-3.4.1 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4

14-3.5.2

Provide approved automatic smoke detection throughout all resident housing areas. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from all but corridors, common spaces, and sleeping rooms with more than four occupants.

Provide automatic sprinkler system according to type of construction used.

16-3.4.1 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system. Exception: Sleeping room smoke detectors need not initiate fire alarm system.

16-3.4.4

1 6-3.5.2

APARTMENTS

18-3.4

18-3.4.4.1

18-3.5.2

Provide corridor smoke detection except when protected throughout by automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite.

Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest, sleeping rooms have a door that opens directly outside at ground level. Install quick response or listed residential sprinklers throughout guest rooms and suites.

Provide fire alarm system for buildings more than three stories or with more than 11 living units except where each living unit is separated from other units by fire barriers with 3/4 hour rating and has independent exit, exit stairway, or ramp discharging to grade. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single station or multiple station smoke detectors powered by house electrical service in every living unit within apartment buildings. The individual units are to be in addition to any sprinkler or detection systems required to be installed in the building.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings where every living unit has either an exit door opening directly to ground level, direct access to an outside stair that serves no more than two units on same floor, or direct access to an interior stair serving only that unit with a one-hour fire resistance rating fire barrier from other portions of building. Install quick response or listed residential sprinklers throughout all living units.

3-119

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 140: NEMA GUIDE CODE Fire Alarm & Detection System

LODGING OR ROOMING HOUSES

20-3.3

20-3.5.2

Provide fire alarm system except when equipped with smoke detection system. Initiate fire alarm by manual means. Provide approved single station or multiple station smoke detectors powered by building's electrical service. Provide single station smoke detectors in each sleeping room.

Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway.

RESIDENTIAZ, BOARD CARE

Small Facilities 22-2.3.4 Provide manual fire alarm system and approved smoke detectors powered by house

electrical system throughout every area. Each sleeping room must be provided with approved, listed single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

22-2.3.5

Large Facilities 2 2-3.3.4

22-3.3.4.7

22-3.3.4.8

22-3.3.5

MERCANTlLE

24-3.4

24-3.5

Provide approved automatic sprinkler system using quick response or residential sprinklers.

Provide fire alarm system to be initiated by manual means, by a manual fire alarm station located at a supervised central location, and by any automatic sprinkler and detection systems. Sleeping room smoke detectors are not required to initiate the building fire alarm.

Provide single station smoke detectors in each sleeping room of large facilities powered from building electrical system.

Provide smoke detectors in all living areas and corridors.

Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

Provide fire alarm system in Class A mercantile occupancies. Initiate by manual means.

Provide supervised, automatic sprinkler system as follows:

Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

3-120

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 141: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

24-4.4.3

24-4.4

ATRIUMS

6-2.4.6

BUSINESS

26-3.4

26-4.2.3.1

28-3.4

STORAGE

29-3.4

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system.

Provide covered mall and all buildings with approved electrically supervised automatic sprinkler system.

Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the atrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

Provide fire alarm system when two or more stories above level of exit discharge or 50 or more occupants above or below level of exit discharge; 300 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system.

Provide detection, alarm, and communications systems in buildings with occupied story 150 feet or more above lowest level of fire department vehicle access. Fire alarm system must use voice communication.

Provide fire alarm system except if total capacity of building is less than 100 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided. Initiate by either manual or automatic means.

3-1 21

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 142: NEMA GUIDE CODE Fire Alarm & Detection System

STORAGE ícontinued)

29-8.3.4 Provide fire a l am system in parking garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

SPECIAL STRUCTURES AND HIGHRISE BUILDINGS

3 -2

30-3.4

30-7.2

30-8.3

Apply provisions to all buildings more than 75 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

Provide fire alarm system except in open structures and towers designed for occupancy by maximum of three persons.

Provide approved automatic sprinkler system throughout windowless and underground structures with an occupant load of 50 or more. Exception: Existing structures with an occupant load of 100 or less.

In high-rise buildings, provide approved, supervised automatic sprinkler system and a fire alarm system with an approved emergency voiceialann communication system throughout.

O T H E R G E N E R A L R E O ~

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from hazard in most occupancies, provide automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

3-1 22

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 143: NEMA GUIDE CODE Fire Alarm & Detection System

1991 NFPA 101 Fire AlarmDetection Systems

Required Required Required

Required Required Required Required

NFPA - Occupancy Assembly Class A Class B Underground Special Amusement

Educational Day Care Group Day Care Family Day Care

Health Care

Hazardous areas Hazardous areas Required Required

Required Required Required Required

Automatic Fire Sorinkler Svstems

> 3 stories

Required

Required Required

I

Required

Required

Required

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Malls

Atriums

Business

Industrial

Required Required Required Required

Required Required > 3 stories or

Required

Required

> 12,000 sq. ft.

I Required 1) Detention and Correctional

Required Required Required

Required

Required

Apartments

Lodging Houses

Required Required

Required

Required

Required

Required

Fire Alarm Automatic Svstems I Detection Svstems

I Required Required

Required

3-1 23

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 144: NEMA GUIDE CODE Fire Alarm & Detection System

Storage

High-rise Buildings > 75 fi.

1991 NFPA 101 Requirements and Exceptions

Required

75 fi. > 150 fi.

ASSEMBLY OCCUPANCIES

8=3.2.1.9 Provide automatic sprinkler system for all stages, in usable spaces under a stage, in auxiliary spaces, and in dressing rooms, storerooms and workshops. Exception: Regular and thrust stages less than 1,000 square feet in area.

8-3.4.1

8-3.4.2

8-3.5.1

84.1.3

84.1.5

84.4.3.7

84.6

Provide approved fire alarm system in Class A and B occupancies and theaters with more than one viewing audience. Initiate alarm by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of Class A and B assembly occupancies unless protected by automatic sprinkler system.

Provide automatic sprinkler system throughout story containing Class A and B assembly occupancies, story below assembly occupancy and when below level of exit discharge throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Sports areas with audience less than 300 people.

Provide automatic smoke detection throughout underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling .

Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

3-1 24

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 145: NEMA GUIDE CODE Fire Alarm & Detection System

EDUCATIONAL

10-3.2.1

10-3.4.1

10-3.5.1

104.1.3

10-7.3.4.1

10-7.3.4.5

10-8.3.4

10-9.3.4

HEALTHCARE

12-1.1.1.6

Provide automtic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies. Exception: May omit manual pull stations in locations per administrative authority in buildings with two-way communication between normally occupied spaces and constantly attended receiving station.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Day-care centers - Provide fire alarm system except day-care centers housed in one room and day-care centers with less than four-person staff. Initiate fire alarm by manual means and by any required smoke detector.

Install smoke detection system in day-care centers except centers housed in only one room.

Group day-care homes -Provide smoke detectors except homes for clients more than six years old with no sleeping facilities. Provide single station smoke detectors powered by building electrical system or system detectors with integral sounding devices in rooms used for sleeping.

Family day-care homes - Provide smoke detectors except homes for clients more than six years old with no sleeping facilities. Provide single station smoke detectors powered by building electrical system or system detectors with integral sounding devices in rooms used for sleeping.

The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

3-1 25

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 146: NEMA GUIDE CODE Fire Alarm & Detection System

HEALTH CARE (continued)

12-3.4

123.5

126.3.4

12-6.3.7.7

Provide electrically supervised fire alarm system initiated by manual means and by required sprinkler and detection systems. Provide an approved automatic smoke detection system in corridors of nursing homes and limited care facilities unless fully sprinkled. Provide an automatic smoke detection system in areas and spaces open to corridors.

Provide approved supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

Provide fire alarm system in all ambulatory health-care centers initiated by manual means and by means of any required detection devices or system.

Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or complete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

DETENTION AND CORRECTIONAL

14-3.4.1 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4 Provide approved automatic smoke detection throughout all resident housing areas. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from ali but corridors, common spaces, and sleeping rooms with more than four occupants.

14-3.5.1 Provide automatic sprinkler system according to type of construction used.

16-3.4.1 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system. Exception: Sleeping room smoke detectors need not initiate fire alarm system.

3-1 26

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 147: NEMA GUIDE CODE Fire Alarm & Detection System

HOTELS/DORMITORIES (continued)

1 6 -3.4.4 Provide corridor smoke detection except when protected throughout by automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite.

16-3.5.2

APARTMENT3

18-3.4

18-3.4.4.1

18-3.5.2

Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest, sleeping rooms have a door that opens directly outside at ground level.

Provide fire alarm system for buildings more than three stories or with more than 1 1 living units except where each living unit is separated from other units by fire barriers with 314 hour rating and has independent exit, exit stairway, or ramp discharging to grade. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single station or multiple station smoke detectors powered by house electrical service in every living unit within apartment buildings. The individual units are to be in addition to any sprinkler or detection systems required to be installed in the building.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings where every living unit has either an exit door opening directly to ground level, direct access to an outside stair, or direct access to an interior stair serving only that unit with a one-hour fire resistance rating fire barrier €rom other portions of building.

LODGING OR ROOMING HOUSES

20-33

20-3.5.2

Provide fire alarm system except when equipped with smoke detection system. Initiate fire alarm by manual means. Provide approved single station or multiple station smoke detectors powered by building's electrical service. Provide single station smoke detectors in each sleeping room.

Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway.

3-1 27

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 148: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTIAL. BOARD CARE

Small Facilities 22-2.3.4 Provide manual fire alarm system and approved smoke detectors powered by house

electrical system throughout every area. Each sleeping room must be provided with approved single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

22-2.3.5.3 Provide approved automatic sprinkler system using quick response or residential sprinklers.

Large Facilities 22-3.3.4 Provide fire alarm system to be initiated by manual means, by a manual fire alarm station

located at a supervised central location, and by any automatic sprinkler and detection systems. Sleeping room smoke detectors are not required to initiate the building fire alarm.

2 2-3.3.4.7

22-3.3.4.8

22-3.3.5

MERCANTiLl3

24-3.4.1

24-3.5

Provide single station smoke detectors in each sleeping room of large facilities powered from building electrical system.

Provide smoke detectors in corridors and common spaces, unless protected throughout with automatic sprinkler systems.

Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

Provide fire alarm system in Class A mercantile occupancies. Initiate by manual means.

Provide automatic sprinkler system as follows:

Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

3-1 28

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 149: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

244.4.3

24-4.4

ATRTUNIS

6-2.4.6

BUSINESS

26-3.4

264.2.2

264.2.3.1

INDUSTRIAL

283.4

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system.

Provide covered mall and all buildings with approved electrically supervised automatic sprinkler system.

Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the atrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

Provide fire alarm system when two or more stories above level of exit discharge or 100 or more occupants above or below level of exit discharge; 1,000 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system.

Protect high-rise buildings throughout by approved electrically supervised automatic sprinkler system.

Provide detection, alarm, and communications systems in buildings with occupied story 150 feet or more above lowest level of fire department vehicle access. Fire alarm system must use voice communication.

Provide fire alarm system except if total capacity of building is less than 100 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

3-1 29

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 150: NEMA GUIDE CODE Fire Alarm & Detection System

STORAGE

29-3.4

29-8.3.4.1

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided.

Provide fire alarm system in parking garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

SPECIAL, STRUCTURES AND HIGHRISE BUILDINGS

3 -2 Apply provisions to all buildings more than 75 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

30-3.4.1 Provide fire alarm system except in open structures and towers designed for occupancy by maximum three persons. Initiate alarm by either manual or automatic means.

30-7.1.2

30-8.2.1

Provide approved automatic sprinkler system throughout windowless and underground structures with occupant load of more than 50 persons. Exception: Existing structures with an occupant load of 100 or less.

In high-rise buildings, provide approved supervised automatic sprinkler system and a fire alarm system with an approved emergency voice/alann communication system throughout.

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from hazard in most occupancies, provide automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

3-1 30

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 151: NEMA GUIDE CODE Fire Alarm & Detection System

1988 NFPA 101 Fire Alarfletection Systems

NFPA - Occunancv Assembly Class A Class B Underground Special Amusement

Educational Day Care Group Day Care Family Day Care

Health Care

II Detention and Correctional

HotelslDormitories

Apartments

Lodging Houses

Residential Board Care Small Facilities Lar e Facilities r Mercantile

II Covered Malls

Business

Automatic Fire SDrinkier Svstems

Required Required

Required

Required Required Required Required

> 75 ft.

Required

Fire Alarm Svstems

Required Required Required

Required Required Required Required

Required

Required

Required

Required

Required Required Required

Required

Required

Required

Automatic Detection Svstems

Required Required

Required Required Required Required

Required

Required

Required

Required

Required Required

3-131

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 152: NEMA GUIDE CODE Fire Alarm & Detection System

Storage

High-rise Buildings > 75 fi.

1988 NFPA 101 Requirements and Exceptions

Required

> 75 fi.

ASSEMBLY OCCUPANCIES

8-3.4.1

8-3.5.1

8.4.1.3

8.4.1.5

8.4.6

EDUCATIONAL

10-3.4.1

10-3.5.1

104.1.3

Provide approved fire protective signaling system in Class A and B occupancies and theaters with more than one viewing audience. Initiate alarm by manual means or with automatic detection ur sprinklcr systems.

Provide automatic sprinkler system throughout story containing Class A and B assembly occupancy, story below assembly occupancy and when below level of exit discharge throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display.

e Sports areas with audience less than 300 people.

Provide automatic smoke detection throughout underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

Provide fire alarm system throughout all educational occupancies. Exception: May omit manual pull stations in locations per administrative authority in buildings with two -way communication between normally occupied spaces and constantly attended receiving station.

Provide automatic sprinkler systems in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

3-1 32

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 153: NEMA GUIDE CODE Fire Alarm & Detection System

EDUCATiONAL (continued)

10-7.3.4.1 Day care centers -provide fire alarm system except day care centers housed in one room and day care centers with less than four-person staff.

10-7.3.4.5 Install smoke detection system in day care centers. Install single station smoke detectors powered by building electrical system in all rooms used for sleeping.

10-8.3.4

1 O -9.3.4

HEALTHCARE

12-3.4

12-3.5

Group day care homes - provide smoke detectors except houses for clients more than six years old with no sleeping facilities. Provide single station smoke detectors powered by building electrical system in rooms used for sleeping.

Family day care -provide smoke detectors except houses for clients more than six years old with no sleeping facilities. Provide single station smoke detectors powered by building electrical system in rooms used for sleeping.

Provide electrically supervised fire alarm systems. Provide approved automatic smoke detection system in corridors of nursing homes and limited care facilities. Provide an automatic smoke detection system in areas and spaces open to corridors.

Provide automatic sprinkler system throughout according to construction type and use of structure. See Section 12-1.6 ofNFPA 101-88.

DETECTION AND CORRECTIONAL

1 4-3.4.1 Provide electrically supervised fire alarm system throughout detention and correctional facilities.

14-3.4.4 Provide approved automatic smoke detection throughout all resident housing areas. Exception: May omit smoke detectors as follows:

ta In sleeping rooms with four or fewer occupants in Use Condition II or III; and ta In buildings protected throughout by automatic sprinkler system, may omit smoke detectors from all but corridors, common spaces, and sleeping rooms with more than four occupants.

3-1 33

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 154: NEMA GUIDE CODE Fire Alarm & Detection System

DETECTION AND CORRECTIONAL (continued)

14-3.5.1 Provide automatic sprinkler system according to type of construction used. See Section 14- 1.6 OfNFPA 101-88.

16-3.4.1 Provide fire alarm system in hotels and dormitories.

16-3.4.4 Provide corridor smoke detection except when protected throughout by automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room.

APARTMENTS

18-1.1.1

18-3.4

18-3.4.4.1

LODGLNG HOUSES

20-33

Provide with or without automatic fire suppression and/or detection according to Table 18-1 ofNFPA i û 1. Protect all high-rise buildings with approved aukmatic sprinkler system.

Provide fire alarm system for buildings more than three stories or 1 1 living units except where each living unit separated from other units by fire barriers with 3/4 hour rating and has independent exit, exit stairway, or ramp discharging to grade. Provide initiation by manual or automatic means or both according to options used in 18.1.1.1.

Provide approved single station or multiple station smoke detectors powered by house electrical service in every living unit within apartment buildings.

Provide fire alarm system except when equipped with smke detection system. Single station detectors allowed powered by batteries. Provide single station smoke detectors as required.

RESIDENTIAL BOARD CARE

21-2.3.4 Small facilities - provide manual fire protective signaling system and approved smoke detectors powered by house electrical system. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

3-1 34

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 155: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENT[AL BOARD CARE (continued)

2 1-2.3.5.2 Small facilities - provide approved supervised automatic sprinkler system in all impractical facilities.

21-3.3.4 Large facilities - provide fire alarm system except in existing facilities more than three stories and sleeping rooms having direct exterior exit access.

Provide single station smoke detectors in each sleeping room of large facilities powered from building electrical system.

21-3.3.4.7

2 1-3.3.4.8 Provide smoke detectors in large facilities in corridors and common spaces.

MERCANTILE

24-3.4.1 Provide fire alarm system in Class A mercantile occupancies.

24-3.5 Provide automatic sprinkler system as follows:

ta Buildings more than stories. Buildings with story more than 12,000 square feet Buildings with gross area more than 24,000 square feet Stories below level of exit discharge more than 2,500 square feet used for combustible goods, etc.

ta

COVERED MALLS

2443.3.1 Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems.

ATRIUMS

24-4.5.3.1

24-4.5.2

Provide fire alarm system with initiation by the smoke detection and sprinkler systems.

Provide smoke detectors at top of space and adjacent to each return air intake from the atrium.

3-1 35

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 156: NEMA GUIDE CODE Fire Alarm & Detection System

BUSINESS

26-3.4

26-4.2.3.1

26-4.3.3

INDUSTRIAL,

283.4

Provide fue alarm system when two or more stories above level of exit discharge or 100 or more occupants above or below level of exit discharge; 1,000 or more occupants total.

Provide detection, alarm, and communications systems in buildings with occupied story 150 feet or more above lowest level of fire department vehicle access.

Provide fire alarm system activated by smoke detection and automatic sprinkler systems in buildings housing atriums. Manual pull stations not required. Provide smoke detectors at top of space and adjacent to each return air intake of the atrium.

Provide fue alarm system except total capacity less than 1 O0 persons and more than 25 persons above or below level of exit discharge.

STORAGE

293.4 Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment system provided.

Provide fire alarm system in garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout.

29-8.3.4.1

HiGHREX BUILDINGS

3 -2 Apply provisions to all buildings more than 75 feet high.

30-3.4.1 Provide fire alarm systems except in open structures and towers designed for occupancy by maximum three persons.

30-8.2 Provide electrically supervised, approved automatic sprinkler system and fire alarm systems.

30-8.3.1 Provide a fire alarm and voice communication system.

3-1 36

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 157: NEMA GUIDE CODE Fire Alarm & Detection System

1985 NFPA 101 Fire AlartdDetection Systems

Fire Alarm Svstems

Automatic Detection Svstems

Class A" Class B Underground

Educational Day Care Group Day Care Family Day Care

Health Care

NFPA - Occupancy Assembly

Required Required

Automatic Fire Sprinkler Systems

Required Required Required Required

Required

Detention and Correctional

Required Required

Required

Required Required Required Required

Required

Apartments

Required Required Required Required

Required

Lodging Houses

> 3 stories

Small Facilities Required

Required

~

Covered Malls

> 3 stories

Business

Required

> 75 ft.

Required Required

Required Required

Required

Required

Required Required

I

Required

Required

Required I

3-1 37

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 158: NEMA GUIDE CODE Fire Alarm & Detection System

Storage

Highrise Buildings

3-1 38

Required

> 75 fi. > 75 ft.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 159: NEMA GUIDE CODE Fire Alarm & Detection System

1985 NFPA 101 Requirements and Exceptions

ASSEMBLY OCCUPANCíES

8-3.4.1

8-3.5.1

8.4.1

EDUCATIONAL

10-3.4.1

10-3.5.1

10-4.13

10-7.3.4

10-7.3.5

10-8.3.4

Provide approved fire alarm system in Class A and B assembly occupancies when required to be sprinkled, theaters with more than one viewing audience, and all assembly occupancies with more than 2,000 occupant load.

Provide automatic sprinkler system in every Class A and B assembly except:

ta Auditoriums with fixed seating. ta Single room multipurpose assemblies less than 12,000 square feet $ Passenger terminals at or above grade. ta Gymnasiums ta Skating rinks and swimming pools with less than 300 person audience facility. ta Class B assemblies used exclusively for restaurants.

Provide automatic smoke detection and supervised voice alarm system in underground portions of assembly structures.

Provide fire alarm system in all educational occupancies.

Provide automatic sprinkler systems in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Day care centers -provide fire alarm system except day care centers housed in one room and day care centers with less than four-person staff.

Day care centers -provide smoke detection systems except centers housed in only one room or centers housing clients age six or older and no sleeping facilities provided.

Group day care homes - provide smoke detectors except houses for clients over six years old and no sleeping facilities.

3-1 39

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 160: NEMA GUIDE CODE Fire Alarm & Detection System

EDUCATIONAL (continued)

10-9.3.4 Family day care -provide smoke detectors except houses for clients over six years old with no sleeping facilities.

HEALTHCARE

12-3.4

12-3.5

Provide electrically supervised fire alarm systems. Provide approved automatic smoke detection system in corridors of nursing homes, custodial care and supervisory, and care facilities.

Provide automatic sprinkler system throughout according to construction type and use of structure. See Section 12-1.6 ofNFPA 101-1985 for construction types permitted.

DETECTION AND CORRECïiONAL

14-3.4.1 Provide electrically supervised fire alarm system throughout detention and correctionai facilities.

14-3.4.4 Provide approved automatic smoke detection throughout all resident housing areas except in sleeping rooms with four or less occupants in Use Condition II or III or when such rooms protected with automatic sprinkler system throughout.

14-3.5.1 Provide automatic sprinkler system throughout according to type of construction used. See Section 14-1.6 for construction type requirements.

16-3.4.1 Provide fire alarm system in hotels and dormitories.

16-3.4.4 Provide corridor smoke detection except when protected throughout by automatic sprinkler system. Provide single station smoke detectors in each sleeping room except such rooms where smoke detectors connected to central alarm.

APARTMEm

18-3.4

18-3.5

Provide fire alarm system for buildings more than three stories or 1 1 living units. Provide single or multiple station smoke detectors powered by building electrical service in each living unit except when building equipped with total automatic smoke detection system throughout.

Provide automatic sprinkler system according to construction type option used. See Section 18-1.1 NFPA 101-1985 forrequirements.

3-1 40

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 161: NEMA GUIDE CODE Fire Alarm & Detection System

LODGING HOUSES

20-3.3 Provide fire alarm system except when equipped with smoke detection system or approved automatic sprinkler system. Existing battery powered single station detectors allowed per administrative authority.

FtESIDENTIAL BOARD CARE

2 1-2.2.2 Small facilities - provide fire alarm system except if approved smoke detection system powered by house electrical service installed and system includes minimum one manual fire alarm station per floor, or other manually activated continuously sounding alarms acceptable to administrative authority installed.

2 1-2.2.4.4

21-3.2.2.5

MERCANTILE

24-3.4.1

24-3.5

COVERED MALLS 24-4.3.3.1

244.4.4

24-4.4.5.1

BUSINESS

26-3.4

Small facilities - provide approved supervised automatic sprinkler system.

Provide smoke detectors in large facilities in corridors and common spaces. Exception: Common spaces with approved automatic sprinkler systems.

Provide fire alarm system in Class A mercantile occupancies.

Provide automatic sprinkler system as follows:

ta Buildings of three or more stories. e Buildings with story more than 12,000 square feet

$ Stories below levei of exit discharge more than 2,500 squm feet used for combustible goods, etc.

Buildings with gross area more than 24,000 square feet

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems.

Provide approved smoke detectors at top of space and adjacent to each return air intake of the atrium.

Provide fire alarm system in buildings housing atriums.

Provide fiie alarm system when two or more stories above level of exit discharge or 100 or more occupants above or below level of exit discharge; 1,000 or more occupants total.

3-1 41

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 162: NEMA GUIDE CODE Fire Alarm & Detection System

INDUSTRIAL

283.4

STORAGE

29-3.4

Provide fire alarm system except total capacity less than 100 persons and less than 25 persons above or below level of exit discharge.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment system provided.

29-8.3.4.1 Provide fire alarm system in garages more than 100,000 square feet in aggregate floor area except open parking garages and garages with automatic sprinkler system throughout.

HIGHRISE BUILDINGS

264.2.1 Apply provisions to all business occupancies more than 75 feet high.

264.2 Provide fire alarm system and automatic sprinkler system throughout.

3-142

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 163: NEMA GUIDE CODE Fire Alarm & Detection System

CHAPTER 4 INTRODUCTION AND EXPLANATION

Chapter 4 contains summaries of requirements and regulations of the state codes as they affect fire alanddetection systems. Each state code section provides information about the state code organization, explanation of the building use group classifications where necessary, a table summarizing the areas where fire suppression, protection and detection systems are needed, and an explanation of the code requirements and exceptions as they apply to the building types.

The administrative requirements for each state provides information on codes adopted, how they are adopted and enforced, and, where applicable, information about the code change cycle and codes history. Where no codes are enforced or state amendments do not affect the model code requirements, no further information is given or the user is referred back to the model codes in Chapter 3, respectively. State amendments or additional requirements are summarized in the administrative requirements and highlighted in the tables and other information.

Because the code requirements are complex and varied, the tables have been set up to indicate when there are code provisions for fire protection systems in each of the use groups. Where possible, the tables indicate the key item, such as building height or number of occupants that dictates using fire protection systems. Where no specific item exists but fire protection systems may be needed, the tables will have the word "required." This alerts the user to review the appropriate listings of code requirements and explanations following the table. The code requirements and explanations are a brief synopsis of the appropriate code text and should be used in conjunction with the actual code for exact details.

1 Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 164: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ALABAMA Administrative Requirements

Enforcement

Code

Stedmann B.McCollough Director Alabama Building Commission The RSA Plaza 770 Washington Ave. Suite 444 Montgomery, AL 36130 (334) 242-4082

Amendments

Summary of Amendments

Preemptive Application

standards of state code. State Fire Marshal’s Office uses 1994 SBC for fire prevention enforcement. See 1994 SBC and 1994 NFPA i01 in Chapter 3 for fire aiaddetection system requirements.

Promulgation

Building Code

1994 SBC

No state amendments

Mandatory minimum for state projects, hotels, schools, motion picture theaters. Voluntary for ail other occupancies.

Alabama Building Commission The RSA Plaza 770 Washington Ave. Suite 444 Montgomery, AL 36130 (334) 242-4082

Comments ILocal jurisdictions may adopt (

Fire Prevention Code

i994 SFPC and VFPA National Fire Codes ind Standards Vo state amendments

Ulandatory minimum itatewide

4labama Building Commission and Department of Insurance State Fire Marshal’s Office 135 South Union Street P. O. Box 303352 Montgomery, AL 36130- 3352 (334) 241-4166

Local jurisdictions or Alabama Building Commission and John Robison State Fire Marshal Department of Insurance State Fire Marshal’s Office 135 South Union Street P. O. Box 303352 Montgomery, AL 36130- 3352 (334) 241-4166

Life Safeîy Code

1994NFPA 101

No state amendments

Mandatory minimum statewide

Department of Insurance State Fire Marshal’s Office 20 1 Monroe Street, Suite 1780 P. O. Box 303352 Montgomery, AL 36130- 3352 (334) 241-4166

Local jurisdictions or John Robison State Fire Marshal Department of Insurance State Fire Marshal’s Office 135 South Union Street P. O. Box 303352 Montgomery, AL 36 130- 3352 (334) 241-4166

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 165: NEMA GUIDE CODE Fire Alarm & Detection System

History: The State of Alabama adopted the SBCCI Standard Building Code in 1957. It was used by fire bureau chiefs to enforce fire standards. In 1965, the NFPA standards were adopted. The Manufactured Housing Commission also adopts SBCCI codes, which are updated as the codes are amended.

The ktest Standard Codes are used for state projects, hotels, schools, and movie theaters and are voluntary for other commercial occupancies. The State Fire Marshal does have the authority to direct local jurisdictions to meet the state building or fire code.

4-3 Alaska

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 166: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ALASKA

Building Code

Administrative Requirements

Fire Prevention Life Safeîy Code Code

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

Summary of Amendments

I I

Code I 1997 UBC I1997 UFC I None

State amendments State amendments

Mandatory minimum. Local jurisdictions may amend to make more stringent. Department of Public Safety Division of Fire Prevention 5700 East Tudor Road Anchorage, AK 99507-1225

Chester Weger Chester WWegcr Assistant State Fire Marshal Department of Public Safety Division of Fire Prevention 5700 East Tudor Road Anchorage, AK 99507-1225

Alaska has state mandatory minimum code requirements for all buildings except 1,2, or 3 family dwellings. Local jurisdictions may amend the codes to be more stringent without state approval. Building code is mandatory for state-financed residential construction. In addition to the 1997 Uniform Code fire protection system provisions, state requires approved automatic sprinkler systems to be provided throughout Group E3 occupancies operating between 1O:OO p.m. and 6:OO a.m. and smoke detectors installed in rooms used for sleeping or napping. See Chapter 3 for summary of 1997 Uniform Codes.

Mandatory minimum. Local jurisdictions may amend to make more stringent. Department of Public Safety Division of Fire Prevention 5700 East Tudor Road Anchorage, AK 99507-1225

(907) 269-5604 (907) 269-5604

Assistant State Fire Marshal Department of Public Safety Division of Fire Prevention 5700 East Tudor Road Anchorage, AK 99507-1225

(907) 269-5604 (907) 269-5604

4-4 Alaska

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 167: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule for reviewing and updating codes. Proposed code revisions are published in the State Administrative Journal. Public comments are solicited.

1

History: Several statewide codes have been enacted for many years but have been enforced only in the last 20 years and only in the rural areas of the state. Most of the larger municipalities have their own building code sections. The Uniform Building, Mechanical, and Fire Codes are enforced through the State Fire Marshal's Office.

4-5 Alaska

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 168: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ARIZONA Administrative Requirements

buildings and schools.

- Code

Amendments

Amendments

county-owned and operated buildings as summarized on the following pages.

~

Preemptive Application

Promulgation

Enforcement

Comments

Building Code

ione (See comments below)

988 UBC adopted by eference in state fire code.

Fire Prevention Code

i988 UFC

State amendments

Mandatory statewide (6 cities :xempt).

Eric Borg Director Department of Building and Fire Safety 29 East Virginia, Suite 100 Phoenix, AZ 85004 (602) 255-4072 Local jurisdictions

îhe six exempt cities, Mesa, Tempe, Phoenix, Glendale, Scottsdale, and Tucson, use NFPA codes, which are more restrictive than the state code. The state code still applies to state-owned or operated

Life Safety Code

Zhapter 31,1988 NFPA 101 idopted by reference in state fire code for fire drills only.

e applicable to state and

4-6 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 169: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle (continued):

4. 5. 6. 7.

Proposed rule is noticed for hearing by the Board (30 days in advance) in the Arizona Administrative Register. Board holds public hearing, votes to close the record and adopts the rule. Rule packet is forwarded to the Attorney General for certification (90 days allowed for this process). Attorney General certifies rule and forwards to the Office of the Secretary of State for filing. effective when filed with the Secretary of State.

Rule becomes

4-7 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 170: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ARUONA FLRE CODE 1988 Uniform Codes (ICBO) with State Amendments

Fire AlarnúDetection Systems

Occupancy Type

Group A - Assembly

Group B - Business B-2 - RetailDrinking

Group E - Educational

Group H - Hazardous H-1 - Flammables/

Explosiues H-2 - Moderate

H-3 - HighHazard H 4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group R - Residential R-1 - Hotelhíultifamily

High-rise -New and Existing Construction B-2 - Ofices R-1 - HoteVMultifamily

Covered Malis

Aviation Control Towers

Automatic Fire Sprinkler Systems

Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Fire Alarm Systems

Required

Required

> 50 occupants

Required

Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Required

Automatic Detection Systems

Required

Required

Required

Required Required Required

> 3 stories

> 75 fi. > 75 ft.

Required

Required

4-8 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 171: NEMA GUIDE CODE Fire Alarm & Detection System

STATE O F ARIZONA F I R E CODE 1988 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 3802 (Building Code) and Section 10.306 (Fire Code)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area. ta Exhibition and display rooms more than 12,000 square feet ta Stairs and enclosed usable space below or over stairs in Group A divisions 2, 2.1,3, and 4.

Under roof and gridiron, tie and fly galleries, proscenium walls of stages, platforms more than 500 square feet, dressing rooms, workshops, and storerooms.

Section 14.104 (Fire Code)

Install fire alarm system in Group A-1, A-2, and A-2.1 occupancies.

GROUP B - BUSINESS

Section 3802(d) (Building Code) and Section 10.306 (Fire Code)

Provide automatic fire extinguishing system in Group B-2 occupancies in retail sales areas where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or when more than three stories.

Section 14.104 (Fire Code) (Amended)

Provide automatic alarm system in Group B-2 occupancies as set forth in Chapter 33 of the Building Code and manual Fire Alarm system in Group B-2 occupancies owned by the state 01- county at the discretion of the Fire Marshal.

Article 81 (Fire Code)

Provide supervised smoke detection throughout areas with high-piled combustible storage with Class I-V materials per limits in Fire Code.

GROUP E - EDUCATIONAL

Section 809 (Building Code)

Provide approved fire alarm systems when occupant load more than 50 persons.

, 4-9 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 172: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 3319 (Building Code)

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2 ) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

Section 3802 (Building Code)

Provide automatic fire extinguishing systems in basements more than 1,500 square feet and in enclosed usable space below or over stairway.

Section 14.104 (Fire Code) (Amended)

Provide manual and automatic fire alarm system in Group E with more than 50 occupants per Chaptei. 33 of Building Code. Lise autmzatic system +vlzeiz construction includes internal corridors which serve as egress passage ways. Install approved smoke detectors in internal corridors.

GROUP H - HAZARDOUS

Section 909 (Building Code) Sections 14.104, 50.113, Article 51 and Article 80 (Fire Code)

Section 911 (Building Code)

Section 3802 (Building Code) and Section 10.306 (Fire Code)

GROUP I - INSTITUTIONAL

Provide approved fire alarm system and automatic smoke detection in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies.

Provide alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Section 1002(b) (Building Code)

Provide smoke detector operated damper(s) at each point where ducts penetrate smoke barrier except where openings in ducts are limited to single smoke compartment and ducts are of steel construction.

4-10 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 173: NEMA GUIDE CODE Fire Alarm & Detection System

GROW I - INSTITUTIONAL (continued)

Section 1009 (Building Code)

Section 1010 (Building Code)

Section 3802 (Building Code) and Section 10.306 (Fire Code)

Section 14.104 (Fire Code) (Amended)

Provide approved fire alarm system in all Group I occupancies.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Provide automatic fire extinguishing system throughout.

Provide manual and automatic fire alarm system in Group I occupancies. Provide automatic system when construction includes internal corridors which serve as egress passage ways. Install approved smoke detectors in internal corridors.

GROUP R - RESIDENTIAL

Section 1210 (Building Code)

Provide smoke detectors in dwelling units and hotel or lodging-house guest rooms installed per manufacturer's instructions.

Section 1211 (Building Code) and Section 14.104 (Fire Code)

Provide manual and automatic approved fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, and hotels three or more stories or containing 20 or more guest rooms. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Buildings with automatic sprinkler system throughout and with local alarm system.

Section 3802 (Building Code) and Section 10.306 (Fire Code)

Provide automatic sprinkler system in apartment house three or more stories or containing more than 15 dwelling units, and hotels three or more stories or containing 20 or more guest rooms.

Section 14.104 (Fire Code)

Provide manual and automatic alarm system throughout R-1 occupancies three or more stories and with more than 15 dwelling units in apartments or 20 or more guest rooms in hotels and smoke detection in common areas.

4-11 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 174: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 1807 (Building Code)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems when buildings have floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Section 14.104 (Fire Code) (Am ended)

Provide fire alarm and communication systems for Group B-2 offices and Group R-1 occupancies with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Separate return wires of above ground$re alarni system wiring.froni outgoing wires by six feet or by a niinimum one-hour fire resistive construction except when making connections to panel.

HIGJBUSE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix Chapter 1 Division II (Building Code)

Provide automatic sprinkler system in Type II-N, Ei-N, or V-N construction and areas occupied by 100 or more persons. Provide fire department communication system and occupant voice notification system. Provide manual fire alarm system except may be waived when approved automatic sprinkler system installed throughout building. Single station smoke detectors in dwelling units and guest rooms, automatic elevator recall.

Appendix 1-B (Fire Code)

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, and public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide fire alarm system connected to approved central station or local fire department dispatch office. Provide single station smoke detectors in dwellings units and guest rooms.

COVERED MALLS

Section 5603 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system.

AVIATION CONTROL TOWERS

Appendix Chapter 7 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

4-12 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 175: NEMA GUIDE CODE Fire Alarm & Detection System

Section 3802 (Building Code) and Section 10.308 (Fire Code)

Appendix Chapter 1 Division 1 Section 112 (Building Code)

Appendix Chapter 1 Division 1 Section 115 (Building Code)

Section 14.109 (Fire Code) (Added)

Except in Group R-3 and M occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 3802 of 1988 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults.

Protect openings into interior shafts in existing buildings other than Group R-3, M, and high-rise buildings by self-closing one-hour fire assemblies or by automatic closing by smoke detection.

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging-house guest rooms used for sleeping purposes in existing buildings.

Fire alarm s,vstems installed in buildings used for public accomnzodation as dejned in A.R.S. 34-492.20 shall meet the requirements 0fA.R.S. 34-431.

413 Arizona

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 176: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ARKANSAS Administrative Requirements

Building Code

Code

Fire Prevention Code

Amendments

1997 SBC

State supplement

Preemptive Application

1997 SFPC

State supplement

Promulgation

:SOI) 618-8624 Local jurisdictions or Lt. Ray E. Carnahan Commander, Fire Marshal Section State Fire Marshal's Office Y I State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209 (501) 618-8624

Enforcement (501) 618-8624 Local jurisdictions or Lt. Ray E. Carnahan Commander, Fire Marshal Section State Fire Marshal's Office #I State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209 (501) 618-8624

Comments

Summary of Amendments

Statewide minimum. Local urisdictions may amend to nake more stringent. Lt. Ray E. Camahan Zommander, Fire Marshal Section State Fire Marshal's Office 71 State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209

Statewide minimum. Local jurisdictions may amend to make more stringent. Lt. Ray E. Carnahan Commander, Fire Marshal Section State Fire Marshal's Office #I State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209

Life Safety Code

1997NFPA 101

No amendments

Statewide minimum. Local jurisdictions may amend to make more stringent. Lt. Ray E. Carnahan Commander, Fire Marshal Section State Fire Marshal's Office #1 State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209 (501 \ 618-8624 Local jurisdictions or Lt. Ray E. Carnahan Commander, Fire Marshal Section State Fire Marshal's Office #1 State Police Plaza Dr. @I-30 and Geyer Springs Little Rock, AR 72209

dings, but local jurisdictions (501) 618-8624

may amend them to be more stringent. The Arkansas Fire Prevention Code specifies the following additions to the model codes adopted:

Sprinkler systems are to be installed and maintained in all high-rise buildings more than 75 feet in height in which permits for construction were issued after January 1, 1984, or existing buildings more than 75 feet in height in which 25 percent or mo re of gross floor area is being remodeled or added thereto.

All required sprinkler systems must be equipped with fire alarm features to communicate an audible and visual alarm throughout building.

All single or multiple station smoke alarms or detectors are required to have an auxiliary power source.

Day Care (Child Care) facilities must comply with the provisions of NFPA 101. See summarv of 1997 Standard Codes and 1997 NFPA 1 O1 in Chanter 3.

4-14 Arkansas

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 177: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule for reviewing and updating codes. The board or department responsible for regulations is empowered to implement the rulemaking process, which includes publication, public comment, and hearings.

History: The Arkansas Fire Code was adopted under authority of Act 254 in 1955. The code was updated in 1958, 1965,1983,1992, and 1999.

4-15 Arkansas

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 178: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CALIFORNIA Administrative Requirements

Building Code

Code 1997 UBC

Fire Prevention Code

1997 UFC

IMandatory statewide. Local

1998 state amendments (Title 24. Part 9)

Amendments

Preemptive

1998 state amendments (Title 24, Pari 2) Mandatory statewide. Local

Application

Promulgation

Enforcement ILocal jurisdictions or ILocal jurisdictions or

jurisdictions may amend to make more stringent. Travis Pitts Travis Pitts Executive Director Executive Director California Buildings Standards California Buildings Standards Commission Commission 1130 E; Street, Suite 101 I i3û K Street, Suite 101 Sacramento, CA 95814-3917 Sacramento, CA 95814-3917

jurisdictions may amend to make more stringent.

(916) 323-6363 (916) 323-6363

John Guhl Department of Forestry and Fire Protection Regulations Coordinator Office of the State Fire Marshal 11 3 1 S Street Sacramento, CA 95814 (916) 445-8421

Comments

Summary of Amendments

John Guhl Department of Forestry and Fire Protection Regulations Coordinator Office of the State Fire Marshal 1131 S Street Sacramento, CA 95814 (91 6) 445-842 i

California has mandatory code requirements for all state-regulated buildings. Local jurisdictions enforce the same edition of the model codes as the state and may amend the codes only if topographic, geological, or climatic conditions warrant.

Title 24 applies to all buildings in California. Seventeen state agencies adopting building standards have a specific jurisdictional authority to regulate construction in California, as specified in statute. At the beginning of each part of Title 24, there is an administrative section, either in the foreword or first chapter, that lists the application for each agency's buildings standards. State amends Building Code to include provisions for new occupancies, existing buildings, and modifies high-rise to include all structures. State also adds chapter on various standards for installation of fire alarm systems. Due to the complexity of the code changes and the application of 17 state departments in enforcement, please refer to code text for exact details of requirements.

Life Safety Code

None

4-16 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 179: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: California has a three-year code change cycle. Proposed revisions are prepared and documented by the state agency proposing adoption. Revisions then go through the state administrative procedures process of review and recommendation of Code Advisory Committees, hearings, public comment, adoption by the California State Building Standards Commission, and publication by the Commission.

History: The State of California to date has enacted statewide standards for housing construction and maintenance; mobile home park and accessory standards for construction and maintenance; standards for employee housing, factory- built housing, and energy conservation; fire safety in assembly areas; and access and adaptability standards for the physically handicapped. In addition to the above standards, there are additional standards for state-owned facilities.

4-17 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 180: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CALIFORNIA 1997 ICBO Use Group Classifications with State Amendments

GROUP A - ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amsement buildings are included in this classification. Sub-classify in divisions as follows:

A-1 Assembly building with stage and occupant load of 1,000 or more.

A-2

A-2.1

A-3

A 4

Building or portion thereof having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Buiiding or portion thereofwith an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUP C - ORGANIZED CAMPS (Added)

Organized camps where programs and facilities are for the primary purpose ofproviding an outdoor group living experience with social, spiritual, educational or recreational objectives for five days or more during one or more seasons of the year.

4-18 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 181: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Sub-classify in divisions as follows:

El

E 2

E 3 (Amended)

Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

Any nonresidential building or portion used.for day-care purposes for more than six children or persons and any residential building awed for da,v-care purposes,for more than I4persons.

GROUP F - FACTORY AND INDUSTRIAL

Building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations. Sub-classi@ in divisions as follows:

F-1

F-2

Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

Low-hazard factory and industrial occupancies including facilities producing noncombustible or non-explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1 Buildings with quantity of material in excess of building code limitations which present high explosion hazard, including but not limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days.

Manufacturing of Class 1.4G fireworks. Unclassified detonatable organic peroxides. Class 4 oxidizers. Class 4 or Class 3 detonatable unstable (reactive) materials.

4-19 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 182: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

H-2 Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to:

ta Class 3 non-detonatable unstable (reactive) materials. tx Pyrophoric gases.

ta Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in closed containers pressurized at more than 15 psi gauge. Exception: aerosols.

Class I organic peroxides.

Flammable or oxidizing gases.

Class 3 oxidizers. Class 3 water-reactive materiais.

H-3

H-4

H-5

H-6

H-7

Buildings with quantity of materials in excess of building code limitations which present high fire or physical hazard, including but not limited to: ta Class II, III, or IV organic peroxides.

ta Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed containers or systems and containers pressurized at 15 psi gauge or less, and aerosols. Lx Class III-B combustible liquids. tx Pyrophoric liquids or solids. ta Class 1 or 2 water-reactive materiais. ta Flammable solids in storage. ta Flammable or oxidizing cryogenic fluids (other than inert). ya Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

Class 1 or 2 oxidizers.

Repair garages not classified as Group S-3.

Aircraft repair hangars and heliports not classified as Group S-5.

Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to: LX Corrosives, except stationary lead-acid battery systems.

Lx Irritants.

ta Other health hazards.

Highly toxic materials.

Sensitizers.

4-20 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 183: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

H-8 (Added)

Laboratories and sintilar areas used for scientific experimentation or research having quantities ofniaterials not in excess ofthose listed in Tables 3-D.1 and 3-1 and not otherwise classified.

GROUP I - INSTlTUTIONAL

State Fire Marshal defines and subdivides Group I occupancies as follows:

1-1.1 (Amended) children.

Nurseries for full-time care of children under the age of six, each accommodating more thansix

Hospitals, sanitariums, nursing homes with non-ambulatory patients where medical care is provided or homes with non-ambulatory guests where medical care is provided, and similar buildings, each accommodating more than six patient s.

1-1.2

1-2 (Am ended)

1-3

Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

Nursing homes for ambulatory patients where medical care isprovided, homes for ambulatory children six years old or over where medical care is provided, or homes with ambulatory guests where pedical care is provided, and similar buildings and honor farms and conservation camps housing inmates who are not restrained, each accommodating more than six patients or children.

Mental hospitals, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates similarly restrained.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL

State Fire Marshal defines and subdivides Group R Occupancies as follows:

R-1 Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

4-2 1 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 184: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

R-2 Classification not used.

R-2.1 (Added)

Residential facilities and residential-care facilities f o r the elderly (each accommodating more than six non-ambulatory clients). ïh is division may include ambulatory clients.

R-2.1.1 (Added)

ResidentiaI.facilities and residential-care.facilities,for the elderly (each accommodating six or less non-ambulatory clients). This division may include ambulatory clients.

R-2.2 (Added)

Residential facilities and residential-care facilities for the elderly (each accommodating more than six ambulatory clients). This division may include non-ambulatory clients and shall not exceed six non-ambulatory clients.

R-2.2.1 (Added)

Residentia1,facilities and residential-care facilities f o r the elderly (each accommodating six or less ambulatory clients). This division may include a maximum of two non-ambulatory clients.

R-2.3 (Added) clients.

Residentia1,facilities providing hospice care and accommodating more than six bedridden

R-2.3.1 (Added)

Residential facilities providing hospice care and accommodating six or less bedridden clients.

R-3 (Added)

Dwellings used for large family day-care homes, lodging houses, and congregate residences, each accommodating ten persons or less.

R-6 (Added) be practiced in these.facilities.

Residential group care facilities providing care and/or supervisory services. Restraint shall not

GROUP S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

s-1

s -2

s -3

Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

Repair garages and parking garages not classified as S-4.

4-22 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 185: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE (continued)

S 4 Open parking garages.

s -5 Aircraft hangars and helistops.

GROUP U - UTILITY

Sub-classify in divisions as follows:

u1

u 2

Private garages, carports, sheds and agricultural buildings.

Fences over six feet high, tanks and towers.

4-23 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 186: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CALJFORNiA 1997 Uniform Codes (ICBO) with State Amendments

Fire AlarmíDetection Systems

Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business

Group E - Educational

Group F - Factory Industrial

Group H - Hazardous H-1 - Flammables/

H-2 - Moderate

H-3 - HighHazard H-4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Explosives

Explosion Hazard

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group M - Mercantile

Group R - Residential R-1 - HoteVMultifamily

Group S - Storage

High-rise -New and Existing Construction B-2 - Offices R-1 - HoteVMultifamily

Covered Malls

Aviation Control Towers

Automatic Fire Sprinkler Systems

Required Required Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories >12,000 sq. ft./floor > 24,000 sq. ft. total

> 3 stories

Required

> 75 fi. > 75 ft.

Required

Fire Alarm Systems

Required Reauired Required

> 50 occupants

Required

Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Required

Automatic Detection Systems

Required Required

Required

Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Required

424 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 187: NEMA GUIDE CODE Fire Alarm & Detection System

425 Califomia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 188: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CALIFORNIA 1997 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area.

Exhibition and display rooms more than 12,000 square feet Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A-4.

<+ Multi-theater complexes. Amusement buildings, except if temporary with floor area less than 1,000

square feet and exit travel distance is less than 50 feet from any point. ta All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages. ta Smoke-protected assembly seating, except press boxes, storage less than 1,000 square feet, or in conjunction with outdoor seating.

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

GROUP B - BUSINESS

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is 1,000 or more, fiie alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarni andior public address systems. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

4-26 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 189: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code) (Am ended)

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Section 1007.3.4 (Building Code) and Section 1007.2.4.2 (Fire Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Provide approved fire alarm system when occupant load is 50 or more persons or containing more than one classroom. When sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide approved fire alarm systems in even) building used for educational purposes other than private& owned trade or vocational schools.

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet.

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire -sprinkler system in woodworking,occupancies over 2,500 square feet where fmely divided combustible waste or materials present.

4-27 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 190: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Section 307.11 (Building Code)

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Section 904.2.5.4 (Building Code) (Amended)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet Boor area.

Provide automatic sprinkler system in Group H-8 occupancies.

GROUP I - INSTITUTIONAL

Section 308.7.2 (Building Code) (Am ended)

Provide automatic sprinkler system of type approved by State Fire Marshal in every hospital, or children's home, nursery or institution, or home or institution for care of aged or senile persons, or sanitarium or institution,for insane or mentally retardedpersons, or any nursing or convalescent home, or any state- owned or state-occupied building used fo r any such specified type or facil is , with more than six patients on premises on a 24-hour-per-day basis. Excepted are homes or institutions for the 24-hour-per-day care of ambulatory children and one-story structures providing 24-hour-per-day care of six or less ambulatory agedpersons iffire alarm system and smoke and/or heat detection system provided.

4-28 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 191: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code) (Am ended)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 308.12.7 (Building Code) (Added)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Appendix Chapter 3A, Division II (Building Code) (Am ended)

Provide approved manual and automatic fire alarm system in all Groups Z-1.1, 1.2, and 2 occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas. Audible devices placed in patient areas are to be chimes or similar sounding devices to alert staJt

Provide in local detention facilities state$fire marshal-approved and listed automatic fire alarm system, which responds to the products of combustion other than heat. Install nianua1,fire alarm-initiating device in all guard control stations capable of alerting personnel in a central control point.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Provide automatic f ire alarm system in existing protective social-care homes or facilities unless equipped with approved automatic sprinkler system.

In Groups 1-1.1,1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and I- 2.

Provide automatic sprinkler system in every building, or portion of building, where inmates are restrained.

Provide state fire marshal-approved manual and automatic fire alarm system, which responds to products of combustion other than heat installed in every detention and correction facility. Also provide smoke detection system.

4-29 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 192: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and more than three stories. Section 1003.2.8 (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 powered in existing buildings. (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer's instructions and receiving primary power from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery

Section 31ü.iü (Building Code) and Section 1007.2.9.1.1 (Fire Code) (Amended) provide a fire alarm/communication system. Exceptions:

In Group K-1 occupancy, provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings

1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Building with approved supervised fire sprinkler system throughout and with local alarm system.

Section 310.10.1-3 (Building Code) (Added) R-2.2 occupancies.

In addition to smoke detectors required under Section 310.9, provide approved manual and automatic fire alarm in Group R-2.1, a manual pull station in Groups R-2.1.1, R-2.2.1, and R-2.3.1, and a manualfire alarm system in Group

Section 310.14 (Building Code) (Added)

Provide an automatic or manually operatedfire alarm system in existing apartment houses three or more stories in height or containing more than 15 apartments and every hotel three or more stories in height or containing 20 or more guest rooms.

Section 310.15.2 (Building Code) (Added)

Provide state fire marshal-approved and listed single-station smoke detector in large family day-care homes.

4-30 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 193: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 310.16.2 (Building Code) Group R-3 occupancies. (Am ended)

Pi-Ovide a State Fire Marshal approved and listed smoke detector in all existing

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick- response standard sprinklers in dwelling units and guest rooms.

Section 904.2.10 (Building Code) (Am ended)

Provide automatic sprinkler system in all Group R-2 occupancies. Exception provided under certain conditions or if equipped with automatic$re alarm system activated by detectors. Provide automatic sprinkler system in Groups R- 2.1, 2.11, 2.2, 2.2.1, 2.3 and 2.3A occupancies. Install residential or quick- response standard sprinklers in sleeping areas of Groups R-2.3 and R-2.3A.

Section 904.2.10 (Building Code) (Amended)

Section 1007.2.9.1.3 81.4 (Fire Code)

Appendix Chapter 3A (Building Code) (Added)

Provide,fire-extinguishing system connected to a remote station protection signaling system in all new public libraries funded from the California Library Construction and Renovation Act of 1988.

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

Provide all Group R-6 occupancies with smoke detectors. Provide all Group R- 6.1 and 6.2 occupancies with an approved automatic f ire alarm system which responds to products of combustion. Where automatic f ire alarm is not required, provide manual pull station in all other Group R-6 occupancies. Excepted are Group R-6 occupancies equipped with an automatic sprinkler system. I f Group R-6 houses hearing impairedpersons; provide notification appliances fo r hearing impaired which operate upon initiation of either an automatic $re alarm system or some detectors.

4-31 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 194: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCTES

Section 403.2 (Building Code) (Amended)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction. This also applies to every new building o f any type of construction or occupancy havingfloors used,for human occupancy located more than 75 feet above the lowestfloor level having building access with exceptions as listed by the State Fire Marshal.

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with tloors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic fire -detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 8 1 -A.

Provide automatic smoke-detection system throughout building when special egress-control devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

4-32 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 195: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTíON, GROW B OFFICE BUILDINGS AND GROW R-1 OCCUPANCIES (continued)

Section 1007.2.12.7 (Fire Code)

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Section 1007.2.12.8 (Fire Code)

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smoke-control system.

Section 1007.2.12.9 (Fire Code)

Provide manual fire alarm system in lumber, plywood, and veneer mills.

HIGHRISE. GROUP B-2 OFFICES A N D GROUP R-1 OCCUPANCIES. EXISTEVG STRUCTURES

Section 403.24 & .25 (Building Code) (Am ended)

Provide approved automatic sprinkler system conforming to NFPA 13 in even, existing high-rise building of Type II-N, Tvpe III-N or Tvpe V-N construction.

Provide either automatic or manually operatedfire alarm system in every existing high-rise building used for housing Group R-I occupancies. If automatic fire-extinguishing system installed, provide an approved,flow indicator to be electrically interconnected with fire alarm system.

Appendix 1-B (Fire Code)

Provide approved automatic sprinkler system in Type II-N, III-N, or V-N construction in all required corridors, stairwells, elevator lobbies, public assembly areas for 100 or more persons, and commercial kitchens.

Provide fire department communication system and occupant voice notification system.

Provide approved manual fire alarm system connected to approved central, proprietary or remote station service, or a system which will provide an audible signal at a constantly attended location.

Provide single station smoke detectors in dwelling units and guest rooms, which may be battery powered.

4-33 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 196: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Appendix Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES (GROUP R DIVISION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

Appendix 1-A (Fire Code)

Protect openings into interior shafts in existing buildings, other than high-rise buildings, by self-closing one-hour fire assemblies or by automatic closing by smoke detection.

4-34 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 197: NEMA GUIDE CODE Fire Alarm & Detection System

OTHFR GENERAL REOuIREMENTS (continued)

Appendix 1-A (Fire Code)

Provide approved automatic sprinkler system in basements of existing buildings, other than high-rise buildings, with more than 1,500 square feet in area and meeting other criteria as established in the 1997 UBC and 1997 UFC.

Appendix 1 -A (Fire Code)

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging house guest rooms used for sleeping purposes in existing other than high-rise buildings. Install smoke detectors to receive primary power source from building wiring if from commercial source or by battery power.

Section 713 (Building Code)

Section 3003.2 (Building Code)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

OTHER STRUc"üRES/S/OCCUPANCIES

Section 414A.4.1 (Building Code) (Added)

Provide automatic sprinkler system and state fire marshal-approved and listed fire alarm system in all stations of fixed guideway transit systems.

Section 431A (Building Code) Section sleeping purposes 1007.2.13 (Fire Code) (Added)

Provide automatic f r e extinguishing system in Group C occupancies. Provide automatic smoke-detection system in every building and structure used for

4-35 California

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 198: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF COLORADO Administrative Requirements

Building Code

Fire Prevention Code

Life Safeíy Code

Code

Amendments

None None None

None

Preemptive Application ,

~~

Promulgation

Enforcement

Comments

Summary of Amendments

Local jurisdictions I I

Local jurisdictions

other construction requirements are the prerogative of local government.

Code Change Cycle: The Housing Act of 1970 gave statutory responsibility to the Division of Housing in areas of the state where no codes exist for hotels, motels, and multifamily dwellings. Current editions of the model codes are always enforced by the Director of Housing.

History: The Housing Act of 1970 gives statutory responsibility for site-built construction in areas of the state where there are no codes for hotels, motels, and multifamily dwellings. It also gives statutory responsibility in the following areas: factory-built housing built to HLJD standards and certification for recreation vehicles constructed to the ANSI 119.2 Standard.

4-36 Colorado

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 199: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICUT Administrative Requirements

Code

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

1996 NBC

State amendments

Mandatory statewide. Local jurisdictions may not amend.

Daniel Tierney Public Safety Building Official Supervisor

Department of Public Safety Division of Fire, Emergency and Building Services Office of State Building Inspector P. O. Box 2794 Middletown, CT 06457-9294

Local jurisdictions (860) 685-83 1 O

I

Fire Prevention Code

{one

Life Safety Code

~~

Connecticut Fire Safety Code based on 1997 NFPA 101 State amendments

Mandatory statewide. Local jurisdictions may not amend.

John Blaschik, Jr. Deputy State Fire Marshal Department of Public Safety Division of Fire, Emergency and Building Safety Office of the State Fire Marshal P. O. Box 2794 Middletown, CT 06457-9294 (860) 685-8380

Local jurisdictions

The state deleted the reference to NFPC-1996 in building code.

that they deal with the same requirements. Where conflicts occur, the more stringent shall apply. See summaries of both the State Building and Fire Codes on the following pages.

Code Change Cycle: Connecticut's codes are reviewed every four years with the publication of the new editions of the model codes. Recommendations for state amendments to the model codes are reviewed by the state's Codes and Standards Committee. Revisions go through the state's administrative procedures process of publication, public comment, and hearings. After approval, the amendment goes to the Commissioner and Attorney General for approval, then to the Secretary of State for final approval. The process generally takes about six months.

4-37 Colorado

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 200: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICüT 1996 BOCA Use Group Classifications with State Amendments

GROUP A - ASSEMBLY

Buildings used for assembly with greater than 50 occupants. Sub-classifi as follows:

A-1 Theaters - Theaters and other buildings for theatrical or operatic performances and exhibitions with raised stage and fixed seats, proscenium curtain, fixed or portable scenery loft, lights, motion picture booth, mechanical appliances, and other theatrical accessories and equipment.

A-2 Nightclubs, Dance Halls - Buildings and public assembly places including rooms, lobbies, and other spaces connected thereto with common means of egress and entrance without theatrical stage accessories and designed for use as dance hall, night club, or similar.

A-3 Restaurants, Recreation - Buildings with or without auditorium and without theatrical stage other than raised platform where people assemble for amusement, entertainment, or recreation and incidental motion picture, dramatic, or theatrical presentations including art galleries, exhibition halls, museums, lecture halls, libraries, restaurants other than nightclubs, recreation centers, and passenger terminals.

A 4 Churches -Buildings used as churches and for similar religious purposes.

A-5 Stadiums - Outdoor assembly structures including grandstands, bleachers, coliseums, stadiums, tents, and similar structures.

GROUP B - BUSINESS

Buildings or parts thereof used for business transactions, rendering of professional services, or for other services involving stocks of goods, wares, or merchandise in limited quantities for use incidental to office uses or sample purposes including: data processing, animal hospitals and kennels, automobile showrooms, banks, beauty and barber shops, car washes, civic administration and post offices, laboratories for testingiresearch, telephone exchanges, laundries and dry cleaning and self-service and pick-up/delivery stations, outpatient clinics, radio/TV stations, fire and police stations, florists and nurseries, print shops, and professional services.

GROUP E - EDUCATION&

Buildings or parts thereof used by more than five persons at one time for educational purposes through twelfth grade including schools, academies, and day-care centers providing care for more than six persons over two -and-one-half years of age for less than 24 hours per day. GROUPF - FACTORY/INDUSTRIAL

Buildings or parts thereof including among others, factories, assembling plants, industrial laboratories, and all other industrial and manufacturing uses where occupants engaged in fabricating, assembling, or processing of products or materials. Sub-classify as follows:

F-1 Moderate Hazard - Moderate hazard factory and industrial uses for manufacturing processes including aircraft, automobiles, appliances, boats, and RVs, bakeries, alcoholic beverages, boilers works, canneries, clothing, machinery, dry cleaning using other than flammables, electronics and electric light plants, food processing, film, furniture, tanneries, woodworking, paper mills, plastic, publishing, printing, refuse incinerators, shoes, soap, sugar, tobacco, upholstery, textile mills, and laundries.

4-38 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 201: NEMA GUIDE CODE Fire Alarm & Detection System

F-2 Low Hazard - Factory and industrial uses involving fabrication or manufacturing of noncombustible materials which during finishing, packing, or processing, do not involve significant fire hazard including nonalcoholic beverages, brick, masonry, ceramic, glass, and gypsum, foundries, ice, metal fabrication and assembly, and water pumping plants.

GROW H - HAZARDOUS

Buildings or parts thereof used for manufacturing, processing, generation, or storage of corrosive, highly toxic, highly combustible, flammable, or explosive materials including loose combustible fibers, dust, and unstable materials that constitute high fire or explosion hazard. Sub-classify as follows:

H-1 - Buildings and structures or parts thereof containing materials which present a detonation hazard.

H-2 - Buildings and structures or parts thereof which contain materials presenting a deflagration hazard or hazard from accelerated burning.

H-3 - Buildings and structures or parts thereof which contain materials that readily support combustion or present a physical hazard.

H-4 - Buildings and structures or parts thereof containing materials that are a health hazard.

GROUP I - INSTlTUTIONAL

Buildings or parts thereof where people suffering from physical limitations due to health or age harbored for medical or other care or treatment, where people detained for penal or correction purposes, or where liberty of inmates is restricted. Sub-classify as follows:

4-39 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 202: NEMA GUIDE CODE Fire Alarm & Detection System

1-1 Supervised - Facilities for children, aged persons, mentally impaired and convalescents including group homes, mentally retarded care facilities, nursing homes, and orphanages, housing six or more individuals who because of age, mental disability, or other reasons, must live in supervised environment but who are physically capable of responding to emergency situation without personal assistance.

1-2 Incapacitated - Use for persons with physical limitations including hospitals, day nurseries, sanitariums, infirmaries, orphanages, homes for aged and infirm, and child care.faci1itie.v accommodating more than six children two-and-one-hayyears of age or less for any length of time.

1-3 Restrained - Buildings or parts thereof including prisons, jails, reformatories, insane asylums, and similar uses, inhabited by occupants under some restraint.

GROUP M - MERCANTILE

Buildings or parts thereof used for display and sales purposes and accessible to public including retail stores, motor h e i service stations, shops, saiesrooms, and markets.

GROUP R - RESIDENTIAL

Buildings or parts thereof where families or households live or where sleeping accommodations provided for individuals with or without dining facilities. Sub-classify as follows:

R-1 HotelsIMotels - Hotels, motels, boarding houses, and similar buildings arranged for shelter and sleeping accommodations for more than five occupants primarily transient in nature who use facilities for less than 30 days,

R-2 Multifamily -Dwellings with more than two dwelling units including boarding houses and similar buildings arranged for shelter and sleeping accommodations for occupants primarily not transient in nature. This also includes dormitories accommodating more than five persons older than 2-1/2 years of age.

R-3 One and Two Family and Multiple Single-family - Buildings arranged for use as one- or two-family dwelling units with maximum five lodgers or boarders per family and multiple single-family dwellings where each unit has its own means of egress. This also includes a childcare facility accommodating six or less children of any age.

440 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 203: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

R-4 Single Family -Detached one- or two-family dwellings and oneTfamily townhouses, not niore than two stories and 35,feet in height, plus habitable attic, 4,800 square feet perfloor, and the accessor,v structures.

GROUP S - STORAGE

Buildings or parts thereof including warehouses, storehouses, and freight depots used primarily for storage of goods, wares, or merchandise. Sub-classify as follows:

S-1 Moderate Hazard - Storage buildings for contents likely to burn with moderate rapidity, but not producing poisonous gases, fumes, or explosives.

S-2 Low Hazard - Storage buildings for noncombustible materials and low hazard wares that do not ordinarily burn rapidly such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings but with negligible amount of plastic trim such as knobs, handles, or film wrapping.

GROUP U - UTILI" AND MISCELLANEOUS

Accessory buildings and miscellaneous structures not classified in any specific use group per Building Code requirements commensurate with fire and life hazard incidental to use. This group to include structures accessory to a residential occupancy.

4-41 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 204: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICUT 1996 National Codes (BOCA) with State Amendments

Fire AJarmDetection Systems

Group I - Institutional I

Occupancy Type Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A-4- Churches

Group B - Business

Group F - Factory F-1 - Moderate Hazard

I Group H - High Hazardous

Group I - Institutional

Group M - Mercantile

Group R - Residential R-1 - HotelMotels R-2 - MUltifamilV

Group S - Storage S-1 - Moderate Hazard 1

II Atriums

Il Covered Maus

Automatic Fire Sprinkler Systems

> 12,000 sq. ft. > 5,000 sq. ft. > 12,000 sq. ft. > 12.000 sa. ft.

> 20,000 sq. fi.

> 3 stories or > 12,000 sq. fi. or > 24,000 sq. ft. total Required

Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required Reauired

> 3 stories or > 12,000 sq. fi. or > 24,000 sq. ft. total

Required

Required

Fire Alarm Systems

Reauired > 2 stories

Required

Required

Required

Required > 3 stories

> 2 stories

Automatic Detection Systems

Required

Required

Required Reauired

> 30 ft. ceiling

Required

4-42 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 205: NEMA GUIDE CODE Fire Alarm & Detection System

Hazardous Production Materials I Required I Required I Required

Public Garages

Special Amusement Building

Underground Structures

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required Required

Required Required Required

4-43 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 206: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICUT 1996 National Codes (BOCA) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout Groups A-1, A-3, and A 4 occupancies if fire area exceeds 12,000 square feet as follows: entire story or floor level where Groups A-1, A-3, or A-4 occupancies are located; all stories and floors below Groups A-1, A-3, or A-4; and all intervening stories and floor levels between Groups A-1, A-3, or A 4 and the highest level of exit discharge serving these use groups. Exception: Group A-4 naves and chancels where main floor is at the level of exit discharge of the main entrance, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance and with no audience facilities.for more than 300persons. These requirements also apply to Group A-2 occupancies, which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy.

Section 918.4.1 (Building Code) (Amended)

Provide fire alarm system in Group A-4 occupancies except in sanctuary and nave areas of churches. A.fire alarm is not required for Assembly occupancies with occupant loads of 300 or less, or in Group A-1 theaters with only one audience- viewing room.

GROUP B - BUSINESS

Section 918.4.2 (Building Code) (Amended)

Provide fire alarm system in Group B occupancies which are two or more stories above or below level of exit discharge, or which have floors two or more stories below the highest level of exit discharge, or which have an occupancy of 300 or more.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code) (Am ended)

Provide automatic fire suppression system throughout Group E occupancies, unless fire area is less than 20,000 square feet. Provide automatic sprinkler system in every portion of building below the level of exit discharge.

4-44 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 207: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 918.4.1 (Building Code) (Am ended)

Section 904.7 (Building Code)

GROW H - HAZARDOUS

Sections 904.5 and 417.1 (Building Code)

Section 419.3 (Building Code)

Section 2806.4 (Building Code)

Section 417.5.3 (Building Code)

Section 918.4.3 (Building Code)

GROW I - INSTlTUTIONAL

Provide fire alarm system in all Group E occupancies. A$re alarm is not required in Group E occupancy with a maximuni area of 1 O00 square feet and containing a single classroom and located not closer than 5O.feet from another building.

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in fire area, or more than 24,000 square feet total area on all floors, or fire area more than three stories above grade.

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code.

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Provide automatic fire detection system per NFPA 72 throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high-hazard materials are used and stored.

Provide a fire alarm system in Groups H-2, H-3, and H-4 occupancies.

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I Occupancies. Exception: Group 1-2 child-care facilities accommodating 1 O0 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

4-45 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 208: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUITONAL (continued)

Section 918.4.4 (Building Code)

Provide fire alarm systems in all Group I Buildings.

Section 919.4 (Building Code)

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide automatic fire detection system and smoke detectors throughout ali resident housing areas. Smoke detectors are not required in sleeping rooms with not more than four occupants.

Section 920.3.3 (Building Code)

Section 409.5.1 (Building Code)

Section 920.3.4 (Building Code) (Added)

GROUP M - MERCANTIIX

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery-power backup.

In Group 1-2, provide automatic fire detection system in corridors and spaces open to the corridors in nursing homes and detoxification facilities. Exception 1 : Not required if patient sleeping rooms have smoke detectors permanently connected to the building’s power supply and have a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station attending the rooms. Exceptions 2: Not required if patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function.

Provide single- or multiple-station smoke detectors in all day care and child care occupancies unless housed in one rooni. Install in each story, in the corridors of allfloors occupied by the occupancy, and in lounges, recreation areas and sleeping rooms.

Section 904.7 (Building Code) (Amended)

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total fire area on all floors, fire area is more than three stories above grade, and throughout stories below the level of exit discharge ifjìre area exceeds 2,500 square feet and used for the sale, storage, or handling of combustible goods and merchandise. Exception: Public garages.

4-46 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 209: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL

Sections 904.8 and 906.2.1 (Building Code)

Section 904.9 (Building Code) (Amended)

Section 918.4.5 (Building Code)

Section 918.4.6 (Building Code)

Section 919.4.4 (Building Code)

Section 920.3.1 (Building Code)

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Provide automatic fire suppression system throughout all Group R-2 occupancies except buildings two stories or less, including basements, and with 12 or less dwelling units and each dwelling unit has a least one door of direct access to exit, and existing Group R-3 buildings converted to Group R-2 with not more than three families.

Provide fire alarm system in all Group R-1 occupancies.

Provide fire alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge, and in all Group R-2 dormitories.

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

Provide single- or multiple-station smoke detectors in Groups R-1, R-2, and R-3 occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery -power backup.

GROUP S - STORAGE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout in Group S-1 occupancies, which are more than 12,000 square feet in fire area, more than 24,000 square feet in total area on all floors, or fire area more than three stories above grade.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

4-47 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 210: NEMA GUIDE CODE Fire Alarm & Detection System

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Section 404.6 (Building Code)

Section 922.4.2 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atrium.

Provide a smoke control system in all atriums that connect more than two stories.

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alarm signaling system.

In a smoke control area with ceiling height over 30 feet, provide smoke detectors to detect smoke above highest floor open to an atrium or at highest point of another smoke control space.

Section 402.10 and 402.14.2 (Building Code)

Provide automatic sprinkler system throughout covered mall building and all connected buildings, including kiosks and similar structures that are covered and located within the mall.

Section 402.7.1 (Building Code)

In anchor store, provide s m k e control system to be activated by smoke detectors installed in return air portion of heating and cooling system, automatic sprinkler system, and manual controls provided in an approved location.

HAZARDOUS PRODUaON MATERIALS FACILITIES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 416.9.2 (Building Code) emergency control station.

Section 416.14.5 (Building Code)

Install smoke detectors in recirculating air stream to initiate a signal at the

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

4-48 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 211: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS

Section 403.1 (Building Code)

Section 403.2 (Building Code)

Section 403.4 (Building Code)

PUBLIC GARAGES

Section 408.3.1 (Building Code)

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-1, H-2 or H-3; and low-hazard special occupancies.

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

SPECIAL AMUSEMENT BUíLDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

4-49 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 212: NEMA GUIDE CODE Fire Alarm & Detection System

STAGES AND PLATFORMS (continued1

Section 411.7 and 412.8 (Building Code)

Provide automatic sprinkler system in all buildings or portions used as sound stages for motion picture or television production and over 1,000 square feet.

U"D S"RTJCTURE3

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voice/alarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

Section 1020.3 (Building Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Section 2807.6 (Building Code)

Provide approved automatic fire suppression system at the top and at alternate floor levels in a waste or linen chute and in the termination and incinerator rooms. System not required if incinerator burns only Type 4 waste.

Section 2808.4 (Building Code)

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

4-50 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 213: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL, FtEOuTREMENTs ícontinued)

Section 904.10 (Building Code)

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.10. Exception: Group R-3 occupancies.

Section 904.1 (Building Code) (Amended)

Provide aiitomatic,fire suppression s.vstem in any building or structure more than four stories tall and used.for human occupancy, in any hotel or motel with six or more guest rooms and providing sleeping accommodations for more than 16 persons, in any residential building having more than 12 units with 80percentof the dwelling units available having at least one resident who has attained the age of 65, and in other occupancies as required by the State Fire Marshal in the interest of safety because o f special occupancy hazards. Exceptions: open parking structures, telecommunications equipment buildings where equipment is located ifother conditions as specified by the code is met, and over an inside swimming pool water surface.

Section 918.5 (Building Code)

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

4-51 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 214: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICUT 1997 NFPA 101 with State Amendments

Fire AlarmlDetection Systems

Automatic Fire NFPA - Occupancy Sprinkler Systems

Assembly Required Underground Special Amusement Required

Educational Required

- Health Care Required

Detention and Correctional Required -

Apartments

Lodging Houses

Required

Required

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Malls

Atriums

Business

Industrial

Fire Alarm

Required Required > 3 sales levels or > 30,000 sq. ft. Required

Required

High hazard

Systems Required Required

Required

Required

Required

Required

> 3 stories

Required

Required Required Required

Required

Required

> 300 persons

Required

Automatic Detection Systems

Hazardous areas Required Required Required

Required

Required

Required

Required

Required

Required Required

Required

4-52 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 215: NEMA GUIDE CODE Fire Alarm & Detection System

Storage Required

High-rise Buildings > 75 ft. > 75 fi.

Day-care Required

4-53 Connecticut

Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 216: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF CONNECTICUT 1997 NFPA 101 with State Amendments

Requirements and Exceptions

8-4.5.5

84.5.10

8-3.4.1

8-3.4.2.2

8-3.5.1

8-4.3.3.4

84.3.5

84.2.1

In proscenium opening, provide emergency ventilation to remove smoke and independently activated by sprinkler system in stage area, smoke detectors over stage area, and by manually operated switch at approved location.

Provide approved automatic sprinkler system for stages, in permanent dressing rooms, storerooms and workshops, and other accessory spaces contiguous to stage. Exception: Stages 1,000 square feet or less in area and 50 feet or less in height and under stage areas less than four feet in height.

Provide approved fire alarm system in assembly occupancies with occupant load of 300 or more and in theaters with more than one audience-viewing room. Initiate a lam by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of assembly occupancies with occupant load of 300 or more unless protected by automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout story of assembly occupancy with occupant load of 300 or more, throughout the story below assembly occupancy, and when below level of exit discharge, throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Participant sports areas with audience less than 300 people.

Provide automatic smoke detection throughout each smoke compartment of underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved, automatic sprinkler system in all enclosed areas with walls and ceilings in buildings or structures containing smoke-protected assembly seating.

4-54 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 217: NEMA GUIDE CODE Fire Alarm & Detection System

ASSEMBLY OCCUPANCZES (continued)

8-7.5.3.7 Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling.

84.7.2 & .3 (Amended)

Provide approved automatic sprinkler system throughout special amusement buildings, except buildings or structures not niore than I0,feet in height and I60 square feet in horizontal projection, or any temporary buildings or structures used for fewer than 60 da,vs with totalfloor area of less than 1,000 square feet and travel distance from any point to an exit is less than 50,feet. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

EDUCATIONAL

10-3.2.1

10-3.4.1

10-3.5

104.1.3 & .6

10-4.1.3.4

Provide automatic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies unless maximum area is 1,000 square feet with single classroom and not location to another building not less than 50 feet. Exception: May omit manual pull stations in locations per administrative authority in buildings with two-way communication between normally occupied spaces and constantly attended receiving station, and when conditions of Section 10-3.4.2.3 are met.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Provide smoke detection system throughout each smoke compartment.

HEALTHCARE

12-2.2.2.6 ' The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

12-3.4.1.1 & 12-3.4.2

Provide fire alarm system equipped with a secondary power supply and initiated by manual means and by required sprinkler and detection systems.

4-55 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 218: NEMA GUIDE CODE Fire Alarm & Detection System

HEALTH CARE ícontinueà)

12-3.4.5.3 In nursing homes, provide approved automatic smoke detection systems in corridors throughout smoke compartments containing patient sleeping rooms and in spaces open to corridors unless excepted by this section. Detection systems are to be provided with a secondary power supply.

1 2 -3.5.1 Provide approved, supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

12-6.3.4.1 & 2 Provide fue alarm system in all ambulatory healthcare centers initiated by manual means and by means of any required detection devices or system.

12-6.3.7.7 Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or complete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

DETENTION AND CORRECTIONAL

14-3.4.1.1 & .2 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4 Provide approved automatic smoke detection throughout all resident sleeping areas and adjacent day rooms, activity rooms, and contiguous common spaces. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from sleeping rooms with more than four occupants.

14-3.5.2 Provide automatic sprinkler system according to type of construction used.

16-3.4.1 & .2 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system Exception: Sleeping room smoke detectors need not initiate fire alarm system.

4-56 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 219: NEMA GUIDE CODE Fire Alarm & Detection System

HOTELSIDORMITORIES íconíinued)

16-3.4.4.1 & .2 (Amended)

Provide corridor smoke detection except when protected throughout by approved, supervised automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite.

In each hotel, motel or inn, install such equipment which, when activated, will provide an approved visible alarm suitable to warn occupants in at least one percent of the units/rooms of such occupancies having I O 0 or more unitshooms. In occupancies having less than I O0 unitsh-ooms, at least one unit/room required to have such an alarni.

163.5.2

APARTMFANTS

18-3.4.1 & .2

18-3.4.4.1

18-3.5.2 (Am ended)

Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest, sleeping rooms have a door that opens directly outside at ground level. Install quick response or listed residential sprinklers throughout guest rooms and suites.

Provide fire alarm system for buildings more than three stories or with more than 1 1 living units except where each living unit is separated from other units by fire barriers with not less than 1-hour rating and has independent exit, exit stairway, or ramp discharging to grade or in buildings not more than four stories or 16 dwelling units protected with an automatic sprinkler system. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single -station smoke detectors powered by house electrical service on all levels and in and outside sleeping rooms of every living unit within apartment buildings. Excepted are buildings protected throughout by an approved, supervised automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings four stories or less where every living unit has either an exit door opening directly to ground level, direct access to an outside stair that serves no more than two units on same floor, or direct access to an interior stair serving only that unit with a one-hour fire resistance rating fire barrier from other portions of building. Install quick response or listed residential sprinklers throughout all living units.

LODGING OR ROOMING HOUSES

20-3.3.1 Provide fire alarm system except when equipped with smoke detection system that includes at least one manual fire alarm station.

20-3.3.4 & .5 (Am ended)

20-3.5.2

Provide approved single-station smoke detectors powered by building's electrical service in every sleeping room. Install smoke alarm which, when activated, will provide an approved visible alarm suitable to warn occupants in at least one room.

Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway. Install to actuate the fire alarm system.

4-57 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 220: NEMA GUIDE CODE Fire Alarm & Detection System

ONE- AND TWO-FAMILY DWELLINGS

2 1 -3.3.1 (A tn ended)

Provide approved single -station smoke detectors powered by building’s electrical system in all sleeping rooms, outside and in the immediate vicinity of sleeping rooms, and on each additional story including basement. Excepted would be buildings protected throughout by an approved autoniatic sprinkler s,vsteni where the bedrooms are equipped with residential sprinklers.

RESIDENTIAL BOARD CARE

Small Facilities 22-2.3.4.1 -3

22-2.3.5.1

Provide manual fire alarm system and approved smoke detectors powered by house electrical system throughout every area. Each sleeping room must be provided with approved, listed single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

Provide approved automatic sprinkler system using quick response or residential sprinklers. Install to initiate fxe alarm system.

Large Facilities 22-3.3.4.1 & .2 Provide fire alarm system to be initiated by manual means, by a manual fire alarm

station located at a supervised central location, and by any automatic sprinkler and detection systems.

22-3.3.4.7 Provide approved single-station smoke detectors in each sleeping room of large facilities powered from building electrical system.

4-58 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 221: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTIAL BOARD CARE ícontinueà)

22-3.3.4.8

22-3.3.5.1

MERCANTILE

24-3.4.1 & -2

24-3.5.1 & -2

COVEREDMALLS

24-4.4.3.1 & .2 (Amended)

ATRIurvLs

6-2.4.6

Provide smoke detectors in all living areas and corridors unless protected by approved automatic sprinkler system.

Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

Provide fire alarm system in Class A mercantile occupancies. Initiate by manual means.

Provide approved, supervised automatic sprinkler system as follows: Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system, a general alarni throughout the covered mall building, and an alarni signal is a continuously attended location for the purpose of initiating emergency action by trained personnel. This requirement also applies to bulk merchandising retail buildings.

Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the atrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

26-3.4.1 & .2 Provide fire alarm system when two or more stories above level of exit discharge or 50 or more occupants above or below level of exit discharge; 300 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system

26-3.2.1 Provide automatic extinguishing system in hazardous locations.

4-59 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 222: NEMA GUIDE CODE Fire Alarm & Detection System

INDUSTRIAL

28-3.2

28-3.4.1

284.1 (Amended)

STORAGE

29-3.4

2 9 -8.3.4

29-8.3.5 (Amended)

DAY CARE

30-3.4.1 & .2

In high hazard industrial occupancies, provide automatic extinguishing systems or other protection appropriate to the particular hazard.

Provide fire alarm system except if total capacity of building is less than 100 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

Provide automatic sprinkler protection in all high-rise buildings.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided. Initiate by either manual or automatic means.

Provide fire alarm system in parking garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

Provide automatic sprinkler protection.

Provide fire alarm system in day-care occupancies housed in more than one room. Fire alarm to be initiated by manual means and by operation o f required smoke detectors, except single-station, and required sprinkler systems.

4-60 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 223: NEMA GUIDE CODE Fire Alarm & Detection System

DAY CARE (continued)

30-3.4.5 Provide smoke detection system in each s toh and in the corridors of all floors occupied by day-care occupancy if housed in more than one room.

30-3.4.1 Provide automatic sprinkler protection. (Am ended)

30-6.3.4 (Am ended)

In day-care homes, provide single-station or multiple station smoke detectors or system detectors with integral sounding devices in all rooms used for sleeping and in any corridors serving a day-care home.

SPECIAL STRUCTURES AND HIGHRISE BUILDINGS

3 -2

32-7.3.1

32-8.2.1 & 32-8.3.1

Apply provisions to all buildings more than 75 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

Provide approved automatic sprinkler system in all areas and floor levels traversed in traveling to the exit discharge throughout windowless and underground structures with an occupant load of 50 or more. Exception: Existing structures with an occupant load 'of 100 or less.

In high-rise buildings, provide approved, supervised automatic sprinkler system and a fire alarm system with an approved emergency voice/alarm communication system throughout.

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from hazard in most occupancies, provide automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

5-2.3.10.1 & .2 Provide smoke detectors to activate both mechanical ventilation and pressurized stair enclosure systems.

4-61 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 224: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REOUIREMENTS íconîinued)

Statutory Requirements (7-7.1.2 & -5)

Snioke alarnzs are required to be powered by both alternating current and batteries if permit issued on or after October I , 1985. Snioke alarms; required to be powered by household electrical service ifpermit issued on or after October 1, 1976, and smoke alarnzs may be battery powered ifpermit issued prior to October 1. 1976.

An automatic sprinkler system is required throughout the,following: tx Al1 buildings f o r hunzan occupanc,v over four stories ( i f permit issued after October 1, 1973). ~3 Hotels and motels having six or more guest rooms and sleeping accommodations for more than 16persons (ifpermit issued after January 1, 1987). t3 Hotels and motels having more than four stories (ifpermit issued after October I , 1992). t3 Residential buildings having more than.four stories and occupiedprimari1,v by elderlypersons (ifpermit issued after Januaq I , 1995). t% Residential buildings having more than 12 living units and occupiedprimarily by elderly persons (ifpermit issued after January I , 1997).

4-62 Connecticut

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 225: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF DELAWARE Administrative Requirements

Amendments

Building Code

Regulations State written.

Fire Prevention Code

Preemptive Application

Promulgation

Enforcement

Co mm en t s

~

Code INone IDelaware State Fire Prevention

Mandatory statewide. Local jurisdictions may amend to make more stringent. State Fire Prevention Commission Office of the State Fire Marshal Delaware Fire Service Center 1537 Chestnut Grove Road Dover, DE 19904-96 10 (302) 739-4394 Local jurisdictions or Greg Haley, CFPS Chief Fire Protection Specialist State Fire Prevention Commission Office of the State Fire Marshal Delaware Fire Service Center 1537 Chestnut Grove Road Dover, DE 19904-96 10 (302) 7394394

State Fire Prevention Regulations adopts NFPA National Fire (

Summary of Amendments

other requirements as the minimum standard throughout the state. State Fire Prevention Regulations require automatic fire suppression systems in buildings more than 10,000 square feet or more than four stories or 40 feet in height, except as noted. See Chapter 3 for summary of NFPA 101 provisions and the following pages for additional fire protection of certain occupancies required by the State Fire Prevention Regulations.

Life Safety Code

1997NFPA 101

State amendments

Mandatory statewide. Local jurisdictions may amend to make more stringent. State Fire Prevention Commission Office of the State Fire Marshal Delaware Fire Service Center 1537 Chestnut Grove Road Dover, DE 19904-9610 (302) 739-4394 Local jurisdictions or Greg Haley, CFPS Chief Fire Protection Specialist State Fire Prevention Commission Office of the State Fire Marshal Delaware Fire Service Center 1537 Chestnut Grove Road Dover, DE 19904-96 1 O (302) 739-4394 Ides and Standards and adds

History: Building codes are enforced and administered at the county government level. New Castle and Kent Counties enforce the National Building Code for all occupancies. Sussex County enforces the Standard Building Code for multiple dwellings only.

4-63 Delaware

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 226: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF DELAWARE 1997 NFPA 101 and State Fire Prevention Regulations

Fire AlarnúDetection Systems

Automatic Fire Sprinkler Systems

~ ~~

Fire Alarm Systems

Required Required Required

Automatic Detection Systems

Hazardous areas Hazardous areas Required Reauired

NFPA-Occu anc I Underground

Assembly Class A Class B

Required Required

Special Amusement Educational

Reauired ~~

Required Required Required Required

Required Required Required Required

Required Required Required Required

Day Care Group Day Care

Health Care

)I Detention and Correctional Required Required Required

Required Required Hotels/Dormitories

Apartments

Lodging Houses

Required

Required Required Required Apartments

Lodging Houses Required Required Required

Required Reauired

Required Reauired

Required Reauired

Small Facilities Large Facilities

II Mercantile Required > 3 stories or

Required > 12,000 sq. ft.

~ ~ ~ _ _ _ _ ~ ~

Covered Malls Required

Required Required Required

> 300 persons

II Industria' Required

4-64 Delaware

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 227: NEMA GUIDE CODE Fire Alarm & Detection System

- Storage

> 10,000 sq. ft. or > 4 stories or > 40 fi.

Highrise Buildings > 40 fi.

Required

4-65 Delaware

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 228: NEMA GUIDE CODE Fire Alarm & Detection System

Section 4-1.1 (State Fire Regs)

Part II, Chapter 5 (State Fire Regs)

Part VI Chapter 1 (State Fire Regs)

Part VI Chapter 2 (State Fire Regs)

Part VI, Chapter 3 (State Fire Regs)

STATE OF DELAWARE 1997 Fire Prevention Regulations

Requirements and Exceptions to 1997 NFPA 101

Install automatic fire suppression systems in the following areas and occupancies: Buildings more than 10,000 square feet gross floor area except one- and two-family

dwellings, buildings of one story subdivided by Class B fire barriers into areas less than 10,000 square feet, and low hazard occupancies with not more than ten occupant load per State Fire Marshal;

All buildings four or more stories or 40 feet; Buildings or areas thereof used for storage, fabrication, assembling, manufacturing,

processing, display or sale of combustible goods, materials or products when more than two stories or 25 feet;

All basement areas more than 2,500 sq. ft; Residential occupancies of Type V (O,O,O) or Type III (2,0,0) construction more than

two stories or 25 feet or Type V ( l , l , l ) and Type III (2,1,1) or Type IV (2,H,H) construction more than three stories or 35 feet. Exceptions: Single lamily dwellirigs and attached one- or two-family dwelling units separated by two-hour rated construction;

All residential apartment building storage areas; Health-care occupancies per NFPA definitions; and Buildings defined as "high hazard" per 1997 NFPA 1 O1 or "extra hazard."

Provide automatic sprinkler systems in every building over 40 feet in height. Every high-rise building over 50 feet must be provided with a central control station and an alarm and communication system.

Provide automatic fire suppression systedautomatic sprinklers per NFPA 13D or 13R, in all intermediate care facilities for the mentally retarded. For the purposes of the state code, this facility is a group home for eight or fewer persons with mental retardation.

Bed and Breakfasts in one- and two-family dwellings include buildings containing not more than two dwelling units in which each living unit is occupied by members of a single family with no more than six outsiders, if any, accommodated in a maximum of three rooms. Provide a comprehensive smoke detection system through the structure.

Provide automatic corridor smoke detection system and a fire alarm system in all new apartment buildings except where each living unit has an exit door opening directly to the outside at ground level or where each living unit has direct access to an interior stair serving only that unit and separated from other portions by one-hour fire resistance. Install smoke detection system to activate building fire alarm system.

Provide an interior corridor and/or hallway and/or stairway smoke detection system in all new apartment buildings.

Install hardwired, battery back-up single station or multiple station smoke detectors in each individual living unit of new apartment buildings. Monitored battery powered smoke detectors may be provided in existing apartment buildings.

4-66 Delaware

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 229: NEMA GUIDE CODE Fire Alarm & Detection System

Part VI, Chapter 4 (State Fire Regs)

Provide interconnected, hardwired smoke detection devices and/or smoke detection systems in all new one- and two-family, mobile and modular home, and townhouse occupancies. Smoke detection devices installed in the immediate vicinity of each bedroom area are to be equipped with a built-in battery back-up power supply.

Provide smoke detection devices and/or smoke detection systems in any new and existing lodging, rooming, or boarding house; hotel, motel, or bed and breakfast facility; dormitory, apartment, or multi-family dwelling; board and care facility; or a residential occupancy by any other name installed per the State Fire Prevention Regulations or NFPA 101.

4-67 Delaware

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 230: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF FLORIDA Administrative Requirements

Preemptive Application

Promulgation

Enforcement

Code

Mandatory statewide. Except Mandatory statewide. Local for SFBC, local jurisdictions jurisdictions may amend to may amend to make more make more stringent. stringent. Richard W. Dixon Charles Clark Director Administrator Department of Insurance Department of Community Division of the State Fire Affairs Marshal 2555 Shumard Oak Boulevard 200 East Gaines Street, Suite Tallahassee, FL 32399-2100 664 (850) 487-1824 Tallahassee, FL 32399-0340

Local jurisdictions Local jurisdictions (850) 413-3600

~ ~~

Amendments

At present, all local governments in the state are required by law to adopt and enforce, as minimum standards, one of the codes listed in the matrix. Amendments are permitted without state approval if they are more stringent than the original code. The same applies for fire prevention. Each municipality, county, and special district with fire safety responsibility is required to adopt minimum fire safety standards that are to operate in conjunction with the state minimum building code that it has adopted. The Dade County Edition of the South Florida Building Code (SFBC) is enforced throughout Dade County and allows no local amendments. Contact: Metro Dade County Board of Rules and Appeals, 140 West Flagler Street, Suite 1603, Miami, FL 33130, (305) 375- 2901. 'The Broward County Edition of the South Florida Building Code (SFBC) is enforced throughout Broward County and allows no local amendments. Contact: Broward County Board of Rules and Appeals, 955 South Federal Highway, Suite 401, Fort Lauderdale, FL 333 16, (954) 765-4500. The EPCOT Codes are enforced throughout Walt Disney World. Contact: Reedy Creek Improvement District, P. O. Box 10170, Lake Buena Vista, FL 32830, (407) 828-2241.

Building Fire Prevention

1997 SBC or South Florida Building Code or EPCOT

199 1 SFPC or EPCOT Fire Prevention Code or NFPA 1 or South Florida Fire Prevention Code

~~

No state amendments INo state amendments

Comments

Life Safety Code

1994 NFPA 1 O 1 plus Uniform Fire Safety Rules of the State Fire Marshal

State amendments

Mandatory statewide. Local jurisdictions may not amend.

Charles Clark Director Department of Insurance Division of the State Fire Marshal 200 East Gaines Street, Suite 664 Tallahassee, FL 32399-0340

Local jurisdictions or Charles Clark Director Department of Insurance Division of the State Fire Marshal 200 East Gaines Street, Suite 664 Tallahassee, FL 32399-0340

(850) 413-3600

(904) 922-3170

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 231: NEMA GUIDE CODE Fire Alarm & Detection System

Summary of Amendments

4-69 Florida

See 1997 SBC and 1994 NFPA 101 in Chapter 3 for code provisions on fire aladdetection systems.

The Uniform Fire Safety Rules and Standards of the State Fire Marshal references NFPA National Fire Codes and Standards including NFPA 101, Life Safety Code.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 232: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Prior to October 1984, all code changes were made by legislative enactment. After October 1984, the Florida Board of Building Codes and Standards was delegated the responsibility for periodically updating, revising, amending, etc. the State Minimum Building Codes by administrative rule and regulation. No specific cycle was mandated. The Florida Building Commission is currently developing the Florida Building Code, which will replace all other building codes in the year 2001. The Commission selected the 1997 edition of the Standard Building Code as the foundation for the Code and recently began consideration of proposed modifications.

History: In response to a survey conducted in 1973, which showed that approximately 30 percent of Florida’s land area was not covered by building construction regulations of any type, the Florida Legislature mandated that all cities and counties adopt and enforce one of five statutorily referenced minimum building codes on an interim basis. The law further created a 15-member Board of Building Codes and Standards and charged that body with making recommendations for the adoption of a single uniform code within two years. The codes authorized on an interim basis were the Standard Building Code, the South Florida Building Code, the EPCOT Code (Disney World), the NFPA National Fire Prevention Code, and the One- and Two-Family Dwelling Code. History (continued):

If the latter was selected for one- and two-family dwellings, then the local jurisdictions are required to adopt and enforce one of the remaining four codes for other than one- and two-family dwellings.

In 1976, legislation was proposed to adopt the Standard Building Code statewide for all jurisdictions since it was the one most prevalently used through the state. This legislation failed and the five codes originally established on an interim basis were allowed to continue on a permanent basis. Local units of government are allowed to adopt more stringent requirements than those contained in the State Minimum Building Codes if there exists some unique conditions which warrant a more stringent requirement and the requirement is not discriminatory against construction materials, methods, or techniques of demonstrated or proven capability.

On July 3 1,1996, Executive Order 96-234 was signed by the Governor to create the Governor’s Building Codes Study Commission to evaluate the current effectiveness of, and through general consensus among the Commission members, recommend any necessary steps to reform the Florida building code system. As a result of the Commission’s report, the Florida Legislature passed HB 418 1 relating to a statewide, unified building code. The legislation charged the Florida Building Commission to adopt a set of codes for use statewide, which will be designated as the Florida Building Code. The statewide code will supersede a patchwork system in which more than 400 political jurisdictions develop, adopt, and enforce building code requirements.

470 Florida

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 233: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF GEORGIA Administrative Requirements

Building Code

Code 1994 SBC

Fire Prevention Code

1994 SFPC and Rules and

Amendments

Mandatory statewide. Local jurisdictions may amend to make more stringent with state

Regulations of the Safety Fire Commissioner based on NFPA National Fire Codes and Standards

Mandatory statewide. Preemptive Application

Promulgation

Enforcement

Andrea Lanier Andrea Lanier Manager, Codes and Industrial Manager, Codes and Industrial Buildings Buildings Georgia Department of Community Affairs Community Affairs Codes and Industrialized Buildings Section Buildings Section 60 Executive Park South, N.E., 3'd Floor 31d Floor Atlanta, GA 30329-2231

Georgia Department of

Codes and Industrialized

60 Executive Park South, N.E.,

Atlanta, GA 30329-2231 (404) 679-3 106 (404) 679-3 106

Local jurisdictions Local jurisdictions for most

Comments

occupancies or Dwayne Garriss Assistant State Fire Marshal Engineering Inspection Office of the Commissioner of Insurance Safety Fire Division/ State Fire Marshal 2 Martin Luther King, Jr. Drive Suite 620, West Tower Atlanta, GA 30334 (404) 656-0697

Life Safeíy Code

1997 NFPA 101

State amendments

Mandatory statewide for buildings other than one- and two-family dwellings or one- and two-family row houses separated by two-hour fire wall except as specified in Chapters 18, 19, and 20. Local jurisdictions may not amend. Dwayne Garriss Assistant State Fire Marshal Engineering Inspection Office of the Commissioner of Insurance Safety Fire Division/ State Fire Marshal 2 Martin Luther King, Jr. Drive Suite 620, West Tower Atlanta, GA 30334

Local jurisdictions for most occupancies or Dwayne Garriss Assistant State Fire Marshal Engineering Inspection Office of the Commissioner of Insurance Safety Fire Division/ State Fire Marshal 2 Martin Luther King, Jr. Drive Suite 620, West Tower Atlanta, GA 30334

(404) 656-0697

(404) 656-0697

4-71 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 234: NEMA GUIDE CODE Fire Alarm & Detection System

Summary of Amendments

See summary of 1997 Standard Codes in Chapter 3. The state’s amendments to 1997 NFPA 101 are shown on the following pages.

The State’s requirements for occupancy classifications or sub-classifications, fire sprinkler systems, fire alarm systems, and smoke detection systems shall be established by the Life Safety Code. However, for areas not specifically addressed in the Life Safety Code but addressed by the Georgia State Minimum Building Code, the Building Code shall be used as a supplement.

Code Change Cycle: State construction codes are promulgated, amended, and reviewed as necessary by the Georgia Department of Community Affairs with the approval of the Board of Community Affairs. Code actions may be initiated by the department or upon recommendation from any citizen, profession, state agency, political subdivision of the state, or the Codes Advisory Council of the department authorized by Georgia Law, Act No. 13 1 1.

Code Change Cycle (continued):

New provisions and amendments or modifications of existing minimum standard codes require, in addition to approval by the Community Affairs Board, the endorsement of a 2 1 -member advisory committee.

Codes are reviewed annually and amended as necessary. Complete new editions are published every three years. Public hearings are held on all proposed changes. In recent years, the State Codes Advisory Committee specifically voted to remain with the 1994 Standard Codes, as currently adopted. There are no plans to adopt the 1997 editions at this time. The Committee has authorized the formation of task forces to begin study of the International Codes.

History: Georgia’s permissive construction codes are designed to help protect the life, health, and property of all Georgians from the hazards of faulty design and construction; unsafe, unsound, and unhealthy structures and conditions; and the financial hardship resulting from unnecessarily high construction and operating costs of houses, buildings, and similar structures.

Local adoption of these standards is authorized by the Georgia Code, as amended, which states in part:

The governing authority of any municipality and the governing authority of any county in this state is hereby authorized to adopt such state minimum standard codes; to provide for the local administration of such codes; to require building permits and fixing charges therefore; and to provide for the inspection of buildings or similar structures to insure compliance with the standard codes. Said governing authorities may contract with each other or with the state to administer such codes, and to provide inspection and enforcement personnel and services necessary to insure compliance with the code. (GA.L.1969, pp. 546-556a. Code Ann. #84-6014)

4-12 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 235: NEMA GUIDE CODE Fire Alarm & Detection System

To assist local inspection officials in their code enforcement responsibilities, the Department of Community Affairs sponsors training programs conducted by the University of Georgia Institute of Government. In addition, the department provides on-site codes technical assistance, information, and referral services to requesting local governments.

By an act of the General Assembly, adopted March 1989, a new statewide uniform construction codes system went into effect October 1, 1991. The Act required mandatory statewide codes for building, gas, electrical, plumbing, mechanical, energy conservation, and the construction of one- and two-family dwellings.

4-73 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 236: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF GEORGIA 1997 NFPA 101 Use Group Classifications with State Amendments

ASSEMBLY

Buildings or portions thereof used for gathering at 50 or more people for deliberation, worship, entertainment, eating, drinking, amusement, or awaiting transportation. Includes special amusement buildings regardless of occupancy.

EDUCATIONAL

Buildings used for gathering groups of at least six people through the 12th grade for purposes of instruction for at least four hours per day or more than 12 hours per week.

"CARE

Buildings used for medical, treatment, or care purposes for persons having physical or mental problems as well as care of infants, infirm aged, and convalescents which provide sleeping facilities for four or more occupants generally incapable of self-preservation, such as hospitals, nursing homes, and limited care facilities.

DETENTION AND CORRECTIONAL

Buildings used to house those under some degree of restraint and who are mostly incapable of self-preservation due to security measures beyond their control.

RESIDENTIAL

Buildings where sleeping accommodations provided for normal residential purposes, except health care or detention and correction facilities. Includes hotels, motels, dormitories, apartments, lodging or rooming houses, board and care facilities, and one- and two-family dwellings. Sub-classify as follows:

Hotels, Motels and Dormitories - Buildings or groups of building under same management with more than 16 sleeping accommodations for hire or providing group sleeping accommodations for more than 16 persons not in same family group without individual cooking facilities.

Apartments - Buildings with more than three living units with individual cooking and bathroom facilities. RESIDENTIAL (continued)

Lodging or Rooming Houses - Buildings with separate sleeping rooms for less than 16 people without separate cooking facilities.

Residential Board and Care (Amended) - Buildings used to provide lodging and boarding for four or more residents unrelated by blood or marriage, for the purpose ofprovidingpersonal care services. Any facility providing lodging and boarding and personal care for,four or more residents who are mostly incapable of seljpreservation because ofphysical or mental disability shall be classijìed as a health care occupancy.

One- and Two-Family Dwellings - Buildings containing maximum two dwelling units.

4-74 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 237: NEMA GUIDE CODE Fire Alarm & Detection System

k MERCANTILE

Buildings or structures for display and sale of merchandise. Minor incidental mercantile operations in buildings of different occupancy subject to exit requirements of main occupancy.

BUSINESS

Buildings, other than mercantile, used for maintaining accounts, records, and similar purposes. When minor and incidental to another occupancy, apply provisions applicable to that occupancy.

INDUSTRIAL

Factories making all kinds of products and properties devoted to processing, assembling, mixing, finishing, packaging, and repairing. Includes laboratories involving hazardous chemicals, laundries, power plants, pumping stations, etc.

STORAGE

Buildings or structures used primarily for storage and sheltering of goods, products, animals, or vehicles. Treat minor incidental storage in another occupancy as part of that occupancy.

DAY CARE

Buildings or portions of buildings where four or more clients receive care, maintenance and supervision by a non- relative for less than a 24-hour period.

4-75 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 238: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF GEORGIA 1997 NFPA 101 with State Amendments

Fire Alarm/Detection Systems

Automatic Fire NFPA - Occupancy Sprinkler Systems

Assembly Required Underground Special Amusement Required

Educational Required

Health Care Required

Detention and Correctional Required

Fire Alarm Automatic Systems Detection Systems

Required Hazardous areas Required Required

Required Required Required

Required Required

Required Required

Hotels/Dormitories Required Required Required

Apartments Required > 3 stories Required

4-76 Georgia

Lodging Houses Required Required Required

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Mails

Atriums

Business

Industrial

Required Required Required Required Required Required > 3 sales levels or Required > 30,000 sq. ft. Required Required

Required Required Required

> 300 persons

High hazard Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 239: NEMA GUIDE CODE Fire Alarm & Detection System

Storage Required

4-77 Georgia

Highrise Buildings

Day-care

> 75 ft. > 75 ft.

Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 240: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF GEORGIA 1997 NFPA 101 with State Amendments

Requirements and Exceptions

ASSEMBLY OCCUPANCIES

84.5.5

84.5.10

8-3.4.1

8-3.4.2.2

8-3.5.1

84.3.3.4

84.3.5

84.2.1

In proscenium opening, provide emergency ventilation to remove smoke and independently activated by sprinkler system in stage area, smoke detectors over stage area, and by manually operated switch at approved location.

Provide approved automatic sprinkler system for stages, in permanent dressing rooms, storerooms and workshops, and other accessory spaces contiguous to stage. Exception: Stages 1,000 square feet or less in area and 50 feet or less in height and under stage areas less than four feet in height.

Provide approved fire alarm system in assembly occupancies with occupant load of 300 or more and in Lheaters with more ihari one audience-viewing mom. Initiate alarm by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of assembly occupancies with occupant load of 300 or more unless protected by automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout story of assembly occupancy with occupant load of 300 or more, throughout the story below assembly occupancy, and when below level of exit discharge, throughout intervening levels and exit discharge level. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Participant sports areas with audience less than 300 people.

Provide automatic smoke detection throughout each smoke compartment of underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved, automatic sprinkler system in all enclosed areas with walls and ceilings in buildings or structures containing smoke-protected assembly seating.

4-78 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 241: NEMA GUIDE CODE Fire Alarm & Detection System

ASSEMBLY OCCUPANCIES (continued)

8-7.5.3.7 Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling.

8-4.7.2 & .3 Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke detection to sound an alarm, illuminate means of egress and stop confusing sounds.

EDUCATIONAL

10-3.2.1

10-3.4.1

10-3.5

10-4.1.3 & .6

10-4.1.3.4

HEALTHCARE

12-2.2.2.6

12-3.4.1.1 & 12-3.4.2

12-3.4.5.3

Provide automatic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies unless maximum area is 1,000 square feet with single classroom and not location to another building not less than 50 feet.. Exception: May omit manual pull stations in locations per administrative authority in buildings with two-way communication between normally occupied spaces and constantly attended receiving station, and when conditions of Section 10-3.4.2.3 are met.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Provide smoke detection system throughout each smoke compartment.

The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

Provide fire alarm system equipped with a secondary power supply and initiated by manual means and by required sprinkler and detection systems.

In nursing homes, provide approved automatic smoke detection systems in corridors throughout smoke compartments containing patient sleeping rooms and in spaces open to corridors unless excepted by this section. Detection systems are to be provided with a secondary power supply.

4-79 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 242: NEMA GUIDE CODE Fire Alarm & Detection System

12-3.5.1 Provide approved, supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

12-6.3.4.1 & .2 Provide fire alarm system in all ambulatory health-care centers initiated by manual means and by means of any required detection devices or system.

12-6.3.7.7 Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or complete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

DETENTION AND CORRECTIONAL

14-3.4.1.1 & .2 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4 Provide approved automatic smoke detection throughout all resident sleeping areas and adjacent day rooms, activity rooms, and contiguous common spaces. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from sleeping rooms with more than four occupants.

14-3.5.2 Provide automatic sprinkler system according to type of construction used.

16-3.4.1 & .2 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system. Exception: Sleeping room smoke detectors need not initiate fire alarm system.

Provide corridor smoke detection system in all interior corridors, halls, and passagewa.vs except when protected throughout by approved, supervised automatic sprinkler system. Install approved single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite. In addition, a 1 -1/2 hour emergency power supply source is required for the back-up power of the detector.

16-3.4.4.1 & .2 (Amended)

4-80 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 243: NEMA GUIDE CODE Fire Alarm & Detection System

HOTELS/DORMITORIES (continued)

16-3.5.2 Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest, sleeping rooms have a door that opens directly outside at ground level. Install quick response or listed residential sprinklers throughout guest rooms and suites.

18-3.4.4.1 (Amended)

183.5.2

Provide fire alarm system for buildings more than three stories or with more than 11 living units except where each living unit is separated from other units by fire barriers with not less than 1-hour rating and has independent exit, exit stairway, or ramp discharging to grade or in buildings not more than four stories or 16 dwelling units protected with an automatic sprinkler system. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single -station smoke detectors powered by house electrical service on all levels and in and outside sleeping rooms of every living unit within apartment buildings. In addition, a I -1/2 hour emergencypower supply source is required for the back-up power of the detector. Install snioke detector to initiate an alarni audible in the unit’s sleeping rooms. This individual detector is in addition to any sprinkler system or other detection system installed in the building.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings where every living unit has either an exit door opening directly to ground level, direct access to an outside stair that serves no more than two units on same floor, ordirect access to an interior stair serving only that unit with a one-hour fire resistance rating fire barrier from other portions of building. Install quick response or listed residential sprinklers throughout all living units.

LODGING OR ROOMING HOUSES

20-3.3.1 Provide fire alarm system except when equipped with smoke detection system that includes at least one manual fire alarm station.

20-3.3.4 Provide approved single -station smoke detectors powered by building’s electrical service in every sleeping room.

20-3.5.2 Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway.

ONE AND TWO-FAMILY DWELLINGS

21-3.3.1 Provide approved single-station smoke detectors powered by building’s electrical system in all sleeping rooms, outside and in the immediate vicinity of sleeping rooms, and on each additional story including basement.

4-81 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 244: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTIAL BOARD CARE

Small Facilities 22-2.3.4.1 -3

22-2.3.5.1

Provide manual fire alarm system and approved smoke detectors powered by house electrical system throughout every area. Each sleeping room must be provided with approved, listed single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

Provide approved automatic sprinkler system using quick response or residential sprinklers.

Large Facilities 22-3.3.4.1 & .2 Provide fire alarm system to be initiated by manual means, by a manual fire alarm

station located at a supervised central location, and by any automatic sprinkler and detection systems.

22-3.3.4.7 (Am ended)

22-3.3.4.8 (Amended)

22-3.3.5.1

MERCANTILE

24-3.4.1 & .2

24-3.5.1 & .2

Provide approved single-station smoke detectors in each sleeping room of large facilities powered from building electrical system and be provided with a 1 -1/2 hour emergency power source.

Provide smoke detectors in all common spaces and corridorsper NFPA 72 and arranged to initiate the fire alarm.

Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

Provide fire alarm system in Class A mercantile occupancies. Initiate by manual means.

Provide approved, supervised automatic sprinkler system as follows: Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

4-82 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 245: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

244.4.3.1 & .2 Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system. This requirement also applies to bulk merchandising retail buildings.

ATRIUMS

6-2.4.6 Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the atrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

26-3.4.1 & .2 Provide fire alarm system when two or more stories above level of exit discharge or 50 or more occupants above or below level of exit discharge; 300 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system.

26-3.2.1

INDUSTRIAL

28-3.2

28-3.4.1

STORAGE

29-3.4

2 9 -8.3.4

Provide automatic extinguishing system in hazardous locations.

In high hazard industrial occupancies, provide automatic extinguishing systems or other protection appropriate to the particular hazard.

Provide fire alarm system except if total capacity of building is less than 100 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided. Initiate by either manual or automatic means.

Provide fire alarm system in parking gaxages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

4-83 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 246: NEMA GUIDE CODE Fire Alarm & Detection System

DAY CARE

30-3.4.1 & .2

30-3.4.5

30-3.5 (Am ended)

304.3.4

Provide fire alarm system in day-care occupancies housed in more than one room. Fire alarm to be initiated by manual means and by operation of required smoke detectors, except single-station, and required sprinkler systems.

Provide smoke detection system in each story and in the corridors of all floors occupied by day-care occupancy if housed in more than one room.

In day-care homes, smoke detectors are required to be installed in ali rooms used for sleeping and in any corridors serving a day-care home.

Provide sprinkler system throughout all buildings containing da,v-care occapanciesper construction types as specij7ed in table of this code.

SPECIAL STRUCTURES AND HIGHFUSE BUILDINGS

3 -2 Apply provisions to all buildings more than i 5 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

32-7.3.1 Provide approved automatic sprinkler system in all areas and floor levels traversed in traveling to the exit discharge throughout windowless and underground structures with an occupant load of 50 or more. Exception: Existing structures with an occupant load of 100 or less.

32-8.2.1 & 32-8.3.1

In high-rise buildings, provide approved, supervised automatic sprinkler system and a fire alarm system with an approved emergency voice/alarm communication system throughout.

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from hazard in most occupancies, provide automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

5-2.3.10.1 & .2 Provide smoke detectors to activate both mechanical ventilation and pressurized stair enclosure systems.

4-84 Georgia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 247: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF HAWAII Administrative Requirements

Building Cade

Code None

Amendments

Preemptive Application

Fire Prevention Code

1988 UFC with 1989 and 1990 supplements State amendments

Adoption by local jurisdictions is voluntary.

Promulgation >ocal jurisdictions

Local jurisdictions Enforcement

Charles Wassman State Fire Council Administrator State Fire Council Department of Labor and Industrial Relations 3375 Koapaka Street, H425 Honolulu, HI 968 19

Local jurisdictions (808) 831-7778

Comments

Summary of

Life Safety Code

I

The State Fire Code as amended is the minimum code allowed for local jurisdictions to adopt. State delegates code adoption and enforcement to local jurisdictions. The State Fire Code will be updated to a later edition by the fall of 1999. See the following pages for a summary of the State Fire Code.

None

I Amendments

Code Change Cycle: Generally, the state agency administering the code reviews the requirements yearly or as often as the model codes change.

If a change in the regulations is deemed necessary, the procedure for amending the rules is initiated. This process is covered by statutes and includes a public hearing. References to model codes in the regulations must include the edition number and date.

History: The statute on Environmental Quality, Chapter 342 of the Hawaii Revised Statutes (HRS), was effected on May 22, 1972, as Act 100, Session Laws of Hawaii, 1972, and the following regulations adopted or amended therefore:

4-85 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 248: NEMA GUIDE CODE Fire Alarm & Detection System

History (continued):

1. Air Pollution Control, Title II, Chapter 60 2. Ambient Air Quality Standards, 11-59 3. Vehicular Noise Control for Oahu, 11-42 4. Community Noise Control for Oahu, 1 1-43 5. Solid Waste Management Control, 11-58 6. Water Pollution Control, 11-55 7. Water Quality Standards, 11-54

The elevator code requirement, Chapter 132 of the HRS, was introduced by Act 24, SLH 1972, and covered buildings constructed after July 1, 1974.

Historic Preservation Program, Chapter 6E, HRS, was started by Act 104, SLH 1976.

486 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 249: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF HAWAII 1988 Uniform Fire Code (ICBO) with State Amendments

Fire Alarm/Detection Systems

Occupancy Type

Group A - Assembly

B-2 - Retaimrinking

II II Group E - Educational

Group H - Hazardous H-1 - Flammables/

Explosives H-2 - Moderate

Explosion Hazard H-3 - HighHazard H-4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group R - Residential R-1 - Hotelhîultifamily

High-rise - New and Existing Construction B-2 - Offices R-1 - Hotelh4ultifamily

Automatic Fire Sprinkler Systems

Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Fire Alarm Systems

Required

Required

> 50 occupants

Required

Required

~- Automatic

Detection Systems

Required

Required

Required

I Required Required Required

Required Required Required

> 3 stories > 3 stories

> 75 ft. > 75 ft.

> 75 fi. > 75 ft.

I Required Required

Required I Required

4-87 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 250: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF HAWAII 1988 Uniform Fire Code with

1989 and 1990 Supplements and Hawaii State Amendments Requirements and Exceptions

GROUP A - ASSEMBLY

Section 10.306 (Fire Code) (Am ended)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area.

ta Stairs and enclosed usable space below or over stairs in Group A divisions 2, 2.1,3, and 4. ta Under roof and gridiron, tie and fly galleries, proscenium walls of stages, platforms more than 500 square feet, dressing rooms, workshops, and storerooms. ta Wall of stages; over and within permanent platfórms in excess of1,OOO square feet in area.

Exhibition and display rooms more than 12,000 square feet

Section 14.104 (Fire Code) (Amended)

GROUP B - BUSINESS

Section 10.306 (Fire Code)

Section 14.104 (Fire Code) (Amended)

Provide approved electrically supervised manual.fii-e alarm systems in Group A occupancy assemblies having a capacity of 300 or more persons. Provide audience or seating area with approved visual alarm devices.

Provide automatic fire extinguishing system in Group B-2 occupancies in retail sales areas where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or when more than three stories.

Provide manualfire alarm system in Group B-2 office buildings (75 feet or more in height) havingfloors used fo r human occupancy located more than 75 feet above the highest grade.

Provide approved electrically supervised manual f ire alarm system for Group B-2 buildings under 75 feet in height but three or more stories in height, with occupant load of 1 O0 or more above or below the level of exit discharge, or the occupancy is subject to 1,000 or more total occupants. Manualfire alarm pull stations are not required for fire alarm systems if building protected thcoughout by approved automatic sprinkler system, or approvedfire detectionialarm initiation systems.

4-88 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 251: NEMA GUIDE CODE Fire Alarm & Detection System

Section 14.104 (Fire Code) (Amended) (Continued)

Provide approved electrically supervised nianual fire alarm system in Group B-2 retail and wholesale stories with aggregate gross area of 3,000 square feet or more, or with more than three floor levels, or having a.floor below the street,floor level for sales purposes. Manua1,fii-e alarm pull stations are not required for.fire alarm systems if building protected throughout by approved automatic sprinkler system, or approved fi re detection/alarrn initiation systems.

Provide annunciator panel on the first floor lobby area for Group B occupancies four or more stories in height. Locate manualfire alarm box adjacent to required exit doors and elevator lobby.

GROUP E - EDUCATIONAL

Section 14.104 (Fire Code) (Amended)

Provide approved electrically supervised manua1,fire alarni system in Group E occupancies with occupant capacity of over 50persons. I f building equipped with an automatic,fire extinguishing or detection s,vsteni, install so that it will automatically activate the school fire alarm system.

GROUPH -HAZARDOUS

Sections 14.104 (Fire Code) (Amended)

Section 10.306 (Fire Code)

Chapter 81 (Fire Code)

Provide approved automatic or electrically supervised manualjre alarm system in Group H occupancies with floor area of 1,000 square feet or more or with a total occupancy capacity of 100persons or more, or if25persons or more are employed above or below the level of exit discharge.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Provide supervised smoke detection throughout areas with high-piled combustible storage with Class I - V materials per limits in the Fire Code.

4-89 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 252: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTlTUlTONAL

Section 10.306 (Fire Code)

Provide automatic fire extinguishing system throughout.

Section 14.104 (Fire Code) (Amended)

Provide,fiïe alarm systems in Group I occupancies.

GROUP R - RESIDENTIAL

Section 10.306 (Fire Code) (Amended)

Section 14.104 (Fire Code) (Am ended)

Provide automatic sprinkler system in apartment house over one story and containing 16 or more dwelling units and hotels over one story and containing 20 or more guest rooms. Residential or quick-response sprinkler heads to be provided in dwelling units and guest rooms.

Provide manua1,fire alarni system in Group R-1 occupancies havingfloors used JOY human occupancy located more than 75 f ee t above the highest grade.

Provide approved automatic alarm system or electrically supervised manual fire alarm system for Group R occupancy apartments, dormitories, and room houses three or more stores or containing more than I5 apartments and every hotel three or more stories or containing 20 or more guest rooms. Provide manualjre alarm pull stations adjacent to exit doors or elevator lobb,v ifrequired b y j r e official. The alarm system is to include provisionsf or smoke detection and manual operation in interior corridors and automatic detection in storage rooms, laundry rooms, equipment rooms, and similar common areas. Buildings not over two stories are exceptedfrom alarm system r*equirement i f one-hourjre-resistive occupancy separations used and each dwelling unit has exit to outside.

Provide smoke detectors in each dormitovy or rooming house of non-fire resistive construction and more than one story with interior exit corridors, interior stairways, or rooms with community -type cooking facilities.

Provide annunciator panel in first floor lobby area and manualjre alarm box at exit doors and elevator lobby ofall buildings four stories or more in height.

490 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 253: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION, GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 14.104 (Fire Code)

Provide fire alarm and communication systems for Group B-2 offices and Group R-1 occupancies with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

HIGHRISE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES, EXISTING STRUCTURES

Appendix 1 -B (Fire Code)

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, and public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide fire alarm system connected to an approved central station or local fire department dispatch office. Provide smoke detectors in sleeping area of dwelling unit, hotel suite, or guest room.

Section 10.306 (Fire Code) (Amended)

Except in Group R-3 and M occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 10.306; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults.

4-91 Hawaii

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 254: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF IDAHO Administrative Requirements

Building Programs Manager Idaho Division of Building Safety 277 North Sixth Street Statehouse Mail Boise, ID 83720-6000 (208) 334-3896

I Building Code

Summary of

Code I 1997 UBC

inspection will be subject to the provisions adopted by the state. See 1997 Uniform Codes and 1997 NFPA 101 summaries in Chapter 3 for fire a ldde tec t ion

Amendments INo state amendments

Preemptive Application

Promulgation

Enforcement

Comments

Fire Prevention Code

1997 UFC

State amendments

Mandatory statewide. Local jurisdictions may amend to make more stringent.

Don McCoy State Fire Marshal Department of Insurance State Fire Marshal 700 West State Street Boise, ID 83720 (208) 334-4370

Local jurisdictions

IIf a local jurisdiction contracts with the state for d a n review an

Life Safetv Code

1997NFPA 101 ~~

No state amendments

Mandatory for state-owned and public schools. Voluntary for all other occupancies.

Jack Rayne Building Programs Manager Idaho Division of Building Safety 277 North Sixth Street Statehouse Mail Boise, ID 83720-6000

Jack Rayne Building Programs Manager Idaho Division of Building Safety 277 North Sixth Street Statehouse Mail Boise, ID 83720-6000 (208) 334-3896 inspection, the review and

(208) 334-3896

Amendments Isystem requirements. The state amendments do not affect where these systems are required.

Code Change Cycle: The state is on a three-year cycle concurrent with the publication of new editions of the Uniform Codes and the National Electrical Code.

History: The State of Idaho's first building code was enacted in 1975 and enforced by the Department of Labor and Industrial Services or the local city or county jurisdictions. Since March 1977, code enforcement in Idaho is optional, permitting jurisdictions to establish their own code programs or not even adopt codes.

4-92 Idaho

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 255: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF ILLINOIS Administrative Requirements

Mandatory for all buildings except 1 and 2 family dwellings and public school buildings. Local jurisdictions ,may amend to make more

Code

stringent. i Office of the State Fire

Amendments

Local jurisdictions

Preemptive Application

Marshal Division of Fire Prevention 1035 Stevenson Drive Springfield, IL 62703-4259 (217) 785-4714 Local jurisdictions or Jack Ahern Deputy State Fire Marshal Office of the State Fire Marshal Division of Fire Prevention 1035 Stevenson Drive Springfield, IL 62703-4259 (217) 785-4714

Promulgation

Enforcement

Comments

Summary of Amendments

Building Fire Prevention

Codes and Standards

Local jurisdictions.

Life Safety Code

1991 NFPA 101

No amendments

Mandatory for all buildings except 1 and 2 family dwellings and public school buildings. Local jurisdictions may amend to make more stringent. Office of the State Fire Marshal Division of Fire Prevention 1035 Stevenson Drive Springfield, IL 627034259 (217) 785-4714 Local jurisdictions or Jack Ahern Deputy State Fire Marshal Office of the State Fire Marshal Division of Fire Prevention 1035 Stevenson Drive Springfield, IL 627034259 (217) 785-4714

State amendments to NFPA 101 speciQ the difference between day-care centers, day-care homes, and group day-care homes. The state applies the 1985 edition ofNFPA 101 to existing buildings. See Chapter 3 for 1991 NFPA 101 fire alanddetection requirements.

4-93 Illinois

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 256: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule for code revisions. Codes are reviewed yearly for possible revisions. After the proposed rules are published in the Illinois Register, there is a 45-day comment period during which any interested person or organization may comment on the proposal. After this period, there is another 45-day period in which the rules are reviewed by the state's Joint Committee on Administrative Rules. It generally takes about six months from the date the rules are drafted until they are promulgated.

History: The State of Illinois does not have a statewide building code, which regulates the construction of all types of buildings. As a result, the requiremenls for the construction of a building varies from very little to quite extensive depending on the location within the state. There are a number of minimum statewide codes that regulate certain parts or types of buildings. These include accessibility standards, fire safety requirements, manufactured housing codes, codes for the construction and operation of health-care facilities, swimming pool requirements, school construction codes, and a plumbing code and license law.

494 Illinois

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 257: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF INDIANA Administrative Requirements

Building Code

Code 1997 UBC

Fire Prevention Life Safeîy Code Code

1997 UFC None ____

Amendments I State amendments I State amendments I Mandatory. Local jurisdictions may amend to make more stringent only with

Preemptive Application

Mandatory.

Promulgation state approval. Indiana Fire Prevention and Building Safety Commission Indiana Government Center South 402 West Washington Street, Room W246 Indianapolis, IN 46204-2739

Indiana Fire Prevention and Building Safety Commission Indiana Government Center South 402 West Washington Street, Room W246 Indianapolis, IN 46204-2739

Enforcement

Comments

(317) 232-1402 Local jurisdictions or

(317) 232-1402 Local jurisdictions or Marlys Pedtke Director, Technical Services and Research Division Indiana Fire Prevention and Building Safety Commission Department of Fire and Building Services Indiana Government Center South 402 West Washington Street, Room W246 Indianapolis, IN 46204-2739

State codes apply to all buildin (317) 232-1402

Marlys Pedtke Director, Technical Services and Research Division Indiana Fire Prevention and Building Safety Commission Department of Fire and Building Services Indiana Government Center South 402 West Washington Street, Room W246 Indianapolis, IN 46204-2739

Summary of Amendments

(317) 232-1402 s except one- and two-family d

buildings. State fire code defers all fire protection system requirements to those in building code. State adds new classification and smoke detector requirements for bed and breakfast establishments. See the following pages for a summary of state requirements.

ellingsänd agricultural

Code Change Cycle: The following process was instituted on July 1, 1984, resulting from the creation of the Fire Prevention and Building Safety Commission as the single rule-making body for statewide building and fire codes. A feature of Indiana law precludes any subordinate unit of government from writing ordinances on any fire or building issue addressed by the Commission.

Each adopted model code is reviewed on an annual basis following publication of annual supplements by the model code organizations. If warranted, important revisions are adopted and subsequently placed in effect. The adopted code is re-promulgated on a three-year cycle as new editions are published by the model code organizations.

4-95 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 258: NEMA GUIDE CODE Fire Alarm & Detection System

The Division of Technical Services and Research provides staff support to the Commission. The division forms and chairs ad hoc advisory committees to evaluate and suggest revisions to new model code editions. A proposed rule to adopt and amend a code is reviewed by the Commission prior to publication in the Indiana Register. Following publication and a public hearing, the rule may be adopted by the Commission. If adopted, it is reviewed for legality by the attorney general, approved by the governor, and published as a final rule with a fixed future effective date.

The process of revision and adoption of a major model code takes about eight months, including a time allowance for code distribution, amendment of local ordinances, and conduct of state level outreach training. Model codes that are adopted with little or no change can be promulgated in about four months.

History: Indiana's state building regulatory program began with legislation in 1909 to establish minimum standards for dwellings. Subsequent legislation in 191 3 and 1917 expanded the scope of enforcement, and in 1923 the General Assembly established a state agency with power to adopt and maintain a mandatory statewide building code. The Indiana Administrative Building Council was given broad rule-making powers, but enforcement was intended to be a function of local government.

Legislative action in 1969 created the Office of the State Building Commissioner to provide administrative support for the Council. Mandatory plan review for all buildings (except single family residences and farm buildings), while previously required, could now be fully implemented with the establishment of operational divisions for plan review and code enforcement. The new agency was established without general fund appropriations and was expected to earn enough from plan review fees and manufactured housing inspection seals to cover its agency expenses. This limitation was successful, but limited the agency in its field inspection functions, which produced no revenue. Local government continued to exercise primary code enforcement responsibility; but many rural counties and towns did not employ building officials or inspectors.

In 1973, the Office of the State Fire Marshal was given authority to perform plan review for new construction in fire safety related areas. This legislation, to some extent, fragmented what had previously been a centralized function. The independent Fire Prevention Commission could not keep pace with its rule -making responsibilities.

in 1984, the General Assembly created a new Fire Prevention and Building Safety Commission to replace the Administrative Building Council, Fire Prevention Commission, and Board of Elevator Safety. On July 1, 1984, the new Commission assumed all rule-making powers for buildings and building systems except for boiler and pressure vessels. A new Department of Fire Prevention and Building Safety (subsequently renamed the Department of Fire and Building Services) was concurrently established to merge all of the previously autonomous state fire and building regulatory agencies in one location under the control of an Executive Director. The Office of the State Building Commissioner and the State Fire Marshal were restructured within the unified department.

Indiana's code development and enforcement program is now a fully integrated process with a single rule-making and code adoption body, and a single administrative department with common management, education, information, data processing, and technical services and research responsibilities.

4-96 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 259: NEMA GUIDE CODE Fire Alarm & Detection System

STAm OF INDIANA 1997 Uniform Codes (ICBO) with State Amendments

Use Group Classifications

GROUP A -ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1 Assembly building with stage and occupant load of 1,000 or more.

A-2

A-2.1

A 3

A 4

Building or portion thereof having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Building or portion thereof with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUP E - EDUCATIONAL

Sub-classify in divisions as follows:

El

E2

Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

4-97 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 260: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

E 3 (Amended)

Buildings used for day-care purposes for more than six persons, except Child I or II child-care homes licensed by the state or child-care ministries registered by the state.

GROUP F - FACTORY AND INDUSTRIAL

Building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations. Sub-classify in divisions as follows:

F-1 Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

F-2 Low-hazard factory and industrial occupancies including facilities producing noncombustible or non-explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1

H-2

Buildings with quantity of material in excess of building code limitations which present high explosion hazard, including but not limited to: ta Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use o f pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days. La Manufacturing of Class 1.4G fireworks. La Unclassified detonatable organic peroxides. La Class 4 oxidizers. ta Class 4 or Class 3 detonatable unstable (reactive) materials.

Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to: ta Class I organic peroxides. ka Class 3 nondetonatable unstable (reactive) materials. La Pyrophoric gases.

Flammable or oxidizing gases.

4-98 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 261: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS (continued)

H-2 (cont.) ta Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in closed containers pressurized at more than 15 psi gauge. Exception: aerosols.

Class 3 oxidizers. ta Class 3 water-reactive materials.

H-3

H 4

H-5

H-6

H-7

Buildings with quantity of materials in excess of building code limitations which present high fire or physical hazard, including but not limited to: G Class II, III, or IV organic peroxides. ta Class 1 or 2 oxidizers. G Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed containers or systems and containers pressurized at 15 psi gauge or less, and aerosols. ta Class III-B combustible liquids. ta Pyrophoric liquids or solids. + Class i or 2 water-reactive materials. ta Flammable solids in storage. ta Flammable or oxidizing cryogenic fluids (other than inert).

Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

Repair garages not classified as Group S-3.

Aircraft repair hangars and heliports not classified as Group S-5.

Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to:

ta Highly toxic materials. 0 Irritants. ta Sensitizers. ta Other health hazards.

Corrosives, except stationary lead-acid battery systems.

499 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 262: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL

Sub-classify in divisions as follows:

1-1.1 Nurseries for full-time care of children under the age of six, hospitals, sanitariums, nursing homes with non-ambulatory patients, and similar buildings, each accommodating more than five persons, except buildings used only for private residential purposes for fàmily group.

1-1.2

1-2

1-3

Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

Nursing homes for ambulatory patients, homes for children six years old or over, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

Mental hospitais, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates similarly restrained, except buildings used only for private residential purposes for family group.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL

Sub-classify in divisions as follows:

R-1

R-2 (Amended)

R-3 (Amended)

Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

Bed and breakfast establishments.

Dwellings and lodging houses in buildings of mixed occupancy having two or less dwelling units, and congregate residences, each accommodating ten persons or less.

4-10 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 263: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

s-1

s -2

s -3

S 4

s -5

GROUP U - UTILITY

Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

Repair garages and parking garages not classified as S-4.

Open parking garages.

Aircraft hangars and helistops.

Sub-classi@ in divisions as follows:

u1 Private garages, carports, sheds and agricultural buildings.

u 2 (Amended)

Tanks and towers. (State deletes fences over 6 feet.)

4-101 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 264: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF INDIANA 1997 Uniform Codes (ICBO) with State Amendments

Fire Alardetection Systems

Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business

Group E - Educational

Group F - Factory Industrial ~ _ _ _

Group H - Hazardous H-1 - Flammables/

H-2 - Moderate Explosives

Explosion Hazard H-3- &&Hazard H-4 - Repair Garages Hd - Semiconductor Facilities H-7 - Health Hazards

Group I - Instiîutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group M - Mercantile

Group R - Residential R-1 - Hotel/Multifamily

Group S - Storage

High-rise -New and Existing Construction B-2 - Offices R-1 - Hotelh4ultifamily

Covered Maus

Aviation Control Towers

Automatic Fire Sprinkler Systems

Required Reauired Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. ft. total

> 3 stories

Required

> 75 fi. > 75 fi.

Required

Systems

Required Reauired Required

50 occupants

Required

Required

Required Required Required

~

> 3 stories

> 75 fi. > 75 ft.

Required

Required

Automatic Detection Systems

Reauired Required

Required

Required

Required Required Required

> 3 stories

> 75 fi. > 75 fi.

Required

Required

4-102 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 265: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF INDIANA 1997 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area.

Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A 4 ta Multi-theater complexes. ta Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. ta All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages.

1,000 square feet, or in conjunction with outdoor seating. Smoke-protected assembly seating, except press boxes, storage less than

Section 303.9 (Building Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

Section 1007.2 (Fire Code) (Amended)

The state fire code deletes text of 1997 UFC Section 1007.2 in its entirely and refers all requirements for an approved manual automatic or manual and automatic f ire alarm system to the Indiana Building Code.

Section 408 (Building Code) (Amended)

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems. (State deletes substitution.)

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

4-103 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 266: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Section 305.9 (Building Code)

Section 904.2.4 (Building Code)

Section 1007.3.4 (Building Code)

Provide approved smoke detectors to activate all autonmtic-closing fire assemblies installed in the atmospheric separation.

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code)

Provide automatic fire -sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

GROUPH -HAZARDOUS

Section 307.9 (Building Code) and Sections 50 13 . l , and Article 80 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

4-104 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 267: NEMA GUIDE CODE Fire Alarm & Detection System

Section 307.11 (Building Code)

Section 904.2.6 (Building Code)

GROUP I - INSTITUTIONAL

Section 308.9 (Building Code)

Section 308.10 (Building Code)

Section 1007.2 (Fire Code) (Am ended)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Appendix Chapter 3, Division 1 (Building Code)

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signai to emergency control station.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Provide approved manual and automatic fire alarm system in all Group I occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

The statefire code deletes text of I997 UFC Section 1007.2 in its entirely and refers all requirements.for an approved manual automatic or manual and automatic fire alarni system to the Indiana Building Code.

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and I- 2 .

Alternative provisions for Group 1-3 housing with more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire alarm system.

4-105 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 268: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.8 (Building Code) and more than three stories. Section 1003.2.8 (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) (Amended)

Section 310.10 (Building Code)

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and guest rooms in hotels, lodging houses, and bed and breakfast establishments used for sleepingpurposes. Installed per manufacturer's instructions. Excepted are totally sprinkled buildings. Primary power shall be from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in a high-rise building provide a fire alarmlcommunication system. Exceptions: i ) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Building with approved supervised f i e sprinkler system throughout and with local alarm system.

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick- response standard sprinklers in dwelling units and guest rooms.

4-106 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 269: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 31 O. 9.1.6 (Building Code) (Added)

Provide smoke detectors in all interior corridors adjacent to sleeping room in corridors of hotels and motels, which are notfiil1,v sprinkled. Wire detectors to activate all detectors in same corridor and provide an audible and visible alarm at the registration desk. Exception: All hotels and motels with 12 or less sleeping rooms or not having interior corridors. All single level dwellings, and all seasonally occupied dwellings. Provide in all of these excepted units a smoke detector in each sleeping room. The detector ma,v be batterypowered if it contains a tamper resistant cover to protect batteries.

HIGHRISE, NEW CONSTRUCTION. GROW B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES

Section 403.2 (Building Code)

Provide approved automatic sprinkler system smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction.

Section 403.3 (Building Code)

Section 403.5 (Building Code)

Section 402.2 (Building Code)

Article 81 (Fire Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic fire detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 81-A.

4107 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 270: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix Chapter 34 Division II (Building Code) (Deleted)

(State deletes Appendix Chapter 34. Local jurisdictions may adopt this appendix chapter by ordinance.)

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AViATION CONTROL TOWERS

Appendix Chapter 4, Dnision II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES (GROUP R DMSION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code) (Deleted)

(State deletes this division ofAppendix Chapter.)

4-108 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 271: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code) (Amended)

Appendix Chapter 34 Division 1, Section 3408 (Building Code) (Deleted)

Section 713 (Building Code)

Section 3003.2 (Building Code)

Except in Groups R-2, R-3, U, and certain Group I occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

(State deletes Appendix Chapter 34. Local jurisdictions may adopt this appendix chapter by ordinance.)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, Le., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

4-109 Indiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 272: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF IOWA Administrative Requirements

Code Code

Code

Amendments State amendments

Mandatory for state-owned mildings and modular-factory- milt structures. Local idoption is voluntary. Roy Marshall State Building Code Commissioner Department of Public Safety Division of the State Fire Marshal State Building Code Bureau 62 1 E. Second Street Des Moines, IA 50309-1831

Preemptive Application

Regulations State-written. References certain NFPA National Fire Codes and Standards. Mandatory for specific building occupancies. Local jurisdictions may adopt more stringent code. Roy Marshall State Building Code Commissioner Department of Public Safety Division of the State Fire Marshal State Building Code Bureau 621 E. Second Street Des Moines, IA 50309-1831

Promulgation

Comments

Summary of Amendments

Enforcement

State Building Code is mandatory for all buildings only when local jurisdictions adopts. State Building Code takes precedence over Fire Marshal Rules and Regulations where a code is adopted. State Fire Marshal’s Rules and Regulations adds specific fire alarm and detection requirements for residential and health-care facilities and group homes. See summary of state requirements on following pages.

Building I Fire Prevention

It.515) 281-3992 (515) 281-3992 Local jurisdictions or Roy Marshall State Building Code Commissioner Department of Public Safety Division of the State Fire Marshal State Building Code Bureau 621 E. Second Street Des Moines, IA 50309-1831

I Local jurisdictions or

(515) 281-3992

Roy Marshall State Building Code Commissioner Department of Public Safety Division of the State Fire Marshal State Building Code Bureau 621 E. Second Street Des Moines, IA 50309-1831 15 1 5 ) 28 1-3992

Life Safety Code

Referenced in Fire Marshal Rules and Regulations

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 273: NEMA GUIDE CODE Fire Alarm & Detection System

History: Legislation passed in 1972 established the Iowa State Building Code, which applies to all state-owned buildings and to all factory-built structures. It also applies to all construction in those cities or counties, which have adopted the State Building Code as their local code.

In 1975, the provisions in the State Building Code for making public-owned buildings accessible for the handicapped were extended to include all privately owned buildings as well and applies statewide.

4-111 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 274: NEMA GUIDE CODE Fire Alarm & Detection System

History (continued):

In 1977, provisions were added to require all construction, which contains more than 100,000 square feet of heated or cooled space to comply with the thermal and lighting efficiency requirements of the State Building Code. These same energy requirements apply to ali new publicly owned construction, factory -built structures, and all construction in those cities or counties, which have any kind of building regulations.

Provisions requiring any manufactured home (mobile home) sold in Iowa to be tied down in compliance with the State Building Code were also added in 1977.

The State Building Code provisions cannot be amended by local ordinances and take precedence when conflicts occur with other state rules. Other state agency rules are the minimum, which can be adopted by local ordinances.

4-112 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 275: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF IOWA 1994 Uniform Building Code and State Fire Code

Fire AlarmDetection Systems

Automatic Fire Sprinkler Systems

Automatic Detection Systems

Fire Alarm Systems

Required

Occupancy Type

> 50 occupants

Required Reauired

Required

Sroup A - Assembly \musement Buildings Sroup B - Business

Group E - Educational

Required

Required Required Required

Reauired Required Required

Required

Group F- Factory Industrial I Required

&up H - Hazardous H-1 - Flammables/

H-2 - Moderate

H-3 - HighHazard H 4 - Repair Garages H-ó - Semiconductor Facilities H-7 - Health Hazards

Explosives

Explosion Hazard

Required

Required Required > 3,000 sq. fi. Required Required

Required

Required Required

I Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Required Required Required

Required Required Required

Required Required Required

Group M - Mercantile > 12,000 sq. fi./floor > 24,000 sq. ft. total

Group R - Residential R-1 - Hotel/Multifamily > 3 stories I > 3 stories > 3 stories

Group S - Storage

High-rise -New and Existing Construction B-2 - Ofices R-1 - Hotel/Multifamily

Required ~

> 75 fi. > 75 ft.

> 75 ft. > 75 fi.

> 75 fi. > 75 ft.

Covered Mails Required

Aviation Control Towers I Required Required

4-113 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 276: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF IOWA 1994 Uniform Building Code (ICBO) and State Fire Code,

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages.

Basements more than 1,500 square feet in floor area. Exhibition and display rooms more than 12,000 square feet Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A-4.

ta Multi-theater complexes. Amusement buildings, except if temporary with floor area less than 1,000

square feet and exit travel distance is less than 50 feet from any point. <& All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages.

Section 303.9 (Building Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

Section 408 (Building Code)

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUPE -EDUCATIONAL

Section 305.2.2 (Building Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Section 305.9 (Building Code)

Provide approved fire alarm system when occupant load is more than 50 persons. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

4-114 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 277: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 904.2.4 (Building Code)

Section 1017.4 (Building Code)

Section 5.502 (Fire Code) (Added)

Section 5.664 (Fire Code) (Added)

Section 5.706 & 5.714 (Fire Code) (Added)

Provide automatic fire extinguishing system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

Provide jìre detection and extinguishing systems fo r child-care centers for seven or more children per chart provided as to type of construction and number of stories. If classrooms have a direct exit door to the outside, complete automatic detection is not required. In this instance, a manual alarm or single-station detector is satisfactory. Provide manual fire alarm stations on each floor of ch ild-care centers.

Provide sprinkler or automatic alarm systems in buildings using entire basement area for classroom purposes, unless building ofjìre-resistive construction. After October I 7 , i 969, in new construction only, provide complete approved automatic sprinkler system and approved automatic smoke venting facilities in underground or windowless educational buildings.

Provide fire alarm system in all new or existing schools having two or more classrooms. In "open plan" buildings that do not have a direct exit door from each classroom to outside, provide a complete automatic fire detection system or sprinkler system.

4-115 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 278: NEMA GUIDE CODE Fire Alarm & Detection System

GROUPH -HAZARDOUS

Section 307.9 (Building Code)

Section 307.11 (Building Code)

Section 904.2.5 (Building Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved manual alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

GROUP I - INSTITUTIONAL

Section 308.9 (Building Code) occupancies.

Provide approved manual and automatic fire alarm system in ail Group I

Section 308.10 (Building Code)

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Section 5.552 (Fire Code) (Added)

Provide automatic fire detection and alarm system in residential care facilities made offrame or ordinary construction not over two stories in height with I S or less residents. Iffacility has I 6 or more residents, provide an approved automatic sprinkler system. Regulations list similar requirements for other types of construction.

Section 5.601 (Fire Code) (Added)

Provide automaticfire-extinguishing system in all health-care facilities. Excepted are those oJjìre-resistive construction of any height or protected noncombustible construction not over one story in height or one story one hour protected frame construction.

Provide automatic fire detection systems in all health-care facilities unless equipped with sprinkIer/approved manual fire alarm system. Every building must be provided with an electrically supervised manually operatedfire alarm system integral with the detection system.

4-116 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 279: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 5.609 (Fire Code) (Added)

Provide afire alarm system in group honte facilities or smoke detection system which includes at least one nianual.fire alarm station per.floor arranged to initiate the smoke detection alasni. Excepted are buildings protected by a complete approved automatic sprinkler alarni system. I f a hazardous area is on the same floor as primary means of escape or a sleeping room, provide automatic sprinkler protection of the hazardous area.

Section 5.620 (Fire Code) (Added)

Provide interconnected smoke detectors on each occtípiedfloor including basements of small group homes for the mentally retarded.

Section 904.2.6 (Building Code)

Provide automatic fire extinguishing system throughout.

Appendix Chapter 3, Division 1 (Building Code)

Alternative provisions for Group 1-3 housing more than six inmates provide automatic sprinkler system; smoke management system with smoke detectors, and fire alarm system.

GROUP M - MERCANTILE

Section 904.2.7 (Building Code)

Provide automatic sprinkler system in retail stores if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code)

Provide smoke detectors in dwelling units, congregated residences, and hotel or lodging-house guest rooms installed per manufacturer's instructions.

Section 310.10 (Building Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings provide a fire aladcommunication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2 ) Building with automatic sprinkler system throughout and with local alarm system.

4-117 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 280: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL fcontinued)

Section 904.2.8 (Building Code) (Amended)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Sprinklers must comply with NFPA 13R (1996) requirements.

Section 5.552(8) (Fire Code) (Added)

Section 5.802 (Fire Code) (Added)

Provide automatic fire detection system in all boarding homes unless equipped with a sprinkleriapproved manual fire alarm system.

Provide approved smoke detectors in every new and existing dwelling unit in apartment houses, dormitories, and every guest room in a hotel, motel, or lodging house used for sleeping purposes.

Install approved automatic or nianual.fire alarm system in every new and existing apartment house three or more stories in height or containing more than I5 apartments and every hotel three stories or more or containing 20 or more guest rooms. Excepted are buildings not over two stories in height with one-hour fire-resistive occupancy separation.

Provide automatic sprinkler system in all residential occupancies more than four stories in height or more than 65 feet above grade level.

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 403.2 (Building Code) (Amended)

In Group B and R-1 occupancies, provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in buildings more than four stories or 65 feet in height above lowest level offire department access or ofgreater height than ladder capability of local f ire department from lowest level offire department vehicle access.

Section 403.3 (Building Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

4-118 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 281: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES fcontinuedl

Section 403.5 (Building Code) .

Provide fire alarm, emergency voiceialarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Section 402.2 (Building Code)

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Section 5.230 (Fire Code) (Added)

Provide automatic sprinkler systems in new high-rise buildings and existing high-rise buildings to which additions, alterations, or repairs are made. Exempt are open parking garages over,four stories in height if of noncombustible construction and house no other occupancy.

HIGHRISE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. E7USTING STRUCTURES

Appendix Chapter 34 Division II (Building Code) (Deleted)

(State does not adopt Appendix Chapter.)

COVERED MAUS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

4-119 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 282: NEMA GUIDE CODE Fire Alarm & Detection System

AVIATION CONTROL TOWERS

Append¡ Chapter 4, Division II, Section 425 (Building Code) (Deleted)

(State does not adopt this division of Appendix Chapter.)

GROUP CARE FACILITIES (GROUP R DMSION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

Section 904.2.2 (Building Code)

Appendiu Chapter 34 Division 1, Section 3408 (Building Code) (Deleted)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1994 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 5 5 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

(State does not adopt this Appendix Chapter.)

Section 713 (Building Code)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper as required by the 1994 UBC.

4-120 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 283: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENEXAL REOUIREMENTS ícontinued)

Section 5.52(7) (Fire Code) (Added)

Provide approved automatic spi-inkler system throughout underground structures with 1,500 square,feet or more.

Section 5.52(6) (Fire Code) (Added)

Provide an approved automatic sprinkler system in every ston, or basement o f all buildings when the,floor area is 1,500 square.feet or more and there is not provided at least 20 square.feet of opening entirely above the adjoining group level in each 50 lineal feet orpaction thereof o,f exterior wall in the story or basement on at least one side of the building. Excepted from this requirement are dwellings, lodging houses, private garages, sheds and agricultural buildings.

Section 5.54(9) (Fire Code) (Added)

Section 5.59(1) (Fire Code) (Added)

Provide smoke detectors to activate closing device of an automatic closing fire assembly.

Provide approvcd smoke detectors in the return air duct or plenum prior to exhausting from building or being diluted by outside air of all buildings with air-conditioning systems or pressure air supply serving more than one story.

4-121 Iowa

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 284: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF KANSAS Administrative Requirements

785) 296-8899 'haine Hoffman lirector lepartment of Administration livision of Architectural ;emices 020 S. Kansas Avenue 'opeka, KS 66612-131 1 785) 296-8899

~

Code

Amendments

Preemptive Application

(785) 296-3401 Local jurisdictions or Gale Haag State Fire Marshal Kansas Fire Marshal Department 700 Southwest Jackson Street, Suite 600 Topeka, KS 66603-3714

State fire code contains minimum baseline life safety requirements with which the state fire code can evaluate existing buildings. State statute states that if a new building conforms to an updated edition of one of the nationally recognized building codes, it shall be deemed to comply with the Kansas Fire Prevention Code.

(785) 296-3401

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

997 UBC

JO amendments

aandatory for state-owned Nuildings and schools. loluntary for all other Nuildings.

'haine Hoffman lirector lepartment of Administration livision of Architecturai iervices 020 S. Kansas Avenue opeka, KS 66612-131 1

Fire Prevention C d e

Kansas Fire Prevention Code

References NFPA National Fire Codes and Standards Mandatory for all buildings except 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent with state approval. Gale Haag State Fire Marshal Kansas Fire Marshal Department 700 Southwest Jackson Street, Suite 600 Topeka, KS 66603-3714

Life Safety Code

1991 NFPA 101

State amendments

Mandatory for ali buildings except 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent with state approval. Gale Haag State Fire Marshal Kansas Fire Marshal Department 700 Southwest Jackson Street, Suite 600 Topeka, KS 66603-3714

Local jurisdictions or Gale Haag State Fire Marshal Kansas Fire Marshal Department 700 Southwest Jackson Street, Suite 600 Topeka, KS 66603-3714

(785) 296-3401

(785) 296-3401

see NFPA 101-1991 in Chapter 3 for fire aladdetection system requirements.

Code Change Cycle: State policy requires that the construction of state-owned buildings be regulated by the latest edition of the Uniform Codes. New codes are usually adopted a year or two after publication. There is no set schedule for revisions of other codes.

4-122 Kansas

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 285: NEMA GUIDE CODE Fire Alarm & Detection System

History: Plans and specifications for ali schools must comply with current Uniform Building Code and the National Electrical Code. The state does not oversee construction; this is done by local jurisdictions. The Department of Education is responsible for the administration of the codes for schools. The Division of Architectural Services administers the codes for all state-owned buildings.

New construction and changes in building occupancies are to be designed and built to the latest edition of one of the three model building codes: Uniform Building Code, National Building Code, or Standard Building Code. The predominant adopted code is the Uniform Building Code. Code adoption and enforcement is at the local level.

4-123 Kansas

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 286: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTHOFKENTUCKY Administrative Requirements

Building Code

Kentucky Building Code based upon 1996 National Building

Code

Fire Prevention Code

1997 NFPA 1

- Amendments $ G e amendments

Mandatory statewide. Local iurisdictions may not amend.

Charles Cotton Commissioner Department of Housing, Buildings and Construction The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfort, KY 40601 -4322 1502) 564-8044

Preemptive Application

No amendments

Mandatory statewide except for single -family dwellings. Local jurisdictions may amend to make more stringent to apply to single -family dwellings. Dave Maniey State Fire Marshal Office of the State Fire Marshal The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfort, KY 40601-4322 (502) 564-3626

Promulgation

Enforcement

Comments

Summary of Amendments

Local jurisdictions or Jack Rhody Director, Division of Building Code Enforcement Department of Housing, Buildings and Construction The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfort, KY 40601-4322 (502) 564-8090

Local jurisdictions or Jack Rhody Director, Division of Building Code Enforcement Department of Housing, Buildings and Construction The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfort, KY 4060 1-4322 (502) 564-8090

Life Safety Code

1997 NFPA 101

Vo amendments

Mandatory statewide for iealth-care facilities under Federal contract.

Vommissioner or State Fire bîarshal (see adjacent entries for contact information).

Jack Rhody Director, Division of Building Code Enforcement Department of Housing, Buildings and Construction The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfor, KY 4060 1-4322 (502) 564-8090 or Dave Manley State Fire Marshal Office of the State Fire Marshal The 127 Building 1047 U. S. Highway 127 South, Bay 1 Frankfort, KY 40601-4337 (502) 564-3626

Building Code does not apply to single-family dwellings unless adopted locally. The Kentucky Building Code is controlling source for new construction requirements for both building and fire safety regulations. State amendments to Fire Code and NFPA codes do not modify alarnddetection requirements. State adds bed and breakfast establishments as R-1 and R-3 occupancies. See following pages for summary of state requirements.

4-124 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 287: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Kentucky has a three-year publication program for the Kentucky Building Code, following the same cycle as the BOCA codes. Once the new edition of BOCA is published, the Department of Housing, Buildings and Construction analyzes the changes and takes administrative steps to incorporate the accepted ones into law within a few months of its publication. The Board of Housing, Buildings and Construction meets quarterly to consider and approve code changes.

4-125 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 288: NEMA GUIDE CODE Fire Alarm & Detection System

History: Following the Beverly Hills Supper Club tragedy, which occurred in May 1977, the Department of Housing, Buildings and Construction was created by executive order in November 1977 and was affirmed through legislation passed by the 1978 Kentucky General Assembly. The purpose of the Department is to devise, enforce, and maintain an effective building inspection program and prevent fire and life safety hazards. To reach these goals, the broad-based Board of Housing, Buildings and Construction was established to adopt a uniform building code for Kentucky. in October 1979, the 1978 BOCA Basic Building Code was adopted as the basis for the Kentucky Building Code. Subsequent editions have since been adopted.

The Kentucky Building Code also includes the Kentucky Plumbing Code, Kentucky handicapped accessibility requirements, and Kentucky boiler rules as well as Board-approved amendments.

Enabling legislation and the Kentucky Building Code provide for tiered enforcement and, in general, the Department has responsibility for larger buildings and local jurisdictions have responsibility for smaller buildings. The Department's major programs include the Division of Building Codes Enforcement (which is responsible for safety in new construction in accordance with the Kentucky Building Code); the State Fire Marshal's Office (which is primarily concerned with fire safety investigations and inspections of existing buildings in accordance with the National Fire Codes); and the Division of Plumbing (which enforces a statewide plumbing code). Bringing together these previously separate programs under one umbrella has alleviated many concerns where multiple or conflicting code requirements affected the same project.

A cornerstone in code administration and enforcement in Kentucky is the Building Inspectors Certification Program mandated by the 1982 General Assembly. Under the program, building inspectors have three years in which to become certified. To achieve certification, a building inspector must pass the appropriate examination(s) dictated by the building inspector's duties and responsibilities as well as complete other specified training.

4-126 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 289: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTHOFKENTUCKY 1996 National Building Code (BOCA) with State Amendments

Use Group Classifications

GROUP A - ASSEMBLY

Buildings used for assembly with greater than 50 occupants. Sub-classify as follows:

A-1 Theaters - Theaters and other buildings for theatrical or operatic performances and exhibitions with raised stage and fixed seats, proscenium curtain, fixed or portable scenery loft, lights, motion picture booth, mechanical appliances, and other theatrical accessories and equipment.

A-2 Nightclubs, Dance Halls - Buildings and public assembly places including rooms, lobbies, and other spaces connected thereto with cornmon means of egress and entrance without theatrical stage accessories and designed for use as dance hall, night club, or similar.

A-3 Restaurants, Recreation -Buildings with or without auditorium and without theatrical stage other than raised platform where people assemble for amusement, entertainment, or recreation and incidental motion picture, dramatic, or theatrical presentations including art galleries, exhibition halls, museums, lecture halls, libraries, restaurants other than nightclubs, recreation centers, and passenger terminals.

A-4 Churches -Buildings used as churches and for similar religio,us purposes.

A-5 Stadiums - Outdoor assembly structures including grandstands, bleachers, coliseums, stadiums, tents, and similar structures.

GROUP B - BUSINESS

Buildings or parts thereof used for business transactions, rendering of professional services, or for other services involving stocks of goods, wares, or merchandise in limited quantities for use incidental to office uses or sample purposes including: data processing, animal hospitals and kennels, automobile showrooms, banks, beauty and barber shops, car washes, civic administration and post offices, laboratories for testinglresearch, telephone exchanges, laundries and dry cleaning and self-service and pick-upldelivery stations, outpatient clinics, radiolTV stations, fire and police stations, florists and nurseries, print shops, and professional services.

4- 127 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 290: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (Amended)

Buildings or parts thereof used by more than five persons at one time for educational purposes through twelfth grade including schools, academies, and day-care centers providing care for more than five persons over two-and-one-half years of age for less than 24 hours per day. Licensed facilities not classified as Use Group I-I or I-2providing care for 13 or niore children or otherpersons,for less than 24 hoursper day.

GROUP F - FACTORY/INDUSTRIAL

Buildings or parts thereof; including among others, factories, assembling plants, industrial laboratories, and all other industrial and manufacturing uses where occupants engage in fabricating, assembling, or processing of products or materials. Sub-classify as follows:

F-1 Moderate Hazard - Moderate hazard factory and industrial uses for manufacturing processes including aircraft, automobiles, appliances, boats, and RVs, bakeries, alcoholic beverages, boilers works, canneries, clothing, machinery, dry cleaning using other than flammables, electronics and electric light plants, food processing, film, furniture, tanneries, woodworking, paper mills, plastic, publishing, printing, refuse incinerators, shoes, soap, sugar, tobacco, upholstery, textile mills, and laundries.

F-2 Low Hazard - Factory and industrial uses involving fabrication or manufacturing of noncombustible materials which during finishing, packing, or processing, do not involve significant fire hazard including nonalcoholic beverages, brick, masonry, ceramic, glass, and gypsum, foundries, ice, metal fabrication and assembly, and water pumping plants.

GROUP H - HAZARDOUS

Buildings or parts thereof used for manufacturing, processing, generation, or storage of corrosive, highly toxic, highly combustible, flammable, or explosive materials including loose combustible fibers, dust, and unstable materials that constitute high fire or explosion hazard. Sub-classify as follows:

H-1 - Buildings and structures or parts thereof containing materials, which present a detonation hazard.

H-2 - Buildings and structures or parts thereof which contain materials presenting a deflagration hazard or a hazard from accelerated burning.

H-3 - Buildings and structures or parts thereof which contain materials that readily support combustion or present a physical hazard.

H-4 - Buildings and structures or parts thereof containing materials that are a health hazard.

4-128 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 291: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITLTIONAL

Buildings or parts thereof where people suffering from physical limitations due to health or age harbored for medical or other care or treatment, where people detained for penal or correction purposes, or where liberty.of inmates is restricted. Subclassify as follows:

1-1 Supervised - Facilities for children, aged persons, mentally impaired and convalescents including group homes, mentally retarded care facilities, nursinghomes, and orphanages, housing six or more individuals who because of age, mental disability, or other reasons, must live in supervised environment but who are physically capable of responding to emergency situation without personal assistance.

1-2 Incapacitated - Use for persons with physical limitations including hospitals, day nurseries, sanitariums, infiiaries, orphanages, and homes for aged and infirm.

1-3 Restrained - Buildings or parts thereof including prisons, jails, reformatories, insane asylums, and similar uses, inhabited by occupants under some restraint.

GROUP M - MERCANTILE

Buildings or parts thereof used for display and sales purposes and accessible to public including retail stores, motor fuel service stations, shops, salesrooms, and markets.

GROUP R - RESIDENTIAL (Amended)

Buildings or parts thereof where families or households live or where sleeping accommodations provided for individuals with or without dining facilities. Sub-classify as follows:

R-1 Hotels/Motels - Hotels, motels, boarding houses, and similar buildings arranged for shelter and sleeping accommodations for more than five occupants primarily transient in nature who use facilities for less than 30 days. Bed-and-breakfast establishments occupied as one-family dwellings but having six or more additional guest rooms rented for sleeping purposes by non-members of the sing1e:family unit.

R-2 Multifamily - Dwellings with more than two dwelling units including boarding houses and similar buildings arranged for shelter and sleeping accommodations for occupants primarily not transient in nature. This also includes dormitories accommodating more than five persons older than 2-1/2 years of age.

4-129 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 292: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (Amended) (continued)

R-3 One and Two Family and Multiple Single-family -Buildings arranged for use as one- or two-family dwelling units with maximum five lodgers or boarders per family and multiple single-family dwellings where each unit has its own means of egress. This also includes a childcare facility accommodating five or less children of any age. Bed- and-breakfast establishments occupied as oneTfaniily dwellings bait having,five or less additional guest roonis rented for sleeping purposes by non-members of the single-faniily unit.

R-4 Single Family - Detached one- or two-family dwellings maximum three stories high.

GROUP S - STORAGE

Buildings or parts thereof including warehouses, storehouses, and freight depots used primarily for storage of goods, wares, or merchandise. Sub-classi@ as follows:

S-1 ModerateHazard - Storage buildings for contents likely to burn with moderate rapidity, but not producing poisonous gases, fumes, or explosives.

S-2 Low Hazard - Storage buildings for noncombustible materials and low hazard wares that do not ordinarily burn rapidly such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings but with negligible amount of plastic trim such as knobs, handles, or film wrapping.

GROUP U - U T l I X I Y AND MIscELLANEouS

Accessory buildings and miscellaneous structures not classified in any specific use group per Building Code requirements commensurate with fire and life hazard incidental to use. This group includes structures accessory to a residential occupancy.

4-130 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 293: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTHOFKENTUCKY 1996 National Building Code (BOCA) with State Amendments

Fire Aiarfletection Systems

II Occupancy Type

Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A 4 - Churches

Group B - Business

Group E - Educational Il Group F - Factory F-1 - Moderate Hazard

Group H - High Hazardous

Group I- Institutional

Group M - Mercantile

Group R - Residential R-1 - HotelMotels

S-1 - Moderate Hazard

Atriums

Automatic Fire Sprinkler Systems

12,000 sq. ft.

> 12,000 sq. ft. > 12,000 sq. ft.

> 5,000 sq. ft.

> 20,000 sq. ft.

> 3 stories or > 12,000 sq. fi. or > 24,000 sq. ft. total Required

Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required

Required

Fire Alarm Svstems

Reauired ~~

> 2 stories

Required

Required

Required

Required > 3 stories

> 2 stories

~~~ ~

Automatic Detection Svstems

Required

Required

Required Required

> 30 ft. ceiling

Required

4- 13 1 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 294: NEMA GUIDE CODE Fire Alarm & Detection System

Hazardous Production Materials Facilities Highrise Buildings

Public Garages

Special Amusement Building

Underground Structures

4-132 Kentucky

Required Required Required

> 75 ft. > 75 fi. > 75ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required Required

Required Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 295: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEQLTHOFKENTIICKY 1996 National Building Code (BOCA) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code) (Am ended)

Section 918.4.1 (Building Code) (Am ended)

Provide automatic fire suppression system throughout Groups A-1 and A-3 occupancies that exceed 12,000 square feet as follows: entire story or floor level where Groups A-1 or A-3 occupancies are located; all stories and floors below Groups A-1 or A-3; and all stories and floor levels between Groups A-1 or A-3 and the level of exit discharge. Exception: Groups A-1 or A-3 auditoriums, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance. These requirements also apply to Group A-2 occupancies, which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy. (State deletes requirements.for Group A-4 in this section.)

.,

Provide fire alarm system in Group A 4 occupancies except in sanctuary and nave areas of churches and church buildings not exceeding 10.000 square feet in which single-station smoke detectors are installed in required locations.

GROUP B - BUSINESS

Section 918.4.2 (Building Code)

Provide fire alarm system in Group B occupancies, which are two or more stories above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code) (Amended)

Provide automatic fire suppression system throughout Group E occupancies, unless floor area is less than 20,000 square feet. (State deletes this section.)

Section 918.4.1 (Building Code)

Provide fire alarm system in all Group E occupancies.

GROUP F -FACTORY/INDUSTRIAL

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in area, or more than 24,000 square feet total area on all floors, or more than three stories above grade.

4-133 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 296: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Sections 904.5 and 417.1 (Building Code)

Section 419.3 (Building Code)

Section 2806.4 (Building Code)

Section 417.5.3 (Building Code)

Section 918.4.3 (Building Code)

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code.

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Provide automatic fire detection system per NFPA 72 throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high-hazard materials are used and stored.

Provide a fue alarm system in Groups H-2, H-3, and H-4 occupancies.

GROUP I - INSTITUTIONAL+

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I occupancies. Exception: Group 1-2 child-care facilities accommodating 1 O0 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

Section 918.4.4 (Building Code)

Provide fire alarm systems in all Group I buildings.

Section 919.4 (Building Code)

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide automatic fire detection system and smoke detectors throughout all resident housing areas. Smoke detectors are not required in sleeping rooms with not more than four occupants.

Section 920.3.3 (Building Code)

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery- power backup.

4-134 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 297: NEMA GUIDE CODE Fire Alarm & Detection System

GROW 1 - INSTITUTIONAL (continued)

Section 409.5.1 (Building Code) (Am ended)

Al l Group I-2 occupancies are to comply with the provisions of NFPA 101.

GROUP M - MERCANTILE

Section 904.7 (Building Code)

GROUP R - RESIDENTIAL

Sections 904.8 and 906.2.1 (Building Code)

Section 904.9 (Building Code) (Amended)

Section 918.4.5 (Building Code)

Section 918.4.6 (Building Code)

Section 919.4.4 (Building Code)

Section 920.3.1 (Building Code)

GROUP S - STORAGE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade. Exception: Public garages.

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Provide automatic fire suppression system throughout all Group R-2 occupancies except buildings in which no dwelling unit is more than one story above or below direct access to exit.

Provide fue alarm system in all Group R-1 occupancies.

Provide fue alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

Provide single- or multiple-station smoke detectors in Groups R-1, R-2, and R-3 occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery-power backup.

Provide automatic fire suppression system throughout in Group S-1 occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade.

4-135 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 298: NEMA GUIDE CODE Fire Alarm & Detection System

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Section 404.6 (Building Code)

Section 922.4.2 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atrium.

Provide a smoke control system in all atriums that connect more than two stories.

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alarm signaling system.

in a smoke control area with ceiling height over 30 feet, provide smoke detectors to detect smoke above highest floor open to an atrium or at highest point of another smoke control space.

COVEREDMALLS

Section 402.7.1 (Building Code)

In anchor store, provide smoke control system to be activated by smoke detectors installed in return air portion of heating and cooling system, automatic sprinkler system, and manual controls provided in an approved location.

Provide automatic sprinkler system throughout covered mall building and all. connected buildings, including kiosks and similar structures that are covered and located within the mall.

Section 402.10 and 402.14.2 (Building Code)

HAZARDOUS PRODUCTION MATERIALS FACILITIES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 416.9.2 (Building Code) emergency control station.

Install smoke detectors in re-circulating air stream to initiate a signal at the

Section 416.14.5 (Building Code)

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

4-136 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 299: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS

Section 403.1 (Building Code)

Section 403.2 (Building Code)

Section 403.4 (Building Code)

PUBLIC GARAGES

Section 408.3.1 (Building Code)

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-1, H-2 or H-3; and low-hazard special occupancies.

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system.

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

SPECIAL AMUSElVENT BUILDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

4-137 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 300: NEMA GUIDE CODE Fire Alarm & Detection System

SPECIAL AMUSEMENT BUILDINGS (continued)

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

Section 412.8 (Building Code)

Provide automatic sprinkler system in all buildings or poltions used as sound stages for motion picture or television production and over 1,000 square feet.

U"D STRUCTURES

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voice/alarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

4-138 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 301: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1020.3 (Building Code)

Section 2807.6 (Building Code)

Section 2808.4 (Building Code)

Section 904.10 (Building Code)

Section 918.5 (Building Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Provide approved automatic fire suppression system at the top and at altemate floor levels in a waste or linen chute and in the termination and incinerator rooms. System not required if incinerator bums only Type 4 waste.

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.10. Exception: Group R-3 occupancies.

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

4-139 Kentucky

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 302: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF LOUISIANA Administrative Requirements

Building Code

1994 SBC

No state amendments

Mandatory statewide except for 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent. Jerry Jones Chief Architect State Fire Marshal's Office 5 150 Florida Boulevard Baton Rouge, LA 70806 (225) 925-4920 Local jurisdictions

Code

Fire Prevention Life Safety Code Code

1997 NFPA 1 1997NFPA 101

No state amendments

Mandatory statewide except for 1 and 2 family dwellings. Local jurisdictions may not amend or supplement. Jerry Jones Jerry Jones Chief Architect Chief Architect State Fire Marshal's Office 5 150 Florida Boulevard Baton Rouge, LA 70806 (225) 925-4920 (225) 925-4920 Jerry Jones Chief Architect State Fire Marshal's Office 5 150 Florida Boulevard Baton Rouge, LA 70806 (225) 925-4920 (225) 925-4920

No state amendments

Mandatory statewide except for 1 and 2 family dwellings. Local jurisdictions may not amend or supplement.

State Fire Marshal's Office 5 150 Florida Boulevard Baton Rouge, LA 70806

Jerry Jones Chief Architect State Fire Marshal's Office 5 150 Florida Boulevard Baton Rouge, LA 70806

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

Summary of Amendments

See 1997 NFPA 101 and 1994 Standard Building Code in Chapter 3 for fire aladdetection system requirements.

Code Change Cycle: There is no set schedule. The State Fire Marshal's Office and the State Health Official have the authority to promulgate rules and regulations. The administrative rulemaking process requires public notification of intent to revise and a public comment period. Hearings are held if warranted.

4-140 Louisiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 303: NEMA GUIDE CODE Fire Alarm & Detection System

History: The Office of Fire Marshal for the State of Louisiana was created by a legislative act in 1904. The early fire laws dealt primarily with fire investigations and the payment of local fire department for reporting fires.

The State Uniform Construction Code adopting the 1991 Standard Building Code and the 1993 National Electrical Code became effective on January 1,1992, as the mandatory statewide construction code.

The Louisiana State Fire Marshal's Office has since grown to a staff of over 100 employees with responsibility for plan review, life safety inspections, boiler inspections, mobile home construction standards, and public fire education, as well as fire investigations and the Louisiana Fire Incident Reporting System. This office is responsible for the promulgation and enforcement of rules protecting life and property of the people from the dangers of fire. Five district offices throughout the state are charged with the responsibility of inspecting hospitals, nursing homes, day care centers, state-owned and state-leased buildings, and penal institutions.

The Office of State Fire Marshal is under the Department of Public Safety with all administrative offices located in Baton Rouge.

All plans for new construction (over two-family dwellings), alterations, additions, or renovations of existing structures must be submitted for approval in conformance with the most current NFPA 101 Life Safety Code and ANSI standards. Upon completion, and before occupancy, final inspections are made by the Fire Marshal deputies. Scheduled meeting for appeals relative to nonconformance submittals are heard before the State Fire Marshal's Board of Review.

4-141 Louisiana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 304: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MAINE Administrative Requirements

Code

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

Building Fire Prevention Code Code

None NFPA National Fire Codes and Standards Includes specific NFPA National Fire Codes and Standards Regulates oil and solid fuel in all buildings except certain plants. Local jurisdictions may amend to make more stringent. Cheryl Hersom Regulatory Board Administrator Department of Professional and Financial Regulation Office of Licensing and Registration #35 State House Station Augusta, ME 04333-0035

Local jurisdictions or Cheryl Hersom Regulatory Board Admini strat or Department of Professional and Financial Regulation Office of Licensing and Registration #35 State House Station Augusta, ME 04333-0035

(207) 624-8603

(207) 624-8603

Life Safety Code

1994NFPA 101

Summary of Amendments

No amendments

See 1994 NFPA 101 in Chapter 3 for fire alarm/detection system requirements.

Mandatory statewide. Local jurisdictions may amend to make more stringent.

Nelson Collins Public Safety Inspector III Department of Public Safety Licensing and Inspections Unit 164 State House Station Augusta, ME 04333-0164 (207) 624-8744

Local jurisdictions

4-142 Maine

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 305: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule. Plumbing rules are reviewed every February for possible revision. The Administrative Rules for Electricians require compliance with the current edition of the National Electrical Code.

History: After six years of lobbying, the Maine legislature passed "An Act to Revise the Energy Building Standards Act" in April 1988. This legislation sets insulation requirements for all residential buildings. Commercial and industrial buildings must meet ASHRAE 90.1-1989.

4-143 Maine

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 306: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MARYLAND Administrative Requirements

Code

Building Code

1996 NBC

Amendments

Preemptive Application

State amendments

Mandatory statewide. Local jurisdictions may amend.

Comments m

Promulgation

Fire Prevention

Kanti Pate1 Chief, Design Standards and R-eview Department of Housing and Community Development Codes Administration, Division of Credit Assurance 100 Community Place Crownsville, MD 2 1032- 2323

Code 1997NFPA 1

Summary of Amendments

State amendments

Mandatory statewide for all buildings except 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent. John F. Bender Chief Fire Protection Engineer Department of State Police Fire Prevention Commission Office of the State Fire Marshal 300 East Joppa Road, Suite 1002 Towson, MD 21286 (410) 339-4220

See Chapter 3 for model code requirements.

John F. Bender Chief Fire Protection Engineer Department of State Police Fire Prevention Commission Office of the State Fire Marshal 300 East Joppa Road, Suite 1002 Towson, MD 21286 (410) 339-4220 Designated local fire officials must enforce State Fire Code as a mandatory minimum. Baltimore City is exempt and enforces its own code.

Life Safety Code

1997 NFPA 101

State amendments

Mandatory statewide for all mildings except 1 and 2 family iwellings. Local jurisdictions may amend to make more stringent.

John F. Bender Chief Fire Protection Engineer Department of State Police Fire Prevention Commission Office of the State Fire Marshal 300 East Joppa Road, Suite 1002 ïowson, MD 21286 (410) 339-4220

John F. Bender Chief Fire Protection Engineer Department of State Police Fire Prevention Commission Office of the State Fire Marshal 300 East Joppa Road, Suite 1002 Towson, MD 2 1286 (410) 339-4220 Designated local fire officials must enforce state code as mandatory minimum. Baltimore City is exempt and has not adopted the Life Safety Code.

4-144 Maryland

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 307: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Maryland state codes can be changed at any time by revising the appropriate regulation. The process requires that the proposed change (code update, amendments, etc.) be advertised in the Maryland Register. This is followed by public hearings or call for comments prior to final adoption. Local jurisdictions may adopt their own code independently of this process.

History: On May 27, 1992, the governor of Maryland signed a law establishing the latest edition of the BOCA National Building Code as the mandatory building code to be adopted and enforced throughout the state. Local jurisdictions may amend the code. Depending upon local jurisdictions’ current codes, the NBC will be adopted between August 1,1994, and August 1,1999. In the interim, local governments adopt and enforce codes of their choice.

4-145 Maryland

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 308: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MASSACHUSETïS Administrative Requirements

Code

Building Fire Prevention Code Code

1993 NBC Massachusetts State Building

Amendments State amendments

Code (Article 10) and Board of Fire Prevention Regulations State amendments

I I

Preemptive I Mandatory statewide. Local IMandatory statewide. Local

Administrator Board of Building Regulations and Standards One Ashburton Place, Room 1301 Boston, MA 02 108 (617) 727-3200

I

Application

Sta& Fire hfarshal Board of Fire Prevention Regulations Executive Office of Public Safety Department of Fire Services P. O. Box 1025, State Road Stow, MA 01775

Promulgation

Local jurisdictions Enforcement (978) 567-3300 Local jurisdictions

jurisdictions may amend to jurisdictions may amend to make more stringent with state make more stringent with state I approval. I approval. ]Thomas L. Rogers !Stephen D. Coan

Comments

Summary of Amendments

IThe Massachusetts Building Code is based on the 1993 BOCA

Life Safety Code

None

Jational Building Code but - with significant changes. In most part, any language in the national code that conflicts with the Massachusetts General Laws has been deleted and other provisions have been coordinated with those of other specialized codes under the control of separate independent boards. Massachusetts adds or redefines several use groups and has detailed provisions of fire detection in residential structures. Chapter 9, Fire Protection, of the BOCA National Building Code has been modified to be very state-specific. The Board of Fire Prevention Regulations in Section 124.07 provides installation locations and spacing for smoke and heat detectors and fire warning systems.

Code Change Cycle: There is no set schedule. The State Board of Building Regulations and Standards is required to revise the building code at least every five years. Suggestions for revisions to the codes may be submitted at any time; however, state law sets the months of May and November for public hearings to entertain changes to the codes and requires “code change proposals” be filed 60 days in advance of such hearings.

History: In 1971, the Board of Standards adopted and promulgated a code based on the 1970 BOCA Basic Building Code with amendments. The code was applicable statewide but only to certain occupancies.

4-146 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 309: NEMA GUIDE CODE Fire Alarm & Detection System

In 1972, Chapter 802 of the Acts of 1972 was enacted, establishing a State Building Code Commission with authority to develop and implement a statewide uniform building code applicable to all buildings and structures, and placing the responsibility for enforcement with local building departments with the exception of state-owned buildings which remained with the Division of Inspection, Department of Public Safety. The Massachusetts State Building Code is based on the BOCA National Building Code, but has been modified to address state needs. Chapter 348 of the Acts of 1984 created the State Board of Building Regulations and Standards as the successor to the State Building Code Commission. The statutory requirement is to revise and amend the State Building Code at least once every five years.

4-147 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 310: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTH OF MASSACHUSETIS Use Group Classifications

GROUP A -ASSEMBLY

Buildings used for assembly with greater than 50 occupants. Sub-classify as follows:

A-1 Theaters -Theaters and other buildings for theatrical or operatic performances and exhibitions with raised stage and fixed seats, proscenium curtain, fixed or portable scenery loft, lights, motion picture booth, mechanical appliances, and other theatrical accessories and equipment.

A-2 Nightclubs, Dance Halls - Buildings and public assembly places including rooms, lobbies, and other spaces connected thereto with common means of egress and entrance without theatrical stage accessories and designed for use as dance hall, night club, or similar.

A-3 Restaurants, Recreation -Buildings with or without auditorium and without theatrical stage other than raised platform where people assemble for amusement, entertainment, or recreation and incidental motion picture, dramatic, or theatrical presentations including art galleries, exhibition halls, museums, lecture halls, libraries, restaurants other than nightclubs, recreation centers, and passenger terminals.

A 4 Churches -Buildings used as churches and for similar religious purposes.

A-5 Stadiums - Outdoor assembly stmctures including grandstands, bleachers, coliseums, stadiums, tents, and similar structures.

GROUP B - BUSINESS

Buildings or parts thereof used for business transactions, rendering of professional services, or for other services involving stocks of goods, wares, or merchandise in limited quantities for use incidental to office uses or sample purposes including: data processing, animal hospitals and kennels, automobile showrooms, banks, beauty and barber shops, car washes, civic administration and post offices, laboratories for testingiresearch, telephone exchanges, laundries and dry cleaning and self-service and pick-upidelivery stations, outpatient clinics, radioiTV stations, fire and police stations, florists and nurseries, print shops, and professional services.

GROUP E - EDUCATION&

Buildings or parts thereof used by more than five persons at one time for educational purposes through twelfth grade including schools, academies, and day-care centers providing care for children more than two years nine months of age.

4-148 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 311: NEMA GUIDE CODE Fire Alarm & Detection System

GROW F - FACTORY/INDUSTRZAL

Buildings or parts thereof including among others, factories, assembling plants, industrial laboratories, and all other industrial and manufacturing uses where occupants engaged in fabricating, assembling, or processing of products or materials. Sub-classify as follows:

F-1 Moderate Hazard - Moderate hazard factory and industrial uses for manufacturing processes including aircraft, automobiles, appliances, boats, and RVs, bakeries, alcoholic beverages, boilers works, canneries, clothing, machinery, dry cleaning using other than flammables, electronics and electric light plants, food processing, film, furniture, tanneries, woodworking, paper mills, plastic, publishing, printing, refuse incinerators, shoes, soap, sugar, tobacco, upholstery, textile mills, and laundries.

F-2 Low Hazard - Factory and industrial uses involving fabrication or manufacturing of noncombustible materials which during finishing, packing, or processing, do not involve significant fire hazard including nonalcoholic beverages, brick, masonry, ceramic, glass, and gypsum, foundries, ice, metal fabrication and assembly, and water pumping plants.

GROUP H - HAZARDOUS

Buildings or parts thereof used for manufacturing, processing, generation, or storage of corrosive, highly toxic, highly combustible, flammable, or explosive materials including loose combustible fibers, dust, and unstable materials that constitute high fire or explosion hazard. Sub-classify as follows:

H-1 - Buildings and structures or parts thereof containing materials, which present a detonation hazard.

H-2 - Buildings and structures or parts thereof which contain materiais presenting a deflagration hazard or a hazard from accelerated burning.

H-3 - Buildings and structures or parts thereof which contain materials that readily support combustion or present a physical hazard.

H-4 - Buildings and structures or parts thereof containing materials that are a health hazard.

GROUP I - INS'llTUTIONAL

Buildings or parts thereof where people suffering from physical limitations due to health or age harbored for medical or other care or treatment, where people detained for penal or correction purposes, or where liberty of inmates is restricted. Sub-classify as follows:

4-149 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 312: NEMA GUIDE CODE Fire Alarm & Detection System

1-1 Supervised - Facilities for children, aged persons, mentally impaired and convalescents including group homes, mentally retarded care facilities, nursing homes, and orphanages, housing six or more individuals who because of age, mental disability, or other reasons, must live in supervised environment but who are physically capable of responding to emergency situation without personal assistance.

1-2 Incapacitated -Use for persons with physical limitations including hospitals, day nurseries, sanitariums, infirmaries, orphanages, and homes for aged and infirm on a 24-hour basis for six or more persons. This sub- classification also includes a child day care center accommodating children two years nine months of age or less.

1-3 Restrained - Buildings or parts thereof inhabited by six or more persons under some restraint or security, including prisons, jails, reformatories, insane asylums, and similar uses.

GROUP M - MERCANTILE

Buildings or parts thereof used for display and sales purposes and accessible to public including retail stores, motor fuel service stations, shops, salesrooms, and markets.

GROUP R - RESIDENTIAL

Buildings or parts thereof where families or households live or where sleeping accommodations provided for individuals with or without dining facilities. Assisted Living Residences, which are certified as such by the State Executive Office of Elder Affairs, will be classified in the residential use Groups R-1, R-2, R-3 or R-4 as applicable. Sub-classifi Group R as follows:

R-1 HotelslMotels - Hotels, motels, boarding houses, and similar buildings arranged for shelter and sleeping accommodations for occupants primarily transient in nature who use facilities for less than 30 days.

R-2 Multifamily - Dwellings with more than two dwelling units including boarding houses and similar buildings arranged for shelter and sleeping accommodations for occupants primarily not transient in nature. This also includes dormitories accommodating more than five persons older than 2-1/2 years of age.

R-3 One and Two Family and Multiple Singlefamily - Buildings arranged for use as one- or two-family dwelling units with maximum five lodgers or boarders per family and multiple single-family dwellings where each unit has its own means of egress. This also includes a childcare facility accommodating five or less children of any age. A family day-care home accommodating not more than six children will be classified as use Groups R-3 or R-4.

4-150 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 313: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESJDENTLAL (continued)

R-4 Single Family -Detached one- or two-family dwellings maximum three stories high.

R-5 Group Residences - Buildings arranged for use as limited group residences.

GROUP S - STORAGE

Buildings or parts thereof including warehouses, storehouses, and freight depots used primarily for storage of goods, wares, or merchandise. Sub-classifi as follows:

S-1 Moderate Hazard - Storage buildings for contents likely to bum with moderate rapidity, but not producing poisonous gases, fumes, or explosives.

S-2 Low Hazard - Storage buildings for noncombustible materials and low hazard wares that do not ordinarily bum rapidly such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings but with negligible amount of plastic trim such as knobs, handles, or film wrapping.

GROUP U - UTILITY AND MISCELLANEOUS

Accessory buildings and miscellaneous structures not classified in any specific use group per Building Code requirements commensurate with fire and life hazard incidental to use. This group includes structures accessory to a residential occupancy.

4-151 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 314: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTH OF MASSACHUSETTS Fire Alarm/Detection Systems

Occupancy Type I A A - Churches

Group A - Assembly A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants

II Group B -Business

Group E- Educational

Group I- Institutional

Group M - Mercantile

Group R - Residential R-1 - HotelMotels R-2 - Multifamily

Group S - Storage

Atriums S-1 - Moderate Hazard

Facilities

Automatic Fire Sprinkler Systems

’ 12,000 sq. ft. > 5,000 sq. fi. > 12,000 sq. ft. > 12,000 sq. fi. > 12,000 sq. ft.

> 12,000 sq. ft.

> 12,000 sq. fi. Required

Required

> 12,000 sq. fi.

Required Required

> 12.000 sa. ft. ~~

Required

Required

Required

Fire Alarm Systems

Required > 2 stories

Required

Required

Required

Required > 3 stories or > 13 units

> 2 stories

Required

Automatic Detection Systems

Required

Required

Required

Required

~

Required Required

> 30 fi. ceiling

Required

Required

4-152 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 315: NEMA GUIDE CODE Fire Alarm & Detection System

High-rise Buildings

Public Garages

Special Amusement Building

Underground Structures

4-153 Massachusetts

> 70 ft. > 70 ft. > 70ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required Required

Required Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 316: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTH OF MASSACHUSE"R3 Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout all portions or uses of all buildings of 12,000 square feet or more in Groups A-1, A-3, and A-4. Provide also in Group A-2 occupancies, which are 5,000 square feet or more in area.

Section 917.4.1 (Building Code)

Provide fire alarm system throughout Group A occupancies.

Section 918.4.1 (Building Code)

Provide automatic fire detection system in Group A 4 occupancies.

GROUP B - BUSINESS

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout all portions or uses of all buildings of 12,000 square feet or more in Group B.

Section 917.4.2 (Building Code)

Provide fire alarm system in Group B occupancies which have occupied floors two or more stories above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout all portions or uses of all buildings of 12,000 square feet or more in Group E occupancies.

Section 917.4.1 (Building Code)

Provide fire alarm system throughout Group E occupancies.

Section 918.4.1 (Building Code)

Provide automatic fire detection system in all Group E occupancies.

Section F-503.5 (Fire Code) Code.

Provide fire alarm system in all existing Group E occupancies per Building

4-154 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 317: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORYLNDUSTRIAL

Section 904.2 (Building Code)

GROUP H - HAZARDOUS

Sections 904.4 and 417.5.3 (Building Code)

Section 503.2 (Fire Code)

Section 419.3 (Building Code)

Section 2806.4 (Building Code)

Section 417.5.3 (Building Code)

Section 917.4.3 (Building Code)

Provide automatic fire suppression system throughout all portions or uses of all buildings 12,000 square feet or more in Group F-1 occupancies.

Provide automatic fire suppression system throughout all Group H occupancies or any other building or structure occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. Included are areas occupied for the dispensing or use of flammable hazardous materials located within 50 feet of either a storage area or building and vehicle-loading racks where flammable hazardous materials are dispensed.

Provide automatic fire suppression system throughout all high-hazard occupancies, including all structures occupied for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic.

Provide automatic fiie suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Provide approved automatic fire suppression system in drying rooms designed for high-hazard materials and processes.

Provide automatic fire detection system per NFPA 72 and NFPA 72E throughout Group H occupancies where required by fire prevention code. Provide detection system in areas where high-hazard materials are used and stored.

Provide a fire alarm system throughout Group H occupancies.

GROUP I - INSTITUTIONAL

Section 904.5 (Building Code)

Section 917.4.4 (Building Code)

Provide automatic fire suppression system throughout all Group I occupancies.

Provide fiire alarm systems in all Group I buildings.

4-155 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 318: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 503.5 (Fire Code)

Section 918.4.3 (Building Code)

Section 918.4.5 (Building Code)

Section 919.3.3 (Building Code)

Section 409.5 (Building Code)

Section 409.5.1 (Building Code)

Section F-503.4 (Fire Code)

GROUPM -MERCANTILE

Section 904.7 (Building Code)

GROUP R - RESIDENTIAL

Sections 904.6 (Building Code)

Provide f r e a l m system in all existing Groups 1-2 and 1-3 occupancies.

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies, unless fully sprinkled throughout.

Provide automatic fire detection system in all Groups 1-3 resident housing areas.

Provide single - or multiple-station smoke detectors or household fire warning systems in all sleeping areas in Group 1-1 occupancies, unless building is equipped throughout with an automatic detection system. Provide battery as secondary power source unless building is fully sprinkled.

Provide automatic sprinkler system throughout smoke compartments containing patient sleeping rooms of Group 1-2. Install quick response sprinklers in patients sleeping rooms.

In Group 1-2, provide smoke detectors with a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station in nursing homes and detoxification facilities. Exceptions: Patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function and sleeping rooms of a childcare facility.

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Use Group 1-1 occupancies. Power source for smoke detector may be either AC or battery.

Provide automatic fire suppression system throughout all portions or uses of all buildings of 12,000 square feet or more in Group M occupancies.

Provide automatic fire suppression system throughout all Groups R-1 and R-2 occupancies.

4-156 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 319: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 917.4.5 (Building Code)

Provide fire alarm system throughout Group R-1 occupancies.

Section 917.4.6 (Building Code)

Provide fue alarm system in Group R-2 occupancies containing 13 or more dwelling units or where dwelling unit is located more than three stories above lowest level of exit discharge or more than one story below the highest level of exit discharge of exits serving the dwelling unit.

Section 918.4.4 (Building Code)

Provide automatic fire detection system in all Groups R-1 and R-2 occupancies. (See Building Code section for exceptions.)

Section 919.3.1 (Building Code)

Provide single- or multiple-station smoke detectors or household fire warning systems in Group R-l. Locate in all sleeping areas; in rooms or hallways in the path of the means of egress from sleeping areas to the door of the guest rooms or suites; and in each story.

Section 919.3.2 (Building Code)

Provide single - or multiple-station smoke detectors or household fire warning systems in Groups R-2, R-3, R-4, and R-5, in immediate vicinity of bedrooms, in all bedrooms, and in each story. In residential units 1,200 square feet or more, provide an additional automatic fire detector for each 1,200 square feet of area, with noted exceptions. Any smoke detector located within 20 feet of a kitchen or within 20 feet of a bathroom containing a tub or shower, installs photoelectric type smoke detector. Wire detectors so that actuation of one alarm will actuate all of the alarms in the individual unit. Provide battery as secondary power source, unless building fully sprinkled.

Section F-503.4 (Fire Code)

Provide a minimum of one approved single-station or multiple-station smoke detector in each guest room, suite, or sleeping area in existing Group R-1 occupancies and in dwelling units in Groups R-2 and R-3 occupancies.

GROUP S - STORAGE

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout all portions or uses of all buildings 12,000 square feet or more in Group S-1 occupancies.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

4157 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 320: NEMA GUIDE CODE Fire Alarm & Detection System

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Section 404.6 (Building Code)

Section 921.4.2 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atrium, except in areas separated from the atrium by fire separation assemblies.

Provide a smoke control system in all atriums that connect more than two stories.

Provide a fire protective signaling system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies, provide a voice/alam signaling system.

In atriums where the height of the atrium ceiling exceeds 30 feet above the floor, provide smoke detectors to detect smoke above the highest floor level open to the atrium.

COVERED MALLS

Section 402.10 & 402.15 (Building Code)

Provide automatic sprinkler system throughout covered mall building and all connected buildings, as well as kiosks and similar structures that are covered and located within the mall.

HAZARDOUS PRODUCTION MATERIALS FACILITIES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HE'M facilities.

Section 416.9.2 (Building Code) emergency control station.

Install smoke detectors in re-circulating air stream to initiate a signal at the

Section 416.14.5 (Building Code)

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

HIGHRZSE BUILDINGS

Section 403.1 (Building Code)

Apply to all buildings more than 70 feet in height above the mean grade.

Section 403.2 (Building Code)

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

4-158 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 321: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS (continued)

Section 403.4 (Building Code)

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and communication system.

PUBLIC GARAGES

Section 408.3.1 (Building Code)

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

SPECIAL AMU&MENT BUILDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

Section 413.4 (Building Code)

Provide automatic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

4-159 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 322: NEMA GUIDE CODE Fire Alarm & Detection System

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level. Exceptions: Group R-3 and public garages equipped throughout with automatic sprinkler system; fixed guideway transit systems; Group A-5 occupancies; and structures wherein the lowest story is the only story that qualifies the structure as an underground structure and which have an area of 1,500 square feet or less and an occupant load less than ten.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voiceialarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Section 1020.3 (Building Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Section 2807.6 (Building Code)

Provide approved automatic fire suppression system at the top and at alternate floor levels in a waste or linen chute and in the termination and incinerator rooms.

Section 2808.4 (Building Code)

Section 904.8 (Building Code)

Section 906.5 (Building Code)

Provide automatic fire suppression system in vaults for conhustible refuse, which are more than 360 cubic feet in volume.

In buildings with windowless story, provide an automatic fire suppression system throughout.

Provide approved audible and visual alarm devices connected to every required water sprinkler system.

4-160 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 323: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REOUIREMENTS (continued)

Section 923.2 (Building Code) .

All fire protective signal or automatic fire detection systems shall be supervised except Group R single- and multiple-station detectors, Group 1-3 smoke detectors, Group 1-2 sleeping room smoke detectors, and Group H fire protective signaling systems.

Section 503.6 (Fire Code)

In existing structures, provide approved smoke or heat detectors in return air ducts or plenums in each re-circulating air system with a capacity of 2,000 cfm or more and serving more than one floor in building exceeding six stories in height. If not part of an approved smoke control system, install so that actuation of the detector automatically stops the fans.

Section 423.7 (Building Code)

Section 424.4.5 (Building Code)

Section 425.4 (Building Code)

Section 426.14 (Building Code)

Section 427.3.5 (Building Code)

Section 428.10, 428.12 & 428.16 (Building Code)

Provide approved automatic fire warning system in Group Residences.

Provide automatic fire detection system in new and existing day care centers. Locate on the floor of the day care center and/or the floor below. The operation of any waterflow device, manual pull station, smokes or heat detector will initiate a special announcement for the day care center to evacuate.

Provide smoke detectors in residential units of new and existing summer camps for children.

Provide either a fire alarm system or emergency notification system in Bulk Merchandising Retail Buildings.

Provide automatic fire suppression systems installed per NFPA 13D in Limited Group Residences. Provide manual fire alarm and approved smoke detectors.

Sleeping rooms in Detoxification Facilities must comply with requirements of R-1 . Provide fire alarm system (manual and automatic). All sleeping rooms for the impaired shall be sprinkled.

4-161 Massachusetts

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 324: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MICHIGAN Administrative Requirements

Code

Building Code

1996 NBC

Amendments

Preemptive Application

Promulgation

Enforcement

Summary of I State modifies Chapter 4 (96 NI

State amendments

Mandatory if adopted. Local jurisdictions may not amend.

Department of Consumer & Industry Services Bureau of Construction Codes 2501 Woodlake Circle Okemos, MI 48864

Local jurisdictions or (517) 241-9313

Fire Prevention Code

lone

Comments JO mandatory codes for new mildings, only for existing ,tructures. NBC is used if ocai jurisdiction does not take :are of the building. All code :nforcement is up to the local urisdiction.

(517) 241-9328 Local jurisdictions may except themselves from state code. If so, it must adopt and enforce the latest edition of a nationally recognized model code and amendments may be made. Cities need state approval. Nursing homes and hospitals are exempted from the state code. They are regulated by the Department oí Public Health. State code is mandatory for all state- ownedifunded buildings.

:) provisions for high-rise builc Amendments

Life Safety Code

None

. _ floors located moré than 40 feet above lowest level of fire department vehicle access and requires automatic sprinkler and fire alarm and detection systems to be provided at that threshold. See Chapter 3 for 1996 BOCA National Building Code requirements.

ngs to those having occupied

4-162 Michigan

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 325: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: The construction codes in the State of Michigan are reviewed and updated every three years to coincide with the latest edition of the BOCA National Building, International Mechanical and Plumbing Codes, as well as the National Electrical Code. A state department, commission, or board may draft a new code by public request, legislative mandate, or agency suggestion. After public hearings are held, the agency submits the rule to the Legislative Service Bureau for approval. It then goes to the Attorney General for approval of its legality. The code then goes to the Michigan Joint Legislative Committee on Administrative Rules for consideration and approval. If approved, the rule returns to the agency for formal adoption and filing with the Secretary of State. The governor's office must be notified ten days before filing. The entire process takes approximately 12 months from the time an agency drafts the administrative rule.

4-163 Michigan

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 326: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MINNESOTA Administrative Requirements

Code 1997 UFC Code

Code 1997NFPA 101

Building

State amendments

Mandatory statewide. Local iurisdictions may amend if more stringent and does not 2onflict with state code.

Jon Nisja Bureau Chief Department of Public Safety State Fire Marshal Division 144 Cedar Street, Suite 145 St. Paul, MN 55101-5145 (651) 215-0500

Local jurisdictions or Jon Nisj a Bureau Chief Department of Public Safety State Fire Marshal Division 444 Cedar Street, Suite 145 St. Paul, MN 55101-5145 (65 1 j 21 5-0500

6 to Building Code, which sets

Code 1997 UBC

No amendments

Mandatory statewide for institutional facilities. Local jurisdictions may amend if more stringent and does not conflict with state code. Jon Nisja Bureau Chief Department of Public Safety State Fire Marshal Division 444 Cedar Street, Suite 145 St. Paul, MN 55101-5145 (651)215-0500

Local jurisdictions or Jon Nisja Bureau Chief Department of Public Safety State Fire Marshal Division 444 Cedar Street, Suite 145 St. Paul, MN 55101-5145 (651) 215-0500

NFPA 101 is used as a supplement to fire code.

out suecial fire protection

Amendments

Summary of

Preemptive Application

IState provides State Chapter 13

Promulgation

Enforcement

Comments

State amendments

Mandatory if local jurisdictions regulate construction. Some may choose not to regulate. Local jurisdictions may not amend. Stephen Hemick Building Code Representative Pepartment of Administration Building Codes and Standards Division 121 East Seventh Place, Suite 408 St. Paul, MN 55101-2181

I(65 1) 296-4329 ILocal jurisdictions or Stephen Hernick Building Code Representative Department of Administration Building Codes and Standards Division 121 East Seventh Place, Suite 408 St. Paul, MN 55101-2181 (651) 296-4329

Amendments

Fire Prevention I Life Safety

- systems as optional provisions. If a local jurisdiction adopts this option, the provisions must be applicable throughout the municipality for new buildings, buildings increased in floor area, and buildings which have the occupancy classification changed.

Code Change Cycle: The State Building Code is based on model codes and certain state specialty codes. The base model code is the Uniform Building Code, which is published on a three-year cycle. When the latest edition of the Uniform Building Code is available, it is adopted with necessary state amendments, with the current edition of other model codes, Le., National Electrical Code, ANSI Elevator Code. Minnesota has an Administrative Procedures Act, which establishes an Office of Administrative Hearings, which holds public hearings on state agency proposed rules. The process from initiation of proposed rules to publication, filing, and effect of law averages from one year to eighteen months.

4-164 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 327: NEMA GUIDE CODE Fire Alarm & Detection System

History: The State Building Code was established in 1969 and pertained to state-owned buildings. In 1971, the State Building Code Division was established to promulgate and administer a statewide building code. Effective July I , 1972, the code superseded all local codes and any municipality adopting construction regulations was required to adopt and administer the State Building Code. Any amendment to the State Code could only be accomplished at the state level. Local govemment and other state agencies were not authorized to promulgate changes.

The first State Code incorporated the 1970 Edition of the Uniform Building Code with other model and state specialty codes, Le., mechanical, plumbing with energy, handicapped, solar, etc., following at later progression periods.

The State Building Code Division is funded by a surcharge on all local govemment permits-which funds the state operation. Annual costs average 55 percent of income. All excess income is rebated to local governments on a prorated basis.

4-165 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 328: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MWNESOTA 1997 Uniform Codes (ICBO) with State Amendments

Use Group Classifications

GROUP A - ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions! recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1 Assembly building with stage and occupant load of 1,000 or more.

A-2

A-2.1

A-3

A 4

Building or portion thereof having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Building or portion thereof with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUP E - EDUCATIONAL

Sub-classify in divisions as follows:

El Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

E 2 Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or4 hours a day.

E 3 Buildings used for day-care purposes for more than six persons.

4-166 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 329: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORY AND INDUSTRIAL

Building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations. Sub-classify in divisions as follows:

F-1

F-2

Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

Low-hazard factory and industrial occupancies including facilities producing noncombustible or non-explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Subclassify in divisions as follows:

H-1

H-2

Buildings with quantity of material in excess of building code limitations which present high explosion hazard, including but not limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days.

Manufacturing of Class 1.4G fireworks. Unclassified detonatable organic peroxides.

Class 4 or Class 3 detonatable unstable (reactive) materials. ta Class 4 oxidizers.

Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to:

Class I organic peroxides. Class 3 non-detonatable unstable (reactive) materials. Pyrophoric gases. Flammable or oxidizing gases. Class I, II, or III-A flammable or combustible liquids used in normally open

containers or systems or in closed containers pressurized at more than 15 psi gauge. Exception: aerosols.

Class 3 oxidizers. Class 3 water-reactive materials.

4-167 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 330: NEMA GUIDE CODE Fire Alarm & Detection System

H-3 Buildings with quantity of materials in excess of building code limitations which present high fire or physical hazard, including but not limited to:

Class II, III, or IV organic peroxides. e Class 1 or 2 oxidizers. Class I, II, or III-A flammable liquids or combustible liquids used or stored in

normally closed containers or systems and containers pressurized at 15 psi gauge or less, and aerosols.

Class III-B combustible liquids. Pyrophoric liquids or solids. Class I or 2 water-reactive materiais. e Flammable solids in storage. e Flammable or oxidizing cryogenic fluids (other than inert). Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

H-4

H-5

H-6

H-7

Repair garages not classified as Group S-3.

Aircraft repair hangars and heliports not classified as Group S-5.

Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to:

+a Corrosives, except stationary lead-acid battery systems.

+Irritants.

e Other health hazards.

Highly toxic materials.

Sensitizers.

GROW I - INSTITUTIONAL

Sub-classifi in divisions as follows:

1-1.1 (Amended)

Nurseries for full-time care of children under the age of six, hospitals, sanitariums, nursing homes with non-ambulatory patients, and similar buildings; each accommodating more than four persons.

4-168 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 331: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

1-1.2

1-2 (Amended)

1-3

Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

Detoxification centers and homes for children six years old or over, each accommodating more than four persons, except buildings used only for private residential purposes for family group.

Mental hospitals, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates similarly restrained, except buildings used only for private residential purposes for family group.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL,

Sub-classifi in divisions as follows:

R-1 (Amended)

Hotels, apartment houses, congregate residences; each accommodating more than ten persons; and Class A-2 supervised living facilities licensed on or after April I I , 1983, and Class B-2 supervised living facilities f o r the mentally retarded, mentally ill, chemically dependent, and physically handicapped, each accommodating more than six persons.

R-2

R-3 (Amended)

Classification not used.

Dwellings, lodging houses, and congregate residences, each accommodating ten persons or less; family day care; group family day care; and Classes A-I, A-2, and B-1 supervised living-facilities having more than six but not more than 15 ambulatoiy or mobile disabled persons.

4-169 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 332: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Subclassify in divisions as follows:

s-1

s -2

Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

s -3 Repair garages and parking garages not classified as S-4.

S-4 Open parking garages.

s -5 Aircraft hangars and helistops.

GROUP U - UTILITY

Sub-classify in divisions as follows:

u1 Private garages, carports, sheds and agricultural buildings.

u 2 Fences over six feet high, tanks and towers.

4170 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 333: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MINNESOTA 1997 Uniform Codes (ICBO) with State Amendments

Fire AlartdDetection Systems

Aviation Control Towers I

Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business

Group E - Educational

Group F- Factory Industrial

Group H - Hazardous H-1 - Flammables/

Explosives H-2 - Moderate

H-3 - HighHazard H-4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Group I- Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

.Group M - Mercantile

Group R - Residential I I R-1 - HoteVMultifamily

Group S - Storage

High-rise - New and Existing Construction

B-2 - Offices R-1 - HoteVMultifamily

Covered Mails

Automatic Fire Sprinkler Systems

Required Required Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. ft. total

> 3 stories

Required

> 75 ft. > 75 ft.

Required

Fire Alarm Systems

Required Required Required

50 occupants--

Required

Required

Required Required Required

> 3 stories

> 75 ft. 75 ft.

Required

Required

~

Automatic Detection Systems

Required Required

~

Required

Required

Required Required Required

> 3 stories

> 75 ft. > 75 ft.

Required

Required

4-171 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 334: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MINNESOTA 1997 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Provide automatic sprinkler systems in Group A as follows:

area when used for consumption of alcoholic beverages. t% Basements more than 1,500 square feet in floor area. t% Exhibition and display rooms more than 12,000 square feet

Rooms and un-separated accessory uses more than 5,000 square feet in total

Enclosed usable space below or over a stairway in Groups A-2,

Multi-theater complexes. A-2.1, A-3, a d A-4.

ta Amusement buildings, exc ept if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. t% All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages.

1,000 square feet, or in conjunction with outdoor seating. Smoke-protected assembly seating, except press boxes, storage less than

State Chapter 1306 (Building Code) (Optional)

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code) (Am ended)

Optional requirements: Provide automatic sprinkler systems in all Group A-1, A-2 with occupant load of 300 or more, Group A-2.1, and Group A-3 with an accumulative occupant load of 300 or more.

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide automatic fire alarm system, except in areas used solely for worship, where an approved automatic fire extinguishing system is installed throughout the building, or where Group A is aportion of a Group E occupancy protected with required alarms. When occupant load is 1,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

Provide automatic fire detectors in laundry rooms, boiler and furnace rooms, mechanical and electrical room, kitchens, storage rooms and similar areas.

4-172 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 335: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP A - ASSEMBLY (continued)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

State Chapter 1306 (Building Code) (Option al)

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code) (Amended)

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Optional Requirements: Provide automatic sprinkler systems in Group B offices and postsecondary classrooms with 8,500 or more, gross feet ofjloov area or three or more stories in height.

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

Provide approved manual and automatic fire alarm system when occupant load is 50 or more, with exception as noted. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide approved automatic fire detectors in laundry rooms, boiler and furnace rooms, mechanical and electrical room, shops, laboratories, kitchens, locker rooms, janitor closets, storage rooms, lounges, and similar areas.

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet.

4-173 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 336: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 1007.3.4 (Building Code) and Exceptions: Section 1007.2.4.2 (Fire Code)

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room.

1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

State Chapter Optional Requirements: 1306 (Building Code) (Optional)

Provide automatic sprinkler s,vstenis in Groups E-I and E-2 occupancies with 8,500 or more, gross square feet orfloor area of two or niore stories in height and Group E-3 with occupant load of 30 or niore.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

State chapter 1306 (Building Code) (Optional)

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Section 307.11 (Building Code)

Provide automatic fxe -sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

Optional Requirements: Provide automatic sprinkler systems in Group F occupancies with 2,000 or 5,000 or more, gross square feet offloor area or three or niore stories in height.

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

4-174 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 337: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

Section 904.2.6 (Building Code) and floor area. Section 1003.2.6 (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet

GROUP I - I N S m O N A L

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Provide approved manual and automatic fire alarm system in all Group I occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas.

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code) required alerting functions.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs

Section 1007.2.7.1.1 (Fire Code)

In Groups I-1.1,1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

Section 1007.2.7.2.4 (Fire Code) (Am ended)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

In Group I-3, provide approved automatic fire detectors in laundry rooms, boiler and furnace rooms, mechanical and electrical room, shops, laboratories, kitchens, locker rooms, janitor closets, trash collection rooms, storage rooms, lounges, giyt shops, commissaries, and similar areas.

Provide approved smoke-detection system throughout resident housing areas, including sleeping rooms and contiguous day rooms, group activity spaces and other common spaces.

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and I- 2.

4175 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 338: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Appendix Chapter 3, Division 1 (Building Code) (Amended)

State Article 8

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and Section 1003.2.8 (Fire Code)

State Chapter 1305 (Building Code) (Optional)

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code) and State Fire Regulation 299F.362

Alternative provisions for Group 1-3 housing mental hospitals, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates are similar1,v restrained. Provide an automatic sprinkler system; smoke management system with smoke detectors, and fire alarm system.

State Fire Code adds new article applicable to adult da,v care centers and supervised living facilities. Protect throughout with a complete automatic4i-e detection system consisting of automatic smoke detection in all corridors, stairways, boiler and furnace rooms, kitchens, storage, janitor closets, laundries, and other hazardous areas. Ifbuilding equipped with manual f ire alarm system, electrically interconnect both systems.

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

Provide automatic sprinkler systems in Group M occupancies with 2,000 or 5,000 or more, gross square feet ofjloor area or three or more stories in height.

Provide smoke detectors in every dwelling unit within a dwelling, congregate residences, apartment, and hotel or lodging-house guest sleeping rooms meeting the requirements of UL or approved by ICBO. In new construction, each smoke detector must be attached to a centralized power source. Single-station smoke detectors may be battery powered in existing buildings.

4-176 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 339: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL ícontinued)

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. in Group R-l occupancies located in a high-rise building provide a fire alarmkommunication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Building with approved supervised fire sprinkler system throughout and with local alarm system.

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Section 1007.2.9.1.3 & .4 (Fire Code)

State Chapter 1306 (Building Code) (Optional)

GROUP S - STORAGE

State Chapter 1306 (Building Code) (Optional)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick- response standard sprinklers in dwelling units and guest rooms.

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

Provide automatic sprinkler systems in Group R-1 apartment houses, hotels, and motels with 8,500 or more, gross square feet offloor area or with dwelling units or guest rooms on three or rnorejloors.

Provide automatic sprinkler systems in Group S-3 sewice stations with 3,000 or more gross square feet offloor areas, not including canopies, Group S-3 parking garages with 5,000 or more gross square feet ofjloor area and all Group S with 2,000 or 5,000 or more gross square feet ofjloor area or three or more stories in height.

HIGHRISE, NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCWANCIES

Section 403.2 (Building Code)

Provide an approved automatic sprinkler system; smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction.

4-177 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 340: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCWANCIES (continued)

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Section 1007.2.12.8 (Fire Code)

Section 1007.2.12.9 (Fire Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenum, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic fire-detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 81-A.

Provide automatic smoke-detection system throughout building when special egresscontrol devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Provide an approved smoke detection system when required by the Building Code for automatic control of a smoke-control system.

Provide manual fire alarm system in lumber, plywood, and veneer mills.

4-178 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 341: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. GROUP B-2 OFFICES AND GROW R-1 OCCUPANCIES. EXISTING STRUClXWRE3

Appendix Chapter 34 Division II (Building Code)

Provide approved automatic sprinkler system in Type II-N, Ei-N, or V-N constniction in all required corridors, stairwells, elevator lobbies, public assembly areas for 100 or more persons, and commercial kitchens.

Provide fire department communication system and occupant voice notification system. .

Provide approved manual fire alarm system connected to approved central, proprietary or remote station service, or a system, which will provide an audible signal at a constantly attended location.

Provide single station smoke detectors in dwelling units and guest rooms, which may be battery powered.

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Appendx Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITES (GROW R DIVISION 4)

Appendx Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

4-179 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 342: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

Appendix Chapter 34 Division 1, Section 3408 (Building Code) and Appendix 1 -A (Tire Codej

Appendix Chapter 34 Division 1, Section 3409 (Building Code) and Appendix 1-A (Fire Code) (Amended)

Appendix Chapter 34 Division 1, Section 3411 (Building Code) and Appendix 1 -A (Fire Code) (Amended)

Section 713 (Building Code)

Protect openings into interior shafts in existing buildings, other than high-rise buildings, by self-closing one-hour fire assemblies or by automatic closing by smoke detection.

Provide approved automatic sprinkler system in basements of existing buildings, other than high-rise buildings, with more than 2,500 square feet in area and meeting other criteria as established in the 1997 UBC and 1997 UFC.

Provide smoke detector installed per approved manufacturer's instructions in dwelling units, congregate residences, and hotel and lodging house guest rooms used for sleeping purposes in existing, other than high-rise, buildings. Install smoke detectors to receive primary power source fiom building wiring if from commercial source or by battery power.

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

4-180 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 343: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REOUIREMENTS ícontinuedl

Section 3003.2 (Building Code)

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

4-181 Minnesota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 344: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MISSISSIPPI Administrative Requirements

Summary of Amendments

Code

Amendments

Preemptive Application

standards not less stringent than the State Fire Code. State fire prevention statutes require every building over 75 feet in height within the state to be equipped throughout with a totally automatic sprinkler system. This also applies to any existing building in which 25 percent or more of the floor space is reconstructed or added to. Exempted are public utility company buildings containing equipment, which would be severely damaged by water.

Promulgation

Enforcement

Building Code

1997 SBC

No amendments

Mandatory for state-owned and leased buildings. Voluntary for all other buildings. Jerry Oakes, Director Department of Finance and Administration Bureau of Building, Grounds and Real Property Management, 1501 Walter Sillers Building Jackson, MS 39201 (601) 359-3621

Jerry Oakes, Director Department of Finance and Administration Bureau of Building, Grounds and Real Property Management, 1501 Walter Sillers Building Jackson, MS 39201 (601) 359-3621

Fire Prevention Code

1997 SFPC

State amendments

Mandatory for buildings owned by the state, used for public assembly or over 75 feet in height. Millard Mackey Chief Deputy Fire Marshal Commissioner of Insurance/State Fire Marshal P. O. Box 79 Jackson, MS 39205-0079 (601) 359-1061

Local jurisdiction or Millard Mackey Chief Deputy Fire Marshal Commissioner of Insurance/State Fire Marshal P. O. Box 79 Jackson, MS 39205-0079 (601) 359-1061

Life Safety Code

1985 "A 101

No amendments

Mandatory for health-care facilities.

Vanessa Phipps Director State Department of Health Division of Health Facilities, Iicensiire and Certificaticm Fire Safety and Construction Branch P. O. Box 1700 Jackson, MS 39215-1700 (601) 354-7300 Vanessa Phipps Director State Department of Health Division of Health Facilities, Licensure and Certification Fire Safety and Construction Branch P. O. Box 1700 Jackson, MS 39215-1700

Code Change Cycle: There is no set schedule; however, the most current editions of the model codes are enforced as soon as they become available.

4-182 Mississippi

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 345: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MISSOURI Administrative Requirements

Building Fire Prevention Code Code

None None Code

Life Safety Code

None

Local jurisdictions

Amendments

Local jurisdictions Local jurisdictions

Preemptive Application

Promulgation

Local jurisdictions Local jurisdictions Local jurisdictions ~

Enforcement

Comments

Summary of Amendments

History: Building codes in Missouri are enforced locally. Currently, industrializedmodular building codes for residential and commercial buildings are enforced by the state, but the state hopes to have local enforcement of this code also.

4-183 Missouri

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 346: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF MONTANA Administrative Requirements

Code

I Building I Fire Prevention Code Code

1997 UBC 1994 UFC

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

State amendments State amendments

Mandatory statewide. Local jurisdictions may not amend.

James Brown Terry L. Phillips Division Administrator State Fire Marshal Department of Commerce Building Codes Division P. O. Box 200517 Helena, MT 59620-05 17 (406) 444-3933 Helena, MT 59620-1415

Local jurisdictions or James Brown Terry L. Phillips Division Administrator State Fire Marshal Department of Commerce Building Codes Bureau P. O. Box 200517 Helena, MT 59620-0517 (406) 444-3933 Helena, MT 59620-1415

Montana's building code is mandatory throughout the state for i

Mandatory statewide for all buildings. Local jurisdictions may amend.

Department of Justice Fire Prevention and Tnvestigatim Program P. O. Box 201415

(406) 444-2050 Local jurisdictions or

Department of Justice Fire Prevention and Investigation Program P. O. Box 201415

(406) 444-2050

Life Safety Code

None

1 buildings except residential with less than five units or their attached-to structures, farm or ranch buildings, private garages or storage garages, or mine buildings. Local jurisdictions adopting codes must adopt the state building code and may make the codes applicable to the buildings exempted by the Building Codes Division.

Summary of Amendments

Montana's building code amendments exempt Group H-4 occupancies having more than 3,000 square feet but less than 5,100 square feet from requirement for an automatic fire-extinguishing system if building is of one-hour fire-resistive construction throughout and has required number of yards and exits.

(See Chapter 3 for 1997 Uniform Building Code requirements for fire alamvdetection systems.

4-184 Montana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 347: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Montana adopts the current editions of the Uniform Building Code, Uniform Mechanical Code, Uniform Plumbing Code, National Electrical Code, and others with certain amendments on a three-year cycle within a few months of the publishing of the model codes.

History: Title 50, Chapter 60, "Building Construction Standards," Montana Code Annotated, which established the statewide building code enforcement program, was enacted in 1969. Since its enactment, the codes in Montana have been updated regularly to keep current with modern technical methods, devices, and improvements consistent with reasonable requirements for the health and safety of building occupants. Model code usage in Montana is prevalent through adoption of those codes published by the International Conference of Building Officials and the National Fire Protection Association.

4-185 Montana

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 348: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEBRASKA Administrative Requirements

No amendments

Mandatory for state-owned buildings.

Kenneth Winters

Code

No amendments State amendments

Mandatory statewide. Local jurisdictions may amend to make more stringent. family dwellings. Kenneth Winters Kenneth Winters

Mandatory statewide for all buildings except 1 and 2

~~

Amendments

State Fire Marshal State Fire Marshal's Office 246 South 14th Street Lincoln, NE 68508

Preemptive Application

Promulgation State Fire Marshal State Fire Marshal's Office 246 South 14th Street Lincoln, NE 68508

Enforcement

Comments

Summary of Amendments

Building Code

State Fire Marshal's Act eeferences 1991 UBC

Fire Prevention Code

Nebraska State Fire Code Regulations, Title 153. References certain NFPA National Fire Codes and Standards.

Statc Firc Marshal State Fire Marshal's Office 246 South 14th Street Lincoln, NE 68508

(402) 471-2027 l(402) 471-2027 I (402) 47 1-2027 Local jurisdictions 1Local jurisdictions or I Local jurisdictions or

Kenneth Winters State Fire Marshal State Fire Marshal's Office 246 South 14th Street Lincoln, NE 68508 (402) 47 1-2027

Kenneth Winters State Fire Marshal State Fire Marshal's Office 246 South 14th Street Lincoln, NE 68508 (402) 47 1-2027

State statute requires that local jurisdictions enforcing a building code must adopt a model building code. See model code requirements of 1994 NFPA 101 in Chapter 3 for code provisions.

Section 81-541 .O1 of the State Fire Marshal's Act requires complete automatic sprinkler system, smoke detection system, and an alandcommunication /central control system in new and existing high-rise office buildings and residential buildings with floors located more than five stories or 75 feet above the lowest level of access by a fire department vehicle.

Section 8 1-5,142 provides smoke detectors in existing dwelling units or apartment houses, lodging houses, hotels and dormitories.

Code Change Cycle: There is no set schedule. Timetables for code changes are dictated by the rules and regulations of the governing boards or by the publication of new editions of the codes. When code changes are proposed, a public notice is issued, then public hearings are held followed by any re-editing or review by the respective boards. Approval is issued by the board; then the code is signed by the governor.

4-186 Nebraska

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 349: NEMA GUIDE CODE Fire Alarm & Detection System

Histov: Nebraska is a large state geographically with the majority of its one and one-half million people located in the eastern third of the state. Other than Omaha and surrounding suburbs, Nebraska has nine communities that exceed the population of 10,000 people. It is a rural state that displays the independence of the agricultural community in general.

Historically, on numerous occasions the issue of a statewide building code has been brought before various committees of the Nebraska Unicameral and, in most cases, never got out of committee. The fact that the majority of people are served by local building departments in the communities and the exemption of the agricultural community within Nebraska from a state building code; always raises the question by many as to the need for a state-wide building code.

4-187 Nebraska

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 350: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEVADA Administrative Requirements

Building Code

Vevada State Fire Marshal Regulations references 1991

Code

Fire Prevention Code

Nevada State Fire Marshal Regulations references 199 1

Amendments State amendments

Mandatory statewide. Local iurisdictions may amend to

Preemptive Application

State amendments and supplement Mandatory statewide. Local jurisdictions may amend to

Promulgation

Summary of Amendments

Enforcement

I

State amends Section 8-4.4.3(e) of 1994 NFPA 101 to require SII booths or areas having over 100 square feet of roof area.

make more stringent. Marvin Carr State Fire Marshal Department of Motor Vehicles 8~ Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 897 1 1 (702) 687-4290 Local jurisdictions or Marvin Carr State Fire Marshal Department of Motor Vehicles & Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 897 1 1 (702) 687-4290

I Comments

make more stringent. Marvin C m State Fire Marshal Department of Motor Vehicles & Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 8971 1 (702) 687-4290 Local jurisdictions or Marvin Carr State Fire Marshal Department of Motor Vehicles & Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 8971 1 (702) 687-4290

Life Safety Code

Vevada State Fire Marshal Regulations references 1994 WPA 101 Vo amendments

Mandatory statewide.-Local iurisdictions may amend to make more stringent. Marvin Carr State Fire Marshal Department of Motor Vehicles k Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 8971 1 í702) 687-4290 Local jurisdictions or Marvin Carr State Fire Marshal Department of Motor Vehicles & Public Safety Office of State Fire Marshal 107 Jacobsen Way Carson City, NV 897 1 1 (702) 687-4290

ke detectors in all exhibit

All buildings erected in the state after January 19, 1984, which are more than 55 feet above or below street level or more than two stories, including any additional height incurred by usable fìoor space within a building, above the grade at any point, must be equipped throughout with approved automatic sprinkler systems to be installed per nationally recognized standards.

See the following pages for state amendments to 1991 Uniform Codes and additional requirements presented in the Nevada State Fire Marshal Regulations.

Code Change Cycle: There is no set schedule for revising state codes. The various state agencies, through their directors, submit proposed revisions to the Legislative Counsel. An administrative procedures process of public notification, public comments, and hearings must be followed.

4-188 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 351: NEMA GUIDE CODE Fire Alarm & Detection System

History: Nevada has mandatory minimum code requirements; local jurisdictions may amend them with more stringent provisions or may adopt codes that are more stringent.

The State Fire Marshal has the authority to enforce the Uniform Codes, the NFPA National Fire Codes, and the State Fire Marshal's administrative rules for state-owned or state-occupied buildings and for all school buildings throughout the state; in all public occupancies in counties whose population is less than 35,000; and in counties whose population is greater than 35,000 when the State Fire Marshal is requested to exercise his authority.

The Nevada Public Works Board acts as the building official and has the authority to enforce construction codes for state-owned facilities and plan review responsibility for all public schools using the latest editions of the Uniform Codes.

4-189 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 352: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEVADA 1991 Uniform Codes (ICBO) with State Amendments

Fire AlarnúDetection Systems

II Occupancy Type II

Group A - Assembly Amusement Buildings Group B -Business B-2 - RetailDrinking

II Group E - Educational

Group H - Hazardous H-1 - Flammables/

Explosivcs H-2 - Moderate

Explosion Hazard H-3 - HighHazard H 4 - Repair Garages H-ó - Semiconductor Facilities H-7 - Health Hazards

Group I - Institutional Hospitals Nursing Homes

II

Group R - Residential R-1 - HotelíMultifamily

High-rise -New and Existing Construction B-2 - Offices R-1 - HotelíMuitifamily

Covered Malls

Aviation Control Towers Il

Automatic Fire Sprinkler Systems

Required Reauired

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories

> 55 ft. > 55 ft.

Required

Fire Alarm Systems

Required Reauired

Required

> 50 occupants

Required

Required

Required Required Required

> 3 stories

> 55 ft. > 55 ft.

Required

Required

Automatic Detection Systems

Reauired

Required

Required

Required

Required Required Required

> 3 stories

> 55 fi. > 55 ft.

Required

Required

4-190 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 353: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEVADA 1991 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 3802 (Building Code) and Section 10.507(c) (Fire Code) (Am ended)

Section 609 (Building Code)

Section 14.104(b) (Fire Code)

Section 610 (Building Code)

GROUP B - BUSINESS

Section 3802(d) (Building Code) and Section 10.507(d) (Fire Code)

Provide automatic sprinkler systems in Group A as follows: G Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area. ta Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A-4. ta Multi-theater complexes. G Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. ta Under roof and gridiron, tie and fly galleries, proscenium walls of stages, platforms more than 500 square feet, dressing rooms, workshops, and storerooms. taCasinos, showrooms and all other roonis for assembly, except churches and theaters with$xed seating.

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system, which activates prerecorded announcement using an approved electrically supervised voice communication or public address system. Exception: Occupancies with automatic fire -extinguishing system installed to activate prerecorded message.

In amusement buildings, provide approved automatic sprinkler, smoke detection, and supervised alarm andior public address systems.

Provide automatic f i e extinguishing system in Group B-2 retail sales areas where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or when more than three stories.

4-191 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 354: NEMA GUIDE CODE Fire Alarm & Detection System

Section 14.104(c)( i) (Fire Code)

Provide fire alarm systems in Group B-2 occupancies as set forth in the following subsections of this code.

Section 14.104(~)(2) and Article 81 (Fire Code)

Provide automatic smoke -detection system throughout high-piled combustible storage uses as required by Article 81. Provide approved automatic fire- extinguishing system when required by Table 8 1.105-A.

Section 14.104(~)(3) (Fire Code)

Provide automatic smoke-detection system throughout building when special egress-control devices are installed on exit doors.

Section 14.104(~)(4) (Fire Code) occupants.

Provide automatic smoke-detection system in corridors, which are not of one hour fire-resistive construction located in office spaces with less than 100

Section 14.104(~)(5) (Fire Code)

Provide fire alarm and communication systems in high-rise office occupancies.

Section 14.104(~)(6) (Fire Code)

Provide approved manual alarm system when required by Article 88 of this code for aerosol storage rooms and general purpose warehouses containing aerosols.

See also specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUP E - EDUCATIONAL,

Section 809 (Building Code) and Section 14.104(d) (Fire Code) in the school. (Amended)

Provide approved fire alarm systems when occupant load more than 50 persons. When automatic sprinkler system or smoke detectors provided, install to automatically activate school fire alarm. TheJire alarm is required to have a different sound, which is distinctive from the local bells or alarms normally used

Section 802(b) (Building Code)

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

4-192 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 355: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 3802(e) (Building Code) and Section 10.507(e) (Fire Code)

Provide automatic sprinkler system in basements more than 1,500 square feet in floor area and in enclosed usable space below or over a stairway.

Section 3318(d) (Building Code)

GROUP H - HAZARDOUS

Section 909 (Building Code) Sections 14.104(e),

50.113, Article 51 and Article 80 (Fire Code)

Provide smoke detectors throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: i ) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Section 911 (Building Code)

Provide alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

Section 3802(f) (Building Code) and Section feet floor area. 10.507(f) (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square

GROW I - INS-ONAL

Section 1002(b) (Building Code)

Provide smoke detector operated damper(s) at each point where ducts penetrate smoke barrier except where openings in ducts are limited to single smoke compartment and ducts are of steel construction.

4-193 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 356: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1009 (Building Code) and Section 14.104(f) (Fire Code)

Provide manual and automatic fire alarm system in Group I occupancies.

Section 1010 (Building Code) and Section 14.104(f)(5) (Fire Code)

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Section 3802(g) (Building Code) and Section 10.507(g) (Fire Code)

Provide automatic fire extinguishing system throughout.

Section 14.104(f)(3) (Fire Code)

Provide smoke detectors at automatic closing doors in smoke barriers and in ducts penetrating smoke barriers and in waiting areas, which are open to

corridors. Install smoke detectors to activate alarm signal audible throughout building.

GROUP R - RESIDENTIAL

Section 1210 (Building Code) and Section 14.104(g)(6 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging-house guest rooms installed per manufacturer's instructions.

Section 1211 (Building Code) and Section 14.104(g) (Fire Code) aladcommunication system. Exceptions:

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings; provide a fire

1) Buildings not more than two stones with all individual units provided one hour fire separation and direct exterior egress; 2) Buildings with automatic sprinkler system throughout and with local alarm system.

4-194 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 357: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 14.104(g) (Fire Code)

In Group R-1 occupancies, provide: ta Manual fire alarm boxes.

required exit for ten or more occupants.

furnace rooms, and similar areas.

designated portions of building.

Smoke detectors in all common areas and interior corridors serving as

Heat detectors in common areas such as recreational rooms, laundry rooms,

Install alann-initiating devices to activate an alarm signal audible throughout

Section 3802(h) (Building Code) and Section 10.507(h) (Fire Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more.

HIGHRISE. NEW CONSTRUCTION, GROW B-2 OFFICES AND GROW R-1 OCCUPANCIES

Section 1807 (Building Code) (Amended)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems when buildings have floors used for human occupancy located more than 55 feet above lowest level of fire,department access.

Section 14.104(g) (Fire Code) (Amended)

Provide fire alarm and communication systems for Group B-2 offices and Group R-1 occupancies with floors used for human occupancy located more than 55 feet above lowest level of fire department access.

HlGHRISE. GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix 1 -B (Fire Code) (Deleted)

(State does not adopt this Appendix Chapter.)

COVEREDMALLS

Section 5603 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system.

ATRIA

Section 1716(b) (Building Code)

Provide smoke control system that operates automatically upon actuation of automatic sprinkler system within atrium and areas open to atrium. Provide smoke detectors that will automatically operate atrium smoke-control system.

4-195 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 358: NEMA GUIDE CODE Fire Alarm & Detection System

AVIATION CONTROL TOWERS

Appendix Chapter 7 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES G R O W R DIVISION 4)

Appendiu Chapter 12 Division II, Section 1232 (Building Code)

Provide approved automatic or manual alarm system.

Section 3802(b) (Building Code) and Section 10.507(b) (Fire Code) (Am ended)

Except in Group R-3 and M occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 3802 of 1991 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults; all buildings which are more than 55 feet high above or below street level or more than two stories, including any additional height incurred by usablefloor space within a building, above the grade at any point. Example: Open parking garages.

Section 4306(f) (Building Code) assembly.

Provide smoke detectors to activate closing device of an automatic closing fire

Section 10.507(i) (Fire Code) (Added)

Provide sprinkler system within shell buildings, retail buildings, and warehouses built f o r unknown tenants and occupancies of various hazards designed fo r commercial use within the general occupancy classification, and multipurpose, shop or storage buildings constructed on prison property.

NEVADA STATE FIRE MARSHAL REGULATIONS

Sections‘ 4 77.560 and 477.566

Provide a device for detection of the products of combustion, other than by detecting heat, in all medical facilities, custodial care facilities, restrained care facilities, and every building used for the care of children.

Provide smoke detectors approved by statejìre marshal in all new and existing child-care facilities.

Section 477.562

Section 477.568 Provide automatic sprinkler system in all child-care facilities used for childcare between the hours of 12:OOp.m. and 6:OO a.m. and care for seven or more children.

Sections 477.910 and 477.915

Provide automatic f ire sprinkler system in all buildings constructed by the state and used for human occupancy. !fused for sleepingpurposes. provide smoke detectors. Provide automatic, fire sprinkler system in all existing state buildings more than 5,000 square feet offloor space by June 30, 1997.

4-196 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 359: NEMA GUIDE CODE Fire Alarm & Detection System

Section 4 77.104 Provide smoke detectors in evew existing hotel or motel containing at least six guest room, or apartment building with at least three dwelling units.

4-197 Nevada

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 360: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW HAMPSHIRE Administrative Requirements

Building Code

Code 1999 NBC sections for fire protection and structural

Fire Prevention Code

1997 NFPA 1

Life Safeîy

Amendments

Code 1997 NFPA 101

integrity No amendments State exceptions State modifications

Mandatory statewide for all buildings except 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent. Donald P. Bliss State Fire Marshal Department of Safety Division of Fire Safety 1 O Hazen Drive Concord, NH 03305 (603) 271-3294

Preemptive Application

I See Chapter 3 for f i e protectioi

Promulgation

Amendments

Enforcement

- after July 1,1999, in multi-unit dwellings, including nursing homes, rooming houses, dormitories, hotels, motels, apartment buildings, and buildings containing condominium units to be powered by the house electrical service. Owners of affected buildings have two years from the above date to replace all battery operated devices which are maintained in an operational state to those powered by the house electrical service.

Section SaEC 6018.03 of State Fire Code adopts and amends the National Fire Alarm Code

Comments

Local jurisdictions or Donald P. Bliss State Fire Marshal Department of Safety Division of Fire Safety 1 O Hazen Drive Concord, NH 03305 (603) 271-3294

Mandatory statewide. Local jurisdictions may amend to make more stringent.

Donald P. Bliss Statc Firc Marshal Department of Safety Division of Fire Safety 1 O Hazen Drive Concord, NH 03305

Local jurisdictions or Donald P. Bliss State Fire Marshal Department of Safety Division of Fire Safety 1 O Hazen Drive Concord, NH 03305

requirements contained in 1999

(603) 271-3294

(603) 271-3294

Mandatory statewide. Local jurisdictions may amend to make more stringent.

Donald P. Bliss State Fire Marshal Department of Safety Division of Fire Safety 10 Hazen Drive Concord, NH 03305

Local jurisdictions or Donald P. Bliss State Fire Marshal Department of Service Bureau of Fire Safety 1 O Hazen Drive Concord, NH 03305

3OCA National Building

(603) 271-3294

(603) 271-3294

ICode and 1997NFPAÏ01. (Section SafC 6018.02 of State Fire Code requires all automatic fire warning devices installed Summarv of

I (NFPA 72).

4-198 New Hampshire

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 361: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule. The state's administrative procedures process for updating codes includes public notification, hearings, testimony, andlor written comments.

History: In November of 1984, New Hampshire adopted a State Fire Code. The state legislated a study committee in 1988, which reported its findings to the Department of Safety for further action. The 1987 National Electrical Code was adopted by the Electricians Board in February 1987. Also in 1987, the Department of Safety was reorganized and as a result the Fire Marshal's Office was removed from Safety Services and now is a Division of Fire Safety reporting directly to the Office of Commissioner of Safety.

4-199 New Hampshire

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 362: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW JERSEY Administrative Requirements

Building Code

1996 NBC

State modifications

Mandatory statewide. Local jurisdictions may not amend.

Code

Fire Prevention Code

State Uniform Construction Code, Fire Protection Subcode (Portions of 1996 NBC, 1993 NMC and 1996 NEC) State modifications

Mandatory statewide. Local jurisdictions may not amend.

Amendments

William Connolly, AIA Director Department of Community Affairs Division of Codes and Standards 101 South Broad Street, P. O. Box 802 Trenton, NJ 08625

I(609) 292-7899

Preemptive Application

(609) 292-7899 I(609) 292-7899

Promulgation William Connolly, AIA Director Department of Community Affairs Division of Codes and Standards 101 South Broad Street, P. O. Box 802 Trenton, NJ 08625

Ií609) 292-7899 Enforcement Local jurisdictions or

William Connolly, AIA Director Department of Community Affairs Division of Codes and Standards 101 SouthBroad Street, P. O. Box 802 Trenton, NJ 08625

Local jurisdictions or William Connolly, AIA Director Department of Community Affairs Division of Codes and Standards 101 South Broad Street, P. O. Box 802 Trenton, NJ 08625

Life Safety Code

None

Summary of Amendments

protection subcode applicable to new construction and alterations. The New Jersey Uniform Fire Code, based on National Fire Prevention Code with amendments, covers fire and life safety for existing buildings. New Jersey Fire Code is primarily a maintenance code with building code taking precedence over new construction. State modifications do not affect fire protection systems. See Chapter 3 for the 1996 National Code fire protection requirements.

Code Change Cycle: A state sponsored code change hearing is held prior to the model code change cycle and appropriate recommendations submitted directly to the model group. Projects under construction for a period of six months after the effective date of the new adopted model code can use the code in prior force.

4-200 New Jersey

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 363: NEMA GUIDE CODE Fire Alarm & Detection System

History: Upon its adoption, the New Jersey Uniform Construction Code rescinded a myriad of existing local and state codes of varying age, which contained diverse standards that had proved costly, time-consuming, and generally added to the profuse confusion that existed in this complex, multi-disciplined field.

All construction codes and their enforcement in New Jersey are entirely controlled by the provisions of the Uniform Construction Code Act. Acting under that authoriiy, the New Jersey Department of Community Affairs adopted a statewide uniform construction code that is made up of several subcodes. The building, electrical, plumbing, and fire protection subcodes became effective on January 1,1977. Subsequently, energy, barrier-free, radon hazard, asbestos, and mechanical subcodes were adopted.

Within the Department of Community Affairs, the Division of Codes and Standards is charged with administering and enforcing the Uniform Construction Code Act throughout the state.

4-201 New Jersey

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 364: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW MEXICO Administrative Requirements

Building Fire Prevention Code Code

1997 UBC 1991 UFC provisions for new Code

Life Safety Code

1997 NFPA 101

Amendments

iurisdictions may amend to make more stringent.

Robert Unthank, Director Division of the Construction [idustries Regulation and Licensing Department 725 St. Michael's Drive P. O. Box 25101 Santa Fe, NM 87504

Preemptive Application jurisdictions may amend to

make more stringent.

Construction Industries Division for UFC adoption or State Fire Marshal for NFPA 1 adoption.

Promulgation State Fire Marshal Bokum Building ,142 West Palace Avenue, 2nd floor P. O. Box 1269 Santa Fe, NM 87504-1269 (505) 827-3550

Enforcement (505) 827-7030 Local jurisdictions or Fermin Aragon Bureau Chief, General Construction Bureau Division of the Construction

I Comments

Local jurisdictions or Division of the Construction Industries for UFC provisions or State Fire Marshal for NFPA 1 provisions.

Local jurisdictions or George Chavez State Fire Marshal Bokum Building 142 West Palace Avenue,

Summary of Amendments

State amendments

construction used as reference documents and 1997 NFPA 1 No amendments State modificat&s I I

Mandatory statewide. Local IMandatory statewide. Local I Mandatory statewide for all

Industries Regulation and Licensing Department 725 St. Michael's Drive P. O. Box 25101 Santa Fe, NM 87504 (505) 827-7041

2nd floor P. O. Drawer 1269 Santa Fe, NM 87504-1269 (505) 827-3550

State adds use occupancy sub-classification as follows: R-4 Residential Group Care Facilities - Group care facilities for ambulatory, non-restrained persons who may have a mental or physical impairment, each accommodating more than five but not more than 16 clients or residents, excluding staff.

I See summary of 1997 Uniform Building Code in Chapter 3 for fire aladdetection system (requirements.

4-202 New Mexico

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 365: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Every three years the State Construction Industries Division appoints a Technical Advisory Committee fi-om within the industry to recommend changes to the New Mexico codes. Public hearings are held throughout the state. The results of the hearings are then presented to the Construction Industries Division Committee. If the Committee approves the code change, it becomes law 30 days after the code is received by the State Archives for record.

History: The 1964 Edition of the Uniform Building Code was the first code adopted by the state on August 17, 1968 with amendments. Other editions were adopted as follows:

Edition Adoution

1970 1973 1976 1979 1982 1985 1988 1991 1997

October 1970 February 1973 August 1977 May 1980 December 1982 January 1986 February 1989 July 1993 December 1998

4-203 New Mexico

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 366: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW YORK Administrative Requirements

Building Fire Prevention Code Code

Code Uniform Fire Prevention and Uniform Fire Prevention and Building Code Building Code

Amendments State-written State-written

Life Safety Code

Uniform Fire Prevention and Building Code references 199 1 NFPA 101

Preemptive Application

Promulgation

Enforcement

Mandatory statewide. Local jurisdictions may amend to make more stringent with state approval. Ronald Piester, R.A. Assistant Director for Code Development Department of State Codes Division 41 State Street Albany, NY 12231-0001 (518) 474-4073 Local jurisdictions

Mandatory statewide. Local Mandatory statewide. Local jurisdictions may amend to jurisdictions may amend to make more stringent with state make more stringent with state approval. approval. Ronald Piester, R.A. Ronald Piester, R.A. Assistant Director for Code Assistant Director for Code Development Development Department of State Department of State Codes Division Codes Division 41 State Street 41 State Street Albany, NY 12231-0001 Albmy,NY 12231-0001 (5 18) 474-4073 (518) 474-4073 Local jurisdictions Local jurisdictions

Comments

Summary of Amendments

4-204 NewYork

I I

New York City is exempt from the state code. State might adopt a model code in the not-to- distant future. Code is state written with amendments made periodically as needed.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 367: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: The State ofNew York conducts an ongoing review for future amendment programs. The Housing and Building Codes Bureau revises the text and submits it for public hearing. The comments are reviewed and assessed, then forwarded to the State Fire Prevention and Building Code Council for approval. The Secretary of State must also approve the amendments. Once approved, the amendments are published and enforced.

History: On July 22, 1981, Chapter 707 of the Laws of 1981 was signed into law. This statute mandated the formulation of a Uniform Fire Prevention and Building Code (Uniform Code) to become effective January 1, 1984, and to be mandatory throughout New York State with the exception of New York City.

The Uniform Code as promulgated retains its performance standard characteristic, is augmented by approximately 450 nationally recognized reference standards, and addresses among other things, standards for construction and fire safety of all buildings and for providing fire protection equipment retroactively in areas of public assembly with financial incentives.

The Uniform Code is subject to amendment on a continual basis. All requests for code amendment are addressed to a 17-member Fire Prevention and Building Code Council who are appointed by the governor.

4-205 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 368: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW YORK Use Group Classifications

GROUP Al - SINGLE FAMILY DWELLING

Residential buildings containing one dwelling unit.

GROUP A2 - TWO FAMILY DWELLINGS

Residential buildings containing two dwelling units.

GROUP B - MULTIPLE OCCUPANCY

Sub-classify as follows:

B1 -Permanent Occupancy. Buildings containing one or two dwelling units with more than four lodgers with a family in either one of such dwelling units, buildings with three or more dwelling units, apartment houses, garden apartments, and community residences.

B2 - Transient Occupancy. Hotels, lodging houses, buildings with sleeping accommodations for more than five persons used or occupied as a club, dormitory, fraternity or sorority house, or for similar uses, motels, and apartment hotels.

B3 - Senior Citizens. Buildings for senior citizens intended primarily for persons 62 years old or more, who are in good physical condition, and do not require physical assistance.

B4 -Adult Residential Care Facility. Buildings for infirm adults who require personal care, supervision, and services.

GROUP C - GENERAL BUILDING CONSTRUCTION

General building construction for the purpose of the code shall be classified in groups in respect to the occupancy or use. The classification shall be in accordance with the following groups:

C1 -Business. Business in which the primary or intended occupancy or use is the transaction of administrative, business, civic or professional service, and where the handling of goods, wares or merchandise in limited quantities is incidental to the primary occupancy or use. Newsstands, lunch counters, barbershops, beauty parlors and similar service facilities are considered as incidental occupancies or uses.

4-206 NewYork

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 369: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP C - GENERAL BUILDING CONSTRUCTION (continued)

C2 - Mercantile. Buildings in which the primary or intended occupancy or use; is the display and sale to the public of goods, wares, or merchandise.

C3 -Industrial. Buildings in which the primary or intended occupancy or use is the manufacture or processing of products of all kinds, including operations such as making, altering, assembling, bottling, canning, finishing, handling, mixing, packaging, repairing, cleaning, laundering, and similar operations.

C4 - Storage. Buildings in which the primary orintended occupancy or use is the storage of, or shelter for, goods, merchandise, products, vehicles, or animals.

C5 -Assembly. Buildings in which the primary or intended occupancy or use is the assembly for amusement, athletic, civic, dining, educational, entertainment, patriotic, political, recreational, religious, social, sports, or similar purposes sub-classified as follows:

C5.1 - for not more than 300 persons;

C5.3 - for more than 1,000 persons; ta C5.2 - for more than 300 but not more than 1,000 persons;

ta C5.4 - churches, synagogues, mosques and similar places of worship; and ta C5.5 - schools, colleges and similar places of education.

C6 - Institutional. Buildings in which the primary or intended occupancy or use is for persons domiciled or detained under supervision, sub-classified as follows:

C6.1 - for persons whose movements are not limited and have a normal sense of perception;

community residences as defined in Section 606.3 of this code; and C6.3 - for persons detained or confined in a mental hospital or for correctional or penal purposes.

ta C6.2 - for persons whose movements are limited because of illness, physical or mental handicap, including

C7 - Miscellaneous. Nonresidential buildings or structures in which the primary or intended occupancy or use is not included in Groups C1 to C6, inclusive. Included are marinas, boatyards, marine terminals, piers and wharves, outdoor storage, and towers.

4-207 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 370: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW YORK Uniform Fire Prevention and Building Code

Fire AlarmDetection Systems

I Required

Occupancy Type

41 - One-Family Dwelling

A2 - Two-Family Dwelling

B1 - Multiple Dwelling Permanent Occupancy

Automatic Fire Sprinkler Systems

> 4 stores

B3 - Multiple Dwelling Senior Citizens

B2 - Multiple Dwelling ïransient Occupancy

> 2 stories

> 3 stories

B4 - Multiple Dwelling Adult Residential Care

C1 -Business

C2 - Mercantile

Required

> 2 stories or > 70 fi.

> 2 stones or > 70 ft.

~~

Fire Alarm Systems

> 4 stories or > 1 1 units and community residences

> 3 stones or > 30 rooms

> 2 stories or > 11 units

Required

~ ~~~

> 2 stories or > 30 fi.

> 2 stories and enclosed malls

> 2 stories

Required

Automatic Detection Systems

Single Station

Single Station

> 4 stories or > 11 units and community residences*

> 3 stories or > 30 rooms*

> 2 stories or > 1 1 units*

Required*

4208 NewYork

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 371: NEMA GUIDE CODE Fire Alarm & Detection System

C6 - Institutional > 2 stories or > 70 fi. Required

*See requirements and exceptions for single station smoke detectors.

Patient sleeping rooms corridors

4-209 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 372: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NEW YORK Uniform Fire Prevention and Building Code

Requirements and Exceptions

GROUP A - 1 AND 2 FAMILY DWELLINGS

Section 721.1, 807.4, & 1193.2 (Buildingmire Code) are permitted.

Provide smoke-detecting devices directly connected to the lighting circuit of the dwelling unit. Locate outside each separate sleeping area, in each sleeping space, and on each floor level. In existing dwellings, battery-operated devices

GROUP B - MULTIPLE DWELLINGS

Section 742.1 (Building/Fire Code)

May substitute fire and smoke detecting system in lieu of required fire alarm system or sprinkler system. May substitute a sprinkler system in lieu of required fire alarm system, fire- and smoke-detecting system, heat- detecting alarm system and special sprinkler installations. In Group B2 and B4 occupancies, these alternate requirements do not apply.

Section 742.2 (Buildingmire Code)

Provide fire alarm system in the following: ta Group B 1, four or more stories or having 12 or more dwelling units,

except where dwelling unit exit is directly to the exterior. Group B2, three or more stories or having more than 30 sleeping rooms.

ta Group B3, two stories or one story having 12 ormore dwelling units, except where each dwelling unit exit is directly to the exterior. ta Group B4, in all buildings.

Section 742.3 (Buildingmire Code)

Provide partial fire- and smoke-detecting systems having manual fire alarm boxes in stairways, corridors, lobbies, spaces for assembly occupancy or use, basements, cellars, boiler rooms, mechanical equipment rooms and service and storage rooms of the following: ta Group B2, three or more stories or having more than 30 sleeping rooms.

where each dwelling unit exit is directly to the exterior. Group B3, two stories or one story having 12 or more dwelling units, except

Group B4, in all buildings.

Provide a fire- and smoke -detecting system in all Group B 1 classified as community residences.

4-210 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 373: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP B - MULTIPLE DWELLINGS ícontinued)

Section 742.4 (Buildingmire Code)

Provide sprinkler systems as follows: $ Group B1 - Throughout buildings four or more stories and with three or more dwelling units between one-hour fire separation. $3 Group B2 - In assembly spaces and exits of buildings not more than two stories. ta Group B2 - Throughout buildings three or more stories. $3 Group B3 - Throughout buildings more than two stories. $3 Group B4 - Throughout buildings.

Provide in the following locations for Groups B1 through B3: $3 Cellars more than 4,000 square feet in fire area.

$Above grade garages more than 5,000 square.feet in fire area. $3 Below grade garages less than 2,000 square feet in fire area.

Cellars more than 2,500 square feet used for flammable storage.

Section 742.6 (Buildingmire Code)

Provide smoke-detecting alarm devices directly connected to the lighting circuit of the dwelling unit. Locate outside each separate sleeping area, in each sleeping space, and on each floor level within dwelling units or in sleeping rooms in Groups B 1 through B4.

Section 742.7 (Buildingmire Code)

Provide heat-detecting alarm system in kitchens and kitchenetts of Group B3 dwelling units in buildings of two stories or less.

Section 1193.3 (Buildingmire Code)

Provide at least one single-station smoke detecting alarm device in each apartment or other sleeping unit of existing multiple dwellings. Battery- operated devices are permitted. Provide portable smoke detectors of both audible and visual design in Group B2 occupancies.

Section 1193.4 (Buildingmire Code) permitted.

Provide portable smoke detectors of both audible and visual design in Group B- 2. Hard-wiring devices into an existing central closed-circuit alarm system is

GROUP C - GENERAL BUILDINGS

Section 774.1 (BuildinglFire required fire alarm system. Code)

Generally, a fire- and smokedetecting system may be provided in lieu of a

4-21 1 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 374: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP C - GENERAL BUILDINGS (continued)

Section 774.2 (Buildingmire Code)

Provide fire alarm systems in the following: ta Group C1 - Buildings more than two stories or more than 30 feet ta Group C2 - Buildings more than two stories. G Enclosed malls, enclosed mall buildings and connected buildings. ta Group C3 - Buildings more than two stories or where the distance of travel to an exit is more than 100 feet G Groups C5.1, C5.2, C5.3, C5.4 - Buildings having more than one area of public assembly and at least one such space accommodates 1 O0 persons or more. ta Group C5.5 - All buildings except one-story, single-room private schools having maximum gross area of 1,2000 square feet used for up to 30 students. ta Group C6 - All buildings.

Section 774.3 &

791.1 (Buildingrnire Code)

Section 774.4 (Buildingmire Code)

Provide fire- and smoke-detecting systems in the following: ta Group C5 - In all areas of public assembly. ta Group C6.2 -In other than day-care centers, in patient rooms or in corridors in lieu thereof and in lounges, lobbies, and recreation spaces.

Provide sprinkler systems in the following: ta Groups C1 through C6.3 except open parking structures and spaces for cold storage and refrigeration: - - from grade by firefighting equipment of the local fire department. - than 2,500 square feet above the first story, and which do not have access openings in at least one wall for entry from the exterior in the event of fire; - Buildings more than two stories in height which have depth of 100 feet or more, and which do not have access openings in at least two walls for entry from the exterior in the event of fire. GGroupsCl,C2,C3.1,C3.2,C4.1 andC5: where fireareasorheightsare increased by sections of the code.

Group C2: enclosed malls, enclosed mall buildings, and connected buildings. e Groups C3.3, C4.3: where fire area more than 1,000 square feet or building is more than one story in height. ta Groups C5.1, C5.2 and C5.3: dance halls, nightclubs and similar occupancies, including accessory spaces, and areas of public assembly for 100 or more persons except places of worship.

Multistory buildings more than 70 feet in height; Buildings more than three stories in height where floors are not reachable

Buildings more than two stories in height or which have fire area of more

4-212 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 375: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP C - GENERAL BUILDINGS (continued)

Section 774.4 (BuildingíFire Code) (continued)

taGroups (3.1, C5.2, C5.3, C5.5: under and over stage areas and auxiliaq spaces, such as dressing rooms, storerooms, and workshops. ta Groups C5.1, C5.2, C5.3, C5.5: exhibit spaces of exhibition buildings where any such space exceeds 15,000 square feet.

- 100 square feet, incinerator rooms and refuse rooms, boiler rooms, mechanical equipment rooms, laundry rooms and storage rooms. - Buildings of Type 2a construction exceeding one story in height and in all buildings of Types 2b, 3,4, and 5 constructions. ta Groups C1 through C6.3: cellar areas of 5,000 square feet or more used for garages or for storage of combustible materials. ta Groups C 1 through C6.3: cellar areas of 1,000 square feet or more used for places of assembly. +a Group C6.1 day-care centers. ta Day-care centers within multiple occupancy buildings.

ta soup C6.2: In hazardous areas, including but not limited to maintenance shops exceeding

Section 774.9 (Building/Fire Code)

Section 1061.1 (BuildingíFire Code)

Section 739.4(d)(8) & 771.4( h)( 1 O ) (BuildingíFire Code)

Provide a coordinated fire safety system in Groups C1 through C6.3 in multi- story buildings more than 70 feet in height, except in open parking structures.

A coordinated fire safety system will include: +a fire alarm system or a fxe- and smoke-detecting system

full sprinkler system standpipe system

ta elevator emergency controls ta re-circulating fan controls +a emergency power and lighting +a f i e control panel +voice communication system +a exit stairway door unlocking system

instructional signs for use of exits

Provide smoke detector every 50 feet of shaft height for the automatic operation of smoke vents in shafts exceeding 150 feet, and an enclosed stairway, shaft or hoistway having an area exceeding four square feet, penetrating two floors or more, and not extending through the roof. Hoistways in Groups C 1 through C4 may be equipped with automatic sprinkler system in lieu of smoke vents.

4-213 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 376: NEMA GUIDE CODE Fire Alarm & Detection System

ATRIUMS

Sections 743.1 and 769.1 (Buildingmire Code)

Sections 743.4(a)(4) and 769.4(a)(4) (Buildingmire Code)

Sections 743.5 and 769.5 (Buildingmire Code)

Provide automatic sprinkler system if building containing an atrium is not of Type 1 or 2 constructions.

For an unenclosed path of travel within the atrium to required exit, provide atrium ceiling, balconies and walkways with smoke detectors.

When atrium connects three or more floors, provide at least two smoke detectors or other automatic fire protection system within the atrium to activate atrium exhaust system.

ENCLOSED MALL BUILDINGS

Section 768.6 (BuildingFire Code)

In enclosed mall buildings and connected buildings, provide the following fire protection systems:

electrically supervised automatic sprinkler, fire alarm, fire- and smoke-detecting

DAY-CARE CENTERS IN MULTIPLE OCcupANcy BWLDING

Section 771.6 (Buildingmire Code)

Provide fire- and smoke-detecting system in day-care center, in corridors adjoining the center, in occupancies on the same floor and above and below the center. Interconnect system with other fire protection equipment.

4-214 New York

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 377: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NORTH CAROLINA Administrative Requirements

Code

Amendments

Preemptive Application

Promulgation

Building Fire Prevention Code Code

1994 SBC 1994 SFPC

State amendments State amendments

Mandatory statewide. Local jurisdictions may amend with state approval. state approval. Grover Sawyer, PE Deputy Commissioner Deputy Commissioner North Carolina Building Code Council Council Department of Insurance 4 1 O North Boylan Avenue P. O. Box 26387

Mandatory statewide. Local jurisdictions may amend with

Grover Sawyer, PE

North Carolina Building Code

Department of Insurance 4 1 O North Boylan Avenue P. O. Box 26387

~

Enforcement

Raleigh, NC 2761 1 (919) 733-3901

~

Comments

Raleigh, NC 2761 1 (919) 733-3901

Local jurisdictions or Barry Gupton Chief Building Code Consultant North Carolina Building Code Council Department of Insurance 4 1 O North Boylan Avenue P. O. Box 26387 Raleigh, NC 2761 1 (919) 733-3901

Summary of Amendments

Local jurisdictions or Rick Diperi Fire Protection Engineer North Carolina Building Code Council Department of Insurance 4 1 O North Boylan Avenue P. O. Box 26387 Raleigh, NC 2761 1 (919) 733-3901

State has amended high-rise fire protection provisions and has requirements for family day-care homes and residential care homes. See the following summary of state amendments to the 1994 Standard Codes.

Life Safety Code

None

Code Change Cycle: The State Building Code Council reviews and approves changes to the state building code on a semi-annual basis. Anyone may request a code change by submitting the proper code change form and supporting documentation to the Secretary of the Council on or before January 1 or July 1.

4-215 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 378: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NORTH CAROLINA 1994 SBCCI Use Group Classifications with State Amendments

GROUP A - ASSEMBLY BUILDINGS

Buildings or portions thereof used for civic, social or religious functions, for recreation, for food or drink consumption, or for awaiting transportation. Sub-classify as follows:

A-1:

A-2:

Large Assembly. Theaters and other places of assembly without a stage with capacity of 1,000 or more persons and theaters and assembly places with working stage having capacity of 700 or more persons. Small assembly. Theaters and other places of assembly with or without working stage requiring proscenium opening protection with capacity of 100 or more persons but having a capacity less than large assembly.

GROUP B - BUSINESS

Buildings or poriions thereof used for office, prüfessiürial üi- sei-vice-type transactions, including normal accessory storage and keeping ofrecords and accounts. These include:

Office Buildings Greenhouses Service Stations Banks Bowling Alleys Educational occupancies above 12th grade

Libraries (other than school) Radio and television stations

GROUP E - EDUCATIONAL

Buildings or space used by six or more persons at any one time for educational purposes through 12th grade. Childcare facilities accommodating any number of children of any age who stay less than 24 hours per day.

GROUP F - FACTORYIINDUSTRIAC

Building or space used for assembly, repairing, fabricating, finishing, manufacturing, and packaging, or for processing operations not otherwise classified in Building Code. Group F includes:

Manufacturing Plant Processing Plant Assembly Plant

Factory Mill

4-216 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 379: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORY/INDUSTRm (continued)

Group F does not include buildings principally involving highly combustible, inflammable, or explosive products or materials.

GROUP H - HAZARDOUS

A building or space, whose principal use involves the manufacturing, processing, generation, storage, or other use of hazardous materials in excess of quantities exempt by this code. Subdivide as follows:

Hi :

H2:

H3:

H4:

Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which present a detonation hazard. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which present a deflagration hazard or a hazard from acceleiated burning. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which readily support combustion or present a physical hazard. Buildings or parts thereof used for the manufacturing, processing, generation or storage of materials, which are health hazards.

GROW I - INSTlTUl'IONAL

Group I buildings are sub-classified into two categories:

Group I restrained: Buildings or portions thereof used to provide sleeping facilities for six or more persons under some degree of restraint or security, such as jail, detention center, correctional institution, and reformatory.

Group I unrestrained: Buildings or portions thereof used for medical, surgical, psychiatric, nursing, or custodial care on a 24-hour basis of six or more persons who are not capable of self-preservation and shall include among others: Hospitals, nursing homes (both intermediate care facilities and skilled nursing facilities), mental hospitals and detoxification facilities.

GROW M - MERCANTIL;E

Buildings or portions thereof used for display and sale of merchandise including stocks of goods, wares or merchandise incidental to such purposes and accessible to the public.

4-217 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 380: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL

Buildings or portions thereof used for sleeping accommodations when not classed as Group I. Subdivide as follows:

R1:

RI:

R2:

R3:

(Transient) Residential occupancies where the occupants are primarily transient in nature (less than 30 days) including: hotels, motels, boarding housing (transient).

(Non-transient) Residential occupancies where the occupants are primarily permanent in nature, but do not occupy individual dwelling units, including: rooming houses (not transienf), convents, fraternities and sororities, monasteries, rectories, dormitory facilities which acconiniodate six or more persons of more than two and one-halfyears of age who stay more than 24 hours.

Multiple dwellings where the occupants are primarily permanent in nature and occupancy individual dwelling units, including: apartment houses and condominiums.

Residential occupancies, including: child-care facilities which accommodate five or less children of any age for any time period, one and two family dwellings where occupants are primarily permanent in nature and not classified as R1, R2, or I, and rooming houses (transient).

GROUP S - STORAGE

Buildings or portions thereof used for storage not classed as Group H, or for sheltering animals. Subdivide as follows:

S1:Moderate Hazard Storage shall include buildings used for the storage of combustible materials when not classified as S2 Low Hazard or Group H.

S2:Low Hazard Storage shall include buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings. Such products may have a negligible amount of plastic trim such as knobs, handles, or film wrapping. S2 Low Hazard Storage shall include but not be limited to the following:

Metal desks with plastic tops and trim Electric coils Electrical motors Dry cell batteries Metal parts Empty cans Stoves Washers and dryers Metal cabinets

GROUP S - STORAGE (continued)

Meats Fresh fruit and vegetables in non-plastic trays or containers Dairy products in non-waxed coated paper containers Beer or wine up to 12% alcohol in metal, glass or ceramic containers Oil filled and other types of distribution transformers

Glass bottles empty or filled with non-combustible liquids Electrical insulators Mirrors Gypsum board Foods in noncombustible containers Inert Pigments Frozen foods Dry insecticides

Cement in bags

4-218 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 381: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NORTH CAROLINA 1994 Standard Codes (SBCCI) with State Amendments

Fire Alarm/Detection Systems

Occupancy Type Group A - Assembly

Group B - Business

Group E - Educational

Group F - FactoryíIndustrial

Group H - Hazardous

Group I - Institutional

Group M - Mercantile

Group R - Residential

Group S - Storage

Atriums

Covered Malls

High-rise Buildings

Special Amusement Buildings

Automatic Fire Sprinkler Systems

Required

Required

Required

Required

Required

Required

> 15,000 sq. fi.

> 3 stories

Required

Required

Required

> 75 ft.

Required

Fire Alarm Systems

Manual when > 1,000 persons Required

Required

Manual when > 2 stories or > 500 persons Required

Required

Manual when > 500 persons

Required

Required

Required

> 75 fi.

Automatic Detection Systems

Required

Required

Required

Required - residential hangars Required

Required

> 75 fi.

Required

4-219 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 382: NEMA GUIDE CODE Fire Alarm & Detection System

Underground Buildings Required Required Required

4-220 North Carolina

Day Care Required Required I

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 383: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NORTH CAROLINA 1994 Standard Codes (SBCCI) Requirements and Exceptions

GROUP A - ASSEMBLY

Section 903.7.2 (Building Code)

Provide approved automatic sprinkler system in Group A-1 occupancies in areas over 15,000 square feet used for display, sale, or storage of combustible materials. Also provide throughout stages and in dressing rooms, workshops, storerooms and other accessory spaces contiguous to stage, and sound stages for motion picture or television productions over 1,000 square feet in area.

Section 905.1 (Building Code) and Section 603.7 (Fire Code) (Am ended)

GROUP B - BUSINESS

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Provide manual alarm system in Group A occupancies with 300 or more persons. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic sprinkler system throughout.

Provide manual fire alarm system in Group B occupancies with 500 or more persons or more than 100 persons located above or below street floor. May omit manual fire alarm when building equipped with automatic fire alarm or automatic sprinkler system throughout.

GROUP E - EDUCATIONAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code) (Amended)

Provide manual fire alarm system throughout Group E occupancies. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic sprinkler system throughout except in individual one-room classrooms.

4-22 1 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 384: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORYDhBUSTRIAL

Section 905.1 (Building Code) and Section 603.7 (Fire Code) (Amended)

GROUPH - HAZARDOUS

Section 407.1.3 (Building Code) and Chapter 22 (Fire Code)

Section 407.2.5 (Building Code) and Chapter 22 (Fire Code)

Section 903.7.4 (Building Code)

Section 905.1 (Building Code) and Section 603.7 (Fire Code) (Am ended)

Section 1303.2 (Fire Code)

Provide manual fire alarm system in Group F having total capacity of 100 or 25 or more persons above or below street floor level. May omit manual fire alarm when building equipped with automatic fire alarm or automatic sprinkler system throughout.

Provide approved automatic sprinkler system throughout Group H indoor storage areas, storage buildings and areas or rooms in which hazardous materials are dispensed or used. Provide internal sprinklers in gas cabinets and exhausted enclosures for the storage of cylinders of highly toxic and toxic compressed gas and provide automatic sprinkler system for roof structures provided for the storage of highly toxic or toxic compressed gases.

Install a local fire alarm manual pull station or approved emergency signal device outside of each interior egress door to a storage room. Also provide an approved supervised smoke detection system in rooms or areas where highly toxic compressed gases, liquid or solid oxidizers or unclassified detonatable, Class I or Class II organic peroxides are stored, and where Class III or Class IV organic peroxides are stored in quantities exceeding exempt amounts specified by this code. Activation of detection system shall sound a local alarm. Exception: Detached storage buildings with an automatic fire extinguishing system. Provide supervision by an approved central, proprietary or remote station service of fire detection or extinguishing systems.

Provide approved supervised automatic sprinkler system throughout Group H Hazardous Production Material (HPM) facilities.

Provide manual fire alarm system throughout Group H except may omit when building equipped with automatic fire alarm or automatic sprinkler system except in hazardous material storage areas.

Provide approved fire alarm system in all Group H buildings used for manufacture of organic coatings.

4-222 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 385: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS (continued)

Section 3605 (Fire Code)

Provide automatic fire extinguishing system and smoke detection system in buildings used for high-piled combustible storage per table in Fire Code and per Building Code.

Section 905.1 Provis-: manua (Building Code) and Section 603.7 (Fire Code)

fire alarm system throughout Group I occupancies.

Group I Unrestrained Occupancy:

Section 409.1.1.1 (Building Code) (Amended)

Provide with an approved automatic wet pipe sprinkler system. Protect smoke compartments containing patient rooms with quick response sprinklers. Quick response sprinklers on dry pipe systems, or standard sprinklers may be used if patient room is equipped with smoke detectors permanently connected to house current.

Section 409.1.2.5 (Building Code)

Provide smoke detectors to activate automatic closing devices on doors in smoke barriers and hazardous areas.

Section 409.1.6 (Building Code)

Provide electrically supervised fire alarm system, which is activated by manual pull stations, by sprinkler activation, and by smoke detection.

4-223 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 386: NEMA GUIDE CODE Fire Alarm & Detection System

Group I Restrained Occupancy:

Section 409.2.10 (Building Code)

Provide a manual and automatic fire alarm system per NFPA 72A.

Section 409.2.12 (Building Code)

Provide approved automatic fire detection system with smoke detectors per NFPA 72A and 72E throughout all resident housing areas, including common spaces, except in sleeping rooms with four or less occupants in a building protected throughout with an approved automatic sprinkler system.

Section 409.2.13 (Building Code)

Provide an electrically supervised approved automatic sprinkler system per NFPA 13 when required by Table 500 of this code.

Section 409.2.14.6 barriers. (Building Code)

Provide smoke detectors to activate automatic closing devices on doors in smoke

Section 409.2.17.4 (Building Code)

Provide automatic extinguishing protection per NFPA 13 in any trash chute or linen chute, including pneumatic rubbish and linen systems.

GROUP M - MERCANTILE

Section 903.7.1 (Building Code)

Provide supervised automatic sprinkler systems in Group M occupancies where combustible storage and story floor area exceeds 15,000 square feet

Section 905.1 (Building Code) and Section 603.7 (Fire Code) sprinkler system throughout.

Provide manual fire alarm system when total occupancy is 500 or more persons or more than 100 persons located above or below street floor. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic

4224 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 387: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL

Section 903.7.5 (Building Code) (Amended)

Section 905.1 (Building Code) and Section 603.7 (Fire Code)

Section 905.2 (Building Code) and Section 603.6 (Fire Code) (Amended)

Provide approved supervised automatic sprinkler system throughout Groups R1 and R2 occupancies three or more stories except when exterior exitway stairs are provided for the guest rooms. An automatic sprinkler system complying with NFPA 13R is permitted for RZ buildings not exceeding,four stories.

Provide manual fire alarm system in hotels for more than 15 guests, apartment houses four or more stories, and dormitories, lodging houses, or rooming houses with more than 15 sleeping accommodations. May omit manual fire alarm system when building equipped with automatic fire alarm or automatic sprinkler system. Also may omit if each guest room or apartment has direct exit to the outside and the building is three stories or less.

Provide approved single-station or multiple-station smoke detector in every dwelling, dwelling unit in apartment house, rental condominium, condominium or townhouse, and every guest or sleeping room in motel, hotel, or dormitory. Install per NFPA 72. Smoke detectors connected to a fire alarm system should be installed per NFPA 72. In all newly constructed dwelling and dwelling units, smoke detectors are to be hardwired into an AC electrical power source. A monitored battery power source is permitted in existing buildings.

Provide approved listed smoke detection devices installed per NFPA 72 in all interior enclosed exit access corridors of Group R buildings and daycare facilities. In buildings with corridors 75 feet or more in length, or more than two stories high, smoke detection system must be electrical1,v interconnected to the fire protective signaling system. In one and two stow buildings with corridors less than 75 feet in length, two or more interconnected single station devices approved.for the dwelling must be provided and powered from the building electrical system.

GROUP S - STORAGE

Section 411.7.7 (Building Code)

Section 41 1.7.8.5 (Building Code)

Section 414.3 & .6 (Building Code)

Provide aircraft hangars with fire suppression as required by NFPA 409.

Provide at least one approved smoke detector within a residential aircraft hangar which is hardwired into the residential smoke alarm or other sounding device to be audible in all sleeping areas of the dwelling.

Provide approved automatic sprinkler system, smoke control system, and smoke detection throughout. Install smoke detectors to activate smoke control system and sound alarm at a constantly supervised station.

4-225 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 388: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 413.4.5.2 (Building Code)

Provide smoke detectors to activate automatic closing devices on doors.

Section 413.8 (Building Code)

Provide automatic fire sprinkler system throughout.

Section 413.10 (Building Code) down air supply.

Provide smoke detectors within return air portion of air conditioning system to shut

HAZARDOUS PRODUCITON MATERIAZ, í"M) FACILITIES

Section 408.1.2 (Building Code)

Provide approved automatic sprinkler system throughout all buildings containing HPM facilities, such as semiconductor fabrication and areas of comparable research and development.

Section 408.3.6.3 (Building Code)

Provide smoke detectors in the re-circulating air stream of ventilation system. Install to initiate a signal at the emergency control station.

Section 408.6.6 (Building Code)

Provide an emergency telephone system or local manual alarm pull station outsde of each interior egress door from HPM cutoff rooms.

4-226 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 389: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRZSE BUILDINGS

Section 412.1.11 (Building Code) (Am ended)

Section 412.3.1 (Building Code) (Amended)

Section 412.6.2.2 (Building Code) (Am ended)

Section 412.12.1 (Building Code) (Amended)

Design of Life Safety Equipment. All electrical, mechanical, central alarm and communications systems, smoke control measures and sprinkler systems must be designed and sealed by a Professional Engineer in the State ofNorth Carolina.

Provide approved sprinkler s,vsteni per NFPA 13 in all buildings. See Section 901.5 .for rooms and areas, which are exempted from having sprinkler heads. Excepted are parking structures of Tvpe I or II construction, which are within buildings or occupancies not required to be provided with automatic sprinkler protection.

Provide approved and listed supervised smoke detectors in each interior or enclosed elevator lobby or elevator entrance areas.

Provide electrical1,v supervised smoke and fire alarm system comply with NFPA 72 in all high-rise buildings. At least one approved smoke detector must be installed in eveïy mechanical equipment, electrical, telephone, elevator equipment or similar room. Thermalhate of rise detectors may be installed in boiler roonis, each opening where a return plenum or return branch duct connects to a vertical shaft, in the return air duct system of every air conditioning and mechanical ventilation system serving anyfloor other than the floor on which the equipment is located, in the supply duct downstream offilters in systems larger than 2000 cfm, and in e v e y interior elevator lobby. Install detector or other initiation device to activate the alarni system and to cause other operations as are necessary toprevent the re- circulation of smoke. Provide audible and visual alarm devices. Manual pull stations must be provided in elevator lobbies.

SPECIAL AMüSEMENT BUILDINGS

Section 403.5.3 (Building Code)

Provide an automatic fire detection system with smoke detectors. An approved alternate type of automatic fire detector may be installed in areas where the ambient conditions may cause a smoke detector to alarm. Install detection device to sound alarm at a constantly supervised station.

Section 403.5.4 (Building Code)

Provide an automatic sprinkler system throughout except when building is temporary with total floor area of 1,000 square feet or less and the exit travel distance from any point is 50 feet or less. Install automatic sprinkler system to sound alarm at a constantly supervised station.

4-227 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 390: NEMA GUIDE CODE Fire Alarm & Detection System

UNDERGROUND BUJLDINGS

Section 415.1 (Building Code)

Applies to building spaces having a floor level used for human occupancy more than 30 feet or more than one story below the lowest level of exit discharge. Exceptions: Fixed guideway transit system, grandstands, parking garages with automatic fire suppression system, buildings which qualify but have an area not more than 1,500 square feet and have under ten occupants.

Section 415.3 (Building Code)

Section 415.4.2 (Building Code)

Section 415.5.2 (Building Code)

Section 415.6 (Building Code)

Provide automatic fire sprinkler system in the highest level of exit discharge serving the underground portion of the building and all levels below.

Provide smoke detectors to activate automatic closing devices on doors between compartments.

Provide at least one smoke detector in every room for mechanical equipment, electrical, transformer, telephone equipment, and elevator machine; in every elevator lobby; in the main return and exhaust air plenum of each air conditioning system serving more than one story; in each connection to a vertical duct or riser serving two or more stories from return air ducts or plenums of KVAC system. Exception: In Group R occupancies, an approved smoke detector may be used in each return air riser carrying not more than 5,000 cfm and serving not more than 10 air inlet openings. Smoke exhaust system must be activated by smoke detectors, automatic suppression system, and manual controls.

Provide fire alarm system throughout when the lowest level of building is more than 60 feet below the lowest level of exit discharge. Alarm to be activated by smoke detectors, automatic fire sprinkler system, and manual pull station. Provide supervised voice communication system in underground portion of building.

OTHERGENJCRALBUILDINGAREAS

Section 903.5 (Building Code)

Provide approved automatic sprinkler system in the following:

Basements more than 2,500 square feet used to manufacture, repair, sell or store combustible material or when used as lounge or night club regardless of size.

In buildings without suitable access per Section 703.2 of this code. Spray finishing booth, area or room.

4-228 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 391: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL BUILDING AREAS (continued)

Section 903.5 (Building Code) per floor. (continued)

Enclosed parking garage more than 65 feet high and more than 10,000 square feet

Repair garages two or more stories high and more than 10,000 square feet in single floor area.

Single story repair garages more than 15,000 square feet Basement garages or repair garages in basement except R3 occupancies. Commercial truck storage garage more than 5,000 square feet Bus garages for four or more buses.

Section 903.7.3 (Building Code) and Chapter 36 (Fire Code)

Provide approved automatic sprinkler system with high-piled combustible stock as required by fire prevention code.

NORTH CAROLINA DAY-CARE STANDARDS

Section 418.1 & .2 (Building Code) and Chapter 45 (Fire Code) (Added)

Provide electrically operated smoke detector with battery backup, or one electrically operated and one battery operated detector located next to each other in all fami1,v da,v-care homes.

Provide manualfire alarm device having a distinct sound, which can be distinguished as an emergency signal in large day-care homes. Also provide approved labeled automatic smoke andior heat detectors in all unoccupied spaces, such as basements, workshops, and fossil fuel fired furnace rooms.

NORTH CAROLINA RESIDENTIAL CARE HOMES

Section 419.2 (Added)

In residential care homes keeping no more than s(x ambulatory adults or six unrestrained ambulatory children, provide smoke detectors on all levels as required by the state electrical code.

Section 419.3 (Added)

In small residential care homes, provide sprinklers per NFPA 13R ifbuilding not of one-hour.fire resistant construction. Provide smoke detectors on all levels per state electrical code and install heat detectors in all attic spaces. Provide building fire alarm system per NFPA 72.

4-229 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 392: NEMA GUIDE CODE Fire Alarm & Detection System

NORTH CAROLINA RESIDENTIAL CARE HOMES (continued)

Section 419.4 (Added)

Provide sprinklers which; are electrically connected directly to an approved central station.faciIi0, in all areas of small non-antbulator,v care,facilities keeping no more than six adults or six children who are unable to respond and evacuate without assistance.

Section 419.5 (Added)

In large residential care facilities keeping no more than I 2 residents, provide sprinklers per NFPA 13R. Provide approved smoke detectors connected to the building,fire alarm system in corridors. A.fire alarm sysrem must be provided per NFPA 72.

4-230 North Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 393: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF NORTH DAKOTA Administrative Requirements

Building Code

1994 UBC Code

Fire Prevention Code

1994 UFC and certain NFPA National Fire Codes and

Amendments Standards

No amendments No amendments I I

Preemptive I Mandatory statewide. Local IMandatory statewide. Local jurisdictions may amend to conform to local needs.

Application jurisdictions may amend to make more stringent.

Promulgation Richard Gray State Building Code/ADA Program Manager 'Division of Community

600 East Boulevard Avenue - IDept. 105 14th Floor, State Capitol Bismarck, ND 58505-0170

~ Services

Dan Hoium State Fire Marshal P. O. Box 1054 Bismarck, ND 58502-1054 (701) 328-5555

Enforcement (701) 328-2094 Local jurisdictions Local jurisdictions

Life Safety Code

1997NFPA 101

Comments

Summary of Amendments

No amendments

Mandatory for state-owned buildings, health-care facilities, schools, hotels, bars, theaters, churches, and other places of assembly. Voluntary for other occupancies. Dan Hoium State Fire Marshal P. O. Box 1054 Bismarck, ND 58502-1054 (701) 328-5555

If a local jurisdiction elects to adopt a code, it has to be the state code.

See summary for 1994 Uniform Codes and 1997 NFPA 101 in Chapter 3 for fire alarmídetection systems requirements.

Dan Hoium State Fire Marshal P. O. Box 1054 Bismarck, ND 58502-1054 1701 328-5555

4-231 North Dakota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 394: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Codes are revised on a three-year cycle or as new materials are approved.

History: North Dakota adopted a statewide building code in 1982. The plumbing code, originally a state-written code, was adopted in 1941. The first electrical code was adopted in 1920.

4-232 North Dakota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 395: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OHIO Administrative Requirements

Code

Amendments

Preemptive Application

Prömuigation

Enforcement

Comments

Summary of Amendments

Building Code

1996 NBC

State amendments

Mandatory statewide for all buildings except 1,2, and 3 family detached. Local jurisdictions may supplement.

John W. Brant Executive Secretary Department of Commerce Board of Building Standards 6606 Tussing Road P. o. Box 4009 Reynoldsburg, OH 43068- 9009

Local jurisdictions or Henry Helton, CBO Bureau of Construction Compliance Department of Commerce Division of Industrial Compliance 6606 Tussing Road Reynoldsburg, OH 43068- 9009

Local building departments

(614) 644-2613

(614) 728-5293

must be certified by the state before they can approve plans and make inspections.

Fire Prevention Code

1996 NFPC

State Amendments

Mandatory statewide for all buildings except 1,2, and 3 family detached. Local iurisdictions may adopt and supplement. Michael G. Kraft Chief of Technical Services Department of Commerce Division of State Fire Marshal 6606 Tussing Road Reynoldsburg, OH 43068- 9009 (614) 728-5460

Local jurisdictions or Michael G. Kraft Chief of Technical Services Department of Commerce Division of State Fire Marshal 6606 Tussing Road Reynoldsburg, OH 43068- 9009 (614) 728-5460

Local building departments must be certified by the state before they can approve plans and make inspections.

centers and facilities, Group H, I, and Group R occupancies.

Life Safety Code

Vone

Some local jurisdictions have adopted NFPA 1 O I .

n for Group E child day-care

See summary of 1996 BOCA codes in Chapter 3. The state’s amendments to the National Building Code are minimal as follows:

Deletes the exception in Section 904.6. In Section 904.9 adds several exceptions as to when an automatic fire suppression system is not required in Group R-2 occupancies. These exceptions do require installation of automatic fire detection system and smoke detectors if an automatic fire suppression system is not present.

4-233 Ohio

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 396: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: The State of Ohio has adopted the BOCA National Building Code. When the new edition comes out, the Board of Building Standards reviews the code; then holds public hearings. The Board may then adopt the code. The process takes approximately a year.

History: Regulations for various uses, such as schools, industrial buildings, and assembly date back to the early part of the century and were enacted under the Department of Industrial Relations. These standards are still regulated by that department which has become the Division of Industrial Compliance under the Department of Commerce. In the early 1950s, these various standards were compiled into a building code. However, the Ohio State Legislature did not pass the measure to implement a building code. A few years later a Board of Building Standards was created and the revised building code was adopted by this board.

4-234 Ohio

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 397: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OKLAHOMA Administrative Requirements

Building Code

Tone Code

Fire Prevention Code

1996 NFPC ~

Amendments

Boulevard, Suite 280 Oklahoma City, OK 73 105

Preemptive Application

Local jurisdictions

Promulgation

(405) 522-5005 Local jurisdictions or Enforcement

1999 NBC is enforced for all Comments (405) 522-5005 Fire Marshal's Office does

Summary of Amendments

Local jurisdictions

Ed Chappel Division Chief, Code Enforcement Office of State Fire Marshal 4545 North Lincoln Boulevard, Suite 280 Oklahoma City, OK 73 1 O5

facilities constructed for state use. Contact: Ron DeLuca Chief Architect Department of Central Services Construction and Properties Division 2401 North Lincoln Boulevard, Suite 106 Oklahoma City, OK 73 105

plan review and inspection. Applies 1997NFPA 101 and/or 1996 BOCA National Building and Fire Prevention Codes' fire protection requirements to new and most existing occupancies.

Life Safety Cade

1994NFPA 101

State amendments

aandatory statewide for all àcilities constructed for state Ise and certain institutional, issembly, educational, and .esidential occupancies. 5d Chappel Division Chief, Code %forcement Dffice of State Fire Marshal 1545 North Lincoln Boulevard, Suite 280 3klahoma City, OK 73 1 O5

Local jurisdictions or Ed Chappel Division Chief, Code Enforcement Office of State Fire Marshal 4545 North Lincoln Boulevard, Suite 280 Oklahoma City, OK 73 105

:405) 522-5005

c405) 522-5005 Fire Marshal's Office does plan review and inspection. Applies 1997 NFPA 101 and/or 1996 BOCA National Building and Fire Prevention Codes' fire prevention requirements to new and most existing occupancies. New and existing day-care facilities are to be constructed and protected by NFPA 1 O 1.

(405) 521-2111 I

care facilities are to be constructed and protected by the life safety code. Also Group 1-1 are buildings and structures which house seven or more individuais. A facility with six or less occupants is to be classified as a residential use group.

See summary of 1996 National Codes and 1997 NFPA 1 O 1 in Chapter 3.

4-235 Oklahoma

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 398: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Code change coincides with three-year model code update cycle. Code changes must go through the state legislature, the governor, and the State Fire Marshal Commission.

History: The State of Oklahoma does not have a statewide building code. Most of its large cities use the BOCA National Building Code and some use the Standard Building Code.

Oklahoma uses the BOCA National Codes for all of its state buildings. The State Fire Marshal uses the BOCA Code for fire and safety requirements in state-owned buildings, and in certain institutional, assembly, educational, and residential occupancies.

The state requires electricians, plumbers, and HVAC tradespeople to be licensed. To be licensed, these trades are required to use the National Building, International Mechanical and Plumbing Codes, and National Electrical Code.

4236 Oklahoma

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 399: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OREGON Administrative Requirements

Amendments

Preemptive Application

Promulgation

Code

State amendments State amendments

Mandatory statewide except 1 Mandatory minimum except 1 and 2 family dwellings not and 2 family dwellings not more than 3 stories in height more than 3 stories in height. and farm-agriculture buildings. Local jurisdictions may amend Local jurisdictions may amend or supplement to make more with state approval. stringent. Peggy Collins Roger Severson Building Official Fire Codes Program

Building Fire Prevention I Code Code

Department of Consumer and Business Services Building Codes Division P. O. Box 14470 Salem, OR 97309

1997 UBC I1997 UFC

Coordinator Office of the State Fire Marshal 4760 Portland Road, NE S a l a , OR 97305-1760

(503) 373-1258 Local jurisdictions or Ravi Mahajan, P.E. Department of Consumer and Business Services Building Codes Division P. O. Box 14470 Salem, OR 97309 (503) 373-1354

Enforcement (503) 378-3473 Local jurisdictions or Roger Severson Fire Codes Program Coordinator Office of the State Fire Marshal 4760 Portland Road, NE Salem, OR 97305-1760 (503) 378-3473

Comments

Summary of Amendments

Life Safety Code

None

State adds new Use Group SR for occupancies where personal care is administered that are licensed by or under the authority of the Oregon Department of Human Resources or any other state agency. See the following pages for summary of state requirements.

4-237 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 400: NEMA GUIDE CODE Fire Alarm & Detection System

Code Chance Cycle: The State of Oregon reviews new model codes as they are published and reviews submitted proposed amendments annually. The proposed model codes and states amendments are adopted by the Building Codes Agency Administrator with approval of advisory boards following public hearings. The code change cycle of three years is comparable with the model code cycle.

History: Prior to 197 1, most large towns in Oregon had construction codes and a few had mechanical codes. At the state level, several of the codes, which are now called specialty codes, were enforced by different branches of state government. Plumbing codes were enforced by the Health Department; electrical, boiler, and elevator codes by the Bureau of Labor; and fire and existing codes by the State Fire Marshal. There were no state structural and mechanical codes. Some local governments adopted these codes, usually based on ICBO codes, but amended up or down at local discretion. Fi@-three different variations of the Uniform Building Code were alleged in the Portland metropolitan area. Sixteen counties and many small cities had no codes.

In 1971, existing state codes-enforcing bodies were brought together in the Department of Commerce. In 1973, the State Legislature enacted the Building Code Law. Key concepts included state adoption of model codes (including structural, mechanical, plumbing, electrical, elevator, boiler, and amusement rides) with state amendments, statewide uniformiíy of codes (no local amendments), local enforcement option, and mandatory certification of building officials, plans examiners and inspectors.

Subsequent legislation has exempted farm buildings and partially exempted moved buildings from the structural code. Increased legislative interest in energy conservation and removal of architectural barriers to the handicapped has strongly influenced state amendments to the Uniform Building Codes. The basic provisions have remained intact now for 16 years.

The Building Codes Division became the Building Codes Agency with the abolishment of the Department of Commerce in 1987. This agency is charged with adopting and enforcing a uniform statewide building code. This code relates to the construction, reconstruction, alteration, and repair of buildings and other structures and to the installation of mechanical, plumbing, and electrical devices and equipment. The agency administers fourteen specialty codes and regulates six other construction industry-related activities. The agency is also responsible for examining, certifying, registering, and licensing 1 1 professions and issues operating permits. Continuing education programs and state administration and enforcement are funded by a five percent surcharge on permits.

4-238 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 401: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OREGON 1997 ICBO Use Group Classifications with State Amendments

GROUP A - ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1

A-2

A-2.1

A-3

A 4

Assembly building with stage and occupant load of 1,000 or more.

Building or portion thereof; having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Building or portion thereof; with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROW E - EDUCATIONAL

Sub-classify in divisions as follows:

El Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

E 2 Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

E 3 Buildings used for day-care purposes for more than six persons.

4-239 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 402: NEMA GUIDE CODE Fire Alarm & Detection System

GROW F - FACTORY AND INDUSTRIAL

Building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations. Sub-classify in divisions as follows:

F-1 Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

F-2 Low-hazard factory and industrial occupancies including facilities producing noncombustible or non-explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1 Buildings with quantity of material in excess of building code limitations, which present high explosion hazard, including bur nor limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days.

ta Manufacturing of Class 1.4G fireworks. ta Unclassified detonatable organic peroxides. ta Class 4 oxidizers. ta Class 4 or Class 3 detonatable unstable (reactive) materials.

H-2 Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to: ta Class I organic peroxides. ta Class 3 non-detonatable unstable (reactive) materials. ta Pyrophoric gases. ta Flammable or oxidizing gases. ta Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in closed

ta Class 3 oxidizers. + Class 3 water-reactive materials.

containers pressurized at more than 15 psi gauge. Exception: aerosols.

4-240 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 403: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS (continued)

H-3 Buildings with quantity of materials in excess of building code limitations, which present high fire or physical hazard, including but not limited to:

Class II, III, or IV organic peroxides. Class 1 or 2 oxidizers. Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed containers or systems and containers pressurized at 15 psi gauge or less, and aerosols. Class III-B combustible liquids.

ta Pyrophoric liquids or solids. ta Class i or 2 water-reactive materiais. ta Flammable solids in storage. ta Flammable or oxidizing cryogenic fluids (other than inert).

Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

I34 Repair garages not classified as Group S-3.

H-5 Aircraft repair hangars and heliports not classified as Group S-5.

H-6 Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

H-7 Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to:

Corrosives, except stationary lead-acid battery systems. ta Highly toxic materials.

Irritants. ta Sensitizers.

Other health hazards.

GROUP I - INS-ONAL

Sub-classi@ in divisions as follows:

1-1.1 Nurseries for full-time care of children under the age of six, hospitals, sanitariums, nursing homes with non- ambulatory patients, and similar buildings, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

4-241 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 404: NEMA GUIDE CODE Fire Alarm & Detection System

1-1.2

I-1.3

1-2

1-3

1-4

Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

Health-care centers f o r ambulatory patients receiving outpatient niedical care which may render the patient incapable of unassisted self-preservation, each tenant space acconzmodatingjve or less such patients.

Nursing homes for ambulatory patients, homes for children six years old or over, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

Mental hospitals, mental sanitariums, jails, pris ons, reformatories, and buildings where personal liberties of inmates are similarly restrained, except buildings used only for private residential purposes for family group.

Correctional facilities including jails, prisons, halfway houses and juvenile detention and correctional educatio1 facilities where egress is controlled.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL

Sub-classify in divisions as follows:

R-1 Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

R-2 Classification not used.

R-3 Dwellings, lodging houses, and congregate residences, each accommodating ten persons or less. Also included ad foster homes in which residential care is provided forfive or fewer adults who are not related by blood or marriai

4-242 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 405: NEMA GUIDE CODE Fire Alarm & Detection System

GROW S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

s-1 Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

s-2 Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

s -3 Repair garages and parking garages not classified as S-4

S 4 Open parking garages.

s -5 Aircraft hangars and helistops.

S-6 Mausoleums and columbariums

GROUP SR - SPECIAL RESIDENTIAL

Occupancies where personal care is administered that are licensed by or under the authority of the Oregon Department of Human Resources or any other state agency. Sub-classify in divisions as follows:

SR-1 A building or portion thereof used for lodging, boarding and personal care of residents whose evacuation capabilitj is classified as "Impractical." SR-1 has the following classifications:

SR-1.1 Large, licensed to provide care for 17 or more residents.

SR-1.2 Small, licensed to provide care for 6 to 16 residents.

SR-1.3 Licensed to provide care for five or less residents.

SR-2 A building or portion thereof used for lodging, boarding and personal care of residents whose evacuation capabilit: is classified as "Slow." SR-2 has the following classifications:

SR-2.1 Large, licensed to provide care for 17 or more residents.

SR-2.2 Small, licensed to provide care for 6 to 16 residents.

SR-2.3 Licensed to provide care for five or less residents.

4-243 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 406: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP SR - SPECIAL RESIDENTLAL íconîinued)

SR-3 A building or portion thereof used for lodging, boarding and personal care of residents whose evacuation capabilit< is classified as "Prompt." SR-3 has the following classifications:

SR-3.1 Large, licensed to provide care for 17 or more residents.

SR-3.2 Small, licensed to provide care for 6 to 16 residents.

SR-3.3 Licensed to provide care for five or less residents.

GROUP U - UTILITY

Sub-classify in divisions as follows:

u1 Private garages, carports, sheds and agricultural buildings.

IF2 Fences over six feet high, tanks and towers.

4-244 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 407: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OREGON 1997 Uniform Codes (ICBO) with State Amendments

Fire AlarmlDetection Systems

Required

Required

Occupancy Type Il

Required

Required

Group F - Factory Industrial

Group H - Hazardous H-i - Flammables/

Explosives H-2 - Moderate

Explosion Hazard H-3 - High Hazard H-4 - Repair Garages H-ó - Semiconductor Facilities H-7 - Health Hazards

II

Group I- Institutional Hospitals Nursing Homes

Group M - Mercantile

R-1 - Hoteihíultifamily

Group SR - Special Residential

High-rise -New and Existing Construction B-2- Offices R-1 - HotelMultifamily

Covered Maiis

Automatic Fire Sprinkler Systems

Required Required Required

Required

Required

Required

Required Required > 3,000 sq. ft. Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./fìoor > 24,000 sq. ft. total

> 3 stories

Required

Required

> 75 fi. 7 5 ft.

Required

Fire Alarm Systems

Automatic Detection Systems

Required

Required > 50 occupants

Required

Required Required

I Required Required Required

Required Required Required

~

> 3 stories > 3 stories

> 75 ft. > 75 ft.

> 75 ft. > 75 ft.

4-245 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 408: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF OREGON 1997 Uniform Codes (ICBO) with State Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Provide automatic sprinkler systems in Group A as follows:

total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area.

Exhibition and display rooms more than 12,000 square feet Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A 4

ta Multi-theater complexes. ta Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. ta All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoiriing such stages. ta Smoke-protected assembly seating, except press boxes, storage less than 1,000 square feet, or in conjunction with outdoor seating.

Rooms and un-separated accessory uses more than 5,000 square feet in

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is 1,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUP B - BUSINESS

Section 304.2.2.3 (Building Code) (Added)

Provide automatic$re sprinkler system in buildings containing lockup facilities. Install in smoke control zone in which lockup cells are located. Also provide automatic smoke detection system in lockup cell area. Install per Fire Code Group I-3 occupancies.

4246 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 409: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Section 305.9 (Building Code) and fire alarm. Section 1007.2.4 (Fire Code)

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Section 1007.3.4 (Building Code) and Exceptions: Section 1007.2.4.2 (Fire Code)

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room.

1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to- ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROW F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire-sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

4-247 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 410: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Section 307.11 (Building Code)

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

Provide automatic fire extinguishing systems throughout H-I, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

GROUP I - INSTJTUTIONAL

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code) (Amended)

Provide approved manual and automatic fire alarm system in all Group I occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas. An automatic auxiliary power supply acceptable to State Fire Marshal must be provided on the premises to maintain operating energy to alarm system.

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code) (Am ended)

Section 1007.2.7.1.1 (Fire Code)

Provide approved smoke detectors in patients sleeping rooms of hospital and nursing homes. Inter-tie with the building f ire alarm system. Actuation must cause a visual display on the corridor side. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups 1-1.1,1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

4-248 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 411: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL ícontinued)

Section 308.2.2.3 (Building Code) (Added)

Section 1007.2.7.2.4 (Fire Code)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code) (Am ended)

Appendix Chapter 3, Division 1 (Building Code)

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and Section 1003.2.8 (Fire Code)

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code)

Provide.fire sprinkler systeni and automatic smoke detection and alarni s,vstem installed per Fire Code in Group I-4 equipped with automatic releasing egress control devices and housed in one-story building of Tvpe V one-hour construction.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

Provide automatic sprinkler system throughout Group I occupancies.

Alternative provisions for Group 1-3 housing with more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire alarm system.

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer's instructions and receiving primary power from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

4249 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 412: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings; provide a fire aladcommunication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2 ) Building with approved supervised fire sprinkler system throughout and with local alarm system.

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick- response standard sprinklers in dwelling units and guest rooms.

Section 1007.2.9.1.3 & .4 (Fire Code)

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

GROUP SR - SPECIAL RESIDENTIAL

Section 3 12A.3.3.5.3 (Building Code) (Added)

Provide automatic sprinkler system and approved.fire alarm and detection system in any Group SR occupancj? provided with egress control devices.

Section 312A.12 (Building Code) (Added)

Provide smoke detectors aspart of the alarm system in SR occupancies per locations indicated by Section 310 or Group I occupancies. Install all smoke detection, f ire alarm and automatic sprinkler systems to be electrically interconnected and have an automatic auxiliary power supply.

HIGHRISE, NEW CONSTRUCTION, GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCLJPANCIES

Section 403.2 (Building Code)

Provide approved automatic sprinkler system; smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction.

4-250 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 413: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES (continued\

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Section 1007.2.12.8 (Fire Code)

Section 1007.2.12.9 (Fire Code)

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic fire -detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 81-A.

Provide automatic smoke-detection system throughout building when special egress-control devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smoke-control system.

Provide manual fire alarm system in lumber, plywood, and veneer mills.

4-251 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 414: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE, GROUP B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Ap pendi Chapter 34 Division II (Building Code) and Appendix 1-B (Fire Code)

(The state does not adopt these Appendix Chapters.)

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Appendix Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES (GROUP R DIVISION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area mo re than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

Section 904.2.9 (Building Code) (Added)

Provide automatic sprinkler system under piers or wharves regulated by Section 418A of the state building code and exceeding 200 feet in length or 5,000 square feet in area. System must comply with NFPA 307-1 990.

4-252 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 415: NEMA GUIDE CODE Fire Alarm & Detection System

Appendix Chapter 34 Division 1, Section 3408 (Building Code) and Appendix 1 -A (Fire Code)

Section 713 (Building Code)

(The state does not adopt these Appendix Chapters.)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

4-253 Oregon

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 416: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF PENNSYLVANIA Administrative Requirements

Building Code

lone Code

Fire Prevention Code

Fire and Panic Regulations

Amendments

,ocal jurisdictions

Preemptive Application

other code is adopted. Charles Sludden, Jr. Promulgation

:he adoption and enforcement bf building codes is under the iuthoritv of local iurisdictions.

Enforcement Director Department of Labor and Industry Bureau of Occupational and Industrial Safety Labor and Industry Building Seventh and Forster Streets, Room 1529 Harrisburg, PA 17120

Philadelphia, Pittsburgh, and Scranton are exempt.

(717) 787-3323 Comments

Summary of Amendments

I State-written I

!Minimum requirements for all buildings with four or more persons housed, employed, or assembled therein. Local jurisdictions must enforce if no

Director Department of Labor and

Bureau of Occupational and Industrial Safety Labor and Industry Building Seventh and Forster Streets, Room 1529 Harrisburg, PA 17 120

Industry

l(717) 787-3323 .ocal jurisdictions Ilharles Sludden, Jr.

Life Safety Code

Fire and Panic Regulations

State-written

Minimum requirements for all buildmgs with four or more persons housed, employed, or assembled therein. Local iurisdictions must enforce if no other code is adopted. Charles Sludden, Jr. Director Department of Labor and

Bureau of Occupational and Industrial Safety Labor and Industry Building Seventh and Forster Streets, Room 1529 Harrisburg, PA 17120

Charles Sludden, Jr. Director Department of Labor and Industry Bureau of Occupational and Industrial Safety Labor and Industry Building Seventh and Forster Streets, Room 1529 Harrisburg, PA 17 120

Philadelphia, Pittsburgh, and Scranton are exempt.

Industry

(717) 787-3323

(717) 787-3323

:ire and panic regulations provide requirements for all buildings that have four or more persons loused, employed, or assembled therein.

4254 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 417: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: There is no set schedule. Revisions to any of the state codes are made by the appropriate governing committees or agencies and have to go through the state's administrative procedures process of publication, a public comment period, and hearings.

History: Administered by the Department of Labor and Industry, Pennsylvania's revised Fire and Panic Regulations went into effect May 19, 1984, the first such revisions in nearly 30 years.

Major changes in the new Fire and Panic Regulations include:

The use of automatic fire detection devices such as smoke or heat detectors in group habitation occupancies, including hotels, motels, dormitories, and apartments. The provision does not include private family dwellings. The installation of automatic sprinkler systems in all new high-rise buildings and high risk portions of new assembly occupancies.

The specification of the minimum size and type of all fire extinguishers in new or renovated buildings as well as standards for maintenance of the units. The establishment of standards for interior finishes such as carpeting, draperies, and wall coverings in means of egress and assembly areas. Installation in existing buildings of an interconnected smoke detection system in buildings where persons sleep such as hotels, motels, apartments, and dormitories.

tx The installation of panic hardware on all exit doors, including doors to the outside and fire tower doors.

4-255 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 418: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF PENNSYLVANIA Use Group Classifications

GROUP A - ASSEMBLY

Buildings used or designed primarily for assembly of persons for amusement, entertainment, worship, recreation, sports, transportation, military drilling, dining, and similar purposes. Sub-classiSl as follows: A-1 - capacity 501 or more; A-2 - capacity 101 - 500; A-3 - capacity 4 - 100.

GROUP B - EDUCATIONAL

Buildings used or designed primarily for education or instruction such as nursery schools, day-care centers, group day-care homes, and similar facilities.

GROUP C - RESJDE"STITUTI0NAL

Buildings used or designed primarily for habitation by at least 4 people. Sub-classify as follows:

C-1 - Buildings with sleeping facilities for at least 4 people who are mostly incapable of self-preservation due to physical or mental illness or disease, or people recovering from such illness or disease. Includes hospitals, sanitariums, nursing homes, convalescent homes, rest homes, and similar facilities.

C-2 - Any building or part thereof with occupants in group-habitation and not covered by any other Group C subdivision. Includes hotels, apartment buildings, multiple dwellings, dormitories, lodging houses, group homes, group foster homes, large personal care homes, children's residential institutions, orphanages, and similar facilities.

C-3 - Any building that only has single living unit housing four to eight residents in group-habitation. Includes dormitories, lodging houses, group homes, group foster homes, small personal care homes, orphanages, children's residential institutions, and similar facilities with four to eight residents.

C 4 - Apartment units that qualify for a single means of egress.

C-5 - Any building or part thereof with occupants in group-habitation who are under restraint and therefore mostly incapable of self-preservation. Includes jails, prisons, reformatories, correction houses, and similar facilities.

4256 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 419: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP D - COMMERCIAL. OFFICE. AND INDUSTRIAL OCCUPANCIES

Buildings used or designed primarily for commercial, storage, office, or similar purposes. Sub-classify as follows:

D-O (ordinary occupancies) - Occupancies involving the manufacture, assembly, warehousing, use, sale, or storage of combustible but not highly flammable products and materials, and buildings used for offices and similar purpose.

D-H (hazardous occupancies) - Occupancies involving such form, characteristic, or volume of highly combustible, explosive, or unstable products or materials as to pose a special fire, life, or toxic hazard. Includes any building, structure, or part thereof used for manufacture, processing, warehousing, use, sale, or storage of highly combustible products or materials.

4-257 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 420: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF PENNSYLVANIA 1987 Fire and Panic Regulations Fire AlarmIDetection Systems

Occupancy Type

Group A - Assembly A-1 A-2

Group B - Educational A-3

Automatic Automatic Fire Fire Alarm Sprinkler Systems Systems Detection Systems

Required Required

> 4 classrooms

Group C - Residential/

c-1 c-2 c - 3 C-4 c-5 Group D - Commercial/

D-O

Institutional

Industrial

Required Required Required --I- **

D-H High-rise Buildings

> 2 stories

Required* Required* Required*

* See requirements and exceptions for single-station smoke detectors.

**See NFPA 101-1981 for fire suppression requirements.

4-258 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 421: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF PENNSYLVANIA 1987 Fire and Panic Regulations

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 51.72 Provide automatic sprinkler protection in Group A-1 storage rooms more than 1 O0 square feet, maintenance and boiler and heater rooms except when operated solely by electricity.

Section 52.72 Provide automatic sprinkler protection in Group A-2 storage areas more than 100 square feet, maintenance and boiler and heater rooms except when operated solely by electricity.

GROUP B - EDUCATIONAL

Section 54.51 Provide fire alarm systems in Group B with more than four classrooms.

GROUP C - R E S I O N A L

Section 55.51 Provide fire alarm systems in Group C-2 more than two stories and buildings with more than 10,000 square feet gross building area except buildings protected with automatic sprinkler system. Provide smoke detectors listed per UL 217, 1980, in common areas such as halls, corridors, stair towers, and basements.

Section 55.82 Provide fire alarm systems in large personal care homes with smoke detectors required in all corridors and rooms.

Section 56.52 Provide fire alarm system in all Group C-3 with smoke detection devices listed per UL 2 17, 1980, on each floor including basement.

Section 57.52 Provide f re alarm system in Group C-4 except buildings protected by automatic sprinkler system and smoke detectors listed per UL 217,1980, in all corridors, stairs, stair towers, or basements.

GROUP D - COMMERCIAMNDUSTRIAL

Section 58.51 Provide fire alarm systems in Group D-O buildings more than two stories with more than 5,000 square feet floor space above the second story.

?RISE BUILDINGS

Section 50.91 Provide automatic sprinkler protection for such buildings that have exterior face exceeding 75 feet when measured from ground level to 5 feet above highest occupiable floor.

4-259 Pennsylvania

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 422: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF RHODE ISLAND Administrative Requirements

Code

I Building I Fire Prevention Code Code

1996 NBC 1997 NFPA 1

Amendments

Preemptive

State amendments State amendments

Mandatory statewide. Local Mandatory statewide except Application iurisdictions may not amend.

Promulgation

1,2, or 3 family dwellings. Local jurisdictions may adopt more stringent provisions, except for those related to fire

Enforcement

Joseph A. Chillo

Comments

alarm systems and explosives. Irving J. Owens

Commissioner State Building Commission One Capitol Hill, Second Floor Providence, RI 02908-5859 (401) 222-3529

Local jurisdictions

I I

State Fire Marshal Division of the State Fire Marshal’s Office 24 Conway Avenue Quonset/Davisville Industrial Park North Kingstown, RI 02852 (401) 294-0861 Local jurisdictions or Irving J. Owens State Fire Marshal Division o f the State Fire Marshal’s Office 24 Conway Avenue Quonset/Davisville Industrial Park North Kingstown, RI 02852 (401) 294-0861

Summary of Amendments

Life Safety Code

1997 NFPA 101

Fire Codes: can be used by local authorities as the accepted standard with regard to fire safety for any unforeseen conditions. In Rhode Island the BOCA National Building Code provisions are supplemental to any applicable provisions of the Rhode Island State Fire Prevention Code. The most restrictive provisions of each code shall apply. The applicable provisions of the State Fire Prevention Code are summarized in the following pages.

No amendments

Mandatory for all new facilities. Local jurisdictions may adopt more stringent provisions, except for those related to fire alarm systems and explosives. h i n g J. Owens State Fire Marshal Division of the State Fire Marshal’s Office 24 Conway Avenue Quonset/Davisville Industrial Park North Kingstown, RI 02852 (401) 294-0861 Local jurisdictions or Irving J. Owens State Fire Marshal Division of the State Fire Marshal’s Office 24 Conway Avenue Quonset/Davisville Industrial Park North Kingstown, RI 02852 (401) 294-0861 190 edition of NFPA National

4-260 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 423: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: The state is on a three-year cycle concurrent with the publication of new editions of the model codes. The Building Code Standards Committee adopts, promulgates, and administers the State Building Code, and the Fire Safety Code Board of Appeal and Reviews has the authority to promulgate, amend, or repeal provisions of the State Fire Safety Code.

History: Based upon legislation originated by the Department of Community Affairs, the Building Code Standards Committee was appointed by the governor in i 973 to draft the first act promulgating the first statewide building code. After two years of work and several hearings, the Committee submitted legislation based upon the adoption of the 1975 BOCA Basic Building Code. Through a series of meetings with the legislature, the act was finally adopted in 1976 and was made effective July 1, 1977. This included the One- and Two-Family Dwelling Code, BOCA Plumbing Code, BOCA Mechanical Code, and the National Electrical Code.

4-261 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 424: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF FUIODE ISLAND Fire AlarmDetection Systems

Rooming Houses Required Required Required

Mercantile > 2 stories Required

Covered Malls Required Required

Business > 2 stories Required

1 Industrial > 2 stories Required

, Storage > 2 stories Required

NFPA - Occupancy Assembly Class A Class B

Automatic Fire Fire Alarm Automatic Sprinkler Systems Systems Detection Systems

Required Required

I Health Care I Required I Required I Required

Class C Educational

Required Required Required Required

I I I

_ _ Apartments 1 > 3 stories 1 Required 1 Required

Hotels/Motels

> 6 living units

Required Required Required

Boarding Houses Required Required Required

4-262 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 425: NEMA GUIDE CODE Fire Alarm & Detection System

- Community Residences Required Required

Detentional and Correctional Required

STATE OF RHODE ISLAND Fire Prevention Code

Requirements and Exceptions

NOTE: All new occupancies are to comply with the provisions of the current Rhode Island Fire Prevention Code and the 1997 Edition of NFPA 101 Life Safety Code.

ASSEMBLY

Section 23-28.6-18 (State Fire Code)

HEATHCARE

Section 23-28.10-1 (State Fire Code)

SCHOOLS

Section 23-28.12-15 (State Fire Code)

Section 23-28.12-22 (State Fire Code)

Section 23-28.15-13 (State Fire Code)

HOTELSMOTELS

Section 23-28.7-14 (State Fire Code)

Section 23-28.7-16 (State Fire Code)

Provide fire alarm systems in Class A, B, and C assembly occupancies.

Provide approved system of automatic sprinklers installed per NFPA 13- 1989 and fire alarm system in all new health-care facilities and all existing buildings converted to such use.

Provide full coverage fire alarm system in all educational occupancies.

Provide automatic sprinklers per NFPA 13-1989 in existing schools of combustible construction with student occupancy above second story except such buildings with one-hour construction enclosing all stairways and corridors.

Provide full coverage fire alarm system in all child day-care centers for 20 or more children.

Protect all new hotels and motels and additions or conversions by approved system of automatic sprinklers installed per NFPA 13-1989.

Provide fire alarm systems in every hotel and local single station AC smoke detector in every sleeping room.

4263 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 426: NEMA GUIDE CODE Fire Alarm & Detection System

BOARDINGHOMES

Section 23-28.13-2 (State Fire Code)

Section 23-28.13-19 (State Fire Code)

Section 23-28.13-34 (State Fire Code)

Provide automatic sprinklers installed per NFPA i 3-1989 in'every new boarding home and existing building converted to such use.

Provide fire alarm system in every boarding house. In addition, install a local single station smoke detector in each sleeping room.

Provide hard-wire smoke detector system in all group care and foster care residential units.

ROOMING HOUSES

Section 23-28.14-12 (State Fire Code)

Provide fire alarm system in every rooming house. In addition, install a local single station smoke detector in each sleeping room.

Section 23-28.14-13 (State Fire Code)

Install complete approved automatic sprinkler system per NFPA 13-1989 in every new rooming lioust: a d existing buildings converted to such use.

APARTMENT HOUSES

Section 23-28.16-14 (State Fire Code)

Provide approved system of automatic sprinklers installed per NFPA 13- i 989 in all apartment houses more than three stories above basement or having more than six living units and existing apartment houses with sleeping accommodations above third story.

Section 23-28.16-16 (State Fire Code)

Provide fire alarm systems in all apartment buildings. In addition, provide smoke detection system in ali living units.

INDUSTRIAL. MERCANTILE. BUSINESS. AND STORAGE BUILDINGS

Section 23-28.17-13 (State Fire Code)

Provide approved automatic sprinklers per NFPA 13-1 989 when more than two stories and construction not better than two-hour fire rated.

Section 23-28.17-14 (State Fire Code) storage buildings.

Provide fire alarm system when in all industrial, mercantile, business, and

Section 23-28.17-15 (State Fire Code)

Provide approved automatic fire suppression system throughout a covered mail independent of buildings connected thereto.

4-264 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 427: NEMA GUIDE CODE Fire Alarm & Detection System

Section 23-28.18-3 (State Fire Code)

Provide fire alarm system in every theater.

Section 23-28.304 (State Fire Code) residences.

Provide automatic sprinklers installed per NFPA 13-1989 in all community

Section 23-28.30-14 (State Fire Code)

Provide fire alarm system in every community residence.

DETENTION AND CORRECTIONAL

Section 23-28.38-2 (State Fire Code)

Provide fire alarm system in all detention and correctional occupancies.

NEW RESIDENTIAL

Section 23-28.34-1 (State Fire Code)

EXISTING RESDENTUL

Section 23-28.35-1 (State Fire Code)

Provide AC smoke detectors with battery backup in all buildings constructed or converted for residential occupancy.

Provide smoke detectors in all existing one, two, and three family dwellings at time of sale of property.

4265 Rhode Island

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 428: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF SOUTH CAROLINA Administrative Requirements

Code

I Building I Fire Prevention Code Code

1997 SBC 1997 SFPC

Preemptive Application

I I

Amendments !No amendments /No amendments

Mandatory statewide. Local jurisdictions cannot amend without Building Codes

Promulgation

~

Mandatory statewide. Local jurisdictions cannot amend without Building Codes

Council approval. Council approval. Gary Wiggins Gary Wiggins Administrator Administrator

Enforcement

South Carolina Building Codes Council Department of Labor, Licensing and Regulation Kingstree Building 1 1 O Centerview Drive, Suite 102 Columbia, SC 292 10 (803) 896-4688 (803) 896-4688 Local jurisdictions Local jurisdictions

South Carolina Building Codes Council Department of Labor, ILicensing and Regulation Kingstree Building 110 Centerview Drive, Suite

Columbia, SC 292 1 O i 102

Summary of Amendments

See Chapter 3 for a summary of the Standard Codes.

Life Safety Code

\lone

Local jurisdictions

Local jurisdictions

I Comments

Code Change Cycle: Since the State of South Carolina has adopted the Standard Building Code for state buildings, its cycle and procedures for amendment are according to those established by the Southern Building Code Congress International. The code change cycle is performed on an annual basis.

History: The first building code known to be adopted and used within the State of South Carolina.was a document developed by and for the City of Charleston in 1907. The City of Columbia followed suit with its own local building code in 19 16. From that point forward, the cities and counties of the state gradually started developing and enforcing construction codes on an individual basis. In the mid-l960s, a variety of building codes were in use with little consistency in interpretation and construction practices. By this time, however, a strong movement was taking place to standardize building codes statewide. By act of the South Carolina General Assembly on June 2 1, 1972, the state had authorized the Southern Standard Building Code, later changed to the Standard Building Code, as its first state approved construction document.

4-266 South Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 429: NEMA GUIDE CODE Fire Alarm & Detection System

History (continued):

By that action, the legislation paved the way for uniform code enforcement on a voluntary basis. If a building code is adopted for use within a local jurisdiction, however, it is mandatory that it be a current edition of a document, which has been previously approved by the state. The legislation further provided that local amendments to the adopted building codes could not be made without approval of the South Carolina Building Codes Council. This unique voluntaryimandatory code adoption procedure was initiated and intended to develop consistency in interpretation and construction practices, as well as provide the design professionals with a single set of documents that would be acceptable to all jurisdictions in the state.

On June 13, 1997, the Governor signed legislation requiring all jurisdictions in the state to adopt a building code, in particular, the 1997 Standard Code series and the 1996 National Electrical Code. Local jurisdictions have a three-year time period to adopt the codes. The time allowed is based on population, with jurisdictions under 35,000 populations having the full three years to implement the legislation.

The South Carolina Building Codes Council travels to many cities and counties throughout the state to meet with local officials and assist with code adoptions.

4-267 South Carolina

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 430: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF SOUTH DAKOTA Administrative Requirements

Fire Prevention Code

1994 UFC Code

Life Safety Code

1994NFPA 101

Amendments State amendments

Preemptive Application

State amendments I No amendments

Promulgation

Mandatory for certain occupancies. Voluntary for all ,other occupancies.

IDan Carlson 1 State Fire Marshal Department of Commerce and Regulation 1 18 West Capitol Avenue

‘Pierre, SD 57501 (605) 773-3562

Enforcement

Mandatory for hospitals, nursing homes, and assisted living centers. Voluntary for all other occupancies. Joan Bachman Administrator Department of Health Division of Health Systems Licensure and Certification 6 15 East Fourth Street Pierre, SD 57501-1700

Comments

Dan Carlson State Fire Marshal Department of Commerce and Regulation 118 West Capitol Avenue Pierre, SD 57501 (605) 773-3562

Summary of Amendments

Dan Carlson State Fire Marshal Department of Commerce and Regulation 118 West Capitol Avenue Pierre, SD 57501 (605) 773-3562

Building Code

1994 UBC

Mandatory for certain xcupancies. Voluntary for all 3ther occupancies.

Dan Carlson State Fire Marshal Department of Commerce and Regulation 1 18 West Capitol Avenue Pierre, SD 57501 [605) 773-3562

I (605) 773-3356 I Joan Bachman Administrator Department of Health Division of Health Systems Licensure and Certification 61 5 East Fourth Street Pierre, SD 57501-1700

I I(605) 773-3356 The State Fire Safety Standards adopts the 1994 Uniform Building and Fire Codes applicable to schools, day-care centers, multifamily buildings over six units, hotels, motels, and state-owned buildings. All other occupancies are within the authority of local jurisdictions, which typically adopt the Uniform Codes with few amendments. State sets out specific requirements for both new and existing day-care centers and group family day-care homes. Day-care centers are to be provided with fire alarm systems, smoke detectors, and automatic sprinkler system if located in basement with 1,500 square feet in area. Provide both new and existing group family day-care homes with residential fire detection comprised of interconnected multiple-system smoke detectors receiving primary power from the building wiring.

State is specific that requirements in the Uniform Codes applicable to Educational Occupancies also apply to existing Group E buildings.

See summary of 1994 Uniform Codes andNFPA 101 in Chapter 3.

Code Change Cycle: There is no set schedule. New editions of the model code are adopted when they become available.

4268 South Dakota

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 431: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF TENNESSEE Administrative Requirements

(615) 741-7190 l(615) 741-7190 State codes are mandatory minimum standards to be enforced

Code

-~

by-all local jurisdictions that

Amendments \To amendments

Preemptive Application

Standards, Vol. 1-12 No amendments

~~

Promulgation

vlandatory statewide for all mildings except 1 and 2 àmily dwellings and licensed iealth-care facilities. Local urisdictions may adopt more ;tringent provisions. N . Stuart Crine State Fire Marshal Iept. of Commerce and nsurance 3ivision of Fire Prevention Davy Crockett Tower, Third Floor 500 James Robertson Parkway Vashville. TN 37243-1 162

Enforcement

Mandatory statewide for all buildings except 1 and 2 family dwellings and licensed health-care facilities. Local jurisdictions may adopt more stringent provisions. W. Stuart Crine State Fire Marshal Dept. of Commerce and Insurance Division of Fire Prevention Davy Crockett Tower, Third Floor 500 James Robertson Parkway Nashville, TN 37243-1 162

Comments

1615) 74112981 Local jurisdictions or for

Summary of Amendments

(615) 741-2981 Local jurisdictions or for

Building Code

1997 SBC

Fire Prevention Code

1997 National Fire Codes and

:ertain occupancies: Tim S. Garrington Director, Codes Enforcement Section Dept. of Commerce and [nsurance Division of Fire Prevention Davy Crocket Tower, ïhird Floor 500 James Robertson Parkway Nashville, TN 37243-1 162

certain occupancies: Tim S. Garrington Director, Codes Enforcement Section Dept. of Commerce and Insurance Division of Fire Prevention Davy Crocket Tower, Third Floor 500 James Robertson Parkway Nashville, TN 37243-1 162

Life Safety Code

1997 NFPA 101

No amendments

Mandatory statewide for all buildings except 1 and 2 family dwellings and licensed health-care facilities. Local jurisdictions may adopt more stringent provisions. W. Stuart Crine State Fire Marshal Dept. of Commerce and Insurance Division of Fire Prevention Davy Crockett Tower, Third Floor 500 James Robertson Parkway Nashville, TN 37243-1 162 (615) 741-2981 Local jurisdictions or for certain occupancies: Tim S. Garrington Director, Codes Enforcement Section Dept. of Commerce and Insurance Division of Fire Prevention Davy Crocket Tower, Third Floor 500 James Robertson Parkway Nashville, TN 37243-1 162 (615) 741-7190

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 432: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Tennessee codes are updated through rule changes. Rules must be approved by a legislative committee. The schedule for adoption depends on when the new editions are published.

History: Rules promulgated under Tennessee Code Annotated 53-250-1, as amended in 1982, establish statewide minimum standards for construction stability and life safety of all buildings with the exception of one- and two-family dwellings, mobile structures, and facilities licensed by the Department of Public Health. Where a local jurisdiction enforces codes but has not obtained an exemption, designers are required by law to design to the codes adopted by the state as well as any local requirements. Where a local jurisdiction has obtained an exemption, state adopted codes apply only to state-owned buildings and to buildings used for day care or education through 12th grade.

The state has adopted NFPA 1 and the other codes and standards referenced in Annex A of the 1997 National Fire Codes and Standards and the 1997 Standard Building Code.

Plans for state-owned buildings and buildings to be used for day care or education through 12th grade must be approved by the Department of Insurance prior to the start of construction. Where the local government has not received an exemption, plans for correctional or detention facilities, assemblies over 300, and buildings of three or more stories used for hotels, apartments, dormitories, offices, or higher education must be approved by the Department of Insurance prior to the start of construction.

4-270 Tennessee

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 433: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF TEXAS Administrative Requirements

Code

Amendments

Preemptive Application

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

None

Local jurisdictions

Local jurisdictions

The State of Texas is unique in

Fire Prevention Code

None

Local jurisdictions

Local jurisdictions

Life Safety Code

1997 NFPA 101

Mandatory statewide for hospitals. Voluntary for all other occupancies. Zenon Pihut Chief Engineer Department of Health Health Facility Licensing Division 1100 West 49th Street Austin, TX 78756

Zenon Pihut (512) 834-6649

Chief Engineer Department of Health Health Facility Licensing Division 1100 West 49th Street Austin, TX 78756 (512) 834-6649

regulation within the state. Because no statewide building code exists, consult with the local iurisdiction for details on codes used. See Chapter 5 for code Drovisions in Houston and Dallas.

Code Chance Cycle: There is no set schedule. Any proposed code changes go through the legislative process or the state's administrative procedures process of publication, public comment, and hearings. The Texas Commission on Fire Protection has held public hearings to explore the possibility of developing legislation for the adoption of a statewide fire prevention code.

History: The Texas Industrialized Building Code Council issues instructions for the inspection, construction, and installation of industrialized housing and guidelines of all occupancies. Cities in Texas adopt building codes. The state adopts codes for the fire safety of may types of special occupancies.

4271 Texas

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 434: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF UTAH Administrative Requirements

Code

Amendments

~~

Preemptive Application

Promulgation

Enforcement

Bu i Id in g Code

1997 UBC

State amendments

Mandatory statewide. Local iurisdictions may amend with State approval.

Dan Jones Manager of Construction Trades Bureau Department of Commerce Division of Occupational and Professional Licensing Heber M. Wells Building 160 East 300 South P. O. Box 146741 Salt Lake City, UT 84 1 14- 6741 (801) 530-6720 Local jurisdictions

Fire Prevention Code

1997 UFC

State requirements for buildings under jurisdiction of Utah Fire Prevention Board [See listing below.) Mandatory statewide. Local iurisdictions may amend to make more stringent.

Gary A. Wise State Fire Marshal Utah Fire Prevention Board Office of the State Fire Marshal 5272 South College Dr. Suite 302 Murray, UT 84123 (801) 284-6350

Local jurisdictions or Gary A, Wise State Fire Marshal Utah Fire Prevention Board Office of the State Fire Marshal 5272 South College Dr. Suite 302 Murray, UT 84123 (801) 284-6350 The Utah Fire Prevention Law mandates minimum standards for all buildings under the jurisdiction of the Utah Fire Prevention Board. These buildings are: state-owned buildings, public and private schools, college and universitj buildings, and institutional an( assembly occupancies with capacity for 50 or more persons.

Life Safety Code

1997NFF'A 101

ûnly certain chapters adopted by Utah Fire Prevention Board.

Mandatory for state-owned buildings, public and private schools, college and university buildings, institutional, and assembly occupancies with 50 or more occupants. Gary A. Wise State Fire Marshal Utah Fire Prevention Board Office of the State Fire Marshal 5272 South College Dr. Suite 302 Murray, UT 84 123 (801) 284-6350

Local jurisdictions or Gary A. Wise State Fire Marshal Utah Fire Prevention Board Office of the State Fire Marshal 5272 South College Dr. Suite 3 02 Murray, UT 84123 (801) 284-6350

4-272 Utah

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 435: NEMA GUIDE CODE Fire Alarm & Detection System

Summary of Amendments

I See summary of 1997 Uniform Codes and 1997 NFPA 101 in Chapter 3.

Statewide amendments to building code do not affect alarmldetection systems except for exception allowing group day care for seven to twelve children to be in an R-3 occupancy provided smoke detectors installed throughout both new and existing dwelling units. State does not adopt UBC Appendix Chapters 4 and 34 or UFC Appendix Chapter I-A.

Code Change Cycle: Code revisions are ongoing, with new editions of codes adopted when they become available. The Uniform Building Code Commission meets monthly to consider requests for code amendments. Amendments are published on March 1 and September 1 of each year for changes enacted during the preceding six-month period.

The Utah Fire Prevention Board meets quarterly but may conduct meetings as needed to consider requests for amendments to the codes. Amendments are published after public meetings have been held and after they have been approved by the Utah Fire Prevention Board.

4-273 Utah

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 436: NEMA GUIDE CODE Fire Alarm & Detection System

STATE. OF VEFWONT Administrative Requirements

Code

Amendments

Preemptive

Building Fire Prevention Code Code

1987 NBC 1992 NFPA I

1988 supplement and state amendments Mandatory statewide for

State amendments

Mandatory statewide for Application

Enforcement

public buildings, condominiums, multifamily dwellings, and uses involving hazardous materials. Voluntary for all other occupancies. Local ?jurisdictions may amcnd with ~ state approval if more

Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, VT 05641 (802) 479-4435 Local jurisdictions or Robert Mackin Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, VT 05641 1802) 4794435

I stringent. Promulgation I Robert Mackin

Comments I Code known as ?1 989 Vermont Fire Prevention and Building Code.?

public buildings, condominiums, multifamily dwellings, and uses involving hazardous materials. Voluntary for all other occupancies. Local jurisdictions may amend with state approval if more stringent. Robert Mackin Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, VT 05641 (802) 479-4435 Local jurisdictions or Robert Mackin Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, Vï 05641 (802) 479-4435

Life Safety Code

1994 NFPA 101

State amendments

Mandatory statewide for public buildings, condominiums, multifamily dwellings, and uses involving hazardous materials. Local jurisdictions may amend with state approval if more stringent.

Robert Mackin Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, VT 05641 (802) 479-4435 Local jurisdictions or Robert Mackin Assistant Fire Marshal Regional Office Manager Department of Labor and Industry 71 Washington Street, Suite 100 Barre, VT 05641 (802) 479435

4-274 Vermont

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 437: NEMA GUIDE CODE Fire Alarm & Detection System

Summary of Amendments

Code Change Cycle: The Administrative Procedures Act covers all code changes. Public hearings must be held before new codes are signed by the governor. The codes are promulgated by the Commissioner of the Department of Labor and Industry. In some programs the codes are jointly promulgated with related boards.

Vermont amends the National Building Code (NBC) to define when day-care and child-care facilities are considered 1-2, E, or R-3. See 1987 BOCA codes in Chapter 3 for fue alarmídetection system regulations. Note that 1988 NBC supplement revises high-rise buildings to apply to all use groups.

The state amends NFPA 1 (22-2.8.4.8) to require approved automatic suppression systems for fuel dispensing areas where Class 1 flammable liquids are dispensed.

The state amends NFPA 101 to require battery backup for smoke detectors installed in apartments, lodging or rooming houses, and residential board care facilities. Amendments are made to require fire alarm systems to be electrically wired as a Class A system in Class A and B occupancies, multiplex theaters, health care, detention and correctional facilities, and in high- rise buildings.

History: Since 1973 when the duties of the State Fire Marshal were decided, the Department of Labor and Industry has worked on a program to consolidate with the safety requirements for public buildings under the Fire Prevention Division. Beginning with the enforcement of safety codes for fire prevention, electrical, and boilers, the Division now also covers safety programs for elevators and lifts, plumbing, and barrier-free access for the handicapped.

The Division also licenses electricians and plumbers, and plays an active role in public fire safety education. Division personnel are members of the state-level hazardous material response.

4275 Vermont

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 438: NEMA GUIDE CODE Fire Alarm & Detection System

COMMONWEALTHOFVIRGINIA Administrative Requirements

Building Code

Code 1996 NBC

Amendments State amendments

Preemptive Mandatory statewide. Local Application jurisdictions may not amend.

Fire Prevention Code

1996 NFPC

State amendments

Mandatory statewide. Local jurisdictions may adopt more

Promulgation

Amendments

Enforcement

Section 3402, General Requirements, delineates where battery-powered or AC-powered smoke detector devices are to be installed in all buildingdfacilities which are the responsibility of a state department or agency, such as college and university buildings containing dormitories for sleeping purposes, adult care residences, day care centers, nursing homes. Requirements are also specified for smoke detectors for the deaf and hearing-impaired. See Chapter 3 for a summary of the 1996 BOCA National Codes.

Comments

Summary of

Curtis L. McIver State Building Code Administrator Department of Housing and Community Development Division of Building and Fire Regulation 501 North Second Street Richmond, VA 23219-1321

Local jurisdictions (804) 371-7150

1 Commonwealth of Virginia rew

stringent provisions. Curtis L. McIver State Building Code Administrator Department of Housing and Community Development Division of Building and Fire Regulation 501 North Second Street Richmond, VA 23219-1321

Local jurisdictions or Charles E. Altizer State Fire Marshal State Fire Marshal’s Office 1501 North Second Street Richmond, VA 23219-1321

(804) 371-7150

ites most of BOCA NBC Chapte

Life Safety Code

None

34 on Existing Structures.

4-276 Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 439: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Virginia reviews its code every three years as the new BOCA codes are published. A 6O-day notice ofpublic hearings is given, proceeded by ad hoc committee review of staff proposals. About 60 days after the hearing, the nine-member Board of Housing and Community Development adopts the code. The new code becomes effective approximately 60 days after that.

History: The General Assembly of Virginia created a Housing Study Commission in 1970 to study the need for a Uniform Statewide Building Code. The Commission found a "patchwork" or "crazy-quilt" pattern of building regulations in the state. Different model codes were in use, and communities made different amendments to those codes. The dates of the model codes varied from community to community and there was some conflict between state and local building requirements. The solution recommended by the Commission was to establish a Uniform Statewide Building Code having the following characteristics:

Building code to be adopted and amended by a broadly based state board. Provisions of the code to be based on nationally recognized model codes and standards. Every county and every city to be required to enforce the code. No local amendments permitted. Each local enforcement jurisdiction to have a local appeals board which could overrule the building official on his interpretation of the code or on his failure to issue a modification when justified. Availability of a broadly based, technically oriented state appeals board to which decisions of local appeals boards could be carried. State appeals board to be separate from the state board that adopts the code. Mandating uniform administrative and enforcement procedure to be used by local agencies. All state and local building regulations to be superseded by the State Building Code.

The Uniform Statewide Code first became effective in September 1973. In 1982, the General Assembly amended the law to permit the state board to adopt regulations for existing buildings.

4277 Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 440: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WASHINGTON Administrative Requirements

State amendments

~

Code

State amendments Amendments

Staff contact: Al Rhoades Local jurisdictions

~~

Preemptive Application

Promulgation

Staff contact: Al Rhoades Local jurisdictions Enforcement

Comments

Summary of Amendments

Building Code

1997 UBC

Fire Prevention Cade

1997 UFC

Mandatory statewide. Local jurisdictions may amend to make more stringent. State Building Code Council Department of Community, Trade and Economic Development 906 Columbia Street SW P. O. Box 48300 Olympia, WA 98504-8300 (360) 586-8999

Mandatory statewide. Local jurisdictions may amend to make more stringent. State Building Code Council Department of Community, Trade and Economic Development 906 Columbia Street SW P. O. Box 48300 Olympia, WA 98504-8300 (360) 586-8999

Local amendments affecting the construction of single family or multi-family residential buildings (up to four units) must be reviewed and approved by the State Building Code Council before amendments can be enforced.

Life Safety Code

None

State includes family child day-care homes in Group R-3 occupancies and adds a Group LC Occupancy classification to cover facilities providing licensed care to clients regulated by other state agencies such as Departments of Health or Social and Health Services.

In Group LC occupancies smoke detectors are required in sleeping rooms. Also required are automatic sprinkler systems and approved manual and automatic fire alarm system if facility is three or more stories in height or having more than 16 clients.

State requires sprinklers in high-rise buildings with a floor used for human occupancy that is located 75 feet or more above the lowest level of fire department access.

For all other requirements, see summary of 1997 Uniform Codes in Chapter 3.

4-278 Washington

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 441: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: On a yearly basis, the State Building Code Council considers proposals to amend the State Building Code. Unless directed by the State Legislature, federal mandates or court order, the Council will not enter formal rulemaking until 2000 as part of its consideration of adoption of the 2000 series of codes. Preliminary action will be taken each year on proposals submitted by the deadline. The deadline for code change proposals is March 1 of each year and proposais must be submitted on forms provided by the Building Code Council.

History: The Washington State Legislature adopted the State Building Code in 1975. The legislature retained the responsibility for updating the codes until 1975 when the responsibility was delegated to the State Building Code Council. The Council regularly updates the codes on a three-year cycle the year they are published. Codes adopted by the Council must sit through the next session of the state legislature before they become effective.

In addition to the Uniform Codes, the State Building Code Council has written and adopted the State Energy Code and the State Regulations for Barrier Free Facilities. By state statute, administration and enforcement of these codes is vested in the local government level.

4-279 Washington

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 442: NEMA GUIDE CODE Fire Alarm & Detection System

STATE. OF WEST VIRGINIA Administrative Requirements

State supplement

Mandatory statewide.

Code

State amendments

Mandatory statewide.

I Building

Preemptive Application

Promulgation

Enforcement

Code 1996 NBC

Mandatory statewide.

State Fire Commission 1207 Quarrier Street, 2nd Floor Charleston, WV 25301 (304) 558-2191 Staff contact: A. B. Corley, Jr. Administrative Assistant Local jurisdictions

Amendments ]No amendments

Comments

Summary of Amendments

Fire Prevention I Life Safety Code I Code

National Fire Codes & I 1997 NFPA 101 Standards (NFPA) I

State Fire Commission 1207 Quarrier Street, 2nd Floor Charleston, WV 25301

Staff contact: A. B. Corley, Jr. Administrative Assistant Local jurisdictions or Richard Corcovilos Field Deputy Fire Marshal 1207 Quarrier Street, 2nd Floor Charleston, WV 25301

(304) 558-2191

State Fire Commission 1207 Quarrier Street, 2nd Floor Charleston, WV 25301

Staff contact: A. B. Corley, Jr. Administrative Assistant Local jurisdictions or Richard Corcovilos Field Deputy Fire Marshal 1207 Quarrier Street, 2nd Floor Charleston, WV 25301

(304) 558-2191

(304) 558-2191 I(304) 558-2191

adopt the state building code, it is the responsibility of contractors, builders, and architects to comply with the code provisions. The State Fire Marshal enforces the fire code in areas of the state that do not adopt codes.

State Fire Code does not apply to personal care homes for three or less patients, farm buildings, or one- or two-family dwellings. Where there is a conflict between State Fire Code and National Building Code, the State Fire Code takes precedence. See summary for 1996 BOCA National Building Code in Chapter 3 for additional regulations. State modifies requirements for high-rise buildings and fire alarm systems.

4-280 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 443: NEMA GUIDE CODE Fire Alarm & Detection System

Code Change Cycle: Changes in the fire codes are based upon revisions of the NFPA National Fire Codes, specifically the Life Safety Code. The new editions of the BOCA codes are reviewed for possible adoption as they become available.

Histon: West Virginia passed legislation in 1987 to adopt a statewide building code. The legislation authorizes the State Fire Commission to adopt a nationally recognized model building code.

4-281 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 444: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WEST VIRGINIA Fire AlarmDetection Systems

Fire Alarm Systems

> 300 occupants > 300 occupants > 300 occupants Required

II NFPA - Occur>ancv

Automatic Detection Systems

Required Required

Assembly Class A Class B Underground

Educational

(1 Health Care

Required

II Detention and Correctional

Required

II Business

II Industrial

High-rise Buildings

Residential Board and Care II

~~ ~

Automatic Fire S~rinkler Svstems

> 40 ft. > 40 fi.

> 40 ft.

> 40 ft.

> 40 ft.

> 40 fi.

> 40 fi.

> 40 ft.

> 40 ft.

> 40 ft.

Required

Required Required

L > 3,000 sq. ft.

I > 300 occupants

Required I

I

Required

4-282 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 445: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WEST VIRGEVIA Fire Prevention Code

Requirements and Exceptions

ASSEMBLY OCCUPANCIES

Section 87-1- 11.3 (State Fire Code) discharge.

Provide fire alarm systems where: ta Occupancy subject to 300 or more occupants. ta Occupancy subject to 100 or more occupants above or below level of exit

fi Building two or more stories above or below level of exit discharge. Theaters with more than one audience-viewing room.

EDUCATIONAL OCCUPANCIES

Section 87-1- 11.2 (State Fire Code)

Provide fire alarm system in all educational occupancies except classroom buildings less than 2,500 square feet with direct exit to outside from each classroom. Provide complete smoke detection system in open plan classroom concepts; smoke detectors in day-care centers located in buildings other than educational and in corridors of all educational buildings except single story building with direct exit to exterior from every student occupied room. Smoke detectors are required to be hardwired in sleeping rooms and corridors of group day care centers.

"CARE

Section 87-1-6 (State Fire Code)

Section 87-1- 11.4 (State Fire Code)

Provide automatic sprinkler systems in all existing and new nursing convalescent, old age, custodial care, long term or extended care homes or institutions, and primary care facilities per NFPA 13. Exception: Homes caring for not more than three patients.

Provide a fire alarm system in every health care occupancy. Provide an approved automatic smoke detection system in all corridors.

DETENTION AND CORRECTIONAL

Section 87-1- 11.5 (State Fire Code)

Provide a fire alarm system in all detention and correctional facilities with smoke detectors installed in corridors or highest point of cell areas.

4-283 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 446: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTIAL OCCUPANCíES

Section 87-1- 11.6 (State Fire Code)

Provide fire alarm systems in all residential buildings, i.e., hotels, motels, dormitories, lodging and rooming houses, and apartments having 12 or more units or 4 or more stories in height. Exception: One-story motels with 16 or less sleeping rooms having direct exiting to the exterior.

Lodging and rooming houses protected throughout with a sprinkler system must be provided with interconnected hardwired smoke detectors as required by NFPA 72. Provide smoke detectors in inside corridors and in open bay sleeping areas of hotels, motels, dormitories, lodging and rooming houses. Provide approved, self-contained, hardwired smoke detectors in all sleeping rooms.

Provide approved, self-contained smoke detectors in all new and existing apartments. Hardwire smke detectors in new construction.

MERCANTILE OCCUPANCIES

Section 87-1- 11.7 (State Fire Code)

Provide fire alarm in mercantile occupancies more than 3,000 square feet

BUSINESS OCCUPANCIES

Section 87-1- 11.8 (State Fire Code) exit discharge.

Provide fire alarm systems when: Occupancy subject to not more than 300 total occupants. Occupancy subject to not more than 100 occupants above or below level of

Building two or more stories in height above or below level of exit discharge.

INDUSTRIAL

28-3.4 W A )

STORAGE

Provide fire alarm system except total capacity less than 100 persons and less than 25 persons above or below level of exit discharge.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment system provided.

4-284 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 447: NEMA GUIDE CODE Fire Alarm & Detection System

STORAGE (continued)

Provide fire alarm system in garages more than 100,000 square feet in aggregate floor area except open parking garages and garages with automatic sprinkler system throughout.

RESIDENTIAL BOARD AND CARE OCCUPANCY

Section 87-1- 14.8 (State Fire Code)

Provide approved electrically supervised fire alarm and an automatic sprinkler system throughout buildings. Provide single -station smoke detectors, hardwired per NFPA 72, in all individual sleeping rooms. Except as noted above, all facilities classified as residential board and care occupancies shall conform to the 1997 NFPA 1 01, Life Safety Code.

" R I S E BUILDINGS

Section 87-1-10 (State Fire Code)

Apply high-rise definitions to buildings more than 40 feet in height, measured from the lowest level of fire department vehicle access to the floor of the highest normally occupied space used for human occupancy. Provide automatic fire extinguishing systems and fire alarm systems in all high-rise buildings. Provide engineered smoke management system acceptable to authority having jurisdiction.

Section 87-1- 10.5 (State Fire Code)

Provide approved electrically supervised fire department voice communication system in high-rise buildings used for human occupancy 75 feet or more in height.

4-285 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 448: NEMA GUIDE CODE Fire Alarm & Detection System

APPROVED FIRE A L M SYSTEM

Section 87-1-1 1 (State Fire Code) 15,000 c h .

Provide duct-type smoke detector in the return air duct or plenum of all heating, ventilation, and air conditioning systems greater than 2,000 cfm but less than

For W A C systems greater than 15,000 cfm, install duct-type smoke detectors in both supply and return air ducts.

Provide thermal detectors, either fixed temperature or rate of rise, in the following areas in all occupancies requiring a fire alarm system: elevator shafts, attic and cockloft spaces, storage rooms, furnace or boiler rooms, janitor closets, kitchens, school labs, auto shops, woodworking shops, home economics rooms, utility rooms, and locker rooms. Exception: Thermal detectors are not required in sprinkled areas or apartment dwelling units.

Provide smoke detectors in the rooms or areas where electrical distribution panels or transformers are located in all occupancies requiring a fire alarm system.

APPROVED AUTOMATIC SPRINKLER SYSTEMS

Section 87-1-5 (State Fire Code)

Install in all new buildings, used for any occupancies, exceeding the areas indicated in the table on the following page.

4-286 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 449: NEMA GUIDE CODE Fire Alarm & Detection System

BUILDING HEIGHT

Type of

443 Fire-Resistive

332 Fire Resistive

Type II 222 Protected Non-Com

I 111 Protected Limited Combustible

000 Unprotected Limited Unprotected Non-Com

Type III ..

21 1 Ordinary Protected

200 Ordinary Non-protected

Type IV 2" Heavy Timber

Type v 111 Protected Wood Frame

Non-protected Wood I :me

1 Story

40,000

40,000

30,000

30,000

10,000

9,000

7,000

9,000

7,000

5,000

2 story

40,000

30,000

20,000

15,000

6,000

6,000

4,000

6,000

4,000

3,000

More than 2 stories and UD to 40 ft.

10,000

10,000

8.000

5,000

All areas require

sprinklers All areas require

sprinklers

All areas require

sprinklers All areas require

sprinklers All areas require

sprinklers

Not permitted

More than 40 fi.

Sec. 10-Highrise

Sec. 10-Highrise

Sec. 10-Highrise

Sec. 10-Highrise

Not permitted

Not permitted

Not permitted

Not permitted

Not permitted

Not Dermitted

More than 75 fi.

Sec. 10-Highrise

Sec. 10-Highrise

Sec. 10-Highrise

Sec. 10-Highrise

Not permitted

Not permitted

Not permitted

Not permitted

Not permitted

Not uermitted

4-287 West Virginia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 450: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WISCONSIN Administrative Requirements

Enforcement

Comments

Code

(608) 267-9152 (608) 266- 1930 Local jurisdictions or Director, Bureau of Integrated Services Section Chief, Integrated Department of Commerce Services Safety and Buildings Division Department of Commerce 201 East Washington Avenue Safety and Buildings Division P. O. Box 2658 201 East Washington Avenue Madison, WI 53707 P. O. Box 2658 (608) 267-9152 Madison, WI 53707

Building and Fire Codes are entirely state-written with individu;

Local jurisdictions or Robin Zentner

(608) 266-1930

Amendments

Summary of Amendments

Preemptivë Application

- - Fire Code is primarily administrative with reference to Building Code for requirements for fire alarmídetection systems. Codes do not apply to one- and two-family dwellings. See the following pages for a summary of state fire protection requirements.

Promulgation

Building Code

State Building Code and Heating, Ventilating and Air Conditioning and Uniform Multifamily Dwellings Code State-written

Mandatory statewide for public buildings, places of employment, and high-rise multifamily buildings. Randy Baldwin Director, Bureau of Integrated Services Department of Commerce Safety and Buildings Division 201 East Washington Avenue P. O. Box 2658 Madison, WI 53707

Fire Prevention Code

State Fire Prevention Code

State-written

Mandatory statewide. Local jurisdictions may amend to make more stringent.

Robin Zentner Section Chief, Integrated Services Department of Commerce Safety and Buildings Division 1201 East Washington Avenue

l'M,di" 2853707

Life Safety Code

None

use groups and requirements.

I

Code Change Cycle: Wisconsin's state-written codes are updated on an ongoing basis through various citizen advisory project committees and the Wisconsin Building Code Advisory Review Board.

Project committees develop suggested changes through committee work, project committee proposals, and miscellaneous staff proposals presented to the review board for public hearing endorsement. After endorsement, public hearings are held in various locations around the state and a written comment period is established. The project committees and Review Board then consider a summary of information from the public hearings. A draft is amended and endorsed for adoption. The final draft is forwarded to the legislative body for committee (Senate and Assembly) review and approval. After approval, the rules are adopted by the Department Secretary, then printed

4-288 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 451: NEMA GUIDE CODE Fire Alarm & Detection System

and distributed. History: In 19 1 1, the Department of Industry, Labor and Human Relations was granted the authority to administer the Wisconsin "safe place" statutes. The first code was enacted in 1914 to protect the health, safety, and welfare of the public and employees in all public buildings and places of employment. The Safety and Building Division is assigned the responsibility for implementing these laws.

Plans and specifications for all new buildings and places of employment, except some agriculture buildings and one- and two-family dwellings, must be submitted for review and approval. Alteration, remodeling, or changing the use of an existing building also requires review and approval prior to construction. The plans are examined for compliance with the Building and Heating, Ventilating and Air Conditioning Code Chapters ILHR 50-64.

The code for public buildings and places of employment sets minimum standards for design, construction, structural strength, quality of material, adequate number of exits, sanitary facilities, heating and ventilating, energy conservation, access for the physically disabled, and fire safety.

4-289 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 452: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WISCONSIN Use Group Classifications

FACTORIES. OFFICE. AND MERCANTILE BUILDINGS

All factories and workshops (including where manual labor employed), office buildings, telegraph and telephone offices, mercantile establishments where commodities bought or sold, warehouses, railroad stations, exhibition buildings, and places for recreation, entertainment, worship, or dining purposes for up to 1 O0 persons.

ï"EATF,R!3 AND ASSEMBLY HALM

Buildings, or parts of buildings, other than theaters, which accommodate over 100 persons for entertainment, recreation, worship, or dining purposes. Consider theaters as buildings or parts of buildings containing an assembly hall with a stage, which may be equipped with curtains or permanent or movable scenery or which is otherwise adaptable for plays, operas, motion pictures, or similar forms of entertainment.

SCHOOLS AND OTHER INSTRUCTION PLACES

Public and private schools, universities, colleges, academies, seminaries, libraries, museums, art galleries, and buildings or building parts used primarily for instruction purposes, except rural school buildings.

RESIDENTIAL OCCUPANCTES

Places of abode, including, but not limited to, apartment buildings; garden apartments; row houses, town houses, condominiums; hotels; motels; rooming houses, dormitories; convents; monasteries; homes for the aged; sheltered facilities for battered women serving more than 20 occupants; community based residential facilities serving at least nine unrelated adults; and community based residential facilities in existing buildings and serving more than 20 unrelated adults.

4-290 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 453: NEMA GUIDE CODE Fire Alarm & Detection System

m T H CARE AND DETENTION FAcIIlTIEs

Health care or hospitals are buildings, structures, institutions, or places used for the maintenance and operation of facilities for the diagnosis, treatment of, and medical and surgical care for three or more unrelated individuals. Detention and correctional facilities are buildings used for purposes such as jails, detention centers, correctional institutions, reformatories, houses of correction, pre -release centers, and other recreational care facilities where occupants are forcibly confined.

HAZARDOUS 0ccUPANcm

Private Garage - A structure or part thereof attached to one- or two-family dwelling or unattached but serving dwelling, housing at least one occupant owned motor vehicle and used only for personal or family service, not serving as place of employment.

Repair Garage - Structure or part thereof where at least one motor vehicle is primarily repaired or serviced.

Storage Garage - Structure or part thereof; where at least one motor vehicle is parked or stored and not a repair garage, private garage, or open parking structure.

CHILD DAY-CARE. FACZLTIIES

Public and private day-care centers accommodating at least nine children; except public schools or short time programs.

CO- BASED RESIDENTiALFACILATES

Facilities providing care, treatment, and services to nine through twenty unrelated adults in existing buildings.

MULTIFAMILY DWELLINGS

Buildings containing three or more attached dwelling units.

4-291 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 454: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WISCONSIN Building Code

Fire Alarm/Detection Systems

Automatic Fire Sprinkler Systems

Storage > 20,000 sq. ft.

> 15,000 sq. ft. or > 30,000 sq. fi. total > 3 stories

> 5,000 sq. fi. or > I00 persons

> 12,000 sq. ft. or > 1,000 persons

> 15,000 sq. ft./floor

Basements

Required

Required

Required

High hazard > 3,000 sq. ft.

Fire Alarm Systems

> 10 persons above 2nd floor

> 4 stories or > 15,000 sq. fi./floor Required

> 20 occupants

Required

Required

Storage and repair garages > 1 O persons

Automatic Detection Systems

Required

Required

Required

4-292 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 455: NEMA GUIDE CODE Fire Alarm & Detection System

I Il p d Day Care I >2Ochilàren I Required

Communi@ Based Residential Facilities Highrise

Atriums

Required > 10 stories or > 60 ft.

Required Required

> 10 stories or > IOOA-. > 1ooft.

STATE OF WISCONSIN Building Code

Requirements and Exceptions

FACTORIES. OFFICES, MERCANTILE. AND ASSEMBLY BUILDINGS

Section 52.013 Provide automatic sprinkler systems in the following: G Mercantile occupancies more than 15,000 square feet per floor or more than 30,000 square feet total floor area on all floors or more than three stories except when provided with automatic smoke detection system monitored by fire alarm system and area less than 20,000 square feet per floor.

exhibition and display purposes.

G Restaurants where floor area exceeds 12,000 square feet or capacity is over 1,ooO persons. ta Buildings used primarily as dance halls or entertaining occupants who are drinking or dining and un-separated accessory uses total area is over 5,000 square feet or capacity is over 300 persons. t% Storage occupancies more than 20,000 square feet and used for high-piled storage of moderate hazard contents.

Exhibition rooms with more than 12,000 square feet of floor area used for

Libraries and museums more than 15,000 square feet per floor.

Section 54.17

SCHOOLS

Section 56.03

Section 56.19

Provide manual fire alarm system in factories and workshops where more than ten persons employed above second story or office buildings four or more stories or has 15,000 square feet or more on any floor level above or below exit discharge level. Exception: May omit when automatic sprinkler systems provided.

Protect basement levels of school with automatic sprinkler system or approved smoke detection and electrically interconnect to fire alarm system. In existing buildings, protect basement corridors with an approved smoke detection system.

Provide fire alarm system in schools and other instructional places, including re- locatable classroom structures containing more than two classrooms.

4-293 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 456: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTUL

Section 57.016

Section 57.16

Section 57.17

"CARE

Section 52.21

Section 58.25

Section 58.29

Section 58.27(2)

Section 58.27(3)

Protect with automatic fire sprinkler systems throughout buildings over 60 feet in height or housing for elderly.

Provide smoke detectors in every open stair, at doors on each floor level leading to enclosed stairs, in basements, and either in sleeping areas or within 6 feet of doorway leading to each sleeping area except in community based residential facilities. Detectors are to be electrically interconnected to required manual fire alarm system.

For community-based residential facilities, provide smoke detectors in each common use room, in corridors and stairways, and in sleeping rooms where smoking is allowed.

Provide fire alarm system in residential occupancies accommodating 20 or more persons except residential occupancies including hotels and motels maximum one story where each living unit has primary exit door at grade level.

Provide manual fire alarm system, automatic smoke detection or sprinkler system to activate the automatic self-closing device on doors in smoke barriers or protecting occupancy separations, or horizontal exits in health facility.

Provide automatic sprinkler protection to all rubbish or laundry chutes, including pneumatic rubbish and laundry systems, in health facility.

Provide automatic sprinkler systems in hospitals and nursing homes and electrically interconnect to fire alarm system.

Provide manual fire alarm system in all health-care facilities.

Provide automatic smoke detection per NFPA 72 in all corridors of nursing homes and electrically interconnect to fire alarm system. Exception: Corridor smoke detection system not required on patient sleeping room floors where each patient sleeping room is protected by approved smoke detection system.

4-294 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 457: NEMA GUIDE CODE Fire Alarm & Detection System

DETENTION AND CORRECTIONAL

Section 52.013 Provide automatic fire sprinkler system in all detention and correctional facilities with resident population of six or more.

Section 58.60 Provide manual fire alarm system, automatic smoke detection, fire detection system, or automatic sprinkler system to activate the automatic self-closing device on doors in smoke barriers or protecting occupancy separations, or horizontal exits in detention and correctional facilities.

Section 58.64

Section 58.65

Provide manual fire alarm system in all detention and correctional facilities.

Provide approved automatic smoke detection in sleeping rooms, holding rooms, and all corridors in connection with sleeping rooms per NFPA 72.

HAZARDOUS AND GARAGES

Section 52.013 Provide automatic fire sprinkler system in all high hazard occupancies more than 3,000 square feet in floor area. Also provide in buildings used for high- piled storage of moderate hazard contents having an area exceeding 20,000 square feet.

Section 59.24

CHILD DAY CARE

Section 60.35

Section 60.36

Provide fire alarm system in every storage and repair garage where more than ten persons are employed above the second story except where protected with complete automatic sprinkler system.

Provide automatic fire sprinkler system throughout child-care facility.

Provide stand-alone, battery -operated smoke detectors in corridors and stairways of all floors occupied by a day-care center accommodating nine to twenty children. Als o install in lounges, recreation areas, and sleeping rooms. Provide fire alarm system and approved smoke detection system in buildings accommodating more than 20 children and where children under the age of 24 months are cared for on floors above or below a floor level of exit discharge.

4-295 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 458: NEMA GUIDE CODE Fire Alarm & Detection System

COMMUNITY BASED RESIDENTIAL FA-

Section 61.14 Provide at least a low voltage interconnected smoke detection system designed to protect entire facility.

HIGHRISE BUILDINGS

Section 52.01(1) Provide complete automatic fire sprinkler system in every building more than 60 feet in height except open parking structures.

Section 52.01(2) Provide fire alamddetection systems in buildings more than ten stories or over 100 feet in height and provide supervised alarm and communication systems. Provide automatic detectors in every air-handling equipment room (unless sprinkled), and in the return air portion of every HVAC system. Approved heat detectors may be substituted in boiler and furnace rooms in lieu of product of combustion detectors. Install detectors to actuate an alarm or signaling system and shut down ventilation system unless automatic smoke control is incorporated in the system.

LOW-RISE BUILDINGS

Section 52.011

ATRIUMS

Section 52.07

Provide automatic fire sprinkler system in buildings fewer than 60 feet in height used as public buildings or places of employment.

Only buildings fully protected by an automatic fire sprinkler system may have atriums. Provide automatic fire sprinkler system within the atrium or areas open to the atrium or two or more smoke detectors or interconnected smoke detection system that will automatically operate the atrium's smoke control system.

MULTIFAMILY DWELLINGS

Section 66.33 Provide automatic fire sprinkler per Table 66.33, Thresholds above which Sprinklers or 2-Hour Separation are Required.

Section 66.49 Provide approved smoke detectors in basements, stairways, and in or near sleeping areas. Wire directly and permanently to a proper un-switched circuit and provide a back-up power source. Interconnect to manual fire alarm system all detectors not within individual dwelling units.

Section 66.50 Provide manual fire alarm system in buildings three to six stories or containing more than ten bedrooms.

4-296 Wisconsin

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 459: NEMA GUIDE CODE Fire Alarm & Detection System

STATE OF WYOMiNG Administrative Requirements

Code

I Building Code

1997 UBC

Amendments

Preemptive Application

Promulgation

No amendments

Mandatory statewide for all buildings except 1 and 2 family dwellings. Local jurisdictions may amend to make more stringent. The Council on Fire Prevention, Electrical Safety and Energy Efficiency in Buildings Herschler Building 122 West 25th Street Cheyenne, WY 82002 (307) 777-7288

~~

Enforcement

Comments

Summary of Amendments

Local jurisdictions or Jim Noel State Fire Marshal Department of Fire Prevention and Electrical Safety Herschler Building 122 West 25th Street Cheyenne, WY 82002 (307) 777-7288

See summary of 1997 Uniform Codes in Chapter 3 for applicable requirements for fire alarm/detection systems.

Fire Prevention Code

1997 UFC

\To amendments

flandatory statewide for all wildings except 1 and 2 ?àmily dwellings. Local urisdictions may amend to nake more stringent. The Council on Fire Prevention, Electrical Safety md Energy Efficiency in Buildings Herschler Building 122 West 25th Street Cheyenne, WY 82002 :307) 777-7288 Local jurisdictions or Jim Noel State Fire Marshal Department of Fire Prevention and Electrical Safety Herschler Building 122 West 25th Street Cheyenne, WY 82002 (307) 777-7288

Life Safety Coàe

None

Code Change Cycle: The state is on a three-year cycle concurrent with publication of the new editions of the model codes. The state codes are reviewed annually. Public hearings are held for proposed rules and regulations changes.

4-297 Wyoming

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 460: NEMA GUIDE CODE Fire Alarm & Detection System

History: The Wyoming legislature adopted the Uniform Building Code and the Uniform Fire Code in 1977. The statute, however, only mandates compliance to the fire and life safety requirements of these codes. Some of the larger communities enforce all provisions of the code through local ordinance.

State statute allows for local enforcement simply at the request of local government and with no provisions or qualifications. In all other areas, enforcement is the responsibility of the Wyoming State Fire Marshal.

The State of Wyoming currently has adopted the 1997 editions of the Uniform Building Code, the Uniform Fire Code, Uniform Mechanical Code, and the 1997 edition of the National Electrical Code.

4-298 Wyoming

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 461: NEMA GUIDE CODE Fire Alarm & Detection System

CHAPTER 5 INTRODUCTION AND EXPLANATION

This chapter contains summaries of requirements and regulations from city and county codes as they affect fire alarmidetection systems. Each city or county code section provides information about the codes used, administrative and organization information; explanation of the building use group classifications where necessary; a table summarizing the areas where fire suppression, protection and detection systems are needed; and an explanation of the code requirements and exceptions as they apply to the building types.

Because the code requirements are complex and varied, the tables have been set up to indicate when there are code provisions for fire protection systems in each of the use groups. Where possible, the tables indicate the key item (i.e., as building height or number of occupants) that dictates using fire protection systems. Where no specific item exists but fire protection systems may be needed, the tables will have the word "required." This alerts the user to review the appropriate listings of code requirements and explanations following the table. The code requirements and explanations are a brief synopsis of the appropriate code text and should be used in conjunction with the actual code for exact details.

5- 1

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 462: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF ATLANTA, GEORGIA Administrative Requirements

code

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

994 SBC

Itate amendments

?orman Koplon, PE Iirector hreau of Buildings 5 Trinity Avenue SW, Suite 900 Ltlanta, GA 30335-0309 104) 330-6152

iorman Koplon, PE Xrector 3ureau of Buildings i5 Trinity Avenue SW, Suite i900 itlanta, GA 30335-0309 404) 330-6152

Fire Prevention Code

1994 SFPC

State and city amendments

Chief Kenneth Allen Fire Marshal Fire Safety Division City Hall East 675 Ponce de Leon Avenue NE, Suite 2001 Atlanta, GA 30308 (404) 853-7041 or Dwayne Garriss Assistant State Fire Marshal Engineering Inspection Office of the Commissioner of tnsurance Safety Fire Division/ State Fire Marshal 2 Martin Luther King Jr. Drive West Tower, Suite 620 Atlanta, GA 30334 (404) 656-0697 Chief Kenneth Allen Fire Marshal Fire Safety Division City Hall East 675 Ponce de Leon Avenue NE, Suite 2001 Atlanta, GA 30308 (404) 853-7041

Life Safety Code

1997NFF'A 101

State amendments

Dwayne Garriss Assistant State Fire Marshal Engineering Inspection Office of the Commissioner of Insurance Safety Fire Division/ State Fire Marshal 2 Martin Luther King Jr. Drive West Tower, Suite 620 Atlanta, GA 30334 (404) 656-0697

Chief Kenneth Allen Fire Marshal Fire Safety Division City Hall East 675 Ponce de Leon Avenue NE, Suite 2001 Atlanta, GA 30308 (404) 853-7041

See Chapter 3 for summary of model code requirements and Chapter 4 for information on 3eorgia State Amendments to Standard Codes and NFPA 101. City has adopted ordinances to ,equire automatic sprinkler protection in existing multistory commercial and office buildings md multifamily buildings including hotels six or more stories or over 75 feet.

5-2 Atlanta, GA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 463: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF BALTIMORE, MARYLAND Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

1996 Ni3C

City amendments

Shawn Karimian Director Building Code Committee Department of Housing and Community Development Construction and Buildings Inspection Permits and Code Enforcement Section 417 East Fayette Street, Room 101 Baltimore, MD 21202

Ghanshyamkumar K. Pate1 Supervisor for Plans Examining Department of Housing and Community Development Construction and Buildings Inspection Permits and Code Enforcement Section 417 East Fayette Street, Room 101 Baltimore, MD 21202

(410) 396-3582

(410) 396-3462

Fire Prevention Cnde

996 NFPC

:ity supplement

rheodore G. Saunders 3ureau Coordinator :ire Prevention Bureau 114 North Calvert Street 3altimore, MD 2 1202 410) 396-5755

rheodore G. Saunders 3ureau Coordinator ;ire Prevention Bureau I14 North Calvert Street 3altimore, h4D 21202 410) 396-5755

Life Safety Code

1997NFPA 101

Uo amendments

rheodore G. Saunders 3ureau Coordinator :ire Prevention Bureau Il 4 North Calvert Street 3altimore, MD 2 1202 410) 396-5755

ïheodore G. Saunders 3ureau Coordinator ?ire Prevention Bureau $14 North Calvert Street 3altimore, MD 21202 1410) 396-5755

See Chapter 3 summary of mod The city requires battery backup power for smoke detectors installed in Groups R-I, R-2, R-3, and 1-1 occupancies. In addition, every hotel, motel, and lodging house, regardless of numb er of units, are required to have at least one smoke detector for the hearing impaired for each 50 units. City amendments to the BOCA National Fire Prevention Code state that all sleeping areas within every occupancy; classified as residential, as defined in NFPA 101, must be provided with at least one approved smoke detector.

code provisions.

5-3 Baltimore, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 464: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF BOSTON, MASSACHUSETTS Administrative Requirements

Building Code

Massachusetts State Building Code Based on 1993 NBC with state amendments

Code

Fire Prevention Code

Boston Fire Prevention Code

City-written Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Thomas L. Rogers Administrator Massachusetts Board of Building Regulations and Standards One Ashburton Place, Room 1301 Boston, MA 021 O8 (617) 727-3200

Joseph Fleming Fire Marshal Boston Fire Department Fire Prevention Division 1 15 Southampton Street Boston, MA 02 1 18 (617) 343-3620

Gary Moccia Assistant Commissioner/Inspectr of Buildings City of Boston Building and Inspectional Services 1010 Massachusetts Avenue Boston, MA 021 18

Joseph Fleming Fire Marshal Boston Fire Department Fire Prevention Division 1 15 Southampton Street Boston, MA 02 1 18 (617) 343-3620

(617) 635-5306, ~ 1 2 2 9

Life Safeîy Code

1997NFPA 101

Used as reference standard for alarm system design, operation and maintenance.

Boston Fire Code is principally an administrative document to supplement provisions in the ~- _ - Massachusetts Building Code and provides enforcement guidelines. Boston Fire Code requires fire alarm systems to be installed in industrial, bulk, processing and chemical plants, refineries and distilleries. Processing plants are also required to be equipped with an approved automatic sprinkler system or special extinguishing system. See Chapter 4 for summary of Commonwealth of Massachusetts Building Code fire protection requirements.

5-4 Boston, MA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 465: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF CHICAGO, ILLINOIS Administrative Requirements

Building Code

1999 Chicago Building Code Code

Fire Prevention Code

1999 Chicago Building Code

Amendments City-written

Harold Olin Managing Deputy Commissioner Department of Buildings 12 1 North LaSalle Street, Room 900 Chicago, IL 60602 (3 12) 744-0229

Enforcement Perri Irrner Deputy Commissioner, Permit Issuance Commissioner of Buildings Department of Buildings 121 North LaSalle Street, Room 900 Chicago, IL 60602 (312) 744-3125

Promulgation

City-written

John Javorka, PE Chief Fire Prevention Engineer Bureau of Fire Prevention 444 North Dearbom St., 2"d Floor Chicago, IL 6061 O (312) 744-1878

John Javorka, PE Chief Fire Prevention Engineer Bureau of Fire Prevention 444 North Dearborn St., 2"d Floor Chicago, IL 606 1 O (312) 744-1878

Comments City of Chicago Building Code encompasses building, fire, mec requirements.

Life Safety

Summary of Amendments

Code Jone

City codes define building use groups for city area only. See building occupancy types.

iical, plumbing, and other

5-5 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 466: NEMA GUIDE CODE Fire Alarm & Detection System

CTIY OF CHICAGO, ILLJIVOlS Building Occupancy Types

CLASS A - RESIDENTIAL UNITS

Buildings or parts thereof designed or used for one or more family units or for sleeping accommodations for other than family units except institutional occupancies. Sub-classify as follows:

O

O

A-1, single-family dwellings. Building containing one dwelling unit only, one family home only for one group home only, or intermediate care facility for maximum 15 developmentally disabled persons. A-2, multiple dwellings. Residential units designed or used for at least two family units or designed or used for sleeping accommodations, other than family units, for more than ten persons. Includes apartment buildings, group homes, clubs, convents, rooming, lodging, and board houses, hotels and motels, monasteries, housing for elderly, transitional shelters and temporary overnight shelters (regardless of capacity), fraternities, dormitories, and tourist houses.

CLASS B - INSTITUTIONAL UMTS

Buildings or parts thereof designed or used for harboring at least three persons for medical, correctional, penal, or other care, treatment, or detention, including:

G Hospitals; Nursing homes offering skilled care, intermediate or childcare, and homes for developmentally disabled and/or mentally retarded; Sheltered care facilities such as sheltered care homes, homes for aged, and residential care (halfway) homes; Residential restrained care facilities such as jails, asylums, and reformatories;

fi G ta Day-care centersíunder 2; and ta Orphanages.

CLASS C - ASSEMBLY UNITS

Buildings or parts thereof designed or used for assembly of persons for civic, political, educational, religious, social, recreational, or similar activities. Includes among others theaters, taverns, galleries, ballrooms, bowling alleys, churches, courtrooms, funeral parlors, gymnasiums, libraries, passenger stations, restaurants, schools , indoor stadiums, indoor pools, and museums. Subclassify as follows:

5-6 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 467: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS C - ASSEMBLY UNITS ícontinueà)

O

LI

C-1, large assembly units, Assembly units, other than schools, with capacity of 300 persons or more in one room or space. C-2, small assembly units. Assembly units, other than schools, with capacity of less than 300 persons in any one room or space. Exceptions: -- Classi@ restaurants, bars, taverns, and similar occupancies with maximum 100-person capacity as Class F,

Mercantile units. When other assembly occupancies with occupancy not more than 100 located in building of another occupancy, classify according to that occupancy.

--

C-3, schools. Assembly units designed or used for educational or institutional purposes. Further classify every school as follows: - Type IA schools include day-care centersl2-6 and day-care centerslunder 2 not included in Type III schools,

kindergarten schools, elementary schools, and similar occupancies. Type IB schools include middle schools, junior high schools, high schools, and similar occupancies. Type II schools include colleges, schools for adult education, and commercial and vocational schools with accommodations for more than 100 persons at any one time. Type III schools include day-care centerd2-6 of 100 children or less located on either second floor, first floor or basement, but not more than one floor; day-care centerslunder 2 of 30 children or less located on ground level; and day-care centershnder 2 and 2-6 combined in one facility of 100 children or less located on group level.

O

-- --

--

CLASS D - OPEN-AIR ASSEMBLY UNITS

Structures or enclosed areas designed or used for assembly in open air, other than drive-in theaters, including amusement parks, outdoor theaters other than drive-ins, athletic fields, reviewing and grand stands, stadiums, observation platforms, race tracks, outdoor swimming pools, band stands, and beach enclosures.

CLASS E - BUSINESS UNITS

Buildings or parts thereof designed or used for business transactions, for rendering of professional services or for other services not involving storage of stocks or goods, wares, or merchandise except such as incidental for display purposes. Includes offices, administration buildings, adult education, commercial and vocational schools accommodating less than 100 persons at any one time, banks, radio stations, civic administration, telephone exchanges, and professional services.

5-7 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 468: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS F - MERCANTILE UNITS

Buildings or parts thereof designed or used for sale of goods, wares, and merchandise and involving only incidental storage of such materials. Includes enclosed mall shopping centers, markets, sales rooms, specialty shops, shops, retail and wholesale stores, and restaurants, bars, taverns and similar occupancies with capacity not more than 100.

CLASS G - JNDUSTRIAL W S

Buildings or parts thereof used primarily for manufacturing or in which five or more persons engaged in fabricating, assembling, or processing of products or materials. Exception: Class I hazardous uses. Sub-classify as follows:

U3 G1, low hazard industrial units. Industrial units designed or used for manufacturing generally noncombustible products. Includes power plants, pumping plants, ice plants, and plants for manufacturing and processing asbestos, clay products, chalk and crayons, glass, ivory, metals, porcelain and pottery, stone, and other materials of similar hazard classification. G2, moderate hazard industrial units. Industrial units other than low hazard Class G-l. O

CLASS H - STORAGE UNITS

Buildings or parts thereof used primarily for storing goods, wares, or merchandise except those defined as Class I hazardous use units and in which less than five persons engaged in manufacturing or processing products or materials. Includes storage and cold storage buildings, hangars, freight depots, livestock shelters, warehouses, and garages. Sub- classify as follows:

O H-1, low hazard storage units. Storage units designed or used for generally noncombustible goods. Includes buildings used for storing asbestos, clay products, chalk, glass, ivory, metals, porcelain or pottery, stone, and materials of similar hazard classification. H-2, moderate hazard storage units. Storage units other than Class H-1 low hazard storage units or Class H-3 garages. 33-3, garages. Buildings or parts thereof with floor area more than 800 square feet and designed or used for sheltering, storing, or servicing motor vehicles containing flammable fuel. Exception: Parking facilities classified as Class J, miscellaneous buildings and structures.

O

O

5-8 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 469: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS I - HAZARDOUS USE UNITS

Buildings or parts thereof used for manufacturing, processing, storage, or use of materials of the following general classifications:

t3

t3

t3

Highly combustible, inflammable, or explosive products or materials likely to burn with extreme rapidity or from which poisonous fumes or explosions may result in event of fire; Highly corrosive, toxic or noxious alkalis, acids, or other liquids; Fume hazardous, explosive, poisonous, irritant, or corrosive gases; Materials involving explosive mixtures of dust or that result in division of matter into fire particles subject to spontaneous combustion; Chemicals or synthetic paints or enamels involving flame, h e , or explosive hazard; and Other hazardous uses per Chapter 60 of Building Code.

CLASS J - MISCELLmOUS BUILDINGS AND STRUCTURES

Gasoline filling stations, greenhouses, lumber yards, parking facilities, parking garages, fire and police stations, public utility structures, fences and retaining walls, signs, sheds, stables, tanks, tents, temporary buildings, and water, transmission, and radio towers.

5-9 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 470: NEMA GUIDE CODE Fire Alarm & Detection System

Cl lY OF CHICAGO, ILLINOIS Building Code

Fire AlarmlDetection Systems

Occupancy Type

Group A - Residential A-1 - Intermediate Care A-2 - Multiple Dwellings

Hotels Dormitories

Group B - Institutional

Group C - Assembly C-1 - Large Assembly C-2 - Small Assembly C-3 - Schools Group M- Mercantile

Automatic Fire Fire Alarm Automatic Sprinkler Systems Systems Detection Systems

Required Required Required

Required Required Required Required Required Required Required Required Required

Required Required Required Required Required > 2 floors

5-10 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 471: NEMA GUIDE CODE Fire Alarm & Detection System

Ci" OF CHICAGO, ILLINOIS Requirements and Exceptions

CLASS A - RESIDENTIAL

Section 3(13-64-120) Provide approved ionization chamber or photoelectric type smoke detectors in every single and multifamily dwelling unit and in all newly constructed buildings. Permanently wire all approved smoke detectors to the electrical service of each dwelling.

CLASS A-1 - INTERMEDIATE CARE FACZLFTIES FOR THE DEVELOPMENTALLY DISABLED - 15 OR LESS.

Sections 9(15-15-1520) and 3(1344- 170)

Provide automatic sprinklers per Sections 9( 1.5-16-1 70) to 9( 15-16-6 1 O), and approved smoke detection system in all rooms and corridors, except toilets and closets. Electrically interconnect with fire alarm system to a central station.

Sections 9(15-16-110) and 34(13-196-200)

Provide standard Class I fire alarm system in new and existing buildings two stories or less in height and not exceeding 8,000 square feet. In buildings over 2 stories or with floor area exceeding 8,000 square feet, equip with a Class II fire alarm system.

CLASS A-2 - MULTIFAMILY

Sections 9(15-16-110) and 34(13-196-200)

Provide approved fire alarm systems as follows:

except when maximum 25 persons sleep above second floor.

more than four stories and maximum 80 feet high.

sleep above second floor.

more and not equipped with a complete sprinkler system.

Class I system in hotels of Type II, III, or IV consimction not more than 80 feet high

Approved fire alarm systems and detection system in hotels of Type I construction

Class I system in dormitories two or more stories except where maximum 25 persons

Class I system in single room occupancies, both new and existing, two stories or

These requirements apply to both new and existing occupancies.

5-1 1 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 472: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS A-2 - MULTIFAMZLY fcont¡nued)

Section 9(15-16-140) Provide automatic fire detectors installed per NFPA 72E-1984 in hotel buildings over four stories not equipped with an approved automatic sprinkler system. Locate in electrical equipment rooms, guest room corridors, and elevator lobbies.

Provide automatic heat detectors in each single room occupancy unit, in public corridors, and at each floor level in every interior stairwell.

Section 34(13-196-100) Provide approved smoke detectors in all existing dwelling units. All approved single station smoke detectors required by this chapter shall be the ionization or photoelectric type, either battery powered or 110 volt AC. Smoke detectors will bear the label of a nationally recognized standards testing laboratory.

CLASS B - INSTITUTIONAL

Sections 9(15-16-110) and 34( 13-196-200) area.

Provide approved fire alarm system as follows: t> Class I systems in buildings two or more stones and less than 8,000 square feet floor

Class II system in buildings more than two stories or with floor area more than 8,000 square feet.

These requirements apply to both new and existing occupancies.

Section 9( 15-1 6-1 40) Provide automatic fire detectors throughout occupancy.

CLASS C - ASSEMBLY

Sections 9(15-16-110) and 34( 13-196-200)

Provide approved fire alarm system in Class C-3 schools as follows: e Class I system in Type I or Type II schools more than one story; containing a day- care center; and

Class II system in Type III schools.

These requirements apply to both new and existing occupancies.

Section 9(15-16-140) Provide automatic fire detectors throughout two-story buildings occupied as open plan schools. Interconnect to the school fire alarm system.

Equip Class I fire alarm systems serving schools/day care centers with automatic detectors. Install smoke detectors at each floor level, in front of doors or stairwells from the facility, in all lounges, recreation areas and sleeping rooms. Provide heat detectors in boiler rooms, kitchens, and combustible storage areas except where equipped with a sprinkler system.

5-12 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 473: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS C - ASSEMBLY (continued)

Section 9( 15-1 6 4 3 O ) Provide automatic sprinkler system in every part of Type 1 stage block, including locations below each fly gallery, beneath the stage ceiling or roof, and above the proscenium opening and including all workshops, storage rooms, property rooms and dressing rooms.

Sections 9( 15-1 6430) and 34( 13-196-180) aged.

Provide automatic sprinkler system in Type I and II schools, open plan schools, hospitals, infirmaries, nurseries, orphanages, sheltered-care homes, sanitoria, and homes for the

CLASS E - BUSINESS UNITS

Section 9(15-16-110)

Section 9( 15-1 6-1 40)

Section 9(15-16430)

CLASS F - MERCANTILE

Section 9(15-16430)

Provide an approved fire alarm system in every new and existing telephone exchange.

Provide fire detectors throughout every telephone exchange.

Provide automatic sprinkler system in new and existing telephone exchanges.

Provide automatic sprinkler system in basement spaces and all floors of department stores two stories or more.

CLASS H - STORAGE

Section 9(15-16430) Provide automatic sprinkler system in basement spaces over 2,500 square feet and not enclosed with two-hour fire resistance partitions and used for storage of combustible material.

Section 9(15-16440) Provide automatic standard sprinkler system in hazardous use units as defined by this code section and in highly flammable material storage.

Section 4(13-96-920) Provide automatic sprinkler system in parking facilities where vehicle storage area on four or more levels is enclosed on all sides.

Sections 9(15-16-030) and 34(13-196-180)

Provide automatic sprinkler system in garages exceeding four stories in height, in buildings of institutional use, any basement garage housing more than three vehicles, and any garage having a storage capacity of twenty or more vehicles and located in buildings . in which stories above the garage are other use classifications.

5-13 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 474: NEMA GUIDE CODE Fire Alarm & Detection System

CLASS I - HAZARDOUS

Sections 9( 15-1 6-030) and 34(13-196-180) of combustibility.

Provide automatic sprinkler system in new and existing shops and storerooms used as paint shops, waste paper baling or storage, and other storage uses having a similar degree

CLASS J - -0US

Section 4(13-96-1100) Provide a standard fire alarm system in every new public utility structure and every existing public utility structure, unless the structure is equipped with a fire detection system connected to a central station alarm service.

Section 9(15-16451)

Section 9(15-16-140)

Sections 9(15-16-030) and 34(13-196-180)

Provide fire suppression system in every public utility structure.

In every new and existing public utility structure, install smoke detectors in all rooms and spaces containing any electric power or communication transformers, switches, capacitors, control panels, cables, cable racks, or equipment racks.

Provide automatic sprinkler system in new and existing buildings used primarily as an exhibition area.

HIGHRISE BUILDINGS

Section 4(13-76410) Apply high-rise provisions to all new buildings more than 80 feet above grade.

Section 4(13-76440) Provide approved system including products of combustion detectors, sounding devices, and heat detectors in all high-rise buildings. Locate automatic products of combustion detectors in fan and electrical equipment rooms; return air ducts and plenums of HVAC system, elevator lobbies and corridor at each floor, and in all dwelling units. Provide heat detectors in storerooms, boiler rooms, and furnace rooms. See Section 4( 13-76-10) for exceptions to these requirements.

GENERAL PROVISIONS OR EXCEPTIONS:

Section 9(15-16420) Provide automatic sprinkler systems throughout every building with floor areas exceeding maximum allowable areas per Section 5( 1348-050).

5-14 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 475: NEMA GUIDE CODE Fire Alarm & Detection System

GENERAL PROVISIONS OR EXCEPTIONS (continued):

Section 9( 15-1 6-530) Connect a local alarm system to any sprinkler system having more than ten sprinklers and installed per Building Code.

Section 9(15-16-140) and Section 34(13-196-240)

In every fire alarm system, provide automatic fire detectors installed as an integral part of a fire alarm system in rooms or portions of the building as follows: t% In every attic and in all rooms where a flammable compressed gas or liquid and other than fuel oil for heating is stored or used; also in shops and storerooms where combustible materials is stored or handled.

In every building used in part as an institutional building, school, hotel, or single room occupancy.

In every storeroom, maintenance shop, fan room, mechanical equipment room, laundry, linen room, janitor closet, kitchen, storage area, and dwelling unit of a dormitory of two or more stories. The automatic detectors provided in the dwelling units of dormitories shall be rate-of-rise type heat detectors with a smoke detector also installed in each unit.

Section 4( 13-208-1 20) Provide approved smoke detectors in every temporary overnight shelter.

Section 9(15-16-150) No automatic heat detector shall be required in any room or portion of a building equipped with an approved installation of automatic sprinklers and provided with a water flow alarm, which is connected to the fire alarm system. This shall not apply to intermediate care facilities for the developmentally disabled with 15 or fewer persons.

Section 9(15-16-1370) When automatic fire detectors are required by this code in occupancies also required to have a standard fire alarm system, activation of either the automatic fire detectors or the manual alarm-sending station shall cause a general alarm to be sounded, except smoke detectors in dwelling units of dormitories.

5-15 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 476: NEMA GUIDE CODE Fire Alarm & Detection System

ClTY OF C " N A T í , OHIO Administrative Requirements

Building Code

Code 1996 NBC

Fire Prevention Code

1996 NFPC

Amendments

Promulgation

State amendments and city supplement Michael Kroeger Assistant Chief Fire Prevention Bureau 430 Central Avenue Cincinnati, OH 45202 (513) 352-2361

State amendments and city supplement William V. Langevin Director Department of Buildings and Inspections City Hall, Room 3 16 801 Plum Street Cincinnati, OH 45202

Enforcement

Comments

Summary of Amendments

(513) 352-3262 William V. Langevin Michael Kroeger Director Assistant Chief Department of Buildings and Inspections 430 Central Avenue City Hall, Room 3 16

Cincinnati, OH 45202 (513) 352-3262 The city issues supplemental requirements to the Ohio Basic BL

Fire Prevention Bureau

Cincinnati, OH 45202 801 Plum Street (513) 352-2361

Life Safe@ Code

1981 "A 101

Michael Kroeger Assistant Chief Fire Prevention Bureau 430 Central Avenue Cincinnati, OH 45202 (513) 352-2361

Michael Kroeger Assistant Chief Fire Prevention Bureau 430 Central Avenue Cincinnati, OH 45202 (513) 352-2361

ding Code and Ohio Fire Prevention Code. The city amendments are primarily administrative. Most changes to fire protection requirements are from state codes. The City Fire Prevention Code does establish remarks for fire protective signaling systems in any business, mercantile or residential use high-rise building (as defined in Building Code), early fire warning systems in all hotel, motel, and residential occupancies.

I See Chapter 4 for State of Ohio Building Code summary.

5-16 Chicago, IL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 477: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF CLEWLAND, OHIO Administrative Requirements

Code

Building Code.

1996 NBC

Amendments

Promulgation

Enforcement

Comments

Fire Prevention Code

State amendments and city supplement Robert Vilkas Deputy Commissioner Division of Building and Housing 60 1 Lakeside Avenue Cleveland, OH 44 i i 4

Mike Iliano Bureau Manager or Tom Ardito Chief Building Inspector Division of Building and Housing 60 1 Lakeside Avenue Cleveland, OH 44144

(2 1 6) 664-2927

(216) 664-3618

1996 NFPC

Summary of Amendments

State amendments and city Supplement Capt. Mark Scott Fire Marshal Fire Prevention Bureau 1645 Superior Avenue Cleveland, OH 441 14-2984 [2 16) 664-6664

Capt. Mark Scott Fire Marshal or Lt. Douglas Veselsky Chief Inspector/Plans Examiner Fire Prevention Bureau 1645 Superior Avenue Cleveland, OH 441 14-2984 (2 16) 664-6664

City supplements are mostly administrative in nature. See Chapter 4 for summary of State of Ohio Basic Building and Fire Codes.

Life Safety Code

None

5-17 Cleveland, OH

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 478: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF DAJALAS, TEXAS Administrative Requirements

Code 1991 UBC Code

Code 1991 UFC

Amendments lity amendments

Buck Morse Chief Building Code 4dministrator Planning & Development Department Building Inspection Division 320 East Jefferson Blvd., Room 105 Dallas, TX 75203 ‘214) 948-4474

Promulgation

City amendments

Joe Pierce Deputy Chief Dallas Fire Department Fire Prevention Education and Inspections Division 2014 Main Street, Rooms 401 & 406 Dallas, TX 75201 (2 14) 670-4628

Enforcement

Building I Fire Prevention

Ed Levine Acting Building Official Planning & Development Department Building Inspection Division 320 East Jefferson Blvd., Room 105 Dallas, TX 75203 (214) 948-4320

I Comments

Summary of Amendments

Joe Pierce Deputy Chief Dallas Fire Department Fire Prevention Education and Inspections Division 2014 Main Street, Rooms 401 & 406 Dallas, TX 75201 (214) 670-4628

Life Safety Code

;lone

City of Dallas expands requirements for fire aladdetection systems in business occupancies and high-rise buildings.

5-18 Cleveland, OH

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 479: NEMA GUIDE CODE Fire Alarm & Detection System

C M Y OF DALLAS, TEXAS 1991 Uniform Codes (ICBO) with City Amendments

Fire Alarm/Detection Systems

Fire Alarm Systems Occupancy Type

Automatic Detection Systems

Group A - Assembly Amusement Buildings Group B - Business B-2 - Retail/Drinkuig

Required Required

Required

>50 occupants Group E - Educational

Group H - Hazardous H-1 - Flammables/

Explosives 8 2 - Moderate

Explosion Hazard H-3 - HighHazard H-4 - Repair Garages H-6 - Semiconductor

H-7 - Health Hazards Facilities

Required

Required

Required

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

> 75 ft. > 75 ft.

Required

Required

Group R - Residential R-1 - Hotel R-2- Multifamily

High-rise -New and Existing Construction

B-2 - Offices R-1 - HotelíMulti-family

> 75 ft. > 75 fi.

Required

Required

Covered Maus

Aviation Control Towers

Automatic Fire Sprinkler Systems

Required Required

Required

Required ~

Required

Required Required > 3,000 sq. ft.

Required Required

Required Required Required

~~

> 3 stories > 4 stories

> 75 ft. > 75 ft.

Required

Required Required

I I

Required Required Required

Required Required Required

> 3 stories 3 stories > 3 stories > 3 stories c

5-19 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 480: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF DALLAS, TEXAS 1991 Uniform Codes (ICBO) with City Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 3802(d) (Building Code) and Section 10.507(c) (Fire Code) (Am ended)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements more than 1,500 square feet in floor area. ta Exhibition and display rooms more than 12,000 square feet.

Enclosed usable space below or over a stairway in Groups A-2,

Multi-theater complexes.

Under roof and gridiron, tie and fly galleries, proscenium walls of stages, platforms

A-2.1, A-3, and A-4.

ta Amusement buildings, except if temporary with floor area 7,500 or less.

more than 500 square feet, dressing rooms, workshops, and storerooms.

Section 609 (Building Code)

Section 14.104(b) (Fire Code) (Amended)

Section 14.104G) (Fire Code) (Added)

Section 610 (Building Code)

GROUP B - BUSINESS

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual f i e alarm system, which activates prerecorded announcement using an approved electrically supervised voice communication or public address system. Exception: Occupancies with approved automatic fire-extinguishing system installed to activate prerecorded message, or automatic sprinkler or smoke detection system installed to activate alarm system.

Provide an approved smoke detection system in amusement buildings. An approved alternate type of automatic detector may be used if in area where ambient conditions will cause a snioke-detection system to alarm.

In amusement buildings, provide approved automatic sprinkler, smoke detection, and supervised alarm and/or public address systems.

Section 3802(e) (Building Code) and Section 10.507(d) (Fire Code)

Provide automatic fire extinguishing system in Group B-2 retail sales areas where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or when more than three stories.

5-20 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 481: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP B - BUSINESS (continued)

Section 14.104(c)(l) (Fire Code)

Provide fire alarm systems in Group B-2 occupancies as set forth in the following subsections of this code.

Section 14.104(~)(2) and Article 81 (Fire Code)

Provide automatic smoke -detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire -extinguishing system when required by Table 8 1.105-A.

Section 14.104(~)(3) (Fire Code)

Provide automatic smoke-detection system throughout building when special egress- control devices are installed on exit doors.

Section 14.104(~)(4) (Fire Code)

Provide automatic smoke-detection system in corridors which are not of one hour fire- resistive construction located in office spaces with less than 100 occupants.

Section 14.104(~)(5) (Fire Code) (Amended)

Provide a manualfire alarm system in any business occupancy where the building is two or more stories in height above the level of exit discharge, has 1 O0 or niore occupants located above OY below the level of exit discharge, or has 1,000 OY more total occupants.

Section 14.104(~)(6) (Fire Code)

Provide approved manual alarm system when required by Article 88 of this code for aerosol storage rooms and general purpose warehouses containing aerosols.

See also specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROUP E - EDUCATIONAL

Section 809 (Building Code) and Section 14.104(d) (Fire Code)

Provide approved fire alarm systems when occupant load more than 50 persons. When automatic sprinkler system or smoke detectors provided, install to automatically activate school fire alarm.

Section 802(b) (Building Code)

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

5-21 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 482: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL (continued)

Section 3802(f) (Building Code) and Section 10.507(e) (Fire Code)

Provide automatic sprinkler system in basements more than 1,500 square feet in floor area and in enclosed usable space below or over a stairway.

Section 3318(d) (Building Code)

GROUP H - HAZARDOUS

Section 909 (Building Code) Sections 14.104(e), 50.113, Article 51 and Article 80 (Fire Code)

Section 911 (Building Code)

Section 3802(g) (Building Code) and Section 10.507(f) (Fire Code)

Provide smoke detectors throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

GROUP I - MSTITUTIONAL

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Section 1002(b) (Building Code)

Provide smoke detector operated damper(s) at each point where ducts penetrate smoke barrier except where openings in ducts are limited to single smoke compartment and ducts are of steel construction.

5-22 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 483: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1009 (Building Code) and Section 14.104(f) (Fire Code)

Section 1010 (Building Code) and Section 14.104(f)(5) (Fire Code)

Section 3802(h) (Building Code) and Section 10.507(g) (Fire Code)

Section 14.104(f)(3) (Fire Code)

Provide manual and automatic fire alarm system in Group I occupancies.

Provide smoke detectors in patient sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Provide automatic fire extinguishing system throughout.

Provide smoke detectors at automatic closing doors in smoke barriers and in ducts penetrating smoke barriers and in waiting areas, which are open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

GROUP R - RESIDENTIAL

Section 1210 (Building Code) and Section 14.104(g)(6 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest-rooms installed per manufacturer's instructions.

Section 1211 (Building Code) and Section 14.104(g) (Fire Code) (Amended) buildings provide a fire alarm/communication system. Exceptions:

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise

1) Buildings not more than three stories with all individual units provided one hour fire separation and direct exterior egress; 2) Buildings with automatic sprinkler system throughout and with local alarm system. Manual fire alarm boxes are not required for interior corvidors having smoke detectors.

5-23 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 484: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 14.104(g) (Fire Code)

In Group R-1 occupancies, provide: G Manual fire alarm boxes.

for ten or more occupants.

rooms, and similar areas.

designated portions of building.

Smoke detectors in all common areas and interior corridors serving as required exit

Heat detectors in common areas such as recreational rooms, laundry rooms, furnace

Install alarm-initiating devices to activate an alarm signal audible throughout

Section 3802(1) (Building Code) and Section 10.507(h) (Fire Code) (Am ended)

Provide automatic sprinkler system in apartment housesfour or more stories or containing mo re than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 50 or more.

HIGHRISE. NEW CONSTRUCTION. GROUP 8-2 OFFICES AND GROUP R-1 OCCUPANCIES

Section 14.104(g) (Fire Code)

Provide fire alarm and communication systems for Group B-2 offices and Group R-1 occupancies with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Section 14.104(1) (Fire Code) (Added)

Provide automatic fire alarm system and a communication system in mechanical equipment, electrical, transformer, telephone equipment, elevator machine or similar rooms; in main return - and exhaust-air plenum of each air-conditioning system located downstream of the last duct inlet; in each connection to a vertical duct or riser serving two or more stories from a return-air duct or plenum ofan air-conditioning system. In Group R-I, approved smoke detector is allowed to be used in each return-air riser carrying not more than 5,000 cfin and serving not more than ten air-inlet openings. Install so that the actuation of the detector will operate the emergency voice alarm- signaling system and all equipment necessary to prevent the re-circulation of smoke.

HIGHRISE BUILDINGS

Section 1807(a) (Building Code) (Added)

Section 1807(d) (Building Code) (Added)

Provide automatic sprinkler systems throughout all buildings, other than Groups B-3, B-4 and A4 occupancies, havingfloors used fo r human occupancy located more than 75 feet above the lowest level ofJre department access.

Provide at least one approved smoke detector in every mechanical equipment, electrical; transformer, telephone equipment, elevator machine or similar room and in the main return and exhaust air plenum of each air-conditioning s-vstem located in a serviceable area downstream of the last duct inlet. Install so that actuation of the detector will shut down the air-handling units or operate dampers toprevent re- circulation of smoke.

5-24 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 485: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1807(e) (Building Code) (Added)

Section 14.104(c) (Fire Code) (Added)

Provide an approved automatic fire alarni system in all Groups A, B-2, E, I, and R-1 occupancies. Provide voice communication system in al1 Groups A , B-2, E, 1-2, and R- 1 occupancies. Automatic f ire alarm and voice comniunication may be a combined s,vstem.

Provide an integrated alarm system with smoke detector or sprinkler system

HIGHRISE, GROW B-2 OFFICES AND GROUP R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix 1-B (Fire Code)

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide approved manual fire alarm system connected to central, proprietary or remote station service, or a local system, which will provide an audible signal at a constantly attended location. Provide fire department communication system and occupant voice notification system. Provide single-station smoke detectors in dwelling units and guest rooms.

COVERED MALLS

Section 5603 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system.

ATRIA

Section 1716(b) (Building Code)

Provide smoke control system that operates automatically upon actuation of automatic sprinkler system within atrium and areas open to atrium. Provide smoke detectors that will automatically operate atrium smoke -control system.

Section 3802(b) (Building Code) (Added)

Provide automatic sprinkler system in all occupancies exceeding maximum allowable un-sprinkled building areas specified in Table 38-B of the City Code. Excepted are open airportions of Group A-4, open parking garages, noncombustible occupancies in Type I or II construction, Group R-1 closets less than 40 square feet and bathrooms less than 100 square feet.

Section 3802(c) (Building Code) and Section 10.507(f) (Fire Code)

Except in Group R-3 and M occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 3802 of 1991 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults.

5-25 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 486: NEMA GUIDE CODE Fire Alarm & Detection System

Section 4306(f) (Building Code)

Section 14.103(1) (Fire Code) (Added)

Provide smoke detectors to activate closing device of an automatic closing fire assembly.

Unless spec$cally indicated, a separate fire alarm s,vsteni need not be provided in buildings, which are protected throughout by an approved, supervised, automatic j ì re- extinguishing systent having a local alarm to not$ all occupants.

5-26 Dallas, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 487: NEMA GUIDE CODE Fire Alarm & Detection System

CITY AND COUNTY OF DENVEX, COLORADO Administrative Requirements

Cade I Building I Fire Prevention

Code

Amendments Fire Codes and Standards

City amendments City amendments and

Promulgation

Enforcement

Comments

supplements Joseph L. Gonzales Division Chief City and County of Denver Department of Fire Fire Prevention Bureau 745 West Colfax Avenue Denver, CO 80204 (303) 640-5522

Joseph L. Gonzales Division Chief or Masoud Sabounchi Chief Fire Protection Engineer City and County of Denver Department of Fire Fire Prevention Bureau 745 West Colfax Avenue Denver, CO 80204 (303) 640-5522

CurtMcMillin *

Acting Coordinator, Building Code Revision Committee Public Works Dept. Building Inspection Division 200 West 14th Avenue, Suite 101 Denver, CO 80204-2700

Pete Bemelen Acting Director, Building Inspection Division Public Works Dept. Building Inspection Division 200 West 14th Avenue, Suite 101 Denver, CO 80204-2700

(303) 640-5843

(303) 640-5843

Life Safety Cade

1994NFPA 101

Summary of Amendments

No amendments

CityiCounty adds to the fire protection regulations in the Uniform Code, which includes provisions for airport buildings. Where there is conflict between the Building Code and the Fire Code provisions, the Building Code prevails. The cityicounty amendments to the Building Code are extensive and contain detailed installation requirements for fire suppression systems. A summary follows, but refer to text of Building Code for exact information.

Joseph L. Gonzales Division Chief City and County of Denver Department of Fire Fire Prevention Bureau 745 West Colfax Avenue Denver, CO 80204 (303) 640-5522

JosephL. Gonzales Division Chief or Masoud Sabounchi Chief Fire Protection Engineer City and County of Denver Department of Fire Fire Prevention Bureau 745 West Colfax Avenue Denver, CO 80204 (303) 640-5522

5-27 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 488: NEMA GUIDE CODE Fire Alarm & Detection System

CITY AND COUNTY OF DENVER, COLORADO 1997 ICBO Use Group Classifications with Ciîy/County Amendments

GROUP A - ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1

A-2

A-2.1

A-3

A 4

An assembly building with a stage and an occupant load of 1,000 or more.

Building or portion there-of having an assembly room with occupant load less than 1,000 and a stage.

Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

Building or portion there-of with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

Stadiums, reviewing stands, and amusement park structures not included in other Group A occupancies.

GROUP B - BUSINESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUP E - EDUCATIONAL

Sub-classify in divisions as follows:

El Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

E 2 Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

E3 Buildings used for adult OY child care purposes.fovperiods of less than 24 hours a day.

5-28 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 489: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP F - FACTORY AND INDUSTRIAL

A building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repairing or processing operations. Sub-classify in divisions as follows:

F-1 Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

F-2 Low-hazard factory and industrial occupancies including facilities producing noncombustible or non- explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROUP H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1 Buildings with quantity of material in excess of building code limitations, which present high explosion hazard, including but not limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days. Manufacturing of Class 1.4G fireworks.

Class 4 oxidizers. Class 4 or Class 3 detonatable unstable (reactive) materials.

Unclassified detonatable organic peroxides.

H-2 Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to:

Class I organic peroxides. Class 3 non-detonatable unstable (reactive) materials. Pyrophoric gases. Flammable or oxidizing gases. Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in closed containers pressurized at more than 1 Spsi gauge. Exception: aerosols. Class 3 oxidizers. Ciass 3 water-reactive materiais.

5-29 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 490: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

H-3 Buildings with quantity of materials in excess of building code limitations, which present high fire or physical hazard, including but not limited to: ta Class II, III, or IV organic peroxides. ta Class 1 or 2 oxidizers. ta Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed

ta Class III-B combustible liquids. ta Pyrophoric liquids or solids.

Class 1 or 2 water-reactive materials. Flammable solids in storage.

Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

containers or systems and containers pressurized at 15psi gauge or less, and aerosols.

ta Flammable or oxidizing cryogenic fluids (other than inert).

H-4 Repair garages not classified as Group S-3.

H-5 Aircraft repair hangars and heliports not classified as Group S-5.

H-ó Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

H-7 Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to: ta Corrosives, except stationary lead-acid battery systems. ta highly toxic materials. ta Irritants.

0 other health hazards. Sensitizers.

GROUP I - INSTlTUTIONAL

Sub-classify in divisions as follows:

1-1.1 Nurseries for full-time care of children under the age of six, hospitals, sanitariums, nursing homes with non-ambulatory patients, and similar buildings, each accommodating more than five persons, except búildings used only for private residential purposes for family group.

5-30 Denver. CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 491: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSlTI’UTIONAL (continued)

1-1.2 Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

1-2 Nursing homes for ambulatory patients, homes for children six years old or over, each accommodating more than five persons, except buildings used only for private residential purposes for family group.

1-3 Mental hospitals, mental sanitariums, jails, prisons, reformatories, and buildings where personal liberties of inmates are similarly restrained, except buildings used only for private residential purposes for family group.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

Sub-classify in divisions as follows:

R-1 Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

R-2 Three or more attached single dwelling units not more than three stories in height, with each unit having an independent means of egress to the exterior of the building, and separated from each other b,v a two- hour fire-rated wall assembly.

R-3 Dwellings, lodging houses, and congregate residences, each accommodating ten persons or less.

GROUP S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

S-1 Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

5-31 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 492: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE (continued)

S-2 I

Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

S-3 Repair garages and parking garages not classified as S-4.

S-4 Open parking garages.

S-5 Aircraft hangars and helistops.

GROUP U - UTILITY

Sub-classify in divisions as follows:

U1 Private garages, carports, sheds and agricultural buildings.

U 2 Fences overfõur feet high, tanks, towers, and other miscellaneous structures.

5-32 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 493: NEMA GUIDE CODE Fire Alarm & Detection System

CITY AND COUNTY OF DENVER, COLORADO 1997 Uniform Codes (ICBO) with City/County Amendments

Fire AlardDetection Systems

Automatic Fire Sprinkler Systems

Fire Alarm Systems

Automatic Detection Systems Occupancy Type

Group A - Assembly Amusement Buildings Group B - Business

Group E - Educational

Group F- Factory Industrial

Required Required Required

Required Required Required

Required Required

Required Required > 50 occupants

Required

Group H - Hazardous

Explosives H-1 - Flammables/

H-2 - Moderate

IT-3 - HighHazard H-4 - Repair Garages H-ó - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Required

Required Required > 3,000 sq. ft.

Required Required

Required

Required Required

Group I- Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

~

Required Required Required

Required Required Required

Required Required Required

Group M - Mercantile > 3 stories > 12,000 sq. ft./floor > 24,000 sq. fi. total

Group R - Residential ~

R-1 - HoteVMultifamily > 3 stories > 3 stories > 3 stories

Group S - Storage

High-rise -New and Existing Construction

B-2 - Offices R-1 - HoteUMulti-family

Required

> 75 ft. > 75 ft.

> 75 fi./> 5 stories > 75 ft.

> 75 ft. > 75 ft.

Covered Malls Required Required Required

Airport Buildings Required Required Required

5-33 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 494: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code)

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

CITY AND COUNTY OF DENVER, COLORADO 1997 Uniform Codes (iCBO) with CiîyKounty Amendments

Requirements and Exceptions

Provide automatic sprinkler systems in Group A as follows:

when used for consumption of alcoholic beverages. Rooms and un-separated accessory uses more than 5,000 square feet in total area

Basements more than 1,500 square feet in floor area. Exhibition and display rooms more than 12,000 square feet Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A 4 Multi-theater complexes. Amusement buildings, except if temporary with floor area less than 1,000 square

All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, feet and exit travel distance is less than 50 feet from any point.

workshops, storerooms, and'other accessory spaces adjoining such stages.

square feet, or in conjunction with outdoor seating. Smoke-protected assembly seating, except press boxes, storage less than 1,000

Provide approved fue alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is 1,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

GROW E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

Section 305.9 (Building Code) and Section 1007.2.4 alarm. (Fire Code)

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate fire

5-34 Denver. CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 495: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code)

Section 907.3.1.2 & 3 (Building Code) (Added)

Section 1007.3.4 (Building Code) and Section 1007.2.4.2 (Fire Code)

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two- hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet.

Providefire detection system in Group E-1 and in Groups E-2 and E-3 occupancies with more than 20 occupants. Not required to be connected to an approved central station ifoccupant load is less than 50.

In Groups E-2 and E-3 with 20 or less occupants, residential g p e single-station smoke detectors, having battery backup and wired to a 120-volt AC un-switched electric power source and interconnected for simultaneous alarm may be provided. The detectors are to be installed in routes of egress or as required by the Fire Department.

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2 ) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Section 307.11 (Building Codey

Provide automatic fire-sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

5-35 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 496: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

GROUP I - INSTITUTIONAL

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Provide approved manual and automatic fire alarm system in all Group I Occupancies. Install audible alarm devices in non-patient areas. Visibie alarm devices may be substituted for audible devices in patient-occupied areas.

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Provide smoke detectors within patient sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

Section 907.3.1.4 & .5 (Building Code) (Added)

Providejre detection system in Group I occupancies with ten or more occupants. In Groups I-] and I-2 with ten or less occupants, residential type single-station smoke detectors, having battery backup and wired to a 120-volt AC un-switched electric power source and interconnected f o r simultaneous alarm may be provided. The detectors aye to be installed in routes of egress or as required by the Fire Department.

5-36 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 497: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1007.2.7.1.1 (Fire Code)

In Groups 1-1 . l , 1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

Section 1007.2.7.2.4 (Fire Code) housing areas.

In Group 1-3, provide approved automatic smoke-detection system throughout resident

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and 1-2.

Appendix Chapter 3, Division 1 (Building Code) alarm system.

Alternative provisions for Group 1-3 housing with more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and Section 1003.2.8 than three stories. (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more

Section 907.2.1.5 (Building Code) (Added)

Provide fire alarni system in Group M occupancies offive stories or more above grade.

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code)

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer's instructions and receiving primary power from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings provide a fire alarm/communication system. Exceptions: I) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Building with approved supervised fire sprinkler system throughout and with local alarm system.

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick-response standard sprinklers in dwelling units and guest rooms.

5-37 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 498: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R OCCUPANCIES (continued1

Section 1007.2.9.1.3 & .4 (Fire Code)

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCWANClES

Section 403.2 (Building Code) (Amended)

Section 403.3 (Building Code) (Amended) and Section 1007.2.12.2.2 (Fire Code)

Section 403.5 (Building Code) (Amended) and Section 1007.2.12.2 (Fire Code)

Sections 402.2 and 910.2.2 (Building Code) (Added) and Section 1007.2.12.3 (Fire Code)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in Groups A, B, E, I, M, and R-1 with floors used for human occupancy located more than 75 feet above lowest level of fire department access and of Type I or II-F.R. construction.

In Group R-1 occupancies, provide smoke detectors connected to automtic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies, interior corridors serving as exit for occupant load often or more occupants, and at openings extending vertically through floors which are not required to be enclosed. Also provide in other than R-I, not less than one foot and not more than 3 feet from the door on the occupied side of each door entering an area of evacuation assistance and an elevator lobby, and an exit stairway, which is not directly exiting from an area of evacuation assistance.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. The operation ofany automatic fire detector, manual fire alarm box, or sprinkler shall automatically sound an alert tone followed by voice instructions giving appropriate information and direction.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building. In other than high-rise buildings, activation of a smoke detector or sprinkler f low alarm in the atrium zone shall operate the atrium supp1,v and exhaust systems.

OTHER SPECIAL USES AND ARTICLES

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Provide automatic fire detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 8 1 -A.

Provide automatic smokedetection system throughout building when special egress- control devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

5-38 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 499: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1007.2.12.8 (Fire Code)

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smoke-control system.

Section 1007.2.12.9 (Fire Code)

Provide manual fire alarm system in lumber, plywood, and veneer mills.

5-39 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 500: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION. GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES (continued)

Section 907.2.1.2 (Building Code) (Added)

Providefire alarm system in Group B occupancies offive stories or more above grade.

HIGHRISE. EXISTING STRUCTURES

Appendx Chapter 34 Division II Section 3416 (Building Code) (Amended)

Appendix Chapter 34 Division II Section 3418 (Building Code) (Am ended)

Appendx Chapter 34, Division II Section 3420.2 and Section 3420.3 (Building Code) (Amended)

COVERED MAUS

Section 404.3.1 (Building Code)

Provide an approved automatic sprinkler system in basements or stories exceeding 1,500 square feet in area and not having a minimum of 20 square feet of opening as specified in Section 341 6 of Appendix Chapter 1.

Provide smoke detectors in dwelling units, all interior corridors which service more than one tenant and which provide apath of egress. Excepted are buildings that have an approved sprinkler sysrem throughouc.

Providejìre sprinkler system throughout existing Group R-1 hotel occupancies, which are over 75 feet in height. Exception: Floors with residential units where corridors are sprinkled and units protected with supervised smoke detectors.

Provide f ire sprinkler systems throughout all existing retail and office occupancies over 75 feet in height unless corridors are fully sprinkled and smoke detectors provided on tenant side of door.

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signai or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of lease-able area.

540 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 501: NEMA GUIDE CODE Fire Alarm & Detection System

AIRPORT BLJiLDINGS AND STRUCTURES

Aviation Control Towers

Section 430.5.5 (Building Code) (Amended)

Provide smoke detectors at each stair door, elevator lobby, return air duct or plenum on eachpoor.

Passenger Terminal Buildings

Section 430.8.5 (Building Code) (Added)

Provide smoke control system connected to the smoke detection and/or automatic sprinkler system of main passenger terminal building. Install to automatically operate when either system is actuated. Provide a product of combustion detector in the supply air system of the passenger terminal building systems. Also provide product of combustion detector in the return or the exhaust air stream to activate smoke control system.

Section 430.8.6 (Building Code) (Added)

Section 430.9.1 (Building Code) (Added)

Section 430.9.4 (Building Code) (Added)

Provide smoke detectors. Thermal detectors or cross zone beam detectors may be used in lieu of smoke detectors if approved by departments.

Provide automatic sprinkler system throughout terminal/concourse buildings including hotel occupancies connected to a passenger terminal building. Provide manual pull station zones at required exits.

Provide detectors in all nonpublic areas that are not sprinkled.

OTHER THAN HIGHRISE EXISTING STRuCIzTRES

Appendix Chapter 34, Division I, Section 3407 (Building Code) (Added)

Provide smoke detectors in dwelling units, hotel rooms and rooms used for sleeping purposes, interior corridors which serve more than two dwelling units, hotel or sleeping i-ooms, and that provide a path of egress.

5-41 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 502: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Appendix Chapter 34, Division 1, Section 3408 (Building Code)

Appendix Chapter 34, Division 1, Section 3409 (Building Code)

Appendix Chapter 34, Division 1, Section 3411 (Building Code)

Section 713 (Building Code)

Section 907.3.2 (Building Code) (Added)

Sections 910.3.1.1 and 910.3.1.4 (Building Code) (Added)

Section 3003.2 (Building Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exceptions: Airport control towers, open parking structures, and Group F-2 occupancies.

Protect openings into interior shafts in existing buildings, other than high-rise buildings, by self-closing one-hour fire assemblies or by automatic closing by smoke detection.

Provide approved automatic sprinkler system in basements of existing buildings, other than high-rise buildings, with more than 1,500 square feet in area and meeting other criteria as established in the 1997 UBC and 1997 UFC.

Provide smoke detector installed per approved manufacturer's instructions in dwelling units and hotel and lodging house guest rooms used for sleeping purposes in existing other than high-rise buildings. Install smoke detectors to receive primary power source from building wiring if from commercial source or by battery power.

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

Provide smoke detectors within all rooms of an occupancy aspavt offire detection system. Heat detectors may be substituted where smoke detectors are not suitable because of environment. Heat detectors are not required when occupancy protected with automatic extinguishing system.

As part ofpressurization system.for interior enclosed exit stairways and elevator lobbies, each outside air intake shall be provided with a smoke detector, which upon smoke detection will be annunciated at the HVAC status panel.

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

5-42 Denver, CO

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 503: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF DETROIT, MICHIGAN Administrative Requirements

Code

Amendments

Promulgation

Building I Code 1996 NBC

City amendments

Amni Meah Acting Asst. Director Buildings and Safety Engineering Department 401 CityKounty Bldg. Detroit, Mi 48226 (3 13) 224-3258

Enforcement

Comments

Summary of Amendments

Sheilah Johnson Asst. Chief of Building

Buildings and Safety Engineering Department 401 CityKounty Bldg. Detroit, MI 48226 (313) 2243243 The Detroit Fire Prevention Co<

Inspection

Fire Prevention Code

Fire Prevention Code of the City of Detroit

Zity-written, references NFPA Vational Fire Codes and 3 t andard s lames Bush Exec. Fire Commissioner Detroit Fire Department 250 West Larned Street Detroit, MI 48226 [3 13) 596-2902

Carleton Smith Fire Marshal Detroit Fire Department 250 West Larned Street Detroit, MI 48226 (3 13) 237-2656

Life Safety Code

Fire Prevention Code of the City of Detroit references NFPA 101

James Bush Exec. Fire Commissioner Detroit Fire Department 250 West Larned Street Detroit, MI 48226 (313) 596-2902

Carleton Smith Fire Marshal Detroit Fire Department 250 West Larned Street Detroit, MI 48226 (313) 237-2656

: is primarily administrative provision to referenced NFPA National Fire Codes and Standards. City amendments to Building Code do not affect fire alarm/detection systems. See Chapter 3 for 1996 National Building Code requirements.

I

543 Detroit, MI

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 504: NEMA GUIDE CODE Fire Alarm & Detection System

DISTRICT OF COLUMBIA Administrative Requirements

Code

Building Code

1990 NBC

Amendments 1 City amendments

Promulgation Armando Lourenco Administrator Department of Consumer and Regulatory Affairs Building and Land Regulation Administration 941 N. Capitol Street, NE Suite 2000 washington, DC 20002

Enforcement Interim Deputy Administrator Department of Consumer and Regulatory Affairs Building and Land Regulation Administration 941 N. Capitol Street, NE Suite 2000 Washington, DC 20002

(202) 442-4455 Denzil Noble

Fire Prevention

Summary of Amendments

Code 1990 NFPC

Columbia except those owned by the United States Government. City makes significant changes in Chapter 2 to define various types of special residential facilities classified as Use Group R-3. Special regulations governing sprinklers and smoke detection for these facilities are included in Articles 625 and 626 of the D.C. City Code supplement.

City amendments

Sydney Lester, Chief District of Columbia Fire Prevention Division 941 N. Capitol Street, NE Suite 2000 Washington, DC 20002 (202) 442-4590

Sydney Lester, Chief District of Columbia Fire Prevention Division 941 N. Capitol Street, NE Suite 2000 Washington, DC 20002 (202) 4424590

Life Safety Code

None

I(202) 442-4455

5-44 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 505: NEMA GUIDE CODE Fire Alarm & Detection System

DISTRICT OF COLUMBLA 1990 National Codes (BOCA) with City Amendments

Fire AlarmlDetection Systems

Group I - Institutional I

A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A A - Churches

Group B - Business

Group E - Educational

Group F - Factory F-1 - Moderate Hazard II

Group H - High Hazard

Group I - Institutional

Group M - Mercantile

Group R - Residential R-1 - HotelMotels R-2 - Multifamily R-3 - Special residential

I facilities Group S - Storage

S-1 - Moderate Hazard

Covered Maus

Automatic Fire Sprinkler Systems

Required > 5,000 sq. ft. > 12,000 sq. ft.

Fire Alarm Systems

Required > 3 stories

Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required

Required Required

> 3 stories or > 12,000 sq. ft. or

24,000 sq. fi. total

Required Required Required

Required > 4 stories

> 3 stories or > 12,000 sq. ft. or

5-45 District of Columbia

Automatic Detection Systems

Required

~~

Required Required Required

Required

> 75 ft.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 506: NEMA GUIDE CODE Fire Alarm & Detection System

Public Garages

5-46 District of Columbia

Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 507: NEMA GUIDE CODE Fire Alarm & Detection System

DISTRICT OF COLUMBIA 1990 National Codes (BOCA) with Ciîy Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 1002 (Building Code)

Provide fire suppression systems in assembly buildings as follows: Group A-1 - Throughout entire story or floor level where Group A-1 located, all stories

and floors below Group A-1 and all stories and floor levels between Group A-1 and level of exit discharge. Exception: Auditoriums.

floor level where Group A-2 located, all stories and floors below Group A-1 and all stories and floor levels between Group A-2 and level of exit discharge. Exception: Auditoriums.

Group A-3 - When more than 12,000 square feet in area, provide throughout entire story or floor level where Group A-3 located, all stories and floors below Group A-1 and all stories and floor levels between Group A-3 and level of exit discharge. Exception: Auditoriums.

Group A-2 - When more than 5,000 square feet in area, provide throughout entire story or

Section 1016.4.1 (Building Code)

Section 404.5 (Fire Code)

Provide fire alarm system in new and existing Group A-4 (churches) except in sanctuary and nave areas.

Provide manual fire alarm system in all existing buildings used as churches or for educational use except sanctuary and nave areas of churches and similar religious buildings.

GROUP B - BUSINESS

Section 1016.4.2 (Building Code) discharge.

Provide fire alarm systems in Group B when two or more stories above or below level of exit

GROUP E - EDUCATIONAL

Section 1016.4.1 (Building Code)

Provide fire alarm systems in all Group E occupancies.

5-47 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 508: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1002.7 (Building Code)

Provide fire suppression system in Group F-1 buildings more than 12,000 square feet in area; or more than 24,000 square feet total area on all floors; or more than three stories high. Exception: Public garages.

GROUP H - HAZARDOUS

Section 1002.5 (Building Code)

Provide fire suppression systems in all Group H buildings or portions thereof.

GROUP I - J ” 0 N A L

Section 610.5 (Building Code)

Provide automatic fire alarm system in patient sleeping rooms, corridors, and common spaces open to corridors in Group 1-2 occupancies. Provide automatic smoke detection system interconnected to fire alarm system in corridors of Group 1-2 not equipped with automatic fire suppression systems. Provide smoke detector in patient sleeping rooms except when rooms equipped with automatic door closing devices with integral smoke detectors on room sides. Provide heat detectors in un-sprinkled areas per Section 610.2 of Building Code.

Section 1002.6 (Building Code)

Provide fire suppression system in all Group I buildings or portions except:

stories; 9 Group 1-2 hospitals of Type 2A construction not more than 45 feet and not more than three stories;

Group 1-2 nursing homes of Types 1,2A, or 2B construction not more than one story; Group 1-2 hospitals of Type 2B construction not more than one story; Group 1-2 child care facilities not more than one story with maximum 100 children and

Group 1-2 hospitals of Type 1 construction not more than 75 feet and not more than five

with each room having direct exit outside; Group 1-1 not more than two stories and having maximum 20 occupants;

Section 1016.4.3 (Building Code)

Provide fire alarm systems in all Group I Buildings.

5-48 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 509: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 1017.4 (Building Code)

Provide automatic fire detection systems in all Group 1-1, automatic fire detector system per 610.5 in Group 1-2, and automatic smoke detectors in 1-3 throughout all resident sleeping areas except sleeping rooms with not more than four occupants in Use Condition II or III or when protected with approved automatic fire suppression systems.

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to h u p 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

Section 1017.5 (Building Code)

Section 1018.3.4 (Building Code)

Provide at least one single station smoke detector in each guest room, suite, or sleeping area in Group I- 1.

GROUP M - MERCANTILE

Section 1002.7 (Building Code)

Provide fire suppression system in Group M buildings more than 12,000 square feet in area; more than 24,000 square feet in total area on all floors; or more than three stories. Exception: Public garages.

GROUP R - RESIDENTIAL

Section 1002 (Building Code) (Am ended)

Provide fire suppression systems throughout Group R-1 except guest rooms which have their own exit directly to outside at grade and throughout R-2 except in bathrooms not more than 55 square feet in area and R3Jire areas.

Section 1016.4.4 (Building Code)

Provide fire alarm systems in all Group R-l.

Section 1016.4.5 (Building Code)

Provide fire alarm systems in Group R-2 where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

5-49 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 510: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTIAL (continued)

Section 1017.4.4 (Building Code)

I

Provide automatic fire detection systems in Group R-1 except units without interior corridors and direct exterior exit access from each sleeping room.

Section 1018.3 (Building Code)

Provide at least one single station smoke detector in all sleeping areas, areas of egress and on each story within each guest room or suite, in Group R-1, in dwelling units in immediate vicinity of bedrooms, on every story including basements in Group R-2 and R-3, and in all bedrooms in Group R-2.

Section 625 (Building Code) (Added)

Section 626 (Building Code) (Amended)

Provide approved supervised automatic sprinkler system throughout all.facilities used.for group homes for the mentally retarded. Provide smoke detectors on all levels, including the basement, living rooms and day rooms. Install a switch to manually activate a smoke detector system on each level adjacent to the exit door. Provide an approved manual fire alarm pull station aspart of the smoke detection system. Other requirements for Group R-3 occupirilcies will üpp1,v.

Provide an approved sprinkler system throughout all communiîy based residential.faci1itie.s more than two stories above grade. Also install smoke detector system. Other requirements for Group R-3 occupancies will apply.

GROUP S - STORAGE

Section 1002.7 (Building Code)

Provide fire suppression system in Group S-1 when more than 12,000 square feet in area; more than 24,000 square feet in total area on all floors; or more than three stories.

PUBLIC GARAGES

Section 609.2.1 (Building Code)

Provide fire suppression system as follows: e Group 1 public garages more than 10,000 square feet in area, more than 7,500 square feet and more than one story, more than 5,000 square feet and more than two stories, more than three stories, when located in buildings with other uses on upper stories, in any story more than 50 percent below grade, and in fuel dispensing areas. ta Group 2 public garages when more than 10,000 square feet and more than one story, more than two stories, and when located in buildings with other uses on upper stories. Exception: Open parking structures. 3 Bus garages per above or when used as passenger terminals or for storage and loading of four or more buses.

5-50 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 511: NEMA GUIDE CODE Fire Alarm & Detection System

COVERED MALLS

Section 601.9 (Building Code)

Provide automatic fire suppression throughout covered mall building and all connected buildings. Electrically supervise all sprinkler control valves.

Section 1019.3 (Building Code) 1987.

Provide smoke control system in covered malls activated by smoke detectors per NFPA 72E-

HIGHRISE BUILDINGS

Section 602.1 (Building Code)

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers, open parking structures, and Group A-5 Occupancies.

Section 602.3 (Building Code) structures.

Provide automatic fire suppression throughout high-rise buildings. Exception: Open parking

Section 602.6 (Building Code) or more floors.

Provide automatic fire detection system in rooms per Building Code and in ducts serving two

Section 602.7 (Building Code)

Provide voice alarm and communication systems.

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and Group 1-3 and single station smoke detectors in sleeping areas and dwelling units.

HAZARDOUS PRODUCTION MA'iERIALS FACILTIIES

Section 603.1.2.1 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 603.1.7.2 (Building Code)

Install smoke detectors in re -circulating air-stream.

Section 603.4.5 (Building Code)

Provide local manual alarm pull station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

5-51 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 512: NEMA GUIDE CODE Fire Alarm & Detection System

Section 617.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

Section 1017.5 (Building Code)

Automatic fire detection system not required when building equipped with automatic fire suppression system but must provide manual fire alarm system. Exception does not apply to Group 1-2 and 1-3 and single station smoke detectors in sleeping areas and dwelling units.

SPECIAL NOTES

Section 606.2 (Building Code)

Provide an electrically supervised automatic sprinkler system.

Section 606.4 (Building Code)

Provide a smoke control system in accordance with Section 1019.4 in all atriums that connect more than two stories.

Section 1019.4.3 (Building Code)

Provide smoke detectors in the atrium and on the ceiling of floors opening into the atrium within 15 feet of the atrium.

Section 606.6 (Building Code)

Provide a fire alarm system in all buildings with an atrium. In Use Groups A, E, or M the system is required to be a voice alarm signaling system.

5-52 District of Columbia

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 513: NEMA GUIDE CODE Fire Alarm & Detection System

CI" OF HOUSTON, TEXAS Administrative Requirements

Building Code

Code 1994 UBC

Amendments City amendments

Fire Prevention Code

1994 UFC

City amendments

Promulgation

Enforcement

Comments

R. D. Kendrick Assistant Fire Marshal Houston Fire Department Fire Prevention 41 O Bagby Street, Room 4 19

Houston, TX 77002

IR. D. Kendrick Assistant Fire Marshal IHouston Fire Department Fire Prevention 410 Bagby Street, Room419 Houston, TX 77002

(713) 247-3182

Melvin L. Embry Building Official Planning & Development Department Building Inspection Division P. O. Box 61 167 Houston, TX 77208-1 167

Melvin L. Embry Building Official Planning & Development Department Building Inspection Division P. O. Box 61 167 Houston, TX 77208-1 167

(713) 535-7510

(713) 535-7510

Life Safeíy Code

Summary of Amendments

None

City revises high-rise provisions to apply to all buildings more than 75 feet. City expands fire protection requirements for educational occupancies, high-rise and existing buildings.

5-53 Houston. TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 514: NEMA GUIDE CODE Fire Alarm & Detection System

CTTY OF HOUSTON 1994 Uniform Codes (ICBO) with City Amendments

Fire Alarm/Detection Systems

Automatic Detection Systems

Automatic Fire Sprinkler Systems

Fire Alarm Systems Occupancy Type

Group A - Assembly Amusement Buildings

Required Reauired

Required Required Required

Required Required Group B - Business Required

> 50 occupants Group E - Educational

Group F- Factory Industrial

Group H - Hazardous H-1 - Flammables/

Explosives H-2 - Moderate

H-3 - HighHazard H 4 - Repair Garages H-ó - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Required

Required

Required

Required

Required Required > 3,000 sq. fi.

Required Required

Required

Required Required

Group I- Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Required Required Required

~

Required Required Required

Required Required Required

Group M - Mercantile > 3 stories > 12,000 sq. ft./floor > 24,000 sq. fi. total

Group R - Residential R-1 - Hotel/Multifamily > 3 stories > 3 stories > 3 stories

Group S - Storage Required

High-rise - New and Existing Construction

B-2 - OEces R-1 - HotelA4ulti-family

> 75 ft. 75 fi.

> 75 fi. > 7 5 ft.

> 75 fi. > 75 fi.

Required ~

Required

Required

Covered Malls

Aviation Control Towers

Required

Required

5-54 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 515: NEMA GUIDE CODE Fire Alarm & Detection System

CíTY OF HOUSTON 1994 Uniform Codes (ICBO) with City Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) (Amended)

Provide automatic sprinkler systems in Group A as follows:

when used for consumption of alcoholic beverages.

ta Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A-4. ta Multi-theater complexes.

Amusement building, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point orfire watch program in place. ta All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages.

Rooms and un-separated accessory uses more than 5,000 square feet in total area

Basements more than 1,500 square feet in floor area.

Section 303.9 (Building Code)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system, which activates prerecorded announcement using an approved electrically supervised voice communication or public address system. Exception: Occupancies with automatic fire-extinguishing system installed to activate prerecorded message.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm and/or public address systems.

GROUP B - BUSINESS

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

5-55 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 516: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2 (Building Code) Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code) (Amended)

Section 904.2.4 (Building Code)

Section 1017.4 (Building Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation. Provide approved manual and automatic fire alarm system when the occupant load is more than 50 persons. Provide products o f combustion detectors in all day-care nurseries, day-care schools, andpre-kindergarten schools, and interconnect with the .fire alarm system. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide smoke detectors in Group E-I in interior corridors serving as exits and in storerooms, mechanical rooms, janitorial rooms and similar areas. Approved heat detectors may be installed in lieu of smoke detectors in mechanical and janitorial rooms and similar areas.

Provide smoke detectors in corridors, in common areas, and in each room or area that exceeds 20 square,feet in,floor area in Group E-3 with occupant load of 50 or more. I f occupant load is less than 50, provide single-station smoke detectors in each occupiable area. Interconnect in such a way that activation of an-v detector will automatical1,v activate the alarm of all detectors.

Provide automatic fire extinguishing system throughout all Group E- 1 occupancies including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two- hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: I ) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

5-56 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 517: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6 and Article 80 (Fire Code)

Section 307.11 (Building Code)

Section 904.2.5 (Building Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved manual alarm pull station or approved signal device outside each exit door from hazardous production materials (Group H-6) storage rooms.

GROUP I - INSTITUTIONAL

Provide automatic fire extinguishing systems throughout H-I, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Section 904.2.6 (Building Code)

Provide approved manual and automatic fire alarm system in all Group I Occupancies.

Provide smoke detectors in Patient sleeping rooms of hospital and nursing homes. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups I-1.1,1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

Provide automatic fire extinguishing system throughout.

5-57 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 518: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Appendix Chapter 3, Division 1 (Building Code)

Alternative provisions for Group 1-3 Occupancy housing more than six inmates. Provide automatic sprinkler system; smoke management system with smoke detectors, and fire alarm system.

GROUP M - MERCANTILE

Section 904.2.7 (Building Code)

Provide automatic sprinkler system in retail stores if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code)

Provide smoke detectors in dwelling units, congregated residences, and hotel or lodging houseguest rooms installed per manufacturer's instructions.

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in a high- rise building provide a fire alarmkommunication system. Exceptions: 1) Buildings not more than two stories with all individual units provided one hour f i e separation and direct exterior egress; 2) Building with automatic sprinkler system throughout and with local alarm system.

Section 904.2.8 (Building Code)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more.

Section 1007.2.9.1.3 (Fire Code)

In Group R-1, provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants.

5-58 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 519: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION

Section 403.2 (Building Code)

Section 403.3 (Building Code) (Amended) and Section 1007.2.12 (Fire Code)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 403.7 (Building Code) (Am ended)

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 7 5 feet above lowest level of fire department access.

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies, and in commercial kitchens.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 7 5 feet above lowest level of fire department access.

Provide at least two approved listed smoke detectors in each elevator 1obb.v located on lobby ceilingpositioned at each opening into the lobby other than elevator door entrances.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

OTHER USES AND SPECIAL CONDITIONS

Section 1007.2.12.4 and Article 81 (Fire Code)

Provide automatic smoke-detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 81-A.

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Provide automatic smoke-detection system throughout building when special egress- control devices are installed on exit doors.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

5-59 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 520: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE. NEW CONSTRUCTION (continued)

Section 1007.2.12.8 (Fire Code)

Provide approved automatic smoke-detection system when required by the Building Code for automatic control of a smoke-control system.

HIGHRISE AND OTHER EXiSTLNG STRUCTURES

Appendm Chapter 34 Division II (Building Code) (Deleted)

(City does not adopt this division ofAppendix Chapter 34.)

Section 1007.4 (Fire Code) (Added)

Appendix 1-B (Fire Code)

COVEREDMALLS

Section 404.3.1 (Building Code)

In existing dwelling units, congregate residences, and guest rooms in hotels or lodging houses, provide approved single-station smoke detectors per building code in effect when the building was constructed and applicable state laws.

Provide automatic sprinkler systems in exit corridors, stairwell, elevator lobbies, and public assembly areas with 100 or more persons, and commercial kitchens. Apply to all existing high-rise buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Provide approved manual fire alarm system connected to approved central, proprietary or remote station service, or a system, which will provide an audible signal at a constantly attended location. Provide single-station smoke detectors in dwelling units and guest rooms.

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Append= Chapter 4, Division II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

5-60 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 521: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP CARE FACILITIES (GROUP R DIVISION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code) (Deleted)

(City does not adopt this division ofAppendix Chapter 3.)

Section 904.2.2 (Building Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1994 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Ekceptions: Airport control towers, open parking structures, and Group F-2 Occupancies.

Appendix Chapter 34, Division 1, Section 3408 smoke detection. (Building Code) and Appendix 1-A (Fire Code)

Protect openings into interior shafts in existing buildings other than Group R-3, M, and high-rise buildings by self-closing one-hour fire assemblies or by automatic closing by

Appendix Chapter 34, Division 1, Section 3409 (Building Code) (Amended) and Appendix 1-A (Fire Code)

Provide approved automatic sprinkler system in basements of existing buildings with more than 1,500 square feet in area and meeting other criteria as established in the I994 UBC and 1994 UFC, and amended by the city. Exception: Groups U, R-3, B, F, M, and S-l and S-2 that are single-story buildings without basements.

5-61 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 522: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REOUIREMENTS íconünued)

Appendm Chapter 34, Division 1, Section 3411 (Building Code) (Amended) and Appendix 1 -A (Fire Code)

Section 713 (Building Code)

Provide smoke detector installed per approved manufacturer's instructions in day-care centers, dwelling units and hotel and lodging houseguest rooms used for sleeping purposes in existing buildings. Smoke detectors may be battery operated or may receive their primary power from the building wiring.

In high-rise buildings, provide an approved nianua1,fire alarm system that will provide an audible signal a t a constantly attended location within the building.

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper as required by the 1994 UBC.

5-62 Houston, TX

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 523: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF LAS VEGAS, NEVADA Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Building Fire Prevention Life Safeîy Code Code Code

1997 UBC 1997 UFC None

City amendments State and city amendments and current edition of NFPA National Fire Codes and Standards

Paul Wilkins Jeff Donahue Building Oficial Deputy Fire Marshal Department of Building and Las Vegas Fire Dept. Safety 500 North Casino Center 73 1 South Fourth Street Boulevard Las Vegas, NV 89 1 O 1 Las Vegas, NV 89101-2986

Paul Wilkins Jeff Donahue Building Oficial Deputy Fire Marshal Department of Building and Las Vegas Fire Dept. Safety 500 North Casino Center 73 1 South Fourth Street Boulevard Las Vegas, NV 89101 Las Vegas, NV 89101-2986

The city amendments to the 1997 Uniform Building Code as indicated on the following pages, are also enforced in other Nevada jurisdictions: Clark County, Boulder City, North Las Vegas, and the Cities of Mesquite and Henderson. City adopts more stringent fire protection provisions.

(702) 229-625 1 (702) 229-0366

(702) 229-625 1 (702) 229-0366

5-63 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 524: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF LAS VEGAS, NEVADA 1997 Uniform Codes (ICBO) with City Amendments

Fire AlarmíDetection Systems

i Required

Occupancy Type

;roup A - Assembly \musement Buildings ;roup B - Business

Group E- Educational

Group F- Factory Industrial

Group H - Hazardous H-1 - Flammables/

Explosives H-2 - Moderate

H-3 - HighHazard H 4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Group M - Mercantile

Group R - Residential R-1 - HoteVMultifamily

Group S - Storage

High-rise -New and Existing Construction

B - Offices R-1 - HotelA4ultifamily

Covered Maüs

Automatic Fire Sprinkler Systems

Required Reauired Required

~~

> 5 0 occupants

Required

Required

Required Required > 3,000 sq. ft.

Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. ft. total

> 3 stories

Required

> 55 ft. > 55 fi.

~~

Required

Fire Alarm Systems

~

Required Required Required

> 50 occupants

Required

Required

Required Required Required

> 3 stories

> 3 stories > 55 ft.

Required

Automatic Detection Systems

Required Required

Required

Required

Required Required Required

> 3 stories

5-64 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 525: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF LAS VEGAS, NEVADA 1997 Uniform Codes (ICBO) with City Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) (Amended) and Section 1003.2.3 (Fire Code)

Section 303.9 (Building Code)

Section 303.10 (Building Code) (Added)

Section 1007.2.2 (Fire Code)

Section 408 (Building Code) and Section 1007.2.12.1.2 (Fire Code)

GROUP B - BUSINESS

Provide automatic sprinkler systems in Group A as follows:

Basements more than 1,500 square feet in floor area. Exhibition and display rooms more than 12,000 square feet Enclosed usable space below or over a stairway in Groups A-2, A-2.1, A-3, and A d . Multi-theater complexes. Amusement buildings, except if temporary with floor area less than 1,000 square

All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms,

Groups A-1, A-2, A-2.1, and A-3 of 5,000 square feet or more, except churches.

feet and exit travel distance is less than 50 feet from any point.

workshops, storerooms, and other accessory spaces adjoining such stages.

square feet, or in conjunction with outdoor seating. Smoke-protected assembly seating, except press boxes, storage less than 1,000

Provide approved fire alarm system in Groups A-I, A-2, and A-2.1 occupancies installed per Fire Code.

Provide an automatic$re extinguishing system and alarm system per Fire Code in any building orportion of a building used as a movie theater, motion picture theater, mini motion picture theater, picture arcade theater, video or live entertainment arcade theater, or multiple arcade theater, or- similar use.

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is 1,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

In amusement buildings, provide automatic sprinkler, smoke detection, and supervised alarm andior public address systems. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

See specific requirements for High-rise Group B Office Buildings and Group R-1 Occupancies for both New Construction and Existing Structures.

5-65 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 526: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Provide approved smoke detectors to activate all automatic -closing fire assemblies installed in the atmospheric separation.

Section 305.9 (Building Code) and Section 1007.2.4 alarm. (Fire Code)

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate fire

Section 904.2.4 (Building Code) and Section 1003.2.4 (Fire Code) (Amended)

Section 1007.3.4 (Building Code) and Section 1007.2.4.2 (Fire Code)

Provide automatic fire sprinkler system throughout all Groups E-1 or E-2 occupancies with an occupant load of 50 or more, including basements and in enclosed usable space below or over a stairway. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour fire resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: 1) When aggregate occupant load of interior room is not more than ten; 2) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire -sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

5-66 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 527: NEMA GUIDE CODE Fire Alarm & Detection System

GROW H - HAZARDOUS

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code)

Section 307.11 (Building Code)

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

GROW I - INSTITUTIONAL

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H 4 occupancies with more than 3,000 square feet floor area.

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Provide approved manual and automatic fire alarm system in all Group I occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas.

Provide smoke detectors in patient sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups I-l.l,I-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

5-67 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 528: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and 1-2.

Appendix Chapter 3, Division 1 (Building Code) alarm system.

Alternative provisions for Group 1-3 housing with more than six inmates, provide automatic sprinkler system, smoke management system with smoke detectors, and fire

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) and Section 1003.2.8 than three stories. (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code) (Am ended)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer’s instructions and receiving primary power from building’s wiring and interconnected within the dwelling unit in which they are installed, with batteries as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code) (Am ended)

Provide approved manual and automatic fire alarm system in apartment house three or more stones or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings, provide a fire alarmícommunication system, except buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress. A manualfire alarm system is not required when the building is protected throughout by an approved monitored automatic sprinkler system and equipped with an approved aaitornatic$re alarm system.

5-68 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 529: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.9 (Building Code) and Section 1003.2.9 (Fire Code)

Section 1007.2.9.1.3 & .4 (Fire Code) (Am ended)

GROUP S - STORAGE

Section 1003.2.10 (Fire Code) (Added)

Provide automatic sprinkler system in apartment houses three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and congregate residences three or more stories or having occupant load of 20 or more. Install residential or quick-response standard sprinklers in dwelling units and guest rooms.

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants. Heat detectors may be installed in lieu of smoke detectors where there is a high probabilit,v of nuisance alarms due to environmental conditions. Smoke detectors in dwelling units must be interconnected as per NFPA 72.

Provide an automatic sprinkler systenz in Group S-1 occupancies more than 2,500 square feet; and in Groups S-2 and S-5 occupancies more than 5,000 square feet. For this purpose, a mini-storage warehouse will be classified as a Group S-I .

HIGHRISE. NEW CONSTRUCTION, GROUP B OFFICE BUILDINGS AND GROUP R-1 OCCUPANCIES

Section 1007.2.3 (Fire Code) (Amended)

Section 403.2 (Building Code) and Section 1007.2.12.2.1 (Fire Code) (Am ended)

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code)

Provide automatic or manualfire alarm system in Group B three or more stories but less than 55 feet above the lowest level offire department access. (See also Section 1007.2. I2 of Fire Code.)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in all Group A, all divisions: Group B: Group E, all divisions: Group I, all divisions: Group M; and Group R-1 buildings, each having floors used for human occupancy located more than 55 feet above lowest level of fire department access.

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

5-69 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 530: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE, NEW CONSTRUCI'ION, GROW B OFFICE BUILDINGS AM> GROUP R-1 OCCUPANCIES (continued)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code)

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Section 1007.2.12.8 (Fire Code)

Section 1007.2.12.9 (Fire Code)

Section 1007.3.3 (Fire Code) (Added)

Provide fire alarm, emergency voice/alarm signaling system and f i e department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access.

Buildings with atriums: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Provide automatic fire -detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 8 1 -A.

Provide automatic smoke -detection system throughout building when special egress- control devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive construction. Install detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smoke -control system.

Provide manual fire alarm system in lumber, plywood, and veneer mills.

In buildings provided with afire alarm system, the smoke detector(s) installed in air handlers must be connected to thejìre alarm control panel. In buildings without afire alarm system, activation of the air handler smoke detector(s) must cause annunciation of an audiblehisual signal in a normally occupied area.

HIGHRISE. GROUP B-2 OFFICES AND GROW R-1 OCCUPANCIES. EXISTING STRUCTURES

Appendix Chapter 34 Division II (Building Code) and Appendix 1-B (Fire Code) (Deleted)

(City does not adopt these Appendix Chapters.)

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

5-70 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 531: NEMA GUIDE CODE Fire Alarm & Detection System

AWTION CONTROL TOWERS

Appendix Chapter 4, Division II, Section 425 (Building Code) (Deleted)

(City does not adopt this Appendix Chapter.)

GROUP CARE FACíLITIES (GROUP R DIVISION 4)

Appendix Chapter 3, Division IV, Section 341 (Building Code)

Provide approved automatic and manual fire alarm systems.

5-71 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 532: NEMA GUIDE CODE Fire Alarm & Detection System

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code) (Am ended)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms; in rooms where nitrate film is stored or handled, in protected combustible fiber storage vaults, throughout ail buildings with floor levels with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access or more than two stories above grade at any point (except airport control towers, open parking structures, and Group F-2 occupancies); and throughout all buildings I 0, 000 square feet or more in total area in which any area 5,000 square feet or more in total area is not separated by an approved area separation wall (except any open parking structure).

Appendix Chapter 34, Division 1, Section 3408 (Building Code) and Appendix 1-A (Fire Code) (Deleted)

Section 713 (Building Code) (Amended)

Section 905.9.5 (Building Code) (Amended)

Section 3003.2 (Building Code)

(City does not adopt these Appendix Chapters.)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the City Building Code.

Equip supply air fans for mechanical smoke-control systems with approved smoke detectors to shut offthe fans and close their respective dampers when smoke is detected.

Provide elevator lobby, entrance area, and associated machine rooms with approved, listed smoke detector for elevator recall purposes when the elevator vertical travel is 25 feet or more.

5-72 Las Vegas, NV

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 533: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF LOS ANGELES, CAJJF'ORNI.4 Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Building Code

1997 UBC

State and city amendments

Andrew Adelman General Manager and Building Official Department of Building and Safety 201 N. Figueroa Street, Suite 1000 Los Angeles, CA 9001 2

Vic Penera Chief, Engineering Bureau (213) 977-6380 or Bob Martin Chief, Inspection Bureau Department of Building and Safety 201 N. Figueroa Street, Suite 1000, Room 1030 Los Angeles, CA 90012

(213) 977-6941

(213) 977-6388

Fire Prevention Code

Los Angeles City Fire Code

Summary of Amendments

City-written

Michael S. Fulmis Assistant Fire Marshal Bureau of Fire Prevention and Public Safety 200 North Main Street 9 1 O City Hall East Los Angeles, CA 90012 (213) 485-5980

City enforces the California Building Code. See summary of California State amendments to the 1997 Uniform Building Code in Chapter 4.

In most instances, the city-written Fire Code refers user to Chapter 9 of the Building Code for fire protection requirements.

Michael S. Fulmis Assistant Fire Marshal Bureau of Fire Prevention and Public Safety 200 North Main Street 9 1 O City Hall East Los Angeles, CA 90012 (213) 485-5980

Life Safety Code

None

5-73 Los Angeles, CA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 534: NEMA GUIDE CODE Fire Alarm & Detection System

COUNTY OF LOS ANGELES, CALIFORNIA Administrative Requirements

Code

I Building I Fire Prevention I Life Safety Code Code Code

1997 UBC 1997 UFC None

Amendments

Promulgation

Enforcement

State and county amendments

County Board of Supervisors

John Kelly Robert New

County amendments

County Board of Supervisors

Superintendent, Building Department Los Angeles County 900 South Fremont Ave. Alhambra, CA 9 1803 (626) 458-3173

5-74 County of Los Angeles

Fire Marshal Los Angeles County Fire Prevention Bureau 5823 Rickenbacker Road Commerce, CA 90040-3027 (323) 890-4132

_ _ _ _ _ ~ ~

Comments

Summary of Amendments

The Los Angeles County Fire Code is the fire code for the unincorporated areas of Los Angeles County and for 5 1 cities in the county who have contracts with the LA County Fire Department for fire service. County enforces the California Building Code. See summary of California State amendments to the 1997 Uniform Building Code in Chapter 4. The County requires the installation of automatic sminkler svstems in all buildings over three stories.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 535: NEMA GUIDE CODE Fire Alarm & Detection System

CITYOFMtAMI,FLORIDA Administrative Requirements

Code

Building Code

South Florida Building Code,

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

County -written

Frank Quintana Director Miami-Dade County Board of Rules & Appeals Building Code Compliance Office Metro-Dade Flagler Building I40 West Flagler Street Suite 1603 Miami, FL 33130

Frank Rollason Director or Roberto Hevia Building Official City of Miami Building and Zoning Department 444 SW Second Avenue, 4'h Floor Miami, FL 33 130

South Florida Building Code (S

(305) 375-2901

(305) 416-1 105

Fire Prevention Code

4s referenced in building code references certain NFPA Vational Fire Codes and Standards) lounty amendments

Frank Quintana Director %ami-Dade County Board of Rules & Appeals Building Code Zompliance Office Metro -Dade Flagler Building 140 West Flagler Street Suite 1603 Miami, FL 33130

Frank Barron Special Assistant to the Fire Marshal City of Miami Division of the Fire Marshal, loth Floor 444 SW Second Avenue Miami, FL 33130

[305) 375-2901

(305) 416-1600

Life Safety Code

1994NFPA 101

No amendments

Frank Quintana Director Miami-Dade County Board of Rules & Appeals Building Code Compliance Office Metro-Dade Flagler Building 140 West Flagler Street Suite 1603 Miami, FL 33 130

Frank Barron Special Assistant to the Fire Marshal City of Miami Division of the Fire Marshal, IOth Floor 444 SW Second Avenue Miami, FL 33130

(305) 375-2901

(305) 416-1600

BC), Dade County edition, covers Miami City/Dade County area and includes NFPA 101 adopted by reference. SFBC contains distinct use group classifications not compatible with standard building codes. SFBC can be amended as often as monthly by County Board of Rules and Appeals. SFBC provides fire suppression requirements per NFPA 101 and as necessary for individual occupancies as classified by Building Code. See 1994 NFPA 101 in Chapter 3 for additional

]code arovisions.

5-75 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 536: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF MIAIW, FLORIDA South Florida Building Code (Dade County)

Use Group Classifications

GROUP A - ASSEMBLY

Buildings or portions thereof used for:

Bowling Centers Auditoriums Churches Courtrooms Pool Rooms Recreation Piers Theaters Club Rooms Exhibition Hails Stadiums Drinking Establishments Lecture or Study Halls

Motion Picture Theaters Skating Rinks Passenger Stations and Terminals of Public Transportation Facilities Dance Halls Gymnasiums Restaurants Night Clubs and Discotheques Meeting and Conference Rooms Armories Libraries

and similar uses with occupant content of 1,000 persons or more.

GROUP B - ASSEMBLY

Sub-classiSl as follows:

B-1 - Assembly uses with occupant content of 300 to 1,000 persons, alternately termed Class B assembly.

B-2 - Assembly uses with occupant content greater than 50 but less than 300 persons; may also term as Class C Assembly Occupancies.

GROUP C - EDUCATIONAL

All schools with classes more than four hours per day or twelve hours per week and providing facilities for more than six students or preschool children.

5-76 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 537: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP D - INSTI'IWTIONAL

Sub-classify as follows:

D-1 - Occupancy where a person's liberties are restricted, such as jail, prison, reformatory, and asylum.

D-2 - Buildings or portions thereof where accommodations are provided for at least four persons who are under physical limitations. Includes hospitals, nursing homes, sanitariums, and orphanages.

D-3 - Occupancies where one or more personal services are provided for more than 24 hour to more than six persons residing therein, not under severe physical limitations that prevents them from having physical and mental capability of evacuating themselves from building in case of emergency.

GROUP E - HAZARDOUS

Hazardous uses such as the storage and use of easily ignited materials that burn rapidly. Sub-classify as follows:

El - Buildings for storage and handling of explosives and highly flammable or exp losive materials other than Class I, II, or IIA liquids.

E 2 - Buildings for storage and handling of Class I, II, and III flammable liquids.

GROUP F - STORAGE/INDUSTRIAL

Sub-classify as follows:

F-1 - Storage occupancies includes warehouses, storage buildings, freight depots, public garages of any size where repair work is done, parking garages for more than four cars, gasoline service stations, or aircraft hangars.

F-2 - Industrial occupancies includes factories, assembly and manufacturing plants, processing mills, laboratories, loft buildings, creameries, laundries, ice plants, sawmills, planing mills, box factories, and woodworking shops with fixed or portable power equipment or tools with combined total more than 20 HP.

5-77 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 538: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP G - MERCANTILEBUSINESS

Sub-classify as follows:

G1 - Mercantile occupancies includes retail stores, shops, sales room, markets, and similar uses.

G2 - Business occupancies includes office buildings, banks, civic administration buildings, telephone exchanges, museums, art galleries, libraries, and similar uses.

GROUPH -MULTIFAMILY RESIDENTIAL

Multiple residential uses, such as hotels, motels, apartment-hotels, apartment houses, bungalow courts, rooming houses, dormitories, fraternity houses, and monasteries and similar uses with three or more living units. Exception: Single-family residences with not more than three bedrooms, not more than two ofwhich are rented to maximum two persons per bedroom are classified as Group I.

GROW I - RESIDENTWL

Includes the following:

G Single-family homes and duplexes. G Dormitory, fraternity houses, and monastery buildings used to house maximum six persons. ta Group C buildings used to house maximum six students and required supervisory personnel.

Group D Division 2 buildings used to house maximum three inmates and required supervisory personnel. Rooming houses operated in single-family residence with maximum three bedrooms, two of which are rented to not more than two persons per bedroom.

ta Group D Division 3 buildings used to house maximum six persons with required supervisory personnel.

GROUP J - ANCILLARY STRUCTURES

Sub-classify as follows:

J-1 - Garages for maximum four motor vehicles, porte-cocheres, and carports.

5-2 - Tanks, towers, and similar structures and fences.

5-3 - Marinas.

J 4 - Cabanas, bathhouses, and similar buildings.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 539: NEMA GUIDE CODE Fire Alarm & Detection System

GROW J - ANCJLLARY STRUCTURES (continued)

5-5 - Public and private swimming pools and accessory buildings.

5-6 - Solariums, sundecks, and similar roofless structures.

5-7 - Greenhouses, agricultural buildings, and farm service buildings not for human habitation, including those used for housing livestock, poultry, farrnmachinery, seed, feed, and fertilizer.

J-8 - Open storage yards including those for lumber and contractor's storage.

5-79 Mianli,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 540: NEMA GUIDE CODE Fire Alarm & Detection System

Occupancy Type

II Group A - Assembly

II Group B - Assembly ~

Group C - Educational

Group E - Hazardous

Group F - Storage/Industrial

Group M - MercantiieíBusiness

Group H - Muitifarnily

Group I- Residential

High-rise I

CITY OF MIAMI, FLORIDA South Florida Building Code

Fire Alarm/Detection Systems

Automatic Fire Sprinkler Systems

~~ ~~

Required

Required

Required

Required

Required

Required

Required

Required

Required

Fire Alarm Systems

> 100,000 sq. fi.

Required

Required

> 3 stories > 11 units

Required

Automatic Detection Systems

Required

Required

Required

5-80 Miarni,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 541: NEMA GUIDE CODE Fire Alarm & Detection System

CI'IYOFMIAMl,FLORIDA South Florida Building Code Requirements and Exceptions

GROUPS A AND B - ASSEMBLIES

Section 3104.3 (Building Code)

Section 3802.3 ,

(Building Code)

Provide sprinklers in theaters with more than one viewing room. Provide approved fire alarm system in assemblies with more than 2,000 persons occupant load.

ta Multipurpose assembly occupancies consisting of single room less than 12,000 square feet area and not used for exhibition and display.

Passenger terminals at or above grade. ta Gymnasiums used for no other purpose.

Skating rinks and swimming pools used exclusively for participant sport with audience facilities for maximum 300 persons.

Group B used exclusively as restaurants.

Also provide in stages, projection rooms, and building equipment or storage rooms per NFPA 101.

GROUP C - EDUCATIONAL

Section 3105.3 (Building Code)

Provide fire alarm system in educational occupancies.

Section 3802.3 (Building Code)

Provide approved automatic sprinkler systems in Group C occupancies having a stage.

GROUP D - INSTITUTIONAL

Section 3802.3 (Building Code)

Provide approved automatic sprinkler systems in Group D occupancies of Type I and Type II construction more than three stories; Type III construction for Group D-1 and D-2; and in Group D-3 where more than six individuals receiving services reside in construction Types III, IV, and V buildings.

5-81 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 542: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP D - INSTITUTIONAL (continued)

Section 3802.3 (Building Code) (continued) automatic fire detection systems.

Exception: Hospital operating rooms, delivery rooms, nurseries, X-ray and therapy equipment rooms, cardiac and intensive care rooms provided such areas protected by

GROUP E - HAZARDOUS

Section 3108.3 (Building Code) 100,000 square feet.

Provide fire alarm system except Group E not exceeding aggregate floor area of

Section 3208.3 (Building Code)

Provide approved automatic sprinkler system in Group E and high hazard areas within buildings of other occupancies per NFPA 101- 1994.

GROUP F - STORAGEXNDUSTRIAL

Section 3108.3 (Building Code)

Provide fire alarm system, except: Storage occupancies limited to low hazard contents. Group F-1 not exceeding aggregate floor area of 100,000 square feet. Group F with automatic extinguishment protection. Group F-1 open parking structures. Group F-2 where total capacity of the building is less than 100 persons and fewer

than 25 persons are above or below level of exit discharge.

Section 3208.3 (Building Code)

Provide approved automatic sprinkler systems throughout as follows: Buildings in or with fire divisions of Group F-1 , other than parking garages,

maximuni two stories high used for the storage of combustible goods or merchandise and more than 20,000 square feet per floor, or such buildings three or more stories exceeding 10,000 square feet per floor area.

Group F-1 enclosed parking garages more than 50 feet high; open air parking garages more than 75 feet high; repair garages more than one story or located below another occupancy, more than 10,000 square feet per floor ofType I construction, or more than 8,000 square feet of protected noncombustible construction; one story repair garages more than 15,000 square feet of Type I construction, 12,000 square feet if of protected noncombustible, or 9,000 square feet floor area if of unprotected noncombustible, heavy timber, or Type III construction.

located under any other occupancy. Basement parking or repair garages more than 5,000 square feet in floor area

5-82 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 543: NEMA GUIDE CODE Fire Alarm & Detection System

GROW F - STORAGE/íNDUSTRIAZ, (continued)

Section 3208.3 (Building Code) (continued)

Group F-2 used for shops, plants, or factories where loose combustible fibers, chips, shavings, and dust are produced or generated and buildings are over one story, or in mixed occupancy exceeding 8,000 square feet per floor, or in buildings one story and exceeding 15,000 square feet in floor area. G Group F-2 used for dry goods and apparel manufacturing more than 10,000 square feet floor area, one or two stories of Type II or Type III construction; more than 2,500 square feet of Type II or Type III constructed wholly or in part with combustible materials; of Type III Unprotected, Type IV or Type V construction; or more than three stories high.

High hazard industrial occupancies and high hazard areas within buildings of other occupancies per NFPA 101 -1994.

GROUP G - MERCANTLE/BUSINESS

Section 3109.3 (Building Code)

Provide fire alarm system in Class A (Group G1) mercantile occupancies and in buildings with an atrium.

Section 3802.3 (Building Code)

Provide approved automatic sprinkler systems in Group G as follows: Group G1 buildings three or more stories or have story more than 12,000 square

feet gross area or more than 24,000 square feet gross area regardless of height. Group G-1 stories below level of exit discharge more than 2,500 square feet. Group G-l Class A stories more than 30,000 square feet.

GROWN - MULTIFAMILY RESIDENTIAL

Section 3110.3 (Building Code)

Provide manual fire alarm system in apartment buildings more than three stories or with more than I l living units. Install approved single or multiple station smoke detectors continuously powered by house electrical service in every living unit in apartment building regardless of size or height. Single station detection not required when building equipped with total automatic smoke detection system throughout.

5-83 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 544: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - MULTIFAMJLY RESIDENTIAL (continued)

Section 3802.3 (Building Code)

Provide approved automatic sprinkler systems in buildings used as public lodging establishments and timeshare plans except buildings less than 75 feet high where there is direct access to exclusively exterior means of egress. All other Group H occupancies must comply with one of the four options specified in Chapter 18 ofNFPA 101-1994.

Provide UL listed single station smoke detectors in residential living units, guest rooms, and timeshare units.

Section 3903.7 (Building Code)

Provide listed single station smoke detectors powered by 1 1 OV circuit within a tenant space of every apartment, hotel suite or guest room. Also provide in public lodging establishments.

GROUP I - RESIDENTIAL

Section 3 11 1.3 (Building Code)

Provide single or multiple station smoke detectors powered by house electrical service except in dwelling units protected by approved smoke detection system.

HIGHRISE BUíLDINGS

Section 3901 (Building Code)

Apply high-rise provisions to buildings more than 50 feet high except Group F-1 enclosed parking garages, Group F-1 open parking garages not more than 75 feet high, Group I and Group J occupancies.

Section 3902 (Building Code)

Provide automatic sprinkler systems throughout high-rise buildings.

Section 3903 (Building Code)

Provide fire alarm systems in high-rise buildings. Install automatic detection system in air conditioning and ventilation systems that extend to more than one floor, and at each floor opening into a smoke-proof enclosure. Provide smoke sensing devices in entrance areas to elevator lobbies.

5-84 Miami,FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 545: NEMA GUIDE CODE Fire Alarm & Detection System

Section 1807.9 (Building Code) terminal rooms.

Provide automatic sprinklers in laundry and trash chutes and service opening and

Section 3802.1(d) (Building Code)

Provide approved automatic sprinkler system in buildings or areas within buildings which are windowless or located underground if the occupant load is more than 50 or there are more than 2,500 square feet of area used for the sale, storage, or handling of combustible materials. Exception: Group F occupancies used for storage.

Section 3808.1 (Building Code)

Install fire alarm system per this code or NFPA 101-1994 for specific occupancies.

5-85 Miami,=

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 546: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF MINNEAPOLIS, MINNESOTA Administrative Requirements

Building Code

Code 1997 UBC

Amendments State amendments

Promulgation Janet Streff Building Code Representative Minnesota Department of Administration Building Codes and Standards Division 121 East Seventh Place,

St. Paul, MN 55101-2181 (612) 296-4329

Director of Inspections Department of Regulatory Services Inspections Division 300 Public Health Center 250 South Fourth Street Minneapolis, MN 55415-1316

Suite 408

Enforcement Menvyn Larson

(612) 673-5821 Comments

Fire Prevention Code

1997 UFC

State amendments and city supplements Gordy Bates Plan Reviewer City of Minneapolis Fire Prevention Bureau 350 South Fifth Street, Room 230 Minneapolis, MN 55415 (612) 67'3-3292

Gordy Bates Plan Reviewer City of Minneapolis Fire Prevention Bureau 350 South Fifth Street, Room 230 Minneapolis, MN 55415 (612) 673-3292

Life Safety Code

None

Summary of Amendments

See State of Minnesota in Chapter 4 for provisions on fire alarm and detection systems.

5-86 Minneapolis, MN

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 547: NEMA GUIDE CODE Fire Alarm & Detection System

MONTGOMERY COUNTY, MARYLAND Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Building Fire Prevention Code Code

1996 BOCA

County supplement County supplement

Shahriar Amiri Theodore Jarboe Chief of Building Fire Marshal Construction Division Dept. of Environmental Protection Suite 201D 255 Rockvilie Pike

NFPA National Fire Codes and Standards

Bureau of Fire Prevention 255 Rockville Pike

Rockville, MD 20850 Rockville, MD 20850 (240) 777-2457 (240) 777-6230 Shahriar Amiri Theodore Jarboe Chief of Building Construction Division Prevention Dept. of Environmental Protection 255 Rockvilie Pike 255 Rockville Pike Rockville, MD 20850

Deputy Chief of Fire

Bureau of Fire Prevention

Suite 20 ID Rockville, MD 20850

(240) 777-6230 (240) 777-2457

Life Safety Code

1997 NFPA 101

Summary of Amendments

County supplement

County amendments to the 1996 BOCA National Building Code require automatic fire suppression systems throughout all Group R-3. It also classifies family day-care and group day-care homes as Group R-3.

See Chapter 3 for 1996 National Code fire protectionrequirements and following pages for Montgomery County’s amendments to 1997 NFPA 101.

Theodore Jarboe Fire Marshal Bureau of Fire Prevention 255 Rockville Pike Suite 201D Rockville, MD 20850 (240) 777-2457

Theodore Jarboe Deputy Chief of Fire Prevention Bureau of Fire Prevention 255 Rockville Pike Suite 201D Rockville, MD 20850 (240) 777-2457

5-87 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 548: NEMA GUIDE CODE Fire Alarm & Detection System

MONTGOMERY COUNTY, MARYLAND 1997 NFPA 101 with County Amendments

Fire Alarm/Detection Systems

Automatic Fire Sprinkler Systems

Required

Required Required

Required

Required

"A - Occupancy Assembly

Underground Special Amusement

Educational

Fire Alarm Systems

Required Required

Required

Required

Required

II Health Care

Required

Required

Detention and Correctional

Required

z 3 stories

I Hotels/Dormitories

Apartments

High hazard

Lodging Houses

Residential Board Care Small Facilities Large Facilities

Mercantile

Covered Malls

> 300 persons

Required

II Atriums

(1 Business

II Industrial

Required Required

Required Required

Required 1 Required

Automatic Detection Systems

Hazardous areas Required Required Required

Required

Required

Required

Required

Required

Required Reauired

Required

5-88 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 549: NEMA GUIDE CODE Fire Alarm & Detection System

Storage Required

5-89 Montgomery County, MD

High-rise Buildings

Day-care

> 75 ft. > 75 ft.

Required Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 550: NEMA GUIDE CODE Fire Alarm & Detection System

MONTOGOMERY COUNTY, MARYLAND 1997 NFPA 101 with County Amendments

Requirements and Exceptions

ASSEMBLY OCCWANCIES

84.5.5 In proscenium opening, provide emergency ventilation to remove smoke and independently activated by sprinkler system in stage area, smoke detectors over stage area, and by manually operated switch at approved location.

84.5.10

8-3.4.1

8-3.4.2.2

8-3.5.1 (Amended)

84.3.3.4

84.3.5

84.2.1

Provide approved automatic sprinkler system for stages, in permanent dressing rooms, storerooms and workshops, and other accessory spaces contiguous to stage. Exception: Stages 1,000 square feet or less in area and 50 feet or less in height and under stage areas less than four feet in height.

Provide approved fire alarm system in assembly occupancies with occupant load of 300 or more and in theaters with more than one audience-viewing room. Initiate alarm by manual means or with automatic detection or sprinkler systems.

Provide automatic detection in all hazardous areas of assembly occupancies with occupant load of 300 or more unless protected by automatic sprinkler system.

Provide full automatic sprinkler protection throughout building containing assembly occupancies above or below level of exit discharge OY with occupant load of 300 or more on level of exit discharge. Exceptions:

Occupancies primarily for worship with fixed seating. Assembly rooms less than 12,000 square feet not used for exhibition and display. Participant sports areas with audience less than 300 people.

Provide automatic smoke detection throughout each smoke compartment of underground portions of assembly buildings.

Provide supervised voice alarm system in underground portions of assembly buildings.

Provide approved, automatic sprinkler system in all enclosed areas with walls and ceilings in buildings or structures containing smoke-protected assembly seating.

5-90 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 551: NEMA GUIDE CODE Fire Alarm & Detection System

ASSEMBLY OCCUPANCIES (continued)

8-7.5.3.7 Provide automatic extinguishing system in certain levels of exhibit booths covered with a ceiling.

84.7.2 & .3 Provide approved automatic sprinkler system throughout special amusement buildings. When operating at reduced lighting levels, provide automatic smoke detection. Provide automatic smoke-detection to sound an alarm, illuminate means of egress and stop confusing sounds.

EDUCATIONAL

10-3.2.1

10-3.4.1

10-3.5

104.1.3 & .6

104.1.3.4

HEMATHCARE

12-2.2.2.6

12-3.4.1.1 & 12-3.4.2

Provide automatic extinguishing system in rooms or spaces used for processing or use of combustible supplies in quantities considered hazardous, including janitor closets.

Provide fire alarm system throughout all educational occupancies unless maximum area is 1,000 square feet with single classroom and not location to another building not less than 50 feet.. Exception: May omit manual pull stations in locations per administrative authority in buildings with two-way communication between normally occupied spaces and constantly attended receiving station, and when conditions of Section 10-3.4.2.3 are met.

Provide automatic sprinkler system in portions below level of exit discharge.

Provide automatic smoke detection for portions underground or more than 30 feet below level of exit discharge. Also provide approved supervised voice alarm system.

Provide smoke detection system throughout each smoke compartment.

The automatic sprinkler system and the fire alarm system shall initiate closing action of all doors throughout entire facility.

Provide fire alarm system equipped with a secondaxy power supply and initiated by manual means and by required sprinkler and detection systems.

5-91 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 552: NEMA GUIDE CODE Fire Alarm & Detection System

HEALTH CARE (continued1

12-3.4.5.3 In nursing homes, provide approved automatic smoke detection systems in corridors throughout smoke compartments containing patient sleeping rooms and in spaces open to corridors unless excepted by this section. Detection systems are to be provided with a secondary power supply.

12-3.5.1 Provide approved, supervised automatic sprinkler system throughout according to construction type. Install listed quick response or listed residential sprinklers throughout patient sleeping area.

12-6.3.4.1 & .2 Provide fire alarm system in all ambulatory health-care centers initiated by manual means and by means of any required detection devices or system.

Section 12-6.3.5.1 (Added)

Provide.ful1 automatic sprinkler protection in buildings containing new ambulatory health care centers located above or below the level(s) of exit discharge.

12-6.3.7.7 Fire alarm system and either a local smoke detector or a complete automatic fire extinguishing system or complete automatic fire detection system shall activate automatic closing devices on doors in smoke barriers.

DETENTION AND CORRECTIONAL

14-3.4.1.1 & -2 Provide electrically supervised fire alarm system throughout detention and correctional facilities. Initiate by manual means and by required detection devices or systems.

14-3.4.4 Provide approved automatic smoke detection throughout all resident sleeping areas and adjacent day rooms, activity rooms, and contiguous common spaces. Exception: May omit smoke detectors as follows:

In sleeping rooms with four or less occupants in Use Condition II or III; and In buildings protected throughout by automatic sprinkler system, may omit smoke

detectors from sleeping rooms with more than four occupants.

14-3.5.2 Provide automatic sprinkler system according to type of construction used.

5-92 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 553: NEMA GUIDE CODE Fire Alarm & Detection System

16-3.4.1 & .2 Provide fire alarm system in hotels and dormitories. Initiate by manual means, by a manual fire alarm station located at a central point, by any automatic sprinkler system, and by any required automatic detection system. Exception: Sleeping room smoke detectors need not initiate fire alarm system.

16-3.4.4.1 & .2

16-3.5.2

APARTMENTS

18-3.4.1 & .2

18-3.4.4.1

18-3.5.2

Provide corridor smoke detection except when protected throughout by approved, supervised automatic sprinkler system. Install single station smoke detectors powered by building electrical system in each sleeping room and each living area within a guest room or suite.

Provide approved supervised automatic sprinkler system throughout. Exception: Buildings other than high-rise where guest sleeping rooms have a door that opens directly outside at ground level. Install quick response or listed residential sprinklers throughout guest rooms and suites.

Provide fue alarm system for buildings more than three stories or with more than 11 living units except where each living unit is separated from other units by fire barriers with not less than 1-hour rating and has independent exit, exit stairway, or ramp discharging to grade or in buildings not more than four stories or 16 dwelling units protected with an automatic sprinkler system. Provide initiation by manual means or by automatic sprinkler system.

Provide approved single-station smoke detectors powered by house electrical service on all levels and in and outside sleeping rooms of every living unit within apartment buildings. Excepted are buildings protected throughout by an approved, supervised automatic sprinkler system.

Provide approved supervised automatic sprinkler system throughout building. Exception: Buildings where every living unit has either an exit door opening directly to ground level, direct access to an outside stair that serves no more than two units on same floor, or direct access to an interior stair serving only that unit with a one-hour fire resistance rating fue barrier from other portions of building. Install quick response or listed residential sprinklers throughout all living units.

5-93 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 554: NEMA GUIDE CODE Fire Alarm & Detection System

LODGING OR ROOMWG HOUSES

20-3.3.1 Provide fire alarm system except when equipped with smoke detection system that includes at least one manual fire alarm station.

20-3.3.4 Provide approved single-station smoke detectors powered by building's electrical service in every sleeping room.

20-3.5.2 Provide automatic sprinkler system in all new lodging or rooming houses unless every sleeping room has a door opening directly to the outside of the building at ground level or an exterior stairway.

ONE- AND TWO-FAMILY DWELLINGS

2 1 -3.3.1 (Amended)

Provide approved single-station smoke detectors powered by building's electrical system in all sleeping rooms, outside and in the immediate vicinity of sleeping rooms, and on each additional story including basement. Smoke alarms not required in sleeping rooms in buildings protected b,v approved automatic sprinkler system using quick response or residential sprinklers.

.

RESIDENTIAL BOARD CARE

Small Facilities 22-2.3.4.1-3 Provide manual fire alarm system and approved smoke detectors powered by house

electrical system throughout every area. Each sleeping room must be provided with approved, listed single station smoke detector. Exception: May omit detectors in buildings protected throughout by approved automatic sprinkler system using quick response or residential sprinklers.

22-2.3.5.1

Large Facilities 22-33.4.1 & .2

22-3.3.4.7

Provide approved automatic sprinkler system using quick response or residential sprinklers.

Provide fire alarm system to be initiated by manual means, by a manual fire alarm station located at a supervised central location, and by any automatic sprinkler and detection systems.

Provide approved single -station smoke detectors in each sleeping room of large facilities powered from building electrical system.

5-94 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 555: NEMA GUIDE CODE Fire Alarm & Detection System

RESIDENTIAL BOARD CARE (continued)

22-3.3.4.8 Provide smoke detectors in all living areas and corridors unless protected by approved automatic sprinkler system.

223.3.5.1 Provide approved automatic sprinkler system throughout all buildings. Install with quick response or residential sprinklers which will activate the fire alarm system.

MERCANTILE

24-3.4.1 & .2 (Amended)

24-3.5.1 & .2

COVERED MALLS

244.4.3.1 & .2

ATRIUMS

6-2.4.6

Provide fire alarm system in Class A mercantile occupancies and multiple story Class B mercantile occupancies. Initiate by manual means.

Provide approved, supervised automatic sprinkler system as follows: Buildings three or more stories in height. Buildings with more than 12,000 square feet in gross area. Stories below level of exit discharge with more than 2,500 square feet of area used for

combustible goods.

Provide fire alarm system in covered malls with initiation by approved automatic sprinkler systems. Install fire alarm system to automatically actuate smoke control system. This requirement also applies to bulk merchandising retail buildings.

Provide an approved supervised automatic sprinkler system in entire building with atrium. Exception: If atrium ceiling is more than 55 feet above the floor, the local authority may permit the omission of sprinklers at the top of the aîrium. Provide smoke detectors at the highest floor level of the atrium and at return air intakes from the atrium.

5-95 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 556: NEMA GUIDE CODE Fire Alarm & Detection System

BUSINESS

26-3.4.1 & .2

2 6-3.2.1

INDUSTRIAL

283.2

2 8-3.4.1

STORAGE

293.4

29-8.3.4

DAY CARE

30-3.4.1 & .2

3 0-3.4.5 (Amended)

Provide fire alarm system when two or more stories above level of exit discharge or 50 or more occupants above or below level of exit discharge; 300 or more occupants total. Initiate by manual means or approved automatic fire detection or sprinkler system.

Provide automatic extinguishing system in hazardous locations.

In high hazard industrial occupancies, provide automatic extinguishing systems or other protection appropriate to the particular hazard.

Provide fire a l m system except if total capacity of building is less than 100 persons and less than 25 persons are above or below level of exit discharge. Initiate fire alarm by either manual or automatic means.

Provide fire alarm system except storage occupancies with low hazard contents or maximum 100,000 square feet or automatic extinguishment protection provided. Initiate by either manual or automatic means.

Provide fire alarm system in parking garages more than 100,000 square feet in aggregate floor area except open parking structures and garages with automatic sprinkler system throughout. Initiate by either manual or automatic means.

Provide fire alarm system in day-care occupancies housed in more than one room. Fire alarm to be initiated by manual means and by operation of required smoke detectors, except single-station, and required sprinkler systems.

Provide smoke detection system in each story and in the corridors of all floors occupied by day-care occupancy if housed in more than one room, with exceptions.

5-96 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 557: NEMA GUIDE CODE Fire Alarm & Detection System

DAY CARE ícontinuedl

30-3.5.1 (Added)

Protect with,full automatic sprinkler protection buildings containing new day care centers above or below the level(s) of exit discharge.

30-6.3.4 (Am ended)

In day-care homes, smoke detectors are required to be installed in all rooms used for sleeping and in any corridors serving a day-care home. Bartery detectors rather than house electric service-powered detectors are accepted if approved by authority having jurisdiction.

SPECIAL STRUCTURES AND HIGHRISE BUILDINGS

3 -2 Apply provisions to all buildings more than 75 feet in height measured from the lowest level of fire department vehicle access to the floor of the highest occupiable story.

32-7.3.1 Provide approved automatic sprinkler system in all areas and floor levels traversed in traveling to the exit discharge throughout windowless and underground structures with an occupant load of 50 or more. Exception: Existing structures with an occupant load of 100 or less.

32-8.2.1 & 32-8.3.1

In high-rise buildings, provide approved, supervised automatic sprinkler system and a fire alarm system with an approved emergency voice/alam communication system throughout.

5-2.1.8 Provide smoke detector to activate automatic self-closing devices on egress doors.

No number As protection from hazard in most occupancies, provide automatic extinguishing system in hazardous areas, including but not limited to areas for general storage, boiler or furnace rooms, fuel storage, and janitor closets.

5-2.3.10.1 & .2 Provide smoke detectors to activate both mechanical ventilation and pressurized stair enclosure systems.

5-97 Montgomery County, MD

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 558: NEMA GUIDE CODE Fire Alarm & Detection System

ClTY OF NEW ORLEANS, LOUISIANA Administrative Requirements

Code 1997 SBC Code

Code 1994 SFPC

Amendments

C. Curtis Mann Chief Building Official (Inspections) or Bhola Dhume (Plan Review & Zoning)

Permits City Hall, Room 7E05 1300 Perdido Street

Department of Safety and

New Orleans, LA 701 12 (504) 565-8228

~

Promulgation

Mark Jee Chief of Fire Prevention or Elbert Thomas Plan Examiner New Orleans Department of Fire Fire Prevention Division 3 17 Decatur Street New Orleans, LA 70130 (504) 565-7805

Enforcement

Summary of Amendments

Comments

In Section 903.9 of the Building Code, the city allows installation of smoke detectors in lieu of required sprinkler protection in electrical closets, rooms and vaults, telephone exchange rooms, elevator equipment rooms, and similar locations where water would damage electrical equipment.

Fire Code amendments do not affect fire protection requirements. See Chapter 3 for summary of Standard Building and Fire Codes. '

Building I Fire Prevention

City amendments (City amendments

Keith Johnson Acting Director Department of Safety and Permits City Hall, Room 7E07 1300 Perdido Street New Orleans, LA 70 1 12 (504) 565-6 11 1

Mark Jee Chief of Fire Prevention New Orleans Department of Fire Fire Prevention Division 3 17 Decaîur Street INew Orleans, LA 70130

Life Safety Code

1997 NFPA 101

No amendments

Jerry Jones Chief Architect or Henry Reed Architect Supervisor Office of the State Fire Marshal 5 1 SO Florida Boulevard Baton Rouge, LA 70806 (504) 925-4920 Jerry Jones Chief Architect or Henry Reed Architect Supervisor Office of the State Fire Marshal 5 150 Florida Boulevard Baton Rouge, LA 70806 (504) 925-4920

5-98 New Orleans, LA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 559: NEMA GUIDE CODE Fire Alarm & Detection System

Ci" OF NEW YORK,NEW YORK Administrative Requirements

Code

Amendments

Promulgation

Building Fire Prevention Code Code

New York City Building Code

City-written City-written

Richard Visconti, RA

New York City Building Code

Gerard A. Barbara

Enforcement

(212) 312-8120

Deputy Commissioner of Technical Affairs Department of Buildings 60 Hudson Street, 14th Floor New York, NY 10013 (212) 312-8120

Richard Visconti, RA Deputy Commissioner of Technical Affairs Department of Buildings 60 Hudson Street, 14th Floor New York, NY 10013

Chief of Fue Prevention Fire Prevention Bureau 9 Metro Tech Center Brooklyn, N Y 11201-3857 (718) 999-2387 or 2386 or Richard Visconti, RA Deputy Commissioner of Technical Affairs Department of Buildings 60 Hudson Street, 14th Floor New York, NY 10013

Gerard A. Barbara Chief of Fire Prevention Fire Prevention Bureau 9 Metro Tech Center Brooklyn, NY 11201-3857 (718) 999-2387 or 2386 or Richard Visconti, RA IDeputy Commissioner of Technical Affairs Department of Buildings ,60 Hudson Street, 14th Floor New York, NY 10013

(212) 312-8120

Comments (212) 312-8120

Referenced standards are promulgated by Department of Buildings and ratified by Board of Standards and

Life Safety Code

None

Amendments

Appeals.

for a summary of the city's fire protection requirements. Amendments

5-99 New York, NY

Appeals.

for a summary of the city's fire protection requirements.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 560: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF NEW YORK, NEW YORK Use Group Classifications

GROUP A - HIGH HAZARDS

Buildings and spaces that store, manufacture, or process potentially explosive products or materials, or highly combustible or highly flammable products or materials likely to bum with extreme rapidity. Include paint shops and storerooms; industrial smoke houses; grain elevators; tanneries with enameling or japanning; distilleries; sugar, starch, cereal, feed, flour, and grist milis; and any space containing gas distribution piping at pressure levels above 15 psig.

GROUP B - STORAGE

Buildings used primarily for storing goods. Sub-classify as follows:

B-1 - Buildings and spaces used for storage of any flammable or combustible materials likely to develop and propagate fire with moderate rapidity. Include warehouses, storerooms, freight depots, stables, coal pockets, and Group 1 public garages.

B-2 - Buildings and spaces used for storage of noncombustible materials that do not ordinarily bum rapidly. Include warehouses, storerooms, private garages, green houses, and Group 2 public garages.

GROUP C - MERCANTILE

Buildings and spaces used for display and sale of goods accessible to public inspection. Include retail stores, shops, sales rooms, and markets.

GROUP D - INDUSTRIAL

Buildings and spaces used for fabricating, assembling, manufacturing, or processing products, materials, or energy. Sub-classify as follows:

D-1 - Buildings and spaces where fabrication, assembly, manufacturing, or processing represents moderate fire hazard. Include baking plants, breweries, automotive repair shops, foundries, heliports, and scenery shops.

5-100 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 561: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP D - INDUSTRIAL ícontinuedj

D-2 - Buildings and spaces where fabrication, assembly, manufacturing, or processing represents low fire hazard. Include mechanical and electrical equipment rooms, power plants and boilers and furnace rooms except those with gas piping at above 15 psig, commercial laundries, vocational training shops, laboratories, and nonresidential kitchens.

GROUP E - BUSINESS

Buildings and spaces for business transactions, providing professional services, and performing other commercial services that might incidentally involve storage of limited stock of goods, or pursuing public or civic services. Include office buildings, banks, civic administration buildings, radio and television stations, telephone exchanges, barber and beauty shops, automatic service stations, neighborhood family care centers, medical offices or group medical centers.

GROUP F - ASSEMBLY

Buildings and spaces, other than dwelling units, designed for religious, recreational, political, or social use, consumption of food or drink or similar group activities or when occupied by 75 or more people for educational purposes. Sub-classify as follows:

F-1 - Buildings and spaces, which during the major period of occupancy, the persons assembled comprise a seated or otherwise passive audience. Further subdivided as: F-la for buildings in which scenery and scenic elements used such as theaters, playhouses, and opera houses; and F-lb for buildings in which scenery and scenic elements not used such as churches, lecture halls, court rooms, convention halls, sports arenas, planetariums, and motion picture theaters.

F-2 - Outdoors structures and spaces such as grandstands, bleachers, stadiums, drive-in theaters, amusement attractions and devices, bandstands, and skating rinks.

F-3 - Buildings and spaces where those assembled are physically active without common center of attention such as exhibition halls, galleries, gymnasiums, museums, passenger terminals, bowling alleys, billiard parlors, and skating rinks.

F-Q - Buildings and spaces of assembly for dancing, eating, drinking, or entertainment or any combination thereof. Include restaurants, nightclubs, cabarets, dance halls, ballrooms, banquet rooms, cafeterias, snack bars, taverns, and coffee houses.

5-101 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 562: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP G - EDUCATIONAL

Buildings, sections, and spaces thereof occupied for instruction or other educational purposes. Include schools, academies, universities, and libraries.

GROUP H - INSTITUTIONAL

Buildings and spaces that house physically limited persons for their care or treatment, persons detained for penal or correctional purposes, or other inmates with restricted liberty. Sub-classify as follows:

H-1 - Buildings and spaces for detention of persons under restraint such as jails, prisons, reformatories, and mental institutions.

H-2 - Buildings and spaces used for treating or caring for persons with physical limitations caused by health or age. Include hospitals, sanitariums, clinics, nursing homes, orphanages, homes for the aged, and day nurseries.

GROW J - RESDENTIAL

Buildings and spaces that serve as dwelling places for families or households, or that provide sleeping accommodations for individuals with or without dining facilities. Sub-classify as follows:

J-1 - Buildings and spaces primarily used for shelter and sleeping accommodations on day-to-day or week-to-week basis. Include hotels, motels, lodging houses, and rooming houses.

5-2 - Buildings with three or more dwelling units primarily occupied for shelter and sleeping accommodations of individuals on month-to-month or longer-term basis. Include apartment houses, apartment hotels, and school dormitory buildings.

5-3 - Buildings occupied as one- and two-family dwellings, rectories, and convents.

GROUP K - MISCELLANEOUS

Structures of temporary character such as sheds, fences, and signs.

5-102 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 563: NEMA GUIDE CODE Fire Alarm & Detection System

CITYOFNEWYORK,NEWYORK 1993 Building and Fire Codes Fire AlardDetection Systems

~

Group B - Storage B-1 - Moderate Hazard

B-2- LOWHZX~

Group C - Mercantile

Occupancy Type

Group A - High Hazard

Group D- Industrial D-1 - Moderate Hazard I D-2- L o w H a z ~ d

Group E- Business Group E- Business Il G r o F F - Assembly F-1 a - Theaters F-1 b - Churches F-2 - Outdoor Assembly F-3 - Museums F-4 - Restaurants

Group G - Education

Group H- Institutional H-1 - Restrained H-2 - Incapacitated

Group J - Residential J-1 - Hotels 5-2 - Apartments

5-3 - 1 and 2 Family

Automatic Fire Sprinkler Systems

Required

> 1,000 sq. ft. or > 75 ft. high > 5,000 sq. ft. or > 75 ft. high z 75 fi. or > 7,500 sq. ft. floor area

> 75 ft. or > 7,500 sq. fi.

> 75 ft.

> 100 ft.

> 75 fi. > 75 ft. > 75 fi. > 75 ft.

> 75 ft.

Required

Fire Alarm Systems

> 75 fi. or > 20,000 sq. ft .

> 70 fi.

Stage areas

Required

Required

Required Required

> 75 ft. > 15 rooms or occupants

Automatic- Detection Systems

Required Required

Rewired

5-103 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 564: NEMA GUIDE CODE Fire Alarm & Detection System

cJTyOFNEWYORK,NEWYORK 1993 Building and Fire Codes Requirements and Exceptions

GROUP A - HIGH HAZARD

Section 27-404 (Building Code)

Provide automatic sprinklers in all buildings and spaces classified as Group A.

GROUP B - STORAGE

Section 27-455 (Building Code)

Provide automatic sprinkler protection and smoke detection or thermostatic alarm with central office connection in public garages (Group B-1 and B-2) except garages in existence prior to 1968.

Section 27-954 (Building Code)

Provide automatic sprinkler protection in buildings classified as Group B1 more than 1,000 square feet floor area or 75 feet or more high, and spaces classified as Group B-1 more than 500 square feet floor area, Group B-2 more than 5,000 square feet in floor area or 75 feet or more high.

GROUP C - MERCANTILE

Section 27-521.13 (Building Code)

Provide smoke detectors at ceiling and adjacent to return air intakes for malls.

Section 27-954 (Building Code)

Provide automatic sprinkler protection in Group C 75 feet or more high, 7,500 square feet or more floor area, or with unenclosed stair or escalator between any two floors.

Section 27-968 (Building Code)

Provide closed circuit electrically supervised fire alarm signal system in department stores or retail sales establishments with publicly accessible floors above street level or 20,000 square feet gross area or more and when more than 75 feet high.

GROUP D -INDUSTRIAL

Section 27-430 (Building Code) Dl).

Provide automatic sprinklers in moderate hazard dry cleaning establishments (Group

5-104 New York. NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 565: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP D - INDUSTRIAL (continued)

Section 27437 (Building Code) Dl).

Provide fire foam extinguishing equipment and fue alarm facilities in heliports (Group

Section 27-954 (Building Code)

Provide automatic sprinkler protection in Group D-1 buildings 75 feet or more high or more than 7,500 square feet except heliports, and Group D-2 75 feet or more high.

GROUP E - BUSINESS

Section 27-954 (Building Code)

Provide automatic sprinkler protection in Group E 100 feet or more in height with air conditioning and/or mechanical ventilation systems serving floor other than the one where located.

Section 27-968 (Building Code)

Provide closed circuit electrically supervised fue alarm signal system in Group E 70 feet or more high, having occupant load more than 500, or having occupant load of more than 1 O0 persons above or below street level.

GROUP F - ASSEMBLY

Section 27-954 (Building Code)

Provide automatic sprinkler protection in dressing rooms and property rooms except for Group F-lb not providing live entertainment and in Groups F-1, F-3, and F-4 more than 75 feet high.

Section 27-968 (Building Code)

Provide closed circuit electrically supervised fire alarm signal system in stages, dressing rooms, and property rooms used in conjunction with places of assembly and in all cabarets.

GROUP G - EDUCATION

Section 27-954 (Building Code)

Provide automatic sprinkler protection in Group G more than 75 feet high.

Section 27-968 (Building Code)

Provide closed circuit electrically supervised fire alarm signal system in all public schools, and private schools and university buildings more than one story.

5-105 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 566: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP J- RESIDENTIAL,

Section 27-954 (Building Code)

Section 27-968 (Building Code)

Section 27-979 (Building Code)

Provide automatic sprinkler protection in Group J-1 , places of assembly located within Group J-1 and existing Group J-1 except residential hotels.

Provide closed circuit electrically supervised fire alarm signal system in hotels, motels, lodging houses, dormitories, and single room occupancies with more than 15 sleeping rooms or accommodating more than 15 lodgers above first or ground floor and health clubs or bath houses with more than 15 sleeping accommodations on the premises and Group J-1 more than 75 feet high.

Provide smoke detecting devices receiving their power from building wiring in ail Group J occupancies except in Groups J-1 and J-2, which contain optional wet sprinkler systems.

5-106 New York, NY

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 567: NEMA GUIDE CODE Fire Alarm & Detection System

ORANGE COUNTY,FLORIDA Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Building Code

1997 SBC

County Amendments

Chris Sanidas Building Official Orange County Building Department 201 South Rosalind Ave. P. O. Box 2607 Orlando, FL 32802

Chris Sanidas (407) 836-5550

Fire Prevention Code

1988 Standard Fire Prevention Code with 1989 and 1990 supplements No amendments

Dan Kucik Fire Marshal Drange County Fire Rescue 6590 Amory Court Winterpark, FL 32792 (407) 836-9080

Summary of Amendments

Dan Kucik Fire Marshal Orange County Fire Rescue 6590 Amory Court Winterpark, FL 32792 (407) 836-9080

The County adds all buildings five stories or more and all buildings over 50 feet in height to those occupancies requiring approved automatic sprinkler systems as listed in Section 903.5 of the Standard Building Code. See Chapter 3 for summary of Standard Building Code provisions.

Life Safety Code

1994NFPA 101

No amendments

Dan Kucik Fire Marshal Drange County Fire Rescue 6590 Amoy Court Winterpark, FL 32792 (407) 836-9080

Dan Kucik Fire Marshal Orange County Fire Rescue 6590 Amory Court Winterpark, FL 32792 (407) 836-9080

5-107 Orange County, FL

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 568: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF PHILADELPHIA, PENNSYLVANIA Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

1996 NBC

City Amendments

David L. Wismer Director, Planning & Code Development Department of Licenses and Inspections Planning and Code Development Unit Municipal Services Bldg. Suite 1180 1401 J. F. Kennedy Blvd. Philadelphia, PA 19102-1687

Michael Fink Director, Construction Services Department of Licenses and Inspections Planning and Code Development Unit Municipal Services Bldg. Suite 1180 1401 J. F. Kennedy Blvd. Philadelphia, PA 19102-1687 (215) 686-1437 or 1440

(215) 686-2549

Fire Prevention Code

1993 NFPC

City Amendments

David L. Wismer Director, Planning & Code Development Department of Licenses and Inspections Planning and Code Development Unit Municipal Services Bldg. Suite 1 180 1401 J. F. Kennedy Blvd. Philadelphia, PA 19102-1687

Kevin Daly Chief, Commercial and Industrial Fire Unit Department of Licenses and Inspections Planning and Code Development Unit Municipal Services Bldg. Suite 1 180 1401 J. F. Kennedy Blvd. Philadelphia, PA 19102-1687

(215) 686-2549

(215) 68.5-3717

Life Safe@ Cnàe

None

Amendments to the Building Code are mostly administrative and do not affect fire protection requirements. The city amendments to the Fire Code require existing high-rise buildings to be retrofitted with automatic sprinkler systems within a certain time period. The city also requires all Group R-2 occupancies to be provided with automatic fire detection in all common areas. See the following pages for summary of fire protection requirements from the 1996 BOCA National BuildinP Code and 1993 National Fire Prevention Code, as amended by the city.

5-108 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 569: NEMA GUIDE CODE Fire Alarm & Detection System

CTITY OF PHILADELPHIA, P E N ” I A 1996 BOCA Use Group Classifications with City Amendments

GROUP A - ASSEMBLY

Buildings used for assembly with greater than 50 occupants. Sub-classify as follows:

A-1 Theaters - Theaters and other buildings for theatrical or operatic performances and exhibitions with raised stage and fixed seats, proscenium curtain, fixed or portable scenery loft, lights, motion picture booth, mechanical appliances, and other theatrical accessories and equipment.

A-2 Nightclubs, Dance Halls - Buildings and public assembly places including rooms, lobbies, and other spaces connected thereto with common means of egress and entrance without theatrical stage accessories and designed for use as dance hall, night club, or similar.

A-3 Restaurants, Recreation - Buildings with or without auditorium and without theatrical stage other than raised platform where people assemble for amusement, entertainment, or recreation and incidental motion picture, dramatic, or theatrical presentations including art galleries, exhibition halls, museums, lecture halls, libraries, restaurants other than nightclubs, recreation centers, and passenger terminals. Included are classroonis, lecture halls, libraries, auditoriums or siinilarplaces of learning with an occupant load of more than 50.

A 4 Churches -Buildings used as churches and for similar religious purposes.

A-5 Stadiums - Outdoors assembly structures including grandstands, bleachers, coliseums, stadiums, tents, and similar structures.

GROUP B - BUSINESS

Buildings or parts thereof used for business transactions, rendering of professional services, or for other services involving stocks of goods, wares, or merchandise in limited quantities for use incidental to office uses or sample purposes including: data processing, animal hospitals and kennels, automobile showrooms, banks, beauty and barber shops, car washes, civic administration and post offices, laboratories for testingiresearch, telephone exchanges, laundries and dry cleaning and self-service and pick-up/delivery stations, outpatient clinics, radio/TV stations, fire and police stations, florists and nurseries, print shops, and professional services. Included are assembly-type and educational-tjpe uses with a total occupant load of less than 50.

5-109 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 570: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP E - EDUCATIONAL

Buildings or parts thereof used by more than five persons at one time for educational purposes through twelfth grade including schools, academies, and day-care centers providing care for more than six persons over two -and-one-half years of age for less than 24 hours per day.

GROW F - FACTORYENDUSTRIAL

Buildings or parts thereof; including among others, factories, assembling plants, industrial laboratories, and all other industrial and manufacturing uses where occupants engaged in fabricating, assembling, or processing of products or materials. Sub-classify as follows:

F-1 Moderate Hazard - Moderate hazard factory and industrial uses for manufacturing processes including aircraft, automobiles, appliances, boats, and RVs, bakeries, alcoholic beverages, boilers works, canneries, clothing, machinery, dry cleaning using other than flammables, electronics and electric light plants, food processing, film, furniture, tanneries, woodworking, paper mills, plastic, publishing, printing, refuse incinerators, shoes, soap, sugar, tobacco, upholstery, textile mills, and laundries.

F-2 Low Hazard - Factory and industrial uses involving fabrication or manufacturing of noncombustible materials which during finishing, packing, or processing, do not involve significant fire hazard including nonalcoholic beverages, brick, masonry, ceramic, glass, and gypsum, foundries, ice, metal fabrication and assembly, and water pumping plants.

GROUPH -HAZARDOUS

Buildings or parts thereof used for manufacturing, processing, generation, or storage of corrosive, highly toxic, highly combustible, flammable, or explosive materials including loose combustible fibers, dust, and unstable materials that constitute high fire or explosion hazard. Sub-classify as follows:

H-1 - Buildings and structures or parts thereof containing materials, which present a detonation hazard.

H-2 - Buildings and structures or parts thereof, which contain materials presenting a deflagration hazard or a hazard from accelerated burning.

H-3 - Buildings and structures or parts thereof which contain materials that readily support combustion or present a physical hazard.

H-4 -Buildings and structures or parts thereof containing materials that are a health hazard.

5-1 10 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 571: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL

Buildings or parts thereof where people suffering from physical limitations due to health or age harbored for medical or other care or treatment, where people detained for penal or correction purposes, or where liberty of inmates is restricted. Sub-classify as follows:

1-1 Supervised - Facilities for children, aged persons, mentally impaired and convalescents including group homes, mentally retarded care facilities, nursing homes, and orphanages, housing six or more individuals who because of age, mental disability, or other reasons, must live in supervised environment but who are physically capable of responding to emergency situation without personal assistance.

1-2 Incapacitated - Use for persons with physical limitations including hospitals, day nurseries, sanitariums, infirmaries, orphanages, and homes for aged and infirm. Included are childcare facilities accommodating more thansix children two-

and one-half years of age or less for any length of time.

1-3 Restrained - Buildings or parts thereof including prisons, jails, reformatories, insane asylums, and similar uses, inhabited by occupants under some restraint.

GROUP M - MERCANTILE

Buildings or parts thereof used for display and sales purposes and accessible to public including retail stores, motor fuel service stations, shops, salesrooms, and markets.

GROUP R - RESIDENTIAL

Buildings or parts thereof where families or households live or where sleeping accommodations provided for individuals with or without dining facilities. Sub-classify as follows:

R-1 HoteldMotels - Hotels, motels, boarding houses, and similar buildings arranged for shelter and sleeping accommodations for more than five occupants primarily transient in nature who use facilities for less than 30 days.

R-2 Multifamily - Dwellings with more than two dwelling units including boarding houses and similar buildings arranged for shelter and sleeping accommodations for occupants primarily not transient in nature. This also includes dormitories accommodating more than five persons older than 2-1/2 years of age.

R-3 One and Two Family and Multiple Single-family - Buildings arranged for use as one- or two-family dwelling units with maximum five lodgers or boarders per family and multiple single-family dwellings where each unit has its own means of egress. This also includes a childcare facility accommodating six or less children of any age.

5-1 11 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 572: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE Buildings or parts thereof including warehouses, storehouses, and freight depots used primarily for storage of goods, wares, or merchandise. Sub-classify as follows:

S-1 Moderate Hazard - Storage buildings for contents likely to burn with moderate rapidity, but not producing poisonous gases, fumes, or explosives.

S-2 Low Hazard - Storage buildings for noncombustible materials and low hazard wares that do not ordinarily bum rapidly such as products on wood pallets or in paper cartons without significant amounts of combustible wrappings but with negligible amount of plastic trim such as knobs, handles, or film wrapping.

GROUP U - UTILITY AND MISCELLANEOUS

Accessory buildings and miscellaneous structures not classified in any specific use group per Building Code requirements commensurate with fire and life hazard incidental to use. This group includes structures accessory to a residential occupancy.

5-1 12 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 573: NEMA GUIDE CODE Fire Alarm & Detection System

C ï ï Y OF PHILADELPHIA, PENTVSYLVANIA 1996 National Codes (BOCA) with City Amendments

Fire AlardDetection Systems

A-1 - Theaters A-2 - Night Clubs A-3 - Restaurants A 4 - Churches

Group B - Business

Group E - Educational

Group F - Factory F-1 - Moderate Hazard

Group M - Mercantile fi Group R - Residential R-1 - HotelMotels R-2 - MUltif&dy

Group S - Storage S-1 - Moderate Hazard

Atriums

Automatic Fire Sprinkler Systems

> 12,000 sq. ft. > 5,000 sq. ft. > 12,000 sq. ft. > 12,000 sq. ft.

> 20,000 sq. ft.

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total Required

Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required Required

> 3 stories or > 12,000 sq. ft. or > 24,000 sq. ft. total

Required

Required

Fire Alarm Systems

Required > 2 stories

Required

Required

Required

Required > 3 stories

> 2 stories

Automatic Detection Systems

Required

Required

Required Required

> 30 ft. ceiling ~ ~~

Required

5-1 13 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 574: NEMA GUIDE CODE Fire Alarm & Detection System

Hazardous Production Materials I Required I Required I Required

Public Garages > 3 stories or > 12,000 sq. ft. or

Special Amusement Building > 24,000 sq. fi. total Required Required

I I I

Underground Structures

5-1 14 Philadelphia, PA

Required Required Required

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 575: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF PHILADELPHIA, PENNSYLVANIA 1996 National Codes (BOCA) with City Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2 (Building Code)

Provide automatic fire suppression system throughout Groups A-1, A-3, and A-4 occupancies that exceed 12,000 square feet as follows: entire story or floor level where Groups A-1, A-3, or A-4 occupancies are located; all stories and floors below Groups A-1, A-3, or A-4; and all stories and floor levels between Groups A-1, A-3, or A-4 and the level of exit discharge. Exception: Groups A-1 or A-3 auditoriums, Group A-4 naves and chancels, or Group A-3 participant sport areas if main floor of each area is at the level of exit discharge of the main entrance. These requirements also apply to Group A-2 occupancies which are more than 5,000 square feet in area or located either above or below the level of exit discharge of exits serving the occupancy.

Section 918.4.1 (Building Code) churches.

Provide fire alarm system in Group A-4 occupancies except in sanctuary and nave areas of

GROUP B - BUSINESS

Section 918.4.2 (Building Code)

Provide fire alarm system in Group B occupancies, which are two or more stones above or below level of exit discharge.

GROUP E - EDUCATIONAL

Section 904.4 (Building Code)

Provide automatic fire suppression system throughout Group E occupancies, unless floor area is less than 20,000 square feet

Section 918.4.1 (Building Code)

Provide fire alarm system in all Group E occupancies.

GROUP F - FACTORY/INDUSTRIAL

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group F-1 buildings more than 12,000 square feet in area, or more than 24,000 square feet total area on all floors, or more than three stories above grade.

5-1 15 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 576: NEMA GUIDE CODE Fire Alarm & Detection System

Sections 904.5 and 417.1 Provide automatic fire suppression system throughout all Group H occupancies or any other (Building Code) building or structure occupied for the manufacturing, processing, dispensing, use or storage of

hazardous materials. Exception: Magazines used for the storage of Group H-1 materials constructed and located per NFPA 495 and the fire prevention code.

Section 503.4 (Fire Code)

Provide automatic fire suppression system throughout all existing high-hazard occupancies used for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic. Also provide automatic fire suppression system in vaults located within buildings for the storage of raw pyroxylin.

Section 419.3 (Building Code)

Provide automatic fire suppression system in all spray, dip and immersing spaces and storage rooms of buildings of portions thereof used for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures.

Section 2806.4 (Building Code)

Provide approved automatic fire suppression system in drying rooms designed for high- hazard materials and processes.

Section 417.5.3 (Building Code)

Provide automatic fire detection system per NFPA 72 throughout Group H Occupancies where required by fire prevention code. Provide detection system in areas where high-hazard materials are used and stored.

Section 918.4.3 (Building Code)

Provide a fire alarm system in Groups H-2, H-3, and H-4 occupancies.

GROUP I - INSTITUTIONAL

Section 904.6 (Building Code)

Provide automatic fire suppression system throughout all Group I Occupancies. Exception: Group 1-2 child-care facilities accommodating 100 children or less located at level of exit discharge with an exit door in each child-care room directly to the exterior.

Section 918.4.4 (Building Code)

Provide fire alarm systems in all Group I Buildings.

5-1 16 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 577: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

Section 919.4 (Building Code)

Provide automatic fire detection system in all Groups 1-1 and 1-2 occupancies except Group 1-2, which are fully sprinkled throughout. In Group 1-3, provide automatic fire detection system and smoke detectors throughout all resident housing areas. Smoke detectors are not required in sleeping rooms with not more than four occupants.

Section 920.3.3 (Building Code)

Provide single- or multiple-station smoke detectors in all sleeping areas in Group 1-1 occupancies, except where the building is equipped throughout with an automatic detection system. Smoke detectors are required to have battery -power backup.

Section 409.5.1 (Building Code)

In Group 1-2, provide automatic fire detection system in corridors and spaces open to the corridors in nursing homes and detoxification facilities. Exception 1 : Not required if patient sleeping rooms have smoke detectors permanently connected to the building’s power supply and have a visible display on the corridor side of each patient room and an audible and visual alarm at the nursing station attending the rooms. Exceptions 2: Not required if patient rooms equipped with automatic door-closing devices with integral smoke detectors on the room side that perform the required alerting function.

GROUP M - MERCANTILE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout Group M occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade. Exception: Public garages.

GROW R - RESIDENTHL

Sections 904.8 and 906.2.1 (Building Code)

Provide automatic fire suppression system throughout all Group R-1 occupancies except guest rooms if not more than three stories above the lowest level of exit discharge and each guest room has at least one door of direct access to exit.

Section 904.9 (Building Code)

Provide automatic fire suppression system throughout all Group R-2 occupancies except buildings two stories or less, including basements, and with 12 or less dwelling units and each dwelling unit has a least one door of direct access to exit.

5-1 17 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 578: NEMA GUIDE CODE Fire Alarm & Detection System

GROW R - RESIDENTIAL (continued)

Section 918.4.5 (Building Code)

Provide fire alarm system in all Group R-1 occupancies.

Section 918.4.6 (Building Code)

Provide fire alarm system in Group R-2 occupancies where dwelling unit is located three or more stories above lowest level of exit discharge or more than one story below the highest level of exit discharge.

Section 919.4.4 (Building Code)

Provide automatic fire detection system in all Group R-1 occupancies except buildings without interior corridors and where all guest rooms have a direct exterior exit access.

Section 920.3.1 (Building Code)

Provide single- or multiple-station smoke detectors in Groups R-1, R-2, and R-3 occupancies. In buildings equipped throughout with an automatic sprinkler system, smoke detectors are not required in bedrooms that are equipped with residential sprinklers. Smoke detectors are required to have battery -power backup.

GROUP S - STORAGE

Section 904.7 (Building Code)

Provide automatic fire suppression system throughout in Group S-1 occupancies which are more than 12,000 square feet in area, more than 24,000 square feet in total area on all floors, or more than three stories above grade.

AIRPORT TRAFFIC CONTROL TOWERS

Section 414.4 (Building Code)

Provide automatic fire detection systems in all such buildings.

ATRIUMS

Section 404.2 (Building Code)

Section 404.4 (Building Code)

Provide automatic sprinkler system in atrium and all stories and floors connected to the atrium.

Provide a smoke control system in all atriums that connect more than two stories.

5-1 18 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 579: NEMA GUIDE CODE Fire Alarm & Detection System

ATRIUMS (continued)

Section 404.6 (Building Code)

Section 922.4.2 (Building Code)

COVERED MALLS

Section 402.10 and 402.14.2 (Building Code)

Section 402.7.1 (Building Code)

Provide a fire alarm system in all occupancies with an atrium that connects more than two stories. In Groups A, E, or M occupancies: provide a voice/alarm signaling system.

In a smoke control area with ceiling height over 30 feet, provide smoke detectors to detect smoke above highest floor open to an atrium or at highest point of another smoke control space.

Provide automatic sprinkler system throughout covered mall building and all connected buildings, including kiosks and similar structures that are covered and located within the mall.

In anchor store, provide smoke control system to be activated by smoke detectors installed in return air portion of heating and cooling system, automatic sprinkler system, and manual controls provided in an approved location.

HAZARDOUS PRODUCIION MATERZALS FACILITES

Section 416.4 (Building Code)

Provide automatic sprinkler system throughout HPM facilities.

Section 416.9.2 (Building Code) station.

Install smoke detectors in re-circulating air stream to initiate a signal at the emergency control

Section 416.14.5 (Building Code)

Provide local fire alarm system station or emergency telephone system outside each interior egress door from HPM cutoff rooms.

Section 403.1 (Building Code)

Apply to all buildings having floors used for human occupancy located more than 75 feet above lowest level of fire department vehicle access. Exceptions: Airport traffic control towers; open parking structures; Groups A-5, H-1, H-2 or H-3; and low-hazard special occupancies.

I 5- 1 19 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 580: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHRISE BUILDINGS ícontinueà)

Section 403.2 (Building Code)

Provide automatic sprinkler system throughout high-rise buildings. Exceptions: Open parking structures and telecommunications equipment buildings.

Section 403.4 (Building Code)

Provide smoke detectors in rooms for mechanical equipment, electrical, transformer, telephone equipment, elevator machine. Install so that actuation of detector sounds alarm at a constantly supervised location. Provide voice alarm and comnunication system.

PUBLIC GARAGES

Section 408.3.1 (Building Code)

Provide automatic sprinkler system in public garages where any area exceeds 12,000 square feet, or the total combined area of all floors exceeds 24,000 square feet, or more than three stories above grade, or if located beneath other use groups. Provide automatic sprinkler system in the fuel-dispensing area of a public garage.

SPECIAL AMüSEMENT BUILDINGS

Section 413.3 (Building Code)

Provide automatic fire detection system in all special amusement buildings. An approved alternative type of automatic detector may be installed where ambient conditions will cause a smoke detector to activate.

Section 413.4 (Building Code)

Provide automtic sprinkler system throughout special amusement buildings. Excepted if total floor area of a temporary special amusement building is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet.

STAGES AND PLATFORMS

Section 412.6 (Building Code)

Provide automatic sprinkler system on stages and enclosed platforms installed under the roof and gridiron, in tie and fly galleries, and in all places beyond the proscenium wall of the stage; over and within enclosed platforms in excess of 500 square feet in area; and in dressing rooms, lounges, workshops and storerooms accessory to such stages or enclosed platforms. See Section 412.6 for exceptions to this requirement.

5-120 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 581: NEMA GUIDE CODE Fire Alarm & Detection System

STAGES AND PLATFORMS (continued)

Section 411.7 and 412.8 (Building Code)

Provide automatic sprinkler system in all buildings or portions used as sound stages for motion picture or television production and over 1,000 square feet.

U”D STRUCTURES

Section 405.1 (Building Code)

Applies to all structures having a floor level used for human occupancy more than 30 feet below, or more than one story below, the lowest level of exit discharge serving that floor level.

Section 405.3 (Building Code)

Provide an automatic sprinkler system throughout the highest level of exit discharge serving the underground portions of the structure and all levels below.

Section 405.5.1 (Building Code)

Provide smoke detection in rooms for mechanical equipment, electrical transformer, telephone equipment, and elevator machinery. Install so that actuation of detector sounds an alarm at a constantly attended location.

Section 405.5.2 (Building Code)

Provide smoke exhaust system to be activated by the automatic sprinkler system, smoke detectors, or manual controls provided for fire department use.

Section 405.6 (Building Code)

Provide a fire alarm system, which includes a voice/alarm signaling system, where the lowest level of a structure is more than 60 feet below the lowest level of exit discharge.

Section 1020.3 (Building Code)

When an exit discharges into an interior lobby located at the level of exit discharge, provide automatic sprinkler system throughout lobby.

Section 2807.6 (Building Code)

Provide approved automatic fire suppression system at the top and at alternate floor levels in a waste or linen chute and in the termination and incinerator rooms. System not required if incinerator burns only Type 4 waste.

I

Section 2808.4 (Building Code)

Provide automatic fire suppression system in vaults for combustible refuse, which are more than 360 cubic feet in volume.

5-121 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 582: NEMA GUIDE CODE Fire Alarm & Detection System

OTHER GENERAL REûuIREMENTs ícontinued)

Section 904.10 (Building Code)

In buildings with windowless story, provide an automatic fire suppression system throughout every story or basement where there is not provided at least one of the type openings outlined by Section 904.10. Exception: Group R-3 occupancies.

Section 918.5 (Building Code)

Where required, provide manual fire alarm boxes not more than five feet from the entrance to each exit. Exception: Manual fire alarm boxes are not required in Group B occupancies where the highest occupied floor is 75 feet or less above the lowest level of fire department vehicle access or the building is protected throughout with automatic sprinkler system.

EXISTING BUILDINGS

Section F-503.2 wire Cnde)

(Added)

Provide,fire alarm systems in existing buildings with Group R-2 occupancies and provide in nther exioting building9 ao dpoignntpd by Rmilding cod^

Section F-503.3 (Fire Code) (Added)

Provide automatic fire detection throughout all existing Groups I-I and I-2, except hospital patient rooms and buildings sprinkled throughout.

Provide automatic fire detection in all common areas, corridors, and basements (except in buildings sprinkled throughout) of all existing Groups R-I and R-2. In Group R-2 where audibility of existingfire alarm indicating devices does not meet the required audibility within the dwelling units, the installation of supplemental sounding devices within the dwelling units will be acceptable if installed per Fire Code.

AutomaticJire detection may be smoke detectors, except an approved alternative type of detector may be installed in spaces such as boiler rooms where, products of combustion may cause actuation of smoke detector.

Section F-503.3.2.2 (Fire Code) (Am ended)

Provide single and multiple-station smoke detectors in each dwelling unit in immediate vicinity of bedrooms and on each story, in each bedroom of existing Group R-2 high-rise buildings (except ifsprinkled throughout), in each guest room of existing Group R-1, and in each boarding unit, dormitory and communal sleeping area. Install per NFPA 72 and connect to primary ACpower source of building OY can be a wireless system. Electrical interconnection required in Group R-2 high-rise buildings.

In existing Group R-3, provide smoke detectors in each unit and on each level per NPFA 72 and Building Code. Battery powered smoke detectors are permitted in Group R-3 and interconnection is not required.

5-122 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 583: NEMA GUIDE CODE Fire Alarm & Detection System

EXISTING BUILDINGS (continued)

Section F-503.4 (Fire Code) (Added)

Provide automatic f ire suppression system installed per NFPA 13 and the Fire and Building Code in basements classi$ed as windowless stories with floor area exceeding 2500 square ,feet and used,for manufacture, sale, or storage (except in G ~ o t p R-3). in commercial kitchen exhaust systems in all buildings, and high-rise buildings.

Section 503.6 (Fire Code)

In existing structures, provide approved smoke or heat detectors in return air ducts or plenums in each re-circulating air system with a capacity of 2,000 cfm or more and serving more than one floor in building exceeding six stories in height. If not part of an approved smoke control system, install so that actuation of the detector automatically stops the fans.

5-123 Philadelphia, PA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 584: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF PHOENIX, ARIZONA Administrative Requirements

Code

I Building I Fire Prevention Code Code

1997 UBC 1997 UFC

Amendments I City amendments City amendments

Promulgation

Summary of Amendments

Enforcement

The city amendments to the 1997 Uniform Building Code adds automatic sprinkler protection requirements for certain industrial shade canopies, weather-protection shade canopies, mercantile shade canopies, and non-residential patio covers. The city does not adopt Appendix Chapter 34 for existing buildings.

See summary of Uniform Codes in Chapter 3.

Comments

Alan Olson Assistant Director/Building Official Development Services Department Building Safety Division 200 West Washington St. Phoenix, AZ 85003

Alan Olson Assistant DirectoríJ3uilding Official Development Services Department Building Safety Division 200 West Washington St. Phoenix, AZ 85003

(602) 262-6901

(602) 262-6901

Barbara Koffron Assistant to the Chief Phoenix Fire Department Urban Services Division 150 S. 12'h Street Phoenix, AZ 85034-2301 (602) 262-6771

~~

Barbara Koffion Assistant to the Chief Phoenix Fire Department Urban Services Division 150 S. 12'h Street Phoenix, AZ 85034-2301 (602) 262-6771

Life Safety Code

None

5-124 Phoenix, AZ

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 585: NEMA GUIDE CODE Fire Alarm & Detection System

Ci" OF PITTSBURGH, PENNSYLVANIA Administrative Requirements

Building Fire Prevention Code Code

Cade 1996 NBC 1996 NFPC

Amendments City amendments City amendments

Promulgation Ronald S. Graziano , Chief Department of Public Safety Bureau of Building Inspection 200 Ross Street Pittsburgh, PA 152 19

Ronald S. Graziano , Chief Department of Public Safety Bureau of Building Inspection 200 Ross Street Pittsburgh, PA 152 19 (412) 255-2176 Pittsburgh, PA 15219

Ronald S. Graziano , Chief Department of Public Safety Bureau of Building Inspection 200 Ross Street Pittsburgh, PA 152 19

Peter J. Micheli, Jr., Chief Bureau of Fire Department of Public Safety Bureau of Fire 100 Grant St., 6'h Floor

(412) 255-2176 (412) 255-2176 Enforcement

(412) 255-2864

Life Safety Cade

None

5-125 Pittsburgh, PA

Comments

Summary of Amendments

Code provisions for high-rise buildings apply to all buildings having floors used for human occupancy located more than six stories or 75 feet above the lowest level of fire department vehicle access. The city revises the threshold for Group E day care facilities to seven or more persons.

See Chapter 3 for summary of 1996 BOCA National Code requirements.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 586: NEMA GUIDE CODE Fire Alarm & Detection System

Cl" OF SAN FRANCISCO, CALIFORNIA Administrative Requirements

Code

Amendments

Promulgation

Enforcement

Comments

Summary of Amendments

Building Code

1997 UBC

State and city amendments

Frank Y. Chiu Director Department of Building Inspection 1660 Mission St., 6'h FI. San Francisco, CA 94103 (415) 558-6131

William Wong Deputy Director, Administration Department of Building Inspection 1660 Mission St. 3Td Fl. San Francisco, CA 941 03 (415) 558-6139

Fire Prevention Code

1997 UFC

State and city amendments

Kevin D. Taylor Fire Marshal San Francisco Fire Dept. Division of Fire Prevention and Investigation Bureau of Fire Prevention 698 Second Street San Francisco, CA 94 107

Kevin D. Taylor Fire Marshal San Francisco Fire Dept. Division of Fire Prevention and Investigation Bureau of Fire Prevention 698 Second Street San Francisco, CA 94107

(415) 558-3300

(415) 558-3300

Life Safety Code

None

City adopts the State of California revisions to the 1997 Uniform Codes. See summary of state codes in Chapter 4.

The city makes several amendments to the model code fire protection provisions as follows:

Section 904.2.3 (Building Code): City requires Group A basements more than 200 square feet in floor area to be provided with automatic sprinkler system.

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code): City requires Group R-1 apartment houses three or more stories or containing six or more dwelling units, hotels and congregate residences three or more stories having an occupant load of 11, and Group R-3 congregate residences having an occupant load of six or more to be equipped with an approved manual and automatic fire alarm system.

Section 403.24 & .25 (Building Code): City requires every existing high-rise building be provided with an approved automatic sprinkler system, except Group R-1 .

5-126 San Francisco, CA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 587: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF SEATTLE, WASHINGTON Administrative Requirements

Building Code

Code 1997 UBC

Fire Prevention Code

1997 UFC

Amendments

Promulgation

City amendments City amendments

Maureen A. Traxler Diane Hansen Code Development Supervisor Fire Prevention Technician Department of Design, Seattle Fire Department Construction and Land Use 220 Third Ave. South 710 Second Avenue, Suite 200 Seattle, WA 98104-2608 Seattle, WA 98 104- 1703 (206) 386- 145 1

Gregory Dean, Fire Marshal Seattle Fire Department 220 Third Ave. South Seattle, WA 98 104-2608 (206) 386-1450

Enforcement

Life Safety Code

None

(206) 233-3892 Thomas Kinsman Principal Engineer Department of Design, Construction and Land Use 710 Second Avenue, Suite 200 Seattle, WA 98104-1703

Comments

Summary of Amendments

5-127 Seattle, WA

(206) 233-7171 I

See the following pages for the city amendments to the 1997 Uniform Codes as they affect the installation of fire aladdetection systems.

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 588: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF SEATTLE, WASHINGTON 1997 ICBO Use Group Classifications with City Amendments

GROUP A - ASSEMBLY

Building or structure for the gathering of 50 or more persons for purposes such as civic, social or religious functions, recreation, education or instruction, food or drink consumption, or awaiting transportation. Amusement buildings are included in this classification. Sub-classify in divisions as follows:

A-1 Assembly building with a stage and an occupant load of 1,000 or more.

A-2 Building or portion thereof; having an assembly room with occupant load less than 1,000 and a stage.

A-2.1 Building or portion thereof with an assembly room with occupant load of 300 or more without a stage, including buildings for educational purposes and other than Groups E or B.

A-3 Building or portion thereof; with an assembly room with occupant load less than 300 without a stage, including buildings for educational purposes and other than Groups E or B.

A 4 Stadiums, reviewing stands, and amusement park structures not included in other Group A Occupancies.

GROUP B - BUSENESS

Building or structure or portion thereof for office, professional or service-type transactions, including storage of records and accounts, and eating and drinking establishments with an occupant load of less than 50.

GROUPE -EDUCATIONAL

Sub-classify in divisions as follows:

El Buildings used for educational purposes through 12th grade by 50 or more persons for more than 12 hours per week or 4 hours per day.

E 2 Buildings used for educational purposes through 12th grade by less than 50 persons for more than 12 hours per week or 4 hours a day.

E3 Da<v-care centers, preschools, and day treatment centers.

GROUP F - FACTORY AND INDUSTRIAL

A building or structure for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repairing or processing operations. Sub-classify in divisions as follows:

5-128 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 589: NEMA GUIDE CODE Fire Alarm & Detection System

F-1 Moderate-hazard factory and industrial occupancies including factory and industrial uses not classified as F-2.

F-2 Low-hazard factory and industrial occupancies including facilities producing noncombustible or non- explosive materials which, during finishing, packing or processing, do not involve a significant fire hazard.

GROW H - HAZARDOUS

Building or structure where manufacturing, processing, generation of storage materials constitute a high fire, explosion or health hazard. Sub-classify in divisions as follows:

H-1 Buildings with quantity of material in excess of building code limitations, which present high explosion hazard, including but not limited to:

Explosives, blasting agents, fireworks, and black powder. Exception: Storage and use of pyrotechnic special effect materials in motion picture, television, theatrical, and group entertainment production when under permit per Fire Code. Maximum time period for storage is 90 days. Manufacturing of Class 1.4G fireworks. Unclassified detonatable organic peroxides.

Class 4 or Class 3 detonatable unstable (reactive) materials. ta Class 4 Oxidizers

8 2 Buildings with quantity of material in excess of building code limitations which present moderate explosion hazard or hazard from accelerated burning, including but not limited to:

Class I organic peroxides. Class 3 non-detonatable unstable (reactive) materials.

Flammable or oxidizing gases. Class I, II, or III-A flammable or combustible liquids used in normally open containers or systems or in closed containers pressurized at more than 15 psi gauge. Exception: aerosols. Class 3 oxidizers.

t> Pyrophoric gases.

+ Class 3 water-reactive materiais.

5-129 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 590: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS (continued)

H-3 Buildings with quantity of materials in excess of building code limitations, which present high fire or physical hazard, including but not limited to:

Class II, III, or IV organic peroxides. LX Class 1 or 2 oxidizers.

Class I, II, or III-A flammable liquids or combustible liquids used or stored in normally closed containers or systems and containers pressurized at 15 psi gauge or less, and aerosols. Class III-B combustible liquids.

tX Pyrophoric liquids or solids. + Class i or 2 water-reactive materiais. Flammable solids in storage.

fi Flammable or oxidizing cryogenic fluids (other than inert). t-3 Class 1 unstable (reactive) gas or Class 2 unstable (reactive) materials.

H-4 Repair garages not classified as Group S-3.

H-5 Aircraft repair hangars and heliports not classified as Group S-5.

H-ó Semiconductor fabrication facilities and comparable research and development areas when facilities in which hazardous production materials (HPM) used and aggregate quantity of materials in excess of building code limitations.

H-7 Occupancies with quantities of materials in excess of building code limitations that are health hazards, including but not limited to: LX Corrosives, except stationary lead-acid battery systems.

Highly toxic materials. 3 Irritants.

Sensitizers. Other health hazards.

GROUP I - INSTITTJTIONAL

Sub-classify in divisions as follows:

1-1.1 Nurseries for full-time care of children under the age of six, hospitals,ps,vchiatric hospitals, nursing homes with non-ambulatory or inobile non-ambulatory patients, and similar buildings, except buildings used only for private residential purposes for family group.

5-130 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 591: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP I - INSTITUTIONAL (continued)

1-1.2 Health-care centers for ambulatory patients receiving outpatient medical care which may render the patient incapable of unassisted self-preservation, each tenant space accommodating more than five such patients, except buildings used only for private residential purposes for family group.

1-2 Nursing homes for ambulatory patients, except buildings used only for private residential purposes for family group.

1-3 Psychiatric hospitals, jails, prisons, reformatories, and buildings where personal liberties of inmates or patients similarly restramed, except buildings used only for private residential purposes for family group.

GROUP M - MERCANTILE

Building or structure or portion thereof for display and sale of merchandise, and involving stocks of goods, wares or merchandise, incidental to such purposes and accessible to the public.

GROUP R - RESIDENTIAL

Sub-classifi in divisions as follows:

R-1 Hotels, apartment houses, congregate residences; each accommodating more than ten persons.

R-2 Classification not used.

R-3 Lodging houses, detached dwellings, and family day care homes.

GROUP S - STORAGE

Building or structure for storage not classified as a hazardous occupancy. Sub-classify in divisions as follows:

S-1 Moderate hazard storage occupancies include buildings or portions thereof used for storage of combustible materials not classified as S-2 or Group H.

S-2 Low-hazard storage occupancies include buildings or portions thereof used for storage of noncombustible materials.

5-131 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 592: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP S - STORAGE (continued)

S-3 Repair garages and parking garages not classified as S 4 .

S 4 Open parking garages.

S-5 Aircraft hangars and helistops.

GROUPU - UTlLlTY

Sub-classify in divisions as follows:

U1 Private garages, carports, sheds, agricultural buildings, and covered boat moorage accessory to a Group R- 3 dwelling unit.

U2 Fences over six feet high, tanks and towers.

GROUP LC

Buildings or structures used for the business ofproviding licensed care to clients regulated by either the Washington Department of Health or the Department of Social and Health Services.

5-132 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 593: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF SEATIZE, WASHINGTON 1997 Uniform Codes (ICBO) with City Amendments

Fire AlardDetection Systems

Automatic Fire Sprinkler Systems

Fire Alarm Systems

Automatic Detection Systems Occupancy Type

Group A - Assembly Amusement Buildin s Group B - Business . Group E - Educational

Required Required Required

Required Required Required

Required

Required Required

> 50 occupants Required

)I Group F- Factory Industrial Required

Group H - Hazardous

Explosives H-1 - Flammables/

H-2 - Moderate

H-3 - HighHazard H-4 - Repair Garages H-6 - Semiconductor Facilities H-7 - Health Hazards

Explosion Hazard

Required

Required Required > 3,000 sq. ft. Required Required

Required

Required Required

Required Required Required

Group I - Institutional 1-1 - Hospitals 1-2 - Nursing Homes 1-3 - Jails

Required Required Required

Required Required Required

> 3 stories > 12,000 sq. ft./floor > 24,000 sq. ft. total

> 3 stories

Group M - Mercantile

Group R - Residential R-1 - Hoteihíultifamily

Group S - Storage

High-rise -New and Existing Construction

B-2 - Offices R-1 - Hotel/Multifamily

_ _ _ _ _ ~

> 3 stories > 3 stories

Required

> 75 ft. > 75 ft.

> 75 ft. > 75 ft.

75 fi. > 75 ft.

Required Required Required

Required Required Aviation Control Towers

5-133 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 594: NEMA GUIDE CODE Fire Alarm & Detection System

CITY OF SEATTLE, WASHINGTON 1997 Uniform Codes (ICBO) with City Amendments

Requirements and Exceptions

GROUP A - ASSEMBLY

Section 904.2.3 (Building Code) and Section 1003.2.3 (Fire Code) (Amended)

Provide automatic sprinkler systems in Group A as follows: ta Rooms and un-separated accessory uses more than 5,000 square feet in total area when used for consumption of alcoholic beverages. ta Basements or basement-like stories more than 1,500 square feet in floor area.

Exhibition and display rooms more than 12,000 square feet ta Enclosed usable space below or over a stairway in Groups A-2,

A-2.1, A-3, and A-4. Multi-theater complexes.

ta Amusement buildings, except if temporary with floor area less than 1,000 square feet and exit travel distance is less than 50 feet from any point. ta All stages more than 1,000 square feet in area and 50 feet in height, dressing rooms, workshops, storerooms, and other accessory spaces adjoining such stages. ta Smoke-protected assembly seating, except press boxes, storage less than i ,000 square feet, or in conjunction with outdoor seating.

Section 303.9 (Building Code)

Provide approved fire alarm system in Groups A-1, A-2, and A-2.1 occupancies installed per Fire Code.

Section 1007.2.2 (Fire Code)

In Groups A-1, A-2, and A-2.1, provide manual fire alarm system. When occupant load is i ,000 or more, fire alarm must immediately activate approved prerecorded announcement using an approved voice communication system.

Section 408 & 904.2.3.6 (Building Code) (Amended) and Sections 1007.2.12.1.2 and 2506.1 (Fire Code) (Added)

In permanent and portable amusement buildings, provide automatic sprinkler system. Also provide smoke detection, and supervised alarm and/or public address systems in amusement buildings. In areas where ambient conditions will cause smoke detector to alarm, an approved alternate type of automatic detector may be substituted.

Provide automatic fire-extinguishing system, as approved by the fire chief; in occupancies usedfor temporary amusement events and amusement buildings.

GROUP B - BUSINESS

See specific requirements for High-rise Occupancies for New Construction.

5-134 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 595: NEMA GUIDE CODE Fire Alarm & Detection System

GROW E - EDUCATIONAL

Section 305.2.2.2 (Building Code)

Section 305.9 (Building Code) and Section 1007.2.4 (Fire Code)

Section 904.2.4 (Building Code) (Added) and Section 1003.2.4 @ire Code)

Section 1007.3.4 (Building Code) and Section 1007.2.4.2 (Fire Code)

Provide approved smoke detectors to activate all automatic-closing fire assemblies installed in the atmospheric separation.

Provide approved fire alarm system when occupant load is 50 or more. When automatic sprinkler or smoke detectors provided, install to automatically activate fire alarm.

Provide automatic fire sprinkler system throughout all Group E-1 occupancies including basements, in enclosed usable space below or over a stairway, and in every boiler room or room containing a central heatingplant below usable space unless separated by a three-hourjire-resistive occupancy separation. Exception allowed when room for instruction has one exit door directly outside at ground level. Exception also allowed when area separation walls or occupancy separation has two-hour f í e resistive rating subdividing building into separate compartments with aggregate floor area not greater than 20,000 square feet

Provide smoke detectors installed throughout area of common atmosphere when the only means of exit from a room is through an adjoining or intervening room. Exceptions: i) When aggregate occupant load of interior room is not more than ten; 2 ) When enclosures forming interior rooms are less than two-thirds of floor-to-ceiling height or not more than eight feet; and 3) Rooms are used exclusively for mechanical and public utility service to building.

GROUP F - FACTORY AND INDUSTRIAL

Section 904.2.5 (Building Code) and Section 1003.2.5 (Fire Code)

Provide automatic fire -sprinkler system in woodworking occupancies over 2,500 square feet where finely divided combustible waste or materials present.

5-135 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 596: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP H - HAZARDOUS

GROUP I - INSTITUTIONAL

Section 307.9 (Building Code) and Sections 1007.2.6, 5013.1, and Article 80 (Fire Code) (Am ended)

Section 307.11 (Building Code)

Section 904.2.6 (Building Code) and Section 1003.2.6 (Fire Code)

Provide approved manual fire alarm system in Group H occupancies used to manufacture organic coatings and Group H-6 hazardous production materials occupancies. Provide approved autonzatic.fire detection, Jire alarm, and smoke detection for rooms used for storage, dispensing, use and handling of hazardous materials.

Provide approved emergency alarm system outside each interior door of hazardous production materials (Group H-6) storage rooms. Install so that activation of emergency alarm device will sound a local alarm and transmit signal to emergency control station.

Provide automatic fire extinguishing systems throughout H-1, H-2, H-3, H-6, and H-7 occupancies and H-4 occupancies with more than 3,000 square feet floor area.

Section 308.9 (Building Code) and Section 1007.2.7 (Fire Code)

Section 308.10 (Building Code) and Section 1007.2.7.1.2 (Fire Code)

Section 1007.2.7.1.1 (Fire Code)

Section 1007.2.7.2.4 (Fire Code)

Provide approved manual and automatic fire alarm system in all Group I Occupancies. Install audible alarm devices in non-patient areas. Visible alarm devices may be substituted for audible devices in patient-occupied areas.

Provide smoke detectors in patients sleeping rooms of hospital and nursing homes. Install to receive primary power from building wiring. Except in rooms equipped with automatic door closers having integral smoke detectors on room side, integral detector may substitute for smoke detector provided it performs required alerting functions.

In Groups 1-1.1, 1-1.2, and 1-2, provide smoke detectors at automatic-closing doors in smoke barriers and one-hour fire-resistive occupancy separations, and in waiting areas open to corridors. Install smoke detectors to activate alarm signal audible throughout building.

In Group 1-3, provide approved automatic smoke-detection system throughout resident housing areas.

5-136 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 597: NEMA GUIDE CODE Fire Alarm & Detection System

GROW 1 - INSTITUTIONAL (continued)

Section 904.2.7 (Building Code) and Section 1003.2.7 (Fire Code)

Provide automatic sprinkler system throughout. Install approved quick-response or residential sprinklers throughout patient sleeping areas in Groups 1-1.1 and 1-2.

Appendix Chapter 3, Division 1 (Building Code)

(City does not adopt this Appendix Chapter.)

GROUP M - MERCANTILE

Section 904.2.8 (Building Code) (Amended) and Section 1003.2.8 (Fire Code)

Provide automatic sprinkler system in rooms classified as Group M and in roonis fo r storage of combustible materials if floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all floors or if more than three stories.

GROUP R - RESIDENTIAL

Section 310.9.1 (Building Code) and Section 1007.2.9.2 (Fire Code) (Added)

Provide smoke detectors in dwelling units, congregate residences, and hotel or lodging house guest sleeping rooms installed per manufacturer's instructions and receiving primary power from building's wiring with a battery backup as secondary power supply. Single-station smoke detectors may be battery powered in existing buildings.

Provide operable detectors in all sleeping and napping areas of family child day care homes.

5-137 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 598: NEMA GUIDE CODE Fire Alarm & Detection System

GROUP R - RESIDENTZAL (continued)

Section 310.10 (Building Code) and Section 1007.2.9.1.1 (Fire Code) (Am ended)

Provide approved manual and automatic fire alarm system in apartment house three or more stories or containing more than 15 dwelling units, hotels three or more stories or containing 20 or more guest rooms, and in congregate residences three or more stories or having occupant load of 20 or more. In Group R-1 occupancies located in high-rise buildings, you must provide a fire aladcommunication system. Exceptions: i) Buildings not more than two stories with all individual units provided one hour fire separation and direct exterior egress; 2) Buildings three stories or less separated b,v at least one-hour.fire-resistive construction and each unit has a means of egress directly to the public way which is not shared by another unit and where no unit is located above another unit.

Section 904.2.9 (Building Code) and Section 1003.2.9 hydrant. (Fire Code) (Amended)

Provide automatic sprinkler system in Group R not having approvedfire department access, not having adequate,fireJow, or located more than 500 feetjroni the nearest

Provide automatic sprinkler system in Group R-1 as.fo1low.s:

t% Buildings having twofloors of Group R-1 located above any occupanc,v other than Groups U and S-3parking garage; or storage, mechanical or laundry rooms. t% Apartment buildings with five or more dwelling units. %% Hotels with ten or more guest rooms. t% Congregate residences of 50 or more occupants.

Buildings three or more stories.

Section 1007.2.9.1.3 8 L .4 (Fire Code) (Amended)

Provide smoke and heat detectors in all common areas and smoke detectors in interior corridors serving as exit for ten or more occupants. Provide heat detectors in un-sprinkled office spaces, retail spaces, parking areas, and other non-residential areas. Where ambient conditionspermit, smoke detectors may be installed in lieu of heat detectors.

GROUP S - STORAGE

Section 904.2.10 (Building Code) (Added)

Provide automatic sprinkler system in liquor warehouses and in roonis used for storage of combustible materials where floor area exceeds 12,000 square feet on any floor or 24,000 square feet on allJoors.

5-138 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 599: NEMA GUIDE CODE Fire Alarm & Detection System

Section 313.8 (Building Code) (Added)

Provide smoke detectors, installed per approved nianifacturer’s instructions, in rooms used for sleeping purposes within licensed care facilities.

Provide an automatic sprinkler systeni throughout every licensed facility three or niore stories or licensed fo r niore than 16 clients. Also provide in licensed carejacilities with 16 or less clients, licensed to provide care fo r more than two clients having an evacuation capability of II or III. Residential or quick-response heads are required.

Section 313.9 (Building Code) and Section 1007.2.11 (Fire Code) (Added)

Provide approved manual and automatic fire alarm system in Group LC licensed three or more stories or with more than 16 clients.

HIGHRISE. NEW CONSTRUCTION

Section 403.2 (Building Code)

Section 403.3 (Building Code) and Section 1007.2.12.2.2 (Fire Code) (Am ended)

Section 403.5 (Building Code) and Section 1007.2.12.2 (Fire Code) (Amended)

Provide approved automatic sprinkler system, smoke detection system, and alarm and communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access and in buildings having floors used fo r human occupancy more than 35 feet above grade which lackfire department vehicle access to at least one side, and of Type I or II-F.R. construction.

Provide smoke detectors connected to automatic fire alarm system in mechanical system ducts or risers, air conditioning return-air and exhaust-air plenums, un- sprinkled mechanical equipment rooms, elevator lobbies and interior corridors serving as exit for occupant load of ten or more occupants in Group R-1 occupancies.

Provide fire alarm, emergency voice/alarm signaling system and fire department communication systems in buildings with floors used for human occupancy located more than 75 feet above lowest level of fire department access. Installfire alarm system in existing high-rise buildings per Article 193 of Fire Code. Fire alarm systems in new construction must meet the requirenzentsper City Building Code.

5-139. Seattle. WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 600: NEMA GUIDE CODE Fire Alarm & Detection System

Section 402.2 (Building Code) and Section 1007.2.12.3 (Fire Code)

Buildings with atrium: Provide smoke-control system that operates automatically upon actuation of automatic sprinkler system within and areas open to atrium. Install smoke-control system to initiate fire alarm signal in designated portions of building.

Section 1007.2.12.4 and Article 81 (Fire Code)

Section 1007.2.12.5 (Fire Code)

Section 1007.2.12.6 (Fire Code)

Section 1007.2.12.7 (Fire Code)

Section 1007.2.12.8 (Fire Code)

Section 1007.2.12.9 (Fire Code)

Provide automatic fire detection system throughout high-piled combustible storage uses as required by Article 8 1. Provide approved automatic fire sprinkler system when required by Table 81-A.

Provide automatic smoke detection system throughout building when special egress- control devices are installed on exit doors.

Provide smoke detectors within office corridors not of one-hour fire-resistive conslruction. Install detectors to activate alarms audible in all areas served by corridor.

Provide approved manual alarm system when required by Article 88 for aerosol storage rooms and general purpose warehouses containing aerosols.

Provide approved automatic smoke detection system when required by the Building Code for automatic control of a smokecontrol system.

Provide manual fire alarm system in lumber, plywood, and veneer mills.

5-140 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 601: NEMA GUIDE CODE Fire Alarm & Detection System

HIGHREE. EXISTING STRUCTURJCS

Article 193 Section I9306 (Fire Code)

The city does not adopt the appendix chapreips of the Uniform Codes but has inserted Article 193 into the city k,fire code. The purpose of this article is to establish minimum standards f o r existing high-rise buildings. Fire protection requirements are as

(Added) folloM1s:

Provide electrically supervised,fire alarm and detection system, as approved by the fire chief; in every existing high-rise building, except a residential occupancy with a system installed by other regulations.

Provide electrically supervised automatic smoke detection in elevator landings, public corridors, and on the corridor orfloor side of each exit stairway, except where corridor has an approved automatic sprinkler system. Provide electrically supewised automatic heat or smoke detection in rooms used for storage, shops, handicraft, janitor, trash and similar purposes if no automatic sprinkler system exists.

COVERED MALLS

Section 404.3.1 (Building Code)

Provide automatic sprinkler system electrically supervised by approved central, proprietary or remote signal or local alarm service throughout. Provide smoke control system connected to both sprinkler system and smoke detector system; excepted are malls not more than one story or with no more than 24,000 square feet of leasable area.

AVIATION CONTROL TOWERS

Appendix Chapter 4, DMsion II, Section 425 (Building Code)

Provide smoke detectors and approved fire alarm system in all occupied levels.

GROUP CARE FACILITIES (GROUP R DMSION 4)

Append= Chapter 3, Division N, Section 341 (Building Code)

(City does not adopt this Appendix Chapter.)

Section 904.2.2 (Building Code) and Section 1003.2.2 (Fire Code)

Except in Group R-3 and U occupancies, provide automatic sprinkler system in every story or basement area more than 1,500 square feet except as detailed in Section 904.2.2 of 1997 UBC; at top of rubbish and linen chutes and their terminal rooms, in rooms where nitrate film is stored or handled, or in protected combustible fiber storage vaults, and throughout all buildings with floor level with an occupant load of 30 or more located 55 feet or more above the lowest level of fire department vehicle access. Exception: Airport control towers, open parking structures, and Group F-2 occupancies.

5-141 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 602: NEMA GUIDE CODE Fire Alarm & Detection System

Appendix Chapter 34 Division 1, Section 3408 (Building Code) and Appendix 1-A (Fire Code)

Section 713 (Building Code)

(City does not adopt these Appendix Chapters.)

Provide approved and listed smoke detectors to activate closing device of an automatic closing fire assembly, i.e., fire door, fire window or fire damper, and to close smoke dampers in ducted or un-ducted air openings as required by the 1997 UBC.

5-142 Seattle, WA

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 603: NEMA GUIDE CODE Fire Alarm & Detection System

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---

Page 604: NEMA GUIDE CODE Fire Alarm & Detection System

Copyright National Electrical Manufacturers Association Provided by IHS under license with NEMA Licensee=Aramco HQ/9980755100

Not for Resale, 01/20/2007 06:28:54 MSTNo reproduction or networking permitted without license from IHS

--```,`,``,,,,,`,,`,,`,,,,,,``-`-`,,`,,`,`,,`---