Page 1: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

NCTCOGNorth Central Texas Council of Government

(COG)

Page 2: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

What is NCTCOG?

A voluntary association of, by and for local governments, established to assist local

governments in planning for common needs, cooperating for mutual benefit, and coordinating

for sound regional development.

Page 3: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

COG was established on January 20, 1966It was intended to help local governments improve

their capability to serve their citizens by defining regional issues, problems and opportunities; by

setting priorities, and devising policies, plans and programs to deal with them.

Page 4: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

About NCTCOGServes 16 Counties and 230 member governments which make up the

General Assembly, who annually elect the Executive Board

Page 5: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

What is NCTCOG Pamphlet online?

Page 6: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Executive Board7 locally elected officials and one ex-officio non-

voting member of the legislature and is the policy-making body for all activities undertaken by the

Council of Governments.

Page 7: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Organizational Chart

Page 8: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

RCCC

Regional Codes Coordinating Committee(RC3)

Resides under the umbrella of the Environment and Development Department

Page 9: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The RCCC researches and provides recommendations on the standardization of municipal construction codes.

28 members serve 2 year termsIt is comprised of building officials, architects, engineers, contractors,

educators, property management professionals, insurance reps, builders and developers.

Page 10: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

RCCC PurposeThe primary purpose of the RCCC is to foster municipal government and private industry cooperation in promoting the

standardization of construction codes used within the North Central Texas region.

This includes the adoption of the NCTCOG Recommended Codes and the NCTCOG Regional Amendments. (The COG Amendments)

Page 11: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Linkshttp://www.nctcog.org/ENVIR/SEEDevEx/codes/index.asphttp://www.nctcog.org/ENVIR/committees/rccc/2017RCCCInternetRoster.pdfhttp://www.nctcog.org/ENVIR/committees/rccc/building/index.asp

Page 12: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

5 Regional Code Advisory Boards

Building & ResidentialElectrical

Energy & GreenFire

Plumbing & Mechanical

Page 13: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Building & Residential Advisory Board

Provides support and technical advice to NCTCOG’s Regional Codes Coordinating Committee (RCCC) on a wide range of building issues.

The current Chair is Selso Mata, Building Official City of Plano The current Vice-Chair is Jack Thompson, Building Official Town of Westover

Hills

Page 14: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

2015 Code Amendments Letter

Page 15: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Current Code Amendments

Page 16: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Typical Amendment Page

Page 17: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Section 1704 Special Inspections

Page 18: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Statement of Required Special Inspections

Page 19: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Approved Agency Documentation

Page 20: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Final Report of Required Special Inspections

Page 21: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 22: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The Code AmendmentsJarod Fancher

Page 23: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

I will not read the code to you.

Page 24: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Most of what I say is paraphrased.

Page 25: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Read the amendment text to fully understand the associated changes.

Page 26: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Treat this presentation as a discussion.

Page 27: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Ask questions when you think of them.

Page 28: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

How to Understand the Amendments Document

Page 29: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Underlined Text is Added InformationStrikethrough Text is Deleted Information

** = No New Changes from Previous Year*** = New Changes from Previous Year

Page 30: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 31: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 1

Page 32: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

101.4 Referenced Codes

Clarification

Page 33: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 34: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Adds legal language to state that an amendment to the IBC shall also amend

other referenced documents.

Page 35: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

When you change the definition of an Atrium from 2 connected stories to 3 in the IBC.

It also changes the definition in the IFC.

Page 36: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 37: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

101.4.8 ElectricalNew section added to include the

reference codes for electrical work.

Page 38: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The ICC Electric Code was replaced by IBC Appendix K in 2012.

Page 39: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The ICC Electric Code was replaced by IBC Appendix K in 2012.

So they removed it…

Page 40: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Appendix K recognizes NFPA 70 as the code for electrical construction.

Page 41: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

NFPA 70 is the National Electric Code

Page 42: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

103.1 Creation of

Enforcement Agency

Recommendation

Page 43: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Recommendation for a city to replace “Department of Building Safety” with the formal

name of their department.

Page 44: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

104.2.1 Damaged Buildings104.10.1 Flood Hazard Areas

Recommendation

Page 45: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Un-amended, this states that the building official determines if work on

a damaged building is technically reconstructionor just repairs.

Page 46: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Recommends that Cities amend or delete these sections based on actual enforcement and flood

hazard ordinances.

Page 47: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

105.2 Work Exempt from Permit

Removes some exceptions.

Page 48: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Single-story tool sheds, storage buildings, play houses and shade-cloth-structures-for-gardens

should not be exempt from permit.

These are often governed by the International Residential Code and local ordinances.

Page 49: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

109.7 Re-Inspection Fee

New Section

Page 50: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

New section which lists the faults that allow a City to charge a fee

for re-inspecting work.

Page 51: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

For fun…

What are the reasons?

Page 52: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The work is not ready for inspection.

Page 53: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The building address or permit card is not posted.

Page 54: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Approved plans are not on site.

Page 55: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Building is locked.

Page 56: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Job is Red Tagged TWICE for the same reason.

Page 57: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

A Red Tag is removed from the job site.

Page 58: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Failure to maintain erosion control, trash control or tree protection.

Page 59: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

109.8 Work Without a Permit

New section

Page 60: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Allows an investigation fee to be charged for work started or completed without a permit.

The avoided permit fee must also be paid.

Page 61: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

110.3.5 Lath & Gypsum Inspections

Removes an exception.

Page 62: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Removes the exception for materials on a non-rated assembly.

All lath and gypsum are inspected.

Page 63: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 2

Page 64: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

202 Definitions

Page 65: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Ambulatory Care Facility

Buildings which provide services on a less-than-24-hour-basis to individuals who are rendered incapable of self-preservation by the

services provided.

The following services shall be included:

Page 66: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

DialysisSedation Dentistry

SurgeryColonic

Psychiatric

Page 67: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Assisted Living Facilities

The definition was removed from the 2012 IBC and should be included since the term is still used

within the code book.

Page 68: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Atrium

An opening connecting two three or more stories.

Allowed by legacy codes. Section 1019 permits unenclosed two-story stairs.

Page 69: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Why?

Section 1019 permits unenclosed two-story stairs & two-story spaces

were allowed by legacy codes.

Page 70: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Repair Garage

Definition added to align with the International Fire Code.

Page 71: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Special Inspector

Now includes language to include the Registered Design Professional

as a party to the special inspections process.

Page 72: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

A qualified person employed or retained by an approved agency

who shall prove to the satisfaction of the registered design professional in responsible charge

and approved by the Building Official as having the competence necessary to inspect a particular type of

construction requiring special inspection.

Page 73: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 74: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

High-Rise Building

Option A: Maintains the original definition with the 75-foot threshold.

Option B: The 75-foot threshold is reduced to 55-feet for jurisdictions who lack certain fire fighting capabilities; therefore, requiring larger sprinkler

threshold requirements.

Page 75: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Question

Does anyone know how the sprinkler thresholds are affected by being a “high-rise building” ?

Page 76: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 3

Page 77: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

303.1.3 Assembly Occupancy Associated

with E Occupancies

Clarification

Page 78: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

An assembly room associated with an Education building is not considered a separate occupancy.

Page 79: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

An assembly room associated with an Education building is not considered a separate occupancy.

Except when applying the assembly requirements of Chapters 10 & 11.

Page 80: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Clarifications Only:

Cafeterias & Auditoriums must comply with means of egress & accessibility.

Page 81: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

304.1 Business Group B

Adds to the uses list.

Page 82: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 83: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Fire Stations

Police Stations with 5 or less detention facilities

Page 84: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

307.1.1 Uses Other than Group HUses with hazardous materials that are not

classified under Group H.

Page 85: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Clarifies Exception 4: Dry Cleaners.

New text calls attention to IFC Chapter 21, Dry Cleaning Plant provisions.

Page 86: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 4

Page 87: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

403.1 High-Rise Buildings

Clarification to an exemption.

Page 88: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

ONLY open air portions of a high-rise stadium are exempt from the high-rise requirements.

Page 89: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

403.3 Automatic Sprinkler System

Removes an Exception

Page 90: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Removes the exception for telecommunication buildings to

be un-sprinkled.

Page 91: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

403.3.2 Water Supply to Fire Pumps

Modification

Page 92: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Buildings above a certain height are required to connect to two separate water mains.

The amendment changes this threshold from 420 feet to only 120 feet.

Page 93: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

404.5 Smoke Control

Removes Exception

Page 94: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Deletes the exception which excludes two-story atriums from requiring

smoke control.

This is consistent with the amended definition for an atrium.

Page 95: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

406.3.5.1 Carport Separation

Adds text.

Page 96: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

A fire separation is not required between carports and R-3 buildings.

COG recommends including R-2 apartment buildings, so long as they are at least

10 feet from the adjacent building.

Page 97: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 5

Page 98: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

506.3.2.1 Open space Limits

Clarification

Page 99: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Explains that an accessible area must be a street, fire lane, or 10 foot pathway meeting fire

department access requirements.

Page 100: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 7

Page 101: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

712.1.9 Two-Story Openings

Modification

Page 102: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Two-story openings will be allowed to open onto corridors in R occupancies, but not allowed in H

occupancies.

This is consistent with the amended definition for an atrium.

Page 103: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 9

Page 104: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

901.6.1.1 Standpipe Testing

New Section

Page 105: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Building owners must maintain and test standpipe systems per NFPA 25.

Page 106: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.1.1 Alternative Protectionfor Automatic Sprinkler Systems

Modification

Page 107: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Alternate extinguishing methods cannot replace sprinkling, but can only be provided in addition to

a sprinkling.

Alternate methods are not as reliable as sprinkling. This also align with local practices.

Page 108: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.2 Where Required

Sprinkler Exclusions

Page 109: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Elevator machine rooms, hoist ways, and elevator pits shall not be sprinkled.

Shunt trips are not allowed.

Page 110: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Storage must not be allowed within an elevator machine room, and signage must be posted on

the entry door stating that storage is not allowed in the machine room.

Page 111: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Telecommunication rooms are not excluded from automatic fire suppression.

Page 112: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.2.9.3 Self-Storage Facility

New Section

Page 113: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

All self-service storage facilities shall be sprinkled.

Page 114: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903..3.1.1.1 Exempt Locationsfor NFPA 13 Sprinkler Systems

Added Language

Page 115: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

When approved by the fire code official, certain spaces may be excluded…

Page 116: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.3.1.2.3 Attics & Attached Garages

New Section

Page 117: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Sprinkler protection is required in attics of buildings over one-story and in all car garages

attached to a building.

Page 118: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.3.1.3 NFPA 13D

Modification

Page 119: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Adds that a 13D system may be installed in residential occupancies or in accordance with

state law.

This allows the plumbing section of the IRC to be used in lieu of the 13D system in the IBC.

Page 120: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.3.1.4 Freeze Protection

New Section

Page 121: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Requires freeze protection in vented attics with dry or anti-freeze systems.

Only allows heat trace & insulation in specific circumstances approved

by the building official.

Page 122: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.3.5 Water Supplies

Added text.

Page 123: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Water-based fire protection systems must be designed with a 10 psi safety factor.

Page 124: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.4 Sprinkler SystemSupervision & Alarms

Added text.

Page 125: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Additional water-flow detectors shall be installed which will detect water flow to prevent significant

water loss.

Page 126: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

903.4.2 Alarms

Added text.

Page 127: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

An alarm device is required on the exterior of the building with a waterproof

horn & strobe, and must be located as closely as practical to each fire department

connection (FDC).

Page 128: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

905.2 Standpipe Installation

Added text.

Page 129: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Dry standpipes must have a minimum 10psi, maximum 40 psi

air pressure high/low alarm.

Page 130: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

905.3.9 Buildings Exceeding 10,000 SF

New Section

Page 131: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Class I wet standpipes shall be provided in buildings with more than 10,000 SF per story or

200 feet of travel distance to the nearest point of fire department access.

Page 132: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

905.4 Location of Hose Connections

Added requirements.

Page 133: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

All standpipes to roofs with a slope less than 4:12 shall be provided with

a two-way hose connection.

Page 134: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Standpipe connections shall be placed at all required exits and at 200-foot

intervals along major corridors or as approved by the code official.

Page 135: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

905.9 Valve Supervision

Added requirements.

Page 136: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Reinforces previous amendment:

Additional water-flow detectors shall be installed which will detect water flow to prevent significant

water loss.

Page 137: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.1.4 Design Standardsfor Fire Alarms

New Section

Page 138: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

All new fire alarms shall be addressable.

Alarms systems with more than 20 smoke detectors shall have

“analog initiating devices”.

Page 139: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Addressable Device

A component of a fire alarm system that has a specific identification and location.

These devices allow the user to check the individual status of a device and control many

other functions.

Page 140: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Analog Initiating Device

Indicates different degrees of conditions, as compared to a conventional device

that only indicates a on or off condition.

Page 141: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.2.1 Group A

Modification

Page 142: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Adds the requirement of a manual fire alarm when there are more than 100 occupants above

or below the the level of exit discharge.

Page 143: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Activation of the fire alarm shall illuminate the means of egress and stop other conflicting sounds

or visual distractions.

Page 144: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.2.3 Group E

Modification

Page 145: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

All day care facilities shall be equipped with a smoke detection system.

Page 146: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.2.13 High-Rise Buildings

Modification

Page 147: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The exception for stadiums is amended to align with the previous amendment.

Only open-air portions of a high-rise stadium do not require smoke detection.

Page 148: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.4.2.7 Fire Alarm Box Type

New Section

Page 149: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Manual alarms shall be double-action.

Page 150: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.6.1.1 Wiring Installation

New Section

Page 151: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Alarm systems shall be designed so that the failure of one device

does not affect the other devices.

Page 152: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

907.6.3 Initiating Device ID

Exceptions Removed

Page 153: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The fire alarms system shall identify each specific device, as well as

its location and status.

Page 154: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

909.22 Pressurization Alternative

New Section

Page 155: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Enforces language from the Fire Code for the pressurization of egress stairs and ramps and

proper ventilation.

Page 156: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

910.2 Smoke & Heat Removal

Modification

Page 157: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Automatic smoke & heat removal is prohibited from areas with an (ESFR) Early Suppression Fast

Response sprinkler system.

Only manual systems can be required.

Page 158: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

910.2.3 Group H

New Section

Page 159: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

H-2 & H-3 buildings of more than 15,000 SF will require smoke & heat removal,

unless the building and its contents are non-combustible.

Page 160: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

This allows for specific instances where it is best for a chemical to burn out

rather than to be extinguished.

Page 161: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

910.3.4 Vent Operation

New Section

Page 162: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Smoke & heat vents shall be capable of activating both automatically and manually, controlled by

the fire alarm system or by a heat sensor.

Page 163: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

910.4.3.1 Make-Up Air

Modification

Page 164: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Make-up air openings for smoke & heat removal shall be automatic.

This decreases the time for first responders to begin fighting a fire and saving lives.

Page 165: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

910.4.4 Activation

Modification

Page 166: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The mechanical smoke removal system shall be activated by manual controls only automatically

by the automatic sprinkler system…

only early response systems will be manual.

Page 167: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

912.2.3 Hydrant Distance

New Section

Page 168: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Hydrants must not be farther than 100’ from the FDC as the hose lays on the ground.

Page 169: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

913.2.1 Fire Pump Room Protection

Modification

Page 170: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

When located on the ground floor at an exterior wall, pump rooms shall have a man door for fire

department access, regardless of any interior access doors.

A knox-box is also required at this exterior door.

Page 171: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 10

Page 172: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1006.2.2.6 Electrical Rooms

Clarification

Page 173: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Instructs the reader to refer to the Electrical Code for exit door requirements.

Page 174: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1009.1 Required Accessible Egress

New Exception

Page 175: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Buildings regulated under State Law and in conformance with State Law are exempt from the

IBC for accessible egress requirements.

Page 176: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1010.1.9.4 Bolt Locks

Modification

Page 177: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, S, or M occupancy, the inactive leaf may receive bolt

locks.

Page 178: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Where a pair of doors serves a Group B, F, S, A or M occupancy, the inactive leaf may receive bolt

locks.

As long as it is not needed to meet egress requirements, the building is sprinkled, and the the leaf is free from latches or panic hardware.

Page 179: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Question

For funzies…

Page 180: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

If the code explicitly allows something…it is allowed.

Page 181: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

If the code explicitly prohibits something…it is not allowed.

Page 182: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

What if it’s not explicit ?

Page 183: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1015.8 Window OpeningsR2 & R3 Occupancies

Red Pill / Blue Pill

Page 184: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Option AUnchanged: IF a window sill is

less than 36” AFF and 6’ above the ground, it must have fall protection.

Page 185: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Option BOperable windows where the sill is

55’ or more above the ground, fall protection is required.

Page 186: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1020.1 Construction

New Exception

Page 187: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Corridor walls in a single-tenant office building are not required to be rated as long as the space is

sprinkled, has a fire alarm, and has smoke detectors tied to that

fire alarm.

This aligns with previous City of Dallas amendments.

Page 188: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1029.1.1.1

Section Removed

Page 189: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Grandstands and bleachers shall be separated (1HR) from spaces below, unless that space is a

ticket booth or restroom.

Page 190: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Reason: Unenforceable.

Page 191: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 11

Page 192: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1101.1 Scope

New Exception

Page 193: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

This is the only time that I am giving you the codeword for word.

Page 194: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

ExceptionComponents of projects regulated by and registered with

Architectural Barriers Division of Texas Department of Licensing and Regulation shall be deemed to be in compliance

with the requirements of this chapter.

Page 195: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

If TDLR covers it…

and there is an EAB number on the drawings…

You can ignore Chapter 11.

Page 196: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

TDLR does not cover “apartment units”.

Those are considered private.

Page 197: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Apartments & condos must still comply with Chapter 11.

Page 198: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Apartments & condos must still comply with Chapter 11.

Right ?

Page 199: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 12

Page 200: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1203.1 General. Ventilation

Modification

Page 201: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Unamended: Buildings must be vented if the air change per hour is less than 5 changes.

Amended: Buildings must be vented if the air change per hour is 5 changes or less.

Page 202: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 15

Page 203: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1505.1 Minimum Roof Classification

Modification

Page 204: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The exception for R-3 & U occupancies to have unclassified materials is revised to exclude R-3.

Only Group U of less than 120 SF is excluded for unclassified combustible materials. Larger than that, must have non-combustible materials if they are to remain unclassified.

Page 205: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Deletes an exception for cedar and redwood shakes. These shall not be used for any commercial roof.

Page 206: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1505.7 Special Purpose Roofs

Removed

Page 207: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Special Purpose Roof = Wood Shingle / Shake Roof

Page 208: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Like we just said…you can’t do it.

Page 209: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

NO wooden roofs.

Page 210: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1510.1 General. Roof Structures

Clarified

Page 211: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Replacement Shingles or Shakes shall be in compliance with 1505.1.

Page 212: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Meaning: You can’t use them unless it is a tiny carport.

Page 213: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Like mini-cooper tiny…

Page 214: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

9 x 18 = 162

Page 215: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

9 x 18 = 162

162 > 120

Page 216: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 217: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

No wooden shakes.

Page 218: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 17

Page 219: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

1704.2 Special Inspections

Modified

Page 220: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Special Inspections must be obtained by the Registered Design Profession in Responsible Charge,

the owner, or the owner’s agent.

Page 221: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

The special inspector must NOT be employed by the contractor.

Page 222: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 29

Page 223: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

2901.1 Scope. Plumbing

Clarified

Page 224: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

IF this chapter conflicts with any part of Chapter 4 in the Plumbing Code, the Building Official chooses.

Page 225: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

2902.1 Minimum # of Fixtures

Clarified

Page 226: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Except for Group E, the number of fixtures may be reduced for special occupancy needs.

Submit reasons in writing to the Building Official for approval.

Page 227: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

2902.1 Footnote ‘f’

Added note

Page 228: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Drinking fountains are not required for Group M with 100 people or less; Group B with 25 people or less; or

any dining & drinking establishments.

Page 229: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

2902.1.3 Additional Fixtures

New Section

Page 230: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Hand washing sinks and service sinks shall be provided at all food preparation areas.

Page 231: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 30

Page 232: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3002.1 Hoistway Enclosure Protection

Clarification

Page 233: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Elevator enclosures within atriums are not required to be rated.

Page 234: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Elevator enclosures within parking garages are not required to be rated if they ONLY serve the

parking garage structure.

Page 235: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3005.4 Machine Rooms

Clarification

Page 236: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Reworded to allow for remote closets where the cables from the closet to the hoist way

are not required to be rated.

Page 237: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3005.7 Fire Protection in Machine Rooms

Modification

Page 238: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Prohibits any fire suppression system that would require a shunt trip.

Shunt trips are not allowed.

Page 239: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3005.8 No Storage Sign

New Section

Page 240: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Reinforces that a machine room requires signage stating that storage is not allowed within the

elevator machine room.

Page 241: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic
Page 242: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3006.2 Hoistway Opening Protection

Options

Page 243: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Option A: Rated doors are required if the hoist way is more than 75 feet in height measured from

the ground level to the top floor.

Option B: …55 feet…

Page 244: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Chapter 31

Page 245: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Ready for the LAST one!!

Page 246: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

3109.1 General. Pools & Spas

Clarification

Page 247: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

Swimming pools shall comply with the requirements of this code as well as applicable

state laws.

Page 248: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic

NCTCOGNorth Central Texas Council of Government

(COG)