Navy Case Study - Base Load Optimization

64
Proprietary and Confidential. Not for distribution. SDG&E – Pt. Loma Naval Base Chiller Plant Upgrade Cuts Energy by over 70% Annually using the Load Based Optimization System [LOBOS] California Center for Sustainable Energy 9-14-11

description

See How the Navy Used the Load Based Optimization System to Save a Boatload of Energy!We cut the energy consumption by over 70% at this 10 year old Navy Chiller Plant!If you are serious about cutting energy consumption and reducing operating costs, you'll want to be at this presentation!“Large Temperature Differential” design will be discussed. Typical TES systems that were a part of the Southern California Edison “Permanent Load Shift” chilled water storage pilot program operated with 25°F to 30°F chilled water temperature differentials, while the PG&E site peaked out with a 44°F temperature differential (not a typo!), with typical summer operation floating between 30°F and 34°F TD’s. The PG&E 900 ton chiller plant all-in efficiency averaged around 0.50 kWh per ton-hour while making 35°F chilled water for the TES system during the TES charge cycle.A preliminary analysis using all of the above strategies and an innovative dehumidification/ reheat system to treat 1,000,000 CFM of makeup air at a large chip fab yielded potential savings of over 27,000,000 kWh per year, and over 400,000 therms per year in natural gas savings.These design, Demand Response and optimization strategies can be applied across a wide variety of facility types, from tilt ups with large RTU’s to Commercial office space, to Universities and Colleges, to military, prison, manufacturing and technology sites.Please join us for an entertaining and educational meeting!Scot M. Duncan, P.E. BiographyWith 39 years of field, design and plant operational experience, the bio gets really long! We’ll just bracket it to cut down on your boredom reading it…Scot started in the business at age 12 helping his dad install an early version of an automation system (the Honeywell Delta 2000 for you old guys) at the Irvine Company Newport Center high rise facilities. Since then, he has been involved in hundreds of successful and sometimes counter-intuitive energy efficiency projects. He is a “Subject Matter Expert” for the U.S. Army Corps of Engineers on 14 different topics, ranging from Net Zero Energy HVAC designs, to high efficiency dehumidification/reheat systems, to HVAC optimization to TES. Scot is a co-author of the International Energy Agency (IEA) ECBCS Annex 46 “Energy and Process Assessment Protocol” (soon to be on Oprah’s “must read” list and a New York Times Best Seller wanna-be…).Scot is a Past President of the AEE SoCal Chapter (1990) and is Vice President of Retrofit Originality Incorporated, and President of Enerliance. He has provided over 100 chiller plant, HVAC and TES energy efficiency and design strategy training seminars since 1985, and has not been booed off the stage even once that he’ll admit to.

Transcript of Navy Case Study - Base Load Optimization

Page 1: Navy Case Study - Base Load Optimization

Proprietary and Confidential. Not for distribution.

SDG&E – Pt. Loma Naval Base Chiller Plant Upgrade Cuts Energy by over 70% Annually using the Load Based Optimization System [LOBOS] California Center for Sustainable Energy 9-14-11

Page 2: Navy Case Study - Base Load Optimization

• We offer this presentation in the memory of Gary Gates, a Navy man that fought tirelessly to save energy while improving working conditions for Navy personnel. He is sorely missed by all who knew him.

ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution. 2

Page 3: Navy Case Study - Base Load Optimization

GE Ecomagination Challenge

• The Ecomagination Challenge is a worldwide competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well as viable methods to effectively produce renewable energy and improve grid/system performance on a global basis.

• Out of 3,800 entries received and evaluated by GE, Enerliance is the only firm with two entries in the top 100.

3ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 4: Navy Case Study - Base Load Optimization

“Poor controls can waste more energy than great equipment can save.”

Prius with “Efficient” HVAC Control Strategies16 MPG

Prius with “Load Based” HVAC Control 99 MPG

11.9 MPG on the Prius

Why LOBOS?

4ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 5: Navy Case Study - Base Load Optimization

Project Description

• The Building 56 Chiller plant at the Pt. Loma Naval Base serves 24/7 loads including data centers, office areas and computerized training labs and other classified areas that we could tell you about, but then we’d have to kill you.

• The project consisted of adding one new 450 ton VFD centrifugal chiller to the two existing 350 ton VFD centrifugal chillers, adding VFD’s to the primary and condenser water pumps, removing a multitude of tertiary pumps from the buildings and installing the Load Based Optimization System (LOBOS) to optimize the system.

5ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 6: Navy Case Study - Base Load Optimization

History

• The Navy had installed a well marketed optimization system from another firm on a previous project, but after two years of operation, it was not meeting expectations.

• When this project was brought up, there was a huge pushback from many in the Navy, due to concerns about not meeting expectations.

• They reviewed real operational data from several Load Based Optimization System projects and decided to utilize this system for their project.

6ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 7: Navy Case Study - Base Load Optimization

History

• Prior to the Load Based Optimization System (LOBOS) installation, the plant was run 24/7 with fixed CHWS temperatures and differential pressure setpoints, as there was no feedback from the loads to allow the system to be run more effectively.

• The timing of the cooling load needs at night and on weekends is based on the use of the data centers and trainers, and is totally unpredictable.

7ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 8: Navy Case Study - Base Load Optimization

Results

• After one year of operation, the M&V process has shown that the results have exceeded savings expectations by over 50%.

• There has been a net reduction of energy used in the chiller plant of over 70%, based on a separate utility meter.

• Additional scope incorporated into the project have added approximately 1,000 MWH of savings that were not expected.

8ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 9: Navy Case Study - Base Load Optimization

Plant load 325 tons, Total Plant = 0.28 kW/ton (note the OSA humidity at 105% - previously existing sensor, and why we do not use RH in any of our code…)

9ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 10: Navy Case Study - Base Load Optimization

Many existing loads still have 3-way valves, so secondary flow and pump energy is still higher than it needs to be. Low CHW temperature differential from 3-ways also drives primary pump energy higher than it needs to be, so we could eventually get down to 0.22 to 0.25 kW/ton for the entire plant under similar conditions.

10ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 11: Navy Case Study - Base Load Optimization

Multiple CT control loops to optimize the chiller plant while protecting the chillers

11ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 12: Navy Case Study - Base Load Optimization

Obvious Savings Directly Attributed to LOBOS

12ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Savings during “Limited Reset Operation” during commissioning were running 45% until Nov. when we were directed to shut LOBOS off. Savings for “Equipment only” changes ran about 12% for the month that LOBOS was shut off. When restarted, savings went back to 45% -50%. When full LOBOS resets were allowed in June, savings climbed to 73%-75% per month.

Page 13: Navy Case Study - Base Load Optimization

13ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Savings during “Limited Reset Operation” during commissioning were running 45% until Nov. when we were directed to shut LOBOS off. When restarted, savings went back to 45% -50%. When full LOBOS resets were allowed in June, savings climbed to 73%-75% per month.

Page 14: Navy Case Study - Base Load Optimization

Nozzle Spray pattern – very little coverage of fill – design flow rate

14ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 15: Navy Case Study - Base Load Optimization

Approximate 14” to 16” wide dry area at the bottom of the fill with the CT fan in

bypass (100% speed) and design CDW flow

15ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 16: Navy Case Study - Base Load Optimization

Bottom of the fill with the fan in bypass –100% speed, design flow rate

16ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 17: Navy Case Study - Base Load Optimization

Bottom of fill with the CT fan off, design flow rate

17ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 18: Navy Case Study - Base Load Optimization

One cell open to flow – Design flow –1100 GPM

18ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 19: Navy Case Study - Base Load Optimization

Solids Buildup with new fill.It is obvious where water is flowing and where water is not

flowing. There is more surface area with solids build up than there is

clean area where water is flowing.

19ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 20: Navy Case Study - Base Load Optimization

Scaling/Solids

• It can be seen from these pictures that scale is already forming on the fill which has been installed for approximately 6 months.

• We rectified the issue by installing nozzles that were two sizes smaller, and getting up inside the towers and directing the spray nozzles to wet the entire fill at low flow rates.

• Works even better at high flow rates.

• Allows much better use of the CT system, as well as reducing CDW pump energy waste and improving chiller energy performance.

20ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 21: Navy Case Study - Base Load Optimization

Future Savings Projects at Pt. Loma• New fan coil units are being selected

at 350 feet per minute face velocity to double CHW system temperature differential, improving overall system efficiency markedly.

• LOBOS being applied to new FCU’s.

21ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 22: Navy Case Study - Base Load Optimization

LOBOS

• Minimize Financial Risk, Maximize Owner Savings

• LOBOS Energy Efficiency (EE) and LOBOS Demand Response (DR) patent protected logic are pre-programmed, pre-tested and pre-commissioned software and hardware solutions that maximize owner savings while minimizing the financial risks and loss of time associated with installing advanced control system routines.

22ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 23: Navy Case Study - Base Load Optimization

LOBOS: How It Works

• Energy Efficiency and Demand Response control logic is contained in the LOBOS system.

• LOBOS integrates into the existing DDC Systems via the OPC server, LonTalk or BACnet software or hardware driver.

• The operating data from the HVAC system is gathered by LOBOS; the control setpointsare calculated and sent back out to the local DDC panels for an optimized PID loop control.

23ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 24: Navy Case Study - Base Load Optimization

Simple & Sustainable

• Energy Efficiency

– Most Energy Management Systems (EMS) leave a substantial amount of savings on the table

– In many cases, complex or non-adjustable optimization programs are disabled or overridden so Facility Engineers can keep tenants comfortable.

24ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 25: Navy Case Study - Base Load Optimization

LOBOS Control Strategy• Make it consistent / repeatable from

building-to-building.

• Make it user-friendly so the Operator can make adjustments within certain parameters.

• Make it self tuning to account for system/climate variations.

• Improve tenant experience, reduce energy costs and consumption.

25ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 26: Navy Case Study - Base Load Optimization

Pick the Right Optimization Strategy!

• Central Plant Optimization routines must look at the site loads – without knowing AHU load information, you cannot maximize energy savings, or respond to load changes properly.

• AHU Optimization routines are required to minimize energy use and promote occupant comfort! Don’t ignore 40% to 50% of the energy consumption of the cooling system!

• The System Must be Operator Friendly – If the person that designed it cannot explain it in an understandable manner to the people that operate the facility, it is too complex.

26ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 27: Navy Case Study - Base Load Optimization

Status at a Glance Efficiency Speedometer

The LOBOS Efficiency Speedometer is dynamic in nature.

The levels of efficiency change with the loads.

27ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 28: Navy Case Study - Base Load Optimization

AHU Set-up Screen

This page presents an overview of the information for each particular AHU. There is general information for the central plant and a summary of the WCAH values being utilized to drive LOBOS. On this page, the user can opt in/out the particular AHU to be monitored by LOBOS.

28ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 29: Navy Case Study - Base Load Optimization

AHU Supply Temperature Tuning

29ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

The Supply Air Temperature Setpoint tuning page allows for setting up the supply fan speed setpoint, which should be set as the value that the operators would like to see the fan speed run at.

Page 30: Navy Case Study - Base Load Optimization

AHU Supply Duct Static Tuning

30ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

The Supply Static Pressure Setpoint tuning page gives adjustability for how aggressive the setpoint will change to widening return air temperature deviation and space temperature deviation.

Page 31: Navy Case Study - Base Load Optimization

LOBOS Air Handler Overview

31ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Provides an overview of values used in establishing Worst Case AHU Size/Criticality/Distance.

All floors are not loaded alike – the Plant Optimization system must consider all loads!

Page 32: Navy Case Study - Base Load Optimization

LOBOS Central Plant Optimization

32ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

To make the CHWS temperature and CHW DP adjustments faster or slower, the slide bars can be used to double the gain, or cut the gain in half, or any amount between them.

Page 33: Navy Case Study - Base Load Optimization

Condenser water return temperature

Condenser water supply temperature

Chiller kW per ton of cooling

Chilled water return temperature

Temp Scale kW/ton Scale

Chilled water supply temperature

Effects of Changing CDW Temp Setpoint on VFD Chiller System Efficiency

33ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 34: Navy Case Study - Base Load Optimization

Case Study – 75% savings at the Navy Point Loma Project

• This project installed one new variable speedchiller, instituted a “variable everything” chilledwater pumping system and implemented theLOBOS software into the existing EMS.

• Overall annual efficiency is running around 0.52kWh per ton and at around 200 tons the plantruns at around 0.36 kW/ton.

• The plant operation should be reduced by over1,500 hours per year, due to “Thermal Flywheel”logic in the control scheme that shuts downchillers and uses the cold water that is in the pipesto meet small loads.

34ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 35: Navy Case Study - Base Load Optimization

Building 56 at Naval Base Point Loma – kWH monthly savings.

35ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

At the current savings rates, the chiller plant / LOBOS upgrade savings will exceed projected savings by more than 55 percent.

Page 36: Navy Case Study - Base Load Optimization

Monthly Average kWh Consumption for Pre and Post TES System Upgrade [From Utility Meter]

36ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

18350 Von Karmen Chiller Plant Monthly Energy Consumption (average, excluding 2003 due to low occupancy)

100,000

200,000

300,000

400,000

500,000

1 2 3 4 5 6 7 8 9 10 11 12

kWh

/mo

Post Modification Pre-Modification

Page 37: Navy Case Study - Base Load Optimization

Average Monthly Energy Savings From TES Upgrade Project

37ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

18350 Von Karmen Chiller Plant Monthly % savings (average, excluding 2003 due to low occupancy)

0%

10%

20%

30%

40%

50%

60%

1 2 3 4 5 6 7 8 9 10 11 12Chiller Plant Monthly % savings

Page 38: Navy Case Study - Base Load Optimization

Case Study 600 B Street San DiegoOptimized Plant vs. Normal Operation/Equipment

38ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 39: Navy Case Study - Base Load Optimization

Case Study Inland Center Mall

• LOBOS control strategies can optimize CHWsupply temperature and CDW supplytemperature, as well as AHU variables.

• Total chiller plant energy efficiency on thefollowing sample project is averaging less than0.50 kW/ton, even on 100°F days.

• Total Plant includes all chillers, chilled waterpumps, condenser water pumps and coolingtowers.

39ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 40: Navy Case Study - Base Load Optimization

E-mail from Dave Manley – 86% HVAC System Energy Reduction

Gentlemen,• If we reduce usage anymore…we can turn everything off

and go home! Overall usage down an amazing 55.89% from last year. HVAC usage down 86.59% from last year, triple checked figures. Duncanization didn’t effect Tower water usage like it did last month. Total monthly breakdown usage shows HVAC = 22%, INTERIOR = 50%, EXTERIOR = 28%. Only increase was in #2 COM. AREA due to increase in RMU’s and contractors using common area power during TI’s.

• David Manley | Operations Manager• Inland Center Mall• 500 Inland Center• San Bernardino, CA, 92408

40ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 41: Navy Case Study - Base Load Optimization

Chiller Plant Snapshot: Inland Center Mall

Chiller @ 0.32 kW/tonTotal chiller plant @ 0.45 kW/ton, including pumps, chillers and CTF’s

100°F OSA.

41ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 42: Navy Case Study - Base Load Optimization

Complete Day Performance: Tons & kW/ton

42ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 43: Navy Case Study - Base Load Optimization

Complete Day Performance: Tons and kW/ton

43ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 44: Navy Case Study - Base Load Optimization

Case Study10-Story Office Building; 80% Energy Efficiency Improvement

44ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 45: Navy Case Study - Base Load Optimization

Total Plant Efficiency @ 0.38 kW/Ton

At 33% load on the chiller, the total HVAC system, including fans and central plant equipment is using 0.51kW per ton.

45ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 46: Navy Case Study - Base Load Optimization

Total Plant Efficiency @ 0.33 kW/Ton

At 55% load on the chiller, the total HVAC system, including fans and central plant equipment is using .52kW per ton.

46ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 47: Navy Case Study - Base Load Optimization

2040 Main Street750 Ton VFD Chiller System

47ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 48: Navy Case Study - Base Load Optimization

Energy Efficiency Summary

48ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

• Properly designed and applied TES systems can reduce site and source energy consumption and enable wind power to become a viable part of the energy infrastructure.

• Energy Efficiency, Demand Response and Demand Reduction Technologies are not mutually exclusive!

• You can start with the most efficient design possible, which reduces demand, then add demand response software and Thermal Energy Storage (TES) if/when appropriate.

• With TES, airside Demand Response controls can be added to further reduce site demand, over and above the central plant peak demand savings.

• It is possible to reduce energy consumption at the site and source, while simultaneously reducing peak electrical demands and T&D congestion and improving occupant comfort.

• It is not cheap, but the benefits and GHG emission reductions are substantial.

Page 49: Navy Case Study - Base Load Optimization

LOBOS Demand Response (LOBOS DR)

49ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 50: Navy Case Study - Base Load Optimization

LOBOS DR• Typical DR Control systems require substantial manual

intervention and often do not get utilized because of the manpower costs associated with enabling them.

• The LOBOS DR 10 Stage is a fully automatic DR control system that can be applied to an individual building or across an entire portfolio.

• The system is as close to set it and forget it as you can get.

• Depending upon the facility size and the demand reduction potential at the site, the SCE Technical Installation Incentive may cover the entire cost of the DR system, thus eliminating any owner out of pocket expense.

• On a Portfolio-level project, incentives from the larger facilities can be applied to offset the costs for the smaller facilities.

50ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 51: Navy Case Study - Base Load Optimization

LOBOS DR Web Home Page

LOBOS allows customers to login from the web.

51ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 52: Navy Case Study - Base Load Optimization

AHU Selection Dashboard

52ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 53: Navy Case Study - Base Load Optimization

Portfolio Bid Allocation Dashboard

53ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

The Portfolio Demand Response Module is intended to be a master control for the individual site DR programs. It will allocate individual kW reduction values to the various sites if they are enabled for DR control.

Page 54: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Central Plant Configuration Dashboard

54ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 55: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Typical Air Handler Configuration Dashboard

5555ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 56: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Our Air Handler Summary Page allows you to view what stage each individual AHU is curtailing too.

5656ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 57: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Dashboard allows you to schedule your individual building on a rotating block curtailment based on the value you input and the time you schedule the event.

5757ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 58: Navy Case Study - Base Load Optimization

Automated Demand Response

LOBOS ADR Configuration & Set-up Dashboard

58ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 59: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Lighting Equipment -up to 20 different zones can be incorporatedSelect the stage # from the individual drop down menu to begin turning off the lighting group when the stage selected is activated (set to zero to Disable DR Control)

5959ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 60: Navy Case Study - Base Load Optimization

LOBOS Demand Response

Miscellaneous Equipment - up to 20 different zones can be incorporated Select the stage # from the individual drop down menu to begin turning off the lighting group when the stage selected is activated (set to zero to disable DR).

60ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 61: Navy Case Study - Base Load Optimization

Demand Response and Automatic AHU Coasting Cycle Showing Fan Speed Reduction after 5:00 PM Based on Floor Loading

61ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 62: Navy Case Study - Base Load Optimization

Summary

• LOBOS Design and Control strategies save energy while improving tenant comfort and temperature control.

• By packaging the LOBOS system and using it in conjunction with the existing EMS network infrastructure, costs can be dramatically reduced.

• User flexibility is enhanced by allowing the operators to tune their facilities without having to enter the EMS programming code.

• LOBOS helps reduce cooling system related energy consumption by 30% to 50% or more.

• LOBOS has been integral to the success of many energy savings projects.

• LOBOS enables you to easily tune your system, which is the key to its long-term success.

62ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 63: Navy Case Study - Base Load Optimization

Q&A

63ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Page 64: Navy Case Study - Base Load Optimization

64ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.

Presented by:

Scot M. Duncan, [email protected]

949 370 8582 enerliance.com

roi-engineering.com