SDG&E – Pt. Loma Naval Base Chiller Plant Upgrade Cuts Energy by over 70% Annually using the Load Based Optimization System [LOBOS] California Center for Sustainable Energy 9-14-11
• We offer this presentation in the memory of Gary Gates, a Navy man that fought tirelessly to save energy while improving working conditions for Navy personnel. He is sorely missed by all who knew him.
ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution. 2
GE Ecomagination Challenge
• The Ecomagination Challenge is a worldwide competition sponsored by General Electric to identify viable strategies to reduce energy waste and consumption, as well as viable methods to effectively produce renewable energy and improve grid/system performance on a global basis.
• Out of 3,800 entries received and evaluated by GE, Enerliance is the only firm with two entries in the top 100.
3ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
“Poor controls can waste more energy than great equipment can save.”
Prius with “Efficient” HVAC Control Strategies16 MPG
Prius with “Load Based” HVAC Control 99 MPG
11.9 MPG on the Prius
Why LOBOS?
4ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Project Description
• The Building 56 Chiller plant at the Pt. Loma Naval Base serves 24/7 loads including data centers, office areas and computerized training labs and other classified areas that we could tell you about, but then we’d have to kill you.
• The project consisted of adding one new 450 ton VFD centrifugal chiller to the two existing 350 ton VFD centrifugal chillers, adding VFD’s to the primary and condenser water pumps, removing a multitude of tertiary pumps from the buildings and installing the Load Based Optimization System (LOBOS) to optimize the system.
5ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
History
• The Navy had installed a well marketed optimization system from another firm on a previous project, but after two years of operation, it was not meeting expectations.
• When this project was brought up, there was a huge pushback from many in the Navy, due to concerns about not meeting expectations.
• They reviewed real operational data from several Load Based Optimization System projects and decided to utilize this system for their project.
6ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
History
• Prior to the Load Based Optimization System (LOBOS) installation, the plant was run 24/7 with fixed CHWS temperatures and differential pressure setpoints, as there was no feedback from the loads to allow the system to be run more effectively.
• The timing of the cooling load needs at night and on weekends is based on the use of the data centers and trainers, and is totally unpredictable.
7ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Results
• After one year of operation, the M&V process has shown that the results have exceeded savings expectations by over 50%.
• There has been a net reduction of energy used in the chiller plant of over 70%, based on a separate utility meter.
• Additional scope incorporated into the project have added approximately 1,000 MWH of savings that were not expected.
8ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Plant load 325 tons, Total Plant = 0.28 kW/ton (note the OSA humidity at 105% - previously existing sensor, and why we do not use RH in any of our code…)
9ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Many existing loads still have 3-way valves, so secondary flow and pump energy is still higher than it needs to be. Low CHW temperature differential from 3-ways also drives primary pump energy higher than it needs to be, so we could eventually get down to 0.22 to 0.25 kW/ton for the entire plant under similar conditions.
10ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Multiple CT control loops to optimize the chiller plant while protecting the chillers
11ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Obvious Savings Directly Attributed to LOBOS
12ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Savings during “Limited Reset Operation” during commissioning were running 45% until Nov. when we were directed to shut LOBOS off. Savings for “Equipment only” changes ran about 12% for the month that LOBOS was shut off. When restarted, savings went back to 45% -50%. When full LOBOS resets were allowed in June, savings climbed to 73%-75% per month.
13ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Savings during “Limited Reset Operation” during commissioning were running 45% until Nov. when we were directed to shut LOBOS off. When restarted, savings went back to 45% -50%. When full LOBOS resets were allowed in June, savings climbed to 73%-75% per month.
Nozzle Spray pattern – very little coverage of fill – design flow rate
14ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Approximate 14” to 16” wide dry area at the bottom of the fill with the CT fan in
bypass (100% speed) and design CDW flow
15ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Bottom of the fill with the fan in bypass –100% speed, design flow rate
16ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Bottom of fill with the CT fan off, design flow rate
17ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
One cell open to flow – Design flow –1100 GPM
18ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Solids Buildup with new fill.It is obvious where water is flowing and where water is not
flowing. There is more surface area with solids build up than there is
clean area where water is flowing.
19ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Scaling/Solids
• It can be seen from these pictures that scale is already forming on the fill which has been installed for approximately 6 months.
• We rectified the issue by installing nozzles that were two sizes smaller, and getting up inside the towers and directing the spray nozzles to wet the entire fill at low flow rates.
• Works even better at high flow rates.
• Allows much better use of the CT system, as well as reducing CDW pump energy waste and improving chiller energy performance.
20ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Future Savings Projects at Pt. Loma• New fan coil units are being selected
at 350 feet per minute face velocity to double CHW system temperature differential, improving overall system efficiency markedly.
• LOBOS being applied to new FCU’s.
21ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS
• Minimize Financial Risk, Maximize Owner Savings
• LOBOS Energy Efficiency (EE) and LOBOS Demand Response (DR) patent protected logic are pre-programmed, pre-tested and pre-commissioned software and hardware solutions that maximize owner savings while minimizing the financial risks and loss of time associated with installing advanced control system routines.
22ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS: How It Works
• Energy Efficiency and Demand Response control logic is contained in the LOBOS system.
• LOBOS integrates into the existing DDC Systems via the OPC server, LonTalk or BACnet software or hardware driver.
• The operating data from the HVAC system is gathered by LOBOS; the control setpointsare calculated and sent back out to the local DDC panels for an optimized PID loop control.
23ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Simple & Sustainable
• Energy Efficiency
– Most Energy Management Systems (EMS) leave a substantial amount of savings on the table
– In many cases, complex or non-adjustable optimization programs are disabled or overridden so Facility Engineers can keep tenants comfortable.
24ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Control Strategy• Make it consistent / repeatable from
building-to-building.
• Make it user-friendly so the Operator can make adjustments within certain parameters.
• Make it self tuning to account for system/climate variations.
• Improve tenant experience, reduce energy costs and consumption.
25ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Pick the Right Optimization Strategy!
• Central Plant Optimization routines must look at the site loads – without knowing AHU load information, you cannot maximize energy savings, or respond to load changes properly.
• AHU Optimization routines are required to minimize energy use and promote occupant comfort! Don’t ignore 40% to 50% of the energy consumption of the cooling system!
• The System Must be Operator Friendly – If the person that designed it cannot explain it in an understandable manner to the people that operate the facility, it is too complex.
26ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Status at a Glance Efficiency Speedometer
The LOBOS Efficiency Speedometer is dynamic in nature.
The levels of efficiency change with the loads.
27ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
AHU Set-up Screen
This page presents an overview of the information for each particular AHU. There is general information for the central plant and a summary of the WCAH values being utilized to drive LOBOS. On this page, the user can opt in/out the particular AHU to be monitored by LOBOS.
28ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
AHU Supply Temperature Tuning
29ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
The Supply Air Temperature Setpoint tuning page allows for setting up the supply fan speed setpoint, which should be set as the value that the operators would like to see the fan speed run at.
AHU Supply Duct Static Tuning
30ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
The Supply Static Pressure Setpoint tuning page gives adjustability for how aggressive the setpoint will change to widening return air temperature deviation and space temperature deviation.
LOBOS Air Handler Overview
31ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Provides an overview of values used in establishing Worst Case AHU Size/Criticality/Distance.
All floors are not loaded alike – the Plant Optimization system must consider all loads!
LOBOS Central Plant Optimization
32ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
To make the CHWS temperature and CHW DP adjustments faster or slower, the slide bars can be used to double the gain, or cut the gain in half, or any amount between them.
Condenser water return temperature
Condenser water supply temperature
Chiller kW per ton of cooling
Chilled water return temperature
Temp Scale kW/ton Scale
Chilled water supply temperature
Effects of Changing CDW Temp Setpoint on VFD Chiller System Efficiency
33ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Case Study – 75% savings at the Navy Point Loma Project
• This project installed one new variable speedchiller, instituted a “variable everything” chilledwater pumping system and implemented theLOBOS software into the existing EMS.
• Overall annual efficiency is running around 0.52kWh per ton and at around 200 tons the plantruns at around 0.36 kW/ton.
• The plant operation should be reduced by over1,500 hours per year, due to “Thermal Flywheel”logic in the control scheme that shuts downchillers and uses the cold water that is in the pipesto meet small loads.
34ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Building 56 at Naval Base Point Loma – kWH monthly savings.
35ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
At the current savings rates, the chiller plant / LOBOS upgrade savings will exceed projected savings by more than 55 percent.
Monthly Average kWh Consumption for Pre and Post TES System Upgrade [From Utility Meter]
36ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
18350 Von Karmen Chiller Plant Monthly Energy Consumption (average, excluding 2003 due to low occupancy)
100,000
200,000
300,000
400,000
500,000
1 2 3 4 5 6 7 8 9 10 11 12
kWh
/mo
Post Modification Pre-Modification
Average Monthly Energy Savings From TES Upgrade Project
37ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
18350 Von Karmen Chiller Plant Monthly % savings (average, excluding 2003 due to low occupancy)
0%
10%
20%
30%
40%
50%
60%
1 2 3 4 5 6 7 8 9 10 11 12Chiller Plant Monthly % savings
Case Study 600 B Street San DiegoOptimized Plant vs. Normal Operation/Equipment
38ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Case Study Inland Center Mall
• LOBOS control strategies can optimize CHWsupply temperature and CDW supplytemperature, as well as AHU variables.
• Total chiller plant energy efficiency on thefollowing sample project is averaging less than0.50 kW/ton, even on 100°F days.
• Total Plant includes all chillers, chilled waterpumps, condenser water pumps and coolingtowers.
39ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
E-mail from Dave Manley – 86% HVAC System Energy Reduction
Gentlemen,• If we reduce usage anymore…we can turn everything off
and go home! Overall usage down an amazing 55.89% from last year. HVAC usage down 86.59% from last year, triple checked figures. Duncanization didn’t effect Tower water usage like it did last month. Total monthly breakdown usage shows HVAC = 22%, INTERIOR = 50%, EXTERIOR = 28%. Only increase was in #2 COM. AREA due to increase in RMU’s and contractors using common area power during TI’s.
• David Manley | Operations Manager• Inland Center Mall• 500 Inland Center• San Bernardino, CA, 92408
40ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Chiller Plant Snapshot: Inland Center Mall
Chiller @ 0.32 kW/tonTotal chiller plant @ 0.45 kW/ton, including pumps, chillers and CTF’s
100°F OSA.
41ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Complete Day Performance: Tons & kW/ton
42ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Complete Day Performance: Tons and kW/ton
43ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Case Study10-Story Office Building; 80% Energy Efficiency Improvement
44ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Total Plant Efficiency @ 0.38 kW/Ton
At 33% load on the chiller, the total HVAC system, including fans and central plant equipment is using 0.51kW per ton.
45ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Total Plant Efficiency @ 0.33 kW/Ton
At 55% load on the chiller, the total HVAC system, including fans and central plant equipment is using .52kW per ton.
46ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
2040 Main Street750 Ton VFD Chiller System
47ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Energy Efficiency Summary
48ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
• Properly designed and applied TES systems can reduce site and source energy consumption and enable wind power to become a viable part of the energy infrastructure.
• Energy Efficiency, Demand Response and Demand Reduction Technologies are not mutually exclusive!
• You can start with the most efficient design possible, which reduces demand, then add demand response software and Thermal Energy Storage (TES) if/when appropriate.
• With TES, airside Demand Response controls can be added to further reduce site demand, over and above the central plant peak demand savings.
• It is possible to reduce energy consumption at the site and source, while simultaneously reducing peak electrical demands and T&D congestion and improving occupant comfort.
• It is not cheap, but the benefits and GHG emission reductions are substantial.
LOBOS Demand Response (LOBOS DR)
49ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS DR• Typical DR Control systems require substantial manual
intervention and often do not get utilized because of the manpower costs associated with enabling them.
• The LOBOS DR 10 Stage is a fully automatic DR control system that can be applied to an individual building or across an entire portfolio.
• The system is as close to set it and forget it as you can get.
• Depending upon the facility size and the demand reduction potential at the site, the SCE Technical Installation Incentive may cover the entire cost of the DR system, thus eliminating any owner out of pocket expense.
• On a Portfolio-level project, incentives from the larger facilities can be applied to offset the costs for the smaller facilities.
50ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS DR Web Home Page
LOBOS allows customers to login from the web.
51ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
AHU Selection Dashboard
52ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Portfolio Bid Allocation Dashboard
53ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
The Portfolio Demand Response Module is intended to be a master control for the individual site DR programs. It will allocate individual kW reduction values to the various sites if they are enabled for DR control.
LOBOS Demand Response
Central Plant Configuration Dashboard
54ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Demand Response
Typical Air Handler Configuration Dashboard
5555ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Demand Response
Our Air Handler Summary Page allows you to view what stage each individual AHU is curtailing too.
5656ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Demand Response
Dashboard allows you to schedule your individual building on a rotating block curtailment based on the value you input and the time you schedule the event.
5757ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Automated Demand Response
LOBOS ADR Configuration & Set-up Dashboard
58ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Demand Response
Lighting Equipment -up to 20 different zones can be incorporatedSelect the stage # from the individual drop down menu to begin turning off the lighting group when the stage selected is activated (set to zero to Disable DR Control)
5959ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
LOBOS Demand Response
Miscellaneous Equipment - up to 20 different zones can be incorporated Select the stage # from the individual drop down menu to begin turning off the lighting group when the stage selected is activated (set to zero to disable DR).
60ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Demand Response and Automatic AHU Coasting Cycle Showing Fan Speed Reduction after 5:00 PM Based on Floor Loading
61ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.
Summary
• LOBOS Design and Control strategies save energy while improving tenant comfort and temperature control.
• By packaging the LOBOS system and using it in conjunction with the existing EMS network infrastructure, costs can be dramatically reduced.
• User flexibility is enhanced by allowing the operators to tune their facilities without having to enter the EMS programming code.
• LOBOS helps reduce cooling system related energy consumption by 30% to 50% or more.
• LOBOS has been integral to the success of many energy savings projects.
• LOBOS enables you to easily tune your system, which is the key to its long-term success.
62ROI | Retrofit Originality Incorporated Proprietary and Confidential. Not for distribution.