National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for...

29
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org MEMORANDUM TO: Technical Committee on Electrical Equipment Maintenance FROM: Sarah Caldwell, Project Administrator DATE: May 10, 2017 SUBJECT: NFPA 70B First Draft Technical Committee FINAL Ballot Results (F2018 Cycle) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 24 Members Eligible to Vote 3 Members Not Returned (Cunningham, Johnson, Schultheis) The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections 3.3.4.3.(c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards.

Transcript of National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for...

Page 1: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

 

M E M O R A N D U M

TO: Technical Committee on Electrical Equipment Maintenance FROM: Sarah Caldwell, Project Administrator DATE: May 10, 2017 SUBJECT: NFPA 70B First Draft Technical Committee FINAL Ballot Results (F2018 Cycle)

According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

24 Members Eligible to Vote 3 Members Not Returned (Cunningham, Johnson, Schultheis)

The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each revision.

To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2/3 of ballots returned. See Sections 3.3.4.3.(c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards.

Page 2: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 1-NFPA 70B-2017 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this recommended practiceand should be considered part of the recommendations of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 70E®, Standard for Electrical Safety in the Workplace®, 2015 2018 edition.

NFPA 110, Standard for Emergency and Standby Power Systems, 2016 2019 edition.

NFPA 496, Standard for Purged and Pressurized Enclosures for Electrical Equipment, 2013 2017 edition.

NFPA 780, Standard for the Installation of Lightning Protection Systems, 2014 2017 edition.

NFPA 791, Recommended Practice and Procedures for Unlabeled Electrical Equipment Evaluation,2014 2018 edition.

NFPA 1600®, Standard on Disaster/Emergency Management and Business Continuity/Continuity ofOperations Programs, 2016 2019 edition.

2.3 Other Publications.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 28 5/10/17, 2:28 PM

Page 3: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

2.3.1 ASTM Publications.

American Society for Testing and Materials ASTM International , 100 Barr Harbor Drive, P.O. Box C700 ,West Conshohocken, PA 19428-2959.

ASTM D92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester,2012b 2016a .

ASTM D445, Standard Test Method for Kinematic Viscosity of Transparent and Opaque Liquids andCalculation of Dynamic Viscosity, 2012 2015a .

ASTM D664, Standard Test Method for Acid Number of Petroleum Products by PotentiometricTitration,2011a 2011e1 .

ASTM D877/D877M , Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids UsingDisk Electrodes, 2013.

ASTM D923, Standard Practices for Sampling Electrical Insulating Liquids,2007 2015 .

ASTM D924, Standard Test Method for Dissipation Factor (or Power Factor) and Relative Permittivity(Dielectric Constant) of Electrical Insulating Liquids,2008 2015 .

ASTM D971, Standard Test Method for Interfacial Tension of Oil Against Water by the Ring Method, 2012.

ASTM D974, Standard Test Methods for Acid and Base Number by Color-Indicator Titration,2012 2014e2 .

ASTM D1298, Standard Test Method for Density, Relative Density (Specific Gravity), or API Gravity ofCrude Petroleum and Liquid Petroleum Products by Hydrometer Method, 2012b.

ASTM D1500, Standard Test Method for ASTM Color of Petroleum Products (ASTM Color Scale), 2012.

ASTM D1524, Standard Test Method for Visual Examination of Used Electrical Insulating Oils ofPetroleum Origin in the Field,1994 (revised 2010) 2015 .

ASTM D1533, Standard Test Method for Water in Insulating Liquids by Coulometric Karl Fischer Titration,2012.

ASTM D1816, Standard Test Method for Dielectric Breakdown Voltage of Insulating Oils of PetroleumOrigin Using VDE Electrodes, 2012.

ASTM D2129, Standard Test Method for Color of Clear Electrical Insulating Liquids (Platinum-CobaltScale), 2005 (revised 2010).

ASTM D2472, Standard Specification for Sulfur Hexafluoride,2000 (revised 2006) 2015 .

ASTM D3284, Standard Practice for Combustible Gases in the Gas Space of Electrical Apparatus UsingPortable Meters, 2005 (revised 2011).

ASTM D3612, Standard Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil by GasChromatography, 2002 (revised 2009).

2.3.2 EASA Publications.

Electrical Apparatus Service Association, Inc. , 1331 Baur Blvd, St. Louis, MO 63132.

ANSI/EASA AR100, Recommended Practice for the Repair of Rotating Electrical Apparatus,2010 2015 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 28 5/10/17, 2:28 PM

Page 4: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

2.3.3 IEEE Publications.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 28 5/10/17, 2:28 PM

Page 5: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

IEEE, Three Park Avenue, 17th Floor, New York, NY 10016-5997.

ANSI/ IEEE 43, Recommended Practice for Testing Insulation Resistance of RotatingMachinery,2000 2013 .

ANSI/ IEEE 80, Guide for Safety in AC Substation Grounding,2000 2013 .

IEEE 81, Guide for Measuring Earth Resistivity, Ground Impedance and Earth Surface Potentials of aGround System, 2012.

ANSI/ IEEE 95, Recommended Practice for Insulation Testing of AC Electric Machinery (2300 V andAbove) with High Direct Voltage,2002 , reaffirmed 2012 .

ANSI/ IEEE 141, Recommended Practice for Electric Power Distribution for Industrial Plants (IEEE RedBook) , 1993, revised 1999.

ANSI/ IEEE 142, Recommended Practice for Grounding of Industrial and Commercial Power Systems(IEEE Green Book) , 2007, Errata, 2014 .

ANSI/ IEEE 241, Recommended Practice for Electric Power Systems in Commercial Buildings (IEEEGray Book) , 1990.

ANSI/ IEEE 242, Recommended Practice for Protection and Coordination of Industrial and CommercialPower Systems (IEEE Buff Book) , 2001, Errata, 2003 .

ANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEEBrown Book) , 1997.

ANSI/ IEEE 400, Guide for Field Testing and Evaluation of the Insulation of Shielded Power CableSystems, 2012.

IEEE 400.1, Guide for Field Testing of Laminated Dielectric, Shielded Power Cable Systems Rated 5 kVand Above with High Direct Current Voltage, 2007.

IEEE 400.2, Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF)Less Than 1 Hertz, 2013.

IEEE 400.3, Guide for Partial Discharge Testing of Shielded Power Cable Systems in a FieldEnvironment,2006 2015 .

ANSI/IEEE 446, Recommended Practice for Emergency and Standby Power Systems for Industrial andCommercial Applications (IEEE Orange Book) , 1995, revised 2000.

ANSI/IEEE 450, Recommended Practice for Maintenance, Testing and Replacement of Vented Lead-AcidBatteries for Stationary Applications, 2010.

ANSI/IEEE 493, Recommended Practice for the Design of Reliable Industrial and Commercial PowerSystems (IEEE Gold Book) , 2007.

ANSI/IEEE 519, Recommended Practices and Requirements for Harmonic Control in Electrical PowerSystems,1992 2014 .

IEEE 637, Guide for Reclamation of Insulating Oil and Criteria for Its Use, 1985. (Superseded by IEEEC57.637.)

ANSI/ IEEE 1100, Recommended Practice for Powering and Grounding Electronic Equipment (IEEEEmerald Book) , 2005.

IEEE 1106, Recommended Practice for Installation, Maintenance, Testing and Replacement of VentedNickel-Cadmium Batteries for Stationary Applications,2005, revised 2011 2015 .

ANSI/IEEE 1125, Guide for Moisture Measurement and Control in SF6Gas-Insulated Equipment, 1993,

revised 2000. (Superseded by IEEE C37.122.5.)

IEEE 1159, Recommended Practice on Monitoring Electric Power Quality, 2009.

IEEE 1188, Recommended Practice for Maintenance, Testing and Replacement of Valve-Regulated LeadAcid (VRLA) Batteries for Stationary Applications, 2005 (r2010 with 2014 amendment) .

IEEE 1578, IEEE Recommended Practice for Stationary Battery Electrolyte Spill Containment andManagement, 2007.

IEEE 1584™, Guide for Performing Arc Flash Hazards Calculations, 2002 (with Amendment 1 and 2).

IEEE 1657, IEEE Recommended Practice for Personnel Qualifications for Installation and Maintenance of

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 28 5/10/17, 2:28 PM

Page 6: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Stationary Batteries, 2009 (2015 amendment) .

IEEE 3007.2, IEEE Recommended Practice for the Maintenance of Industrial and Commercial PowerSystems, 2010.

ANSI/Accredited Standards Committee IEEE C2, National Electrical Safety Code®(NESC®),2012 2017 .

ANSI/IEEE C37.13, Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures,2008 2015 .

IEEE C37.20.1, Standard for Metal-Enclosed Low-Voltage (1000 Vac and Below, 3200 Vdc and Below)Power Circuit Breaker Switchgear, 2002 2015 .

IEEE C37.23, Standard for Metal-Enclosed Bus, 2003 2015 .

IEEE C37.122.1, IEEE Guide for Gas-Insulated Substations Rated Above 52 kV , 1993, revised2002 2014 .

IEEE C37.122.5, Guide for Moisture Measurement and Control SF 6 Gas-Insulated Equipment , 2013.

ANSI/IEEE C57.104, Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers,2008.

ANSI/IEEE C57.106, Guide for Acceptance and Maintenance of Insulating Oil in Equipment,2006 2015 .

ANSI/IEEE C57.110, Recommended Practice for Establishing Liquid-Filled and Dry-Type Power andDistribution Transformer Capability When Supplying Nonsinusoidal Load Currents, 2008.

ANSI/IEEE C57.111, Guide for Acceptance of Silicone Insulating Fluid and Its Maintenance inTransformers,1989, revised 2009. 1995 (2009).

ANSI/IEEE C57.121, Guide for Acceptance and Maintenance of Less-Flammable Hydrocarbon Fluid inTransformers, 1998.

IEEE C57.637, Guide for the Reclamation of Mineral Insulating Oil and Criteria for its Use , 2015.

2.3.4 ITI Publications.

Information Technology Industry Council, 1250 Eye 1101 K Street, NW, Suite 200 610 , Washington, DC20005. 202-737-8880. http://www.itic.org.

ITI (CBEMA) Curve Application Note, 2000.

2.3.5 NEMA Publications.

National Electrical Manufacturers Association, 1300 North 17th Street, Suite 1847, Rosslyn 900,Arlington , VA 22209.

Evaluating Water-Damaged Electrical Equipment, 2014.

Evaluating Fire- and Heat-Damaged Electrical Equipment, 2013.

ANSI/NEMA AB 4, Guidelines for Inspection and Preventive Maintenance of Molded-Case CircuitBreakers Used in Commercial and Industrial Applications, 2009.

ANSI/NEMA C84.1, Electric Power Systems and Equipment, Voltage Ratings (60 Hertz), 2011.

ANSI/NEMA KS 3, Guidelines for Inspection and Preventive Maintenance of Switches Used inCommercial and Industrial Applications, 2010.

NEMA MG 1, Motors and Generators, 2011 2016 .

ANSI/NEMA PB 2.1, General Instructions for Proper Handling, Installation, Operation, and Maintenance ofDead Front Distribution Switchboards Rated 600 Volts or Less, 2013.

ANSI/ NEMA WD 6, Wiring Devices and — Dimensional Specifications, 2012 2016 .

2.3.6 NETA Publications.

InterNational Electrical Testing Association, P.O. Box 687, Morrison, CO 80465. 3050 Old Centre Ave.,Suite 102, Portage, MI 49024.

ANSI/NETA ATS, Standard for Acceptance Testing Specifications for Electrical Power DistributionEquipment and Systems, 2013 2017 .

ANSI/NETA MTS, Standard for Maintenance Testing Specifications for Electrical Power DistributionEquipment and Systems, 2011 2015 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 28 5/10/17, 2:28 PM

Page 7: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

2.3.7 OSHA Publications.

Occupational Safety and Health Administration, 200 Constitution Ave., NW, Washington, DC 20210.

OSHA Safety & Health Information Bulletin (SHIB), “Certification of Workplace Products by NationallyRecognized Testing Laboratories,” 02-16-2010.

2.3.8 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and Circuit Breaker Enclosures,Twelfth edition, 2013.

ANSI/UL 943, Standard for Ground-Fault Circuit Interrupters, Fourth 5th edition, 2006 (revised2010) 2016 .

UL 1436, Outlet Circuit Testers and Similar Indicating Devices, Fifth edition, 2014.

UL Firefighter Safety and Photovoltaic Installations Research Project, November 2011.

2.3.9 U.S. Government Publications.

U.S. Government Printing Office, Washington, DC 20402-9328. Publishing Office, 732 North CapitolStreet, NW, Washington, DC 20401-0001.

Federal Emergency Management Agency (FEMA), FEMA P-348, Protecting Building Utilities from FloodDamage, 1999 updated 2012.

Title 29, Code of Federal Regulations, Part 1910.

Title 29, Code of Federal Regulations, Part 1910.94(a), “Occupational Health and Environmental Control— Ventilation.”

Title 29, Code of Federal Regulations, Part 1910.94(a), “Occupational Health and Environmental Control— Ventilation.”

Title 29, Code of Federal Regulations, Part 1910.146, “Permit-Required Confined Spaces.”

Title 29, Code of Federal Regulations, Part 1910.242(b), “Hand and Portable Powered Tools and OtherHand Held Equipment.”

Title 29, Code of Federal Regulations, Part 1910.269, “Electric Power Generation, Transmission, andDistribution,” Paragraph (e), Enclosed Spaces.

Title 29, Code of Federal Regulations, Part 1910.331 through Part 1910.335, “Safety Related WorkPractices.”

Title 29, Code of Federal Regulations, Part 1926.

Title 40, Code of Federal Regulations, Part 761, “Protection of Environment — Polychlorinated Biphenyls(PCBs) Manufacturing, Processing, Distribution in Commerce, and Use Prohibitions.”

TM 5-694, Commissioning of Electrical Systems for Command, Control, Communications, Computer,Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities, 2006.

TM 5-698-1, Reliability/Availability of Electrical and Mechanical Systems for Command, Control,Communications, Computer, Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities, 2007.

TM 5-698-2, Reliability-Centered Maintenance (RCM) for Command, Control, Communications, Computer,Intelligence, Surveillance, and Reconnaissance (C4ISR) Facilities, 2006.

TM 5-698-3, Reliability Primer for Command, Control, Communications, Computer, Intelligence,Surveillance, and Reconnaissance (C4ISR) Facilities, 2005.

Toxic Substances Control Act, Environmental Protection Agency, www.epa.gov/agriculture/lsca.html.

U.S. General Services Administration and U.S. Department of Energy, Building Commissioning Guide,2009.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 28 5/10/17, 2:28 PM

Page 8: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

2.3.10 Other Publications.

ABB Power T & D Company, Inc., Instruction Book PC-2000 for Wecosol TM Fluid-Filled Primary andSecondary Unit Substation Transformers.

Merriam-Webster's Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

Penn-Union Catalog, http://www.penn-union.com/Services/Literature.

PowerTest Annual Technical Conference, Flood Repair of Electrical Equipment, Pat Beisert, ShermcoIndustries, March 12, 2009.

Square D Catalog, Schneider Electric, www.schneider-electric.com/us.

Square D Services, Procedures for Startup and Commissioning of Electrical Equipment, PDF available athttp://static.schneider-electric.us/docs/Electrical%20Distribution/Services/New%20Installation%20Services/O18OIB0001.pdf http://www.schneider-electric.us/en/download/document/0180IB0001/

2.4 References for Extracts in Recommendations Sections.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 70E®, Standard for Electrical Safety in the Workplace®, 2015 2018 edition.

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 10:29:08 EST 2017

Committee Statement

CommitteeStatement:

Referenced documents updated for current SDO names, addresses, standard names,numbers, and editions.

Response Message:

Public Input No. 46-NFPA 70B-2016 [Chapter 2]

Public Input No. 70-NFPA 70B-2017 [Section No. 2.3.1]

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

19 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Cunningham, Karl M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 28 5/10/17, 2:28 PM

Page 9: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Hall, Jeffrey

Update UL 1436 publication "Outlet Circuit Testers and Similar Indicating Devices" to indicate Sixth edition 2016

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 28 5/10/17, 2:28 PM

Page 10: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 2-NFPA 70B-2017 [ Section No. 9.1 [Excluding any Sub-Sections] ]

Electrical studies are an integral part of system design, operations, and maintenance. These engineeringstudies generally cover the following areas:

(1) Short-circuit studies

(2) Coordination studies

(3) Load-flow studies

(4) Reliability studies

(5) Risk Assessment assessment study

(6) Maintenance-related design study

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 11:23:08 EST 2017

Committee Statement

CommitteeStatement:

A maintenance related design study similar to that as detailed in NFPA 70E Informative Annex OSafety-Related Design Requirements is a logical step after performing a risk assessment study.This study can provide design alternatives which if implemented may enhance work place safety forelectrical maintenance related work practices.

ResponseMessage:

Public Input No. 69-NFPA 70B-2017 [Section No. 9.1 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

20 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Cunningham, Karl M.

Johnson, Darrel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 28 5/10/17, 2:28 PM

Page 11: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 28 5/10/17, 2:28 PM

Page 12: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 3-NFPA 70B-2017 [ New Section after 9.6 ]

9.7 Maintenance-Related Design Study.

9.7.1

A maintenance-related design study uses the risk assessment study as input and evaluates designconcepts for electrical equipment and installations that impact the safety of maintenance practices. Theobjective is to develop design options that eliminate or reduce hazards or reduce risk. Facilitiesmanagement can use this study to assist in making decisions on implementing changes to the electricalequipment.

9.7.2

After the risk assessment study in Section 9.6 is completed, a maintenance-related design studyshould be performed.

9.7.3

For more information, see the safety-related design requirements in Informative Annex O ofNFPA 70E .

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 11:44:22 EST 2017

Committee Statement

CommitteeStatement:

A maintenance related design study similar to that as detailed in NFPA 70E Informative Annex OSafety-Related Design Requirements is a logical step after performing a risk assessment study.This study can provide design alternatives which if implemented may enhance work place safety forelectrical maintenance related work practices.

ResponseMessage:

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

18 Affirmative All

3 Affirmative with Comments

0 Negative with Comments

0 Abstention

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 28 5/10/17, 2:28 PM

Page 13: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Not Returned

Cunningham, Karl M.

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Bingham, Richard

though the material added is useful in general, its another item that is not really a task for the target audience ofthe document, the electrical maintenance person. we should be prudent not to expand on this in future revisions.

Crnko, Timothy

Task Group of A. Corbett, W. Harris, J. White, and T.Crnko expanded 9.7 to be considered in the 2nd DraftMeeting as follows: 9.7 Maintenance Related Design Study 9.7.1 A maintenance related design study shoulddevelop design options that eliminate or reduce hazards or reduce risk for daily or maintenance operations. Thisstudy should use input that may include the electrical system design, equipment maintenance instructions, thecompany’s historical maintenance data, as well as results of other studies such as the reliability and the riskassessment studies. The study should evaluate design and operational concepts for electrical equipment andinstallations which impact the safety of maintenance practices and then makes recommendations forimprovement. Facilities management should use this study to make decisions for implementing. Designconsiderations to enhance operations should include the entire life cycle cost of the building or system. The initialcost for efficient use of energy and to provide an efficient maintenance environment should be considered asvaluable long term investments that support daily operations. Workspaces and systems should be designed toallow safe maintenance or urgent repair while other operations continue. System monitoring equipment can beused for planning predictive maintenance and help prevent unplanned outages. 9.7.2 A maintenance relateddesign study should include evaluating various options such as maintenance-related design elements are allowingsufficient clearances to remove and install drawout circuit breakers, installation of remote operating controls andremote racking for circuit breakers, installation of lift mechanisms to allow safe removal of drawout circuitbreakers, installation of motor control centers with the capabilities for individual buckets to be racked in or outremotely, installation of permanently-mounted absence-of-voltage testers, performing an incident energy analysis

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 28 5/10/17, 2:28 PM

Page 14: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

in addition to short circuit and coordination studies, designing redundancy into the electrical power system tofacilitate safe maintenance work practices, installation of motor overload relays so they can be reset withoutexposing the worker to energized conductors or circuit parts, installation of infrared windows to allow for testingand inspection without exposing workers to energized parts, thermal sensors for critical terminations, ultrasonicsensors in medium voltage equipment, partial discharge monitoring of critical cables and equipment, andinstallation of automatic transfer switches with maintenance by-pass switches. 9.7.3 After the risk assessmentstudy in 9.6 is complete, NFPA 70E Informative Annex O Safety-Related Design Requirements should bereferenced for other items to consider for evaluating in the maintenance related design study.

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 28 5/10/17, 2:28 PM

Page 15: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 7-NFPA 70B-2017 [ Section No. 9.6.1.1 ]

9.6.1.1

A risk assessment study is an important consideration for electrical safe work practices. Refer toChapter 3 for definitions of arc flash hazard and arc flash hazard analysis . Refer to NFPA 70Efor useof the incident energy analysis method or the hazard/risk category (HRC) method. for guidance on riskassessment and selection of PPE.

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 14:03:03 EST 2017

Committee Statement

Committee Statement: The section is updated to conform with current edition of NFPA 70E.

Response Message:

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

19 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Cunningham, Karl M.

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 28 5/10/17, 2:28 PM

Page 16: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Hickman, Palmer L.

Revise this sentence as follows to add the concept of hierarchy of control as PPE is a last resort: "Refer to NFPA70E for guidance on risk assessment, hierarchy and selection of PPE."

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 28 5/10/17, 2:28 PM

Page 17: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 4-NFPA 70B-2017 [ Section No. 11.4 ]

11.4 Frequency of Tests.

Most routine testing can best be performed concurrently with routine preventive maintenance, because asingle outage will serve to allow both procedures. For that reason, the frequency of testing generallycoincides with the frequency of maintenance. The optimum cycle depends on the use to which theequipment is put and the operating and environmental conditions of the equipment. many factors such asequipment design, condition, use, age, loading, and duty cycle as well as prior recorded maintenancedata, environmental factors, and reliability requirements. In general, this cycle can range from 6 monthsto 3 years, depending on conditions and equipment use. from 3 months to 6 years. The difficulty ofobtaining an outage should never be a factor in determining the frequency of testing and maintenance.Equipment for which an outage is difficult to obtain is usually the equipment that is most vital in theoperation of the electrical system. Consequently, a failure of this equipment would most likely create themost problems relative to the continued successful operation of the system. In addition to routine testing,tests should be performed any time equipment has been subjected to conditions that possibly could havecaused it to be unable to continue to perform its design function properly. Annex L provides an initialguideline for equipment maintenance intervals. See Section L.1 .

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 12:58:13 EST 2017

Committee Statement

CommitteeStatement:

The revision adds clarity to the requirement. There are many factors to consider in determiningthe intervals for maintenance including testing. It is not a simple one interval serves allinstallations.

ResponseMessage:

Public Input No. 62-NFPA 70B-2016 [Section No. 11.4]

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

20 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 28 5/10/17, 2:28 PM

Page 18: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Cunningham, Karl M.

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 28 5/10/17, 2:28 PM

Page 19: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 5-NFPA 70B-2017 [ Chapter D ]

Annex D Informational References

D.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections ofthis recommended practice and are not part of the recommendations of this document unless also listed inChapter 2 for other reasons.

D.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

D.1.2 Other Publications.

D.1.2.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM D92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup Tester, 2012 2016b .

ASTM D1933, Standard Specification for Nitrogen Gas as an Electrical Insulation Material, 2003 (Rev.2008 revised 2017 ).

D.1.2.2 IEEE Publications.

Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ08855-1331. IEEE, Three Park Avenue, 17th Floor, New York, NY 10016-5997.

ANSI/IEEE 43, Recommended Practice for Testing Insulation Resistance of RotatingMachinery,2000 2013 .

IEEE 100CD , Authoritative Dictionary of IEEE Standards Terms,2000 2013 .

ANSI/ IEEE 315 (ANSI Y32.2-75) , Graphic Symbols for Electrical and Electronics Diagrams, 1975 (Reaff.1993).

IEEE 450, Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-AcidBatteries for Stationary Applications, 2010.

IEEE 1106, Recommended Practice for Installation, Maintenance, Testing and Replacement of VentedNickel-Cadmium Batteries for Stationary Applications, 2005, revised 2011 2015 .

IEEE 1188, Recommended Practice for Maintenance, Testing, and Replacement of Valve-RegulatedLead-Acid (VRLA) Batteries for Stationary Applications, 2005 (2010 with 2014 amendment) .

IEEE C57.12.00, General Requirements for Liquid-Immersed Distribution, Power, and RegulatingTransformers,2010 2015 .

D.1.2.3 NETA Publications.

InterNational Electrical Testing Association, P.O. Box 687, Morrison, CO 80465. 3050 Old Centre Ave.,Suite 102, Portage, MI 49024.

ANSI/NETA MTS, Standard for Maintenance Testing Specifications for Electrical Power DistributionEquipment and Systems,2011 2015 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 28 5/10/17, 2:28 PM

Page 20: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

D.1.2.4 Other Publications.

ANSI C107.1, Guidelines for Handling and Disposal of Capacitor and Transformer-grade AskarelsContaining Polychlorinated Biphenyls, 1974.

IEC 60076-2, Power Transformers — Part 2: Temperature Rise for Liquid-Immersed Transformers ,1993-04-07. , 3rd edition, 2011.

Leiter, David, Distributed Energy Resources, U.S. Department of Energy for Fuel Cell Summit IV,Washington, DC, May 10, 2000.

MIL-STD-339 HNDK-508 , Wiring and Wiring Devices for Combat and Tactical Vehicles, Selection andInstallation of, December 7, 1987 April 21, 1998 , available from Defense Automated Printing Service(Customer Service) DLA Document Services , 700 Robbins Avenue, Building 4D, Philadelphia, PA19111-5094. (Supersedes MIL-STD-339)

RAC Publications, Reliability Tool Kit, page 12.

D.2 Informational References.

The following documents or portions thereof are listed here as informational resources only. They are nota part of the recommendations of this document.

D.2.1 IEEE Publications.

Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ08855-1331. IEEE, Three Park Avenue, 17th Floor, New York, NY 10016-5997.

ANSI/IEEE 1100, Recommended Practice for Powering and Grounding Electronic Equipment (IEEEEmerald Book) , 2005.

D.3 References for Extracts in Informational Sections. (Reserved)

NFPA 70 ® , National Electrical Code ® , 2017 edition.

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 13:29:53 EST 2017

Committee Statement

CommitteeStatement:

Updated referenced standards with current SDO names, addresses, standard names,numbers, and editions.

Response Message:

Public Input No. 47-NFPA 70B-2016 [Chapter D]

Public Input No. 71-NFPA 70B-2017 [Section No. D.1.2.1]

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

20 Affirmative All

1 Affirmative with Comments

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 28 5/10/17, 2:28 PM

Page 21: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

0 Negative with Comments

0 Abstention

Not Returned

Cunningham, Karl M.

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 28 5/10/17, 2:28 PM

Page 22: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

First Revision No. 6-NFPA 70B-2017 [ Section No. L.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 28 5/10/17, 2:28 PM

Page 23: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

L.1 Introduction.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 28 5/10/17, 2:28 PM

Page 24: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

This annex provides, in Table L.1, an initial guideline for maintenance intervals for equipment. It should bestressed that environmental or operating conditions of a specific installation should be considered andmight dictate a different frequency of maintenance than suggested in this annex (see 8.2.4). Chapter 12and Annex K deal specifically with the maintenance of equipment that, by nature of its application,necessitates long intervals between shutdowns. It should be noted that maintenance, inspection, and testmethods for equipment that can operate for long periods are essentially the same as for equipment thatmight be shut down frequently. However, the recommended work should be performed with more care anddiligence to obtain the desired reliability for service to loads that can operate continuously for months oryears.

Table L.1 Interval Guidelines

Item/Equipment Task/Function Interval Reference

Substations (Outdoor) Infrared scanning Annually 11.17

Insulators Visual inspection 4–6 months 15.1.2.1

Corona detection 4–6 months 15.1.2.2

Electrical testsAs indicated byother PM

11.9

ConductorsVisual inspection ofconnections

4–6 months 15.1.3

Check connections fortightness

As indicated byother PM

15.1.3

Air-disconnecting switches Visual inspection 4–6 months 15.1.4.2

Operation check Annually 15.1.4.3

Contact inspection Annually 15.1.4.3

Grounding equipment Visual inspection Annually 15.1.5

Check connections fortightness

1–2 years 15.1.5

Electrical test 3 years 11.13.1, 11.13.2, 11.13.3

Enclosures Security/operational check 1–3 months 15.1.6

Switchgear Assemblies Infrared scanning Annually 11.17

Enclosures Security/operational check 15.2.5

 Outdoor 1–3 months

 Indoor 6 months

Visual inspection 15.2.6 through 15.2.7.2

 Outdoor 1–3 months

 Indoor 6 months

Ventilation Visual inspection 1–3 months 15.2.9

Space heaters Operational check Annually 15.2.8

Insulation Visual inspection/clean Annually15.2.11 through

15.2.15.3

Electrical tests 2 years 11.9

Air Circuit Breakers, Medium Voltage

Insulation Visual inspection/clean Annually 15.4.2

Electrical tests 3 years 11.9

Contacts Visual inspection/clean Annually 15.4.3.5

Adjust Annually 15.4.3.6

Electrical test 3 years11.16.1.2.2, 11.16.1.2.7,

11.9.3.2

Arc interrupters Visual inspection/clean Annually 15.4.4.3, 15.4.4.4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 28 5/10/17, 2:28 PM

Page 25: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Item/Equipment Task/Function Interval Reference

Electrical test 3 years 15.4.4.4

Air-puffer operational check Annually 15.4.4.5

Operating mechanism Visual inspection Annually 15.4.5.2

Operationalcheck/adjustment

Annually 15.4.5.2

Trip device circuit Operational check Annually 15.4.6.3

Air Circuit Breakers, LowVoltage

Visual inspection/clean/adjust

Electrical tests

Annually

3 years15.4, 11.9, 11.10.6

Vacuum Circuit BreakerVisual inspection/clean/adjust

Annually 15.4

Contact checks/vacuumintegrity

3 years 15.5.1, 15.5.2

Electrical tests 3 years 11.9, 11.10.6

Oil Circuit BreakerGeneral inspections andtests

3 years 11.9, 11.16.4.2.5

Bushings Visual inspection/clean 3 years 15.6.2.1

OilDielectric breakdown testlevel

Annually 15.6.2.3, 11.9

Annually 15.6.6

Contacts Resistance check 3 years 15.6.3

Visual inspection 3 years 15.6.3

Interrupter SwitchesSee Air Circuit Breakers,Medium Voltage

15.7

Surge Arresters Visual inspection 15.9.2.1

 Outdoor 3–6 months

 Indoor Annually

Electrical test 3–6 years 15.9.2.2

Capacitors Visual inspection 3–6 months 15.8.3.4

Fuse check 3–6 months 15.8.3.3

Stationary Batteries andChargers

Visual inspection/clean Monthly15.9.4.4 through

15.9.4.4.13

   Torque intercellconnectors Checkconnection resistance

Annually11.14.2.4,

15.9.4.4.11 15.9.4.4.12

   Pilot cell measurements Monthly 11.14.2.2

   All lead–acid cell-specificgravity

Quarterly 11.14.2.1

   Capacity test 1–5 years 11.14.2.3

   Sample connectionresistances

Quarterly 11.14.2.4

   Infrared scanning Annually 11.14.2.5, 11.17

Protective RelaysCleaning, calibration, andfunction tests

15.9.7.3, 11.12

 Electromechanical 1–2 years

 Solid state 3 years

Supervisory Control and Data Acquisition (SCADA)

Electrical/electronic Systems Lamp test/verify indicators Monthly 12.14.11.1, 12.14.11.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 28 5/10/17, 2:28 PM

Page 26: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Item/Equipment Task/Function Interval Reference

   Inspect enclosures for dirt,heat, water

Monthly 8.7.1, Table L.1

Physically exercise valvesand actuators

6 months (Reserved for future)

Actuate switches 6 months (Reserved for future)

Run PLC diagnostics 6 months 22.4.4

Calibrate sensors andtransmitters

Annually 11.7

Calibrate actuators Annually 11.7

Calibrate meters Annually

Test batteries 6 months 15.9.4.6

Test automatic controlsequences

Annually (Reserved for future)

Verify alarms Annually 15.9.6.1, 12.4.11, 15.9.6

Pneumatic system/components Check regulators and filters Monthly (Reserved for future)

Inspect tubing and piping Monthly (Reserved for future)

Actuate pressure switches 6 months (Reserved for future)

Physically exercise valvesand actuators

6 months (Reserved for future)

Calibrate switches andsensors

Annually (Reserved for future)

Calibrate pressure gauges Annually (Reserved for future)

Calibrate thermometers Annually (Reserved for future)

Power and DistributionTransformers

Liquid filled Current and voltage readings Weekly–monthly 21.2.2.2, 21.2.3

Temperature readings Weekly–monthly 21.2.4

Liquid level check Weekly–monthly 21.2.5.1

Pressure/vacuum gaugereadings

Weekly–monthly 21.2.5.2

Liquid analysis Annually 21.2.8

Comprehensive liquid tests Annually 11.11.9, 11.19

Insulation test 3–5 years 21.2.9, 11.9

Turns-ratio test 3–5 years 21.2.9, 11.11.2

Fault gas analysis Annually 21.2.9, 11.11.9

Dissolved-gas-in-oil analysis Annually 11.11.10

Dry typeCleaning, inspection, andtesting

2 years 11.9, 11.11.2

Power Cables Visual inspection Yearly 19.2

Electrical testing 1–3 years 19.5, 11.9.2.4

Motor Control Equipment Infrared scanning Annually 11.17

Enclosures Visual inspection/clean Annually 16.2.1 through 16.3.5

Bus bar, wiring, and terminalconnections

Check connections fortightness in accordance with8.11

2 years 16.4.2

Visual inspection ofinsulators

Annually 16.4.4

Visual inspection of wiring Annually 16.4.5

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 28 5/10/17, 2:28 PM

Page 27: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Item/Equipment Task/Function Interval Reference

Electrical tests 2 years 11.9.2.3

Disconnects Visual inspection/clean Annually 16.5.3

Operation check Annually 16.5.5

Contactors Visual inspection/clean Annually 16.8.2.1 through 16.8.3

Motor overload relays,Check connections fortightness

2 years 16.9.4

nonthermal typeCleaning, calibration, andfunction tests

3 years 16.9.1.3, 16.9.2

Electrical interlocks Inspection Annually 16.11.1.2

Mechanical interlocks Inspection Annually 16.11.2

Electronic Equipment Inspection Annually 22.4.1

Cleaning 3 years 22.4.2

Adjustments/calibration 3–5 years 22.4.3

Molded-Case Circuit BreakersVisual inspection/clean 3 years 17.7 through 17.11

   Mechanical test 2 years 17.11

Electrical test 3–5 years 11.10.5

Fuses, 1000 Volts or Less

Fuse terminals and fuseclips Visual inspection 3 years 18.1.2

Clip contact pressure 3 years 18.1.3

Cleaning of contact surfaces 3 years 18.1.3

FusesVisual inspection fordiscoloration and damage

3 years 18.1.3

Fuses, Over 1000 Volts

Insulators Visual inspection/cleaning 3 years 18.2.3.1

Fuse terminals and fuseclipsInspection of contactsurfaces

3 years 18.2.3.2

FusesVisual inspection forcorrosion

3 years 18.2.3.2

Terminal connections andhardware

3 years 18.2.3.3

Fuse tubes 3 years 18.2.3.3

Fuses, Vented ExpulsionType

Visual inspection of seals 3 years 18.2.3.4

Rotating Equipment Vibration analysisContinuously to6-month intervals

26.7

Stator and rotor windingsVisual and mechanicalinspection, cleaning

Annually 8.7, 25.3, 25.6

Electrical testing Annually 11.20

Brushes, collector rings, andcommutators

Visual and mechanicalinspection

Annually 25.4

Bearings, sleevedOil level check

Drain, flush, and lubricate

Weekly–monthly

Annually25.5

 Waste-packed Re-oil, check air gap 1000 hours 25.5.2.3

Ball and roller Inspection and lubrication Per manufacturer 25.5.3

Kingsbury thrust bearings Drain, flush, and lubricate Per manufacturer 25.5.4

Wiring Devices

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 28 5/10/17, 2:28 PM

Page 28: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Item/Equipment Task/Function Interval Reference

Attachment plugs, cordconnector bodies

InspectionMonthly andwhen used

24.2.1 through 24.6

Receptacles InspectionMonthly andwhen used

24.3.1

Operation checkMonthly andwhen used

24.3.2

General-use snap switches Operation check When used 24.5.2 through 24.5.4

Pin-and-sleeve devices,heavy-duty industrial-typeplugs, cord connectors, andreceptacles

Inspections, cleaning, andchecks

Monthly andwhen used

24.8

Portable Electric Tools Inspections/cleaningMonthly andwhen used

29.1.3, 29.3.1, 29.3.2

Lubrication Per manufacturer 29.3.3

Electrical tests Quarterly 29.7

Low-Voltage Busway Infrared scanning Annually 20.4.2.1

Visual inspection Annually 20.4.3.2

Electrical test 2 years 20.4.8

Uninterruptible Power SupplySystems

Infrared scanning Annually 11.17, 20.3.8

   Visual inspection Quarterly 28.3.8

Routine maintenance 6 months 28.3.8

System tests 2 years 28.5

Battery testsSee StationaryBatteries andChargers.

15.9.4

UPS support standby generator Test run, exercise Monthly 28.3.5

Supplemental Information

File Name Description Approved

70B_SR6_attachement.docxTHIS IS THE CHANGE FOR SR-6 ONLY TWO CHANGES MADE TO THE SAME SECTION. For staff use.

Submitter Information Verification

Submitter Full Name: Christopher Coache

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Feb 22 13:53:43 EST 2017

Committee Statement

CommitteeStatement:

The section references for stationary batteries and charges where updated to be consistentwith the body of the standard.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 28 5/10/17, 2:28 PM

Page 29: National Fire Protection Association · PDF fileANSI/ IEEE 399, Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book) , 1997

Ballot Results

This item has passed ballot

24 Eligible Voters

3 Not Returned

20 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Cunningham, Karl M.

Johnson, Darrel

Schultheis, Timothy

Affirmative All

Bingham, Richard

Bishop, Thomas H.

Butcher, Aaron

Cantor, William P.

Corbett, Adria

Crnko, Timothy

Evans, James B.

Green, Dennis M.

Grimes, Ryan

Hall, Jeffrey

Harris, William R.

Hickman, Palmer L.

Horne, Mark C.

Huffman, David

Manche, Alan

Rempe, Kenneth J.

Staires, John E.

Taylor, Kiley

Urdinola, Robert

White, James R.

Affirmative with Comment

Moshiri, Ahmad A.

Affirmative

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 28 5/10/17, 2:28 PM