National Construction Code Fire Engineering Report Product Evaluation EURO CLAD SELEKTA PANEL PREPARED FOR: URBANLINE PTY LTD 114 Mica Street Carol Park QLD 4300 18 June 2017 Issue 01 Revision 01 REFERENCE: 5130

Transcript of National Construction Code Fire Engineering Report Product Evaluation...

  • NationalConstructionCodeFireEngineeringReport

    ProductEvaluation

    EUROCLADSELEKTAPANEL

    PREPAREDFOR:

    URBANLINEPTYLTD114MicaStreet

    CarolParkQLD4300

    18June2017Issue01

    Revision01REFERENCE:5130

  • Copyright©

    Allrightsreserved.Nopartofthecontentofthisdocumentmaybereproduced,published,transmittedoradaptedinanyformorbyanymeanswithoutthewrittenpermissionoftheIgnisSolutionsPtyLtd.Disclaimer

    Theinformationcontainedinthisdocumentisprovidedforthesoleuseoftherecipientandnorelianceshouldbeplacedontheinformationbyanyotherperson.Intheeventthattheinformationisdisclosedorfurnishedtoanyotherperson,theIgnisSolutionsPtyacceptsnoliabilityforanylossordamageincurredbythatpersonwhatsoeverasaresultofusingtheinformation.

    RegisteredOffice

    IgnisSolutionsPtyLtdSuite1614LonsdaleStreet

    BraddonACT2612POBox674,CivicSquare,ACT2608

    Tel:+61261003900Email:[email protected]:www.ignissolutions.com.au

    DOCUMENT REVISION HISTORY

    JOBNUMBER:5130

    Issue Revision Date Purpose of Issue Prepared by Reviewed by 01 01 18-06-17 Issued for comment BR

    CONDITIONS AND LIMITATIONS The report does not provide guidance in respect of areas, which are used for bulk storage, processing of flammable liquids, explosive materials, multiple fire ignitions or sabotage of existing fire safety systems.

    Apart from where noted in the specific sections of this report, we have not verified information provided by external parties and assume that the remainder of the building will comply with the DtS provisions of the NCC Volume One – BCA.

    Any application of the content of this report should be made taking into full account the following items:

    • observations of the building fire safety systems and fire hazards listed in this report have been based on examination of documentation made available.

    • any change in the information referenced including product design as detailed in this report to suit future re-organisation or planning will require further assessment to confirm compliance with the intent of the design objectives.

    • the data, methodologies, calculations and conclusions documented within this report specifically relate to the product and must not be used for any other purpose.

    • specifically, the report does not consider property damage; e.g. building and contents damage caused by fire, potential increased insurance liability and loss of business continuity.

    • this report considers a single point of fire as a source of ignition. • the design complies with the current DtS provisions of the BCA

    except for the specific performance solutions identified within this report.

    • figures provided within the report are indicative only. Full and appropriate detail is expected to be provided within discipline specific engineering specifications and associated detail design drawings by others.

    • this report should not be considered as a stand alone document but read as part of the buildings suite of approved documents including architectural drawings, fire safety systems detail including specifications and associated drawings as well as the buildings design, construction, installation and commissioning approvals.

    Potential risks of incendiary are limited in the scope of engineering design. Conventional building design can only provide limited protection against malicious attack; for example, large scale incendiary and multiple ignition sources can potentially overwhelm some fire safety systems.

    Strategies such as security, housekeeping and other management procedures may be more effective than additional fire protection in addressing arson events.

    This report is applicable to the Project only. It does not consider property damage to the building as a result of the alternative building solutions addressed in the evaluations.

    A number of issues within the NCC Volume One – BCA are interpretive in nature. Where these issues are encountered, interpretations are made that are consistent with standard industry practice.

    This report is prepared in good faith and with due care for information purposes only, and should not be relied upon as providing any warranty or guarantee. In particular, attention is drawn to the nature of the inspection and investigations undertaken and the limitations these impose in determining with accuracy the state of the product applied within the building, its services or equipment and life safety.

    Ignis Solutions’ involvement in the Project is limited to the role outlined in the service acceptance. This report reflects that role. Any reliance on, or use of, this report for purposes outside the scope of service is at the user’s own risk.

    Ignis Solutions shall not be held liable for any loss or damage resulting from any defect of the building or its services or equipment or for any non compliance of the building or its services or equipment with any legislative or operational requirement, whether or not such defect or non-compliance is referred to or reported upon in this report, unless such defect or non-compliance should have been apparent to a competent engineer undertaking the assessment of the type undertaken for the purpose of preparation of this report.

    Ignis Solutions has carefully reviewed and applied to the best of our ability the requirements of State/Territory Legislation, the BCA and the International Fire Engineering Guidelines.

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE3OF11

    TABLE OF CONTENTS

    DOCUMENTREVISIONHISTORY ___________________________________ II

    CONDITIONSANDLIMITATIONS___________________________________ II

    INTRODUCTION_____________________________________________4

    FIRESAFETYANDINSTALLATIONREQUIREMENTS _________________5

    EUROCLADPERFORMANCESOLUTION__________________________6

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE4OF11

    INTRODUCTION

    GeneralThepurposeofthisassessmentistoevaluateaPerformanceSolutionoftheEuroCladproducttosatisfytheperformancerequirementsoftheNational ConstructionCodeVolumeOneandTwo–BuildingCodeofAustralia(BCA).Theassessmentevaluatestheproductasaninternalandexternalwalllining/attachmenttoloadbearingornon-loadbearingwallsthatdoordonot requireaFireResistanceLevel. The followingclausesof theBCAhavebeenevaluatedandidentifiedasbeingcompliedwith:

    CP2(a) – Building elements avoid the spread of fire, P2.3.1 Protection from the spread of fire

    TheEuroCladbuildingelementhasbeentestedinaccordancewithAS1530.3Methods for fire testsonbuildingmaterials, components andstructures – Simultaneous determination of ignitability, flamepropagation, heat release and smoke release, AS/NZS 3837:1998 –Method of test for heat and smoke release rates for materials andproducts using an oxygen consumption calorimeter andAS 5113 Firepropagationtestingandclassificationofexternalwallsofbuildings.Thetestinghasdemonstratedthefortheproposedinstallationlocationsthat they do not present an independent fire hazard or risk of firespread.

    Clause C1.1 – Type of Construction Required

    • Specification C1.1 Clause 2.4 – Attachments not to impair fire-resistanceo The combustible components and assembly complies with thefirehazardpropertiesofSpecificationC1.10Clause7table4

    o When located near or directly above a required exit does notmaketheexitunusableinafire

    o Doesnototherwiseconstituteanundueriskoffirespreadviathefaçadeofthebuilding

    o TheattachmentdoesnotimpairtherequiredFRLofthatpart.

    CP4 Fire hazard properties of materials

    The Euro Clad building element has been tested in accordance withAS/NZS3837:1998toachieveaGroup3ratingandthereforesatisfiesCP4 and subsequently Clause C1.10 where a Group 3 material ispermittedonawallorceiling.

    Clause C1.10 Fire Hazard Properties

    • Sub-clause (a)(ii) wall linings and ceiling linings that comply withSpecificationC1.10Clause4

    • Sub-clause (a)(ix) Other materials that comply with SpecificationC1.10Clause7

    Clause G5.2 Bushfire Protection (including associated State variations) Part 3.7.4 Bushfire Areas

    • AS3959Constructionofbuildingsinbushfire-proneareasBAL12.5to29.

    ProductDetailThe Urbanline Euro Clad Selekta Panel is a pre-finished compositecladdingfaçadewithatimber-grained-embossedsurface.Designedforstabilityand longevitywithpurportedtobeeco-friendlymaintenancefreeandeasytoinstall.TheEuroCladSelektaPanelis170mminwidthwitha155mmcover,18mminthicknessandupto5400mminlength.The maximum fixing span is 625mm. The Euro Clad Selekta PanelachievesaSpreadofFlameIndexof0andSmokeDevelopmentIndexof3whentestedtoAS1530.3:1999andagroup3numberwhentestedtoAS/NZS3837:1998.

    Product Identification

    TheEuroCladpanelcanbeidentifiedbytheuniqueproductprofileaswellasitsdeliverypackagingasdetailedbelow.FIGURE 1: Product Identification

    Panel Fixing and Installation

    TheEuroCladpanelcanbemechanicallyfixedtothewallframeviaatophatortimbersub-frame,toallowforabreathableaircavitytoTypeAandBorTypeCconstructionrespectivelyprovidedthewallandsub-framecomplywiththerequirementsoftheBCA.Thefixingistobeatcentresnogreaterthan625mmasdetailedbelow.Thisincludeswheninstalledonthediagonal.FIGURE 2: Installation Figure example

    The Euro Clad Selekta Panel has been evaluated by SummermoreStructural and Civil Engineers in accordance with the BCA, AS/NZS1170.0:2002,AS/NZS1170.1:2002,AS1720.1:2010andAS1684:2010.TheanalysisdetailedthattheEuroCladSelektaPanelhasamaximumfixingspacingof645mmforgeneralcladdingareasand300mmforareaswithin 1200mm of corners. The analysis excluded considerations forimpact resistance as required for cyclonic areas under AS/NZS1170.2:2011. This applies to N1 to N4 and C1 to C3 applications.Urbanlinehaslimitedthemaximumspacingto625mmwith30mmlong6gaugestainlessorgalvanisedsteelscrews.

    LimitationsThe Euro Clad product can be installed on walls or ceilings on theinternalorexternalpartsofwalls.WheninstalledontheexteriorofawalltheEuroCladproductistobeinasingleverticalplaneonly.I.e.ifinstalledonanexternalwall,anyreturnorwingwall(atananglelessthan90)isnotpermittedtohavetheEuroCladproductinstalled.ThisdoesnotlimittheEuroCladbeinginstalledonanexternalwallaswellasceilingoreveportionofabuilding.

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE5OF11

    FIRESAFETYANDINSTALLATIONREQUIREMENTS

    ScopeofUse

    The Euro Clad Selekta Panel is permitted to be used, on theinteriororexteriorsideofthewallframeorstructure,vertically,horizontally on a soffit of a building, awning, architecturalfeature or the like attached to a wall. The Euro Clad SelektaPanelcanbefixedtoawallwithanFRLornot inbuildingsofTypeA, B or C constructionwithout the requirement for anyadditional non-combustible lining outside of the walls FRLdesign.

    TheEuroCladSelektaPanelisnotpermittedtobeusedontwoadjacentwalls facingeachother lessthan90° forbuildingsofTypeAorBconstruction.

    The Euro Clad Selekta Panel is permitted to be used on aninternalwallorceilingwhereaGroup3material ispermittedunderBCASpecificationC1.10Table3.

    ItissuitablefortheEuroCladSelektaPaneltobemechanicallyfixed through anyweatherproofing sarking-typematerial, fireresistance or acoustic material and directly to the primarybuilding element, wall frame sub-frame or associated furringchannel.

    The Euro Clad Selekta Panel is permitted to be installed inbushfireproneareasfromBAL12.5toBAL29.

    NCCComplianceVolumeOneandTwo–BuildingCodeofAustralia

    Clause A0.2 and 1.0.2 (c) evidence to support the use of amaterialmeetsthenominatedPerformanceRequirementsandDeemed-to-SatisfyProvisionscomplyingwithacombinationofPerformanceSolutionsandDeemed-to-SatisfySolutions.

    ClauseA2.2and1.2.2sub-clause(a)(iii)asevidencetosupportthat the Euro Clad Selekta Panel meets the nominatedPerformance Requirements under a certificate from aprofessionalengineer.

    PerformanceRequirementCP2–SpreadofFire–TheEuroCladSelektaPaneldoesnotcontributetothespreadoffirewhenonasingleverticalplane.

    TheEuroCladSelektaPanelhasbeentestedtoAS5113:2016andachievesA100-BB29classification.

    PerformanceRequirementCP4–Spreadoffireandgenerationofsmokeandheat,andanytoxicgases–TheEuroCladSelektaPanel does not contribute to the spread of fire, generateexcessivesmoke,heatortoxicgaseslikelytolimitthetenableconditionsduringoccupantevacuationfrombeingmaintained.

    • ClauseC1.10(a)Firehazardproperties.• SpecificationC1.1Clause2.4Attachmentsnotto impairfire-resistance.

    PerformanceRequirementP2.3.1–Protectionfromthespreadoffire–TheEuroCladSelektaPaneldoesnotcontributetothespreadoffire.

    GP5.1(including(NSWandQLDGP5.1,TasGP5.1(a))

    • G5.2Protection(includingNSWG5.2,SAG5.2,SAG5.3)• AS3959:2009–Constructionofbuildingsinbushfire-proneareas,section4BAL–LowtoSection6BAL29.

    P2.3.4Bushfireareas

    • Part 3.7.4 Bushfire areas (including NSW, SA and Tas Statevariations)uptoaBushfireAttackLevel(BAL)of29.• AS3959:2009–Constructionofbuildingsinbushfire-proneareas,section4BAL–LowtoSection6BAL29.

    InstallationLimitations This evaluation is limited to the details within this report

    includingtheabovecomplianceelements,productdescriptionandscope.Thisevaluationreportistoberead,consideredandusedasawholedocument.

    TheEuroCladPanelisnotpermittedtobeusedontwoadjacentwallslessthan90°toeachother.

    The Euro Clad Selekta Panel is approved to be installed inaccordance with mechanical fixing at stud, batten or furringchannel centres no greater than 625mm with 30mm long 6gaugestainlessorgalvanisedsteelscrews.

    TheEuroCladSelektaPaneldoesnotprovideaFireResistanceLevel.Wheretheproductisusedwithin900mmofaboundaryforClass1buildingsorwhereanFRL is requiredforClass2-9buildings, the FRL is to be provided by other systems orproducts.

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE6OF11

    EUROCLADPERFORMANCESOLUTION BCA Deemed-to-Satisfy Basis

    ItisproposedtopermittheuseoftheEuroCladSelektaPanelasadecorativefaçadeorwalllininginmultipleconfigurations. This includes an internal or external ceiling/roof or wall lining or external attachment, inaccordancewithbothVolumeOneandTwooftheNationalConstructionCode.

    BCA Performance Requirement TherelevantBCAPerformanceRequirementsareCP2(a)(iii),CP4andP2.3.4.

    Meeting the Performance Requirement The Performance Requirement will be satisfied by A0.2 (c): a combination of (a) and (b) where (a) is aPerformanceSolutionand(b)isaDeemed-to-SatisfySolution.

    Assessment Method BCAProvisionA0.5(b)(ii)VerificationMethodsastheappropriateauthorityacceptsfordeterminingcompliancewiththePerformanceRequirement.

    Methodology The following methodologies will be applied to the evaluation: þ Absolute þ Quantitative þ Deterministic

    o Comparative þ Qualitative o Probabilistic

    Absolute approach

    AsoutlinedintheInternationalFireEngineeringGuidelineanabsoluteapproachistypicallywhenanevaluationiscarriedoutonanabsolutebasis,theresultsoftheanalysisofthetrialdesignarematched,usingtheagreedacceptance criteria against the objectives or performance requirementswithout comparison to deemed-to-satisfyorprescriptiveor“benchmark”designs.

    Quantitative approach

    Aquantitativeapproachreferstoananalysisthatinvolvesnumericalevaluationofanidentifiedprocess.Thequantitativeapproachincludesdetailedmathematicalandengineeringcalculations.

    Qualitative approach

    Aqualitativeapproachreferstodescriptionsordistinctionsbasedonaqualityorcharacteristicratherthanonaquantity or measures value. The qualitative approach includes structured arguments to demonstratecompliance.

    Deterministic approach

    Adeterministicapproachisamethodologybasedonphysicalrelationshipsderivedfromscientifictheoriesandempiricalresultsthatforagivensetofconditionswillalwaysproducethesameoutcome.

    Acceptance Criteria TheacceptancecriteriaforthisperformancesolutionisthattheEuroCladmaterialhastherequiredfirehazardproperties, group number and via the full scale fire test to the degree necessary, avoids the spread of firebetweenbuildings.

    Identified Hazard ThepotentialhazardisthatafiremayoccurandspreadviatheEuroCladPanel

    ThefollowingimagesdetailsomecommonacceptableapplicationsfortheEuroClad.Itisimportanttonotetheapplicationalongsingleplanesandnotontwowallsatrightanglestoeachother.

    FIGURE3:TYPICALAPPLICATIONSFOREUROCLAD

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE7OF11

    External Application The construction of walls defined within the BCA consists of threeprinciple elements, internal linings, the wall itself and externalattachments. This part of the evaluation is focused on externalattachments,linings,veneersandthelike.TheBCApermitscombustibleassembliestobeattachedtoexternalwallsdependingontwoscenarios.The first is where the wall requires a Fire Resistance Level and thesecond is where no Fire Resistance Level is required. Both thesescenariosrequirecompliancewithPerformanceRequirementCP2.

    Forexternalinstallations,theBCArequires,inaccordancewithClauseC1.10,compliancewithSpecificationC1.10,Clause7table4wherethespread of flame and smoke development indices are less than thatpermittedbytheBCA.Table4alsorequiresthememberorassemblytoretain the protection in position so that it prevents ignition of thematerialandcontinuestoscreenitfromaccesstofreeairforaperiodof not less than 10 minutes. Where the wall is to achieve a FireResistance Level, compliance with Specification C1.1 Clause 2.4 isrequired.ThisclausereiteratescompliancewithSpecificationC1.10,notlocatedsuchtomaketheexitunusableinafireanddoesnototherwiseconstituteanundueriskoffirespreadviathefaçadeofthebuilding.Anevaluationoftherelevantclausesandtestingrequirementsfortheuseofthepanelasanexternalattachmentisdetailedbelow.

    CP2 Performance Evaluation

    BCAPerformanceRequirementCP2(a)(iii) is identifiedas the relevantperformance requirement for the use of the material in an externalapplication. The other elements relate to internal design or wallrequirementssuchasfireratedcompartmentation.

    TABLE 1: PERFORMANCE REQUIREMENT CP2 (A)(III)

    (a) A building must have elements which will, to the degree necessary, avoid the spread of fire-

    (iii) between buildings Source: BCA 2016

    Firespreadbetweenbuildingscanoccurduetothespreadoffirebeinggreater than a permitted opening resulting in the radiant heat fluxexceedingthevaluespermittedunderCV1orCV2.Ithasbeenidentifiedviavariouspublicationsthatthereisnodeemedtosatisfyprovisionfordemonstrating an external wall element to avoid the spread of fire.Thesereferencedocumentsinclude:

    - VBA Fact Sheet Non-Deemed-to-Satisfy External Wall CladdingSystemsissuedApril2015

    - Victorian Building Control Commission, Fire Protection for High-RiseBuildings2000

    - The fire protection research foundation, fire hazards of exteriorwallassembliescontainingcombustiblecomponentsJune2014

    - SAMFSCombustibleexternalcladdingmaterialstobuildingsletterdated30December2015.

    - Australian Senate Economic References Committee, non-conformingbuildingproductsinterimreportSafety–‘notamatterofgoodluck’May2016

    - ABCBRegulatoryImpactStatementnon-compliantuseofexternalcladdingproductsonbuildingsAugust2016

    SpecificationC1.1Clause2.4detailsarequirementforattachmentsnottoimpairfire-resistance.

    AS 5113 External Façade Test

    AS 5113 provides procedures for the fire propagation testing andclassificationofexternalwallsofbuildingsaccordingtotheirtendencyto limit thespreadof firevia theexternalwallandbetweenadjacentbuildings.

    AS5113isapplicabletofirepropagationviaallexternalverticalornearverticalsurfacesandcoversalltypesofexternalwallsystems,includingfacades,outerskins,corematerials,cavitiesandattachments.

    AS 5113:2016 is not a reference document within the NationalConstruction Code. It is anticipated that this will occur in the 2019versionoftheNCC.ThefollowingevaluationconsiderstheresultsfromAS5113incontexttotherequirementsofCP2.

    AS 5113:2016 section 6 sets conditions on the reporting of theclassification.Areportisrequiredtopreparedindependentlytothefiretest.

    BS8414–Fireperformanceofexternalcladdingsystems.Testmethodsfornon-loadbearingexternalcladdingsystemsappliedtothefaceofabuilding.

    Asdetailedabove,theBS8414externalwallfiretest,asreferencedinAS 5113 is intended to simulate the multi-storey flammability fireperformanceofanentireexternalwallassemblies.

    It involvestheconstructionofatwo-storeytestrigcladinthesubjectproductwhichissubjectedtoafiresourceconsistingofatimbercrib.

    The pass/fail criteria is based on flame propagation vertically andlaterally across the subject material, which is measured by variousthermocouplesandobservationsofflamesemittingfromthesurfaceofthespecimenatspecificlocations.Thisstandardisconsideredtobeaverygoodindicatorofthe‘as-installed’fireperformanceofanexternal

    claddingmaterialbecauseitisalargescaletestdesignedtomimicrealinstallations.

    TheproductstestingtoBS8414wasundertakenbyBREGlobalwithintheirindoorfacility.BREGlobaloperatesoneofthelargestfireresearchandtestinglaboratoriesinEuropebeingaccreditedbyUKAS0578.Thetestingoccurredon7July2014.ThetestreportdetailsthattheBS8414testapparatusisusedtoevaluatethefirepropagationcharacteristicsofexterior non-load-bearing wall assemblies and panels used ascomponents of curtain wall assemblies that are constructed usingcombustible materials or that incorporate combustible componentswithinthewallassembliesasspecifiedinthefollowing:

    The ability of thewall assembly to resist flamepropagation over theexteriorfaceofthewallassembly.

    The ability of the wall assembly to resist vertical flame propagationwithinthecombustiblecoreorwithinothercombustiblecomponentsfromonestoreytothenext.

    Theabilityofthewallassemblytoresistverticalflamepropagationovertheinteriorsurfaceofthewallassemblyfromonestoreytothenext.

    Theabilityofthewallassemblytoresistlateralflamepropagationfromthecompartmentoffireorigintoadjacentcompartmentsorspaces.

    TheAS5113testwasundertakenwiththesupportoftheBRE.Thewallconsistedofthefollowingmakeup:

    • 13mmstandardgradePlasterboard• 75mmLightweightsteelFrame• Fibrecementsheet• Glasswoolfibreinsulation• Tyveksarking• 61mmFurringchannels• EuroCladpanel

    The following table details the results of the test against therequirementsofAS5113.

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE8OF11

    TABLE 2: AS 5113 ACCEPTANCE CRITERIA

    Test Requirements Pass/Fail

    Tw5m

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE9OF11

    Volume Two bushfire areas

    The Euro Clad Selekta Panel has been tested in accordancewith therequirementsofAS1530.8.1toaratingofBAL29byExovaWarringtonintheirtestreport46212000.1AS3959-2009Clause5.4,6.4and7.4forBAL12.5andBAL29

    BushfireAttackLevel: 29

    Required Fire Safety Measures

    BasedonthetestingoftheEuroCladSelektaPaneltoAS5113,theEuroClad Selekta Panel can be installed as an external element of a wallprovideditisusedonasingleplaneofawallorexternalsoffitwithanywing or return wall at 90° or less constructed of non-combustiblematerial.EquallytheEuroCladpanel ispermittedtobeusedinareaswhereaBAL29requirementisapplied.

    Evaluation Summary

    IntheopinionofIgnisSolutions,theassessmenthasdemonstratedthattheEuroCladpanelcanbeusedonasingleplaneofawallorexternalsoffitwithanywingor returnwall at90° or less constructedofnon-combustible material and therefore in these locations satisfies therequirementsofBCAPerformanceRequirementCP2(a)(i),(ii)and(iv).AswellasP2.3.4forbushfire.

    Internal Application TheBCAdetailsanumberofprovisionsfortheuseofbuildingelementswithinabuilding.This includesPerformanceRequirementCP2(a)(i)(ii)and(iv)aswellasCP4asdetailedbelow.TABLE 3: PERFORMANCE REQUIREMENT CP2 (a)(i), (ii) AND (iv)

    (a) A building must have elements which will, to the degree necessary, avoid the spread of fire-

    (i) to exits; and (ii) to sole-occupancy units and public corridors; and (iv) in a building

    Source: BCA 2016

    TABLE 4: PERFORMANCE REQUIREMENT CP4

    To maintain tenable conditions during occupant evacuation, a material and an assembly must, to the degree necessary, resist the spread of fire and limit the generation of smoke and heat, and any toxic gases likely to be produced, appropriate to-

    (a) the evacuation time; and (b) the number, mobility and other characteristics of occupants; and (c) the function or use of the building; and (d) any active fire safety systems installed in the building.

    Source: BCA 2016

    To satisfy the requirements of CP2 (a)(i), (ii) and (iv) as well as CP4compliance through the Deemed-to-Satisfy Clause C1.10(ii) for Firehazardpropertiesisrequiredforwallliningsandceilingliningsaswellasattachmentsandothermaterials.

    TheBCA sets theprinciple requirements for firehazardpropertiesofbuilding materials within Part A2 Clause A2.4 for where buildingcomponents or assemblies are to have fire hazard properties. ClauseA2.4requirescomplianceinaccordancewithSpecificationA2.4.

    Specification A2.4 – Fire Hazard Properties sets the scope fordetermining the fire hazard properties of assemblies to be tested toAS/NZS1530.3.

    The construction of walls defined within the BCA consists of threeprinciple elements, internal linings, the wall itself and externalattachments.

    For internal installations, theBCArequires, inaccordancewithClauseC1.10,compliancewithSpecificationC1.10,Clause7table4wherethespread of flame and smoke development indices are less than thatpermittedbytheBCA.Table4alsorequiresthememberorassemblytoretain the protection in position so that it prevents ignition of thematerialandcontinuestoscreenitfromaccesstofreeairforaperiodof not less than 10 minutes. Where the wall is to achieve a FireResistance Level, compliance with Specification C1.1 Clause 2.4 isrequired.ThisclausereiteratescompliancewithSpecificationC1.10,notlocatedsuchtomaketheexitunusableinafireanddoesnototherwiseconstituteanundueriskoffirespreadviathefaçadeofthebuilding.Anevaluationoftherelevantclausesandtestingrequirementsfortheuseofthepanelasanexternalattachmentisdetailedbelow.

    Clause C1.1 Type of construction required

    ClauseC1.1oftheBCAsetsthetypeofconstructionrequiredwithinabuilding as per Table C1.1 where construction of Type A, B or C is

    requireddependentonthebuildingsriseinstoreys.ClauseC1.1setstherequirementforcompliancewithSpecificationC1.1oftheBCA.

    TheguidetotheBCAdetailsthattheintentofClauseC1.1istoestablishtheminimumfire-resistingconstructionrequiredforClass2-9buildingswithSpecificationC1.1providingclaritythatSpecificationC1.1containsrequirementsforfire-resistingconstructionofbuildingelements.

    Specification C1.1 requirements and the associated compliance aredetailed below. Based on compliance against Specification C1.1,compliancewithClauseC1.1aswellasPerformanceRequirementCP2andCP4isdeemedsatisfied.

    Specification C1.1 – Clause 2.4

    SpecificationC1.1Clause2.4setscriteriaforattachmentstobuildingstonotimpairthefire-resistance.TheguidetotheBCAclarifiestheintentasbeing‘tominimisetheriskthatafinish,liningorattachmenttoawallorroofrequiredtohaveafire-resistancelevel(FRL)will:• ImpairtheFRLofthewallorrooftowhichitisattached;• Compromisethesafeevacuationofthebuilding;and• Leadtothespreadoffirebywayofthebuildingfaçade.

    Note: It is important to note that in some circumstances, an FRL of -/-/- can be considered a required FRL and therefore in some circumstances by the Authority Having Jurisdiction Specification C1.1 Clause 2.4 remains valid for all wall scenarios.

    Theguidegoesonfurthertostate:

    SpecificationC1.1ClauseC2.4doesnotprohibittheuseofcombustiblematerialsasafinish,liningorotherattachmenttoawall,rooforotherbuildingelementrequiredtohaveanFRL.Thecombustiblematerialcanonlybeusedifthematerial:

    a. IsoneoftheexemptionsfromfirehazardpropertieslistedinC1.10(c), or complies with the fire hazard properties prescribed inSpecificationC1.10;

    b. Isnot locatedinapositiontomakearequiredexitunusable inafire, therefore it will not compromise the building’s safeevacuation;

    c. Willnotleadtothespreadoffirebywayofthebuildingfaçaded. WillnotimpairtheFRLofthewall,rooforotherbuildingelementtowhichitisattached.

    It is noted that Clause 2.4(a) only applies to the use of finishes orlinings,andotherattachments.Clause2.4(b)prohibits a required FRLof abuildingpart frombeingreducedbytheattachmentoffacingsorfinishes.a. TheEuroCladSelektaPanelhashaditscorematerialaswellasthe

  • 5130I01R00URBANLINECOMPLIANCENCCANALYSIS17062017.DOCX PAGE10OF11

    full assembly tested in accordance with AS 1530.3. The materialachievedthefollowingresults:

    FireHazardPropertiesSpreadofFlameIndex 0SmokeDevelopmentIndex 3

    These results provide a Spread of Flame Index as well as SmokeDevelopedIndexlessthanthatofthefirehazardpropertiesprescribedinSpecificationC1.10beingamaximumof8and9respectively.

    b. TheEuroCladSelektaPanelisnotpermittedtobeusedwithinafireisolatedstair,ramporpassageway.Whenusedinorneararequiredexit,internaltothebuilding,itsatisfiestherequirementsofGroup3.Whenusedexternaltoabuilding,thepanelhasnotbeenobservedtoburnunlessasubstantialfireeventwaslocatedwithinproximitytothepanels.Inthisscenario,itwouldbethefireeventthatrenderstherequiredexitunusableandnotthepanel.

    Basedonthetestingofthepanel,complianceagainstSpecificationC1.1Clause 2.4 with assistance from the Guide to the BCA has beendemonstrated.

    Clause C1.10 Fire hazard properties

    ClauseC1.10sets twoconditions for theuseof theEuroCladSelektaPanel within buildings. The first is through sub-clause (a)(ii) beinginternalwallandceilingliningsandthesecondissub-clause(a)(ix)othermaterialsandlocations.

    Clause C1.10 requires the fire hazard properties to comply withSpecificationC1.10.

    Specification C1.10

    ForwallandceilingliningscompliancewithClause4andsubsequentlyestablishmentofaGroupnumberisrequired.TestingoftheEuroCladSelektaPanelresultsinagroup3material.TheEuroCladSelektaPanelispermittedtobeusedinternallyinthelocationsdesignatedforgroup3productsinthefollowingtableasextractedfromtheBCASpecificationC1.10Clause4table3.

    FIGURE 4: BCA SPECIFICATION C1.10 TABLE 3

    TestingoftheEuroCladpanelisdetailedasfollows:

    AS/NZS3837:1998–Methodoftestforheatandsmokereleaseratesformaterialsandproductsusinganoxygenconsumptioncalorimeter.

    EXOVAWarringtonhasundertakentestingoftheproductinaccordancewithAS/NZS3837intheirreport326591-00cb.1.ExovaWarringtonisaRegistered TestingAuthoritywith theNational Association of TestingAuthorities.Thetestreportwasissuedon05August2015andproducedthefollowingresults:

    GroupNumber: 3

    Forothermaterialsand locations,Clause7 table4 requiresmaterialsandassembliesnottoexceedtheindiceslisted.

    FIGURE 5: BCA SPECIFICATION C1.10 TABLE 4

    TheEuroCladSelektaPanelhasbeentestedtotherequirementsofAS1530.3. These results, as detailed above are less than themaximumvaluessetbyClause7table4.Table4providesforconditionswhenthecompositememberorassemblydoesnotcomplywithTable4.Giventhe results of the corematerial and as an assembly complywith the

    indices listed, compliance with Specification C1.10 is achieved andsubsequentlyClauseC1.10.

    AWTA AS 1530.3:1999 Methods for fire tests on building materials,components and structures – Simultaneous determination ofignitability, flame propagation, heat release and smoke releaseCertificateofTest7-586357-CQ.

    The Australian Wool and Textile Authority (AWTA) is a RegisteredTestingAuthoritywith theNationalAssociationofTestingAuthoritiesaccreditation 1356. Testing to AS 1530.3 is within AWTA scope oftesting.

    The test report was issued on 02 August 2012 and produced thefollowingresults:

    FireHazardPropertiesSpreadofFlameIndex 0SmokeDevelopmentIndex 3

    Required Fire Safety Measures

    BasedonthetestingoftheEuroCladpaneltoAS/NZS3837:1998andAS1530.3:1999,thepanelachievesaGroup3rating,SpreadofFlameIndexof0andSmokeDevelopmentIndexof3.

    Evaluation Summary

    IntheopinionofIgnisSolutions,theassessmenthasdemonstratedthattheEuroCladpanelcanbeusedwhereGroup3productsarelistedandtherefore in these locations satisfies the requirements of BCAPerformanceRequirementCP2(a)(i),(ii)and(iv)aswellasCP4throughtheDeemed-to-SatisfyClauseC1.10(ii).