National Building Code for Our Secondary Exit
-
Upload
avithpereira -
Category
Documents
-
view
228 -
download
0
description
Transcript of National Building Code for Our Secondary Exit
8.5 Arrangement of Exits
8.5.1 Exits shall be so located that the traveldistanceon the floor shall not exceed the dis-tance given in Table 24.
TABLE 24 TRAVEL DISTANCE FOROCCUPANCY AND TYPE OF CONSTRUCTION
si.xo. GROUP OF MAXIMUMTRAVEl.OCCUPANCY DISTANCECONSTRUCI10N
, Types Types'1&2 3&4
(1) (2) (3) (4)m m
i) Residential (A) 22.5 22.5ii) Educational (B) 22.5 22.5iii) Institutional (C) 22.5 22.5iv) Assembly (D) 30.0 30.0v) Business (E) 30.0 30.0vi) Mercantile (F) 30.0 30.0vii) Industrial (G) 45.0viii) Storage (H) 30.0ix) Hazardous (J) 22.5
NOTE 1- For the sprinkler system, the travel distancemay be increased by 50 percent of the values specified.
NOTE 2 - In so far as basements are concerned, thetravel distance will reckon half the value as prescribedin Table 24. Ramps shall also be counted as one of themeans of,escape.
• Construction of. type 3 or 4 is not permitted.
8.5.2 The travel distance to an exit from thedead end of a corridor shall not exceed half thedistance specified in Table 24, except in as-sembly and institutional occupancies in whichcase it shall not exceed 6 m.
8.5.3 Whenever more than one exit is re-quired for any room space or floor of a build-ing, exits shall be placed as remote from eachother as possible and shall be arranged toprovide direct access in separate directionsfrom any point in the area served.
8.6 Number of Exits8.6.1 GENERAL - The general requirementsof number of exits shall supplement the re-quirement of different occupancies in 9 to 17.
8.6.2 All buildings which are 15 m in heightor above and all buildings used as educational,assembly, institutional, industrial, storage andhazardous occupancies, and mixed occupan-cies with any of the aforesaid occupancies,having area more than 500 m2 on each floorshall have a minimum of two staircases. Theyshall be of enclosed type; at least one of themshall be on external walls of buildings and shallopen directly to the exterior, interior open
space or to an open place of safety. Further,the provision or otherwise of alternative stair--case shall be SUbject to the requirements oftravel distance being complied with.
8.7 Doorways
8. 7.1 E~ exit doorway shall open into anenclosed stairway or a horizontal exit of acorridor or passageway providing continuousand protected means of egress.
8.7.2 No exit doorway shall be less than 100em in width except assembly buildings wheredoor width shall be not less than 200 em.Doorways shall be not less than 200 em inhight.
8.7.3 Exit doorways shall open outwards, thatis, away from the room, but shall not obstructthe travel along any exit. No door, whenopened, shall reduce the required width ofstairway or landing to less than 90 em; over-head or sliding doors shall not be installed.
NOTE - In the case of buildings where there is acentral corridor, the doors of rooms shall open inwardsto permit smooth flow of traffic in the corridor.
8.7.4 Exit door shall not open immediatelyupon a flight of stairs; a landing equal to atleast the width of the door shall be provided inthe stairway at each doorway; the level of land-ing shall be. the same as that of the floor whichit serves.
8.7.5 Exit doorways shall be openable fromthe side which they serve without the use of akey.
8.7.6 Mirrors shall not be placed in exit waysor exit doors to avoid confusion regarding thedirection of exit.
8.8 Corridors and Passageways
8.8.1 Exit corridors and passageways shall beof width not less than the aggregate requiredwidth of exit doorways leading from them inthe direction of travel to the exterior.
8.8.2 Where stairways discharge through cor-ridors and passageways, the height of cor-ridors and passageways shall be not less than2.4m.
8.8.3 All means of exit including staircases,lift lobbies and corridors shall be adequatelyventilated.
NATIONAL BUILDING CODE OF INb~