N2 Unit - Cost Elimination by in-House Logic Development

download N2 Unit - Cost Elimination by in-House Logic Development

of 14

Transcript of N2 Unit - Cost Elimination by in-House Logic Development

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    1/14

    N2 Unit - Cost Eliminatioby In-House Logic

    DevelopmentA Presentation by Asadullah Qureshi/AQ (I&E ROP)

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    2/14

    Current Arrangement at the N2 Unit

    Nitrogen extraction at the N2 Unit is carried out using Sieme200 family of PLCs – CPU 222 at the Old N2 Unit and CPU 22New N2 Unit.

    • However, the PLCs come pre-programmed and the programprotected using a Level 4 Lock.

    •A Level 4 Lock means the program cannot be accessed for emodification or back-up purposes.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    3/14

    Current Arrangement at the N2 Unit

    Since modification is not an option, the usefulness of the covery limited.

    • The control algorithm cannot be refined or modified as peroperational requirement.

    • A new program must be commissioned every time a modific

    required.• The program costs almost the same as the PLC and its assoc

    modules.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    4/14

    The Proposal

    The nitrogen extraction algorithm is fairly simple and the prbe developed in-house.

    • This would allow us access to the program for further modifand eliminate the cost of having to commission the program

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    5/14

    The Proposal

    The nitrogen extraction algorithm uses a total of ten digital open and close SOVs as per a programmed timing sequence

    • The timing sequence may be replicated by recording how thstatus LEDs light up on the DO card as nitrogen extraction isout.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    6/14

    Logic Development

    The timing sequence was first studied by making a recordingDO card while nitrogen extraction continued in the backgro

    • The timing sequence is shown in the table below:

    Valve 57 sec 0.5 sec 0.5 sec 1 sec 0.5 sec 57 sec 0.5 sec 0.5 sec

    SOV1 1 1 1 1

    SOV2 1 1 1 1

    SOV3 1 1 1 1 1

    SOV4 1 1 1 1 1 1 1 1

    SOV5 1 1 1 1 1 1 1 1 1

    SOV6 1 1 1 1 1 1 1 1 1

    SOV7 1 1 1

    SOV8 1 1

    SOV9

    SOV10 1 1 1 1 1

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    7/14

    1

    3

    7

    2

    4

    9 10

    5 6

    8

    Inlet Air

    Outlet Air

    Exhaust

    Tank A Tank B

    Nitrogen Extraction via

    Pressure Swing Adsorption

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    8/14

    Logic Development

    A timer runs for a total 1 minute and 59 seconds.• It is used to regulate the entire process.

    • It provides a reference point against which each SOV is turned on o

    • It restarts the sequence after the 1 minute and 59 seconds mark.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    9/14

    Logic Development

    The algorithm treats each SOV separately.• Comparison is made with the timer’s count to come up with

    for each SOV.

    • This can be seen by using SOV0 as an example.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    10/14

    Logic Development

    The timing sequence only continues as long as the level switthe two CMS tanks are HIGH.

    • This indicates that the CMS level in the tanks is appropriate.

    • Each SOV either turns on once or it turns on twice in one giviteration of the sequence.

    • The logic is presented in the next slide.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    11/14

    Start Scan

    Cycle

    T >= x

    AND

    T = x AND

    T = y AND

    T

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    12/14

    Cost Benefit Analysis

    The cost of the program factors into the overall cost of procspare PLCs for the N2 Unit.

    • By programming the PLC in house, we get to save money.

    • It also allows us to incorporate various interlocks into the looperational requirement.

    PLC + Program Rs. 235000

    PLC - Rs. 119000

    Money Saved Rs. 116000

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    13/14

    Cost Benefit Analysis

    We now have access to the program and we understand thais very simple from a control point of view.

    • We can therefore even go as far as replacing Siemens’ S7-20with a cheaper option.

    • Before we look at alternatives that may replace the S7-200,

    to list out the variables or parameters that determine their operformance. This is discussed in the appendix.

  • 8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development

    14/14

    Appendix  – Room for Expansion

    Parameter Siemens’ S7-200

    CPU 222

    Siemens’ S7-200

    CPU 224

    Fatek FBs-24MA Allen

    Micro

    1761

    Program size 2048 words 4096 words 20K words 737 ins

    437 da

    Execution speed 0.37 μs 0.37 μs 0.33 μs

    No. of on-board digital

    outputs

    6 10 10 12

    No. of on-board digital

    inputs

    8 14 14 20

    Input current 4 mA nominal 4 mA nominal 7.6 mA nominal 8 mA n

    Output current 0.75 A 0.75 A 0.5 A 8 A ma

    Communication

    protocols supported

    RS-485 (on-board),

    Ethernet (expansion

    module)

    RS-485 (on-board),

    Ethernet (expansion

    module)

    RS-232 (on-board), USB

    (on-board) and Ethernet

    (expansion module)

    RS-232

    Ethern

    modul

    Cost Over 100k Over 100k Between 20k to 80k Betwe