N2 Unit - Cost Elimination by in-House Logic Development
-
Upload
anonymous-x4kchkkcnc -
Category
Documents
-
view
221 -
download
0
Transcript of N2 Unit - Cost Elimination by in-House Logic Development
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
1/14
N2 Unit - Cost Eliminatioby In-House Logic
DevelopmentA Presentation by Asadullah Qureshi/AQ (I&E ROP)
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
2/14
Current Arrangement at the N2 Unit
•
Nitrogen extraction at the N2 Unit is carried out using Sieme200 family of PLCs – CPU 222 at the Old N2 Unit and CPU 22New N2 Unit.
• However, the PLCs come pre-programmed and the programprotected using a Level 4 Lock.
•A Level 4 Lock means the program cannot be accessed for emodification or back-up purposes.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
3/14
Current Arrangement at the N2 Unit
•
Since modification is not an option, the usefulness of the covery limited.
• The control algorithm cannot be refined or modified as peroperational requirement.
• A new program must be commissioned every time a modific
required.• The program costs almost the same as the PLC and its assoc
modules.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
4/14
The Proposal
•
The nitrogen extraction algorithm is fairly simple and the prbe developed in-house.
• This would allow us access to the program for further modifand eliminate the cost of having to commission the program
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
5/14
The Proposal
•
The nitrogen extraction algorithm uses a total of ten digital open and close SOVs as per a programmed timing sequence
• The timing sequence may be replicated by recording how thstatus LEDs light up on the DO card as nitrogen extraction isout.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
6/14
Logic Development
•
The timing sequence was first studied by making a recordingDO card while nitrogen extraction continued in the backgro
• The timing sequence is shown in the table below:
Valve 57 sec 0.5 sec 0.5 sec 1 sec 0.5 sec 57 sec 0.5 sec 0.5 sec
SOV1 1 1 1 1
SOV2 1 1 1 1
SOV3 1 1 1 1 1
SOV4 1 1 1 1 1 1 1 1
SOV5 1 1 1 1 1 1 1 1 1
SOV6 1 1 1 1 1 1 1 1 1
SOV7 1 1 1
SOV8 1 1
SOV9
SOV10 1 1 1 1 1
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
7/14
1
3
7
2
4
9 10
5 6
8
Inlet Air
Outlet Air
Exhaust
Tank A Tank B
Nitrogen Extraction via
Pressure Swing Adsorption
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
8/14
Logic Development
•
A timer runs for a total 1 minute and 59 seconds.• It is used to regulate the entire process.
• It provides a reference point against which each SOV is turned on o
• It restarts the sequence after the 1 minute and 59 seconds mark.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
9/14
Logic Development
•
The algorithm treats each SOV separately.• Comparison is made with the timer’s count to come up with
for each SOV.
• This can be seen by using SOV0 as an example.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
10/14
Logic Development
•
The timing sequence only continues as long as the level switthe two CMS tanks are HIGH.
• This indicates that the CMS level in the tanks is appropriate.
• Each SOV either turns on once or it turns on twice in one giviteration of the sequence.
• The logic is presented in the next slide.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
11/14
Start Scan
Cycle
T >= x
AND
T = x AND
T = y AND
T
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
12/14
Cost Benefit Analysis
•
The cost of the program factors into the overall cost of procspare PLCs for the N2 Unit.
• By programming the PLC in house, we get to save money.
• It also allows us to incorporate various interlocks into the looperational requirement.
PLC + Program Rs. 235000
PLC - Rs. 119000
Money Saved Rs. 116000
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
13/14
Cost Benefit Analysis
•
We now have access to the program and we understand thais very simple from a control point of view.
• We can therefore even go as far as replacing Siemens’ S7-20with a cheaper option.
• Before we look at alternatives that may replace the S7-200,
to list out the variables or parameters that determine their operformance. This is discussed in the appendix.
-
8/19/2019 N2 Unit - Cost Elimination by in-House Logic Development
14/14
Appendix – Room for Expansion
Parameter Siemens’ S7-200
CPU 222
Siemens’ S7-200
CPU 224
Fatek FBs-24MA Allen
Micro
1761
Program size 2048 words 4096 words 20K words 737 ins
437 da
Execution speed 0.37 μs 0.37 μs 0.33 μs
No. of on-board digital
outputs
6 10 10 12
No. of on-board digital
inputs
8 14 14 20
Input current 4 mA nominal 4 mA nominal 7.6 mA nominal 8 mA n
Output current 0.75 A 0.75 A 0.5 A 8 A ma
Communication
protocols supported
RS-485 (on-board),
Ethernet (expansion
module)
RS-485 (on-board),
Ethernet (expansion
module)
RS-232 (on-board), USB
(on-board) and Ethernet
(expansion module)
RS-232
Ethern
modul
Cost Over 100k Over 100k Between 20k to 80k Betwe