HI-FI BEST BUYS - HI-FI BEST BUYS - HI-FI BEST BUYS - HI ...
Multron FI
-
Upload
marlon-agno -
Category
Documents
-
view
53 -
download
13
description
Transcript of Multron FI
![Page 1: Multron FI](https://reader030.fdocuments.us/reader030/viewer/2022020710/552e517455034629178b4917/html5/thumbnails/1.jpg)
FFIIRREEMMAANN IINNTTEERRCCOOMM SSYYSSTTEEMMSS
DESIGNED TO :- SINGAPORE STANDARD : SS CP 25 1999 PSB TEST REPORT REF : 30S0004255/LHP/YCI
CCOONNVVEENNTTIIOONNAALL TTYYPPEE MMOODDEELL:: FFII SSEERRIIEESS
SSUUIITTAABBLLEE FFOORR ::
HIGH RISE BUILDINGS APARTMENTS COMMERCIAL COMPLEXES HOSPITALS SHOPPING CENTRES
![Page 2: Multron FI](https://reader030.fdocuments.us/reader030/viewer/2022020710/552e517455034629178b4917/html5/thumbnails/2.jpg)
1) The raising of any Remote Handset from its cradle shall :-
Indicate at the Control Panel the location of that Handset by means of a flashing visual red LED indication.
Sound a distinct audible signal at the Control Panel ; and
Produce an audible tone in that Handset to indicate that the System is functioning until
such time that the Master Handset at the Control Panel is raised from its cradle and the respective calling zone been selected , then the tone shall disappear and communication is established.
2) The raising of the Master Handset and selecting the calling zone at the Control Panel shall :-
Silence the audible signal ;
Replace the flashing visual red LED indication with a continuous visual indication ;
Permit two-way communication with one or any number of Remote Handsets that are selected.
By default, the communication shall be on privacy mode once the Master Handset is raised
from its cradle, unless `Party-Line’ switch is otherwise selected. 3) If during the course of a normal private conversation between the Master Handset and a Remote
Handset, one or more additional Remote Handsets are raised, then this condition shall be indicated by a flashing visual indication at the Control Panel. These additional handsets shall receive a “busy” tone and shall be able to listen to, or join in the conversation after the Control Panel has activated the corresponding selection switch.
Alternatively, these additional Remote Handsets, once raised, shall be able to listen or join in the conversation when the `Party-Line’ switch is pressed & selected.
Operation of Two-way Voice Communication
Typical Panel Facial Layout
DESCRIPTION MODEL NOTE 1. ZONE CARD FI-10 V2 ONE PER ZONE (MOUNTED ONTO FI-20 V2) 2. ZONE SELECTION MODULE FI-20 V2 ONE EVERY 10 ZONE 3. MASTER HANDSET MODULE FI-30 V2 ONE PER SYSTEM 4. FAULT / CONTROL MODULE FI-40 V2 ONE PER SYSTEM 5. POWER / CHARGER MODULE FI-50 V2 ONE PER SYSTEM (MOUNTED INSIDE PANEL) 6. I/O TERMINATION BOARD FI-60 V2 ONE EVERY (MOUNTED INSIDE PANEL) 20 ZONE
![Page 3: Multron FI](https://reader030.fdocuments.us/reader030/viewer/2022020710/552e517455034629178b4917/html5/thumbnails/3.jpg)
Modules & Devices
Fault / Control Module FI-40 V2
This Module provides the Panel general Indications &
Controls including `Lamp Test’ & `Privacy’ pushbuttons.
One unit shall be provided for each panel.
Recording Interface Module with Cassette Recorder may be provided as an optional feature.
Model FI-70 V2 – For Surface Mount Model FI-71 V2 – For Flush Mount
Remote Handset with Cabinet & Breakglass Keylock
Remote Phone Socket Pto be used in conjunctioPortable Handset FI-95.
9911J, n with
Portable Handset Model FI-95
Master Handset Module FI-30 V2
This Module provides the Master Handset with Mounting Base.
One unit shall be provided for each Panel.
Power / Charger Module FI-50 V2
This Module incorporates the Power & Charger circuitry for the System.
One Unit shall be provided for each Panel.
I/O Termination Board FI-60 V2
This Board provides the termination for signal to all the Remote Handsets corresponding to their respective zone.
Auxiliary Relay Output & Audio Out signal are provided as standard.
Zone Card FI-10 V2
Zone Selection Module FI-20V2
This Module provides plug-in connectors to accommodate 10 pcs Zone Card FI-10V2.
More Modules may be added to suit the number of zones required.
![Page 4: Multron FI](https://reader030.fdocuments.us/reader030/viewer/2022020710/552e517455034629178b4917/html5/thumbnails/4.jpg)
Typical Wiring Termination Diagram
Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.
Distributed By :-
MEMBER
Version : 12-06-2008
Technical Specifications :-
• Mains Supply :- 230 VAC • System Supply :- 24 VDC • Monitoring features provided for :-
• Master Handset • Remote Handset • Mains Failure • System Failure • Module Disconnection • Positive / Negative Earth Fault • Battery Failure • Power Consumption :-
• Standby : 100 mA for Standard 10 zone Pane (Plus 40mA for addition of every 10 zone)
• Communication : 180 mA with 1st Remote Handset (Plus 30mA for addition Remote Handset during conferencing)
• Master Handset Buzzer : 30 mA
• Remote Handset Buzzer : 10 mA