4
FIREMAN INTERCOM S SYSTEMS DESIGNED TO :- SINGAPORE STANDARD : SS CP 25 1999 PSB TEST REPORT REF : 30S0004255/LHP/YCI CONVENTIONAL TYPE MODEL: FI SERIES SUITABLE FOR : HIGH RISE BUILDINGS APARTMENTS COMMERCIAL COMPLEXES HOSPITALS SHOPPING CENTRES

description

fireman intercom brochure

Transcript of Multron FI

Page 1: Multron FI

FFIIRREEMMAANN IINNTTEERRCCOOMM SSYYSSTTEEMMSS

DESIGNED TO :- SINGAPORE STANDARD : SS CP 25 1999 PSB TEST REPORT REF : 30S0004255/LHP/YCI

CCOONNVVEENNTTIIOONNAALL TTYYPPEE MMOODDEELL:: FFII SSEERRIIEESS

SSUUIITTAABBLLEE FFOORR ::

HIGH RISE BUILDINGS APARTMENTS COMMERCIAL COMPLEXES HOSPITALS SHOPPING CENTRES

Page 2: Multron FI

1) The raising of any Remote Handset from its cradle shall :-

Indicate at the Control Panel the location of that Handset by means of a flashing visual red LED indication.

Sound a distinct audible signal at the Control Panel ; and

Produce an audible tone in that Handset to indicate that the System is functioning until

such time that the Master Handset at the Control Panel is raised from its cradle and the respective calling zone been selected , then the tone shall disappear and communication is established.

2) The raising of the Master Handset and selecting the calling zone at the Control Panel shall :-

Silence the audible signal ;

Replace the flashing visual red LED indication with a continuous visual indication ;

Permit two-way communication with one or any number of Remote Handsets that are selected.

By default, the communication shall be on privacy mode once the Master Handset is raised

from its cradle, unless `Party-Line’ switch is otherwise selected. 3) If during the course of a normal private conversation between the Master Handset and a Remote

Handset, one or more additional Remote Handsets are raised, then this condition shall be indicated by a flashing visual indication at the Control Panel. These additional handsets shall receive a “busy” tone and shall be able to listen to, or join in the conversation after the Control Panel has activated the corresponding selection switch.

Alternatively, these additional Remote Handsets, once raised, shall be able to listen or join in the conversation when the `Party-Line’ switch is pressed & selected.

Operation of Two-way Voice Communication

Typical Panel Facial Layout

DESCRIPTION MODEL NOTE 1. ZONE CARD FI-10 V2 ONE PER ZONE (MOUNTED ONTO FI-20 V2) 2. ZONE SELECTION MODULE FI-20 V2 ONE EVERY 10 ZONE 3. MASTER HANDSET MODULE FI-30 V2 ONE PER SYSTEM 4. FAULT / CONTROL MODULE FI-40 V2 ONE PER SYSTEM 5. POWER / CHARGER MODULE FI-50 V2 ONE PER SYSTEM (MOUNTED INSIDE PANEL) 6. I/O TERMINATION BOARD FI-60 V2 ONE EVERY (MOUNTED INSIDE PANEL) 20 ZONE

Page 3: Multron FI

Modules & Devices

Fault / Control Module FI-40 V2

This Module provides the Panel general Indications &

Controls including `Lamp Test’ & `Privacy’ pushbuttons.

One unit shall be provided for each panel.

Recording Interface Module with Cassette Recorder may be provided as an optional feature.

Model FI-70 V2 – For Surface Mount Model FI-71 V2 – For Flush Mount

Remote Handset with Cabinet & Breakglass Keylock

Remote Phone Socket Pto be used in conjunctioPortable Handset FI-95.

9911J, n with

Portable Handset Model FI-95

Master Handset Module FI-30 V2

This Module provides the Master Handset with Mounting Base.

One unit shall be provided for each Panel.

Power / Charger Module FI-50 V2

This Module incorporates the Power & Charger circuitry for the System.

One Unit shall be provided for each Panel.

I/O Termination Board FI-60 V2

This Board provides the termination for signal to all the Remote Handsets corresponding to their respective zone.

Auxiliary Relay Output & Audio Out signal are provided as standard.

Zone Card FI-10 V2

Zone Selection Module FI-20V2

This Module provides plug-in connectors to accommodate 10 pcs Zone Card FI-10V2.

More Modules may be added to suit the number of zones required.

Page 4: Multron FI

Typical Wiring Termination Diagram

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Distributed By :-

MEMBER

Version : 12-06-2008

Technical Specifications :-

• Mains Supply :- 230 VAC • System Supply :- 24 VDC • Monitoring features provided for :-

• Master Handset • Remote Handset • Mains Failure • System Failure • Module Disconnection • Positive / Negative Earth Fault • Battery Failure • Power Consumption :-

• Standby : 100 mA for Standard 10 zone Pane (Plus 40mA for addition of every 10 zone)

• Communication : 180 mA with 1st Remote Handset (Plus 30mA for addition Remote Handset during conferencing)

• Master Handset Buzzer : 30 mA