Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter...

6
g Energy Rapid integration into BACnet management systems High accuracy multifunction power meter, 0.2% class revenue certifiable energy and demand metering Ultra compact and easy to install, fits both ANSI and DIN cutouts EnerVista™ software makes metered data and power quality status easily accessible User programmable for different system voltages and current measurements Standard Modbus™ TCP communications Easy to read, large 3 line .56” bright LED display for better visibility and longer life LEED projects Smart buildings Commercial energy management HVAC efficiency monitoring Building management systems Communications BACnet/IP 100BaseT Ethernet protocol 40 pre-defined BACnet objects facilitate rapid integration Embedded web-server, allows BACnet/IP interface to be remotely configured and BACnet objects can be remotely viewed over the internet with a web browser Standard Modbus TCP communications can be used to poll the EPM 6010 while BACnet/IP interface is being used Measuring and Metering High accuracy multifunction power meter, 0.2% class revenue certifiable energy and demand metering Samples at 400+ times per cycle and has 24 bit A/D conversion to measure accurately and reliably Meets ANSI C12.20 (0.2%) and IEC 687 (0.2%) accuracy classes Total harmonic distortion (%THD) Load percentage graphical bar for instant load visualization True RMS multifunction measurements including voltage, current, power, frequency and energy FEATURES APPLICATIONS KEY BENEFITS EPM 6010 BUILDING AUTOMATION POWER METER BACnet ® /IP Communications and Energy Measurement Multilin™

Transcript of Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter...

Page 1: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

g Energy

• RapidintegrationintoBACnetmanagementsystems

• Highaccuracymultifunctionpowermeter,0.2%classrevenuecertifiableenergyanddemandmetering

• Ultracompactandeasytoinstall,fitsbothANSIandDINcutouts

• EnerVista™softwaremakesmetereddataandpowerqualitystatuseasilyaccessible

• Userprogrammablefordifferentsystemvoltagesandcurrentmeasurements

• StandardModbus™TCPcommunications

• Easytoread,large3line.56”brightLEDdisplayforbettervisibilityandlongerlife

• LEEDprojects

• Smartbuildings

• Commercialenergymanagement

• HVACefficiencymonitoring

• Buildingmanagementsystems

Communications

• BACnet/IP100BaseTEthernetprotocol

• 40pre-definedBACnetobjectsfacilitaterapidintegration

• Embeddedweb-server,allowsBACnet/IPinterfacetoberemotelyconfiguredandBACnetobjectscanberemotelyviewedovertheinternetwithawebbrowser

• StandardModbusTCPcommunicationscanbeusedtopolltheEPM6010whileBACnet/IPinterfaceisbeingused

Measuring and Metering

• Highaccuracymultifunctionpowermeter,0.2%classrevenuecertifiableenergyanddemandmetering

• Samplesat400+timespercycleandhas24bitA/Dconversiontomeasureaccuratelyandreliably

• MeetsANSIC12.20(0.2%)andIEC687(0.2%)accuracyclasses

• Totalharmonicdistortion(%THD)

• Loadpercentagegraphicalbarforinstantloadvisualization

• TrueRMSmultifunctionmeasurementsincludingvoltage,current,power,frequencyandenergy

FEATURES

APPLICATIONS

KEY BENEFITS

EPM 6010BUILDING AUTOMATION POWER METER

BACnet®/IPCommunicationsandEnergyMeasurement

Multilin™

Page 2: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

2

EPM 6010Building Automation Power Meter

GEDigitalEnergy.com

CommunicationsPortsThe Multilin EPM 6010 provides twoindependent communication ports withadvancedfeatures:

• IrDA port–AuniqueopticalIrDAportallowstheunittobesetupandprogrammedusingaremotelaptopwithoutneedingacommunicationcable.SimplypointatthemeterwithanIrDA-equippedPCcomputertoconfigureit.

• Ethernet Port–Thisportprovidesconnectivityviaa10/100BaseTRJ45connection.ModbusTCPandBACnetprotocolsaresupported.

BACnet/IPWebInterfaceThe Multilin EPM 6010 comes standardwithaweb interface.Use theBACnet/IPinterfacetoremotelysetuptheBACnet/IPconfigurationandtrackenergyusewithanystandardwebbrowser.

EnerVistaSoftware

EnerVista Software

EnerVista Launchpad is a powerfulsoftware package that provides users aplatform to access all of the setup and

OverviewThe Multilin EPM 6010 is an industryleading revenue grade power meterwith native BACnet/IP communications.This meter is designed to integrateseamlesslyintoexistingandnewbuildingmanagementsystemsusingthepopularBACnetprotocol.Themeterallowsuserstogatherdataonvoltage,current,powerandenergyusagethroughoutafacility.

Designed to be the perfect device forenvironmental initiatives, LEED certifiedprojects and smart energy projects, theEPM 6010 provides superior metrology,and revenue testable 0.2% energyaccuracy.ThemeterisincompliancewithANSI and IEC accuracy standards, hasadvanced DSP technology, samples athighrates,andhas24bitA/Dconversiontomeasureandanalyzepoweraccuratelyandreliably.

BACnetCommunicationsThe Multilin EPM 6010 with BACnet/IPsupports building energy managementstrategies, LEED certification and otherGreen Building initiatives. By allowingusers to track energy use and powerquality, the meters gives users theinformation they need to accuratelyidentify cost-saving measures andrespondtopowerqualityproblemswhentheyarise.

MeasuredValuesEPM6010measuresthefollowingvalues:

MEASURED VALUES

REAL-TIME AVG MAX MIN

Voltage L-N • • •Voltage L-L • • •Current Per Phase • • • •Watts • • • •VAr • • • •VA • • • •PF • • • •+Watt-hr •-Watt hr •Watt-hr net •+VAr-hr •-VAr-hr •VAr-hr net •VA-hr •Frequency • • •Voltage Angles •Current Angles •%THD • • •% of Load Bar •

BACnet home web page

BACnet/IP interface statistics

View BACnet objects and their status

Page 3: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

3

EPM 6010Building Automation Power Meter

GEDigitalEnergy.com

Direct PC Interface

HTTP Web Server

BACnet/IP

Modbus TCPWireless Communication

support tools needed for configuringand maintaining GE Multilin Products.Launchpad allows configuration ofdevices in real-time by communicatingusingRS232,RS485,Ethernet,ormodemconnections.

UsingLaunchpadasthesingle interfacetothesetupandanalysissoftwaremakesitsimpletoentersetpoints,readmeteredvalues, monitor status and evaluatepowerquality.

Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when neededby automatically checking for anddownloading new versions of manuals,applications nates, specifications, andservicebulletins.

Viewpoint Monitoring

Viewpoint Monitoring is a simple-to-use, full-featured monitoring and datarecording software package for small

systems.ViewpointMonitoringprovidesacompleteHMIpackagethatinstantlyputscritical real-timedevicedataonyourPCthroughpre-configuredgraphicalscreenswiththefollowingfunctionality.

• Plug-&-PlayDeviceMonitoring

• SystemSingle-LineMonitoring&Control

• AnnunciatorAlarmScreens

• TrendingReports

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

Simultaneous Dual Communications Paths

EnerVista Viewpoint Monitoring Data Recording and Real-Time Status

Create tabular trending reports of usage data

Historical minimum and maximum values to understand fluctuations on the network

Real-time power values to instantly analyze system capacity

Building Automation System

Master Host or Multiple Masters

Web Browser

Page 4: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

4

EPM 6010Building Automation Power Meter

GEDigitalEnergy.com

EnerVista Integrator

EnerVista Integrator is a toolkit thatallowsseamlessintegrationofGEMultilindevices intoneworexistingautomationsystems by sending GE device data toHMI,DCS,andSCADAsystems.IncludedinEnerVistaTMIntegratoris:

• OPC/DDEServer

• GEMultilinDrivers

• AutomaticEventRetrieval

• AutomaticWaveformRetrieval

DimensionsandMounting

UserInterface

EnerVista Viewpoint Monitoring Data Recording and Real-Time Status

Create graphical trending reports of usage overtime

Real-time metering values and phasors to verify device connection

10/100BaseTviaRJ45Connector

KYZPulseOutput

UniversalVoltageInputs

Current“Gills”

Only3.25”

IRDAPort

%LoadBar

VhPulse

ReadingTypeDesignator

Large.56”LEDs

Front View Side View Rear View Transducer

ScreenSelectors

AutoScaleIndicator

Page 5: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

5

EPM 6010Building Automation Power Meter

GEDigitalEnergy.com

TechnicalSpecifications

VOLTAGE INPUTSUniversal Voltage Input•0-416VoltsLineToNeutral•0-721VoltsLinetoLineInputwithstandcapability–MeetsIEEEC37.90.1(surgewithstandCapability)ProgrammablevoltagerangetoanyPTratioSupports:3elementWYE,2.5elementWYE,2ElementDelta,4WireDeltaSystemsBurden:0.36VAperphasemaxat600V,0.014VAat120VoltsInputwiregaugemax(AWG12/2.5mm2)

CURRENT INPUTSClass10:0to11AmpsSecondary/5AmpsNominal/10AmpsMaxClass2:0to2AmpsSecondary/1AmpNominal/2AmpsmaxFaultCurrentWithstand:•100Ampsfor10Seconds•300Ampsfor3Seconds•500Ampsfor1Second.ProgrammableCurrenttoAnyCTRatioBurden0.005VAperphaseMaxat11Amps5mAPickupCurrentFrequency50Hzor60Hz+/-3HzaboveandbelownominalrangePassthroughwiregaugedimension:0.177”/4.5mm

ISOLATIONAllInputsandOutputsaregalvanicallyisolatedto2500VoltsAC.

SENSING METHODTrueRMSSamplingat400+SamplesperCycleonallchannelsmeasuredreadingssimultaneouslyHarmonic%THD(%oftotalharmonicdistoration)

UPDATE RATEWatts,VArandVA-100msecAllotherparameters-1second

POWER SUPPLYUniversalAC/DCSupply•90to265VoltsACand•100to370VoltsDC.Optional24to48VoltsDCSupply.Burden:10VAmax.

COMMUNICATIONS2ComPorts(BackandFacePlate):• IrDA(ThroughFaceplate)- ProtocolModbusASCII- ComPortBaudRate:56.7k- Address:1

•Ethernet(BackPanel)- 10/100BaseTviaRJ45connector- ProtocolModbusTCP- BACnet/IP

BACnet OBJECTS

VoltsA-N WhrNet

VoltsB-N TotalWhr

VoltsC-N PositiveVARh

VoltsA-B NegativeVARh

VoltsB-C PositiveWatts,3-Phase,AverageDemand

VoltsC-A PositiveVARs,3-Phase,AverageDemand

AmpsA NegativeWatts,3-Phase,AverageDemand

AmpsB NegativeVARs,3-Phase,AverageDemand

AmpsC PositiveWatts,3-Phase,MaxAverageDemand

TotalWatts PositiveVARs,3-Phase,MaxAverageDemand

TotalVARs NegativeWatts,3-Phase,MaxAverageDemand

TotalVA NegativeVARs,3-Phase,MaxAverageDemand

TotalPF VAs,3-phase,AverageDemand

TotalVAh VAs,3-phase,MaxAverageDemand

TotalVARh Volts,A-N%THD

VARhNet Volts,B-N%THD

Frequency Volts,C-N%THD

NeutralCurrent Amps,A%THD

WhrReceived Amps,B%THD

WhrDelivered Amps,C%THD

Thereare40pre-definedBACnetObjectsintheEPM6010’sBACnet/IPprotocol

METERING ACCURACY

Measured Parameters

Accuracy% of Reading Display Range

Voltage L-N 0.1% 0-9999ScalableVorkV

Voltage L-L 0.1% 0-9999VorkVScalable

Current 0.1% 0-9999AmpsorkAmps

+/- Watts 0.2% 0-9999Watts,kWatts,MWatts

+/-Wh 0.2% 5to8DigitsProgrammable

+/-VARs 0.2% 0-9999VARs,kVARs,MVARs

+/-VARh 0.2% 5to8DigitsProgrammable

VA 0.2% 0-9999VA,kVA,MVA

VAh 0.2% 5to8DigitsProgrammable

PF 0.2% +/-0.5to1.0

Frequency 0.01Hz 45to65Hz

%THD 5% 0-200%

%Load Bar 1-120% 10DigitResolutionScalable

PULSE OUTPUTFrontpanelWhinfaredtestpulseBackpanelWhpulseoutput

DIMENSIONS & SHIPPINGWeight:2lbsBasicUnit:H4.85xW4.82xL4.25Mountsin92mmDINandANSIC39.1RoundCut-outsShippingContainerDimensions:6”cube

ENVIRONMENTALStorage -20°Cto+70°COperating -20°Cto+70°CHumidity to95%RHNon-CondensingFaceplate Rating NEMA12(WaterResistant)

MountingGasketIncluded

COMPLIANCEIEC687(0.2%Accuracy)ANSIC12.20(0.2%Accuracy)ANSI(IEEE)C37.90.1SurgeWithstandANSIC62.41(Burst)IEC1000-4-2–ESDIEC1000-4-3–RadiatedImmunityIEC1000-4-4–FastTransientIEC1000-4-5–SurgeImmunity

APPROVALSISO Manufacturedtoan

ISO9001registeredprogram

UL/cUL ListedunderE200431CE ConformstoEuropean

CEstandards

Page 6: Multilin™ EPM 6010 - GE Grid Solutions...EPM 6010 Building Automation Power Meter GEDigitalEnergy.com EnerVista Integrator EnerVista Integrator is a toolkit that allows seamless

g imagination at work

EPM 6010Building Automation Power Meter

120711-V3

GEDigitalEnergy215AndersonAve.Markham,ON,CanadaL6E1B3TollFree(NAOnly):1-800-547-8629Tel:905-294-6222Fax:905-201-2098email:[email protected]

GEDigitalEnergy.comBACnet is a registered trademark of American Society of Heating, Refrigerating and Air-ConditioningEngineers(ASHRAE).ModbusisatrademarkofSCHNEIDERAUTOMATION,INC.GE,theGEmonogram,MultilinandEnerVistaaretrademarksoftheGeneralElectricCompany.GEreservestherighttomakechangestospecificationsofproductsdescribedatanytimewithoutnoticeandwithoutobligationtonotifyanypersonofsuchchanges.Copyright2012,GeneralElectricCompany.

OrderingPL6010 * * * * DescriptionFrequency 5 50Hz-BACnet/IPCommunicatingMultimeter

6 60Hz-BACnet/IPCommunicatingMultimeterCurrent Inputs 5A 5Amps

1A 1AmpSoftware THD THD,LimitsAlarms&OneKYZPulseOutputPower Supply HI AC/DCPowerSupply(90-265)VACor(100-370)VDC

LDC LowVoltageDCPowerSupply(18-60)VDC Example – EPM 6010 for 60Hz system with 5 Amp secondary and an AC/DC Power supply. PL601065ATHDHI

EPM 6010 is available without a display as the EPM 6010T. Please see the online store for ordering information.